QCP e 11 Hipot Test
QCP e 11 Hipot Test
QCP e 11 Hipot Test
This procedure is intended to provide general guidelines for dielectric withstand (Hi-Pot) test of
MV cables and switchgear.
Hi-Pot field test is not considered on sites for MV motors and generators except where
specifically required.
All safety precautions must be observed during the testing. Testing equipment operating
manual shall be used for proper testing.
References
- Testing Equipment Operating manual
- Relevant industry standards
- Project Safety Manual
- Applicable local safety procedures
Preparation
Cables shall be disconnected from equipment to minimize erroneous result in case AC or VLF
Hi-Pot testing is considered or to prevent damage to equipment in case DC Hi-Pot testing is
considered.
Adequate clearances are required between the cable ends and other equipment and ground.
Barricade the area where the test will be connected. Also barricade the remote ends in case of
cables and where necessary position a personnel guard (watchman) to prevent unauthorized
access to the cables under test.
Testing equipment shall be verified to be in good working condition and the calibration certificate
shall be valid the time of conducting the test and the calibration label shall be visible on the
testing equipment
MV Switchgear
Medium Voltage
Medium Voltage
Medium Voltage
Medium Voltage
Medium Voltage
Medium Voltage
DC Hi-Pot
Cables
Medium Voltage
Medium Voltage
Medium Voltage
Medium Voltage
Medium Voltage
Medium Voltage
MV Switchgear
Medium Voltage
Medium Voltage
Medium Voltage
Medium Voltage
Medium Voltage
Medium Voltage
Rated
Voltage
3.6/6 (7.2) KV
6/10 (12) KV
6.35/11 KV
8.7/15 (17.5)
12/20 (24) KV
18/30 (36) KV
Test
Voltage
12 KV
20 KV
22 KV
30 KV
40 KV
60 KV
Rated
Voltage
3.6/6 (7.2) KV
6/10 (12) KV
6.35/11 KV
8.7/15 (17.5)
12/20 (24) KV
18/30 (36) KV
Test
Voltage
12 KV
20 KV
22 KV
30 KV
40 KV
60 KV
Rated
Voltage
3.6/6 (7.2) KV
6/10 (12) KV
6.35/11 KV
8.7/15 (17.5)
12/20 (24) KV
18/30 (36) KV
Test
Voltage
28 KV
20 KV
22 KV
56 KV
40 KV
80 KV
Rated
Voltage
3.6/6 (7.2) KV
6/10 (12) KV
6.35/11 KV
8.7/15 (17.5)
12/20 (24) KV
18/30 (36) KV
Test
Voltage
12 KV
20 KV
22 KV
30 KV
40 KV
60 KV
Time
15 minutes
15 minutes
15 minutes
15 minutes
15 minutes
15 minutes
Time
1 minute
1 minute
1 minute
1 minute
1 minute
1 minute
Time
15 minutes
15 minutes
15 minutes
15 minutes
15 minutes
15 minutes
Time
1 minute
1 minute
1 minute
1 minute
1 minute
1 minute
Acceptance Criteria
Leakage Current Stabilize
Leakage Current Stabilize
Leakage Current Stabilize
Leakage Current Stabilize
Leakage Current Stabilize
Leakage Current Stabilize
Acceptance Criteria
Leakage Current Stabilize
Leakage Current Stabilize
Leakage Current Stabilize
Leakage Current Stabilize
Leakage Current Stabilize
Leakage Current Stabilize
Acceptance Criteria
Leakage Current Stabilize
Leakage Current Stabilize
Leakage Current Stabilize
Leakage Current Stabilize
Leakage Current Stabilize
Leakage Current Stabilize
Acceptance Criteria
Leakage Current Stabilize
Leakage Current Stabilize
Leakage Current Stabilize
Leakage Current Stabilize
Leakage Current Stabilize
Leakage Current stabilize