Generator Protection
Generator Protection
Generator Protection
PROTECTION
INTRODUCTION
A generator is the heart of an electrical power system, as it
converts mechanical energy into its electrical equivalent, which is
further distributed at various voltages. It therefore requires a
‘prime mover’ to develop this mechanical power and this can take
the form of steam, gas or water turbines or diesel engines.
TURBINES
Steam turbines are used virtually exclusively by
the main power utilities, whereas in industry
three main types of prime movers are in use:
1. Steam turbines: Normally found where waste steam is available
and used for base load or standby.
2. Gas turbines: Generally used for peak-lopping or mobile
applications.
3. Diesel engines: Most popular as standby plant.
It will be appreciated that a modern large generating unit is a
complex system, comprising of number of components:
7
GENERATOR PROTECTION
8. Rotor Earth Fault Protection (64R)
9. Restricted Earth Fault Protection
10. Backup Impedance Protection
11. Low Forward Power Protection
12. Reverse Power Protection
13. Pole Slip Protection
14. Pole Discrepancy Protection
15. Local Breaker Back Protection
16. Bus Bar Protection
17. Over Frequency Protection
18. Under Frequency Protection
19. Over Voltage Protection
8
MANY DIFFERENT FAULTS CAN OCCUR ON THIS
SYSTEM, FOR WHICH DIVERSE PROTECTION
MEANS ARE REQUIRED. THESE CAN BE
GROUPED INTO TWO CATEGORIES:
STATOR INSULATION FAILURE
The stator insulation failure can lead to earth fault in the
system.
The neutral point of the generator stator winding is normally
earthed so that it can be protected, and impedance is generally
used to limit earth fault current.
Earth fault protection can be applied by using a transformer and
adopting a relay to measure the earthing transformer secondary
current or by connecting a voltage-operated relay in parallel with
the loading resistor
GROUND-FAULT PROTECTION FOR UNGROUNDED
GENERATORS GROUNDED BY THE CONNECTED
SYSTEM.
OVERLOAD PROTECTION
Generators are very rarely troubled by overload, as the amount of
power they can deliver is a function of the prime mover, which is
being continuously monitored by its governors and regulator.
Where overload protection is provided, it usually takes the form of
a thermocouple or thermistor embedded in the stator winding. The
rotor winding is checked by measuring the resistance of the field
winding.
OVER CURRENT PROTECTION
It is normal practice to apply IDMTL relays for over current
protection, not for thermal protection of the machine but as a
‘back-up’ feature to operate only under fault conditions. In the
case of a single machine feeding an isolated system, this relay
could be connected to a single CT in the neutral end in order to
cover a winding fault. With multiple generators in parallel, there is
difficulty in arriving at a suitable setting so the relays are then
connected to line side CTs.
OVERVOLTAGE PROTECTION
Overvoltage can occur as either a high-speed transient or a
sustained condition at system frequency.
Power frequency over voltages are normally the result of:
DC injection method
POTENTIOMETER METHOD
39
GENERATOR DIFFERENTIAL PROTECTION