At a glance
Powered by AI
The document discusses cable accessories produced by Kabeldon for connecting and joining power cables at various voltage ratings.

Cable accessories are used to connect and join power cables in order to safely distribute electricity through cable networks.

The document covers cable accessories for voltages ranging from 1 kV up to 420 kV, with specific sections for accessories rated at 1 kV, 12-36 kV, and 52-420 kV.

2009, edition 1

Kabeldon cable accessories 1 - 420 kV


32 Vi förbehåller oss rätten att ändra konstruktion och sortiment! ABB Kabeldon
2006 utgåva 1
Introduction

Introduction
Table of contents

Page No.

Introduction ............................................................................................................................. 4
Fundamental technologies ...................................................................................................... 5
Reasons for choosing Kabeldon cable accessories ............................................................... 6
Standards ................................................................................................................................ 8
Reference illustrations ........................................................................................................... 10
Table of contents Kabeldon cable accessories ≤ 1 kV .......................................................... 11
Table of contents Kabeldon cable accessories 12-36 kV XLPE............................................ 21
Table of contents Kabeldon cable accessories 12-52 kV PILC ............................................ 61
Table of contents Kabeldon cable accessories 52-420 kV ................................................... 77
General accessories ........................................................................................................... 107
List of content in alphabetical order .................................................................................... 110
List of content by product category .................................................................................... 113

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 3
Introduction

Introduction

Our factory is situated in Alingsås, Sweden.


The production is automated and meets
stringent quality and environmental requirements.
We work to create safe electrical
distribution via power cable networks.
To achieve this, we develop, manufacture Our business idea is:
and market a broad range of cable "We provide companies that work with electric
accessories, switching devices and power with solutions which enable them to
enclosures. joint and connect cables easily and safely, and
Our main groups of customers distribute electricity".
are power supply companies, network
companies, industrial companies and
OEMs. Quality and the environment are among our
Our primary areas of expertise are top-priorities. They are important and self-
electrical connections in cable systems evident parts of the strategic plan.
and control of electrical field. Our carefully considered investments in
Our own testing plant is an important aid the quality and the environment are based on
to product development. modern principles. They lead to the fulfilment
of ambitious goals for competitiveness and
Catalogue profitability, with a view to maximising value
The introductory pages show the most to the customer.
important products in their proper We work continuously to improve our
environment. The entire range is then processes. Important foundations for this work
presented in three main parts including are:
product facts and ordering information in  ISO 9001 quality standard
table form.  ISO 14001 environmental standard.
❑ Cable accessories  1 kV
❑ Cable accessories 12-36 kV
❑ Cable accessories 52-420 kV

An alphabetical list of contents and a list of ABB AB


contents by product category can be found Kabeldon
in the end of this catalogue. Box 531, SE-441 15 Alingsås, Sweden
The product catalogue is also available Tel: +46 322 770 00
on CD and at our website. Fax:+46 322 770 01
We reserve the right to alter the design www.abb.se/kabeldon
and range of our products.

4 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Introduction

Introduction
Fundamental technologies

We work on the basis of four fundamental Development of creepage


technologies within which we have current resistant materials
accumulated substantial expertise over Outdoors, cable accessories
many years. are exposed to major stresses,
e.g. UV radiation from the sun
Electrical connections and creepage currents caused
The safe and secure transfer by precipitation and pollution.
of electric current Cable accessories are
between cable installed everywhere on
conductors or the face of the planet:
between a cable in humid tropical
conductor and a device requires a good- environments, in extreme cold
quality electrical connection. We test and or in the swirling salt mist of
develop various methods, but in most coastal regions. We develop
cases we use bolt technology. This gives materials
us the possibility of offering complete and designs for out-
solutions in line with our philosophy of door use that are only
easy and safe installation. minimally affected
by external factors.
Controlling electrical fields In the case of cable
At high voltages the electrical fields must terminations, it is
be controlled so that the strength of the the insulators, both
insulation or the surrounding material is not in porcelain and
put at risk. Depending on the voltage level, composite material.
we work with different methods, e.g. Practical endurance
geometrical, refractive or resistive field tests are an important part of our development
control. work. In addition to Weather-O-Meter,
Geometrical field control is achieved salt-mist-chamber tests and other destructive
with premoulded stress cones and splicing long-term tests, the products are tested under
blocks. extreme weather conditions.
Resistive and refractive field control are
achieved with special field-controlling Design of low voltage networks
materials integrated into premoulded Electrical distribution in power cable networks
termination blocks. calls for safe and rugged products to connect
cables and to withstand external factors such
as humidity, vibration, etc., for a long time
without causing malfunctions.
Lengthy experience of our own manufacture
of switching devices and hot-dip galvanized
enclosures, as well as good customer
relations, means that we can quickly adapt
product development to suit the needs of
the market.

A separate product catalogue for Kabeldon low


voltage switchgear system is available on request.

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 5
Introduction

Reasons for choosing


Kabeldon cable accessories

A power cable network must be capable in the field of polymers, well-equipped


of supplying electric power without high-voltage and high-current laboratories.
interruption. If a failure does occur, it is
usually the junction points in the network Better economy
that are at fault, rarely the cable. So it pays Kabeldon cable accessories provide
to choose cable accessories with care. greater safety. This means major savings in
the long term, as well as lower costs from
Unique, long experience simplified routines for purchasing, deliveries
Long experience brings great expertise. and storage.
We have been manufacturing cable
accessories for paper-insulated cables for
about 80 years. When XLPE insulated
cables began to be used almost 50 years
ago, we were involved from the outset.
Since then we have always been in the
forefront of developments.

Manufacturing outdoor cable terminations for


paper-insulated cables in 1962.

Leading research and development


• Our watchwords are simplicity and
safety.
• Our core competence is our expertise
in electrical connections in power cable
systems.
Successful product development requires
proper resources. We have an advanced
chemistry laboratory and profound expertise

6 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Introduction

Introduction
Professional training
The technology of cables and their
installation is constantly developing.
We offer broad-based training in cable
technology and cable accessories.
Our instructors also take part in our
development projects, so you can be
sure that they have access to the
latest technology.
We arrange training programmes
and practical exercises in the assembly
of cable accessories up to 420 kV.
All course participants will receive a
diploma or a training certificate after
passing a theoretical and practical test.
If you would like to know more about
the courses, please contact our training
department.

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 7
Introduction

Standards

Definition of voltages
Cables and cable accessories are classified
according to the voltages at which they
operate. A rapid survey at standards all over
the world shows that the designations are
a little different. However, IEC designations
gives a clear picture of used vocabulary. The
voltages normally used in this context are:

U0 = the rated r.m.s.(root mean square)


power-frequency voltage between
each conductor and screen or sheath
for which cables and accessories are
designed.

U = the rated r.m.s power-frequency


voltage between two different Tests in the high voltage laboratory.
conductors for which the cables
and accessories are designed. These standards were developed by
CENELEC for the European countries.
Um= the maximum r.m.s power-frequency The aim is to use the same standards
voltage between two different throughout Europe, to eliminate
conductors for which the cables and obstacles to trade. In most cases,
accessories are designed. It is the these standards harmonize with IEC
highest voltage that can be sustained standards. Each European country
under normal operating conditions at publishes the standard as its own, and
any time and at any point in a system. there may be some national deviations
It excludes temporary voltage and special requirements.
variations due to fault conditions
and the sudden disconnection of large IEEE (The Institute of Electrical and
loads. Electronics Engineers)
This standard is mainly used in the USA.
Standards and type testing
Electrical components must meet numerous Earlier Swedish standards are being replaced
requirements in areas such as functional by standards drawn up by CENELEC. For ex-
safety, technical performance, personal ample, Swedish standard SEN 24 14 34 edition
safety and so on. For cable accessories, 2, 1977 for XLPE-insulated cables is replaced
compliance with the quality requirements is by SS 424 14 45 edition 1, which is identical to
checked by type and routine testing. HD 629.1 S1.
We perform these tests to various standards, Some customers require special tests that
both international and national. are not included in the usual standards. We
These are the standards on which our are usually able to meet their requirements.
tests are usually based:
EBR (Electricity Building Rationalisation)
IEC (International Electrotechnical is a Swedish system for the rational
Commission) planning, construction and maintenance
An international standard. of electricity distribution plants and
facilities in the range 0.4-145 kV.
EN (European Norm)

HD (Harmonization Document)

8 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Introduction

Introduction
Standards

Voltage range Um 1.2 kV IEEE: The currently applicable standards


In this voltage range, the function of cable are Std. 48 for terminations covering
accessories is to provide mechanical insulation classes 2.5-765 kV, and Std.
protection and insulation. There is no need 404 for joints rated at 2.5-500 kV. The test
for controlling the electrical field. voltage for joints is generally lower than for
In the past, there was no international equivalent terminations.
standard, only national standards. The voltage classes in IEEE are not
CENELEC therefore produced an identical with those in IEC. Some of the
international standard, HD 623 S1, definitions also differ slightly between IEEE
which is equivalent to Swedish standard, and IEC. This can make direct comparisons
SS 424 14 44. difficult.
When the CENELEC standard is adopted
in a country, it can be supplemented with Voltage range Um 52-420 kV
one or more national options, for example IEC standard 60840 covers cable systems
requirements for impact resistance at low with voltages above 36 kV up to 170 kV. The
ambient temperature. third edition of the standard now also treats
routine testing of cable accessories.
Voltage range Um 7.2-42 kV IEC standard 62067 covers cable systems
IEC: Current standards are IEC 61442, with voltages above 170 kV up to 550 kV.
which covers test methods, and IEC 60502-4, The standard also states methods and
which sets out the testing requirements. requirements for the routine testing of cable
IEC contains Um  36 kV. accessories.
Both 60840 and 62067 deal with testing
CENELEC: Current standards are of outer protection for buried joints and
EN 61442 which covers test methods and is screen separation kits. These tests are to
identical to IEC 61442. HD 629.1 S1, which qualify the electrical performance of the
sets out the testing requirements. The main outer protection with special emphasis on
difference between IEC and CENELEC is that watertightness.
CENELEC stipulates a longer period of tem-
perature cycling under voltage.
IEC voltage classes
A test conducted in accordance with
CENELEC also satisfies the IEC requirements. Uo U Um
Standard HD 629.2 S1 applies to
26 45-47 52
accessories for paper-insulated cables 36 60-69 72.5
and transition joints. 64 110-115 123
To include the less common voltages 76 132-138 145
87 150-161 170
which occur in certain European countries,
127 220-230 245
CENELEC has included more voltage 160 275-287 300
classes than IEC. 190 330-345 362
In addition, CENELEC runs up to Um42 kV. 220 380-400 420

CENELEC voltage classes


Uo U Um

3.6 6 7.2
3.8 6.6 7.2
6 10 12
6.35 11 12
8.7 15 17.5
12 20 24
12.7 22 24
18 30 36
19 33 36 We supply cable accessories for various types
20.8 36 42 of cables.

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 9
Introduction

Manufacturing and testing

Manufacturing of premoulded connectors. The different


layers are vulcanized together.

The three layers of the joint are vulcanized together


in a unique manufacturing process.

The premoulded cable joints are routine tested after A snapshot of a cable termination manufacture.
manufacturing.

We test and develop electrical connections with reliable Research and development are the basis for
bolt connector technology. manufacturing of our products.

10 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon
Kabeldon cable
cable accessories
accessories < 1 kV

Table of contents
Cable accessories ≤ 1 kV

Accessories < 1 kV
Page No.

Introduction ........................................................................................................................... 12
Cable joint, cast resin, SMARTA............................................................................................ 13
Cable joint, branch, SAGA 11Y ............................................................................................. 14
Cable joint, heat-shrink, SMKC ............................................................................................ 15
Cable joint, taped, SMILA, SMULA ....................................................................................... 16
Cable termination, LPH, LXAC .............................................................................................. 17
Protective hood, KAL ............................................................................................................ 19
Cable connection, AK-ADAS................................................................................................. 20

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 11
Kabeldon
Kabeldon
Kabeldon
cable
cable
cable
accessories
accessories
accessories
52-420
<Notes
1 kV

Introduction
Cable accessories ≤ 1 kV

The most important tasks of the cable Cast resin products are the obvious choice
accessories are to create a safe electrical in slightly more challenging environments.
connection, insulation and provide The robust joint is able to cope with a
mechanical protection. depth of water of 10 m, for example, and
The product range includes accessories can be used for both power and control
designed on different principles with cables.
different properties.
Accessories which utilize tape technology
are simple to use, flexible and unaffected
by the dimensions of the cable.
Cable accessories which utilize
heat-shrink technology offer a simple
alternative.

Cast resin joint type SMARTA.

Cast resin branch joint type SAGA.


Protective hood type LPH.

Tape joint type SMILA / SMULA.

Protective hood type LXAC. Heat-shrink joint SMKC

12 We reserve the right to alter the design and range of our products. Kabeldon, 2009 Edition 1
Kabeldon
Kabeldon cable
cable accessories
accessories < 1 kV
• Robust
• Approved down to 10 metres
water depth

Cable joint with cast resin for


plastic and paper-insulated
cables, and control cables

Accessories < 1 kV
SMARTA

Use hardening the joint becomes resistant.


For jointing 1 kV plastic and paper-insulated When jointing paper-insulated cable, and
3-, 4- and 5-core cables as communication at the transition between paper and plastic
cables and the transition between plastic cables, accessory kit PPC must be used.
and paper-insulated cables. Can be used in Note that, when jointing plastic-insulated
down to 10 metres water depth. to paper-insulated cables, connectors with
a partition must be used.
Standards The joint is also excellent to use when
SMARTA meets the requirements of: jointing cables with an integrated tube for
– SS 424 14 44 Edition 1 opto fibre, which must be jointed without
– EBR KJ 24:89 heating. The material for jointing the opto
tube is not included.
Design
The joint consists of a transparent casting To be ordered separately
mould with flexible sealing rings between – Connectors
the casting mould and the cable. – PPC (see below)
Compounding cast resin and hardener are
mixed in a sealed bag. Please note, the
lower the temperature is, the longer the
hardening time will be. SMARTA ought not
to be installed if temperature is below -10o
C. After

Designation Conductor Control cable Cable Casting mould Weight


cross section max number of cores diameter Length Diameter
Cu Al with without
individual screen
mm2 mm mm kg/item

SMARTA 10-5 2.5-10 – 14 27 5-27 240 35 0.8


SMARTA 11-5 6-16 – 27 39 15-30 340 40 1.2
SMARTA 12 25-70 25-50 91 – 25-50 540 72 3.6
SMARTA 13 95-150 70-150 – – 30-65 660 96 7.6
SMARTA 14 185-240 185-240 – – 35-70 840 105 10.5

To be ordered separately
Accessory kit Used for Weight
kg/item

PPC 11 SMARTA 10-5 / SMARTA 11-5 0.2


PPC 12 SMARTA 12 0.3
PPC 13 SMARTA 13 0.4
PPC 14 SMARTA 14 0.5

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 13
Kabeldon
Kabeldon
Kabeldon
cable
cable
cable
accessories
accessories
accessories
52-420
<Notes
1 kV

• Robust
• Approved down to 10
metres water depth

Cable joint, branch for


plastic-insulated cables
SAGA 11 Y

Use Compounding cast resin and hardener are


Branching of 1 kV plastic-insulated 3- and mixed in a sealed bag. After hardening the
4-core cables. Can be used in down to 10 joint becomes resistant.
metres water depth. Please note, the lower the temperature
is, the longer the hardening time will be.
Standards SAGA 11 Y ought not to be installed if the
SAGA 11 Y meets the requirements of: temperature is below -10o C.
– SS 424 14 44 Edition 1 Branching takes place with the help of
– EBR KJ 24:89 clamps, which penetrate the insulation
on the main cable. The clamps, which are
Design included in the kit, are tightened with a
The joint consists of a transparent casting torque wrench.
mould with flexible sealing rings between
the casting mould and the cable.

Designation Conductor cross section Diameter Dimensions Weight


Main cable Branch cable Main cable Branch cable L Ø
mm² mm mm kg/item

SAGA 11 Y 16-50 10-50 15-30 5-25 500 96 4.5

14 We reserve the right to alter the design and range of our products. Kabeldon, 2009 Edition 1
Kabeldon
Kabeldon cable
cable accessories
accessories < 1 kV

• Easy installation

Cable joint, heat-shrink


for plastic-insulated cables
SMKC

Accessories < 1 kV
Use Design
For jointing 1 kV plastic-insulated cables SMKC 11-5 contains one outer and five
with 3-, 4- and 5-cores, with or without inner sleeves. SMKC 12-14 contain one
screen. outer and four inner sleeves.
The sleeves are made of cross-linked
Standards polyethylene, coated internally with a
Meets the requirements of: hot-melt adhesive and are installed with
– SS 424 14 44 Edition 1 heat.
– EBR KJ 24:89
To be ordered separately
– Connectors

Designation Conductor cross section Outer sleeve Weight


plastic cable before/after
heat shrinkage
Al Cu Al/Cu Length Ø max/min
mm² mm kg/item

SMKC 11-5 – 2.5-16 – 380 34/14 0.2


SMKC 12 25-50 25-70 50/25 550 66/20 0.4
SMKC 13 70-150 95-150 150/70-95 790 83/26 0.5
SMKC 14 185-240 185-240 240/120-150 950 110/40 0.9

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 15
Kabeldon
Kabeldon
Kabeldon
cable
cable
cable
accessories
accessories
accessories
52-420
<Notes
1 kV

• Fits all cable dimensions

Cable joint, tape for


plastic-insulated cables
SMILA and SMULA

Use Design
For jointing 1 kV plastic-insulated cables The kit contains insulating vulcanizing tape
with 3-, 4- and 5-cores, with or without and electrical tape. SMILA also includes a
screen. copper net. Insulating vulcanizing tape is
SMILA is used for jointing cables with used for insulation of the connectors. The
screen. Otherwise SMULA is used. stripped cable sheaths and electrical tape
are used as outer protection.
Standards The joints are packed in kits. Two
Meets the requirements of: SMILA 12 or SMULA 12 kits are used to
– SS 424 14 44 Edition 1 joint 70-150 mm² cables, and three kits are
– EBR KJ 24:89 used for 185-240 mm² cables.

To be ordered separately
– Connectors

Designation Conductor cross section Cable joint Weigh


Al Cu Length
mm2 mm kg/item

SMILA 11 – 2.5-16 420 0.2


SMILA 12 25-50 25-70 570 0.3

For larger cable cross sections, use SMILA 12 as below.


SMILA 12 (two) 70-150 95-150 770 0.6
SMILA 12 (three) 185-240 185-240 920 0.9

SMULA 11 – 2.5-16 420 0.1


SMULA 12 25-50 25-70 570 0.3

For larger cable cross sections, use SMULA 12 as below.


SMULA 12 (two) 70-150 95-150 770 0.6
SMULA 12 (three) 185-240 185-240 920 0.9

16 We reserve the right to alter the design and range of our products. Kabeldon, 2009 Edition 1
Kabeldon
Kabeldon cable
cable accessories
accessories < 1 kV

• Weather-proof
• Oil-resistant
• Flexible
• UV-resistant

Cable termination
Protective hood for
plastic-insulated cables

Accessories < 1 kV
LPH

Use Design
Termination outdoors for 1 kV plastic- The cable termination consists of a hood
insulated underground cables with made of weather-proof and oil-resistant
3-, 4- or 5-cores, 2.5-95 mm2. rubber. The cable cores are bent
downwards and fixed with tape before the
Standards hood is pushed on. Cable cores can be
Meets the requirements of: protected against UV-radiation by using
– SEN 24 14 34 IS insulating hose.

IS
Insulating hose for plastic cables, overhead cables
or for connection to aerial bundled cables. Meets
the requirements of SEN 24 21 11 and is
UV- and cold-resistant.

Designation Conductor cross section Internal Internal Weight


diameter height
3-core 4-core 5-core
mm2 mm mm kg/item

LPH 2532 16 10 – 30 83 0.1


LPH 4052 50 35 10 49 137 0.1
LPH 6070 95 70 16 67 176 0.3
LPH 70 – 95 – 68 175 0.3

To be ordered separately
Designation Conductor cross section Thickness Length Weight
mm2 mm m/roll kg/roll

IS 16 2.5-16 0.7 25 0.7


IS 50 25-50 1.0 25 1.5
IS 95 70-95 1.2 25 2.3

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 17
Kabeldon
Kabeldon
Kabeldon
cable
cable
cable
accessories
accessories
accessories
52-420
<Notes
1 kV

• Weather-proof
• Oil-resistant
• Impact resisting
• UV-resistant

Cable termination
Protective hood for
plastic-insulated cables
LXAC

Use Design
Termination outdoors for 1 kV plastic- The cable termination consists of a bush-
insulated underground cables, 2-, 3- or ing and hood made from impact-resistant
4-cores 2.5-35 mm2. black polyethylene. The cable cores are
bent downwards and pushed into grooves
Standards in the bushing before the hood is pushed
Meets the requirements of: on. Cable cores can be protected against
– SEN 24 14 34 UV-radiation by using IS insulating hose.

