Systxccitw 06si
Systxccitw 06si
Systxccitw 06si
SYSTXCCITN01
Infinityr Touch Control
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation.
US Patents: Carrierr U.S. Pat No. 7,243,004, Carrierr U.S. Pat No. 7,775,452,
pointSETt U.S. Pat No. 7,415,102
TABLE OF CONTENTS
PAGE
1.Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3.Quick Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3.1. Set Time and Date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3.2. Set Dealer Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4.Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4.1. Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4.2. Check Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4.3. Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.3.1. Wall Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.3.2. Remote Room Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.3.2.1.Remote Room Sensor Averaging . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.3.3. Smart Sensors (for zoning applications) . . . . . . . . . . . . . . . . . . . . . . 7
4.4. Wiring Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.4.1. Shielded Wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.4.2. Damper Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.5. Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.5.1. Decorative Backplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.6. Humidifier Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
TABLE OF CONTENTS (cont.)
PAGE
4.6.1. Bypass Humidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.6.2. Fan Powered Humidifiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.1. Searching for Indoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.2. Searching for Outdoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.3. Indoor Evaporator Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.4. Electric Heater Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.4.1. Hydronic Heat Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.5. Searching SAM Module (If Applicable) . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.6. Searching for Zones (If Applicable) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.7. Filter Type Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.8. Humidifier Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.9. Ultraviolet Lights Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.10.Equipment Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.11.Static Pressure Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5.12.Duct Assessment (zoning applications only) . . . . . . . . . . . . . . . . . . . . . . 20
6.Service Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.1. Equipment Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.2. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.3. Set up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
TABLE OF CONTENTS (cont.)
PAGE
6.3.1. Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.3.1.1.Auto Mode set up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.3.1.2.Heat/Cool Deadband . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.3.1.3.Offsets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.3.1.4.Reset factory defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.3.1.5.Scheduling Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.3.1.6.Smart Recovery Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.3.1.7.Temperature Units Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.3.2. Fan Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.3.2.1.Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6.3.2.2.Altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6.3.2.3.Fan Coil Dehumidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.3.2.4.Fan Coil G-- Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.3.3. Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
6.3.3.1.Furnace Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
6.3.3.2.AC/HP Air Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
6.3.3.3.Furnace Staging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.3.3.4.Furnace Airflow Limits (modulating furnace only) . . . . . . . . . . . . 32
6.3.3.5.Furnace Off Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.3.3.6.Altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
TABLE OF CONTENTS (cont.)
PAGE
6.3.3.7.Furnace Dehumidifier Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6.3.3.8.Furnace G Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6.3.4. AC/Heat Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.3.4.1.Cooling Lockout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.3.4.2.Defrost Interval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.3.4.3.Low Ambient Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.3.4.4.Quiet Shift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.3.4.5.AC/Heat Pump RPM Max . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.3.4.6.Defrost Fan Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.3.4.7.Brownout Disable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6.3.4.8.Energy Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6.3.5. Heat Source Lockout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6.3.6. Zoning (If Applicable) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
6.3.6.1.Zoning Disable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.3.6.2.Zone Offsets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.3.6.3.Zone Airflow Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.3.6.4.Duct Assessment Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
TABLE OF CONTENTS (cont.)
PAGE
6.3.7. Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
6.3.7.1.Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6.3.7.2.Humidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6.3.7.3.Ultraviolet Lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6.3.7.4.Ventilator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6.3.8. Utility Curtailment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6.3.9. Hydronic Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.4. Check out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.4.1. Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.4.2. Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.4.3. Hydronic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.4.4. Air Conditioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.4.5. Heat Pump Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
6.4.6. Heat Pump Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
6.4.7. Humidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
6.4.8. Ventilator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
6.4.9. Zoning (If Applicable) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
6.4.9.1.Airflow Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
6.4.9.2.Damper/Sensor Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
TABLE OF CONTENTS (cont.)
PAGE
6.4.9.3.Zone Duct Assessment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.4.9.4.Sensor Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.5. Service Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.5.1. Fan Coil Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
6.5.2. Furnace Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
6.5.3. AC Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
6.5.4. Heat Pump Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
6.5.5. Zoning Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6.5.6. Last 10 System Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6.5.7. Run/Fault History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.5.8. Model/Serial Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
6.5.9. Service Phone Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
6.5.10. Energy Tracking Watt Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
6.6. Refrigerant Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.6.1. Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.6.2. Pump down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
6.6.3. Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.7. Dealer Logo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
7.Wireless Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
8.Appendix A - Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
1. Safety Considerations
Improper installation, adjustment, alteration, service, maintenance, or use can cause
explosion, fire, electrical shock, or other conditions which may cause death,
personal injury or property damage. Consult a qualified installer, service agency or
your distributor or branch for information or assistance. The qualified installer or
agency must use factory-- authorized kits or accessories when modifying this
product. Refer to the individual instructions packaged with the kits or accessories
when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves.
Have a fire extinguisher available. Read these instructions thoroughly and follow
all warnings and cautions included in literature and attached to the unit. Consult
local building codes and the current edition of the National Electrical Code (NEC)
NFPA 70. In Canada, refer to the current editions of the Canadian Electrical Code
CSA C22.1.
Recognize safety information. When you see this symbol on the unit and in
instructions or manuals, be alert to the potential for personal injury. Understand the
signal words DANGER, WARNING, and CAUTION. These words are used with
the safety-- alert symbol. DANGER identifies the most serious hazards, which will
result in severe personal injury or death. WARNING signifies hazards, which could
result in personal injury or death. CAUTION is used to identify unsafe practices,
which may result in minor personal injury or product and property damage. NOTE
is used to highlight suggestions which will result in enhanced installation,
reliability, or operation.
2. Introduction
The Infinityr System consists of several intelligent communicating components
which includes the Infinityr Touch Control (or User Interface), variable speed
furnace or FE fan coil, and 2-- stage AC or HP, which continually communicate with
each other via a four-- wire connection called the ABCD bus. Commands, operating
1
conditions, and other data are passed continually between components over the
ABCD bus. The result is a new level of comfort, versatility, and simplicity.
