DC Sytem 1
DC Sytem 1
DC Sytem 1
COMPONENTS OF DC
SYSTEM
BATTERY
PLANT
CHARGER/POWER
BATTERY
LOAD
(COMMUNICATION
EQUIPMENT)
COMPONENTS OF DC SYSTEM
IB
AC i/p
Battery
charger
I CH
Load
IL
I CH = I B+IL
DISCHARGING
AS A GENERAL RULE,NEVER
DISCHARGE BATTRIES BEYOND
Sp.GRAVITY < 1.170
VOLTAGE < 1.175 V
BOOST CHARGING/CONSTANT
CURRENT CHARGING
PLANTE
VRLA
NiCd
PLANTE BATTERY
1859-GADSTON PLANTE
DEVELOPED.NOW MAINLY USED
FOR STAND BY DUTY BATTERY
VOLTAGE 2V/CELL
24X2V=48V FOR COMMUNICATION
55X2= 110V FOR SUBSTATION
PLANTE BATTERY
AH CAPACITY=200 AH
CAPACITY IN AMPERE HOURS
WHENDISCHARGEDAT THE RATE OF
10 HOURS
20 A -10 HOURS 100% CAPACITY 200 Ah
40 A 5 HOURS 92% CAPACITY200 A -1 HOURS 65% CAPACITY
VRLA BATTERIES
VRLA BATTERY
VRLA BATTERY
DISADVANTAGES
BATTERY CHARGERS
CONVENTIONAL CHARGERS
THYRISTOR CONTROLED
BATTERY CHARGER
BATTERY VRLA
MAINTENANCE OF BATTERY
CHECKING
STATE OF CHARGE OF BATTERY
CONDITION OF INDIVIDUAL CELL
INCREASE OR DECREASE IN
RESISTANCEIN THE SERIES CIRCUIT
CARRYING OUT REMEDIAL
MEASURES
BATTERY CHARGER
FILLING OF ACID
FIRST CHARGE
FIRST CHARGE
SECOND PORTION
SECOND PORTION OF CHARGE MUST BE GIVEN NOT
LESS THAN 30 HOURS OF FINISHING RATE TILL THE
COMPLETION OF SIGNS OF CHARGING ARE OBSERVED
SIGNS OF CHARGING
1.SPECIFIC GRAVITY- REACH A MAXIMUM VALUE AND
SHOULD BE CONSTANT FOR 3 COSECUTIVE READINGS 3
HOURS
2.VOLTAGE- WILL RISE TO MAXIMUM AND CONSTANT
FOR SAME-SPECIFIC GRAVITY- ADJUST THE SPECIFIC
GRAVITY
CHARGER REQUIREMENTS
VOLTAGE REGULATION +_ 1 %
AUTO FLOAT TO BOOST CHANGE OVER FACILITY AT
a) FLOAT TO BOOST: AT 5% OF RATED Ah
CAPACITY IN AMPS
b) BOOST TO FLOAT: AT 3% OF RATED Ah
CAPACITY IN AMPS
300 Ah I> 15 FLOAT TO BOOST
TEMPERATURE COMPENSATION -3mV/ CELL C RISE
IN TEMPERATURE ABOVE 27 C
24 CELLS = 72 mV c
FRESHENING CHARGE
INTERVALS
AVERAGE
ABIENT
TEMP C
INTERVAL
(MONTHS)
<27
27-32
32-37
37-42
42-47
06
4.5
03
2.25
1.5
TEST DISCHARGE
OPERATION
MODE
15C-32C
24
CELLS
FLOAT
54V
BOOST
55.2V
ABOVE 32C
CURRE
NT
LIMIT(A
MPS)
THANK YOU