2363 2021 Ti en Smart Safety Link
2363 2021 Ti en Smart Safety Link
2363 2021 Ti en Smart Safety Link
Date: 03.05.2021
Technical Information Official: Marier
Department: BT-FIR/MKP3
Short Description: Use relay contacts to interface with PRAESENSA voice alarm systems
Affected Products (details) CTN SAP no. Aff. version New version
PRAESENSA PRA-SCL F.01U.325.042 n.a. n.a.
AVENAR panel 8000 FPE-8000-PPC F.01U.352.441 n.a. n.a.
AVENAR panel 2000 FPE-2000-PPC F.01U.352.443 n.a. n.a.
FPA-5000 MPC-XXXX-C F.01U.169.501 n.a. n.a.
MPC-XXXX-B F.01U.074.867 n.a. n.a.
FPA-1200 FPA-1200-MPC-C F.01U.169.502 n.a. n.a.
FPA-1200-MPC F.01U.090.045 n.a. n.a.
Action Plan
Inform customers
Arrange re-work of stock (CSO)
Arrange re-work of stock (customer)
Arrange re-work of installed products
See detailed actions on following pages
Print out of this template is not subject of the updating service. Only the version in the Intranet is always up to date.
Removed features:
Solved Issues:
Notes:
Use relay contacts to interface FPA and AVENAR fire panels with PRAESENSA voice alarm systems.
An Ethernet connection between a fire panel and PRAESENSA can currently disrupt the functional
behavior and may lead to fire alarms that are not transmitted.
Smart Safety Link to Praesideo, PAVIRO and Plena voice alarm systems are released solutions and still
allowed to be installed in the field.