This document summarizes the air system sizing for AHU-1 in Colombo, Sri Lanka. It was prepared on 07/14/2016 for a 1-zone air handling unit serving a 30.3 square meter floor area. Key specifications include a central cooling coil load of 6.8 kW requiring 427 L/s of air at peak conditions in February. The outdoor air ventilation rate was designed for 17 L/s. Fan power was calculated at 0 kW given the 472 L/s maximum airflow requirement.
Download as RTF, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
10 views
Air System Sizing Summary For AHU-1
This document summarizes the air system sizing for AHU-1 in Colombo, Sri Lanka. It was prepared on 07/14/2016 for a 1-zone air handling unit serving a 30.3 square meter floor area. Key specifications include a central cooling coil load of 6.8 kW requiring 427 L/s of air at peak conditions in February. The outdoor air ventilation rate was designed for 17 L/s. Fan power was calculated at 0 kW given the 472 L/s maximum airflow requirement.
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 1
Air System Sizing Summary for AHU-1
Project Name: cecb project 1
07/14/2016 Prepared by: sanjeev 03:58PM
Air System Information
Air System Name ............................................... AHU-1 Equipment Class ......................................... SPLT AHU Air System Type ............................................ 1FDDVAV
Number of zones ............................................................. 1
Floor Area ................................................................... 30.3 m Location ........................................... Colombo, Sri Lanka
Sizing Calculation Information
Zone and Space Sizing Method: Zone L/s ............................... Peak zone sensible load Space L/s ...................... Individual peak space loads
Calculation Months ......................................... Jan to Dec
Sizing Data ...................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ............................................................ 6.8 Sensible coil load ..................................................... 6.3 Coil L/s at Feb 1600 ................................................ 427 Max block L/s at Feb 1600 ...................................... 472 Sum of peak zone L/s ............................................. 472 Sensible heat ratio ............................................... 0.919 m/kW ....................................................................... 4.4 W/m ..................................................................... 225.9 Water flow @ 5.6 K rise ......................................... N/A
kW kW L/s L/s L/s
Load occurs at ................................................... Feb 1600
OA DB / WB ...................................................... 34.8 / 26.6 Entering DB / WB ............................................. 25.0 / 17.1 Leaving DB / WB .............................................. 12.8 / 12.0 Coil ADP ..................................................................... 11.4 Bypass Factor .......................................................... 0.100 Resulting RH ................................................................. 44 Design supply temp. ................................................... 12.8 Zone T-stat Check .................................................... 1 of 1 Max zone temperature deviation .................................. 0.0
C C C C % C OK K
Central Heating Coil Sizing Data
Max coil load ............................................................ 0.2 kW Coil L/s at Des Htg ...................................................... 6 L/s Max coil L/s ................................................................. 6 L/s Water flow @ 11.1 K drop ...................................... N/A
Load occurs at ..................................................... Des Htg
W/m ............................................................................. 5.4 Ent. DB / Lvg DB .............................................. 21.3 / 43.3 C
Preheat Coil Sizing Data
No heating coil loads occurred during this calculation.
Supply Fan Sizing Data
Actual max L/s at Feb 1600 .................................... 472 L/s Standard L/s ............................................................ 472 L/s Actual max L/(s-m) .............................................. 15.59 L/(s-m)
Fan motor BHP ........................................................... 0.00 BHP
Fan motor kW ............................................................. 0.00 kW Fan static ......................................................................... 0 Pa L/s/person ................................................................... 5.53 ............................................................................L/s/person