Safe Ring Switchgear Test: A. Mechanical Check and Visual Inspection
Safe Ring Switchgear Test: A. Mechanical Check and Visual Inspection
Safe Ring Switchgear Test: A. Mechanical Check and Visual Inspection
CO
CUSTOMER
ASTOON HOSPITAL
SWGR NAME
PROJECT
SWGR NO.
PLANET NO.
Main Substation
CUBICLE TYPE
SAFE RMU
SAFE RING
Item
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
Description
Checked
TEST VALUE ()
RED - GND
YELLOW - GND
BLUE - GND
RED YELLOW
RED BLUE
YELLOW BLUE
1.054 T
1.173 T
1.183 T
7.09 T
6.07 T
8.44 T
ABB
NAME
SIGN
DATE
23/01/2015
ASTOON HOSPITAL
NAME
SIGN
DATE
:
Page 1 of 2
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
13.8kV
SERVICE.CO
CUSTOMER
ASTOON HOSPITAL
SWGR NAME
PROJECT
SWGR NO.
PLANET NO.
Main Substation
CUBICLE TYPE
MEASURED RESISTANCE()
480
300
370
PHASE
R
Y
B
F. REMARKS
SIGN
DATE
SAFE RING
REMARKS
OK
OK
OK
HI POT TEST FOR THIS TYPE OF SAFE RING UNIT IS N/A (AS PER ABB FACTORY )
INFORMATION).
ABB
NAME
SAFE RMU
23/01/2015
ASTOON HOSPITAL
NAME
SIGN
DATE
:
Page 2 of 2
13.8kV