Three-Phase A.C. Circuits
Three-Phase A.C. Circuits
CH003-H8747.indd 85
85
4/10/2008 3:24:46 PM
86
In any rotating a.c. machine, the rotating part is called the rotor, and
the stationary part is called the stator. Thus, in an alternator, the field
system is contained in the rotor. The winding in which the emf is
generated is contained in the stator. The reasons for this are as follows:
In this context, the term field refers to the magnetic field. This field is normally produced
by passing d.c. current through the rotor winding. Since the winding is rotated, the
current is passed to it via copper slip-rings on the shaft. The external d.c. supply is
connected to the slip-rings by a pair of carbon brushes.
G
E
stator
rotor
F
H
Fig. 3.1
CH003-H8747.indd 86
4/10/2008 3:24:50 PM
87
around the inner periphery of the stator. The two ends of this winding
are then led out to a terminal block on the casing. The rotor winding
is also mounted in slots, around the circumference of the rotor. This
figure is used to illustrate the principle. A practical machine would
have many more conductors and slots.
Since the conductors of the stator winding are spread around the whole
of the slots, it is known as a distributed winding. As the rotor field
sweeps past these conductors an emf is induced in each of them in turn.
These individual emfs reach their maximum values only at the instant
that the rotating field cuts them at 90. Also, since the slots have an
angular displacement between them, then the conductor emfs will be
out of phase with each other by this same angle. In Fig. 3.1 there are a
total of twelve conductors, so this phase difference must be 30. The
total stator winding emf will therefore not be the arithmetic sum of the
conductor emfs, but will be the phasor sum, as shown in Fig. 3.2. The
ratio of the phasor sum to the arithmetic sum is called the distribution
factor. For the case shown (a fully distributed winding) the distribution
factor is 0.644.
F
E
30
G
D
H
K
B C
M
A
AB, CD etc. are conductor (coil) emfs.
AM is the phasor sum
Fig. 3.2
Now, if all of the stator conductors could be placed into a single pair
of slots, opposite to each other, then the induced emfs would all be
in phase. Hence the phasor and arithmetic sums would be the same,
yielding a distribution factor of unity. This is not a practical solution.
However, if the conductors are concentrated so as to occupy only one
third of the available stator slots, then the distribution factor becomes
0.966. In a practical single-phase alternator, the stator winding is
distributed over two thirds of the slots.
Let us return to the option of using only one third of the slots. We will
now have the space to put two more identical windings into the stator.
Each of the three windings could be kept electrically separate, with
their own pairs of terminals. We would then have three separate singlephase alternators in the same space as the original. Each of these would
CH003-H8747.indd 87
4/10/2008 3:24:50 PM
88
also have a good distribution factor of 0.966. The three winding emfs
will of course be mutually out of phase with each other by 120, since
each whole winding will occupy 120 of stator space. What we now
have is the basis of a three-phase alternator.
The term three-phase alternator is in some ways slightly misleading.
What we have, in effect, are three identical single-phase alternators
contained in the one machine. The three stator windings are brought
out to their own separate pairs of terminals on the stator casing. These
stator windings are referred to as phase windings, or phases. They
are identified by the colours red, yellow and blue. Thus we have the
red, yellow and blue phases. The circuit representation for the stator
winding of such a machine is shown in Fig. 3.3. In this figure, the three
phase windings are shown connected, each one to its own separate
load. This arrangement is known as a three-phase, six-wire system.
However, three-phase alternators are rarely connected in this way.
LOAD 1
LOAD 2
LOAD 3
Fig. 3.3
VY
VR
180
VB
360 (deg)
Fig. 3.4
CH003-H8747.indd 88
4/10/2008 3:24:51 PM
89
VB
VR
VY
Fig. 3.5
VR
VB
VY
Fig. 3.6
CH003-H8747.indd 89
4/10/2008 3:24:51 PM
90
of the three phases together. For example, either the three F ends or
the three S ends are commoned. This form of connection is shown
in Fig. 3.7, and is known as a star or Y connection. With the resulting
4-wire system, the three loads also are connected in star configuration.
The three outer wires are called the lines, and the common wire in the
centre is called the neutral.