All Infinityr furnaces or fan coils are variable-- speed and multi stage for maximum
flexibility, efficiency, and comfort. They support controlled ventilation,
humidification, dehumidification, and air quality control. Either an Infinityr
(communicating), or a standard single-- stage 24VAC controlled outdoor unit may be
used.
When using conventional single-- stage outdoor units, the Infinity furnace or fan coil
provides the 24 volt signals needed to control them. Also, the Infinityr Network
Interface Module (P/N SYSTXCCNIM01) allows connection of a Carrier HRV or
ERV without the need for separate wall control.
When using a Carrier HRV or ERV with a zoned system, the Infinityr Zone board
allows connection of a Carrier HRV or ERV without the need for separate wall
control.
All system components are controlled through the wall mounted Infinity Touch
Control, which replaces the conventional thermostat and provides the homeowner
with a single wall control for all features of the system.
3. Quick Start
3.1. Set Time and Date
From the main screen, touch MENU, on the bottom of the control. The
TIME/DATE icon allows you to set the time and date for the Infinityr Touch
Control.
d To set the HOUR, MINUTE, MONTH, DAY, or YEAR touch the feature
you wish to change.
d Use the Up (Y) and Down (B) buttons to make the appropriate changes.
d When you have completed all of the settings touch SAVE.
2
d If you make a mistake you may touch CANCEL and begin again.
A12175
3.2. Set Dealer Information
From the main screen, touch MENU, on the bottom of the control. The SERVICE
icon allows you to upload your contact information into the Infinity Touch Control.
A12176
S Format your contact information and logo (if applicable) using the PC/MAC
application, save it to a standard USB drive. See Section 6.7.
S Touch the SERVICE icon for about 10 seconds, then touch DEALER LOGO
UPLOAD.
S Place the USB drive into the USB port on the bottom of the Infinity Touch
Control and follow the on screen prompts.
3
S More detailed information can be found on HVACPartners.com under the
Product tab> Thermostats & Controls> SYSTXCCITW01> Documents &
Downloads> Marketing/Miscellaneous> Infinity Touch Control Dealer Logo
Application - Instructions.
4. Installation
4.1. Overview
This instruction covers installation of the Infinityr Touch Control and the Infinityr
Wireless Access Point only. Physical installation instructions for the indoor and
outdoor equipment, and accessories are provided with each unit.
Setup, commissioning, operation, and troubleshooting of the Infinityr System are
covered only in this installation instruction. It is the guide to connecting the system
components and commissioning the system once all physical components are
installed. Special screen prompts and start-- up capabilities are provided in the
Infinityr System to simplify and automate the initial commissioning of the system.
S Install the Infinity Touch Control according to this instruction.
S Install indoor unit, outdoor unit, and accessories according to their instructions.
S Wire complete system according to this instruction.
S Setup, commission, and operate system according to this instruction to assure a
smooth and trouble free start-- up.
4.2. Check Equipment
Inspect equipment. File a claim with shipping company prior to installation if
shipment is damaged or incomplete.
4
4.3. Location
! WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury
or death.
Disconnect power before routing control wiring.
All wiring must comply with national, local, and state codes.
4.3.1. Wall Control
The Infinity Touch Control is the command center for the Infinity System. It should
be located where it is easily accessible and visible to the adult homeowner or end
user. For accurate temperature measurement, the following guidelines should be
followed:
The Infinity Touch Control and Remote Room Sensors SHOULD be mounted:
S Approximately 5-- ft (1.5 m) from the floor.
S Close to or in a frequently used room, preferably on an inside partitioning wall.
S On a section of wall without pipes or ductwork.
The Infinity Touch Control and Remote Room Sensors SHOULD NOT be
mounted:
S Close to a window, on an outside wall, or next to a door leading to the outside.
S Exposed to direct light or heat from a lamp, sun, fireplace, or other
temperature-- radiating objects which could cause a false reading.
5
S Close to or in direct airflow from supply registers.
S In areas with poor air circulation, such as behind a door or in an alcove.
4.3.2. Remote Room Sensors
A Remote Room Sensor can be used with the Infinity Touch Control to take the
place of the control’s internal temperature sensor. This allows the Infinity Touch
Control to be mounted in areas with less than optimal airflow (such as near an
exterior door, window or in a closet). The remote sensor can be wired to the
terminal block connectors labeled S1 and S2 at the control’s backplate, or the ZS1
and ZS1C connection at the Damper Control Module. In either case, the Infinity
Touch Control will automatically detect the Remote Room Sensor and ignore its
internal temperature sensor.
4.3.2.1. Remote Room Sensor Averaging
Typically, one remote sensor is used but, multiple sensors may be used and
averaged in some applications. Averaging requires a special series-- parallel wiring
method with a specific number of sensors. See figure below. It is also important to
note the humidity sensor cannot be remotely located, so do not locate the Infinity
Control in an area where humidity sensing may not be accurate.
6
Damper Control Damper Control
Module Module
ZS_ ZS_C
Sensor 1 Sensor 2
Sensor 3 Sensor 4
A03233
7
NOTE: ABCD bus wiring only requires a four-- wire connection; however, it is
good practice to run thermostat cable having more than four wires in the event of a
damaged or broken wire during installation.
Each communicating device in the Infinityr Zone System has a four-- pin connector
labeled ABCD. It is recommended that the following color code be used when
wiring each device:
A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)
A B C D
A03193
It is not mandatory that the above color code be used, but each ABCD connector in
the system MUST be wired consistently.
NOTE: Some outdoor units provide their own low-- voltage power source and do
not require the “C” (24VAC common) and “D” (24VAC power) connections. See
the outdoor unit installation instructions for more information.
8
! WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury
or death.
Before installing, modifying, or servicing system, the main
electrical disconnect switch must be in the OFF position. There
may be more than 1 disconnect switch. Lock out and tag
switch with a suitable warning label.
