Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Esp CalCULATION DATA SHEET Final

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 14
At a glance
Powered by AI
The document discusses pressure losses in ducts, elbows, and reducers for an HVAC system. It provides formulas and coefficients to calculate losses for different components based on factors like geometry, flow rate, and velocity.

The document discusses pressure losses in straight ducts, elbows, and reducers. For straight ducts it provides formulas relating pressure loss to length and flow rate. For elbows it relates pressure loss to radius, velocity, and a coefficient. For reducers it discusses relating pressure loss to area ratios and a coefficient.

Pressure losses in straight ducts are calculated based on length and flow rate using provided formulas and coefficients. For elbows the loss is calculated as the velocity pressure multiplied by a fitting loss coefficient related to the radius. For reducers the loss is calculated based on the area ratio and a coefficient.

IN.

WG PASCALS

PR.LOSS IN STRAIGHT DUCTS = 0.0349 8.6899


PRESSURE LOSS IN ELBOWS = 0.0051 1.2629
PRESSURE LOSS IN REDUCERS = 0.0227 5.6601

20% SAFETY FACTOR = 0.0125 3.1226

TOTAL PR.LOSS =
0.0752 18.7356
SIZE IN mm FLOW RATE LENGTH IN SIZE IN in LENGTH FLOW RATE PRESSURE PRESSURE PRESSURE LOSS
S.NO ITEM REFRENCE EQUIVALENT DIA
L/S M IN FT CFM LOSS/100FT LOSS (IN.WG) (PASCALS)
W H W H
CLICK HERE
1 STR.DUCT A-B 200 150 47 28 8 6 91.8 7.6 100 0.038 0.0349 8.69
2 STR.DUCT B-C
3 STR.DUCT C-D
4 STR.DUCT E-F

TOTAL FRICTION LOSS IN STRIGHT


= 0.0349 8.69
DUCT
PRESSURE LOSSES IN ELBOWS
SIZE IN mm CLICK HERE FITTING
FLOW RATE RADIUS OF FLOW RATE VELOCITY IN VELOCITY
S.NO ITEM REFRENCE R θ H/W R/W LOSS(IN.WG)
Width(W) Height(H) L/S ELBOW(r) Coefficiant-C M³/s FPM PRESSURE(Vp)
= CxVp

1 ELBOW EL-1 300 300 284 150 300 1.0 1.0 0.21 0.284 622 0.0242 0.0051
2 OUTLET

TOTAL PRESSRE
= 0.005
LOSS IN ELBOW
FITTING
LOSS(PASCALS)

1.26

1.263
SIZE IN mm FLOW
ANGLE VELOCITY
S.NO ITEM REFRENCE RATE
(θ) PRESSURE
W H L/S
500 300
1 REDUCER RD-1 30 300 0.12786
200 200
400 300
2 REDUCER RD-2 30 100 0.01421
200 200
3 REDUCER RD-3 30 150

4 REDUCER RD-4 30 800

5 REDUCER RD-5 30 200

6 REDUCER RD-6 30 500

7 REDUCER RD-7 30 600

8 REDUCER RD-8 30 800

9 REDUCER RD-9 30 200

10 REDUCER RD-10 30 300


AREA-1 AREA-2 CLICK HERE PRESSURE LOSS
A1/A
(A1) sqf (A) sqf IN "IN.WG"
COEFFICIANT

1.67 0.44 3.8 0.06 0.00767

1.33 0.44 3.0 1.06 0.01506

ENTER ENTER
2.06
DUCT SIZE DUCT SIZE
ENTER ENTER
DUCT SIZE DUCT SIZE
ENTER ENTER
DUCT SIZE DUCT SIZE
ENTER ENTER
DUCT SIZE DUCT SIZE
ENTER ENTER
DUCT SIZE DUCT SIZE
ENTER ENTER
DUCT SIZE DUCT SIZE
ENTER ENTER
DUCT SIZE DUCT SIZE
ENTER ENTER
DUCT SIZE DUCT SIZE
TOTAL
PRESSURE = 0.02273
LOSS
PRESSURE LOSS
IN "PASCALS"

1.91029

3.74984

5.66013
1

EQUI.DIA = (WxH) POWER 0.625)/(W+H)POWER 0.25

W = WIDTH OF DUCT
H = HEIGHT OF DUCT

TOTAL PRESSURE LOSS IN FITTING = C x Vp


C = FITTING LOSS COEFFICIANT
Vp = VELOCITY PRESSURE

3
1 IN.WG = 249 PASCALS

4
1L/S = 2.119 CFM
1
FLOWRATE 0.284
AREA 0.09
VELOCITY 3.155556
VELOCITY 621.6444