F F
F
S
S
Fig. 3.7
If the three loads were identical in every way (same impedance and
phase angle), then the currents flowing in the three lines would be
identical. If the waveform and/or phasor diagrams for these currents
were drawn, they would be identical in form to Figs. 3.4 and 3.5. These
three currents meet at the star point of the load. The resultant current
returning down the neutral wire would therefore be zero. The load in
this case is known as a balanced load, and the neutral is not strictly
necessary. However it is difficult, in practice, to ensure that each of
the three loads are exactly balanced. For this reason the neutral is left
in place. Also, since it has to carry only the relatively small out-ofbalance current, it is made half the cross-sectional area of the lines.
Let us now consider one of the advantages of this system compared
with both a single-phase system, and the three-phase 6-wire system.
Suppose that three identical loads are to be supplied with 200 A each.
The two lines from a single-phase alternator would have to carry the
total 600 A required. If a 3-phase, 6-wire system was used, then each
line would have to carry only 200 A. Thus, the conductor csa would
only need to be 1/3 that for the single-phase system, but of course,
being six lines would entail using the same total amount of conductor
material. If a 4-wire, 3-phase system is used there will be a saving on
conductor costs in the ratio of 3.5:6 (the 0.5 being due to the neutral).
If the power has to be sent over long transmission lines, such as the
National Grid System, then the 3-phase, 4-wire system yields an
enormous saving in cable costs. This is one of the reasons why the
power generating companies use three-phase, star-connected generators
to supply the grid system.
CH003-H8747.indd 90
4/10/2008 3:24:51 PM
3.3
91
IL
Iph
Vph
IN
VL
VL
Vph
Iph
B
Iph
Vph
VL
IL
Y
Fig. 3.8
VYN
VBN
B
30
0
30
A
VRN
VYN
Fig. 3.9
CH003-H8747.indd 91
4/10/2008 3:24:51 PM
92
30
60
Fig. 3.10
Hence,
OB
3
OA
2
3 .OA
2
but OC 2 OB 3 .OA
so OB
(3.1)
The complete phasor diagram for the line and phase voltages for a star
connection is shown in Fig. 3.11. Also, considering the circuit diagram
of Fig. 3.8, the line and phase currents must be the same.
Hence, in star configuration, I L I ph
(3.2)
CH003-H8747.indd 92
4/10/2008 3:24:52 PM
VBN
93
VRY
VBR
30
30
VRN
30
VYN
VYB
Fig. 3.11
A 415 V, 50 Hz, 3-phase supply is connected to a star-connected balanced load. Each phase of the load
consists of a resistance of 25 and inductance 0.1 H, connected in series. Calculate (a) phase voltage,
(b) the line current drawn from the supply, and (c) the power dissipated.
A
Whenever a three-phase supply is specified, the voltage quoted is always the
line voltage. Also, since we are dealing with a balanced load, then it is necessary
only to calculate values for one phase of the load. The figures for the other two
phases and lines will be identical to these.
VL 415 V; f 50 Hz; Rph 25 ; Lph 0.1 H
IL Iph
25
Vph
0.1 H
VL
Fig. 3.12
CH003-H8747.indd 93
4/10/2008 3:24:52 PM
94
(a)
VL
415
3
3
so Vph 240 V Ans
Vph
(b) Since it is possible to determine the impedance of a phase of the load, and
we now know the phase voltage, then the phase current may be calculated:
X L 2fL ohm 2 50 0.1
hence X L 31.42
2 X 2 ohm 252 3 1 . 422
Z ph Rph
L
Z ph 40.15
I ph
Vph
Z ph
amp
240
40.15
so I ph 5.98 A
In a star-connected circuit, IL IPh
therefore IL 5.98 A Ans
2 R
The power in one phase, Pph I ph
ph watt
5.982 25
Pph 893.29 W
and since there are three phases, then the total power is:
P 3 Pph watt 3 893.29
hence P 2.68 kW Ans
3.4
S
Iph
VL
F IL
Iph
S
F
S
IL
Fig. 3.13
CH003-H8747.indd 94
4/10/2008 3:24:53 PM
3.5
95
(3.3)
It is also apparent that the current along each line is the phasor
difference of a pair of phase currents. The three phase currents are
mutually displaced by 120, and the phasor diagram for these is shown
in Fig. 3.14. Using exactly the same geometrical technique as that for
the phase and line voltages in the star connection, it can be shown that:
I L 3 I ph
(3.4)
IB(ph)
120
120
IR(ph)
120
IY(ph)
Fig. 3.14
The phasor diagram for the phase and line currents in delta connection
is as in Fig. 3.15. Note that the provision of a neutral wire is not
applicable with a delta connection. However, provided that the load
Iph
IL
IL
30
30
Iph
30
Iph
IL
Fig. 3.15
CH003-H8747.indd 95
4/10/2008 3:24:53 PM
96
A balanced load of phase impedance 120 is connected in delta. When this load is connected to a
600 V, 50 Hz, 3-phase supply, determine (a) the phase current, and (b) the line current drawn.
A
Zph 120 ; VL 600 V; f 50 Hz
The circuit diagram is shown in Fig. 3.16.
