Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Car Park Ventilation System Design

Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

Car Park Ventilation System Design - Fan Quantities

Description
For the purpose of estimating costs, the steps on the following pages may be bypassed. Allow 5N of thrust per 100m 2 of car park floor area to
approximate the number of fans required.
Estimating fan quantities
The following steps are sufficient to create an initial impulse ventilation system design. A Computational Fluid Dynamics (CFD) analysis is often
required to prove and further refine the design. Fans may need to be re-orientated, or in some cases, added or removed. An impulse ventilation
system can be tailored to suit virtually any car park. Before considering fan locations, the system layout will need to be identified. Refer to the
previous section for information relating to system layouts and their suitability for particular car parks.
Step 1 - Assessing Car Park Geometry
First identify the supply and exhaust points in the car park. A system that complements the natural air path and is able to circulate or move air
effectively within the car park should be chosen. Certain layout features may assist the effectiveness of a particular layout as shown below:
(a) ‘Natural air path’

Figure 6(a). Preferred natural air path

Figure 6(b). Natural air path to be avoided

• For ‘Linear Flow Systems’, supply and exhaust points should be spaced across the length of a car park.
• ‘Circular Mixing Systems’ are more tolerant of closely placed supply and exhaust points, but it is advisable to have a good amount of separation.
• Supply air points should include access ramps to outside.
• The impulse ventilation system layout should complement the natural air path from supply to exhaust points.
(b) Ceiling features
To make the system more effective, position JetVent Fans in-line with supporting ceiling beams as illustrated in Figure 7(a). If this is not possible,
the system becomes less effective and more fans may be needed.

Figure 7(a). Fan’s air movement parallel to beams is most effective

Figure 7(b). Fan’s air movement perpendicular to beams is less effective


(c) Vertical clearance
Sufficient vertical clearance ensures maximum flexibility in system design. JetVent Fans may be recessed between ceiling beams to minimise the
height of the system.

Figure 8(a). Sufficient clearance

Figure 8(b). Insufficient clearance

(d) Obstructions
If there is no option and the JetVent Fans must blow across ceiling beams, they have to be positioned a sufficient distance away from the
obstruction as illustrated in Figure 9(b). A horizontal distance eight times (8x) the height of the obstruction is generally sufficient. Nozzles on the
JetVent units are specially designed and angled downwards for this purpose.
Figure 9(a). Obstruction too close

Figure 9(b). Obstruction out of the way


(e) Clashes with other services
Place mechanical service components, such as sprinklers, signs and pipework out of the JetVent’s discharge pattern area. Examples of these
clashes are shown below.
Figure 10(a). An example of how to avoid clashes with pipe-work

Figure 10(b). Jet fan layout in relation to sprinkler heads

Step 2 - Identify Fan Selection and Spacing


Table 5 shows the maximum and recommended spacings between JetVent Fans for different levels of fan thrust. These spacing distances are
guidelines for fans placed in series. When using these spacings, air velocities in most of the ventilated areas should be greater than 1m/s.
Analysis will determine whether this is achieved in a particular car park design. In some ideal cases, designs using the maximum distances have
been effective.
Fan thrust depends on the operating speed of a particular fan unit and its thrust rating. See tables one to four for the thrust ratings of various fan
models at different speeds.
Operating Recommended fan to fan Maximum fan to fan Approximate
fan thrust spacing distance spacing distance coverage area

50N 45m 60m 100m2

28N 34m 45m 560m2

25N 30m 40m 500m2

19N 23m 30m 380m2

12N 12m 20m 250m2

Table 5. Fan spacing and coverage


Note that using fewer higher rated JetVent fans generally makes the system more cost effective than using more lower rated fans. However, to
effectively ventilate car parks with unusual or irregularly shaped geometries, selecting more fans with smaller thrust ratings may be necessary.

Figure 11(a). Two 25N fans


Figure 11(b). One 50N fan

Step 3 - Design Example


For the purpose of estimating costs, the steps below may be bypassed. Allow 5N of thrust per 100m 2 of car park floor area to approximate the
number of fans required. Fans should be placed in the laneways with the air blowing along them. This will ensure that the high air velocities close
to the outlet nozzle do not significantly disturb pedestrian traffic as velocities will be lower at the lane edges. Also, ensure that the throw pattern of
the selected fan is long enough to reach the next impulse fan.
Figure 12 shows an example of how fans are sized and placed based on floor area.
Figure 12. Fan sizing
and placement example
Design parameters;
• Based on 5N per 100m2 floor area, minimum total fan thrust = car park floor area x 5N/100m2
= 1920m2 x 5N/100m2
= 96N
• Minimum thrust criteria can be achieved with 4 x JISU-CPC-50N fans on low speed (operating thrust 25N), total fan thrust= 25N x 4= 100N.
• Fans are spaced within the 30m spacing recommendation for 25N thrust.
• Final fan to wall spacing under 40m maximum spacing guide lines for 25N fan thrust. This is because the exhaust point is an area of low pressure,
making it likely to enhance the fan throw distance.
Placement of CO sensors:
Because the guidelines for positioning CO sensors in AS/NZS1668.2:2012 is based on a ducted system, we propose that the following guidelines
be used as a starting point for their placement in a jet fan system.
• No part of the enclosure shall be greater than 25 metres from a sampling point. (A 50 metre diameter circle around a CO sensor can show
coverage areas).
• Additional detectors shall be installed in areas where people may congregate within the car park and are not within separately ventilated areas.
• The most practical mounting position for a CO sensor within a car park is the support columns.
• CO sensors will be more effective if placed in areas where CO levels are likely to be high. Eg. Placing a CO sensor in front of a fresh air intake is
not likely to be effective.
If jet fans are placed in each laneway of a car park and the recommended low speed jetfan spacings are followed, the above guidelines can be
achieved by using one CO sensor per jet fan and providing additional CO sensors at congregation points. Therefore, for this car park we would
suggest installing 5 (4 + 1) CO sensors for good coverage.

