Generator Protection
Generator Protection
Generators used at thermal power generating units are equipped with two pole non salient
cylindrical rotor. Thus they are known as turbo alternator or turbo generator. Turbo generators
required comprehensive safety and supervisory devices to prevent damage and long forced
outages. The generators require protection against mechanical and electrical faults. The
mechanical faults are described below
1. High cold gas temperature in generator.
2. Liquid in Generator Terminal Box.
3. High Hot Air Temperature in Exciter Unit.
Each of these criteria activates a turbine trip. The generator is disconnected from the grid and de
excited through the two channel reverse power relay.
The protection against these faults is done through following protection circuits:
1. Protection against overheating of Generator
The protection circuit for criterion 1 prevents insufficient cooling and thus
overheating of the hydrogen cooled components. This is done by measuring temperature
of the cooling gas by using RTD (Resistance Temperature Detector) and transmitted
directly to the protection circuit.
2. Protection against Internal Ground fault through Terminal Short circuit
The generator can be damaged due to leakage in its components through which the
cooling water or seal oil flows. The operation of Generator is affected when there is large
leakage. In case of large leakage due to the restricted volume of the compartment or
terminal box, the level of liquid rise quickly, resulting in terminal short circuit or ground
fault. For this two level detectors are connected to generator terminal box and signal is
sent to the protection circuit.
3. Protection against the overheating of Exciter Unit
The hot air temperature after the main exciter is sensed with the help of RTD
(Resistance Temperature Detector) and is transmitted directly to the protection circuit.
This is required for protection against the overheating of the Exciter unit due to insufficient
cooling (failure of exciter cooler).
Apart from the protection required against faults developed mechanically, protection against
electrical faults is also required. The protection schemes used for protection of generator against
electrical faults are described below.
Generators may be endangered by short circuits, ground faults, under excitation, over voltages
and thermal stresses.
Following protective equipments are recommended:
Differential protection
Stator ground fault protection
Rotor ground fault protection
Under excitation protection
Over voltage protection
Over current protection
Differential protection
Breakdown of insulation between different stator phase windings result in an internal short
circuit. The fault is detected by a differential relay which initiates immediate isolation and
de-excitation of the generator. In order to obtain high sensitivity, the protected area
should include the generator only.
Relay time<=60ms
In certain cases the generator may also be included in the differential protection for the
main transformer and station service feeder
breakdown of insulation between stator winding and the frame result in a stator
ground fault. The stator ground fault protection should cover the complete winding
including the neutral point of the generator. The protection is to initiate the immediate
isolation and de-excitation of the generator.
Relay time <= 1s
The load resistance of a grounding transformer and any required boost to raise the
neutral point potential should be selected so that the ground current due to a fault
should be less than 15 Ampere.
A one line to ground fault may develop into a double ground fault resulting in dangerous
magnetic unbalances, especially on four pole generators. Danger arises if a second earth
fault occurs at a separate point in the field system, to cause the high field current to be
diverted, in part at least, from the intervening turns. Serious damage to the conductors
and possibly the rotor can occur very rapidly under these conditions. More damage may
be caused mechanically. If a large portion of the winding is short-circuited, the flux may
adopt a pattern such as that shown in Figure.
To minimize the consequential damage, it is recommended to provide two-pole and four- pole
generators with a protection circuit featuring a delayed response in the core of four pole
generators, the rotor ground fault protection must always operate to avoid the hazard of
sudden, extremely high vibrations due to magnetic unbalances.
Relay time: approximately 1 s
Field winding
circuit
short
Under excitation
protection
Failure of the voltage regulator, mal-operation of the
generator or
transformer control systems and generator operation in a system with capacitive load may
result in a reduction of the excitation required to ensure system stability below a
predetermined minimum value. Short -circuits or interruptions in a field circuit result in a
complete loss of field and thus in instability of the generator this result in the higher rise of
temperature in the rotor and core end portion.
Loss of excitation may occur for a variety of reasons. If the generator was initially operating
at only 20%-30%of rated power, it may settle to run super-synchronously as an induction
generator, at a low level of slip. In doing so, it will draw reactive current from the power
system for rotor excitation. This form of response is particularly true of salient pole
generators. In these circumstances, the generator may be able to run for several minutes
without requiring to be tripped. There may be sufficient time for remedial action to restore
the excitation, but the reactive power demand of the machine during the failure may severely
depress the power system voltage to an unacceptable level. For operation at high initial
power output, the rotor speed may rise to approximately 105% of rated speed, where there
would be low power output and where a high reactive current of up to 2.0p.u. may be drawn
from the supply. Rapid automatic disconnection is then required to protect the stator
windings from excessive current and to protect the rotor from damage caused by induced slip
frequency currents.
The protection used varies according to the size of generator being protected. A momentary
excursion beyond a steady state stability limit must not result in a loss of stability .therefore a
under excitation protection is designed to give a warning when steady state limit is reached.
The protection must operate instantaneously if a loss of field occurs when a steady state
stability limit is reached.
Over-voltage Protection.
Over-current Protection.
Over-current protection of generators may take two forms. Plain over-current protection
may be used as the principle form of protection for small generators, and back-up
protection for larger ones where differential protection is used as the primary method of
generator stator winding protection. Voltage dependent Over-current protection may be
applied where differential protection is not justified on larger generators, or where
problems are met in applying plain over-current protection.
to be induced in the rotor iron. If this component becomes high severe overheating of
the rotor may be caused.
A three-phase balanced load produces a reaction field that, to a first approximation, is
constant and rotates synchronously with the rotor field system. Any unbalanced
condition can be resolved into positive, negative and zero sequence components. The
positive sequence component is similar to the normal balanced load. The zero sequence
components produce no main armature reaction.
Effect of negative sequence current:
The negative sequence component is similar to the positive sequence system, except
that the resulting reaction field rotates in the opposite direction to the d.c. field
system. Hence, a flux is produced which cuts the rotor at twice the rotational
velocity, thereby inducing double frequency currents in the field system and in the
rotor body. The resulting eddy-currents are very large and cause severe heating of
the rotor .
A means of indicating when the transition from exporter to importer of power occurs is
provided by a device known as a reverse power relay. As its name suggests, it is
triggered by power flowing in a direction opposite to that which is normally desired. This
can be used for generator protection, as is the case with standby generators, or as a
permissive alarm/interlock for turbine generator motoring Figure shows a typical
arrangement of a reverse power protection circuit employing both a CT and a voltage
transformer (VT) to power the relay, and hence, protect the generator. The relay will
operate when any negative power flow is detected.
excessively low frequency by tripping of the generators concerned. With some prime
movers, operation in narrow frequency bands that lie close to normal running speed
(either above or below) may only be permitted for short periods, together with
cumulative lifetime duration of operation in such frequency bands. While connected to a
stable grid, the grid frequency and voltage are usually constant If the system frequency
drops excessively. it indicates that there has been a significant increase in load. This
could lead to a serious problem in the grid, and it is of little use to supply a grid that may
be about to collapse. In this case, the generator would be separated from the grid. The
grid (or at least portions of it) may well collapse. The system can slowly rebuild (with
system generators ready to restore power) to proper, Pre-collapse operating conditions;
As mentioned above, if a generator connected to the grid has sufficient excitation
applied below synchronous speed (since grid frequency has dropped) for it to produce
rated voltage, the excitation level is actually higher than that required at synchronous
speed.
A specialized volts/hertz relay compares voltage level and frequency and will trip the
generator if preset volts/hertz levels are exceeded.