Segment Protector
Segment Protector
Assembly
Features
4 ... 12 outputs Ex ic, Ex nL (FISCO or Entity) or nonincendive (Div 2)
Short circuit current limitation per output
Segment Protector in Zone 2/Div. 2
Instruments in Zone 2/Div. 2 or Zone 1/Div. 1
For FOUNDATION Fieldbus H1 and PROFIBUS PA
Power, Com, and Error LEDs
T-connector for easy installation and maintenance
Test points for easy troubleshooting
Function
The R2 Segment Protector, a device coupler for DIN rail
installation, connects 4 ... 12 instruments located in Zone
2/Div. 2. to the segment with intrinsic safety (Ex ic), energy
limitation (Ex nL). Device connections in Zone 1/Div. 1 require
additional methods of ignition protection. Short circuit
protection at each spur ensures proper operation of the
segment during faults or hot work at the spur.
The T-connector at the trunk allows for exchange of a
Segment Protector with no effect on the remaining segment.
The terminator is mounted at the 'T' and removed for network
extensions ensuring proper termination.
All plugs feature retaining screws. LEDs and test access
points simplify troubleshooting and help to decrease repair
time. Any grounding and shielding concept is possible based
on FieldConnex enclosure solutions.
R
+-S
+-S
Spur
+-S
Spur
S-+
Spur
Trunk,
Ex nA
non-arcing
S-+
Spur
t48119_eng.xml
Connection
Spur 1 ... n
Ex ic, Ex nL
Zone 2/Div. 2
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group
USA: +1 330 486 0002
Germany: +49 621 776 2222
www.pepperl-fuchs.com
pa-info@us.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com
Technical data
Fieldbus interface
Main cable (Trunk)
Rated voltage
9 ... 31 V DC
Rated current
4.5 A
Outputs
Number of outputs
Rated voltage
31 V
Rated current
43 mA
Short-circuit current
max. 58 mA
1.3 V
0V
Terminating resistor
Surge protection
Indicators/operating means
LED ERR
red: short-circuit
LED PWR
LED COM
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC
EN 61326-1:2006
Standard conformity
Electromagnetic compatibility
NE 21:2006
Protection degree
IEC 60529
Fieldbus standard
IEC 61158-2
Shock resistance
EN 60068-2-27
Vibration resistance
EN 60068-2-6
Ambient conditions
Ambient temperature
Storage temperature
Relative humidity
< 95 % non-condensing
Shock resistance
15 g 11 ms
Vibration resistance
1 g , 10 ... 150 Hz
Corrosion resistance
Mechanical specifications
Connection type
Core cross-section
Housing material
Polycarbonate
Housing width
Housing height
Housing depth
Protection degree
IP20
Mass
Mounting
t48119_eng.xml
Outputs
Voltage
Uo
Current
Io
Co
Inductance
Capacitance
Statement of conformity
Lo
Directive conformity
Directive 94/9/EC
International approvals
FM approval
Control drawing
Approved for
UL approval
Approved for
Technical data
IECEx approval
IECEx 11.0011 X
Approved for
DNV A-10798
General information
Supplementary information
Dimensions
_9
10
11
12
PWR
COM
77 (3")
_
6
Segment Protector
_
Trunk
PEPPERL+FUCHS
37 (1.5")
42 (1.7")
60 (2.4")
all dimensions in millimeters (mm) and inch (") without tolerance indication
Description:
1
2
3
4
5
6
7
t48119_eng.xml
Installation note
see manual
*-N4
4
93 mm (3.7")
130 g
max. 8 mA
248 mW**
*-N6
6
121 mm (4.7")
180 g
max. 8 mA
248 mW**
*-N8
8
148 mm (5.8")
230 g
max. 8 mA
248 mW**
*-N10
10
177 mm (7")
280 g
max. 10 mA
310 mW**
*-N12
12
205 mm (8")
330 g
max. 10 mA
310 mW**
Technical data
Accessories
Fieldbus plug sockets with test points TP-CON.3, (packaging unit = 4 pieces)
One plug per output comes with the Segment Protector R2-SP*
t48119_eng.xml