Series 27100, 28000: Description
Series 27100, 28000: Description
Series 27100, 28000: Description
2
Table 2.
s u o d r a z a H
n o i t a c o L
l e d o M
r b m u N
r o F d e r i u q e R g n i t t i F
s g n i t s i L C L U , L U
l a v o r p p A M F d n a
s p u o r G , * I s s a l C
; D d n a C , B , A
s p u o r G , * I I s s a l C
G d n a F , E
2 2 - 0 2 1 7 2
0 2 - 1 2 1 7 2
3 - 0 2 0 8 2
5 - 1 2 0 8 2
a o t r o t c e t e d t n u o M
n i g n i t t i f d e t s i l - y l b a t i u s
h t i w e c n a d r o c a
e d o C c i r t c e l E l a n o i t a N
y t i r o h t u a l a c o l r o / d n a
. n o i t c i d s i r u j g n i v a h
s p u o r G , * I s s a l C
; D d n a C , B
s p u o r G , * I I s s a l C
G d n a F , E
0 - 0 2 1 7 2
0 - 1 2 1 7 2
0 - 1 2 0 8 2
*Division 1 and 2.
INSTALLATION
1. Kidde-Fenwal recommends that standard 4-inch oc-
tagonal outlet boxes be used to mount detectors.
2. Attach detector to outlet box cover through a 0.875 inch
diameter hole and using two 1/2-14 NPT retainer nuts
as indicated.
3. Connect system wiring to detector per Figure 3 and ap-
plicable electrical codes.
4. Ordinary Locations: The DETECT-A-FIRE Units are
to be installed in grounded metallic junction boxes only.
They are to be secured to the boxes using two lock
nuts, one on either side of the mounting plate. DETECT-
A-FIRE Units are not to be installed in non-metallic junc-
tion boxes.
5. Hazardous Locations: For Class I, Division 1 and 2
locations, install the DETECT-A-FIRE Unit in a listed
explosion-proof enclosure with a minimum thread en-
gagement of five full turns. No non-conductive material
is to be placed on the threaded joint of the DETECT-A-
FIRE Unit or in the listed explosion-proof enclosure.
For Division 2 locations, assure that a protective ground
terminal is provided in the listed explosion-proof enclo-
sure when flexible metal conduit is used.
6. Do not exceed a maximum torque without thread lubri-
cant of 20 foot-pounds (27.1 Newton Meters).
Series 28000 units are similar to Series 27100 units except
they have two 1/2-14 NPT threads for mounting.
The unit may be mounted as described above or may be
threaded into a 1/2-14 NPT tapped hole in the vessel wall or
threaded into a coupling brazed or welded to the vessel wall.
FIELD WIRING REQUIREMENT
Field wiring must be capable of withstanding the maximum
anticipated ambient temperature in the application.
FUNCTIONAL TEST
When used with automatic fire extinguishing systems first
disconnect the initiator/solenoid leads from the panel and
connect a 24 VDC bulb to initiator terminals in the control
unit. Heat the D-A-F units with a heat lamp or other conve-
nient source. When the bulb in the control unit changes state,
remove heat source and allow D-A-F unit to cool. Reset con-
trol unit. Test lamp must change state and stay changed
after system is reset. Do not reconnect initiator/solenoid leads
until all D-A-F units have cooled below set point as indicated
by test lamp. When D-A-F units are used in other types of
systems, disconnect them from the system, connect a 24
VDC lamp and power source in series with the D-A-F units
and test with heat source as above. Make sure that contacts
have reset to normal condition before reconnecting to sys-
tem circuit.
Figure 1 Figure 2
3
WARNING
!
1. In order to function properly, the sensing shell of the unit must remain free from paint, grease, oil, etc. Should such a
build up occur, do not, under any circumstances, attempt to remove it. Replace the unit.
2. Detectors mounted in an area subject to physical abuse or damage, other than above, must be suitably protected
without obstructing the thermal air path to the unit.
3. Do not install the unit where the shell would be physically damaged by sand, grain, rocks, etc.
4. Do not overtorque the unit when installing.
5. Any detector that has been abused or damaged must be replaced.
6. Consult the factory for special precautions necessary for outdoor use or moist environments.
ANY OF THE ABOVE COULD CHANGE THE FACTORY TEMPERATURE SETTING, WHICH MAY RESULT IN PROP-
ERTY DAMAGE AND/ OR PERSONAL INJURY OR DEATH.
IT IS POSSIBLE FOR A UNIT TO HAVE BEEN ABUSED OR DAMAGED AND NOT DISPLAY ANY OUTWARD INDICA-
TION OF THE DAMAGE. ALL UNITS SHOULD BE TESTED PERIODICALLY IN ACCORDANCE WITH NATIONAL FIRE
PROTECTION ASSOCIATION REQUIREMENTS (72E) OR THE AGENCY HAVING LOCAL JURISDICTION.
These instructions do not purport to cover all the details or variations in the equipment described, nor do they provide for every possible
contingency to be met in connection with installation, operation and maintenance. All specifications subject to change without notice. Should
further information be desired or should particular problems arise which are not covered sufficiently for the purchasers purpose, the matter
should be referred to KIDDE-FENWAL, Inc., Ashland, Massachusetts.
Figure 3. System Wiring
Typical Fire Alarm System Method
Typical Security System Method
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes no
responsibility for the product's suitability for a particular application. The product must be prop-
erly applied to work correctly.
If you need more information on this product, or if you have a particular problem or question,
contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000
R
KIDDE-FENWAL, INC.
400 MAIN STREET, ASHLAND, MA 01721
TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
12.01.D 8/99 1999 Kidde-Fenwal, Inc. Printed in U.S.A. CP