Nec 220.84

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 2

1

516 x 3 x 12
2
12 x 2 x 1500
3
1.5KVA X 12 Units x
B
Dish Washer = 1.5 KVA
E.W.H = 4.5KVA
Range = 8KVA
Ref = 0.5KVA
1.5KVA + 4.5 + 8 + 0.5
14.5KVA x 12 = 174KVA
2.4KVA + 3.5KVA x 12
72.576KVA + 3.5KVA x 12
317.37KVA
317.37KVA x 0.041
Damand Load = 130.12KVA
130.12 X 2
260.24KVA
NEC 220.52B
G. Light & Recep (units)
Small Appliances CKT.
Laundry circuit
NEC 220.12
NEC 220.52A
Appliance Cal Load
AC Load
Total Connected load
NEC 220.84
For BLD - A (Complete)
1
300 = 30,000 VA
2
24 x 2 x 1500 = 72,000 VA
3
1500 X 28 + 2 x 6500 = 55,000 VA
4
1 + 2 + 3 = 157,000 VA
5
1500 + 4500 + 500 + 8000 = 14,500 VA
14500 x 24 = 348,000 VA
6
2400 x 24 = 57,600 VA
7
4 + 5 + 6 = 562,600 VA
562,600 x 0.35 = 196,910 VA
196,910 x 2 = 393,820 VA
Total General Lighting,Small Appliance & Laundry Loads
RESIDENTIAL BUILDING
( MULTI FAMILY DWELLING )
Electric Range,Electric Water Heater
Dish Washer & Refrigerator
Small Appliance Branch-Circuits
Laundry Branch circuit
NEC 220.52(B)
Minimum of two 20A branch-circuit
General Light & Receptacle Load
Sq.ft @ 3VA Per Sq.ft (24 Units)
NEC 220.12
NEC 220.52(A)
Apply Demand Factor Using
NEC 220.84
Total Demand Load of
Building B is
Demand Load is
Air Conditioning Load
Total Connected Load