9
S Adjust length and routing of each wire to reach each wire entry on the
connector backplate. Strip 1/4-- in (6.4 mm) of insulation from each wire.
S Match and connect thermostat wires to proper terminals on control backplate.
d See wiring diagrams in Appendix A.
S Push any excess wire into the wall. Seal hole in wall to prevent any air leaks.
Leaks can affect operation.
S Attach Infinity Control to the mounting plastic by lining up the plastic guides
on the back of the control with the opening on the mounting plastic and push
on.
S Perform installation of all other system equipment (i.e. dampers, humidifier,
ventilator, UV lights, etc.).
S Turn on power to equipment.
4.4.1. Shielded Wire
If the thermostat wiring will be located near or in parallel with high voltage wiring,
radio, TV or Ethernet wiring, then four conductor, twisted-- pair, shielded cable can
be used to reduce or eliminate potential interference. The shield wire should be
connected to the C terminal, or ground, at the indoor unit. The shield wire should
NOT be connected to any terminal at the user interface. Connecting the shield to
ground at both ends can cause current loops in the shield, reducing shield
effectiveness.
Connect one pair of the two-- pair (minimum) cable to the A and B communication
terminals, and another pair to the C and D terminals at both ends of the cable. The
shield wire should ONLY be connected at the indoor equipment ground or C
terminal. Note that some outdoor units only require the A and B connections. See
the outdoor unit installation instructions for more information.
10
4.4.2. Damper Control Module (zoning systems only)
All wiring is run back to the Damper Control Module. Select a location near the
furnace or fan coil where wiring from the control, each Remote Room Sensor or
Smart Sensor, each damper actuator, and the equipment itself can come together
easily. The Damper Control Module is approved for indoor use only and should
never be installed with any of its components exposed to the elements. The Damper
Control Module (and zone dampers) may be installed in any area where the
temperature remains between - 4_F to 158_F (-- 20_C to 70_C), and there is no
condensation. The cover must be installed to prevent damage from other sources.
Do not locate where it will be accessible to children. It may be mounted in either
vertical or horizontal position. Remember that wiring access is likely the most
important consideration.
! CAUTION
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
To prevent possible damage to the Damper Control Module,
DO NOT mount on plenum, ductwork, or flush against
furnace or fan coil.
4.5. Mounting
First become familiar with all plastic assembly pieces shown on the following page.
The Infinity Touch Control will snap together with the backplate. A backplate is
supplied. Attach backplate using only a small hole in the wall allowing a four wire
connection to pass through. Mount the assembly to the backplate.
11
A12214
A12215
NOTE: Once Infinity Control is secured to wall with the backplate assembly
(snapped together), care must be taken not to bend or break the interlocking tabs
when removing.
12
A12213
NOTE: Once the Infinity Touch Control is secured to wall with the backplate
assembly (snapped together), care must be taken not to bend or break the
interlocking tabs when removing.
A12177
NOTE: If the Infinity-- compatible indoor equipment (furnace or fan coil) cannot be
found, the control will display “Indoor unit not found”. This MUST be corrected
before the initial power up sequence can continue. Proceed to the next section,
Searching for outdoor unit. If it is not corrected, the Infinity Touch Control will go
into its DEMO operating mode.
14
A12178
15
A13118
16
A13119
17
A13117
18
A12185
19
selected. If an incorrect selection was made, touch RE-- INSTALL to restart the
installation process.
A13120
20
approximately one minute per zone. The duct assessment will override a call for
heat or cool.
A duct assessment will automatically occur each day at a user selectable time. The
factory default time is 1:00 p.m. but, may be changed by entering the Zoning Setup
menu (see pages 36 - 37). If there is an active call for heating or cooling, the
system will wait until the call is satisfied before it performs the duct assessment.
The system will first open all zones and drive the blower to 175 CFM/ton of cooling
(or the minimum indoor unit’s airflow, whichever is greater). It will then take a
static pressure measurement. The system will then close all zones and open one
zone at a time, taking a static pressure measurement for each zone.
The system will then close all zones and take a pressure measurement, getting a
value for the duct leakage up to and through the dampers. With these static pressure
measurements, the system will calculate the relative size of each zone as well as the
percent leakage through the dampers At the end of the process, the display will
show the relative size of each zone duct.
If the Infinity Touch Control detects an error (damper not moving or damper wired
backwards), it will perform the duct assessment again. If it still detects a damper
problem, it will default the measurements into equal sizes, with 10% leakage, and
display the zone number for the suspected zone damper.
After the duct assessment is complete, touch NEXT.
A12186
21
6. Service Menu
The Service menus contain a set of vital information. This information enables the
installer or service person to view a summary of what has been installed, etc. This
information is not covered in the Owner’s Manual.
To enter service menus, touch menu, then touch and hold the SERVICE icon for at
least ten seconds. The following screens are available in installation and service. To
return to the previous screen, touch BACK. To exit the Service menus, touch
DONE.
A12145
22
Example: SPP Equipment Summary Screen
A13121
6.2. Installation
Touch INSTALLATION to perform the start-- up process in order to learn all
equipment in system. Press right side button to initiate the process. Touch NEXT to
begin the process.
Touch Duct Assessment to perform a duct assessment. This can be done if duct
modifications have been made since installation of the UI. Duct assessment can be
performed without performing a full system install.
A12146
23
NOTE: For Small Packaged Products (SPP), please use the following instructions
for Set-- up (Section 6.3), Checkout (Section 6.4), and Service (Section 6.5):
- For PAC AC Indoor and OAC HP Indoor, follow Fan Coil instructions.
- For Gas PAC Indoor and Gas PHP Indoor, follow Furnace instructions.
- For all PAC Outdoor, follow AC/Heat Pump instructions.
6.3. Set up
A13130
NOTE: Depending upon the equipment installed, the following options will be
displayed.