IS
Insulating hose for plastic cables, overhead cables
or for connection to aerial bundled cables. Meets
the requirements of SEN 24 21 11 and is UV- and
cold-resistant.

Designation Conductor cross section Max External Height Weight


polymeric cable cable diameter
3-, and 4-core diameter Ø
mm² mm mm mm kg/item

LXAC 116 16 27 60 100 0.1


LXAC 135 35 31 75 125 0.1

To be ordered separately
Designation Conductor cross section Thickness Length Weight
mm² mm m/roll kg/roll

IS 16 2.5-16 0.7 25 0.7


IS 50 25-50 1.0 25 1.5

18 We reserve the right to alter the design and range of our products. Kabeldon, 2009 Edition 1
Kabeldon
Kabeldon cable
cable accessories
accessories < 1 kV

• UV-resistant
• Double insulation

Protective Hood
Connection protection
for plastic-insulated cables

Accessories < 1 kV
KAL

Use Design
Enclosed connection protection for KAL is made from UV-resistant PVC latex
transformer bushings 1 kV. and consists of an inner yellow and an
outer black layer.
Standards These layers provide double insulation,
Electrical breakdown strength > 40 kV. at the same time as the inner yellow layer
functions as a warning signal in the event
of wear or damage to the protection.
Each kit includes three hoods.

Designation Max cable diameter Max bushing diameter Weight


A B
mm mm kg/kit

KAL 11 15 35 50 0.70
KAL 12 20 50 75 1.25

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 19
Kabeldon
Kabeldon
Kabeldon
cable
cable
cable
accessories
accessories
accessories
52-420
<Notes
1 kV

• Dimensioned according
to the cable loading and
short-circuit data

Cable connection , prefabricated


AK-ADAS

Use
For the extension of Al cable, for example
in conjunction with connection in cable
distribution cabinets, service distribution
boards and switchgears. Dimensioned in
accordance with the cable loading and
short-circuit data.

Standards
Meets the requirements of:
– SEN 24 50 10 Edition 1
– SEN 24 50 12 Edition 1

Design
Flexible XLPE-insulated Cu conductor
compressed onto a prefabricated Al/Cu
cable connection. The aluminium part is
designed for crimping with the Elpress
system. The length of all the connectors
are 700 mm.

Designation Fits aluminium Conductor Weight


conductor cross section of
cross section connector
mm2 mm2 kg/kit

AK-ADAS 5025-7 50 25 0.2


AK-ADAS 7035-7 70 35 0.3
AK-ADAS 9550-7 95 50 0.5
AK-ADAS 12070-7 120 70 0.5
AK-ADAS 15070-7 150 70 0.6
AK-ADAS 185120-7 185 120 0.9
AK-ADAS 240120-7 240 120 1.0

20 We reserve the right to alter the design and range of our products. Kabeldon, 2009 Edition 1
Kabeldon cable accessories for XLPE cables 12-36 kV

Table of contents
Cable accessories 12-36 kV

Page No.

Accessories XLPE 12-36 kV


Introduction ........................................................................................................................... 22

Cable accessories for XLPE-insulated cables


Quick guide to choosing cable accessories for XLPE-insulated cables ............................... 23
Dimensional drawings for installation of cable terminations ................................................. 24
Cable terminations with resistive/refractive field control 10-36 kV, SOT .............................. 25
Cable connectors, screened separable 12-24 kV, SOC ........................................................ 29
Cable termination, shrouded 12 kV, TB-A 12 ........................................................................ 35
Cable termination, shrouded 12-24 kV, KAP 12-24 kV ......................................................... 36
Cable joint with geometrical field control,12-24 kV, SOJ ...................................................... 40
Cable joint with resistive/refractive field control, tape 12-36 kV, SMXB ............................... 46
Cable cabinet for branching 12-24 kV, HDC ......................................................................... 49
Screen separation kit, PSSK, PSSK-E .................................................................................. 53
Branch seal kit, TSH .............................................................................................................. 54
Earthing kits for cable terminations, JXT, JSA ...................................................................... 55
Screen connection for cable joints, JSA ............................................................................... 56
Armouring kit, ARM ............................................................................................................... 57
Connectors ............................................................................................................................ 58
Bird protection ....................................................................................................................... 60

Cable accessories for paper-insulated cables


Cable termination 12 kV, OTIA .............................................................................................. 61
Cable joint and repair joints 12 kV, SMTD ............................................................................. 63
Cable joint, transition 12 kV, SMTXB ..................................................................................... 65
Cable joint, transition 24-36 kV, SMTXD .............................................................................. 66
Cable joints 24-52 kV, SMTA and SMTPA ............................................................................ 67
Dimensional drawings, SMT.................................................................................................. 68
Spring-loaded gaskets .......................................................................................................... 69
Accessories for joints and transition joints............................................................................ 70

General accessories .............................................................................................................. 72


Tools ...................................................................................................................................... 75

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 21
Kabeldon cable accessories for XLPE cables 12-36 kV

Introduction
Cable accessories 12-36 kV

Kabeldon cable accessories for 12-36 kV


are characterized by simple solutions with
a reliable function. Long experience and
continuous product development enable
us to offer products that meet future
Easy and safe installation with products from ABB
requirements for reliable and dependable Kabeldon.
systems.
At the time when XLPE cable was Manufacturing the products from soft
introduced in the beginning of the 1960s, we rubber also means that fewer sizes are
already appreciated the importance of the required to cope with different cable
cable accessories having a constant, active dimensions. All of this, in combination
pressure over the cable, in this way with the bolt technology
following the physical changes in the cable that we use in our cable
in service. The solution at the time was to connectors and cable lugs,
use tapes with different properties. Our gives a reliable and
patented field-control material and the first dependable system.
premoulded products were introduced in More than one million
the 1970s. The technology has since been a premoulded cable joints,
guiding force for our product development. terminations and connectors
have already been installed
by customers in
electricity distribution
networks all over the world.
Cable accessories with four important functions: Our cable terminations and
control of electrical fields, control of creepage currents, screened separable cable
moisture barriers and mechanical protection. connectors are also p
urchased by customers who manufacture
switchgears and other installations.
Our current range includes cable joints,
In addition to the products presented in
cable terminations and screened
this catalogue, we offer specially adapted
separable cable connectors in line with
products and solutions for different
this concept. The fact that the products
markets and cables and a range of cable
are premoulded means that they are
preparation tools. Please do not hesitate
manufactured in
to contact us if you have any other needs
a single piece
or queries.
and that important
functions such
as electrical
field-control,
insulation and
sealing are
already built in at
the factory. The use of flexible materials
gives an active pressure, which follows
variations in the cable under loading.

22 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories for XLPE cables 12-36 kV

Quick guide to choosing


cable accessories for
XLPE-insulated cables
12-36 kV

The kits shown in this section of the catalogue can be used on cables with copper wire
screen, as described.

Accessories XLPE 12-36 kV


For other types of screen, the accessories must be adapted as follows:

3-core cables with copper Three 1-core cables


tape screen and armouring with Al foil screen

Armouring
Copper tape screen Aluminium foil

Indoor termination
1. Termination type SOT Page 25-28
2. Earthing kit type JSA Page 55
Suitable kits of cable joints,
terminations and screened Outdoor termination
separable connectors are 1. Termination type SOT-31 Page 25-28
available for this cable type. 2. Earthing kit type JSA Page 55
Contact us for information.
Screened separable connector
1. Connector type SOC Page 29-34
2. Earthing kit type JSA Page 55

Insulated connector
1. Connector type KAP Page 36-39
2. Earthing kit type JSA Page 55

Prefabricated joint
1. Three joints type SOJ-1 Page 40-45
2. Screen connection kit
type JSA 14-16 Page 56

Taped joint Taped joint


1. Joint type SMXB -3 Page 46-48 1. Joint type SMXB -3 Page 46-48
2. Screen connection kit 2. Screen connection kit
type JSA 10-13 Page 56 type JSA 14-16 Page 56
3. Armouring kit type ARM Page 57

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 23
Kabeldon cable accessories
Kabeldon cable
for XLPE
accessories
cables 12-36 kV

Dimensional drawings for All dimensions in mm

installation of cable termination

Minimum air gap C B A

Max voltage Indoor Outdoor


kV phase to phase to phase to phase to phase to
earth A phase B phase C earth A phase B

10 90 90 10 130 130
12 120 120 10 160 160
24 220 250 30 270 270
36 320 370 50 380 380

Minimum air gap between cores in parallel


10 kV 12 kV 24 kV 36 kV
C 10 mm 10 mm 30 mm 50 mm

24 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories for XLPE cables 12-36 kV

• Cold-applied
• Can be used in small spaces
• No special tools
• Premoulded for easy and
safe installation
Cable termination • Minimal cable stripping
• Active pressure
indoor, premoulded • Few components
• Long shelf life
SOT 10 kV

Use
Premoulded cable termination for XLPE-

Accessories XLPE 12-36 kV


insulated cables with Al or Cu conductor for
6.6/10 kV, indoors.
It can also be installed in an indoor humid
environment.
135

Standards

00
Min 2
Meets the requirements of:
CENELEC
– HD 629.1 S1

Design
Premoulded cable termination; rubber
sleeve with integrated field control.
The length of the termination is approx.
145 mm which also makes it suitable for
installations in narrow spaces.
The terminations are supplied in kits for
3-phase cables.
Kits with outdoor terminations for 3-core
cables include crutch seal and protective
heat shrink hoses.

Designation XLPE-Ø Conductor Weight


cross section
mm mm2 kg/kit

3-core / three 1-core


SOT 101-3 10.5-15 10-35 0.2
SOT 102-3 12.9-25.8 50-185 0.2
SOT 103-3 21.4-34.9 185- 500 0.2

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 25
Kabeldon cable accessories
Kabeldon cable
for XLPE
accessories
cables 12-36 kV

• Cold-applied
• No special tools
• Premoulded for easy
and safe installation
• Minimal cable stripping
Cable termination • Active pressure
• Few components
indoor and outdoor, • Long shelf life

premoulded
SOT 12-36 kV

Use
Premoulded termination for XLPE-insulated
cables 1- or 3-core with Al or Cu conductors
for 12-36 kV.
The indoor termination can also be
installed in a humid indoor environment.

Standard
Meets the requirements of:
CENELEC
– HD 629.1 S1
– IEEE 48 1996*

Design
Premoulded cable termination made of
rubber with integrated field control and top
sealing. The outdoor variant has permanent
SOT 1- and 3-core SOT 1- and 3-core
sheds which give a prolonged creepage indoor. outdoor.
distance.
The terminations are supplied in kits for Kits with outdoor terminations for 3-core
1- or 3-phase cables. cables include crutch seal and protective
heat shrink hoses.
Designation Weight Designation Weight XLPE-Ø Conductor cross section
12 kV 24 kV 36 kV
kg/kit kg/kit mm mm²

Indoor termination Indoor termination


3-core / 3 x 1-core 1-phase kit
SOT 241 A-3 0.60 SOT 241 A 0.20 11-15 10-35 10 –
SOT 241-3 0.60 SOT 241 0.19 15-28 50-185 25-120 –
SOT 242-3 0.70 SOT 242 0.23 24-39 240-500 150-400 –
SOT 242 B-3 0.90 SOT 242 B 0.30 38-54 630** 500-630** –
Outdoor termination Outdoor termination
incl. crutch seal for 3-core 1-phase kit
SOT 243 A-3 1.90 SOT 243 A 0.31 11-15 10-35 10
SOT 243-3 1.80 – – 15-24 50-120 25-70 –
SOT 244-3 2.00 – – 22-33 150-300 95-240 –
SOT 245-3 2.50 – – 31-40 400-500 300-400 –
Outdoor termination Outdoor termination
3 x 1-core 1-phase kit
SOT 243-31 0.80 SOT 243 0.27 15-24 50-120 25-70 –
SOT 244-31 0.90 SOT 244 0.30 22-33 150-300 95-240 –
SOT 245-31 1.11 SOT 245 0.38 31-40 400-500 300-400 –
SOT 246-31 1.50 SOT 246 0.51 38-54 500-630** 500-630** –
Indoor/outdoor termination Indoor/outdoor termination
3 x1-core 1-phase kit
SOT 361-31 1.40 SOT 361 0.42 26-39 – – 95-300
SOT 362-31 1.60 SOT 362 0.52 38-54 – – 400-630**
* Is valid for outdoor terminations (SOT 243 A-SOT 246).
** Can be mounted on cables with 800 and 1000 mm2, by using
silicone rubber tape IA 2342 as top seal, see "General accessories".
For selecting accessories see the following pages.

26 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories for XLPE cables 12-36 kV

Kits complete with screw cable lug


Cable termination including bi-metallic

Accessories XLPE 12-36 kV


screw cable lug for Al and Cu conductors.
The cable lug is equipped with shear-off bolts.

Designation Weight Designation Weight Cable cross section


12 kV 24 kV
kg/kit kg/kit mm²

1-core indoor 3 -core / 3 x 1-core indoor


SOT 241A S1 0.35 SOT 241A-3 S1 1.05 16 - 35 16
SOT 241 S1 0.34 SOT 241-3 S1 1.02 50 - 70 25 - 70
SOT 241 S2 0.44 SOT 241-3 S2 1.32 95 - 150 95 - 120
SOT 241 S3 0.59 SOT 241-3 S3 1.50 185 –
SOT 242 S2 0.48 SOT 242-3 S2 1.44 – 150
SOT 242 S3 0.63 SOT 242-3 S3 1.89 240 185 - 240
SOT 242 S4 0.98 SOT 242-3 S4 2.94 300 - 400 300 - 400
SOT 242B S5 1.78 SOT 242B-3 S5 5.25 500 - 630 500 - 630

1-core outdoor 3-core outdoor


SOT 243A S1 0.46 SOT 243A-3 S1 1.56 16 - 35 16
SOT 243 S1 0.42 SOT 243-3 S1 1.42 50 - 70 25 - 70
SOT 243 S2 0.52 SOT 243-3 S2 1.52 95 - 120 –
SOT 244 S2 0.55 SOT 244-3 S2 1.65 150 95 - 150
SOT 244 S3 0.70 SOT 244-3 S3 1.80 185 - 240 185 - 240
SOT 244 S4 1.05 SOT 244-3 S4 2.15 300 –
SOT 245 S4 1.13 SOT 245-3 S4 2.51 400 300 - 400
SOT 245 S5 1.83 SOT 245-3 S5 3.15 500 –
SOT 246 S5 1.96 – – 630 500 - 630

3 x 1-core outdoor
SOT 243 A-31 S1 1.38 16-35 16
SOT 243-31 S1 1.26 50-70 25-70
SOT 243-31 S2 1.56 95 - 120 –
SOT 244-31 S2 1.65 150 95 - 150
SOT 244-31 S3 2.10 185 - 240 185 - 240
SOT 244-31 S4 3.15 300 –
SOT 245-31 S4 3.40 400 300 - 400
SOT 245-31 S5 5.50 500 –
SOT 246-31 S5 5.90 630 500 - 630

1-core indoor/outdoor 36 kV
SOT 361 S2 0.67 95 - 150 –
SOT 361 S3 0.82 185 - 240 –
SOT 361 S4 1.17 300 –
SOT 362 S4 1.27 400 –
SOT 362 S5 1.97 500 - 630 –

3 x 1-core indoor/outdoor 36 kV
SOT 361-31 S2 2.10 95 - 150 –
SOT 361-31 S3 2.46 185 - 240 –
SOT 361-31 S4 3.50 300 –
SOT 362-31 S4 3.80 400 –
SOT 362-31 S5 5.95 500 - 630 –

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 27
Kabeldon cable accessories
Kabeldon cable
for XLPE
accessories
cables 12-36 kV

Dimensional drawings All dimensions in mm

and accessories
SOT

I
L

Creepage distance
L
I
I

SOT, indoor SOT, outdoor

Designation l L D Creepage
mm distance

SOT 241/242/242 B 235 min 300 – –


SOT 243/244/245 330 min 430 70/75/80 min 520
SOT 246/361/362 390 min 500 80/85 min 725

To be ordered separately
Designation Description See page

SKSA, SKSB Cable lug 59


UKR Universal clamp for fastening cable to a pole, etc. 108
JSA, JXT Earthing kits when the cable does not have a Cu wire screen 55
FK Overhead line clamp 58
PSSK Screen separation kit (indoor) 53

28 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories
Kabeldon cable
for XLPE
accessories
cables 12-36 kV

• Cold-applied
• No special tools
• Premoulded for simple
and safe installation
• Minimal cable stripping
Cable connectors, premoulded • Active pressure
• Complete kits
screened separable 250 A • Few sizes
• Long shelf life
SOC 250 TP, SOC 250 STP
12-24 kV

Use
Screened separable plug-in connectors for

Accessories XLPE 12-36 kV


XLPE-insulated 1- or 3-core cables with Al or
Cu conductor for 12-24 kV. Can be installed
indoor as well as outdoor.
The connector fits standard bushings in
accordance with EN 50181, type outer cone.

Standards
Meets the requirements of:
– SS 244 14 45 Edition 1 SOC 250 TP SOC 250 STP
Elbow connector. Straight connector.

CENELEC
– HD 629.1 S1

Design
The connector is made of rubber in three
layers: inner conductive layer, insulating
layer and outer conductive layer.
A metallic part is moulded into the
insulation which makes it possible to
perform voltage check. The metallic part
is protected by a cover which is easily
removed when checking the voltage.
The connector meets the requirements
for being touch-proof. Note: For 3-core cable with common
The connectors are supplied in kits of Cu-screen wires, a screen separation kit
three. Supplied complete with screw cable must be used. See page 53.
lug for the cable.

Designation XLPE/EPR Conductor* Bushing Weight


diameter cross section type
mm mm² kg/item

Angled connector with capacitive test point


SOC 250 TP 12.5-25.8 25-95 Plug-in Ø 7.9 2.2

Straight connector with capacitive test point


SOC 250 STP 12.9-25.8 25-95 Plug-in Ø 7.9 2.2
* For 10 and 16 mm² cables, use AK 250 as accessory, see next page.

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 29
Kabeldon cable accessories
Kabeldon cable
for XLPE
accessories
cables 12-36 kV

Dimensions and accessories All dimensions in mm

SOC 250

140
C 2x45° Ø 63 C-C min 65
R1 R3 124

Ø 32.5
Ø 48.5

Ø 31
Ø 90

Ø 52
9 48
3.5
1

Bail holder Ø 54
Ø4
210
Standard bushing EN 50181
200 series 250 A
Contact type: Plug-in Ø 7.9 mm
Interface type: A

260
Ø 65

Fits bushing 200 series


250 A as above.

CU 250 JP 250 IP 250


Coupling piece to connect two Earth circuit connector Screened insulating plug for installation in
connectors. The kit consists of a for short-circuit the connector so that the cable can
double epoxy bushing with fixing protective earthing to be energized even when disconnected
lugs bail restrain to SOC and a be mounted on from the switchgear or transformer.
screw connector SH-SKR 35 to disconnected
connect the screen of the cable. connector.

MA 250
Measurement adapter used for mega
 measurements and to perform different
AK 250 measurements up to 5 kV DC,
IH SOC 250 TP Kit of accessories, allowing for example determination of phases.
Insulating hood of flexible rubber installation on smaller cables with
with outer conductive layer and a conductor cross section
preinstalled insulating rod. 10-16 mm2.
To be mounted on the bushing The kit consists of three
in a 250 A switchgear or a adapters and three inserts. Every LBR 250
transformer to insulate it when a insert is made of tinned copper Extended bail restrain for
cable is temporarily disconnected and is clamped to the conductor SOC 250 STP for installation in
but other cables are energized. with pliers before it is installed. Schneider switchgear MGRM6.

Designation Description Qty. Weight


kg/item

CU 250 Coupling piece to connect two connectors 1 0.2


MA 250 Measurement adapter 1 0.3
JP 250 Earth kit 1 2.7
IP 250 Insulating plug 1 0.8
IH SOC 250 TP Insulating hood 3 2.3
AK 250 Accessories kit 3 0.2
LBR 250 Extended bail restrain 3 0.01
PSSK, PSSK-E Screen separation kit for 3-core cable See page 53 1.0

30 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories
Kabeldon cable
for XLPE
accessories
cables 12-36 kV

• Cold-applied
• No special tools
• Premoulded for simple
and safe installation
• Minimal cable stripping
Cable connectors, premoulded • Active pressure
• Complete kits
screened separable 400 A • Few sizes
• Long shelf life
SOC 400, 12-24 kV

Use
Screened separable plug-in connectors for

Accessories XLPE 12-36 kV


XLPE-insulated 1- or 3-core cables with
Al or Cu conductors for 12-24 kV. Can be
installed indoor as well as outdoor.
The connectors fit standard bushings type
outer cone according to EN 50181 type plug-in.