IL
Iph
Z
120
VL Vph
600 V
Fig. 3.16
(a) In delta, Vph VL 600 V
I ph
Vph
Z ph
amp
600
120
so, I ph 5 A Ans
(b)
in delta, I L 3 I ph amp 3 5
therefore I L 8.66 A Ans
3.6
CH003-H8747.indd 96
4/10/2008 3:24:54 PM
97
VL
3
, and I ph IL
VL
3
I L cos
(3.5)
I ph
3
and substituting these values into eqn [1] will yield the same result
as shown in (3.5) above. Thus, the equation for determining power
dissipation, in both star and delta-connected loads is exactly the
same. However, the value of power dissipated by a given load when
connected in star is not the same as when it is connected in delta. This
is demonstrated in the following example.
A balanced load of phase impedance 100 and power factor 0.8 is connected (a) in star, and (b) in
delta, to a 400 V, 3-phase supply. Calculate the power dissipation in each case.
A
Zph 100 ; cos 0.8; VL 400 V
(a) the circuit diagram is shown in Fig. 3.17
IL Iph
VL
400 V
Vph
Z
100
Fig. 3.17
CH003-H8747.indd 97
4/10/2008 3:24:54 PM
98
VL
400
volt
3
3
so Vph 231 V
Vph
I L I ph
Vph
Z ph
amp
231
100
and I L 2.31 A
P 3 VL I L cos watt 3 400 2.31 0.8
therefore P 1.28 kW Ans
(b) The circuit diagram is shown in Fig. 3.18.
IL
Iph
Z
100
VL Vph
400 V
Fig. 3.18
Vph VL 400 V
I ph
Vph
Z ph
amp
400
100
so I ph 4 A
but I L 3 I ph 3 4
so I L 6.93 A
P 3 VL I L cos watt 3 400 6.93 0.8
therefore P 3.84 kW Ans
Comparing the two answers for the power dissipation in the above
example, it may be seen that:
Power in a delta-connected load is three times
that when i t is connected in star configuration.
(3.6)
A balanced star-connected load is fed from a 400 V, 50 Hz, three-phase supply. The resistance in each
phase of the load is 10 and the load draws a total power of 15 kW. Calculate (a) the line current
drawn, (b) the load power factor, and (c) the load inductance.
A
VL 400 V; f 50 Hz; R 10 ; P 15 000 W
CH003-H8747.indd 98
4/10/2008 3:24:54 PM
99
10
VL 400 V
Fig. 3.19
(a)
The power in one phase will be one third of the total power, so
P
15 000
watt
5 kW
3
3
2 R watt
but, Pph I ph
Pph
so, I L I ph
Pph
R
I L 22.36 A Ans
5000
10
P 3 VL I L cos watt
(b)
15 000
P
3 VL I L
3 400 22.36
X ph
Rph
Rph
Zph
Xph
Fig. 3.20
CH003-H8747.indd 99
4/10/2008 3:24:55 PM
100
A balanced delta-connected load takes a phase current of 15 A at a power factor of 0.7 lagging when
connected to a 115 V, 50 Hz, three-phase supply. Calculate (a) the power drawn from the supply, and
(b) the resistance in each phase of the load.
