BILL OF QUANTITIES - HVAC INSTALLATIONS

SL. NO. ITEM DESCRIPTION Unit QTY. PRICE

Supply Square Diffuser with VCD, 450x450 Neck Size No. 29

Return Square Diffuser, 450x450 Neck Size No. 10

Fire Damper, UL listed;


800x1200 No. 1

650x650 No. 1

Volume Control Dampers (VCD);


400x400 No. 6

500x300 No. 3

500x350 No. 5

500x400 No. 6

500x500 No. 5

750x650 No. 2

900x650 No. 1

600x500 No. 1

650x600 No. 1

Kitchen Hood Extract 2hrs Fire rated GI Duct works


with fittings and 100mm thick rockwool insulation

400x400 m 12.2

500x300 m 6

500x350 m 8

500x400 m 9.2

500x500 m 11

500x600 m 7

600x600 m 3

800x600 m 16

800x700 m 2

700x700 m 5

500x700 m 7.8
750x700 m 5

700x950 m 1

950x950 m 7
Kitchen Hood Supply GI Duct works with fittings
without insulation
400x400 m 12.2

500x300 m 6

500x350 m 8

500x400 m 9.2

500x500 m 11

500x600 m 7

600x600 m 3

800x600 m 16

800x700 m 2

700x700 m 11

500x700 m 7.8

750x700 m 8

700x950 m 1

950x950 m 13

Fresh air GI Duct works & Fittings with thermal


insulation

400x300 m 13

500x400 m 40

650x500 m 7.2

750x650 m 10.5

900x600 m 3

900x650 m 3.5
1000x800 m 2.3

1200x800 m 5

600x350 m 6

600x500 m 8

650x600 m 1.5

650x650 m 6.6

1200x500 Bell mouth with GI wire mesh No. 1

1000x500 Bell mouth with GI wire mesh No. 1

GI Duct works with thermal insulation, acoustic


insualtion & weather proof protection, 0.6mm
Hammered Aluminium cladding etc.

500x400 m 7

500x500 m 3.5

600x500 m 8.5

700x500 m 3

900x650 m 11

1100x900 m 10

1200x800 m 7
Fresh Air duct, 1200x800 with VCD & 2000x2000mm
No. 2
Sand trap louvre
2700x2600mm Sand trap louvre & Washable Filter
No. 5
section.
2500x2500mm Sand trap louvre & Washable Filter
No. 2
section
400x200mm Fresh air intake with Sand trap louvre &
No. 1
VCD
1200x600mm Fresh air intake with Sand trap louvre &
No. 1
VCD
Kitchen Hood extract ductwork with Sand trap louvre &
No. 2
Goose neckArrangement 800x600mm
Sound Attenuators, 950x650 No. 2

Sound Attenuators, 1100x900 No. 1

Sound Attenuators, 500x400 No. 1


NRD 950x650 No. 2

Insulated Refrigerant pipes run in GI cable Tray m 47

Variable Frequency Drive Fresh Air Handling unit (FAHU-


K-1 & 2) with Condenser Unit (CND-K-1 & 2), Cooling
load - 262.5 kW (On Coil, DB/WB-46/30 deg. C, Off Coil,
DB/WB- 14/13.5 deg.C), Air flow - 3500 lps, 300 Pa, with
insulated Condensate drain pipe with U-trap, anti No. 2
vibration pads, flexible connection, control Panel, isolator,
cables etc.
Note: Variable Frequency Drive Panels to be kept in Air
conditioned room.

Variable Frequency Drive Fresh Air Handling unit (FAHU-


B-1) with Condenser Unit (CND-B-1), Cooling load - 243
kW (On Coil, DB/WB-46/30 deg. C, Off Coil, DB/WB-
14/13.5 deg.C), Air flow - 4000 lps, 250 Pa, with insulated
Condensate drain pipe with U-trap, anti vibration pads, No. 1
flexible connection, control Panel, isolator, cables etc.

Note: Variable Frequency Drive Panels to be kept in Air


conditioned room.

Package Unit (PAC-B-1), Cooling load - 28 kW (On Coil,


DB/WB-27/22 deg. C, Off Coil, DB/WB- 14/13.5 deg.C),
No. 1
Air flow - 800 lps, 200 Pa, anti vibration pads, control
Panel, isolator, cables etc.

Variable Frequency Drive Kitchen Hood weather


proof Axial Supply Fan to be interfaced with FAHUs
and Kitchen Hood Extract Fan with Anti-vibration
pads, control Panel, isolator, cables etc.
Note: Variable Frequency Drive Panels to be kept in Air
conditioned room.
KHSF-K-1: 5908, Pa:150 No. 1
KHSF-K-2: 6451, Pa:150 No. 1
KHSF-K-3: 3136, Pa:150 No. 1
KHSF-K-4: 3640, Pa:150 No. 1
KHSF-K-5: 2884, Pa:150 No. 1
KHSF-B-1: 5908, Pa:150 No. 1
KHSF-B-2: 6451, Pa:150 No. 1

Variable Frequency Drive Kitchen Hood weather


proof Direct Driven Byfurcated Upblast Centrifugal
Extract Fan to be interfaced with FAHUs and Kitchen
Hood Supply Fan with control Panel, isolator, cables
etc.
Note: Variable Frequency Drive Panels to be kept in Air
conditioned room.
KHEF-K-1: 7385, Pa:250 No. 1
KHEF-K-2: 8064, Pa:250 No. 1
KHEF-K-3: 3920, Pa:250 No. 1
KHEF-K-4: 4550, Pa:250 No. 1
KHEF-K-5: 3605, Pa:250 No. 1
KHEF-B-1: 4550, Pa:250 No. 2

DX Type cooler unit capacity same as existing No. 1


IDU-B-01, Cap: 1.5 TR Ceiling Suspended cabinet type
with roof mounted outdoor unit with all electrical No. 1
accessories.
IDU-B-02, Cap: 2.0 TR Ceiling Suspended cabinet type
with roof mounted outdoor unit with all electrical No. 1
accessories.