Standards
Meets the requirements of:
– SS 244 14 45 Edition 1

CENELEC
– HD 629.1 S1

Design SOC 400 SOC 400 TP


The connector is made of rubber in three Elbow connector. Elbow connector
with capacitive test
layers: inner conductive layer, insulating layer point.
and outer conductive layer.
The connector meets the requirements for
being touch-proof.
The connectors are supplied in kits of three.
Supplied complete with screw cable lug Note: For 3-core cables with common
and plug-in connection. Cu-screen wires, a screen separation kit
must be used. See page 53.

Designation XLPE/EPR Conductor Bushing Weight


diameter cross section type
mm mm² kg/item

Angled connectors
SOC 400-1 15.0-26.8 50-120* Plug-in Ø 14 5.6
SOC 400-2 21.4-34.9 150-300 Plug-in Ø 14 6.0

Angled connector with capacitive test point


SOC 400-1 TP 15.0-26.8 50-120* Plug-in Ø 14 5.6
SOC 400-2 TP 21.4-34.9 150-300 Plug-in Ø 14 6.0
* For 35 mm² contact us.

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 31
Kabeldon cable accessories for XLPE cables 12-36 kV

Dimensions and accessories All dimensions in mm

SOC 400

210
Ø 78 C-C min 85 172

Ø 68

250

R3 40
R3 R3
Ø 102

Ø 56
Ø 46
Ø 70

11 90
5.5 Standard bushing EN 50181
Bail holder 400 series 400 A
Contact type: Plug-in Ø14
Interface type: B

JP 400 IP 400 IH SOC 400


Earth circuit connector for Screened insulating plug for Inuslating hood of flexible rubber
short-circuit protective earthing. installation in the connector so with outer conductive layer and a
To be mounted on the that the cable can be energized preinstalled insulating rod.
disconnected connector. even when disconnected from the To be mounted on bushing in
switchgear or transformer. a 400 A switchgear or transformer
to insulate it when a cable is
temporarily disconnected but other
cables are energized.
Designation Description Qty. Weight
kg/item

JP 400 Earth circuit connector 1 2.2


IP 400 Insulating plug 1 2.2
IH SOC 400 Insulating hood 3 5.7
PSSK, PSSK-E Screen separation kit for 3-core cable See page 53 1.0

32 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories
Kabeldon cable
for XLPE
accessories
cables 12-36 kV

• Cold-applied
• No special tools
• Premoulded for simple
and safe installation
• Minimal cable stripping
Cable connectors, premoulded •

Active pressure
Complete kits
screened separable, 630 A • Few sizes
• Long shelf life
SOC 630, 12-24 kV

Use
Screened separable connector for

Accessories XLPE 12-36 kV


XLPE-insulated 1- or 3-core cables
with Al or Cu conductors for 12-24 kV.
Can be installed indoor as well as
outdoor.
The connectors fits standard bushings
type outer cone in accordance with
EN 50181 for 400 series M16 bolt.

Standards
Meets the requirements of:
– SS 244 14 45 Edition 1

CENELEC
– HD 629.1 S1 SOC 630 SOC 630 TP SOC 630
Elbow Elbow connector with Elbow connector
connector. capacitive test point. for larger cables.
Design
The connector is made of rubber in three
layers: inner conductive layer, insulating
layer and outer conductive layer.
The connector meets the requirements for Note: For 3-core cables with common
being touch-proof. Cu-screen wires, a screen separation kit
The connectors are supplied in kits of must be used. See page 53.
three. Supplied complete with screw cable
lug and screw connection.

Designation XLPE/EPR Conductor Bushing Weight


diameter cross section type
mm mm2 kg/item

Angled connectors
SOC 630-1 15.0-26.8 50-120 Bolt M16 5.1
SOC 630-2 21.4-34.9 150-300 Bolt M16 5.5
SOC 630-3 31.5-42 400 Bolt M16 7.8
SOC 630-4 31.5-42 500 Bolt M16 7.7
SOC 630-5 40-46 630 Bolt M16 7.6

Angled connector with capacitive test point


SOC 630-1 TP 15.0-26.8 50-120* Bolt M16 5.1
SOC 630-2 TP 21.4-34.9 150-300 Bolt M16 5.5
SOC 630-3 TP 31.5-42 400 Bolt M16 7.8
SOC 630-4 TP 31.5-42 500 Bolt M16 7.7
SOC 630-5 TP 40-46 630 Bolt M16 7.6
* For 35 mm² contact us.

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 33
Kabeldon cable accessories for XLPE cables 12-36 kV
Dimensions and accessories All dimensions in mm

SOC 630
Ø 78 C-C min 85 170 172 172
R3 29
R3 1.5 R3

Ø 46
Ø 56
Ø 70

Ø 68
90
11
250
Standard bushing EN 50181
400 series 630 A
Contact type: Bolted M16
Interface type: C
SOC 630 1/2
89.5 90 202 202 202

Ø 90

317

SOC 630 3/4/5

PC 630
Parallel coupling piece. PG 630 IP 630 PC 630/250
Replaces the plug in Bushing for voltage testing of Screened insulating plug for Parallel coupling piece.
SOC 630-1/2 when making the cable. installation in the connector Replaces the plug in
a parallel connection to SOC 630 does not need to so that the cable can be SOC 630-1/2 when making
SOC 630-1/2/3/4/5. be removed from its position. energized even when a parallel connection to
The test bushing is installed disconnected from the SOC 250 TP.
on the connector instead of the switchgear or transformer.
insulating plug.

MA 630
Measurement adapter used
for mega  measurements to
PC 630 L
perform different measurements
Parallel coupling piece.
up to 5 kV DC, for example
Replaces the plug in
JP 630 determination of phases.
SOC 630-3/4/5 when IH SOC 630
parallel connection with Earth circuit connector Insulating hood of flexible rubber
SOC 630-1/2/3/4/5. for short-circuit with outer conductive layer and a
protective earthing preinstalled insulating rod.
to be mounted on To be mounted on the HBS 10
the disconnected bushing in a 630 A switchgear or Extended hex bit socket 10 mm
connector. transformer to insulate it when a with 1/2" drive for torque
cable is temporarily disconnected wrench. For installation of
but other cables are energized. PC 630 and PC 630 L.

Designation Description Qty. Weight


kg/item

PC 630 Parallel connector between two SOC 630 1 1.1


PC 630 L Parallel connector between two SOC 630 3/4/5 1 1.2
PC 630/250 Parallel connector between SOC 630 and SOC 250 3 3.0
PG 630 Test bushing 1 1.5
IP 630 Screened insulating plug 1 2.2
JP 630 Earthing kit 1 5.0
IH SOC 630 Sealing hood 3 5.2
MA 630 Measurement adapter 3 0.1
HBS 10 Hex bit socket 1 0.1
PSSK Screen separation kit for 3-core cable See page 53 1.0

34 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories for XLPE cables 12-36 kV

• No special tools
• Easy measurement
• Easy installation
• Complete kits
• Active pressure
Shrouded termination for
XLPE-insulated cables 12 kV
TB-A 12

Use
Shrouded cable termination for connecting

Accessories XLPE 12-36 kV


XLPE-insulated cables, 12 kV in switchgear,
type ABB SafeLink.

Standards
Meets the requirements of:
– CENELEC, HD 629

Design
TB-A is a shrouded termination made of
rubber. Supplied in complete 3-core kits
including cable terminations, two-piece
boots, cable lugs with shear-off bolts, grease,
cleaning cloth and installation instructions.
Due to the smart installation method the
upper part of the two-piece boot will stick
to the bushing.
When necessary for measuring, the lower
part of the boot can easily be pulled down
to expose the palm of the bushing.

Note: For 3-core cables with common


Cu-screen wires, a screen separation kit
must be used. See page 53.

Connector Designation Length Weight


cross section
mm² mm kg/kit

Three 1-core or one 3-core kits


10 – 35 TB-A 12630-1 400 2.65
50 – 150 TB-A 12630-2 400 2.90
185 – 300 TB-A 12630-3 450 3.10

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 35
Kabeldon cable accessories for XLPE cables 12-36 kV

• No special tools
• Prefabricated for easy
and safe installation
• Complete kits
• Active pressure
Shrouded termination for
XLPE-insulated cables 12-24 kV
KAP 630

Use Design
For XLPE-insulated 1- or 3-core cables KAP is an insulated
with Al or Cu conductors for 12-24 kV. connector made
KAP can be used to connect a cable to of rubber. It is
gas-insulated SF6 switchgear and in other supplied complete
compact installations, as well as for sub- with cable termination
station transformers. and screw cable lug.
The connectors are supplied in kits of The covers are provided
three. with a removable plastic
plug to allow direct voltage
Standards testing on the conductor.
Meets the requirements of:
– SEN 24 14 34
– SS 424 14 17 Edition 4 For plug-in connector
250 A or 400 A, see SOC.

Designation Conductor Specification Weight


cross section
12 kV 24 kV
mm² kg/item

KAP 630-11 50-120 50-120* Bolt M16 2.2


KAP 630-12 150-185 – Bolt M16 2.5
KAP 630-22 240-300 150-300 Bolt M16 2.5
KAP 630-P11 50-120 50-120* Connection in parallel 2.5
KAP 630-P12 150-185 – Connection in parallel 2.5
KAP 630-P22 240-300 150-300 Connection in parallel 2.5
KAP 630-S12 – – Surge arrester 7.7
KAP 630-S24 – – Surge arrester 10.5
* For 35 mm² contact us.

Technical data of surge arresters for KAP


Designation Maximum Voltage- Residual voltage at impulse Temporary over voltage capability kV
voltage class current 8/20 µs kV 1 seconds 3 seconds 10 seconds
Um KV U kV 1 kA 5 kA 10 kA 20 kA A B A B A B

KAP 630-S12 12 10 26.0 29.0 30.7 34.0 13.6 13.2 13.4 12.9 13.1 12.6
KAP 630-S24 24 20 52.0 58.0 61.4 68.0 27.2 26.3 26.7 25.7 26.2 25.1
A = Before impulse current Value A & B has been determined with a test sample
B = After 4/10 µs 100 kA impulse current. preheated at 60OC according to IEC 60099-4 and refer to an
ambient temperature of up to 45O C.

To be ordered separately for 3-core cable


Designation Description See page

PSSK, PSSK-E Screen separation kit 53

36 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories
Kabeldon cable
for XLPE
accessories
cables 12-36 kV

Dimensional drawings All dimensions in mm

KAP 630

185 A B C D ~316

130

Accessories XLPE 12-36 kV


86

260

C-C 133
70

KAP 630 KAP 630 P

D Recommended minimum Recommended minimum air gap


distances
The indicated recommended Voltage Insulation A B C D
minimum distances are generally kV level kV mm
applicable. For applications in 12 75 50 10 90 10
which type testing has been 24 125 90 30 110 50
performed, other minimum
distances may be applied.
This is the case, for example,
for gas-insulated Ring Main Unit
(RMU).

KAP 630-S
KAP 630 with surge arrester.

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 37
Kabeldon cable accessories for XLPE cables 12-36 kV

• No special tools
• Cold-applied

Insulating boot for 12-24 kV


KAP 300 U

Use
For XLPE-insulated 1- or 3-core cables
with Al or Cu conductors, for 12-24 kV.
KAP 300 U is especially well suited for
the renovation of, for example, oil-filled
transformer boxes, when replacing paper-
insulated cable with XLPE cable. An indoor
termination type SOT (must be ordered
separately) is installed together with
KAP 300 U on the XLPE cable, thus
insulating the connection point when the
oil is drained from the cable box.
KAP 300 U can also be mounted straight.

Standards
Meets the requirements of:
– SEN 24 14 34
– SS 424 14 17 Edition 4

Design
An insulating boot made of rubber.
The covers are fitted with a removable
plastic plug to allow direct voltage testing on
the conductor.
Termination and cable lug are not included.

NB.
See dimensional drawings on the next page
for minimum distance to earth.

Designation Conductor Specification Weight


cross section
12 -24 kV
mm² kg/item

KAP 300 U 25-300 Bolt 2.0

To be ordered separately for 3-core cable


Designation Description See page

PSSK, PSSK-E Screen separation kit 53


SKSB Screw cable lug 59
SOT Cable termination 25

38 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories
Kabeldon cable
for XLPE
accessories
cables 12-36 kV

Dimensional drawings All dimensions in mm

KAP 300 U

210

Accessories XLPE 12-36 kV


78

195

A B C D

44

345

Straight KAP 300 U. Recommended minimum distances


The indicated recommended minimum distances are
generally applicable.

Recommended minimum air gap


Voltage Insulation A B C D
kV level kV mm
12 75 50 10 90 10
24 125 110 50 130 50

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 39
Kabeldon cable accessories
Kabeldon cable
for XLPE
accessories
cables 12-36 kV

• Cold-applied
• No special tools
• Premoulded for easy
and safe installation
• Active pressure
Cable joint, premoulded • Few components
• Long shelf life
with cold shrink outer sheath • Reliable
• Joint bodies routine-
SOJ 12-24 kV tested

Use Outer sheath is to be selected as below:


Premoulded cable joint for XLPE-insulated
1- or 3-core cables with Al or Cu conductors, SOJ CSS
12-24 kV. Contains cold-shrink outer sheath and screw
connectors for conductor and screen.
Standards
– HD 629.1 S1 SOJ CS
– IEEE 404 1993 Contains cold-shrink outer sheath.
– SS 424 14 45 Edition 1 Connectors are not included.
– VDE 0278
– KEMA S8
For 16-35 mm2 cables ADAPTER must be
Design ordered separately, see following pages.
The joint body is made of rubber in three WIM 3 / WIM 4 – To be used as complement
layers: a conductive outer layer, an insulating when jointing 3-core watertightened cable,
and a conductive inner layer. see following pages.
The kit contains all mounting material.

SOJ CSS

Cable cross section XLPE- Designation CSS CS Designation CSS CS


12 kV 24 kV diameter 1-core Weight Weight 3-core Weight Weight
mm² mm kg/kit kg/kit kg/kit kg/kit

50-70 – 15-19.5 SOJ 121-1 2.5 2.4 SOJ 121-3 5.0 4.7
95-150 – 18.5-24 SOJ 122-1 2.6 2.5 SOJ 122-3 5.5 5.2
185-240 – 23-28 SOJ 123-1 3.4 3.2 SOJ 123-3 7.0 6.2
300-400 – 27-34 SOJ 124-1 4.7 4.2 SOJ 124-3 – 7.3
500-630 – 33.5-46 SOJ 125-1 5.5 4.8 – – –

– 50-70 19-23.5 SOJ 241-1 3.3 3.2 SOJ 241-3 5.8 5.5
– 95-150 22.5-28 SOJ 242-1 3.6 3.5 SOJ 242-3 6.9 6.5
– 185-240 27-35 SOJ 243-1 4.3 4.0 SOJ 243-3 8.8 8.0
– 300 27-35 4.5 4.0 – – –
– 400 33.5-46 SOJ 244-1 5.3 4.8 – – –
– 500-630 33.5-46 5.5 4.8 – – –

To be ordered separately
Accessories Use SOJ CSS SOJ CS See page

ADAPTER Cables with different dimensions – X 43


JSA 10-13 Cables with copper tape screen – X 56
JSA 14-16 Cables with aluminium foil screen – X 56
TS Additional kit for sector shaped 3-core cables X X 43
SH-SKRM Screw connector – X 59
STOP Crutch-seal for three 1-core cables X X 43

40 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories for XLPE cables 12-36 kV

• Cold-applied
• No special tools
• Premoulded for easy
and safe installation
• Active pressure
• Few components
Premoulded cable joint for • Long shelf life
radially watertightened cable • Reliable
• Joint bodies routine-
SOJ 12-24 kV tested

Use There are different variations of the cable


Premoulded cable joint for XLPE-insulated joints depending to the cable construction
1- or 3-core cables with Al or Cu conductor according to the following:

Accessories XLPE 12-36 kV


and radially watertightened aluminium foil
for 12-24 kV. SOJ CSWS
Used for jointing watertightened 1-core
Standards cable with copper wire screen. Contains
– VDE 0278 cold-shrink cable sheath, Al foil tube and
– HD 629.1 S1 also connectors for conductor and screen.
– IEEE 404 1993
– SS 424 14 45 edition 1 SOJ RWI
– KEMA S8 Used for jointing three 1-core cables,
Prysmian type WISKITM or similar. Contains
Design copper braids to connect screens, Al foil
The joint body is made of rubber in three tubes for radially watertightness and also
layers: a conductive outer layer, an outer sheath RULLE.
insulating and a conductive inner layer. Connectors and items for jointing of
The kit contains all mounting material. separate earth wire are not included.

SOJ RWIT
Used for jointing three 1-core cables
SOJ CSWS
Prysmian type WISKITM or similar, to a
standard 3-core cable. Contains copper
braids to connect screens, STOP longitudinal
watertightness and outer sheath RULLE.
SOJ RWI Connectors and articles for jointing a
separate earth wire are not included.
For 16-35 mm2 cables, ADAPTER must be
ordered separately, see the table below!
SOJ RWIT

Cable cross section XLPE- Designation CSWS Designation RWI RWIT


12 kV 24 kV diameter 1-core Weight 3 x 1-core Weight Weight
mm² mm kg/kit kg/kit kg/kit

50-70 – 15-19.5 SOJ 121-1 50 3.0 SOJ 121-31 7.3 5.0


95-150 – 18.5-24 SOJ 122-1 95150 3.2 SOJ 122-31 7.9 5.5
185-240 – 23-28 SOJ 123-1 240 4.0 SOJ 123-31 10.3 7.0
300-400 – 27-34 SOJ 124-1 400 5.3 – – –
500-630 – 33.5-46 SOJ 125-1 630 6.1 – – –

– 50-70 19-23.5 SOJ 241-1 50 3.9 SOJ 241-31 10.0 5.5


– 95-150 22.5-28 SOJ 242-1 95150 4.2 SOJ 242-31 10.9 6.5
– 185-240 27-35 SOJ 243-1 240 4.9 SOJ 243-31 13.0 8.0
– 300-400 33.5-46 SOJ 244-1 400 5.9 – – –
– 500-630 33.5-46 SOJ 244-1 630 6.1 – – –

Accessories Use SOJ CSWS SOJ RWI SOJ RWIT See page

Adapter Adapter kit for cables with different dimensions X X X 43


TS Additional kit for sector shaped cables X 43
SH-SKRM Screw connector X X 59

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 41
Kabeldon cable accessories
Kabeldon cable
for XLPE
accessories
cables 12-36 kV

• Cold-applied
• No special tools
• Premoulded for easy
and safe installation
• Active pressure
Premoulded cable joint with • Few components
• Long shelf life
or without outer sheath, RULLE • Reliable
• Joint bodies routine-
SOJ 12-24 kV tested

Use Outer sheath is to be selected as below:


Premoulded cable joint for XLPE-insulated
1- or 3-core cables with Al or Cu conductor SOJ R
for 12-24 kV. Contains outer sheath RULLE, a two-layer
tape of EPDM-rubber and mastic, which is
Standards wrapped around the joint.
– HD 629.1 S1 Connectors are not included.
– SS 424 14 45 edition1
– VDE 0278 SOJ SL
– KEMA S8 Supplied without outer sheath. NB! An outer
– IEEE 404 1993 sheath approved by us must be added, for
example type ARM.
Design Connectors are not included.
The joint body is made of rubber in three
For 16-35 mm2 cables ADAPTER must be
layers: a conductive outer layer, an
ordered separately, see the table below!
insulating and a conductive inner layer.
WIM 3 / WIM 4 – To be used as
The kit contains all mounting material.
complement when jointing 3-core
watertightened cable, see the table below.

SOJ R

Cable cross section XLPE- Designation R Designation SL Designation R Designation SL


12 kV 24 kV diameter 1-core Weight Weight 3-core Weight Weight
mm² mm kg/kit kg/kit kg/kit kg/kit

50-70 – 15-19.5 SOJ 121-1 2.6 SOJ 121-1 SL 1.0 SOJ 121-3 4.7 SOJ 121-3 SL 2.0
95-150 – 18.5-24 SOJ 122-1 3.0 SOJ 122-1 SL 1.1 SOJ 122-3 5.6 SOJ 122-3 SL 2.3
185-240 – 23-28 SOJ 123-1 3.1 SOJ 123-1 SL 1.2 SOJ 123-3 6.4 SOJ 123-3 SL 2.7
300-400 – 27-34 SOJ 124-1 4.3 SOJ 124-1 SL 1.6 SOJ 124-3 8.9 SOJ 124-3 SL 4.2
500-630 – 33.5-46 SOJ 125-1 5.9 SOJ 125-1 SL 2.2 – – – –

– 50-70 19-23.5 SOJ 241-1 3.2 SOJ 241-1 SL 1.3 SOJ 241-3 6.2 SOJ 241-3 SL 2.8
– 95-150 22.5-28 SOJ 242-1 3.9 SOJ 242-1 SL 1.5 SOJ 242-3 7.0 SOJ 242-3 SL 3.4
– 185-300 27-35 SOJ 243-1 4.5 SOJ 243-1 SL 1.8 SOJ 243-3 9.1 SOJ 243-3 SL 4.5
– 400-630 33.5-46 SOJ 244-1 6.4 SOJ 244-1 SL 2.2 – – – –

Accessories Use SOJ R SOJ SL See


page

Adapter Cables with different dimensions X X 43


JSA 10-13 Cables with copper tape screen X X 56
JSA 14-16 Cables with aluminium foil screen X X 56
TS Additional kit for sector shaped 3-core cables X X 43
WIM Diffusion seal X X 44
ARM Armouring kit – X 57
STOP Branch seal for three 1-core cables X – 43
SH-SKRM Screw connector X X 59

42 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories for XLPE cables 12-36 kV

Accessories for SOJ

D
Additional kit TS
Additional kit for sector shaped 3-core cables,
for use when the D-dimension over the insulation

Accessories XLPE 12-36 kV


is above the value as below.