A
VL Vph 115 V; f 50 Hz; Iph 15 A; cos 0.7
IL
Iph
15 A
R
VL Vph
115 V
L
Fig. 3.21
(a)
I L 3 I ph amp 3 15
I L 25.98 A
P 3 VL I L cos watt 3 115 25.98 0.7
so P 3622.5 W Ans
(b)
P 3622.5
1207.5 W
3
3
2 R watt
and Pph I ph
Pph
so R
Pph
2
I ph
ohm
1207.5
152
R 5.37 Ans
CH003-H8747.indd 100
4/10/2008 3:24:55 PM
101
I1
I3
20:1
I2
V1
11 kV
V4
V2
V3
Z 25
cos 0.75
Fig. 3.22
A
V1 11 000 V; Np/Ns 20/1; Zph 25 ; cos 0.75
(a)
V1
11 000
3
3
V2 6.351 kV Ans
V2
V3
N
s
V2
Np
so V3
NsV2
6351
volt
20
Np
(b) In order to calculate the currents, we shall have to start with the load, and
work back through the circuit to the primary of the transformer:
I3
183.3
V4
amp
Z ph
25
I 3 7.33 A Ans
I3
7.33
3
3
I 2 4.23 A Ans
I2
N
I1
s
I2
Np
so I1
Ns I 2
4.23
amp
Np
20
CH003-H8747.indd 101
4/10/2008 3:24:55 PM
102
(c)
A
f 50 Hz; R 15 ; L 36 mH; Vph 231 V
I1
I2
V1
15
231 V
V2
R
L
36 mH
Fig. 3.23
(a) For the alternator: V1 Vph 231 V
V2 VL 3 Vph
V2 400 V
I ph I L I1
For the load:
V2 VL Vph 400 V
X L 2fL ohm 100 36 103
X L 11.31
Z ph R 2 X L2 ohm 152 11.3 12
Z ph 18.79
I ph I 2
Vph
Z ph
amp
400
18.79
I 2 21.29 A Ans
I L I1 3 I 2 3 21.29
I1 36.88 A Ans
(b) p.f. cos
R
Z
15
18.79
p.f. 0.8 lagging Ans
CH003-H8747.indd 102
4/10/2008 3:24:56 PM
(c)
103
3.8
W1
N
B
Y
Fig. 3.24
In the situation where the star point is not accessible, then an artificial
star point needs to be created. This is illustrated in Fig. 3.25, where
the value of the two additional resistors is equal to the resistance of the
wattmeter voltage coil.
In the case of an unbalanced star-connected load, one or other of the
above procedures would have to be repeated for each phase in turn.
The total power P P1 P2 P3, where P1, P2 and P3 represent the
three separate readings.
CH003-H8747.indd 103
4/10/2008 3:24:56 PM
104
W1
B
Y
Fig. 3.25
W1
B
Y
Fig. 3.26
CH003-H8747.indd 104
4/10/2008 3:24:57 PM
IR
W1
105
VRB
IB
B
VYB
IY
Y
W2
Fig. 3.27
(3.7)
CH003-H8747.indd 105
4/10/2008 3:24:57 PM
106
IB
VBN
VBR
VR
VRN
IY
(30 )
(30 )
VYN
IR
VRB
VYB
Fig. 3.28
(3.8)
P2 VL I L cos (30 )
(3.9)
From these results, and using Fig. 3.29, the following points should be
noted:
wattmeter
readings
90 30
30
90
150 (30 )
Fig. 3.29
1 If the load p.f. 0.5 (i.e. 60); both meters will give a positive
reading.
2 If the load p.f. 0.5 (i.e. 60); W1 indicates the total power,
and W2 indicates zero.
3 If the load p.f. 0.5 (i.e. 60); W2 attempts to indicate a
negative reading. In this case, the connections to the voltage coil
CH003-H8747.indd 106
4/10/2008 3:24:57 PM
107
(3.10)
The power in a 3-phase balanced load was measured, using the two-wattmeter method. The recorded
readings were 3.2 kW and 5 kW respectively. Determine the load power and power factor.
A
P1 3.2 kW; P2 5 kW
P P1 P2 watt (3.2 5) kW
therefore, P 8.2 kW Ans
P P
1
tan1 3 2
P2 P1
5 3 .2
tan1 3
5 3 .2
hence, 20.82
and p.f. cos 0.935 Ans
A 3-phase balanced load takes a line current of 24 A at a lagging power factor of 0.42, when connected
to a 415 V, 50 Hz supply. If the power dissipation is measured using the two-wattmeter method,
determine the two wattmeter readings, and the value of power dissipated. Comment on the results.
A
IL 24 A; cos 0.42; VL 415 V
cos1 0.42 65.17
P1 VL I L cos (30 ) watt
415 24 cos (35.17 )
therefore, P1 8.142 kW Ans
P2 VL I L cos (30 ) watt
415 24 cos (95.17 )
therefore, P2 896.7 W Ans
P P1 P2 watt 8142 ( 896.7)
hence, P 7.244 kW Ans
To obtain the negative reading on W2, the connections to its voltage coil must
have been reversed.
