Professional Documents
Culture Documents
Commissioning of DAVR
Commissioning of DAVR
DAVR
1) Digital Automatic Voltage Regulator (DAVR) is used to Regulate the
Terminal Voltage of Generator under different loading conditions and
fault conditions as per the desired value, which is fixed by the
operator.
3) Fault into DAVR can also lead to the Tripping of the unit.
Types of Excitation System
Body Earthing
2) Zero Volt Earthing: This is the earthing of zero volt of 24V supply, generated
inside by UN0664 module. It is necessary to earth, in order to maintain a 24 V
supply, which is used for electronic modules.
Use Colour coded cables for CT & PT, AC/DC Power Supplies,
PMG & Exciter Cables.
Multiple cores can be used for CT Connections.
Size of the cable should be appropriately selected.
Power Cables & Signal Cables should be routed via separate
cable trays.
For copper cables, use copper lugs only.
Correct tool should be used for specific jobs.
Screen cables to be earthed at one end only.
2.2) Cabling & Termination……….
If these settings are not done as test report, the module may show fail
status or may not function properly.
4) Power Supplies Checking
Do not switch on any power supply, without checking for proper polarity, magnitude and short
circuit.
Record should be maintain, for different voltage levels, calibrations done, if any.
Ensure software settings are correctly feed into the UN0660 for
different functions. These parameters to be entered through micro-
terminal.
The Generator Voltage calibrations can be done by adjusting pots Ur, Us, Ut at the front
plate of UN0661.
With this calibrations, the Micro-Terminal should read Uact. and Igac as 100%.
Check in both the channels the computation of all other signals in Micro-Terminal such
as
Active Power (P)
Reactive Power (Q)
Power Factor (Cos phi)
Load Angle (Dact.)
8) Check all the External Wiring.
TG Panels for Speed >90% & Auto Synchroniser Raise / Lower Commands.
Connect Load Across AVR output terminal eg:- bulb load, heater load or
rheostat.
Ensure correct phase sequence of input supply connected at PMG terminals, the
magnitude of input supply should not be more than rated PMG voltage.
Ensure Usync LED is not glowing and measure Ur, Us, Ut socket voltage at
UN0663 modules.
Tabulate the Uc, AVR output and If at shunt, micro-terminal and HMI.
For a 3-Phase Thyristor Rectifier Bridge, the Output DC Voltage will be:
If we know the Firing Angle, then Output DC Voltage can be verified with the
above formula, for the corresponding value of Firing Angle.
If any one of the Thyristor is not conducting in the Bridge, the magnitude of the
DC Output voltage will be 0.66 times the value at when all the Thyristors were
conducting.
9.3.3) By Measuring the frequency of the output DC Signal.
The Frequency of the Rectified DC Output Voltage is Six Times the Frequency
of the Input AC Voltage.
Disconnect the load and connect exciter terminals and vary excitation as per
requirement for SCC and OCC test of Generator.
During SCC and OCC record the reading at TBs, micro-terminal, HMI and
meters and cross check the values with GRP reading.
V0 = Static Gain
Uref = ______
Uact = ______
Frequency at address F8B0 =_____ Hz i.e. ____%.
So present V/F ratio is: ________
Turn off V/F limiter by calling address F714 and changing it from 1111 to
0000.
Now increase excitation to Uref = ______ %
Uact = ______ %
So new V/F ratio is ___________
Now call address F280 and change it from 115 % to 100 %.
Now limiter is turned ON by calling address F714 and changing it from
0000 to 1111.
11) Unit Synchronization.
Adjust, the generator excitation in such a way, that -2% changes and +3% changes from this point, will keep
the generator operation well within the safe operating point.
Note down all the readings from the micro terminal at this operating point, as per the table.
Now gradually increase the excitation by 2 % and note down all the readings as per the table.
Bring back the excitation to the initial operating point. Note down the changes in the field current. In order
to check the intervention/operation of limiter, Field current limiter reference value (F400) shall be adjusted
within the above two values recorded For example, if upon changing the excitation by 2%, the field current
changes from 60 % to 70 %, then set the field current limiter reference (F400) from initial value of 105% to
testing value of 65%.
For changing the reference value, switch off the limiter first, by calling addresses F752 and changing it
from initial value of ‘2222’ to a new value of ‘0000’. Now call the address F400 and change its value
from 105% to desired value. And now, the limiter can be made on, by making address F752 to “2222”.
The Excitation can now again be increased by 2 % gradually, the field current will also rise, but will be
limited by the Limiter in the mid-way. The time after which limiter operates depends upon, the running
value, limit value and the integral constant. The further increase in Uref. will not cause field current to
increase.
With limiter in operated condition, note down all the parameters as per table.
Reduce Uref such that Gen. comes out of limiter operation.