S Indoor:
d Furnace
d Fan coil
d PAC AC Indoor
d PAC HP Indoor
d GAS PAC Indoor
d GAS PHP Indoor
24
S Outdoor:
d AC/Heat pump
d PAC AC outdoor
d PAC HP outdoor
d GAS PAC outdoor
d GAS PHP outdoor
Once the equipment has been selected, the appropriate menus will be displayed.
6.3.1. Thermostat
First touch SETUP, then touch THERMOSTAT to set up the parameters for the
Infinityr Touch Control.
A12187
25
6.3.1.2. Heat/Cool Deadband
The minimum difference enforced between heating and cooling desired
temperatures. This can allow one setting to “push” the other to maintain this
difference. When the correct deadband is set, touch SAVE.
S Deadband: Adjustable from 0 to 6_F (0 to 2_C)
d Default = 2_F
6.3.1.3. Offsets
This option allows calibration (or deliberate miscalibration) of the temperature and
humidity sensors. These offsets are added to the actual temperature/humidity
values. When the correct offsets are made, touch SAVE.
S Outdoor temperature: Adjustable from - 5 to 5_F (-- 3 to 3_C)
d Default = 0_F
S Humidity: Adjustable from - 10 – 10%
d Default = 0%
26
d Default = On
6.3.1.6. Smart Recovery Enable
Applies to programmable operation only. Will start recovery 90 minutes prior to
schedule change in both heating and cooling mode. After the selection is made,
touch SAVE.
S Smart Recovery: On or Off
d Default = On
A12188
27
6.3.2.1. Airflow
This option allows the installer to select the appropriate air flow based on the needs
of the installation. The QUIET airflow means the minimum cooling airflow that the
system can safely run (typically 300 CFM/ton). Use this setting if duct noise is a
severe problem. Note that duct sweating in high humidity environments could
become an issue at low airflows. The COMFORT airflow means airflow is varied
depending on humidity and temperature demand settings. This selection enables the
full dehumidify and comfort capabilities of the system. The EFF325 airflow is a
fixed airflow used to achieve specified ratings – no dehumidification airflow
reduction is performed. This is nominally 325 CFM/ton, but will vary if a 2-- stage
outdoor unit is used. The EFF350 airflow is a fixed airflow used to achieve
specified ratings – no dehumidification airflow reduction is performed. This is
nominally 350 CFM/ton, but will vary if a 2-- stage outdoor unit is used. The MAX
airflow is a fixed 400 CFM/ton. No dehumidification airflow reduction is
performed.
The dehumidify airflow, when set to NORMAL, is allowed to adjust to a minimum
to satisfy the dehumidification call. When set to HIGH, the minimum airflow
during the dehumidify mode is increased to reduce duct and register sweating. Also
the airflow increases minimum airflow during normal cooling operation to help
reduce duct sweating.
After the selections are made, touch SAVE.
S Cooling Airflow: Quiet, Comfort, EFF325, EFF350, or Max
d Default = Comfort
S Dehumidify Airflow: Normal or High
d Default = Normal
6.3.2.2. Altitude
S Static Pressure selection: 0 to 10,000 feet. This is used to correct the static
pressure readings the system performs.
28
6.3.2.3. Fan Coil Dehumidification
The Dehum Drain Time option turns off the continuous fan at the end of cooling for
five minutes in order to drain the indoor coil of water. The fan will only be turned
off if a dehumidify demand existed at the start of or during the cooling cycle.
The Electric Reheat option enables the electric heat to be used while
cool-- to-- dehumidify is running. This will allow the cool-- to-- dehumidify function to
run longer, greatly improving humidity control in cooling mode. Accumulated
electrical energy used while reheating (in kilowatt-- hours) is shown on the Fan Coil
Run Hours screen and can be reset there. This option is only available with fan coil
systems.
After the selections are made, touch SAVE.
S Dehum Drain Time: Adjustable from 5 to 60 minutes or OFF
d Default = 15 minutes
S Electric Reheat: Yes or No
d Default = No
29
d Normally Open
d Normally Closed
6.3.3. Furnace
First touch SETUP, then touch FURNACE to set up the parameters for the furnace
unit.
A12189
30
6.3.3.2. AC/HP Air Flow
This option elects the airflow of the furnace when cooling, heat pump heating, and
dehumidification.
The QUIET airflow means the minimum cooling airflow that the system can safely
run (typically 300 CFM/ton). Use this setting if duct noise is a severe problem. Note
that duct sweating in high humidity environments could become an issue at low
airflows. The COMFORT airflow means airflow is varied depending on humidity
and temperature demand settings. This selection enables the full dehumidify and
comfort capabilities of the system. The EFF325 airflow is a fixed airflow used to
achieve specified ratings – no dehumidification airflow reduction is performed.
This is nominally 325 CFM/ton, but will vary if a 2-- stage outdoor unit is used. The
EFF350 airflow is a fixed airflow used to achieve specified ratings – no
dehumidification airflow reduction is performed. This is nominally 350 CFM/ton,
but will vary if a 2-- stage outdoor unit is used. The MAX airflow is a fixed 400
CFM/ton. No dehumidification airflow reduction is performed.
The dehumidify airflow, when set to NORMAL, the airflow is allowed to adjust to
a minimum to satisfy the dehumidification call. When set to HIGH, the minimum
airflow during the dehumidify mode is increased to reduce duct and register
sweating. Also the airflow increases minimum airflow during normal cooling
operation to help reduce duct sweating.
After the selections are made, touch SAVE.
S Cool: Quiet, Comfort, EFF325, EFF350, or Max
d Default = Comfort
S HP Heat: Comfort or EFF350
d Default = Comfort
S Dehumidify: Normal or High
d Default = Normal
31
6.3.3.3. Furnace Staging
This option controls the staging of the furnace and selects the minimum amount of
time low stage must operate before high stage is activated. SYSTEM setting will
allow the Infinityr Zone Control to determine furnace staging. LOW will only run
the low stage of furnace heat. LOW-- MED will run the low and medium stages (2
stages of heat). MED will only run the medium stage of heat. MED-- HIGH will run
the medium and high stages (2 stages of heat). HIGH will only run the high stage
of furnace heat.
