Air System Sizing Summary for GF-ES- PAC 5

Project Name: PRIVATE SCHOOL AT AL KHOUD 03/26/2012


Prepared by: abc 07:25AM

Air System Information


Air System Name ................................... GF-ES- PAC 5 Number of zones ............................................................. 1
Equipment Class ........................................ PKG ROOF Floor Area ................................................................. 434.4 m
Air System Type ................................................ SZCAV Location .................................................... Masqat, Oman

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s .......................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space L/s ...................... Individual peak space loads Sizing Data ...................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load .......................................................... 71.8 kW Load occurs at ................................................... Aug 1500
Sensible coil load ................................................... 57.4 kW OA DB / WB ...................................................... 48.0 / 30.0 C
Coil L/s at Aug 1500 .............................................. 3775 L/s Entering DB / WB ............................................. 26.7 / 19.0 C
Max block L/s ........................................................ 3775 L/s Leaving DB / WB .............................................. 14.1 / 13.4 C
Sum of peak zone L/s ........................................... 3775 L/s Coil ADP ..................................................................... 12.7 C
Sensible heat ratio ............................................... 0.800 Bypass Factor .......................................................... 0.100
m/kW ....................................................................... 6.0 Resulting RH ................................................................. 52 %
W/m ..................................................................... 165.4 Design supply temp. ................................................... 13.4 C
Water flow @ 5.6 K rise ......................................... N/A Zone T-stat Check .................................................... 1 of 1 OK
Max zone temperature deviation .................................. 0.0 K

Supply Fan Sizing Data

Actual max L/s ....................................................... 3775 L/s Fan motor BHP ........................................................... 2.81 BHP
Standard L/s .......................................................... 3768 L/s Fan motor kW ............................................................. 2.10 kW
Actual max L/(s-m) ................................................ 8.69 L/(s-m) Fan static ..................................................................... 300 Pa

Outdoor Ventilation Air Data


Design airflow L/s .................................................... 391 L/s L/s/person ................................................................... 4.88 L/s/person
L/(s-m) ................................................................... 0.90 L/(s-m)