Designation Fitting joint D Weight


mm kg/item

TS 121 SOJ 121-3 20 0.1


TS 242 SOJ 242-3 29 0.1
TS 243 SOJ 243-3 39 0.1

Adapter kit, ADAPTER


Adapter for cables from 10 mm2 and for jointing cables
with a smaller cross section. Manufactured and tested to
cope with one step down to the nearest joint size (each
kit contains one adapter).

Designation Fitting joint Minimum XLPE Weight


conductor cross section diameter
mm2 mm kg/item

ADAPTER 1* SOJ 121, 241 10 Minimum 10 0.1


ADAPTER 2 SOJ 122 50 15.0-19.5 0.1
ADAPTER 3 SOJ 123 95 18.5-24.0 0.1
SOJ 242 50 19.0-23.5 0.1
ADAPTER 4 SOJ 124 185 23.0-28.0 0.1
SOJ 243 95 22.5-28.0 0.1
ADAPTER 5 SOJ 125 300 27.0-34.0 0.1
SOJ 244 185 27.0-35.0 0.1
ADAPTER 6 SOJ 125 185 23.0-28.0 0.1
SOJ 244 95 22.5-28.0 0.1
* Minimum diameter over connector is 12 mm.

Crutch seal, STOP


For sealing when three 1-core cables are jointed
to a 3-core cable.

Designation Voltage Suitable for 1-core cables Weight


kV with conductor cross
section in mm2 kg/item

STOP 1 12 50-185 0.2


24 50-95 0.2
STOP 2 12 > 240 0.2
24 > 120 0.2

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 43
Kabeldon cable accessories
Kabeldon cable
for XLPE
accessories
cables 12-36 kV

Accessories for SOJ

WIM 3 WIM 4

Diffusion seal, WIM


Used as complement to SOJ CS, SOJ CSS or SOJ R
when jointing 3-core watertightened cables with diffussion
barrier of aluminium.

Designation Fitting joint Type of cable Weight


kg/kit

WIM 3 SOJ 121-3, 122-3, 123-3, 3-core with Al foil 0.5


SOJ 241-3, 242-3, 243-3 in direct contact with
screen

WIM 4 SOJ 121-3, SOJ 122-3 3-core with inner cable 4.0
sheath between Al foil
and screen

WIM 5 SOJ 121-1, SOJ 122-1 1-core with Al-foil in 0,4


direct contact with screen

WIM 6 SOJ 123-1, SOJ 124-1, 1-core with Al-foil in 0,4


SOJ 125-1, SOJ 241-1, direct contact with screen
SOJ 242-1, SOJ 243-1,
SOJ 244-1

To be ordered separately
Accessories Type of jointing / cable type CSS CS R SL RWI RWIT See
page

TS Additional kit for sector shaped 3-core cables X X X X X 43


Adapter Cables with different dimensions X X X X X X 43
STOP 3 x 1-core to a 3-core X 43
WIM Radial watertightness cable X X X 44
JSA 10-13 Cable with copper tape screen X X X 56
JSA 14-16 Cable with aluminium foil screen only X X X 56
ARM Armoured cable or when extra
mechanical protection is required X 57
SH-SKRM Screw connector X X X X X 59

44 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories for XLPE cables 12-36 kV

Dimensional drawings, SOJ All dimensions in mm

B
C

B
C

Accessories XLPE 12-36 kV


A

SOJ with outer sheath RULLE.


A
B C
SOJ with outer sheath cold shrink.

B SOJ with outer sheath cold shrink for watertightened


1-core cables.
B
C

A A

SOJ with outer sheath RULLE on SOJ with outer sheath RULLE on 3 x 1-core
3 x 1-core WISKITM cables. WISKITM cables to a 3-core XLPE-cable.
Designation Dimensions
A* B* C*
mm

1-core
SOJ 121-1 980-1060 770-860 60
SOJ 122-1 980-1100 770-900 65
SOJ 123-1 1050-1220 940-960 75
SOJ 124-1 1050-1370 940-1080 75
SOJ 125-1 1050-1400 940-1200 90

SOJ 241-1 1050-1220 900-940 75


SOJ 242-1 1050-1220 900-940 80
SOJ 243-1 1050-1370 940-1080 85
SOJ 244-1 1050-1400 940-1200 90

3-core
SOJ 121-3 1200-1350 1000 120
SOJ 122-3 1350 1150 125
SOJ 123-3 1390-1500 1190 140
SOJ 124-3 1500 1310 165

SOJ 241-3 1350 1140 145


SOJ 242-3 1320-1390 1190 160
SOJ 243-3 1500 1310 180
* Estimated dimensions depending on installation and type of outer sheath.

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 45
Kabeldon cable accessories
Kabeldon cable
for XLPE
accessories
cables 12-36 kV

• Fits all cable dimensions


• Easy jointing of cables
with different sizes
• Active pressure

Cable joint, tape


SMXB 12-36 kV

Use Design
For jointing XLPE-insulated 1- and The joint kit consists of tapes, stress grading
3-core cables with Al or Cu conductors pads FSD and a copper net.
12-36 kV. The connectors for the conductor and
screen must be ordered separately.
Standards Welding of conductors will require welding
Meets the requirements of: equipment, which must be ordered
– SEN 24 14 34 separately.
– SS 424 14 17 Edition 4
– VDE 0278

Designation Weight Designation Weight


kg/item kg/item

1 x 3-core or 3 x 1-core cables 1 x 1-core cable


SMXB 1-3 2.6 SMXB 1-1 0.9
SMXB 2-3 3.7 SMXB 2-1 1.1
SMXB 3-3 4.0 SMXB 3-1 1.4
SMXB 4-3 4.3 SMXB 4-1 1.6
SMXB 5-3 4.5 SMXB 5-1 2.0
SMXB 6-3 5.9 SMXB 6-1 2.2
SMXB 7-3 6.7 SMXB 7-1 2.5
SMXB 8-3 9.7 SMXB 8-1 3.6
SMXB 9-3 12.9 SMXB 9-1 5.1
SMXB 10-1 3.8
SMXB 11-1 5.1
For selecting size see next page. SMXB 12-1 6.7
SMXB 13-1 7.8

46 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories for XLPE cables 12-36 kV

Recommendation tables
for SMXB

For compression of aluminium conductors


Voltage Insulation Cross section mm²

Accessories XLPE 12-36 kV


thickness 10 25 35 50 70 95 120 150 185 240 300 400 500 630
kV mm

One 3-core or Cable joint SMXB No.


three 1-core cables

12 3.4 1 1 1 1 1 2 2 2 3 3 6 7 7 8
24 5.5 2 3 4 4 4 5 5 6 6 6 8 8 8 9
One 1-core cable
36 8.0 – 10 10 10 10 10 10 10 11 11 11 11 11 12

For compression of copper conductors


Voltage Insulation Cross section mm²
thickness 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1200
kV mm

One 3-core or Cable joint SMXB No.


three 1-core cables

12 3.4 1 1 1 1 1 1 2 2 3 3 7 7 7 – –
24 5.5 3 3 3 3 3 5 5 5 6 6 7 8 8 – –
One 1-core cable
36 8.0 10 10 10 10 10 10 10 11 11 11 11 11 11 13 13

For thermite welding of aluminium or copper conductors


Voltage Insulation Cross section mm²
thickness 400 500 630 800 1000 1200
kV mm

One 3-core or Cable joint SMXB No.


three 1-core cables

12 3.4 7 7 7 – – –
24 5.5 8 8 8 – – –
One 1-core cable
36 8.0 11 11 11 11 12 12

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 47
Kabeldon cable accessories for XLPE cables 12-36 kV

Accessories for SMXB

STOP
Crutch seal for sealing when 3 x 1-core
cables are jointed to a 3-core cable.

Designation Voltage Suitable for 1-core cables Weight


with conductor cross
kV section in mm² kg/item

STOP 1 12 50-185 0.2


24 50-95 0.2
STOP 2 12 > 240 0.2
24 >120 0.2

WIM 3 WIM 4

WIM
Diffusion seal kits for restoring radial watertightness
on cables with diffusion barrier of aluminium.

Designation Fitting joint Type of cable Weight


kg/kit

WIM 1 SMXB 1-1, 2-1, 3-1, 4-1 1-core with Al foil 0.5

WIM 2 SMXB 5-1, 6-1, 7-1, 8-1, 9-1, 10-1, 11-1, 12-1 1-core with Al foil 0.5

WIM 3 SMXB 1-3, 2-3, 3-3, 4-3 3-core with Al foil 0.5
SMXB 5-3, 6-3 in direct contact with screen

WIM 4 SMXB 1-3, 2-3, 4-3, 5-3 3-core with inner 4.0
sheath between Al foil
and screen

To be ordered separately
Designation Description

Connector Only crimp connectors can be used


Welding equipment Welding of conductors

48 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories
Kabeldon cable
for XLPE
accessories
cables 12-36 kV

• Touch-proof
• Possibility of capacitive
test point
• Possibility of earthing
• Possibility of branching
Cable cabinet 250 A cables with different
sizes
HDC 250 • Simple, safe and compact

Use
For jointing or branching XLPE-insulated

Accessories XLPE 12-36 kV


1-core or 3-core, 12-24 kV cables with
conductor cross-section 10-95 mm²,
250 A. Up to 3 cables can be connected
in parallel.

Standards
Enclosure meets the requirements of
mechanical impact tests according to:
IEC 60439-5

Cable accessories meets the requirements


of electrical tests according to:
– SS 424 14 45

CENELEC:
– HD 629.1 S1

Design
The enclosure is made of hot-dip-galvanized
sheet steel with a foundation base plate
and additional corrosion protection on parts
which will be buried under ground.
The screened separable cable
connections are connected by coupling
pieces which are mounted in the enclosure.
Connectors with capacitive test point Mounting two 3-core cables with three 1-core cables
for connecting three 3-phase cables are and screen connection kits.
included.
Any chosen cable could then be Note: For 3-core cables, screen separation kit
disconnected for live sectioning or to be must be used!
earthed. It must be ordered separately according to
The cable cabinet is supplied with locks page 53.
and padlock shackles.

Designation XLPE- Conductor Dimensions Weight


diameter cross section Height Width Depth
mm mm² mm kg /unit

HDC 250 12.9-25.8 25-95* 895 996 312 117


* For 10 and 16 mm², use AK 250 as accessory, see next page!

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 49
Kabeldon cable accessories for XLPE cables 12-36 kV

Accessories for cable cabinet HDC 250

AK 250
Accessory kit for SOC 250,
allowing installation on smaller
cables with conductor cross
section 10-16 mm2.
The kit consists of three
IP 250
adapters and three inserts. Every
Screened insulating plug for
insert is made of tinned copper
installation in the connector so that
and is clamped to the conductor
the cable can be energized
with pliers before it is installed in
even when the connection is JP 250-HDC
the connector.
disconnected. Earth circuit connector for
short-circuit protective earthing.
To be mounted on a disconnected
connector. 3 pieces in a case.

MA 250
Measurement adapter used for mega
 measurements and to perform
IH SOC 250 TP different measurements up to 5 kV
Insulating hood made of flexible DC, for example determination of
rubber with outer conductive layer phases.
and an already installed insulating
hood. To be mounted at the bushing
in HDC 250 for insulation when a
cable is temporary disconnected Ø 13
and remaining cables are under
voltage.

35

PSSK: for cables with Cu-wire


screen, heat-shrink.
KA 250 PSSK E: for Ericsson's cables UKRA 90
Transversal anchor bar. with Al-wire screen, heat-shrink. Universal clamp.

Designation Description Qty Weight


kit kg/unit

IP 250 Screened insulating plug 1 0.8


JP 250-HDC Earthing circuit connector 3 3.0
AK 250 Accessories kit for cables 10-16 mm² 3 2.2
IH SOC 250 TP Insulating hood 3 2.3
MA 250 Measurement adapter 1 0.3
KA 250 Busbar 1 0.5
PSSK 1 heat shrink Screen separation kit for 3-core cable 10-70/12 kV, 10-35/24 kV 1 1.0
PSSK 1 E heat shrink* Screen separation kit for 3-core cable 10-70/12 kV, 10-35/24 kV 1 1.0
UKRA 90 Clamp for fixing cables 1 0.23
* Special screen separation for Ericsson’s 3-core cable with Al-wire screen.

50 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories
Kabeldon cable
for XLPE
accessories
cables 12-36 kV

• Touch-proof
• Possibility of capacitive
test point
• Possibility of earthing
• Possibility of branching
Cable cabinet 630 A cables with different
sizes
HDC 630, 12-24 kV • Simple, safe and compact

Use
For jointing or branching XLPE-insulated

Accessories XLPE 12-36 kV


1-core or 3-core 12-24 kV cables with
conductor cross section 50-300 mm²,
630 A. Up to 4 cables can be connected
in parallel.

Standards
Enclosure meets the requirements of
mechanical impact tests according to:
IEC 60439-5

Cable accessories meets the requirements


of electrical tests according to:
CENELEC:
– HD 628.1 S1
– HD 629.1 S1

Design
The enclosure is made of hot-dip-galvanized
sheet steel with a foundation base plate and
additional corrosion protection on parts
which will be buried under ground.
The screened separable cable connections
are connected by coupling pieces which are
mounted in the enclosure.
Connectors with capacitive test point
for connecting two three-phase cables are Mounting two 3-core cables with screen connection kits
included. and three 1-core cables.
To be completed with three parallel
connectors type PC 630 and one kit of
screened separable connector SOC 630 Note: For 3-core cables, screen separation kit
of the appropriate size when branching is must be used!
needed. It must be ordered separately according to
Any chosen cable can then be page 53.
disconnected for live sectioning or to be
earthed.
The cable cabinet is supplied with standard
locks and padlock shackles.

Designation XLPE- Conductor Dimensions Weight


diameter cross section Height Width Depth
mm mm² * mm kg /unit

HDC 630-1 15.0-26.8 50-120 895 996 450 140


HDC 630-2 21.4-34.9 150-300 895 996 450 140
* 400-630 mm² if required.

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 51
Kabeldon cable accessories for XLPE cables 12-36 kV

Accessories for cable cabinet HDC 630

PC 630 PC 630 L
Parallel coupling piece. Parallel coupling piece. IP 630
Replaces the plug in Replaces the plug in Screened insulating plug for
SOC 630-1 and -2 when SOC 630-3/4/5 when installation in the screened
making a parallel connection making a parallel connection separable connector so that
to SOC 630-1/2/3/4/5. to SOC 630-1/2/3/4/5. the cable can be energized
even when the connector is
SOC 630
disconnected from the
Screened separable connector. JPA V switchgear or transformer.
Tool for earthing-for-work
PC 630/250 device.
Connector for connecting a
SOC 250, in parallel with a
previously mounted
SOC 630.

MA 630 JPA 630-HDC


SOC 250-TP Measurement adapter used Earthing-for-work device.
Screened separable connector for mega  measurements 3 pieces in a case. PSSK: for cables with
with possibility of capacitive and to perform different Cu-wire screen, heat shrink.
test point. For connecting an measurements up to 5 kV DC, PSSK E: for Ericsson's cables
additional cable for 250 A. for determination of phases. with Al-wire screen, heat
shrink.
Ø 13
IH SOC 630
KA 630 Insulating sealing hood of
Transversal anchor bar. flexible rubber with outer
conductive layer and an
JP 630-HDC already installed insulating
Earthing device for HBS 10 hood. To be installed in SOC 35
short-circuit protective Extended hex bit socket instead of cable in order to
earthing. To be mounted to 10 mm with 1/2" drive for temporarily insulating 630 A
disconnected connector. torque wrench. For installation switchgear or transformer UKRA 90
3 pieces in a case. of PC 630 and PC 630 L. bushings. Universal clamp.

Designation Description Qty Weight


a kit kg/unit

SOC 630-1 Screened separable connector for branching 3 2.2


SOC 630-2 Screened separable connector for branching 3 2.2
SOC 250 TP Connector with capacitive test point 3 2.2
PC 630 For connecting of cable for branch seal 1 1.1
PC 630 L For connecting of cable for branch seal 1 1.4
IP 630 Insulatated plug 1 0.8
JP 630-HDC Earthing circuit connector 3 1.3
MA 630 Measurement adapter 1 0.1
JPA 630-HDC Earthing-for-work device 3 1.9
PSSK 1 Screen separation 3-core cable 10-70/12 kV, 10-35/24 kV 1 1.0
PSSK 2 Screen separation 3-core cable 95-300/12 kV, 50-300/24 kV 1 1.0
PSSK 1 E * Screen separation 3-core cable 10-70/12 kV, 10-35/24 kV 1 1.0
PSSK 2 E * Screen separation 3-core cable 95-300/12 kV, 50-300/24 kV 1 1.0
PC 630/250 Parallel connector between SOC 630 and SOC 250 3 3.0
HBS 10 Hex bit socket 1 0.1
IH SOC 630 Insulating hood 3 5.2
JPA V Tool for earthing-for-work device 1 1.8
KA 630 Busbar, add two when using 1-core cables 1 0.8
UKRA 90 Clamp for fixing cables 1 0.23
* Special screen separation for Ericsson’s 3-core cable with Al-wire screen.

52 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories for XLPE cables 12-36 kV

• Prevent flash-over
between phases

Screen separation kit


for SOC and KAP,
PSSK

Use
For cables with common copper

Accessories XLPE 12-36 kV


wire screen or Ericsson cables with
aluminium wire screen.
The screen of the 3-core cable is
split up to each phase.
Used to prevent flashover between
the phases, for example in a switchgear
bay.
Used together with screened separable
connector SOC or shrouded termination
L
KAP.
When a connector type SOC is installed,
each core screen is connected to
the outer conductive layer.

Standard
Meets the requirements of EBR KJ 25:99.

Design
A copper stocking with a screen cross
section of 25 mm² is fitted on each
phase and connected to the screen wires
of the cable.
A heat shrink crutch seal and hoses are
used as an outer sheath.
Standard length is about 1200 mm
plus length of accessory. It can also
be cut for shorter installation.

Designation Conductor cross section Length Weight


12 kV 24 kV L
mm² mm kg/item

PSSK 1 10 -70 10 -35 1200 1.0


PSSK 2 95 -300 50 -300 1200 1.0
PSSK 1 E* 10 -70 10 -35 1200 1.0
PSSK 2 E* 95 -300 50 -300 1200 1.0
* Special kits to be used with Ericsson's cables with Al-screen wires.

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 53
Kabeldon cable accessories for XLPE cables 12-36 kV

Branch seal kit for


XLPE-insulated 3-core cables
with copper wire, TSH
Screen prolongation hose, SSH

Use
TSH, branch seal for sealing the branch
when installing cable terminations SOT on
XLPE-insulated 3-core cables, indoor or
outdoor.
SSH are kits with protective hoses to be
used as additional prolongation of the
branch seal when necessary.

Design
TSH includes branch seal and protective
hoses of heat-shrink material, lashing wire
for mechanical reinforcement of the branch,
earth wire and non-corrosive band strip for
connection of earth potential to termination.
• TSH 1 L and TSH 2 L include
3 heat-shrink hoses, length 1.2 m.
• TSH 1 S and TSH 2 S include
1 heat-shrink hose, length of 1.2 m
to be cut in suitable lengths for current
installation.
• SSH 1 L and SSH 2 L include
3 heat-shrink hoses, length 1.2 m.
• SSH 1 S and SSH 2 S include
3 heat-shrink hoses, length 0.4 m.