NOTE: Two-- stage furnace has LOW and HIGH selections only.
S Stages: System, Low, Low-- Med, Med, Med-- High, or High
d Default = System
32
d Default = 120 seconds
6.3.3.6. Altitude
For gas de-- rating, this setting will adjust the furnace’s airflow to compensate for
altitude. Altitude adjustment is not available with older furnaces. Please see furnace
instructions for further details. After the selection is made, touch SAVE.
S Altitude: 0000 – 2000, US 2001 – 3000, CN 2100 – 4500, US 3001 – 4000,
US 4001 – 5000, US 5001 6000, US 6001 – 7000, US 7001 – 8000, US 8001 –
9000, and US > 9000.
d Default = US 2001-- 3000
S Static Pressure selection: 0 to 10,000 feet. This value is used to correct the
static pressure readings the system performs.
6.3.3.7. Furnace Dehumidifier Drain
This option selects the time the continuous fan turns off at the end of cooling in
order to drain the indoor coil of water. The fan will only be turned off if a
dehumidify demand existed at the start of or during the cooling cycle.
S Dehumidify Drain Time: Adjustable from 5 to 60 minutes
d Default = 15 minutes
33
S Fan Speed: Low, Med, or High
d Default = Low
S Shutdown:
d Normally Open
d Normally Closed\
d The shutdown function may not be immediate. Blower off delays, etc., will
still be used. The shutdown is not intended for commercial applications. If
immediate shutdown is required, provision must be made to remove power
to indoor unit.
6.3.4. AC/Heat Pump
First touch SETUP, then touch AC/HEAT PUMP to set up the parameters for the
AC/Heat Pump unit.
34
A12190
35
d Default = 30 minutes
6.3.4.3. Low Ambient Cooling
Selecting YES will enable the low ambient cooling operation in the outdoor unit.
This setting is only available with communicating outdoor units and with Cooling
Lockout set to NONE. Low ambient kits are not needed with communicating
outdoor units. After the selection is made, touch SAVE.
S Low Ambient Cooling: Yes or No
d Default = No
36
switching reversing valve. This setup is only available on communicating heat
pumps. After the selection is made, touch SAVE.
S Defrost Fan Delay: Yes or No
d Default = No
37
A12149
S HP Lockout: Adjustable from 5 to 55_F (-- 15 to 13_C) or None
d Default = None
S Furnace, Electric Heat or Hydronic Lockout: Adjustable from 5 to 55_F
(-- 15 to 13_C) or None
d Default = None
S Defrost with Furnace, Electric Heat or Hydronic: Yes or No
d Default = Yes
38
A12191
39
airflow; HIGH means 250% of maximum assessed airflow; and NO LIMIT means
the equipment does not stage down.
CFM associated for each limit is shown on the screen. Compare this value with the
equipment’s low stage CFM value to ensure that equipment will run for each zone.
Assessed airflow is determined as described in DUCT ASSESSMENT.
After the selections are made, touch SAVE.
S Touch the zone name that you wish to change
S Select the zone to adjust airflow: Low, Med-- Low, Medium, Med-- High, High,
or No Limit
d Default = High
6.3.7. Accessories
First touch SETUP, then touch ACCESSORIES to set up the parameters for the
accessories installed with the system.
40
A12192
6.3.7.1. Filter
With this option, the installer has the option of selecting pressure monitoring, the
type of filter installed, and the time interval for cleaning. After the selections are
made, touch SAVE.
S Pressure Monitoring (not available with Electric Air Cleaner): Enable or
Disable
d Default = Enable
S Clean Interval: Selectable from 1 to 18 months
d Default = 3 months
S Filter Type: Air Filter, Electric Air Cleaner or Air Purifier
d Filter type is selected during installation; otherwise default = air filter
6.3.7.2. Humidifier
With this option, the installer has the option of selecting whether a humidifier is
installed, to humidify with the fan in low speed, and the time interval for changing
the humidifier pad. After the selections are made, touch SAVE.
S Humidifier Installed: Yes or No
d Humidifier selection made during installation; otherwise default = no
41
S Change Pad: Selectable from 1 to 24 months
d Default = 12 months
S Humidify with Fan: Yes or No
d Default = No
6.3.7.4. Ventilator
When a ventilator is installed, the installer has the option of selecting the time
interval for cleaning the ventilator. After the selections are made, touch SAVE.
S Clean Interval: Selectable from 60, 90, 120, 150 or 180 days
d Default = 90 days
42
lows stage when the curtailment function is active. After the selections are made,
touch SAVE.
A12193
S Cooling: Disabled, Low Stage or Turn off
d Default = Disabled
S Heat Pump: Disabled, Low Stage or Turn off
d Default = Disabled
A12194
43
S Airflow: Selectable between Off to Max in 50 CFM increments
d Off = 450 CFM, MAX = (odu_size in KBTU * 400) / 12)
d Default = Off
S Blower On Delay: Selectable from 0 to 240 seconds
d Default = 30 seconds
S Blower Off Delay: Selectable from 0 to 240 seconds
d Default = 0 seconds
A13122
44
S Medium Heat: Selectable from 0 to 120 minutes
d Default = 5 minutes
S High Heat: Selectable from 0 to 120 minutes
d Default = 5 minutes
6.4.2. Furnace
Make sure the furnace is properly installed.
This option allows the furnace to be exercised. First, a low heat run time and high
heat run time are selected. The furnace will execute its ignition start-- up sequence.
This sequence will be displayed on the screen. After the gas valve and blower
motor turn on, the screen will show the current operating status of the furnace. After
the selections are made, touch START.
