1894 N2XH
1894 N2XH
1894 N2XH
N2XH
Version 1/2009
Halogen-Free Cable
with Improved Fire Behaviour
Application:
Safety cables are used in all locations where a high degree of protection
against fire and fire-damage has to be provided for human life and equipment
and are, therefore, subject to high security requirements. These cables may be
used indoors and outdoors. They may not be installed directly into the ground
and into the water. This cable conforms to Safety Class II standards.
Construction:
According to:
Technical data:
Nominal voltage Uo/U
Test voltage
Temperature range
Operating temperature
Short circuit time
Bending radius
Flammability
[V]
[V]AC
in motion
short circuit
max.
single core style
multi core style
standard
C
[sec]
x diameter
x diameter
Number of cores
and nominal
cross section
mm
1 x 6 RE
1 x 16 RM
1 x 25 RM
1 x 35 RM
1 x 50 RM
1 x 70 RM
1 x 95 RM
1 x 120 RM
1 x 150 RM
1 x 185 RM
1 x 240 RM
1 x 300 RM
Copper
figure
kg/km
Overall
diameter
appr.
mm
60
160
250
350
500
700
950
1.200
1.500
1.850
2.400
3.000
7,8
9,8
11,4
12,6
13,8
15,7
17,4
19,0
20,9
23,1
25,6
28,1
Calorific
potential
kWh / m
Weight
appr.
kg / km
0,33
0,46
0,62
0,71
0,82
1,00
1,14
1,32
1,59
1,91
2,24
2,58
112
226
327
429
555
765
1.024
1.263
1.542
1.918
2.466
3.065
MEINHART KABEL STERREICH GMBH , MEINHART, MEINHART LAN and MEINHART-Logo are registered trademarks of MEINHART Kabel sterreich GmbH
Meinhart Kabel sterreich GmbH, Westbahnstrae 6, A- 4490 St. Florian, Tel. +43 (0)7224 690-0, Fax +43 (0)7224 690-610INTERNET: HTTP://WWW.MEINHART.AT,
UID-NR.: ATU63684739, FN: 299994v LANDESGERICHT STEYR
The above values correspond to the manufacturers specifications and are not guaranteed..
Datasheet
Version 1/2009
Number of cores
and nominal
cross section
mm
2 x 1,5 RE
2 x 2,5 RE
3 x 1,5 RE
3 x 2,5 RE
3x 4
RE
3x 6
RE
3 x 10
RE
3 x 16
RM
3 x 25
RM
3 x 35
RM
3 x 50
RM
3 x 50/25 SM/RM
3 x 70/35 SM/RM
3 x 95/50 SM
3 x 120/70 RM
3 x 150/70 RM
3 x 185/95 RM
3 x 240/120 RM
4 x 1,5 RE
4 x 2,5 RE
4x 4
RE
4x 6
RE
4 x 10
RE
4 x 16
RM
4 x 25
RM
4 x 35
RM
4 x 50
SM
4 x 70
SM
4 x 95
SM
4 x 120
SM
4 x 150
SM
5 x 1,5 RE
5 x 2,5 RE
5x 4
RE
5x 6
RE
5 x 10
RE
5 x 16
RE
5 x 16
RM
5 x 25
RM
5 x 35
RM
7 x 1,5 RE
12 x 1,5 RE
19 x 1,5 RE
24 x 1,5 RE
30 x 1,5 RE
7 x 2,5 RE
12 x 2,5 RE
19 x 2,5 RE
24 x 2,5 RE
7x 4
RE
Copper
figure
kg/km
30
50
45
75
120
180
300
480
750
1.050
1.500
1.750
2.450
3.216
4.300
5.200
6.500
8.400
60
100
160
240
400
640
1.000
1.400
2.000
2.800
3.800
4.800
6.000
75
125
200
300
500
800
800
1.250
1.750
105
180
285
360
450
175
300
475
600
280
Overall
diameter
appr.
mm
9,3
10,1
9,7
10,6
11,7
12,8
14,9
17,7
24,0
27,0
29,0
32,0
37,0
41,0
45,0
49,0
55,0
62,0
10,4
11,4
12,6
13,8
16,3
19,2
23,9
26,7
29,1
32,2
37,2
40,8
50,0
11,2
12,3
13,7
15,4
17,8
21,6
21,6
27,0
37,0
12,0
16,0
18,6
22,2
24,0
15,0
19,0
22,0
25,0
14,9
Calorific
potential
kWh / m
0,45
0,52
0,51
0,59
0,70
0,80
1,02
1,36
2,25
2,56
3,19
3,53
4,31
5,58
6,58
7,64
0,60
0,69
0,84
0,95
1,26
1,63
2,48
2,93
3,76
4,55
5,72
6,36
7,14
0,71
0,84
1,00
1,21
1,52
2,17
2,17
3,14
3,95
0,80
1,29
1,80
2,35
2,72
1,31
2,00
2,69
3,28
1,48
Weight
appr.
kg / km
125
158
142
184
247
322
480
732
1.200
1.600
1.800
2.200
2.950
3.900
4.800
5.750
7.200
9.150
166
220
298
391
599
908
1.413
1.863
2.362
3.151
4.339
5.332
6.350
195
260
357
486
723
1.138
1.138
1.420
2.400
239
395
557
736
900
400
600
840
1.050
457
MEINHART KABEL STERREICH GMBH , MEINHART, MEINHART LAN and MEINHART-Logo are registered trademarks of MEINHART Kabel sterreich GmbH
Meinhart Kabel sterreich GmbH, Westbahnstrae 6, A- 4490 St. Florian, Tel. +43 (0)7224 690-0, Fax +43 (0)7224 690-610INTERNET: HTTP://WWW.MEINHART.AT,
UID-NR.: ATU63684739, FN: 299994v LANDESGERICHT STEYR
The above values correspond to the manufacturers specifications and are not guaranteed..