CH003-H8747.indd 107
4/10/2008 3:24:58 PM
108
A delta-connected load has a phase impedance of 100 at a phase angle of 55, and is connected to a
415 V three-phase supply. The total power consumed is measured using the two-wattmeter method.
Determine the readings on the two meters and hence calculate the power consumed.
A
Zph 100 ; 55; VL 415 V Vph
W1
IL
Zph
100
VL 415 V
VL 415 V
IL
W2
Fig. 3.30
I ph
Vph
Z ph
amp
415
4 .1 5 A
100
I L 3 I ph 3 4 .15 7 .19 A
P1 VL I L c os (30 ) watt 415 7.19 cos 25
P1 2.704 kW Ans
P2 VL I L cos (30 ) watt 415 7.19 cos 85
P2 260 W Ans
P P1 P2 watt 2704 260
P 2.964 kW Ans
CH003-H8747.indd 108
4/10/2008 3:24:58 PM
109
An unbalanced, star-connected load is supplied from a 3-phase, 415 V source. The three phase loads
are purely resistive. These loads are 25 , 30 and 40 , and are connected in the red, yellow and
blue phases respectively. Determine the value of the neutral current, and its phase angle relative to
the red phase current.
A
VL 415 V; RR 25 ; RY 30 ; RB 40
The circuit diagram is shown in Fig. 3.31.
IR
25
Vph
VL
40
IN
IY
30
Y
B
IB
Fig. 3.31
VL
415
240 V
volt
3
3
Vph
Vph
Vph
amp
IR
amp; IY
amp; I B
RR
RY
RB
Vph
240
25
I R 9.6 A
240
30
IY 8 A
240
40
IB 6 A
IB
60
60
IR
H.C.
V.C.
IY
IN
Fig. 3.32
CH003-H8747.indd 109
4/10/2008 3:24:58 PM
110
CH003-H8747.indd 110
4/10/2008 3:24:59 PM
111
Summary of Equations
Phase and line quantities:
CH003-H8747.indd 111
4/10/2008 3:24:59 PM
112
Further
Electrical
and Electronic
Prinicples
Fundamental
Electrical
and Electronic
Principles
Assignment Questions
1
CH003-H8747.indd 112
11
12
13
14
15
4/10/2008 3:24:59 PM
Fundamental ElectricalThree-Phase
and ElectronicA.C.
Principles
Circuits
113
113
Assignment 2
To measure the power in three-phase systems, using both single and twowattmeter methods.
Apparatus:
Low voltage, 50 Hz, three-phase supply
3 1 k rheostats
2 wattmeters
1 DMM
CH003-H8747.indd 113
4/10/2008 3:24:59 PM
114
Method:
1 As for Assignment 1, carefully adjust the three rheostats to the same value
(1 k).
2 Connect the circuit shown in Fig. 3.33, and measure the power in the red
and yellow phases.
W1
W2
Fig. 3.33
3 Transfer one of the wattmeters to the blue phase, and measure that power.
4 Add the three wattmeter readings to give the total power dissipation. Check
to see whether this is three times the individual phase power.
5 Switch off the power supply, and reconnect as in Fig. 3.34.
W1
R
Y
W2
Fig. 3.34
6 Record the two wattmeter readings, and check whether their sum is equal
to the total power recorded from paragraph 4 above.
7 Switch off the power supply and reconnect the circuit as in Fig. 3.35.
8 Record the two wattmeter readings.
9 Switch off the supply, and transfer one of the wattmeters to the third phase.
10 Record this reading. Add the three readings to give the total power, and
check that this is three times the phase power.
11 Switch off the supply and connect the circuit of Fig. 3.36.
12 Record the two wattmeter readings, and check that their sum equals the
total power obtained from paragraph 10 above.
CH003-H8747.indd 114
4/10/2008 3:25:00 PM
115
W1
W2
Fig. 3.35
W1
R
Y
W2
Fig. 3.36
Assignment 3
Show how the two-wattmeter method of power measurement can be
accomplished by means of a single wattmeter, together with a suitable
switching arrangement. You may either devise your own system, or discover
an existing system through library research.
CH003-H8747.indd 115
4/10/2008 3:25:00 PM
CH003-H8747.indd 116
4/10/2008 3:25:00 PM