This document summarizes the air system sizing for AHU-GF-02 serving a 623.2 square meter floor area in Kuala Lumpur, Malaysia. The central cooling coil has a total load of 100.9 kW with a sensible load of 81 kW. At peak conditions in August at 1600 hours, the required airflow is 6237 L/s. The supply fan is sized to deliver 6221 L/s at 0 Pa static pressure using 0 kW of motor power. Outdoor air is provided at 729 L/s or 1.17 L/s per square meter.
Download as RTF, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
35 views
Air System Sizing Summary For AHU-GF-02
This document summarizes the air system sizing for AHU-GF-02 serving a 623.2 square meter floor area in Kuala Lumpur, Malaysia. The central cooling coil has a total load of 100.9 kW with a sensible load of 81 kW. At peak conditions in August at 1600 hours, the required airflow is 6237 L/s. The supply fan is sized to deliver 6221 L/s at 0 Pa static pressure using 0 kW of motor power. Outdoor air is provided at 729 L/s or 1.17 L/s per square meter.
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 1
Air System Sizing Summary for AHU-GF-02
Project Name: 2014-09-18 Cyberjaya Skypark
Prepared by: PECE
09/25/2014 05:59PM
Air System Information
Air System Name ....................................... AHU-GF-02 Equipment Class ............................................ CW AHU Air System Type ................................................ SZCAV
Number of zones ............................................................. 1
Floor Area ................................................................. 623.2 m Location .................................... Kuala Lumpur, Malaysia
Sizing Calculation Information
Zone and Space Sizing Method: Zone L/s .......................... Sum of space airflow rates Space L/s ...................... Individual peak space loads
Calculation Months ......................................... Jan to Dec
Sizing Data ...................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ....................................................... 100.9 Sensible coil load ................................................... 81.0 Coil L/s at Aug 1600 .............................................. 6237 Max block L/s ........................................................ 6237 Sum of peak zone L/s ........................................... 6237 Sensible heat ratio ............................................... 0.803 m/kW ....................................................................... 6.2 W/m ..................................................................... 161.8 Water flow @ 8.9 K rise ........................................ 2.71
kW kW L/s L/s L/s
L/s
Load occurs at ................................................... Aug 1600
OA DB / WB ...................................................... 34.2 / 25.5 Entering DB / WB ............................................. 26.0 / 19.2 Leaving DB / WB .............................................. 15.2 / 14.6 Coil ADP ..................................................................... 14.0 Bypass Factor .......................................................... 0.100 Resulting RH ................................................................. 51 Design supply temp. ................................................... 14.4 Zone T-stat Check .................................................... 1 of 1 Max zone temperature deviation .................................. 0.0
C C C C % C OK K
Supply Fan Sizing Data
Actual max L/s ....................................................... 6237 L/s Standard L/s .......................................................... 6221 L/s Actual max L/(s-m) .............................................. 10.01 L/(s-m)
Outdoor Ventilation Air Data
Fan motor BHP ........................................................... 0.00 BHP
Fan motor kW ............................................................. 0.00 kW Fan static ......................................................................... 0 Pa L/s/person ................................................................... 7.80 L/s/person