660 Generator Protection Schemes
660 Generator Protection Schemes
660 Generator Protection Schemes
The following are the main protection schemes adopted for our generator.
It is one of the important protections to protect generator winding against internal faults such as
phase-to-phase and three phase-to-ground faults. This type of fault is very serious because very large
current can flow and produce large amounts of damage to the winding if it is allowed to persist. One
set current transformers of the generator on neutral and phase side, is exclusively used for this
protection. The differential protection cannot detect turn-to-turn fault and phase to ground within one
winding for high impedance neutral grounding generator such as ours. Upon the detection of a phase-
to-phase fault in the winding, the unit is tripped without time delay.
Relays acted: a. Flag operation at Protection panel. b. Acting of Master relay
c. Indication at Annunciation Panel.
Consequences: a. Tripping of 220KV breaker b. Tripping of Field breaker
c. Stop command to Turbine thro’ Mark-IV
Status: a. Unit is at coasting down.
Once the differential protection operated, the unit cannot be taken into service unless the generator
winding is thoroughly examined by the maintenance staff of any internal faults