Cat. 6A F/Utp Cable For Local Area Networks 4 Pairs and 2 X 4 Pairs

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

87045 LIMOGES Cedex

Telephone: (+33) 05 55 06 87 87 - Fax: (+33) 05 55 06 88 88


1/2
Technical data sheet: F00989EN/01 Updated on: 03/03/2011 Created on: 28/09/2009
3. MARKING OF LEGRAND CABLES
- Legrand
- Catalogue number
- Number of pairs
- Gauge
- Type
- Impedance
- Type of sleeve
- Category
- Conformity to standards
- VPN/NVP
- Batch number
- Measurement (remaining length)
4. PERFORMANCE AT 500 MHZ (standard EIA/TIA 568-C.2)
Maximum attenuation (dB/100 m): ...............45.3
Minimum NEXT (dB): ...................................33.8
PS NEXT (dB): .............................................31.8
ACRF (dB / 100 m): .......................................13.8
PS ACRF (dB / 100 m): .................................10.8
Return Loss (dB): .........................................15.2
1. USE
Cat. 6A cables with 4 pairs and 2 x 4 twisted pairs, 100 ohms very
high speed, for horizontal floor or backbone distribution. These cables
enable the use of protocols supported by Class EA for 10G Base-T
applications. They are characterised up to 500 MHz.
2. DESCRIPTION

1. Conductor: Bare solid copper, 23 AWG


2. Type of insulation: PE with low dielectric loss
3. Separator: Specially designed to optimise NEXT
performance
4. Tape: Synthetic and water-repellent; ensures stability
of the structure and performance after laying
5. Screen: Aluminium/polyester; ensures optimum ANEXT
performance
6. Continuity: Tinned copper wire; for earthing on 9-pin
connector
7. Type of sleeve: Low smoke zero halogen flame retardant
material
Note:
The conductive part of the shielding is inside (wire side).
Catalogue number: 327 78/328 78
Cat. 6A F/UTP cable for local area networks
4 pairs and 2 x 4 pairs
2/2
Technical data sheet: F00989EN/01 Updated on: 03/03/2011 Created on: 28/09/2009
7. ORDERING INFORMATION
Catalogue number 327 78/328 78
Type F/UTP
Colour Yellow RAL 1018
Pack (m) 500
Packaging Reel
8. ENVIRONMENTAL FEATURES
Storage and transport temperature: 0 to + 50C
Usage temperature: 20 to + 60C
Fire resistance: IEC 60332-1, UL VW-1
9. STANDARDS AND APPROVALS
Cat. 6A, 500 MHz
EIA/TIA 568-C.2
EN 50173
EN 50288-2.1
IEC 11801
IEC 61156-5
5. TECHNICAL AND MECHANICAL FEATURES
Catalogue Number 032778 032878
Type F/UTP F/UTP
Type of sleeve LSOH LSOH
Number of pairs 4 2 x 4
Assembly Pairs Pairs
Diameter over insulation (mm) 1.16 0.05 1.16 0.05
Cable diameter (mm) 7.3 0.3
Weight of cable (kg/km) 51 57
Min. bending radius when laying (mm) 60 60
AWG gauge 23 23
6. ELECTRICAL FEATURES AT 20C
Catalogue number 327 78 328 78
Type U / UTP F / UTP
Maximum linear resistance of the cable
(ohm/km)
95 * 95 *
DC dielectric strength
1 kV/
1 min *
1 kV/
1 min *
Minimum insulation resistance (Mohm.km)
5000 5000
Minimum propagation speed (marked on
cable)
> 66% > 66%
Characteristic impedance from 1 to 100
MHz
100
15%
100
15%
* According to standard IEC 61156-5