Designation Outer diameter Core Cable Length Weight


cable diameter cross section
Min Max Min Max 12 kV 24 kV
mm mm mm² m kg/kit

TSH 1 L 22 60 9 27 10-95 10-50 Approx. 1.25 0.5


TSH 1 S 22 60 9 27 10-95 10-50 Approx. 0.45 0.3
TSH 2 L 47 110 16 50 120-300 70-300 Approx. 1.25 1.0
TSH 2 S 47 110 16 50 120-300 70-300 Approx. 0.45 0.7
SSH 1 L – – 9 27 10-95 10-50 1.2 0.4
SSH 1 S – – 9 27 10-95 10-50 0.4 0.1
SSH 2 L – – 16 50 120-300 70-300 1.2 0.6
SSH 2 S – – 16 50 120-300 70-300 0.4 0.2

54 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories
Kabeldon cable
for XLPE
accessories
cables 12-36 kV

• The range can be used


for different screen
types

Earthing kit for


cable terminations,
JXT 1-3 and JSA 4-6

Earthing kits for XLPE-insulated cables JXT 1-3 contains copper stockings which
with earth screen of copper tape or are connected to the screen with constant

Accessories XLPE 12-36 kV


aluminium foil. The kits are designed for force springs.
Kabeldon terminations and connectors.
There is enough material in the kits for Cables with aluminium foil screen
three 1-core cable terminations. JSA 4-6 contains copper braids which are
There are also complete kits for 1-core connected to the screen with a plate and
cable. constant force springs.

Cables with copper tape screen

If the cable has only copper wire screen, no


earthing kit is needed.

For cables with other screen types, or 3-core cable


with Cu-tape screen, contact us for information. Copper tape screen Al foil

Cable For cables with For cables with


copper tape screen aluminium foil screen
Ø Screen mm 15 – 25 20 – 30 31 – 50 20 – 30 25 – 40 20 – 30
Earthing kit JXT 1 JXT 2 JXT 3 JSA 4 JSA 5 JSA 6
Cable accessories IV-tape IV-tape Shrink sleeve

SOT 241 X X X
SOT 242 X X
SOT 242 B X
SOT 243 X X
SOT 244 X X X
SOT 245 X X
SOT 246 X
SOT 361 X X
SOT 362 X
SOC 250 X X X
SOC 400-1 X X X
SOC 400-2 X X X
SOC 630-1 X X X
SOC 630-2 X X X
KAP 630-11 X X X
KAP 630-12 X X X
KAP 630-22 X X

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 55
Kabeldon cable accessories for XLPE cables 12-36 kV

• The range can be used


for different screen
types

Screen connection for


cable joints, JSA 10-16

Screen connection kits for XLPE-insulated Cables with copper tape screen
cables with earth screen of copper tape or JSA 10-13 contains copper stockings which
aluminium foil. The kits are designed for are connected to the screen with constant
Kabeldon cable joints type SOJ and SMXB. force springs. Connections to armouring
There is enough material in the kits for one (if any) are made with lashing wire.
3-core joint or three 1-core joints.
There are also complete kits for 3-core Cables with aluminium foil screen
cables with Cu-tape screen. JSA 14-16 contains copper braids which are
connected to the screen with a plate and
constant force springs.

Armouring Copper tape screen


If the cable has only copper wire screen, no
earthing kit is needed.

Aluminium foil
For cables with other screen types, or 3-core
cables with Cu-tape screen, contact us for
information.

Cable For cables with For cables with


copper tape screen aluminium foil screen
Ø XLPE mm 17 – 20 19 – 27 25 – 35 31 – 48 19 – 27 25 – 35 31 – 48
Earthing kit for 1-core JSA 10-1 JSA 11-1 JSA 12-1 JSA 13-1 JSA 14-1 JSA 15-1 JSA 16-1
Earthing kit for 3-core JSA 10-3 JSA 11-3 JSA 12-3 JSA 13-3 JSA 14-3 JSA 15-3 JSA 16-3
Cable joint

SOJ 121 X
SOJ 122 X X
SOJ 123 X X
SOJ 124 X X
SOJ 125 X X
SOJ 241 X X
SOJ 242 X X
SOJ 243 X X
SOJ 244 X X
SMXB 1 X
SMXB 2 X X
SMXB 3 X X
SMXB 4 X X
SMXB 5 X X
SMXB 6 X X
SMXB 7 X X
SMXB 8 X X
SMXB 9 X X
SMXB 10 X X
SMXB 11 X X

56 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories
Kabeldon cable
for XLPE
accessories
cables 12-36 kV

Armouring kit
ARM

Use ARM kit size


For restoring a steel wire or steel tape

Accessories XLPE 12-36 kV


armoured cable. ARM can be used with Ø
SOJ and SMXB joints, as well as other
L
joints.
E.g. Ø 115 and L 850 mm give ARM 3.

Kabeldon cable joints type SOJ and


SMXB are to be completed with ARM
as following:

Cable joint ARM 1 ARM 2 ARM 3

SOJ 121-3 X
Design SOJ 122-3 X
SOJ 123-3 X
The kit consists of plastic mesh, spiral, SOJ 124-3 X
funnel with holder, transparent tape and
cast resin. SOJ 241-3 X
The mesh and spiral are placed over the SOJ 242-3 X
SOJ 243-3 X
joint and sealed with the tape. The cast
resin, which contains a base and hardener SMXB 1-3 X
in a partitioned bag, is mixed and poured SMXB 2-3 X
into the funnel until the mesh is full. SMXB 3-3 X
SMXB 4-3 X
The maximum storage temperature for SMXB 5-3 X
the cast resin is 30 °C. SMXB 6-3 X
SMXB 7-3 X
SMXB 8-3 X
Selecting ARM for unknown application requires
the length of joint "L" and diameter over joint "Ø"
as below. Designation Weight
kg/item
Ø (mm)
1 2 3 4 ARM 1 3.5
140 ARM 2 6.5
ARM 3 8.0
ARM 4 10.0

100

60

500 1000 L (mm)

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 57
Kabeldon cable accessories
Kabeldon cable
for XLPE
accessories
cables 12-36 kV
• No special tools

Connectors All dimensions in mm

50
FK 120
Overhead line clamp. 28
A greased tin-plate must
be used when connecting to 50
a Cu conductor outdoors.

28
100

23.5

72

FK 300 40
Overhead line clamp.
A greased tin-plate must
be used when connecting
to a Cu conductor outdoors. 72

40

131

38

FKFB
Bracket to connect overhead
line clamp FK to surge
arrester.

Designation Conductor Al or Cu Tightening Aerial line Al Weight


size max Ø torque size Ø
mm² mm mm² mm kg/item

FK 120 50-120 13 25 Nm 31-99 5-12 0.5


FK 300 50-300 21 25 Nm for 50-100 mm² 62-234 10-20.5 0.9
45 Nm for > 100-300 mm²
FKFB – – – – – 0.1

58 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories for XLPE cables 12-36 kV

• No special tools

Connectors All dimensions in mm

D C
D
C
C B
A A
D C

Accessories XLPE 12-36 kV


Ø
28
,5
E A
B

SH-SKRM
SKSB Ø A B
37 Screw connector with partition
Bi-metallic screw cable lug for ,5 and shear-off bolt for Al and Cu
Al and Cu conductors up to conductors up to 36 kV.
36 kV. • Meets the requirements of:
• Meets the requirements of: SKSA 95-13, 300-13
IEC 61238-1.
IEC 61238-1 Screw cable lug for indoor and
• The connector is equipped
• The cable lug is equipped with outdoor connection of Al or Cu
with a turnable two-sided
a turnable two-sided shear-off conductors. Can be connected to
shear-off bolts and a specially
bolt and a specially designed an Al or Cu busbar.
designed nut. The bolt is
nut. A greased cupal washer must
rotated in the appropriate
The bolt is rotated in the be used when connecting to a Cu
direction, and the nut is then
appropriate direction, and the conductor outdoors.
assembled. When the
nut is then assembled. • Meets the requirements of:
specified torque is reached,
When the specified torque is IEC 61238-1
the bolt will shear off and
reached, the bolt will shear-off • Single core kits.
the installation is completed.
and the installation is completed. • Single core kits.
• Single core kits.
CW 3013, CW 3817
Cupal washer, to be used when
connecting an aluminium cable lug
to a copper busbar outdoors. The
washers are coated with contact grease.
• Supplied in bags of three.
Designation Conductor Al or Cu Tightening Dimensions Weight
sector shaped Round max Ø torque A B C D(Ø) E(Ø)
mm2 mm2 mm mm kg/item

SKSB 70-12 25-70 16-70 11 15* 90 103 25 13 21.5 0.15


SKSB 150-12 95 95-150 16 20* 103 118 30 13 27 0.25
SKSB 240-12 120-185 185-240 20 30* 125 140 30 13 33.5 0.40
SKSB 400-16 240 300-400 25.5 40* 166 185 37 17 41.5 0.75
SKSB 630-16 – 500-630 33 45* 201 227 55 17 49 1.45
SKSA 95-13 – 25-95 11.6 25* 88 103 30 13 – 0.10
SKSA 300-13 – 50-300 20.6 25**/45*** 140 160 40 13 – 0.30
SH-SKRM 70 25-70 16-70 11 15* 100 – 21.5 – – 0.25
SH-SKRM 150 95 95-150 16 20* 114 – 27 – – 0.35
SH-SKRM 240 120-185 185-240 20 30* 144 – 33.5 – – 0.60
SH-SKRM 400 240 300-400 25.5 40* 175 – 41.5 – – 0.90
SH-SKRM 630 – 500-630 33 45* 210 – 49 – – 1.20

Designation Outer diameter Hole diameter Thickness Weight


mm mm mm g/item

CW 3013 30 13 2 5
CW 3817 38 17 2 8
* The bolt will be sheared-of at the right tightening torque.
** When 50-95 mm².
** When 120-300 mm².

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 59
Kabeldon cable accessories for XLPE cables 12-36 kV

• Protects bird life


• Prevents short-circuit
caused by birds
• UV-resistant material

Bird protection for pole-


mounted transformers,
support insulators, etc

Use HU 200
Used for bird protection on the high-voltage
bushings for pole-mounted transformers. HUF
To prevent short-circuits caused by larger
birds, HU is also placed on the surge
arresters, but for total protection HU
should be combined with an insulated
down-conductor. This is done with
insulation spiral HUS.
On post insulators, HU is used in
combination with two wings HUF, which
protect the overhead line closest to
the insulator from short-circuiting.

Standards HUS
HU is designed for bushings with a
diameter of 120-220 mm according to
DIN 42531 standard.

Design
All components are made of UV-resistant
plastic.

HU 150

Designation Bushing diameter A Pieces/kit Length Weight


min max
mm m kg/item

HU 150 120 160 3 – 0.6


HU 200 160 220 3 – 0.8
HUF – – 6 0.6 1.1
HUS – – 1 30 1.8

60 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories for PILC cables 12-52 kV

• Flexible for compact switchgear


• Oil in branch area prevents
discharges

Cable termination, indoor


for paper-insulated cable
OTIA 12 kV

Use
Indoor termination for paper-insulated
3-core cables 12 kV.

Standards
Meets the requirements of:
– SEN 24 14 34

Rated pressure
0.3 MPa (overpressure)

Design

Accessories PILC 12-52 kV


The housing is made of cross-linked
HD-polyethylene (XLPE) with a transparent
lower part, so that the oil level can be seen.
A spring-loaded gasket type FPA
provides a seal between cable and housing,
as well as electrical contact between cable
screen and housing.
A GEX expansion vessel can be
connected to the filling opening for the oil.
The paper-insulated cable is jointed in the
upper part of the housing to a flexible
connecting cable. The length is 900 mm
and must be pressed with the Elpress press
system. The Pfisterer press system can be
used for Al conductors (for Simel press
system, please contact us). As an
alternative, screw connection is available
for Cu conductors for certain cross sections.

Designation Conductor cross section Suitable spring loaded Weight


Al Cu gasket
mm² kg/item

OTIA 152 35-240 25-240 FPA 4.1

To be ordered separately
Designation Description See page

GEX Expansion vessel 62


AK-ASA, K-ASA, K-ASB Connecting cable 62
SKSB Cable lug 59
FPA Spring-loaded gasket 69

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 61
Kabeldon cable accessories for PILC cables 12-52 kV

Accessories for OTIA All dimensions in mm

min 120 (free air gap)

min min
100 30

min 650

Ø 135
GEX 01 GEX 02
Expansion vessel Expansion vessel
for one OTIA 152. for two OTIA 152.
Ø 112
OTIA 152

Designation For use Weight


with kg/item

GEX 01 One OTIA 2.0


GEX 02 Two OTIA 2.0

Flexible connecting cable. Each kit contains one connecting cable (length 900 mm).
Designation Conductor Cross section of Max Max Weight
cross section connecting conductor short-circuit continuous
Al Cu Cu flexible current rating
mm2 mm2 kA A kg/item

Press type connecting cable


AK-ASA 3535-9 35 – 35 6.2 200 0.6
AK-ASA 5035-9 50 – 35 6.2 200 0.6
AK-ASA 7035-9 70 – 35 6.2 200 0.6
AK-ASA 95150-9 95 – 150 16.6 350 1.2
AK-ASA 120150-9 120 – 150 16.6 350 1.2
AK-ASA 150150-9 150 – 150 16.6 350 1.2
AK-ASA 185150-9 185 – 150 16.6 350 1.2
AK-ASA 240150-9 240 – 150 26.1 500 1.8
K-ASA 185150-9 – 185 150 26.1 500 1.8
K-ASA 240150-9 – 240 150 26.1 500 1.8

Screw type connecting cable


K-ASB 7035-9 – 35-70 35 6.2 500 0.8
K-ASB 150150-9 – 95-150 95 16.6 500 1.2

62 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories for PILC cables 12-52 kV

• No special tools
• Insulating bitumen compound
and insulating oil need not be
heated at temperatures exceeding
+10°C
Cable joint and • No soldering
• The oil prevents discharges in
repair cable joint for paper-insulated cable

paper-insulated cable
SMTD 12 kV

Use seal between the cable and the joint tube,


For jointing paper-insulated lead-sheathed as well as electrical contact between cable
cables with Al or Cu conductor 12 kV. screens and joint tube. Type FPA or FP for
belted cables and FPMP for separately
Standards lead-sheathed cables.
Meets the requirements of: The length of the SMTD 152 LK and
– SEN 24 14 34 SMTD 153 K joint tube allows crossing of
– SEN 24 14 23 the conductors, in order to obtain the right
– VDE 0278 phase sequence. The repair joint
SMTD 152 RK should be completed with
Rated pressure three extension cores, of paper- or XLPE-
0.3 MPa insulated cable (not included).

Accessories PILC 12-52 kV


Insulating bitumen compound and
Design insulating oil need not be heated at
The joint tube is a plastic-coated steel tube. temperatures exceeding +10°C.
The joint insulation consists of transparent
polyester film and insulating oil. The oil
prevents discharges in the paper-insulated
cable. Spring-loaded gaskets provide a

Designation Type Maximum Suitable Joint Weight


Conductor cross section spring-loaded tube
Al/Cu gasket Ø
mm² mm kg/item

SMTD 152 K Standard 3x240 FPA 100 25


SMTD 152 LK* Extended 3x240 FPA 100 27
SMTD 153 K Standard 3x300 FP, FPMP 150 52
SMTD 152 RK** Repair 3x240 FPA 100 39

To be ordered separately
Designation Description Required See page
Qty.

FPA, FP, FPMP Spring loaded gasket 2 69


SH-SKRM Screw connector 3*** 59
* Extended type, allows crossing of the conductors, in order to obtain the right phase sequence.
** For jointing with XLPE-conductor, three insulating materials type IG 1718 must be added.
*** 6 connectors should be used for SMTD 152 RK.

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 63
Kabeldon cable accessories for PILC cables 12-52 kV

Supplementary kit for SMTD


(For conversion to a transition joint)

PXS

PXSA

A. B.
Select the basic kit, SMTD joint (see page before) and Select a XLPE kit, PXS or PXSA, in accordance with
spring-loaded gasket according to the dimension of the following table.
the paper-insulated cable.

Designation Conductor Diameter across Type of Joint Weight


cross section insulation termination tube
for XLPE cable Ø
mm² mm mm kg/item

PXS 02 10-240 ≤ 32 Tape 100 2.9


PXS 03 10-300 ≤ 32 Tape 150 5.5
PXSA 12 A 10-35 11-15 SOT termination 100 2.6
PXSA 12 50-185 15-26 SOT termination 100 2.6
PXSA 12 W* 50-185 15-26 SOT termination 100 2.6
PXSA 22 240 25-32 SOT termination 100 2.7
PXSA 22 W* 240 25-32 SOT termination 100 2.7
PXSA 23 240-300 25-32 SOT termination 150 5.2
* For 3 x 1-core XLPE-cables with Al foil screen.

To be ordered separately
Designation Description Required See page
Qty.

SH-SKRM Connector with a partition 3 59

64 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories for PILC cables 12-52 kV

• No special tools
• Insulating bitumen compound
and insulating oil need not be
heated at temperatures exceeding
+10°C
Cable joint, transition • No soldering
• The oil prevents discharges in
SMTXB 12 kV paper-insulated cable

Use A crutch seal provides a seal between


For jointing a paper-insulated 3-core cable the steel joint tube and the XLPE-insulated
with an XLPE-insulated 1- or 3-core cable cable, which is also covered with either a
with Al or Cu conductors 12 kV. premoulded termination (SOT) or silicone
tape.
Standards Spring-loaded gaskets provide a seal
Meets the requirements of: between the cable and the joint tube, as
– SEN 24 14 34 well as electrical contact between cable
– VDE 0278 screens and joint tube. Type FPA or FP for
belted cables and FPMP for separately
Rated pressure lead-sheathed cables.
0.3 MPa Insulating bitumen compound and

Accessories PILC 12-52 kV


insulating oil need not be heated at
Design temperatures exceeding +10°C.
The joint tube is a plastic-coated steel tube. A sealing ring for three 1-core cable is
The joint insulation consists of transparent included in the kit.
polyester film and insulating oil. The oil
prevents discharges in the paper-insulated cable.

Designation XLPE- Conductor Conductor Suitable Tube Weight


diameter cross section cross section spring-loaded
XLPE-cable paper-insulated gasket
PXSA PXS cable maximum Ø
mm mm² mm² mm kg/item

SMTXB 1502 ≤ 32 – 10-240 240 FPA 100 28


SMTXB 1502 L* ≤ 32 – 10-240 240 FPA 100 30
SMTXB 1503 ≤ 32 – 10-300 300 FP, FPMP 150 57
SMTXB 1522 15-26 50-185 – 240 FPA 100 28
SMTXB 1522 L* 15-26 50-185 – 240 FPA 100 30
SMTXB 1522 W** 15-26 50-185 – 240 FPA 100 28
SMTXB 1532 25-32 240 – 240 FPA 100 28
SMTXB 1532 L* 25-32 240 – 240 FPA 100 30
SMTXB 1532 W** 25-32 240 – 240 FPA 100 28
SMTXB 1533 25-32 240-300 – 300 FP, FPMP 150 57
* L = Extended type, allows crossing of the conductors, in order to obtain the right phase sequence.
** For 3 x 1-core XLPE-cables with Al foil screen.

To be ordered separately
Designation Description Required See
Qty. page

FPA, FP, FPMP Spring-loaded gasket 1 69


SH-SKRM Connector with a partition 3 59
Options
Designation Steel tube Description Qty. See
internal Ø mm page

GC 100 Clamps for 3 x 1-core XLPE-cables Ø 40-45 mm 1 kit 70

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 65
Kabeldon cable accessories for PILC cables 12-52 kV

• No special tools
• Insulating bitumen compound
and insulating oil need not be
heated at temperatures exceeding
+10°C
Cable joint, transition • No soldering
• The oil prevents discharges in
SMTXD 24-36 kV paper-insulated cable

Use The outer conductive layer of the cable


For jointing a paper-insulated 3-core cable is restored by conductive, impregnated
and XLPE-insulated 1-core or 3-core cable crepe paper and copper net.
with Al or Cu conductors 24-36 kV. A crutch seal provides a seal between
the steel tube and the XLPE-insulated
Standards cable, which is also covered with an oil
Meets the requirements of: barrier of silicone tape.
– SEN 24 14 34 Spring-loaded gaskets provide a seal
– VDE 0278 between the cable and the joint tube, as
well as electrical contact between cable
Rated pressure screens of PILC cable and joint tube.
0.3 MPa Type FP for belted cables and FPMP for
separately lead-sheathed cables.
Design Insulating bitumen compound and
The joint tube is a plastic-coated steel tube. insulating oil need not be heated at
The insulation consists of impregnated temperatures exceeding +10°C.
crepe paper tape and insulating oil. The oil A sealing ring for three 1-core cable is
prevents discharges in the paper-insulated included in the kit.
cable.

