AIR HANDLING UNIT - PRESSURE DROP

Sheet no.:1

of

1 Computed by:

Checked by:
Approved by:

Column number

Tag number

AHU-G-1

System served

Reception

Internal Static
Pressure

EXTERNAL
STATIC
PRESSURE.
AIR SIDE (in
wg)

TOTAL AIR SIDE


Summary

Duct Run (m)

Friction\100ft

0.08

Duct Work

0.013

Fittings 15%

0.002

Volume Damper

0.100

Duct Heater (if any)

0.000

Fire Damper

0.000

Terminal Box (if any)

0.000

Air Outlet

0.100

Fresh Air Louver (if any)

0.000

30% Safety

0.035

Sub total ( External)

0.250

TOTAL + 10% safety

0.275

EXTERNAL (pa)

62

TOTAL (pa)

68