S Low Heat: Selectable from 0 to 120 minutes
d Default = 5 minutes
S High Heat: Selectable from 0 to 120 minutes
d Default = 5 minutes
6.4.3. Hydronic
This option allows the hydronic heat relay to be exercised. First, it will energize the
relay and turns on the blower. This sequence will be displayed on the screen. After
the selections are made, touch START.
S Hydronic heater check: Selectable from 0 to 120 minutes
d Default = 5 minutes
45
display will change to show the AC operating status. After the selections are made,
touch START.
NOTE: Airflows during Checkout modes are fixed to the EFFICIENCY setting
and are independent of other airflow settings. To view airflows for normal air
conditioning cooling mode, exit the CHECKOUT screen and apply a heating
demand to the system.
S Low Cool Run Time: Selectable from 0 to 120 minutes
d Default = 5 minutes
S High Cool Run Time: Selectable from 0 to 120 minutes
d Default = 5 minutes
46
100%
d Default = lowest available as specified by variable speed heat pump
S Defrost: Yes or No
d Default = No
6.4.7. Humidifier
The humidifier can be exercised On and Off with this menu option. To end the
humidifier checkout, touch STOP.
S Humidifier Check: On or Off
47
6.4.8. Ventilator
The ventilator can be exercised through all of its operating speeds with this menu
option. To end the ventilator checkout, touch STOP.
S Humidifier Check: High, Low or Off
6.4.9. Zoning (If Applicable)
6.4.9.1. Airflow Limits
Because there is no bypass damper, the zone airflow limit check will allow the
installer to assess the airflow noise generated by the system providing the
maximum amount of airflow to each zone. Touch AIRFLOW LIMITS: When
START is touched, the selected zone’s damper will fully open, all others will close,
and the indoor unit will provide the maximum airflow for that zone (as selected in
SETUP — ZONING, Airflow Limits). If the airflow noise is objectionable, the
installer can select a lower airflow noise limit. If the noise is not objectionable, the
installer should leave HIGH selected, or even NO LIMIT.
NOTE: Selecting a lower airflow noise limit may decrease the homeowner’s
comfort in that zone.
Touch the Left (<) or Right (>) buttons to change the desired zones. Once the
proper airflow limits are set, touch SAVE, to see ZONING CHECKOUT menu.
6.4.9.2. Damper/Sensor Check
The Sensor/Damper Check allows the installer to check each zone damper for
operation, as well as insure the zone sensor corresponds to that particular zone.
When first initiated, the Zone 1 damper will fully open, and all other zones will
close. Using the Left (<) or Right (>) buttons, the installer can select each zone and
verify the damper is fully open while all other dampers remain closed.
48
After proper damper operation has been verified, the installer can now check and
verify that each Remote Room Sensor corresponds to the proper zone damper in the
same zone. For systems with remote room sensor, temporarily disconnect any other
zone Remote Room Sensor (at sensor location). That zone damper will now open,
while the Zone 1 damper will close.
For systems using Smart Sensors, the installer may press and hold the Hold and
Mode buttons simultaneously for 3 seconds to change the zone under test. This
should be done with each zone to verify that the zone sensor corresponds to that
particular zone.
Once each zone has been checked, touch DONE to return to the ZONING
CHECKOUT menu.
6.4.9.3. Zone Duct Assessment
This screen shows the results from the previous duct assessment. The duct
assessment is performed at initial start-- up and at 1 P.M. or the installer selected time
each day. If another duct assessment is desired, the service technician should
perform a re-- install of the system.
NOTE: A Duct Assessment will automatically occur every 24 hours at selected
time to check system static and calibrate dampers.
Once the duct assessment is complete, touch DONE to return to the ZONING
CHECKOUT menu.
6.4.9.4. Sensor Type
This option shows a list of all zones with corresponding sensor types.
6.5. Service Information
The Service Info menu will only show the equipment installed in the system. To
enter this menu of options, touch SERVICE INFORMATION.
49
A13123
A12197
50
A12198
6.5.3. AC Status
The AC status screen displays relevant information about the AC operation. To
return to the previous screen, touch BACK. To exit the Service menus, touch
DONE.
A12199
51
A12200
A12201
52
equipment that generated the event. To return to the previous screen, touch BACK.
To exit the Service menus, touch DONE.
A12151
53
A12202
54
A12203
A12204
6.6.1. Charging
Within the CHARGING screens, the installer will have the ability to enter the
LINESET length and the VAPOR LINE diameter. After the selections are made,
touch NEXT.
S Lineset: Selectable from 5 to 200 feet
55
S Vapor line: Selectable with various diameters by using the up and down
buttons
Next, the installer will enter the WEIGH IN screen to verify the current total charge
is accurate. Once the installer has confirmed, touch DONE.
Next, the installer will enter the SERVICE VALVE SUBCOOL screen. This screen
will show the current liquid line subcool target (in _F). To begin the charging, touch
START. If the outdoor temperatures are not in the required range, Service Valve
Subcool may not be available.
Next, the installer will enter the SERVICE VALVE INFORMATION screen. The
current liquid line subcool target, stabilization time, mode and speed in rpm, EXV
position in percent, indoor airflow in CFM, outdoor coil temperature in _F, indoor
temperature in _F, outdoor temperature in _F, compressor discharge pressure in
psig, and accumulator suction pressure in psig are displayed on this screen. Once
the stabilization time has expired, touch DONE.
6.6.2. Pump down
Because this system has an inverter controlled compressor, suction pressure
transducer and EXV, conventional procedure cannot be used to “pump down” and
isolate the refrigerant into the outdoor unit. The control has provisions to assist in
performing this function.
S Select mode to pump down in (COOL or HEAT). COOL mode allows
refrigerant to be isolated in outdoor unit. HEAT mode allows the refrigerant to
be isolated in indoor coil and lineset. Set desired time period.
d Default time period for procedure is 120 minutes.
S Touch START to begin the pump down process. Unit will begin running in
selected mode after a brief delay.