Designation Conductor Dimensions of Suitable Joint Weight


cross section PILC cable spring-loaded tube
12/20 (24) kV 18/30 (36) kV lead sheath Cross section gasket
mm2 Ø mm mm2 kg/item

SMTXD 3613 10-150 10-50 20-85 10-300 FP, FPMP 150 76


SMTXD 3623 185-240 70-150 20-85 10-300 FP, FPMP 150 76
SMTXD 3633 300 240 20-85 10-300 FP, FPMP 150 76

To be ordered separately
Designation Description Required Qty See page

FP and FPMP Spring-loaded gasket 1 69


SH-SKRM Connector with a partition 3 59

66 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories for PILC cables 12-52 kV

• No special tools
• Insulating bitumen compound
and insulating oil need not be
heated at temperatures
exceeding +10°C
Cable joint for • No soldering
• The oil prevents discharges in
paper-insulated cable paper-insulated cable

SMTA and SMTPA 24-52 kV

Use Design
For jointing paper-insulated 3-core cables The joint tube is a plastic-coated steel tube.
with Al or Cu conductors 24-52 kV. The insulation consists of impregnated
crepe paper tape and insulating oil. The oil
Standards prevents discharges in the paper-insulated
Meets the requirements of: cable. The outer conductive layer of the
– SEN 24 14 34 cable is restored by conductive, impregnated
– SEN 24 14 23 crepe paper and copper net.
Spring-loaded gaskets provide a seal
Rated pressure between the cable and the joint tube, as
0.3 MPa well as electrical contact between cable
screens and joint tube. Type FPA or FP

Accessories PILC 12-52 kV


for belted cables and FPMP for separately
lead-sheathed cables.
Insulating bitumen compound and
insulating oil need not be heated at
temperatures exceeding +10°C.

Designation Maximum conductor Diameter of Suitable Joint Weight


cross section Al/Cu lead sheathed spring-loaded tube
24 kV 36 kV 52 kV min max gasket
mm² mm kg/item

For belted cable


SMTA 24362 3x120 3x70 – 12 63 FPA 100 25

For belted and separate lead-sheathed cable


SMTPA 24523 3x300 3x240 3x150 20 85 FP/FPMP 150 62

To be ordered separately
Designation Description Required See page
Qty.

FP, FPA, FPMP Spring-loaded gasket 2 69


SH-SKRM Screw connector 3 59

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 67
Kabeldon cable accessories for PILC cables 12-52 kV

Dimensional drawings, SMT... All dimensions in mm

A A
B B

D C D
C

Designation Dimensions in mm Designation Dimensions in mm


A B C D A B C D

SMTXB 1502 1135 175 900 100 SMTXD 3613 1500 228 1200 150
SMTXB 1502 L 1335 175 1100 100 SMTXD 3623 1500 228 1200 150
SMTXB 1503 1500 228 1200 150 SMTXD 3633 1500 228 1200 150
SMTXB 1522 1135 175 900 100
SMTXB 1522 L 1335 175 1100 100
SMTXB 1522 W 1135 175 900 100
SMTXB 1532 1135 175 900 100
SMTXB 1532 L 1335 175 1100 100
SMTXB 1532 W 1135 175 900 100
SMTXB 1533 1500 228 1200 150

A A
B B

D C D
C

Designation Dimensions in mm Designation Dimensions in mm


A B C D A B C D

SMTD 152 K 1135 175 900 100 For belted cable


SMTD 152 LK 1335 175 1100 100 SMTA 24362 1335 175 1100 100
SMTD 153 K 1500 228 1200 150
SMTD 152 RK 1935 175 1700 100 For belted or separate lead-sheathed cable
SMTPA 24523 1500 228 1200 150

68 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories for PILC cables 12-52 kV

 No special tools
 No soldering

Spring-loaded gaskets The diameter of the lead


sheathed cable should be
for paper-insulated cables measured.

FPA FP FPMP
Ø 100 mm for belted cables. Ø 150 mm for belted cables. Ø 150 mm, 3-hole gasket,
non-magnetic design for
separate lead-sheathed cables.

Accessories PILC 12-52 kV


Designation Diameter over Weight Designation Diameter over Weight
lead sheath lead sheath
mm kg/item mm kg/item

FPA 1021 18-21 1.2 FP 1530 25-30 4.2


FPA 1024 21-24 1.2 FP 1535 30-35 4.2
FPA 1027 24-27 1.1 FP 1540 35-40 4.3
FPA 1030 27-30 1.1 FP 1545 40-45 4.1
FPA 1033 30-33 1.1 FP 1550 45-50 4.2
FPA 1036 33-36 1.1 FP 1555 50-55 3.9
FPA 1039 36-39 1.0 FP 1560 55-60 4.1
FPA 1042 39-42 1.0 FP 1565 60-65 4.0
FPA 1045 42-45 1.0 FP 1570 65-70 3.9
FPA 1048 45-48 1.0 FP 1575 70-75 3.8
FPA 1051 48-51 1.0 FP 1580 75-80 3.9
FPA 1054 51-54 0.9 FP 1585 80-85 4.0
FPA 1057 54-57 0.9
FPA 1060 57-60 0.9
FPA 1063 60-63 0.9
FPA 1065 63-66 0.9

Designation Diameter over Weight


lead sheath
mm kg/item

FPMP 1523 20-23 4.5


FPMP 1526 23-26 4.4
FPMP 1529 26-29 4.4
FPMP 1532 29-32 4.4
FPMP 1535 32-35 4.2
FPMP 1538 35-38 4.1
FPMP 1540 38-40 4.2

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 69
Kabeldon cable accessories for PILC cables 12-52 kV

General accessories for


paper-insulated cable joints
and transition joints

GC IA 2502 - 2519 RKM 402


The kit contains one sealing ring, Bituminized paper for Funnel for oil filling.
screws and two roomy clamp filling, for example in
halves for Ø 100 mm joint tubes. cable clamps.
The clamps are made from glass
fibre reinforced polymer. The bolt
and washer are moulded into the
material. Used on the XLPE side
of the transition joints;
SMTXB 1502/1522/1532 when
installing 1-core cables with an outer
diameter greater than 40 mm.

IA 1003 IA 2112 - 2113 IKP


Stress controlling tape. Impregnated crepe Impregnated carbon crepe
paper tape. paper (conductive).

Designation Use Length Width Thickness Weight


m mm mm kg/item

GC SMTXB with Ø 100 joint tube Cable Ø 40-45 – – 0.72


IA 1003 Paper-insulated cable joint – – – 0.13
IA 2112 Paper-insulated cable joint 9 10 – 0.40
IA 2113 Paper-insulated cable joint 9 24 – 0.60
IA 2502 For filling cable clamps 3 83 0.5 0.20
IA 2508 For filling cable clamps 14 200 0.5 1.40
IA 2518 For filling cable clamps 10 83 0.5 0.50
IA 2519 For filling cable clamps 14 100 0.5 0.75
IKP – – – – 0.30
RKM 402 For oil filling – – – 0.10

70 We reserve the right to alter the design and range of our products. Kabeldon 2009, edition 1
Kabeldon cable accessories for PILC cables 12-52 kV

Accessories for paper-insulated


cable joints and transition joints

IG 1201

Accessories PILC 12-52 kV


Cold insulating bitumen compound for cable
clamps. IG 1601, IG 1604
Insulating oil, for joints and terminations for
paper-insulated cables 12-52 kV. Need not be
heated at temperatures exceeding +10°C.

IG 1717, 1718
Insulating film made of transparent
polyester for transition joints and
for paper-insulated cables 12-24 kV,
type SMTXB and SMTD.

IK 1002 IK 1003
Linen yarn. Polyester tape.

Designation Length Width Volume Weight


m mm l kg/item

IG 1201 – – – 1.3
IG 1601 – – 1.0 1.0
IG 1604 – – 4.0 4.1
IG 1717 1.7 457 – 0.3
IG 1718 1.5 711 – 0.2
IK 1002 5 – – 0.2
IK 1003 4x1.5 2.5 – 0.1

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 71
Kabeldon
Kabeldon
cable
general
accessories
accessories
Notes
1 kV

Tapes

IA 2333 - 2338 IA 2339 IA 2342 IA 2343


Insulating vulcanizing Insulating vulcanizing Silicon rubber tape. Silicon rubber tape.
tape. tape.

IA 2352 IA 2362 IA 2421 IA 2441 - 2444 RULLE


Semiconducting tape. Filling tape. Electrical Protective tape. Two-layer insulating
tape. tape made of EPDM
and butyl rubber.

Designation Length Width Thickness Weight


m mm mm kg/item

IA 2333 9 38 0.8 0.50


IA 2337 9 19 0.5 0.20
IA 2338 9 38 0.5 0.40
IA 2339 2 25 0.76 0.10
IA 2342 9 25 0.5 0.16
IA 2343 2.5 25 0.5 0.30
IA 2352 4.5 19 0.8 0.10
IA 2362 1.5 38 3.2 0.30
IA 2421 10 19 0.18 0.06
IA 2441 10 25 0.4 0.20
IA 2443 10 50 0.4 0.30
IA 2444 30.5 50 0.4 0.90
RULLE 1 3.5 60 2.0 0.60
RULLE 2 5.5 60 2.0 0.90

72 We reserve the right to alter the design and range of our products. Kabeldon, 2009 Edition 1
Kabeldon general accessories

Other accessories

IK 1105, 1106, 1107, IK 1405, IK 1406


1108, 1109 Lashing wire (tin-coated copper wire).
Abrasive cloth.

IK 1401, IK 1407 IK 1502


Lashing wire (tin-coated copper wire). Lashing wire (galvanized steel wire).

IK 2221 IK 2233
Silicone grease, 25 g. Grease, type AP paste, 10 g.

Designation Length Diameter Coarseness Weight


m mm kg/item

IK 1105 1 – 100 0.1


IK 1106 1 – 80 0.1
IK 1107 1 – 120 0.1
IK 1108 1 – 220 0.1
IK 1109 1 – 400 0.1
IK 1401 2 1.4 – 0.1
IK 1405 5 1.4 – 0.1
IK 1406 9.5 1.4 – 0.2
IK 1407 6 1.0 – 0.2
IK 1502 4 1.5 – 0.1
IK 2221 – – – 0.03
IK 2233 – – – 0.02

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 73
Kabeldon
Kabeldon
cable
general
accessories
accessories
Notes
1 kV

Other accessories

IA 1701 IA 1706 IA 1710


Earthing braid, sold by the Copper net for e.g. SMXB, sold by Earthing braid with
metre, 10 mm². the metre, approx. 10 mm². lining, 22 mm².

IK 2230 MBR 250 SKALUS


Washing cloth, 3 alcohol-soaked Stainless marking tape, Peeling string for
paper cloths 200 x 300 mm. 100 units/kit. XLPE-insulation.

Designation Length Width Thickness Weight


m mm mm

IA 1701 – 16 1.0 0.10 kg/m


IA 1706 – 80 1.0 0.06 kg/m
IA 1710 0.4 27 0.1 0.09 kg/unit
IK 2230 – – – 0.03 kg/unit
MBR 250 0.25 – 1.0 0.50 kg/kit
SKALUS 2 – 1.0 0.02 kg/unit

74 We reserve the right to alter the design and range of our products. Kabeldon, 2009 Edition 1
Kabeldon general accessories

Tools

350 285

730 R
Torque wrench for screw connectors,
screw cable lugs, overhead line clamps,
etc. Supplied with 7 mm socket head, Intercable No. RKS 1607 054
extension and 8 mm internal hexagon Cable shears for cutting cable
head. Ø max 54 mm.
Torque range 6-50 Nm.

305

RKM 1055
Splitting tool for longitudinal splitting
off XLPE-insulation with Ø 10-55
mm.

145 330

RKM 670 RKM 672


Cable knife, 30 mm blade. Sheath removing knife with
two handles for plastic sheated
cable.

Designation Description

730 R Torque wrench


RKS 1607 054 Cable shears
RKM 1055 Peeling tool
RKM 1055 K Spare blade for RKM 1055
RKM 670 Cable knife
RKM 672 Sheath removing knife

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 75
Kabeldon
Kabeldon
cable
general
accessories
accessories
Notes
1 kV

Tools

153
177
Intercable No. AV 6220
Sheath removing tool for
PE-sheathed cable Ø > 20 mm.

Intercable No. FBS 1722 1


Stripping tool for the vulcanized, outer
conducting layer of XLPE-insulated
cable Ø 10-52 mm.
The tool is supplied in a rigid case
with a tube of silicone grease.

235

175

GB-M20 Model 1700 Series


Cutting tool for cable sheath Peeling tool for strippable outer
and XLPE-insulation: conductive layer on XLPE-insulated
Diameter: Ø 15-50 mm cable Ø 13-51 mm.
Cutting depth:  8 mm

Designation Description

AV 6220 Sheath removing tool


FBS-1722 1 Stripping tool
GB-M20 XLPE stripping tool
Model 1700 Series Peeling tool

76 We reserve the right to alter the design and range of our products. Kabeldon, 2009 Edition 1
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Table of contents
Cable accessories 52-420 kV

Page No.

Introduction cable accessories 52-420 kV ............................................................................ 78


Cable terminations, outdoor, porcelain APED 36-84/composite APED P 36 & 72 kV ......... 79
Cable terminations, outdoor porcelain APECB 84-420/composite APECB P 84-300 kV .... 82
Cable terminations, outdoor flexible APSEA 52-72 kV ...................................................... 85
Cable terminations, APEGA GIS/TRF 84-420 kV .................................................................. 88
Cable joints, premoulded JS 52-123 kV, JX 52-123 kV ....................................................... 92
Cable joints, premoulded JS 245 kV, JX 245 kV .................................................................. 96
Cable joints, premoulded SMPGB, SMPGB-C, SMPGB BOX 145-170 kV ......................... 98
Cable joints, premoulded SMPGB 362-420 kV .................................................................. 101
Earth kits for cable terminations.......................................................................................... 103
Tools and oil ........................................................................................................................ 105

Cable accessories 52-420 kV

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 77
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Introduction
Cable accessories 52-420 kV

ABB in Alingsås has a long experience One feature that sets apart our range of
in the area of 52-420 kV and has always led accessories for this voltage range is their
the field in research and development. modular design. This makes the accesso-
We were among the first in the world to use ries unusually easy to install. The installers
stress cone technology to control electrical become familiar with the components, and
fields. this reduces the risk of mistakes.
One reason for our success is that we Unless otherwise specified, the cable
have constantly developed accessories for accessories are supplied as standard with
all types of cables. This has given us an screw connection for conductors.
experience base that is both broad and deep. Another advantage is that our cable
We have also developed our accessories terminations can be assembled on the
to facilitate for optical fibre in power cables, ground under controlled conditions and
and even integrated cross bonding in cable then lifted into place, - simple and safe!
joints. This involves system designers to We offer training courses for installers
improve their systems. and supervisors. For training prospectus,
For more than 20 years we have had our contact our training department.
own testing station to evaluate outdoor
performance.

Assembling premoulded cable joints, Assembly of premoulded cable


SMPGB-C. joint JS.

Our cable terminations can be assembled


horizontally on the ground and then lifted We develop accessories for most cable
into place, both easily and safely! designs, including cables with optical fibre.

78 We reserve the right to alter the design and range of our products. Kabeldon 2009 Edition 1
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

• Reliable
• Proven
• Bolt technology
• Can be assembled horizontally on the
ground before installation
Outdoor cable termination • Composite insulator, low weight

porcelain: APED 36-84


composite: APED 36-72 P

Use
Suitable for installations in which the
termination is to be used as a fixed
connection point and for installations top bolt
where there is a risk of very high
continuous creepage currents.

Standards insulator
Meets the requirements of:
synthetic
SS, IEC, IEEE
insulating oil

Design stress cone


The cable termination consists of
a porcelain or composite insulator
installed on a box body made of Al
castings. box body
The box body consists partly of
insulating material, which provides
insulated installation. The base part cable clamp
must be installed on a bracket.
The field control component is a
premoulded stress cone. APED 521
The insulator has sheds of the
short-long type and is filled with
synthetic insulating oil.

Cable accessories 52-420 kV


The porcelain insulator can be ordered
APED 722 P
in brown or grey. The composite APED 722
APED 843
insulator is only available in grey.
A supporting plate with three stand-off
insulators are used for an insulated Installation
mounting. Installation can be simplified by assembling
The maximum permissible diameter the termination horizontally on the ground
across the oversheath of the cable is 85 mm. before lifting it into place.
The diameter across the prepared insulation
The following cable data should be stated
must be 25-66 mm. Maximum cable cross
when ordering:
section is 1200 mm2.
– Voltage
The top bolt with a diameter of 30 mm,
– Conductor cross section
is included in the kit. Select between screw,
– Conductor material Cu or Al
press or welding type.
– Diameter across prepared insulation
– Screen, cross section and type
– Outer diameter of the cable
– Top bolt:
• Diameter and material (Cu or Al)
for connecting to overhead power line
Ø
• Contact technology, screw (standard),
Prepared insulation press or weld
Ø 25-66 mm

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 79
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Technical specification All dimensions in mm

APED

30 Max 35 Ø 18
Max. permissible forces
acting on the top bolt,
125
horizontally and vertically:
2000 N.

202,5
Creepage
distance

A
182

234

Attachment to bracket for insulated mounting


Three 18 mm holes for M16 bolts.
280

52 Ø 14
There are three versions of insulators for
APED 36-84 kV:
– Without suffix: Brown porcelain in traditional
76
design.
– With suffix G: Grey porcelain in traditional design 32
– With suffix P: Composite insulator with grey
silicone rubber and a fibreglass reinforced epoxy,
resin hollow core, light-weight and less sensibility
for outer damages. (only for 36 and 72 kV) Attachment to beam
Three 14 mm hole for M10 bolts.

Designation Voltage Insulator Creepage distance Dimensions Net weight


min A Ø
kV mm mm kg/item

APED 360 12-36 Porcelain 915 530 267 38


APED 521 52 Porcelain 1340 645 267 48
APED 722 72 Porcelain 2200 925 267 60
APED 843 84 Porcelain 2635 1040 267 67

APED 360 P 36 Composite 950 570 270 27


APED 722 P 72 Composite 2330 950 270 33

80 We reserve the right to alter the design and range of our products. Kabeldon 2009 Edition 1
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Applications and accessories


APED

30°

PIU-APED
Post insulator kit for
fixing to a supporting
GAP-APED plate for insulated
Inclination up to 30°. Rod gap. installation.

Cable accessories 52-420 kV


RE-APED-T RE-APED-M
Re-assembly kit for APED-T Re-assembly kit for APED-M
(for XLPE Ø 25-48.1 mm). (for XLPE Ø 48-66 mm).

To be ordered separately

Designation Description Use See page

GAP-APED Rod gap Protects against over-voltage. 81


PIU-APED Post insulator kit When insulated mounting. 81
RE-APED-M Re-assembly kit Used for re-assembly of a termination. 81
RE-APED-T (Stress cone and top bolt to be ordered
separately as required).
JSA Earthing kit For cable with metallic screen. 103
Not needed when cable has only Cu wire screen.
SCK Screen connection For radial waterproof cable with
Al-foil and Cu wire screen. 103

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 81
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

• Reliable
• Proven
• Bolt technology
• Can be assembled
horizontally on the
Outdoor cable termination ground before installation
• Will fit large cables
porcelain: APECB 84-420 • Low total weight
• Integrated insulated
composite: APECB 84-300 P installation
• Few components
Use APECB 420
For installations in which the
termination is to be used as a fixed
connection point and in installations
where there is a risk of very high
continuous creepage currents.

Standard
Meets the requirements of:
APECB 245-300 P
SS, IEC, IEEE

Design
The cable termination consists of APECB 170
a porcelain or composite insulator APECB 84
installed on a box body made of Al
castings.
top bolt
The box body consists partly of
insulating material, which provides
insulated installation. The base part insulator
must be installed on a bracket.
For 420 kV post-insulator kit must synthetic
insulating oil
be used.
The field control component is a
premoulded stress cone. stress cone
The insulator has sheds of short-
long type and is filled with synthetic base part
insulating oil. cable clamp
The porcelain insulator can be ordered
in brown or grey. The composite insulator
is only available in grey for 84-300 kV. APECB 84 P
APECB 145 P
For the maximum permitted diameter
across the oversheath of the cable and APECB 245-300
the diameter across prepared insulation, Installation
see the table below. Installation can be simplified by assembling
A screw clamp in the top fitting is used the termination horizontally on the ground
to connect the conductor to the top bolt. before lifting it into place.
Top bolt and screw clamp are included in
the kit. When ordering, please state the
following data:
– Voltage
– Conductor cross section, diameter
– Diameter across prepared insulation
– Screen, cross section and type
(optical fibres)
Voltage XLPE-diameter Outer
Ø mm sheath
– Outer diameter of cable
Ø Ø – Insulator, porcelain or composite
kV min max Ø mm
– Top bolt:
APECB 245 APECB 84  170 45.5 107 170 • Diameter and material (Cu or Al)
APECB 300 APECB 145 245 45.5 120 170
300 80 120 170
for connecting to overhead power
APECB 420 APECB 170
420 80 120 170 line
Prepared insulation

82 We reserve the right to alter the design and range of our products. Kabeldon 2009 Edition 1
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Technical specification All dimensions in mm

APECB 84-420, APECB 84-300 P

ØB Ø 18,5
Max. permissible forces
acting on the top bolt,
horizontally and vertically: 140 345-350
Min 125
2000 N.

