Design of R.C. Column (Axially Loaded) : Provide 10-16#bars As Main Bars

This document summarizes the design of a reinforced concrete column that is 4 meters long, axially loaded with 1000 kN, made of 20 N/mm2 concrete with 10 number 16mm diameter main bars and 8mm diameter lateral ties spaced at 256mm. The column's capacity is calculated as 2540.1 kN which exceeds the load of 1500 kN, so it is determined to be safe.

Uploaded by

daddakoli007
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (1 vote)
176 views

Design of R.C. Column (Axially Loaded) : Provide 10-16#bars As Main Bars

This document summarizes the design of a reinforced concrete column that is 4 meters long, axially loaded with 1000 kN, made of 20 N/mm2 concrete with 10 number 16mm diameter main bars and 8mm diameter lateral ties spaced at 256mm. The column's capacity is calculated as 2540.1 kN which exceeds the load of 1500 kN, so it is determined to be safe.

Uploaded by

daddakoli007
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3

DESIGN OF R.C.

COLUMN (AXIALLY LOADED)

Length of
column
l, m
4
Effective
length
Le, m
2.6

Column size
B, mm
D, mm
500
500

Load
P, kN
1000

Grade of
concrete
fck, N/mm2
20

Grade of
steel
fy, N/mm2
415

Area of
Area of
Gross Area
steel
concrete
Ag, mm2 Asc, mm2 Ac, mm2
250000
2000
248000

Capacity of Column
Pu, kN
2540.1

Load on column
Pu, kN
1500

Check
Capacity of colum is Greater than load on Column
Safe
Continue the Design
No of Bars
10

Provide 10-16#bars as main bars


Check for lateral ties
Provide dia
of bar
mm
8

Spacing
mm
256

Provide 8mm @ 256mm C/C

ALLY LOADED)

End condition of
column
Fixed-Fixed

Percentage
of steel
(assumed)
%
0.8

CHECK
It is SHORT COLUMN
and Axially Loaded

Dia of
Main Bar
mm
16

Dia of
lateral
ties
mm
8

Fixed-Fixed
Fixed-Hinged
Hinged-Hinged

20
25
30
35
40
45
50

250
415
500