56
6.6.3. Evacuation
Because this system has an EXV for the heating expansion device, additional steps
must be taken to open the EXV if the heat pump unit must be evacuated for service
reasons. If the EXV is not open when pulling a vacuum or recovering refrigerant
from the heat pump unit, extended evacuation time may be required and/or
inadequate vacuum obtained. The control has provisions to open the EXV for
refrigerant recovery and/or evacuation.
S Set desired time period.
d Default time period for procedure is 120 minutes.
S Touch START on UI to open the valve.
S Begin evacuation or refrigerant recovery as required for the procedure after
control indicates the EXV is open. Power may be removed from heat pump
after the control indicates “READY TO EVACUATE.”
6.7. Dealer Logo
Touch DEALER LOGO to upload the dealer logo and contact information from a
standard USB memory device connected to the Infinityr Touch Control. The
“Dealer Logo Application” PC/MAC software download available at
www.MyInfinityTouch.Carrier.com/Infinity/downloads is required to properly
format the dealer logo and contact information for use on the wall control.
Along with the dealer logo (if any), three lines of dealer information are provided
on the wall control:
Dealer name (50 characters, max)
Dealer phone number (20 characters, max)
Dealer URL (50 characters, max)
The wall control dealer information display is 30 characters wide. Dealer names
and URLs over 30 characters will be split into two lines on the display.
57
The PC/MAC software application to format the dealer logo and contact
information can be found at:
www.MyInfinityTouch.Carrier.com/Infinity/downloads
Download the program and follow the program instructions.
Once the dealer logo and contact information have been properly loaded onto the
USB memory device, insert the USB device into the bottom edge of the Infinityr
Touch Control. The control will prompt you whether or not to upload the dealer
logo. Once complete, you will receive a confirmation that your upload was
successful. If the information was not stored properly on the USB device, you will
receive an error message that the dealer logo was not found. Refer back to the
PC/MAC software application instructions and try again. Once the upload is
complete, touch NEXT.
If you have problems, contact your distributor service manager for support.
A12205
58
(LAN). An Infinityr Wireless Access Point is provided in the Infinity Touch
Control Wi-- Fi bundle to ease connection of the Infinityr System to a home LAN.
If you or the homeowner encounter problems with Wi-- Fi or network connections,
please call 1-- 800-- CARRIER for support with the installation and setup of the
Wireless Access Point, connection of the Infinityr Control to the Wireless Access
Point, or connection of the Infinity System to the web applications. Verify that
Internet connections to other devices in the home are operating properly before
calling for support for Internet problems. If other devices in the home do not have
Internet connection, disconnect the Wireless Access Point from the home LAN. If
the Internet problems persist with other devices in the home, the homeowner should
contact their Internet Service Provider.
The ability to remotely access and adjust the settings of the Infinityr Touch Control
with the MyInfinity web and mobile applications is dependent on the compatibility
of the user’s computer/network or mobile device, the Infinity Touch Control, and/or
the MyInfinity web server with, and the availability of, the user’s internet service
provider or mobile device carrier service. Carrier Corporation makes no
representations or warranties, express or implied, including, to the extent permitted
by applicable law, any implied warranty of merchantability or fitness for a
particular purpose or use, about the compatibility of the user’s computer/network,
or mobile device, with the Infinity Touch Control, and/or the MyInfinity web server,
with, and the availability of, the user’s internet service provider or mobile device
carrier service, or that the ability to remotely access and adjust the settings of the
Infinity Touch Control will not be negatively affected by the network-- related
modifications, upgrades, or similar activity of the user’s internet service provider or
mobile device carrier service.
7.1. Connect Wireless Access Point ot Home LAN
The Wireless Access Point may be located anywhere there is an Ethernet cable
connected to the home LAN router, including next to the router itself. To install
Wi-- Fi connectivity to the Infinity Touch Control, connect the WAN connection
59
(BLUE port) of the TP-- LINKr Wireless Access Point (supplied with the Infinity
Touch Control Wi-- Fi Bundle) to an open LAN port on the homeowner’s existing
router using the provided Ethernet cable.
If there are no open LAN ports available on the homeowner’s existing router, the
home router’s LAN ports may be expanded by use of an Ethernet Network Switch,
available from a local electronics store. Consult the information supplied with the
network switch for instructions on applying and using the network switch.
The LAN ports on the back of the TP-- LINK Wireless Access Point should not be
used for other devices. The TP-- LINK Wireless Access Point should only be used
for connection of the Infinity Touch Control and is not intended to be used, wired or
wirelessly, with any other devices.
Once the Ethernet cable is connected, install the power supply to the Wireless
Access Point, plug the power supply into a household receptacle, and press the
power button on the back of the Wireless Access Point. The power light on the front
of the Wireless Access Point should light and after a few minutes three other
indicator lights will begin to blink (LAN Activity, Wi-- Fi Activity and WAN/Internet
Activity).
Verify the signal strength of the wireless access point radio signal at the desired
location of the Infinity Touch Control with a wireless laptop computer. Use the Scan
for Wireless Networks utility and verify that the signal for “MyHVACxxxxxx” is
“Strong” or better. If not, reposition the wireless access point to provide a strong
signal at the wall control location.
7.2. Connect the Infinity Touch Control to the Wireless Access
Point
Touch the WIRELESS icon from the second page of the Infinity Touch Control
MENU screen. First, enable the Wi-- Fi connection by touching the ENABLE
button.
60
A12206
S Verify that the Wi-- Fi connection is enabled, by noting that ENABLED is
highlighted in green.
S Touch SETUP A WI-- FI CONNECTION to begin the process.
S Next, touch SCAN FOR AVAILABLE ACCESS POINTS.
