CH 11 - Generator Protection PDF
CH 11 - Generator Protection PDF
Generator Protection
Introduction
Device Numbers
Symmetrical Components
Fault Current Behavior
Generator Grounding
Stator Phase Fault (87G)
Field Ground Fault (64F)
Stator Ground Fault (87N, 51N, 59N, 27-3N)
Generator Protection
Generator Protection
63
49
25
G
51N
64F
51
60
87G
REG
62
47
27
81U
59
81O
32-1 32-2
59N
87T
24
40
51V
51
50
IE
46
273N
51GN
Generator Protection
Generator Protection
Generator Protection
Symmetrical Components
Positive Sequence
Negative Sequence
A set of three phasors that have the same magnitude, are equally
displaced from each other by 120, and have the same phase
sequence as the system under study (ex ABC)
A set of three phasors that have the same magnitude, are equally
displaced from each other by 120, and have the opposite phase
sequence as the system under study (ex ACB)
Zero Sequence
Symmetrical Components
Symmetrical Components
Symmetrical Components
Symmetrical Components
Symmetrical Components
Symmetrical Components
Example Problem
One conductor of a three phase line is
open. The current flowing to the delta
connected load thru line a is 10A. With
the current in line a as reference and
assuming that line c is open, find the
symmetrical components of the line
currents.
Symmetrical Components
Example Problem
Ia = 10/0 A, Ib = 10/180 A, Ic = 0 A
Ia0 = (1/3)(Ia + Ib + Ic )
Ia1 = (1/3)(Ia + Ib + 2 Ic )
Ia2 = (1/3)(Ia + 2 Ib + Ic )
Symmetrical Components
Example Problem
Ib0 = 0
Ib1 = 5.78 /-150
Ib2 = 5.78 /150
Ic0 = 0
Ic1 = 5.78 /90
Ic2 = 5.78 /-90
Symmetrical Components
Example Problem
Symmetrical Components
Example Problem
Note: the components Ic1 and Ic2 have
definite values although line c is open and
can carry no net current. As expected, the
sum of these currents is zero.
The sum of the currents in line a is 10/0
The sum of the currents in line b is 10/180
Symmetrical Components
Symmetrical Components
Symmetrical Components
Symmetrical Components
Symmetrical Components
Max DC Offset
No DC Offset
Generator Grounding
Generator Grounding
Low Impedance Grounding
Single phase to ground fault current between 200A and 150%
High Impedance Grounding
Single phase to ground fault current between 5 and 20A
EB
ZA
ZT
ZB
Generator
Transformer
System
+X
EA/EB>1
EA/EB=1
ZB
Q
EA/EB<1
ZT
-R
+R
ZA
A
-X
B
X
System
R
Trans
P
Gen X'd
A
B
Element Element
Pickup Pickup
Blinder
Elements
Mho
Element
50 (3-phase)
81U
62
60
50
60
81U
86
0.5sec Pickup
0.1sec Dropout
62
86
-DC
60
To
Protective
Relays
To
Excitation
Controller
21
51V
Pickup Inhibit/Enable
100%
Inhibit
25%
25%
100%
80%
100%
Conclusion
Generators must be protected from electrical faults,
mechanical problem and adverse system conditions
Some faults require immediate attention (shutdown) while
others just require alarming or transfer to redundant
controllers
Design of these systems requires extensive understanding
of generator protection
Further study IEEE C37.102 Guide for AC Generator
Protective Relaying