For normalizing the limiter reference value, the limiter shall be made off first, then restore the factory
setting and then make the limiter on.
Integral Time Constant
12.2) Inductive Stator Current Limiter
Adjust, the generator excitation in such a way, that -2% changes and +4% changes from this point, will
keep the generator operation well within the safe operating point.
Note down all the readings from the micro terminal at this operating point, as per the table.
Now gradually increase the excitation by 3 % and note down all the readings as per the table. The
Generator operation must remain in the Inductive zone only.
Bring back the excitation to the initial operating point. Note down the changes in the stator current. In
order to check the intervention/operation of limiter, Stator Inductive current limiter reference value (F430)
shall be adjusted within the above two values recorded For example, if upon changing the excitation by
3%, the stator current changes from 60 % to 66 %, then set the stator current limiter reference (F430)
from initial value of 105% to testing value of 63%.
For changing the reference value, switch off the limiter first, by calling addresses F754 and changing it
from initial value of ‘2222’ to a new value of ‘0000’. Now call the address F430 and change its value from
105% to desired value. And now, the limiter can be made on, by making address F754 to “2222”.
The Excitation can now again be increased by 3 % gradually, the stator current will also rise, but will be
limited by the Limiter in the mid-way. The time after which limiter operates depends upon, the running
value, limit value and the integral constant. The further increase in Uref. will not cause stator current to
increase.
With limiter in operated condition, note down all the parameters as per table.
Reduce Uref such that Generator comes out of limiter operation.
For normalizing the limiter reference value, the limiter shall be made off first, then restore the
factory setting and then make the limiter on.
12.3) Capacitive Stator Current Limiter
Adjust Excitation to maintain Generator Power Factor to 0.99 Leading. Reduce the excitation to
bring the Generator PF to 0.96 Leading. This variation is subject to the grid conditions and to be
followed as per the generator loading. In the entire range of this variation, the generator operation
must remain, well within the capability curve.
Note down all the parameters of DVR as per table. Bring back excitation to 0.99 lead. Note down
Generator stator current variation zone hence obtained from reading at 0.99 lead & 0.96 lead. Hence
to check the intervention/operation of limiter, Capacitive stator current value shall be adjusted
within this zone.
For adjusting the limit value, switch off the limiter first, by calling address F756 and changing
it from ‘2222’ to ‘0000’. Now call the limiter reference value at F460, change its value from
105% to desired value. Then switch on the limiter by making F756 to ‘2222’.
Gradually reduce the excitation, the stator current will start to increase (in leading side), but will be
limited by the limiter in the mid-way. Further reduction in excitation, will not cause stator current to
increase.
Note down the parameters as per the table.
Increase the excitation, so that the limiter becomes out of operation.
For normalizing the limiter reference value, the limiter shall be made off first, then restore the
factory setting and then make the limiter on.
12.4) Load Angle Limiter
With Uref at 100%, Note down all the parameters of DVR as per following table.
Gradually reduce Uref to 95% (Variation is subjected to grid conditions). Ensure Gen.
Goes to leading side. Now, again note down all the parameters of DVR as per
following Table.
Bring back the Uref to 100%.
Note down load angle variation zone hence obtained by varying Uref from 100% to
95% To check the intervention/operation of limiter, the load angle shall be adjusted
within this zone.
After adjusting limiter value (F4A0) to new value, reduce Uref gradually from 100 %
to 95 %.
Check operation / intervention of load angle limiter at set value.
With the help of dual channel recorder record the intervention. Also check the
operation of output relay at digital output card.
At limiter operated condition, note down all the parameters as per table.
13) Power System Stabiliser
Ensure the correctness of all the factory settings in CPU for XE-identification
(AA/AB 13) and in Auto channel CPU (AA/AB 49).
Maintain Generator loading within 60% to 80%. Ensure that, the load remains
constant during the entire testing.
All the limiters, must remain in service.
Adjust the excitation within -2% to +5% and ensure that the generator operation
remains well within the safe operating range.
Recorder settings to be kept as follows………
13.2) Procedure for testing PSS Response
Give a step of +/- 2% into UREF. and record all the above mentioned parameters.
This step in UREf. will bring oscillations into the Active power. If oscillations are
not observed, then the step in Uref. can be increased up to 5 %. The oscillations
in power, depends upon, how well PID parameters are tuned.
Switch off PSS, by calling address F750 and changing it from initial value of
‘2222’ to ‘0000’.
Perform the same step as mentioned in point ‘a’. Take the recordings. Compare
the two recordings, when PSS was in Service and when PSS was not in service.
With PSS in service, the damping of oscillations in active power should be
limited to one cycle.
PSS OFF
PSS ON
13.3) Tuning for improving the Response
Keep the Gain for Frequency, C332 to Zero or to a very low value 0.01
or 0.02.