345-350
Fixing to bracket for 84-300 kV min 280
Creepage distance

Insulated or non-insulated:
four 18 mm holes for M16 bolts.
Ø 22

A 150 495

ØC Fixing to bracket for 420 kV


Non-insulated: four 18 mm holes
for M16 bolts. 495
Insulated: four 22 mm holes for min 350
M20 bolts.

There are three versions of insulators for APECB 84-300 kV:


– With suffix B: Brown porcelain in traditional design.

Cable accessories 52-420 kV


– With suffix G: Grey porcelain in traditional design
– With suffix P: Composite insulator with grey
D
silicone rubber and a fibreglass reinforced epoxy, resin hollow
core, light-weight and less sensibility for outer damages.
APECB 420 kV is available only with brown porcelain!

Designation* Voltage Insulator Dimensions Creepage Net


A ØB ØC D distance min weight
kV mm mm kg/kit

APECB 841 84 Porcelain 1300 40/50/54/60 386 235 2710 160


APECB 1452 145 Porcelain 1620 40/50/54/60 386 235 3870 185
APECB 1703 170 Porcelain 1860 40/50/54/60 386 235 4570 220
APECB 1704 170 Porcelain 2120 40/50/54/60 396 235 5500 230
APECB 1705 170 Porcelain 2620 40/50/54/60 396 235 7250 325
APECB 2456 245 Porcelain 2570 40/50/54/60 520 235 8300 515
APECB 3006 300 Porcelain 2570 40/50/54/60 520 235 8300 515
APECB 4201 420 Porcelain 4575 40/50/54/60 760 500 14700 1700

APECB 841 P 84 Composite 1320 40/50/54/60 359 235 2820 100


APECB 1452 P 145 Composite 1620 40/50/54/60 359 235 3750 105
APECB 1703 P 170 Composite 1820 40/50/54/60 359 235 4500 110
APECB 1704 P 170 Composite 2140 40/50/54/60 359 235 5950 120
APECB 1705 P 170 Composite 2720 40/50/54/60 359 235 8000 135
APECB 2456 P 245 Composite 3030 40/50/54/60 490 235 9360 290
APECB 3006 P 300 Composite 3030 40/50/54/60 490 235 9360 290
* When the cable diameter is greater than 120 mm, add: Ø 170 at the end of the designation (e.g. APECB 841 Ø 170).
For 245 kV also add OKT when the cable has optical fibre.
For 84-170 kV and 300-420 kV see next page!

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 83
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Applications and accessories


APECB 84-420, APECB 84-300 P

30°

Inclination up to 30°.
GAP-APECB
Rod gap.

OKT PIU-APEC
Opto kit for cables with Post insulator kit for fixing
integrated optical fibres in APECB 420 kV when
the earth screen. insulated mounting.

To be ordered separately
Designation Description Use See page

GAP-APECB Rod gap Protection against over-voltage 84-170 kV. 84


OKT Optofibre kit For optical fibres in the screen 84
of the cable 84-420 kV.
PIU-APEC Post insulator For insulated mounting of APECB 420 84
JSA Earthing kit For cable with metallic screen.
Not needed if cable has only
Cu wire screen. 103
SCK Screen connection For radial waterproof cable with
Al foil and Cu-wire screen. 103

84 We reserve the right to alter the design and range of our products. Kabeldon 2009 Edition 1
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

• Cold-applied
• Premoulded for easy installation
• Versatile can be completed by
several sheds
• Can be used with cable drum
Outdoor flexible for mobile transformer station
• Bolt technology
cable termination • Can be installed at any angle
• Can be used as bushing on the
APSEA 52-72 wall with two APSEA and a
cable between them

Use
Flexible cable termination, suitable for
installations in which the termination can
be installed in any angle. The termination is top bolt
not self-supporting.
creepage current
Standards electrode
Meets the requirements of:
top cap
SS and IEC.
sheds
Design
The cable termination is made up of
modules comprising a field controlling
stress relief cone, sheds to increase the
creepage distance and a top cap. The
modules are made of proven weather and
leakage current resistant rubber.
stress cone
The diameter across the prepared
insulation is 33-66 mm. Top bolt or cable creepage current
collector
lug is to be ordered separately. Top bolt;
see following pages.

Cable accessories 52-420 kV


Installation
The termination is installed easily, entirely
without heat. The stress cone and sheds
are to be threaded onto the cable and
"snapped" together. APSEA 72 APSEA 52
Installation can be simplified by
assembling the termination horizontally
on the ground before lifting it into place.

The following cable data should be stated


when ordering:
– Voltage
– Conductor cross section
– Conductor material Cu or Al
– Diameter across prepared insulation
– Screen, cross section and type
– Outer diameter of the cable
– Top bolt:
• Diameter and material (Cu or Al)
for connecting to overhead power line
Ø Prepared insulation
Ø 33-66 mm • Contact technology, bolt (standard),
press or weld

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 85
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Technical specification All dimensions in mm

APSEA 52-72

Ø 30/40

125

Ø 165
Creepage distance

Designation Voltage Prepared Creepage Length Net weight


insulation distance
Ø min A
kV mm mm mm kg/item

APSEA 521 U 52 33-36 1150 580 4


APSEA 522 U 52 36-39.5 1150 580 4
APSEA 523 U 52 39.5-43 1150 580 4
APSEA 524 U 52 43-48 1150 580 4
APSEA 525 U 52 48-54 1150 580 4
APSEA 526 U 52 54-60 1250 650 4
APSEA 527 U 52 60-66 1250 650 4

APSEA 721 U 72 33-36 1420 690 5


APSEA 722 U 72 3-39.5 1420 690 5
APSEA 723 U 72 39.5-43 1420 690 5
APSEA 724 U 72 43-48 1420 690 5
APSEA 725 U 72 48-54 1790 870 5
APSEA 726 U 72 54-60 1790 870 5
APSEA 727 U 72 60-66 1790 870 5

86 We reserve the right to alter the design and range of our products. Kabeldon 2009 Edition 1
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Applications and accessories


APSEA 52-72

A Ø
180 °

Top cap, THSA


125

XLPE Ø range Ø Top hole Top cap


designation

33-48 mm (APSEA 521-524, APSEA 721-724)


28 THS 28
37 THS 37
47 THS 47
B 60 THS 60

A/K-TBF SKR 48-66 mm (APSEA 525-527, APSEA 725-727)


Top bolt 28 THSA 28
37 THSA 37
47 THSA 47
60 THSA 60
Can be installed in any angle. Select top cap based on the APSEA size and with a
hole that matches the outer diameter of the available
Top bolts cable lug or top bolt.

Designation Cable Cable Diameter Net weight


conductor cross section A B

Cable accessories 52-420 kV


material mm² mm kg/kit

A-TBF 30 120 SKR Al 120 30 45 0.5


A-TBF 30 150-185 SKR Al 150, 185 30 45 0.5
A-TBF 30 240 SKR Al 240 30 50 0.8
A-TBF 30 300-400 SKR Al 300, 400 30 55 0.8
A-TBF 30 500 SKR Al 500 30 60 0.9
A-TBF 30 630 SKR Al 630 30 60 0.9
A-TBF 40 800 SKR Al 800 40 65 1.2
A-TBF 40 1000 SKR Al 1000 40 65 1.2
A-TBF 40 1200 SKR Al 1200 40 65 1.1
K-TBF 30 120 SKR Cu 120 30 45 1.6
K-TBF 30 150-185 SKR Cu 150, 185 30 45 1.6
K-TBF 30 240 SKR Cu 240 30 50 2.4
K-TBF 30 300-400 SKR Cu 300, 400 30 55 2.4
K-TBF 30 500 SKR Cu 500 30 60 2.8
K-TBF 30 630 SKR Cu 630 30 60 2.8
K-TBF 40 800 SKR Cu 800 40 65 4.0
K-TBF 40 1000 SKR Cu 1000 40 65 3.8
K-TBF 40 1200 SKR Cu 1200 40 65 3.5

To be ordered separately
Designation Description Use See page

Cable lug Cable lug – 59


UKR Universal clamp For fixing cables. 107
JSA Earthing kit For cable with metallic screen.
Not needed if cable has only Cu wire screen. 103
SCK Screen connection For radial waterproof cable with
Al foil and Cu-wire screen. 103

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 87
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

• Reliable
• Proven technique
• Bolt technology
• Can be assembled
horizontally on the
Cable termination for connection ground before installation
• Flexible, fits big cables
to gas-insulated switchgear (GIS)
and transformers (TRF)
APEGA 84-420

Use
Suitable for installations where the APEGA 420
termination is to be used as a fixed
connection point in gas-insulated
switchgear, in transformers without
top fitting
a separate cable box or where the APEGA 84
cable box is filled with transformer oil.

Standards epoxy
insulator
Meets the requirements of:
SS, IEC, IEEE syntetic
insulating oil
stress cone
Design
The cable termination consists of an pressure
ring
epoxy insulator standing on a base
made of aluminium alloy. box body
The field controlling component is a
stress cone made of rubber. APEGA 170 cable clamp
The insulator is filled with synthetic
APEGA 300
insulating oil. A flange for insulated mounting
is integrated in the epoxy insulator.
APEGA 245
A pressure ring is also included,
see next page.
For the maximum permissible diameter
across the sheath of the cable and the Voltage Cable insulation Ø Oversheath
diameter across the prepared cable insulation, min max Ø
see the table. kV mm mm mm
84 25 66 85
170 45.5 100 150
Installation 245 73 120 160
Installation can be simplified by assembling 300 73 120 160
the termination horizontally on the ground 420 73 120 160
before lifting it into place.
The following cable data should be stated
when ordering:
– Voltage
– Conductor cross section
– Conductor material Cu or Al
– Diameter across prepared insulation
– Screen, cross section and type (if optical fibre)
Ø Ø
– Outer diameter of the cable
Ø
Type of connector:
– Bolt (standard )
APEGA 245 APEGA 170 APEGA 84 – Weld (up to 170 kV)
APEGA 300 Prepared insulation
APEGA 420

88 We reserve the right to alter the design and range of our products. Kabeldon 2009 Edition 1
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Technical specification All dimensions in mm

APEGA 84-420

Expansion Ø 690
vessel Ø 640

A Ø 18 (20x)
Ø

Ø 448

AF 420
Adapter flange for APEGA 420.

Ø 270 320

Cable accessories 52-420 kV


Ø 12 (8x)
Ø 19 (12x) Ød

Ø 217 270 b

Ø 300 345 a
Pressure ring for APEGA 84. Pressure ring for APEGA 170. Pressure ring for APEGA 245-420.

APEGA a b c d

245-300 612 450 582 18 (16x)


420 570 464 535 14 (20x)

Designation Voltage Standard Dimensions Net weight


A Ø
kV mm kg/item

APEGA 841 84 IEC 60859 ~ 1030 245 55


APEGA 1703 170 IEC 62271-209 ~ 1460 298 75
APEGA 2456 245 IEC 62271-209 ~ 1670 450 270
APEGA 3006 300 IEC 62271-209 ~ 1670 450 270
APEGA 4202 420 IEC 62271-209 ~ 2175 614 400

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 89
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Technical specification for


connecting APEGA 84-420
to a transformer

Expansion vessel CST 84/CST 170 Expansion vessel

A Ø
A

Dimension drawing for APEGA 84-170 kV.


Ø 370

Dimension drawing for APEGA 245-420 kV. Ø 220

32

8
CST 245-420 CST 84, CST 170 AFT 1703
Corona shield for installing Corona shield for installing Adapter flange for welding
APEGA 245-420 kV in transformer. APEGA 84 kV and APEGA between APEGA 170 and
170 kV in transformer. transformer box.

Designation Voltage Dimensions Dimensions Weight


standard A Ø
kV mm kg/item

APEGA 841 TRF 84 EN 50299 ~ 1150 245 55


APEGA 1703 170 EN 50299 ~ 1580 298 75
APEGA 245 245 EN 50299 ~ 1830 450 270
APEGA 300 300 EN 50299 ~ 1830 450 270
APEGA 420 420 EN 50299 ~ 2335 614 400

To be ordered separately
Designation Description Use

CST 84 Corona shield For installing APEGA 84 kV in transformer


CST 170 Corona shield For installing APEGA 170 kV in transformer
CST 245-420 Corona shield For installing APEGA 245-420 kV in transformer
AFT 1703 Adapter flange Adapter flange to be welded between termination and transformer

90 We reserve the right to alter the design and range of our products. Kabeldon 2009 Edition 1
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Tools and accessories


APEGA

SPT 1
Circlip pliers for installation RE-APEGA
of top fitting. Re-assembly kit.

SPV 1
Panduit pliers for bundle tape
APEGA 170 kV.

Cable accessories 52-420 kV


OKT
Optofibre kit for cables with integrated optical DMT 1
fibres in the earth screen. Top fitting removal kit.

To be ordered separately
Designation Description Use

SPT 1 Circlip pliers When installing top fitting.


SPV 1 Panduit pliers For installation of bundle tape around stress cone.
OKT Optofibre kit For cables with integrated optical fibres in the earth screen
RE-APEGA Re-assembly kit Used for re-assembly of a termination.
(Stress cone and top bolt must be ordered separately
as required).
DMT 1 Top fitting removal kit When removing top fitting.
JSA Earthing kit For cable with metallic screen (see page 103).
Not needed if cable has only Cu wire screen.
SCK Screen connection For Al-foil radial waterproof and Cu-wire screen cable
(see page 103).

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 91
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

• Prefabricated for safe


and easy installation
• Active pressure
• Reliable
• Joint bodies routine-
Premoulded one-piece tested according to IEC
• Bolt connector technology
cable joints with or without • Compact joint for
minimal cable stripping
screen interruption
JX 52-123 or JS 52-123

Use: Design:
For jointing XLPE- or EPR-insulated Premoulded three-layer rubber body:
52-123 kV cables with Al or Cu conductors conductive / insulating / conductive.
and different cable sheaths. The joint is available either with (JX) or
without (JS) screen interruption.
Standards: The joints are supplied with screw cable
Meets the requirements of: connector and heat-shrink oversheath.
- IEC 60840 including Annex H A torque wrench, mounting kit, installation
cone, installation tool, RKM 123 and saw,
RKM 850 are needed for assembling.
For diameter across the prepared
insulation and conductor cross section,
see table below.

JS
Premoulded cable joint without
screen interruption.

JX
Premoulded cable joint with
Designation Oversheath Installation tube*
screen interruption.
Ø mm Ø mm

Installation kit 63 < 51 63


Installation kit 75 51-63 75
Installation kit 83 63-68 83
Installation kit 90 68-75 90
Installation kit 100 75-84 100
Installation kit 110 84-94 110
Installation kit 125 94-108 125

* Installation tube must be chosen according to


diameter of the cable oversheath.

For essential equipment for installion, see The following cable data should be stated
following pages! when ordering:
– Voltage
– Conductor cross section
Voltage XLPE-Ø Over- Conductor
– Conductor material Cu or Al
min max sheath Ø cross section
kV mm mm mm mm2 – Diameter across prepared insulation
– Diameter across conductor
52 33 75 Max 94 150-1600 – Screen, cross section and type
72 33 75 Max 94 150-1600
– Outer diameter of the cable
123 46 100 Max 108 150-2500

92 We reserve the right to alter the design and range of our products. Kabeldon 2009 Edition 1
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Technical specification All dimensions in mm

JS 52-123

Designation XLPE- Dimensions Net Designation XLPE- Dimensions Net


diameter L Ø weight diameter L Ø weight
mm mm kg/kit mm mm kg/kit

Copper wire screen Copper wire screen


JS-A 05210 C 33-38 1460 140 25 JS-A 07210 C 33-38 1460 140 25
JS-A 05211 C 38-42 1460 140 25 JS-A 07211 C 38-42 1460 140 25
JS-A 05212 C 42-47 1460 150 25 JS-A 07212 C 42-47 1460 150 25
JS-A 05213 C 47-54 1460 150 25 JS-A 07213 C 47-54 1460 150 25
JS-A 05214 C 54-63 1460 170 25 JS-A 07214 C 54-63 1460 170 25
JS-A 05215 C 63-75 1460 170 25 JS-A 07215 C 63-75 1460 170 25

Metal-PE laminated (PAL) Metal-PE laminated (PAL)


JS-A 05210 P 33-38 1460 140 25 JS-A 07210 P 33-38 1460 140 25
JS-A 05211 P 38-42 1460 140 25 JS-A 07211 P 38-42 1460 140 25
JS-A 05212 P 42-47 1460 150 25 JS-A 07212 P 42-47 1460 150 25
JS-A 05213 P 47-54 1460 150 25 JS-A 07213 P 47-54 1460 150 25
JS-A 05214 P 54-63 1460 170 25 JS-A 07214 P 54-63 1460 170 25
JS-A 05215 P 63-75 1460 170 25 JS-A 07215 P 63-75 1460 170 25

Cable accessories 52-420 kV


Metal screen lead, corrugated copper Metal screen lead, corrugated copper
JS-A 05210 M 33-38 1460 140 25 JS-A 07210 M 33-38 1460 140 25
JS-A 05211 M 38-42 1460 140 25 JS-A 07211 M 38-42 1460 140 25
JS-A 05212 M 42-47 1460 150 30 JS-A 07212 M 42-47 1460 150 30
JS-A 05213 M 47-54 1460 150 30 JS-A 07213 M 47-54 1460 150 30
JS-A 05214 M 54-63 1460 170 30 JS-A 07214 M 54-63 1460 170 30
JS-A 05215 M 63-75 1460 170 30 JS-A 07215 M 63-75 1460 170 30

Designation XLPE Dimensions Weight Designation XLPE Dimensions Weight


diameter L Ø diameter L Ø
mm mm kg/kit mm mm kg/kit

Copper wire screen Metal screen lead, corrugated copper


JS-A 12310 C 46-51 1460 170 28 JS-A 12310 M 46-51 1460 176 29
JS-A 12311 C 51-57 1460 174 28 JS-A 12311 M 51-57 1460 180 29
JS-A 12312 C 57-63 1460 180 30 JS-A 12312 M 57-63 1460 195 31
JS-A 12313 C 63-72 1460 190 30 JS-A 12313 M 63-72 1460 198 31
JS-A 12314 C 72-84 1460 212 32 JS-A 12314 M 72-84 1460 218 33
JS-A 12315 C 84-100 1460 220 32 JS-A 12315 M 84-100 1460 226 33

Metal-PE laminated (PAL)


JS-A 12310 P 46-51 1460 176 29
JS-A 12311 P 51-57 1460 180 29
JS-A 12312 P 57-63 1460 195 31
JS-A 12313 P 63-72 1460 198 31
JS-A 12314 P 72-84 1460 218 33
JS-A 12315 P 84-100 1460 226 33

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 93
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Technical specification All dimensions in mm

JX-A 52-123

Designation XLPE- Dimensions Net Designation XLPE- Dimensions Net


diameter L Ø weight diameter L Ø weight
mm mm kg/kit mm mm kg/kit

Copper wire screen Copper wire screen


JX-A 05210 C 33-38 1800 200-235 55 JX-A 07210 C 33-38 1800 200-235 55
JX-A 05211 C 38-42 1800 200-235 55 JX-A 07211 C 38-42 1800 200-235 55
JX-A 05212 C 42-47 1800 200-235 55 JX-A 07212 C 42-47 1800 200-235 55
JX-A 05213 C 47-54 1800 200-235 55 JX-A 07213 C 47-54 1800 200-235 55
JX-A 05214 C 54-63 1800 200-235 55 JX-A 07214 C 54-63 1800 200-235 55
JX-A 05215 C 63-75 1800 200-235 55 JX-A 07215 C 63-75 1800 200-235 55

Metal-PE laminated (PAL) Metal-PE laminated (PAL)


JX-A 05210 P 33-38 1800 200-235 55 JX-A 07210 P 33-38 1800 200-235 55
JX-A 05211 P 38-42 1800 200-235 55 JX-A 07211 P 38-42 1800 200-235 55
JX-A 05212 P 42-47 1800 200-235 55 JX-A 07212 P 42-47 1800 200-235 55
JX-A 05213 P 47-54 1800 200-235 55 JX-A 07213 P 47-54 1800 200-235 55
JX-A 05214 P 54-63 1800 200-235 55 JX-A 07214 P 54-63 1800 200-235 55
JX-A 05215 P 63-75 1800 200-235 55 JX-A 07215 P 63-75 1800 200-235 55

Metal screen lead, corrugated copper Metal screen lead, corrugated copper
JX-A 05210 M 33-38 1800 200-235 60 JX-A 07210 M 33-38 1800 200-235 60
JX-A 05211 M 38-42 1800 200-235 60 JX-A 07211 M 38-42 1800 200-235 60
JX-A 05212 M 42-47 1800 200-235 60 JX-A 07212 M 42-47 1800 200-235 60
JX-A 05213 M 47-54 1800 200-235 60 JX-A 07213 M 47-54 1800 200-235 60
JX-A 05214 M 54-63 1800 200-235 60 JX-A 07214 M 54-63 1800 200-235 60
JX-A 05215 M 63-75 1800 200-235 60 JX-A 07215 M 63-75 1800 200-235 60

Designation XLPE Dimensions Weight Designation XLPE Dimensions Weight


diameter L Ø diameter L Ø
mm mm kg/kit mm mm kg/kit

Copper wire screen Metal screen lead, corrugated copper


JX-A 12310 C 46-51 1800 235-300 60 JX-A 12310 M 46-51 1800 235-300 60
JX-A 12311 C 51-57 1800 235-300 60 JX-A 12311 M 51-57 1800 235-300 60
JX-A 12312 C 57-63 1800 235-300 60 JX-A 12312 M 57-63 1800 235-300 65
JX-A 12313 C 63-72 1800 235-300 60 JX-A 12313 M 63-72 1800 235-300 65
JX-A 12314 C 72-84 1800 235-300 65 JX-A 12314 M 72-84 1800 235-300 65
JX-A 12315 C 84-100 1800 235-300 65 JX-A 12315 M 84-100 1800 235-300 65

Metal-PE laminated (PAL)


JX-A 12310 P 46-51 1800 235-300 60
JX-A 12311 P 51-57 1800 235-300 60
JX-A 12312 P 57-63 1800 235-300 65
JX-A 12313 P 63-72 1800 235-300 65
JX-A 12314 P 72-84 1800 235-300 65
JX-A 12315 P 84-100 1800 235-300 65

94 We reserve the right to alter the design and range of our products. Kabeldon 2009 Edition 1
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Equipment for installation


of JS and JX 52-123

Installation cone
For installing adapter.

