Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Static Frequency Converter - TS150

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Static Frequency Converter

TMP-TS150/TMP-TS170

Dimensions
TMP-TS150
Converter

TMP-TS170

DC Reactor

Converter

Inverter

DC Reactor

Inverter

2950

2850

Static Frequency Converter

1300

1100
5200

5900

Weight: 10300 (kg) min.

Weight: 12100 (kg) min.

SFC

SFC control panel


(Common to series)

2350

* The dimensions and weight of SFC Transformer


depend on the capacity.

1050
1660
Weight: 1100 (kg)

Specifications
TMP-TS150-35
TMP-TS150-40
TMP-TS150-50
TMP-TS170-60
TMP-TS170-35
TMP-TS170-40
TMP-TS170-50
System Rating
Output power (MW)
3.5
4
5
6
DC voltage (kV)
4
DC current (A)
875
1,000
1,250
1,500
Output voltage (kV)
3.5 (50 Hz area) / 3.6 60 Hz area)
Output voltage variation (%)
+/2
Output current (Arms)
714
816
1,021
1,225
Output frequency (Hz)
0.05 to 33 (50 Hz area) / 0.05 to 40 60 Hz area)
Input frequency (Hz)
50 / 60
Incoming voltage variation (%) +/10
Converter/Inverter Cubicle
Thyristor configuration
2S1P6A
Pulse number
6
DC Reactor
Inductance (mH)
12
11
9
7
Insulation class
Class H
Temperature rise class
Class H
Core
Silicon steel sheet
Type
Dry
Other
Total loss (kW)
(Converter Cubicle + Inverter
100
110
130
150
Cubicle + DC Reactor Cubicle)
Cooling method
Forced air cooling (self-cooling for oil-immersed transformer)
Protection class
IP41 (IP20 for terminals and inlet/outlet) (except oil-immersed transformer)
Time rating
100% continuous
Conforming standard
IEC-60146-1-1
Installation location
Indoors (outdoors for oil-immersed transformer), altitude 1,000 m max.
Ambient temperature ()
0 to 40
*1 RMS value including a harmonic component equivalent to 6-pulse converter.
Standard Model

*1

Output voltage/torque characteristics

TMP-TS170-70
7
1,750

1,429

[For 50 Hz area]

[For 60 Hz area]

Output voltage

Output voltage
AVR constant
field control

3.5 kV

Torque

Torque
*Ta

*Tb
*C

*C

180

5 Hz

*Fa =

*Ta =
Typical Requirement for Input Transformer

Capacity (kVA)
Secondary voltage (kV)
% x (%)

TMP-TS150-35
TMP-TS170-35
4,700
3.75
8

TMP-TS150-40
TMP-TS170-40
5,400
3.75
10

TMP-TS150-50
TMP-TS170-50
6,800
3.80
12

AVR constant
voltage control

3.6 kV

33 Hz

*Fa

TMP-TS170-60

TMP-TS170-70

8,200
3.85
14

9,700
3.90
16

6 Hz

3.5 kV x 50 Hz
[Hz]
Generator rated voltage

Output power x 974 x Generator rated voltage

Standard Model

AVR constant
field control

AVR constant
voltage control

3000 rpm x 3.5 kV

*Fb =

[kgm]

*Tb

Generator rated voltage

[Hz]

Output power x 974 x Generator rated voltage


[kgm]
=

3600 rpm x 3.6 kV

Output power x 974


*Ca= Inverse proportional curve of
Frequency x 60

108-0073
Mita 43MT Bldg.13-16, Mita 3-chome, Minato-ku, Tokyo
Phone: +81-3-5441-9100 FAX: +81-3-5441-9105
Phone: +81-3-5441-9140
URL http://www.tmeic.co.jp/global/

Information contained in this catalog is subject to change without prior notice for improvement.

40 Hz

*Fb

3.6 kV x 60 Hz

[BUH-00046-C, Dec. 2011]

You might also like