A12115
S Select the myHVACxxxxxx connection from the list, then touch NEXT
d Note that “myHVAC” is followed by the last 6 digits of your Wireless Ac-
cess Point’s MAC address
d This is the “SSID” of the Wireless Access Point
d The SSID for the Wireless Access Point may also be found on a label on
the bottom of the Wireless Access Point
61
d You may have to use the down arrow to scan to the next screen to find the
“myHVACxxxxxx”SSID
A12162
S Use the on-- screen keyboard to enter the Wi-- Fi security key, then touch NEXT
d The security key can be found on the label on the bottom of the Wireless
Access Point
d Touch in the security key area, and the keyboard will appear
d Begin typing and the ENTER TEXT label will disappear
A12163
S The control will inform you if the connection is successful. If so, touch DONE.
62
d If the connection is unsuccessful, verify the Wireless Access Point SSID
and Security Key from the label on the bottom of the Wireless Access
Point.
d A message of “Security Mis-- match” indicates that the security has been
entered incorrectly.
d Touch RETRY and the wall control will go through the process again
d If you continue to have problems, call 1-- 800-- CARRIER for support
A12165
S Verify the status of the Wi-- Fi connection by touching VIEW REMOTE
ACCESS STATUS on the WI-- FI SETUP screen
d “Connected” should appear next to Network Status
d If the Network Status is “not connected”, repeat the process in section 7.2
d The MyInfinity Server status may take up to 15 minutes to show “Connec-
ted” due to Internet traffic
d If the MyInfinity Server status fails to show “Connected” after 15 minutes,
check Internet connectivity with other devices in the home. The
homeowner should contact their Internet Service provider to diagnose
general Internet problems in the home
d If you continue to have problems, call 1-- 800-- CARRIER for support
63
Once Internet connectivity is established, the weather forecast should appear on the
HOME screen and on the WEATHER button/screen, found on the second page
under the MENU option.
7.3. Connect to MyInfinity Web Server
After connection to the Internet is established, the Infinity Touch Control must
register with the web server database in order to enable the web applications. To do
this, touch the WIRELESS icon from the second page of the MENU screen. In the
WI-- FI SETUP screen, touch MyInfinity REGISTRATION INFO. Write down
the Infinity Touch Control Serial Number, MAC Address, and PIN that are
displayed on this screen. This is the information that the consumer will need to
register on the www.MyInfinityTouch.Carrier.com website. It is also the
information that you may need to identify the system through
www.HVACpartners.com, if the homeowner allows you access to their system.
NOTE: DO NOT use the MAC address, serial number or security key from the
Wireless Access Point label to register on the MyInfinity website. It will NOT work.
Use the Infinity Touch control information from the MyInfinity Registration Info
screen to register the system on the MyInfinity website.
The consumer may follow the information provided on
www.MyInfinityTouch.Carrier.com to register their system. This must be done
BEFORE you attempt to access the system through www.HVACpartners.com.
If you or the consumer have problems, contact 1-- 800-- CARRIER for support.
64
8. Appendix A - Wiring Diagrams
Variable-Speed
Furnace/ Fan Coil Communicating
User Interface AC or H P*
Green - Data A Green
A A A
Yellow - Data B Yellow
B B B
White - COM White
C C C
Red - 24VAC Red
D D D
S1 Optional Remote
Room Sensor
S2 HUM
ABCD
Humidifier
Connection
Connections
COM
24V
OAT
OAT Sensor
(Optional)
*NOTE: Some outdoor units do not require the “C” and “D” connections.
See outdoor unit Installation Instructions.
*NOTE: For SPP products, ABCD connection between Indoor and Outdoor
control boards are pre-wired at the factory.
*NOTE: For new SPP installations in which the OAT Sensor is required,
please refer to the SPP Installation Instructions.
A13124
Universal Four-- Wire Connection
65
Variable-Speed
Furnace/Fan Coil
User Interface
Green - Data A
A A
Yellow - Data B
B B
White - COM ABCD
C C Connection
Red - 24VAC
D D
COM C
24V
Y/Y2 Y
OAT OAT
Sensor
A12354
Connection Diagram for Furnace or FE Fan Coil with
1-- Stage Air Conditioning
66
Variable-Speed
Fan Coil
User Interface
Green - Data A
A A
Yellow - Data B
B B
ABCD
White - COM
C C Connection
Red - 24VAC
D D
R R
O O
W W2
Y Y
OAT OAT
Sensor
A12355
Connection Diagram for FE Fan Coil with Non-- communication
1-- Stage Heat Pump
67
Indoor Communicating
Zone Control Unit AC or HP
User Interface &
Smart Sensor(s) Green
A A
Yellow
A B C D B B
White
C C
Red
D D
A B C D A B C D
Humidifier HUM
Connection
Damper COM
24V
Control
OAT
module Sensor
(Optional)
OAT
A04018
Zoning Connection for Communicating Indoor Unit with
2-- Stage Communicating Outdoor Unit
68
Indoor
Zone Control Unit
User Interface &
Smart Sensor(s) Green
A
Yellow
A B C D B
White
C
Red
D
A B C D A B C D 1-Stage
. AC
HUM
Humidifier
Connection
COM C
24V
Damper
Control Y/Y2 Y
module
OAT
OAT
Sensor
A04019
Zoning Connection Diagram for Furnace or FE Fan Coil with
Non-- Communicating 1-- Stage Air Conditioning
69
Zone Control Variable-Speed
User Interface & Fan Coil
Smart Sensor(s) Green
A
Yellow
A B C D B
White
C
Red
D
1-Spd. HP
A B C D A B C D
Humidifier HUM
Connection C C
G
R
R
Damper O O
Control W W2
module Y Y
OAT
OAT
Sensor
A07149
Zoning Connection diagram for FE Fan Coil with
Non-- communicating 1-- Stage Heat Pump
70
R
FE Fan Coil or
Variable Speed Furnace
A07114
G Input Wiring for Blower Operation
71
R
FE Fan Coil or
Variable Speed Furnace
A07115
G Input Wiring for System Shutdown
72
NOTES:
73
NOTES:
74
Infinity and HYBRIDHEAT are trademarks or registered trademarks of Carrier
Corporation in the United States and other countries. Other brands and product
names are trademarks of their respective holders.