Step 4 - Calculate Supply & Exhaust Rates


Section 4 of AS/NZS1668.2:2012 details requirements for ventilating car parks. In particular, sup-sections 4.4.3 and 4.4.4.2 of the standard
outlines calculations of exhaust rates. In any of the two cases below, the exhaust air flow rate for a car park is taken as the greatest of the
following calculations:
Calculation of exhaust air flow rates
Car parks with more than 40 spaces Car parks with less than or equal to 40 spaces

a) 2000 x F x T Litres/s (minimum air quantity for one operating car) a) 2000 Litres/s

b) 0.85 x P x (100 x n1+ n1 x d1 + n2 x d2 ) x E x T b) 2.5 x A Litres/s

c) 2.5 x A Litres/s (minimum air quality based on area of car park) c) 400 n1 x P Litres/s

Supply air flows should range from 75% to 90% of the exhaust air quantity. This is based on the pressurisation of the car park, which should be
12Pa maximum.
Reference information for the calculation of exhaust air flow rates in the table above:
A = the area of the zone or level, in square metres
d1 = the average driving distance, in metres, within the zone or level under consideration for the exit of a car parked there (see Clause 4.4.4.1)
d2 = the average driving distance, in metres, within the zone or level under consideration for the exit of a car whose exit route passes through the
zone or level under consideration, but excluding any part of the exit route designated as queuing areas and ventilated in accordance with Clause
4.6 (see Clause 4.4.4.1)
E = the staff exposure factor (E)
F = the staff usage factor (F)
n1 = the number of parking spaces in the zone of level under consideration (see Clause 4.3.2)
n2 = the number of parking spaces situated in other parts of the car park, having exit routes passing through the zone or level under consideration
P = the parking usage factor (P)
T = the vehicle type factor (T)

If the car park has significant queuing areas for vehicles, refer to section 4.6 in AS1668.2:2012
Appendix
AS/NZS1668.2 - 2012 Calculation Factors
Parking Usage Factor (P)
Parking
Use of car park usage
factor (P)

Residential 0.3

Commercial 0.5

Retail/food and drink services 0.7

Entertainment/sports centres 1.0

Vehicle Depots 2.4

Vehicle Type Factor (T)


Vehicle type
Use of car park Parking
factor (T)

No special vehicle
1.0
population

Diesel vehicles 2.4

LPG vehicles 1.0

CNG vehicles 1.0

Electric powered vehicles 0.1

Motorcycles 0.25

Staff Usage/Exposure Factor (E & F)


Staff exposure
Parking procedure Staff usage factor (F)
factor (E)

No special procedures (self-parking), any staff in separate enclosure


1 1
ventilated in accordance with Clause 4.2.2

Self-parking stack parking, any staff in separate enclosure ventilated in 1 + 0.1 x No. of car spaces without immediate
1
accordance with Clause 4.2.2 access to driveway

No special procedures (self-parking), staff located in car parking


1.8 2
enclosure

2 + 0.25 x No. of car spaces without immediate


Self parking stack parking, staff located in car parking enclosure 1.8
access to driveway

Attendant parking no stack parking 1.8 2.5 x No. of attendants

Attendant parking stack parking 1.8 3.5 x No. of attendants

2 x No. of car engines


Mechanical stack parking 1.8
operating at any one time
References
• Australian Building Codes Board 2013, Building Code of Australia Class 2 to Class 9 Buildings Volume One, ABCB, Canberra.
• British Standards Institution 1999, Fans for general purposes. Methods of noise testing (BS 848-2 – 1985), British Standards, London.
• British Standards Institution 1999, Fans for general purposes. Performance testing of jet fans (BS 848-10 – 1999), British Standards, London.
• Federation of Environmental Trade Associations (FETA) 2007, CFD Modeling for Car Park Ventilation Systems, Federation of Environmental
Trade Associations, Berkshire.
• Standards Association of Australia 1999, Methods of test and rating requirements for smoke-spill fans-(AS 4429 – 1999), Standards Australia,
Sydney.
• Standards Association of Australia 1998, The use of ventilation and air-conditioning in buildings Part 1: Fire and smoke control in multi-
compartment buildings (AS 1668.1 – 1998), Standards Australia, Sydney.
• Standards Association of Australia 2012, The use of ventilation and air-conditioning in buildings Part 2: Ventilation design for indoor air
contaminant control (AS 1668.2 – 2012), Standards Australia, Sydney.

You might also like