Generator Rotor Protection
Generator Rotor Protection
POLE SLIPPING
by
Sanpreet Kaur
Student ID: 250447390
Project Report
Table Of Contents
1. Introduction…………………………………………………………………..................3
2. Rotor Protection………………………………………………………………………...4
2.1 Rotor Earth Fault Protection……………………………………………….….4
2.2 Rotor Overheating Protection…………….………………………….………..5
2.3 Loss of Excitation Protection……………….……………….………………...7
3. Loss of Field Protection………………………...............................................................7
4. Pole Slipping……………………………………………………………………………9
5. References………………………………………………………………………..…....11
3
1. Introduction
In this project I am going to discuss various protection methods used for rotor protection,
loss of field and pole slipping.
In the rotor mainly faults are earth faults or inter turn faults these are caused by thermal
and mechanical stresses.
The field system is normally ungrounded so when a single fault between field winding
and rotor body exist does not give rise to any fault current. But when second earth fault
exist it short circuit the rotor winding and therefore produce an unsymmetrical field
system and unbalance force on the rotor. This causes vibration of the rotor and damage to
the bearings. So rotor earth fault protection is provided to restrict the fault spreading.
Because of this fault, unbalance in three phase stator currents exists. As unbalance three
phase currents have a negative sequence component, it rotates in a opposite direction at
synchronous speed giving rise to double frequency currents. This results in overheating
of the rotor and other damage to the rotor. So rotor temperature indicators are used for
detecting the rotor overheating.
Rotor open circuit faults are very rare to exist causes arcing problems and reduced
excitation. Loss of excitation or field failure occurs due to short circuit or open circuit in
field winding. In this case generator start running as induction generator, supplying
power at leading power factor. Due to loss of excitation loss of synchronism and system
stability occur. In this case rotor protection can be done by using tripping scheme which
opens field circuit breaker which will trip the generator unit breaker.
4
2. Rotor Protection
Different Protection schemes are used for protection of faults occurring in rotor. These
schemes are:-
2.1 Rotor earth fault protection:-As the field circuit are operating unearthed a
single earth fault does not affect the operation of the generator. But this fault
increases the stress to the ground because stator transients induce an extra
voltage in the field winding. So if there is only single earth fault but relay
should be provided to give the knowledge that fault has occurred so the
generator may take out of service until second fault occurs and cause serious
damage. Two methods are used for rotor earth fault protection.
Method I- In this method a high resistance is connected across the rotor
circuit and its mid point is grounded through a sensitive relay. This relay
detects the earth fault for whole circuit except the rotor center point
MI D
POI NT
Fig1: Rotor Earth
E X CIT E R GE NE RA T OR
A RM A TURE FIE LD
Fault Protection WI NDNG
Method I
S ENSI TIV E
EA RT H
F A ULT
RELAY
because in case when we use ac the relay not picking up the current that
flows normally through capacitance to ground and also care should be
taken to avoid resonance between capacitance and inductance.
moving coil relay. The operating coil being used as voltage coil and
restraining coil used as current coil. The relay measure the ratio of voltage and
current because resistance gives the measure of rotor temperature.
Fig 3: Rotor
Overheating
Protection
Field Protection Phenomena: - When the field supply is tripped, it speed increased and
it start behaving as induction generator so heavy currents are produced in the teeth and
wedges of the rotor. Because of the drop in excitation voltage the generator output
voltage drops slowly to compensate this voltage current start increasing then generator
become under excited and start drawing reactive power 2 to 4 times the generator load.
Before losing excitation, the generator is delivering power to the system. But when loss
of field occur this large reactive load thrown on the system abruptly with loss of
generator’s reactive power and it further causes voltage reduction and extensive
instability.
Protection against Loss of field:-
If the system has capability to tolerate the difference of reactive power
then automatic protection is not required but if the system will be instable
in this condition and has not capability to tolerate then automatic
protection is required.
Under current Moving coil relay is connected across a shunt in series with
field winding. But in case of large generators which operate over a wide
range of field excitation then this relay will not work properly because
8
field failure due to the failure of the excitation is not detected by it because
it is held in by the ac induced from the stator.
GENERATOR EXCITER
FIELD
WINDINGS
SHUNT
UNDER
CURRENT
MOVING
COIL
The most valid type of protection in this case is by using directional-distance type
relay operating by alternating current and voltage at the generator terminals. In
offset-mho relay is used and its setting is like that when the excitation goes certain
value then this relay start operating because machine start running
asynchronously. Its characteristics are shown on R-X diagram. When excitation is
lost the generator impedance start a curve from the first quadrant to the fourth
quadrant. This region is enclosed in the operating area of the relay so the relay
will operate when the generator starts to slip poles and will trip the field breaker
and disconnect the generator from the system. The generator may then return to
service when the cause of failure is cleared.
9
jX S Y ST EM C H AR A C T ER I S T I C S
RE LA Y CHARACTERI STIC S
5. Pole Slipping
When angular displacement of the rotor exceeds the stability limit then rotor slips a pole
pitch or we can say rotor flux slips with respect to stator flux. This condition is called
pole slipping.
Causes:-
(i) Power system fault that persists for long duration.
(ii) Connecting line between two systems is opened.
(ii) Because of the insufficient electromagnetic torque that keep rotor in
synchronism
(iv) Faulty excitation system.
(v) Operating errors.
Pole Slipping Phenomena:- Pole slipping does not occur very often when faults are
cleared very fast. When pole slipping occurs due to this synchronising power will start
10
flowing in reverse direction twice for every slip cycle. On drawing this synchronising
power on the impedance plane the flow of it characterised by cyclic change in the load
impedance and load impedance locus passes between +R and –R quadrants because real
power flows in reverse direction. When the load impedance is very reactive in nature then
two systems are 180 degree out of phase, this instant is when drawn on the jx axis the
point corresponding to this instant is called transition point. At this stage only reactive
power flows and system voltage reached to zero at the electrical mid point of the two
systems. Mid point is that point where pole slipping take place and its location can be
determined from the apparent load impedance to the point where the locus crosses the jx
jx
Locus of Pole
Slipping center
Stage I
axis. Three parameters magnitude, direction and rate of change of load impedance with
respect to the generator terminals tell us about the pole slipping, that is it taking place.
Need of Pole Slipping Protection:- High currents and torques can
STAGE 1
STAGE 2 SYSTEM
This is protection against loss of synchronism. Impedance type protective relays are used
in this case. There are two types relays connected to both current transformers and
voltage transformers on l.v and h.v side of generator transformer respectively pole
slipping detection relays and directional control relays. Protection can be done by two
stages.
Stage I- Reaching through generator to neutral point into the transformer to cover the
whole winding but not crossing the h.v terminals.
Stage II-Operation after adjustable no of pole slips whether the system center is in the
generator transformer unit or out of it.
References
http://www.mantatest.com/GeneratorProtection.html
(2) Generator Protection Application Guide
http://www.basler.com/downloads/genprotguidC.pdf
http://books.google.com/books?as_list=BDVMdkmQQ07rIpNbYz-24ARoU_eo3-
ak5HJwQmdfKkzT9VoV4N80