RKM 145
Installation tool.

Cable accessories 52-420 kV

Designation Description

RKM 145 Installation tool


Installation cone Installation cone

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 95
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

• Premoulded for safe


and easy installation
• Active pressure
• Joint bodies routine-
tested according to IEC
Premoulded one-piece • Bolt connector technology

cable joints with or without


screen interruption
JX 245 or JS 245

Use: Design:
For jointing XLPE-insulated 245 kV cables Premoulded one-piece joint body.
with Al or Cu conductors and various types The joint is available either with (JX) or
of cable sheaths. without (JS) screen interruption.
The joints are supplied complete with
Standards: screw cable connector for both conductor
Meets the requirements of: and screen.
- IEC 62067 including Annex D Torque wrench and installation tool
RKM 245 are needed for assembling.

JX
Premoulded cable joint with
screen interruption.

JS
Premoulded cable joint without
screen interruption.

The following cable data should be stated


when ordering:
– Voltage
– Conductor cross section
– Conductor material Cu or Al
– Diameter across prepared insulation
Voltage XLPE-Ø Oversheath Conductor – Diameter across conductor
min max max Ø cross section – Screen, cross section and type
kV mm mm mm mm²
– Outer diameter of the cable
245 74 120 143 500-2500 – If optical fibres in screen

96 We reserve the right to alter the design and range of our products. Kabeldon 2009 Edition 1
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Technical specification All dimensions in mm

JX and JS 245

2730

400

JX

2600

346

JS

JX 245 P for aluminium laminated cables JS 245 P for aluminium laminated cables

Joint body size XLPE-diameter (mm) Joint body size XLPE-diameter (mm)
10 74-81 10 74-81
11 79-87 11 79-87
12 85-94 12 85-94
13 92-102 13 92-102
14 100-110 14 100-110
15 108-120 15 108-120

Weight kg/kit 170-200 Weight kg/kit 170-200

Cable accessories 52-420 kV


Accessories and installation tool for JX and JS 245 kV

RKM 245 OKJ


Installation tool. Kit for optical fibers in screen.

Designation Description

RKM 245 Installation tool


OKJ Kit for optical fibres
Soldering kit Soldering kit

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 97
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

• Premoulded for safe


and easy installation
• Active pressure
• Reliable
• Joint bodies routine-
Premoulded cable joint tested according to
IEC before delivery
SMPGB, SMPGB-C, SMPGB BOX • Bolt connector technology
• Compact joint for
145-170 minimal cable stripping
• Easy jointing of cables
with different sizes

Use There are joints for different types of


Suitable for jointing XLPE or EPR insulated screen, armouring and oversheath:
cables with Al and Cu conductors and
different types of cable sheaths. SMPGB
Standard joint with heat-shrink oversheath.
Standard
Meets the requirements of: SMPGB-C
SS, IEC Cable joint with screen interruption.
The same technology as for SMPGB BOX
Design (see following paragraph) is used for the
The cable joint consists of a joint tube with oversheath for this design.
two prefabricated adapters and a screw
cable clamp. For diameter across the pre- SMPGB BOX
pared insulation and conductor diameter, Standard joint with reinforced oversheath in
see the table below. the case of locating in or under water. Two
Screw technology facilitates jointing of protective halves form a box which is filled
the conductor. A torque wrench, installa- with two-component compound for blocking
tion cone and installation tools RKM 170 are water and to provide mechanical properties.
needed for assemblying.

SMPGB

SMPGB-C Pb

SMPGB Pb BOX
The following cable data should be stated
when ordering:
– Voltage
– Conductor cross section
Voltage XLPE-Ø Conductor – Conductor material Cu or Al
mm Ø mm – Diameter across prepared insulation
kV min max min/max
– Diameter over conductor
145 48 107 16-65 – Screen, cross section and type
170 61 107 16-65 – Outer diameter of the cable

98 We reserve the right to alter the design and range of our products. Kabeldon 2009 Edition 1
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Technical specification All dimensions in mm

SMPGB 145-170

SMPGB Ø L SMPGB L Ø L
mm mm
14501-14509 std 1300 205 1701-1704 std 1300 205 Ø
14510-14513 std 1950 205 1705-1708 std 1950 205
14501-14509 PAL 1600 210 1701-1704 PAL 1600 210
SMPGB
14510-14513 PAL 2250 210 1705-1708 PAL 2250 210
14501-14509 Pb 1620 245 1701-1704 Pb 1650 245
14510-14513 Pb 2220 245 1705-1708 Pb 2220 245

SMPGB-C L B/Ø L
mm
1701-1704 Pb 1660 410
1705-1708 Pb 1660 410 B
1701-1704 PAL 1500 400
1705-1708 PAL 2080 400
SMPGB-C Pb

SMPGB BOX L B/Ø


mm L
14501-14505 Pb 1660 410
14506-14513 Pb 1660 410
14501-14513 PAL 1660 410 B
1701-1704 Pb 1660 410
1705-1708 Pb 1500 410
1701-1704 PAL 1500 400 SMPGB Pb BOX

Designation* Designation* Designation* Voltage XLPE Installation

Cable accessories 52-420 kV


SMPGB SMPGB-C SMPGB diameter cone
Standard Cross-bonding with BOX kV mm

SMPGB 14501 – SMPGB 14501 BOX 145 48-51 4209.2384


SMPGB 14502 – SMPGB 14502 BOX 145 50-53 4209.2385
SMPGB 14503 – SMPGB 14503 BOX 145 52-56 4209.2386
SMPGB 14504 – SMPGB 14504 BOX 145 55-59 4209.2387
SMPGB 14505 – SMPGB 14505 BOX 145 58-62 4209.2388
SMPGB 14506 – SMPGB 14506 BOX 145 61-65 4209.2331
SMPGB 14507 – SMPGB 14507 BOX 145 63-68 4209.2332
SMPGB 14508 – SMPGB 14508 BOX 145 66-71 4209.2333
SMPGB 14509 – SMPGB 14509 BOX 145 69-76 4209.2334
SMPGB 14510 – SMPGB 14510 BOX 145 74-82 4209.2335
SMPGB 14511 – SMPGB 14511 BOX 145 80-91 4209.2336
SMPGB 14512 – SMPGB 14512 BOX 145 89-100 4209.2337
SMPGB 14513 – SMPGB 14513 BOX 145 98-107 4209.2400
SMPGB 1701 SMPGB-C 1701 SMPGB 1701 BOX 170 61-65 4209.2331
SMPGB 1702 SMPGB-C 1702 SMPGB 1702 BOX 170 63-68 4209.2332
SMPGB 1703 SMPGB-C 1703 SMPGB 1703 BOX 170 66-71 4209.2333
SMPGB 1704 SMPGB-C 1704 SMPGB 1704 BOX 170 69-76 4209.2334
SMPGB 1705 SMPGB-C 1705 SMPGB 1705 BOX 170 74-82 4209.2335
SMPGB 1706 SMPGB-C 1706 SMPGB 1706 BOX 170 80-91 4209.2336
SMPGB 1707 SMPGB-C 1707 SMPGB 1707 BOX 170 89-100 4209.2337
SMPGB 1708 SMPGB-C 1708 SMPGB 1708 BOX 170 98-107 4209.2400
* For lead-sheathed cable add Pb at the end of the type designation. For metal-PE laminated
cable with radial waterproofing, add PAL (e.g. SMPGB 1701 Pb, SMPGB 1701 PAL).
For SMPGB with BOX; add Pb or PAL before BOX.
For installation tool see next page.

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 99
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Tool and accessories


SMPGB 145-170

Max 4 m

Installation cone
For installing adapter.

RKM 170
Installation tool for
SMPGB joint 145-170 kV.

Designation Description Weight


kg/kit

RKM 170 Installation cone for SMPGB 145-170 kV 42


Installation cone Installation cone

100 We reserve the right to alter the design and range of our products. Kabeldon 2009 Edition 1
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

• Premoulded for safe


and easy installation
• Active pressure
• Reliable
• Joint bodies routine-
Premoulded cable joint tested according to
IEC before delivery
SMPGB 362-420 • Bolt connector technology
• Compact joint for
minimal cable stripping
• Easy jointing of cables
with different sizes

Use The use of screws makes conductor jointing


For jointing XLPE- or EPR-insulated cables easier. Torque wrench, assembly cone
with aluminium and copper conductors and assembly tool RKM 362 are needed for
and different types of cable sheaths. assemblying.
The joints are used for various types of
Standard screen, armouring and oversheath.
Meets the requirements of:
SS, IEC, IEEE

Design
The cable joint consists of a jointing tube
with two premoulded adapters made of
rubber, a screw cable clamp and a heat-
shrink oversheath.
See table below for diameter across the
prepared insulation.

Cable accessories 52-420 kV


The following cable data should be stated
when ordering:
– Voltage
– Conductor cross section
For SMPGB 420 kV contact us! – Conductor material Cu or Al
– Diameter across prepared insulation
– Diameter over conductor
– Screen, cross section and type
– Outer diameter of the cable

Designation* Voltage XLPE Installation


diameter cone
kV mm

SMPGB 3622 362 80-88 4209.2378


SMPGB 3623 362 86-95 4209.2379
SMPGB 3624 362 93-103 4209.2380
SMPGB 3625 362 101-111 4209.2381
SMPGB 3626 362 109-120 4209.2382
* For lead sheathed cable add Pb at the end of type designation and for
poly metal-PE laminated cable add PAL (e.g. SMPGB 3622 Pb, SMPGB 3622 PAL).

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 101
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Technical specification, All dimensions in mm

tools and accessories


SMPGB 362-420

SMPGB
L

SMPGB L Ø
mm

362x PAL 2000 350


362x Pb 2100 375

Max 3 m

Installation cone RKM 362


For installing adapter. Installation tool for SMPGB joint 362 kV.

To be ordered separately
Designation Description Net weight
kg/kit

RKM 362 Installation tool for SMPGB 362 kV 74


Installation cone Installation cone

102 We reserve the right to alter the design and range of our products. Kabeldon 2009 Edition 1
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Earthing kits for cable terminations


Note that the earthing kit increases the cable
outer diameter by 20 mm!
The earthing kit connects the screen of the
cable to the termination. The earthing kit is For corrugated screen made of:
designed to handle the total screen • Aluminium use JSA 1 Al
cross section. It also provides the cable • Copper use JSA 1 Pb
with a sealing. • Stainless steel; contact us

Cable with copper wire screen only. No earthing kit is needed.

Cable with copper wire screen and metal-PE laminate. Use earthing kit SCK 2.

Cable accessories 52-420 kV


Metal-sheathed cable with or without screen wires. Use earthing kit JSA 1 Pb.

Cable with copper tape screen and cable with armouring. Contact us.

Designation Diameter over No of Total No of For cables with


oversheath plates Cu equivalent cross Cu braids
section in earthing kit
mm mm2

JSA 1 Al – – 130 6 Corrugated aluminium


JSA 1 Pb 40-120* – 130 6 Lead sheathed or corrugated copper
JSA 1 Pb 10 120-150* – 220 10 Lead sheathed or corrugated copper
JSA 1 Pb 15 150-200* – 330 15 Lead sheathed or corrugated copper
SCK 2-1 13-26 1 – – Metal-PE laminated as radial watertightness
SCK 2-2 26-46 2 – – Metal-PE laminated as radial watertightness
SCK 2-3 46-66 3 – – Metal-PE laminated as radial watertightness
SCK 2-4 66-86 4 – – Metal-PE laminated as radial watertightness
SCK 2-5 86-106 5 – – Metal-PE laminated as radial watertightness
SCK 2-6 106-126 6 – – Metal-PE laminated as radial watertightness
SCK 2-7 126-145 7 – – Metal-PE laminated as radial watertightness
* Applicable for metalic sheath < 4 mm. For thicker metallic sheath contact us.

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 103
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Accessories All dimensions in mm

ARM Selection guide for ARM


For restoring the armouring when jointing Selecting ARM for unknown applications
armoured cables. requires the length of joint "L" and diameter
over joint "Ø" as below:

Ø (mm)
Design: 140

100

The kit consists of plastic mesh, spiral, fun-


nel with holder, transparent tape and cast 60
resin. The mesh and spiral are placed over 500 1000 L (mm)
the joint and sealed with the tape. The cast
resin, which contains base and hardener in ARM kit size
a partitioned bag, is mixed and poured into
the funnel until the mesh is full. Ø
The maximum storage temperature for
the casting resin is 30 °C. L

E.g. Ø 115 and L 850 mm give ARM 3.

Other dimensions on request.

SKKB
SKKB is a cross bonding kit for cables up to
170 kV. It can be mounted with advantage on
already laid cable, where the load condition
has changed and losses need to be reduced.
Also gives the opportunity to optimize the
cable system when cross-bonding can be
chosen at a free position along the cable.
Designation Cable Ø Use

ARM – Armouring kit for armoured cable


SKKB 5 PAL < 50 Al laminate as radially watertightness
SKKB 10 PAL 50-100 Al laminate as radially watertightness
SKKB 15 PAL 100-150 Al laminate as radially watertightness
SKKB 5 MET < 50 For metallic screen with or without Cu screen wires
SKKB 10 MET 50-100 For metallic screen with or without Cu screen wires
SKKB 15 MET 100-140 For metallic screen with or without Cu screen wires
SKKB 5 CUW < 50 Cu screen
SKKB 10 CUW 50-100 Cu screen
SKKB 15 CUW 100-150 Cu screen

104 We reserve the right to alter the design and range of our products. Kabeldon 2009 Edition 1
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Tools and oil All dimensions in mm

140 mm 360 mm 153 mm

RKM 670 RKM 672


Cable knife, 30 mm Sheath removing knife, with
blade. two handles, for XLPE cable. AV 6220
Sheath removing tool for PE-sheathed
cable Ø > 20 mm.
350 mm
450 mm

730R RKM 130


Torque wrench for screw connectors, screw Torque wrench for screw connectors, screw
cable lugs, overhead line clamps, etc. cable lugs, overhead line clamps, etc. Torque
Supplied with 7 mm socket head, extension wrench can be used with standard
arm and 8 mm internal hexagon head. 1/2" sockets.
Torque range 6-50 Nm. Torque range 25-130 Nm.

Cable accessories 52-420 kV


RKM-FV
Vessel heater. Fits
650-1200

RKM-PM and 60-litre


drum. IG 180X
Synthetic insulating oil.

RKM-PM
Oil filling equipment
(30 litres).

Designation Description Designation Description

RKM 670 Cable knife RKM 130 Torque wrench 25-130 Nm


RKM 672 Sheath removing knife RKM-PM Manual oil filling equipment
AV 6220 Sheath removing tool RKM-FV Vessel heater
730 R Torque wrench 6-50 Nm

Designation Description Contents Vessel


litre

IG 1801 Synthetic insulating oil 4 Tin


IG 1803 Synthetic insulating oil 2 Tin
IG 1804 Synthetic insulating oil 5 Tin
IG 1805 Synthetic insulating oil 60 Drum
IG 1807 Synthetic insulating oil 190 Drum

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 105
Kabeldon
Kabeldon
cable cable
accessories
accessories
52-420
Notes
1 kV

Tools All dimensions in mm

322 ~ 500

MB 1
Cable sheath breaker.
SV140, SV190, SV 215
Tools for installation of stress
cones as following:
- SV 140 for SKG
- SV 190 for SKGB
- SV 215 for SKGE

SH 50, SH 80, SH 130


Tool for removing and pealing
XLPE-insulation and for removing
outer conductive layer.

Designation Description Diameter across


XLPE-insulation
Ø mm

MB 1 Outer sheath breaker (pack of two)


SH 50 XLPE-shaver 15-50
SH 80 XLPE-shaver 40-80
SH 130 XLPE-shaver 70-130
IN-SH 50, 80 130 Spare blade for removing XLPE-insulation in SH 50, 80, 130
FK-SH 50, 80 130 Spare blade for pealing XLPE-insulation in SH 50, 80, 130
SV 140 Installation tool for stress cone, SKG
SV 190 Installation tool for stress cone, SKGB
SV 215 Installation tool for stress cone, SKGE

106 We reserve the right to alter the design and range of our products. Kabeldon 2009 Edition 1
Kabeldon general accessories

Universal clamps All dimensions in mm

UKR 90, UKRA 90

Ø 13
UKR 90
Use: For fixing cables, tubes, hoses, etc. It will fix
round profiles with Ø 20-90 mm or angular profiles 90
UKJ
with circumferences of 60-300 mm.
Earthing plate.

35
Design: The bracket is made of non-magnetic
hot-dip galvanized steel. The band is made of
UKR 90
stainless steel SS 2333-02 with rounded edges
Universal clamp.
and has a thickness of 0.2 mm. The band can be 78
tightened and locked in one operation. The locking UKS 90
bolt is made of die-cast zinc alloy. Spacer.

UKRS 90
UKRS 90
Consists of one UKR 90, a spacer with a wooden
Universal clamp
screw for fastening on a wooden pole e.g. with spacer.

Applications:

UKRA 90
Use: For fixing cables with Ø 20-90 mm to the Ø 13
anchor bars in a cable distribution cabinet, etc.

Design: The bracket is made of non-magnetic


hot-dip galvanized steel. The band is made of
stainless steel according to SS 2333-02 with
rounded edges and has a thickness of 0.2 mm. 35
The band can be tightened and locked in one
General accessories

operation. The locking bolt is made of die-cast


zinc alloy.
A spring-loaded nut with a reversible UKRA 90 Dimensional drawing of the
locking washer offers a choice of fixed or Universal clamp with anchor bar.
flexible position and direction. bracket for anchor bar.

Designation Weight
kg/item

UKR 90 0.17
UKRA 90 0.23
UKS 0.28
UKRS 90 0.45
UKJ 0.14

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 107
Kabeldon
Kabeldon
cable
general
accessories
accessories
Notes
1 kV

Universal clamps All dimensions in mm

UKR 200, UKRA 200

UKR 200
Use: For bundling cables with Ø 50-275 mm.

55
Design: The bracket is made of non-magnetic
hot-dip galvanized steel. The band is made of
stainless steel SS 2333-02 with rounded edges
and has a thickness of 0.2 mm.
The band can be tightened and locked in one
operation.The locking bolt is made of die-cast UKR 200
zinc alloy. Universal clamp.

UKRF
For fixing cables, etc., to cable ladders.
For use together with UKR 200. The height
of the ladder profile is approx.16 mm and
13 78
will fit within the specified dimensions.
The bracket is made of hot-dip 21
galvanized steel. UKRF UKRS 200
Fixing bracket. Universal clamp UKR 200 with
UKRS 200 spacer.
Consists of one UKR 200 and a spacer with
a wooden screw for fastening cables on a wall
or a wooden pole.

UKRA 200
Use: For fixing cables with Ø of 50-275 mm to the
anchor bars.

Design: The bracket is made of non-magnetic


hot-dip galvanized steel. The band is made of
stainless steel SS 2333-02 with rounded edges 55
and a thickness of 0.2 mm.
The locking bolt is made of die-cast zinc alloy
and can be tightened and locked in
one operation. UKRA 200
Universal clamp with Dimensional drawing of
A spring-loaded nut with a reversible
bracket for anchor bar. the anchor bar.
locking washer offers a choice of fixed or flexible
position and direction.

Designation Weight
kg/item

UKR 200 0.32


UKRA 200 0.45
UKRF 0.21
UKRS 200 0.81

108 We reserve the right to alter the design and range of our products. Kabeldon, 2009 Edition 1
Kabeldon general accessories

• Withstands high short-circuits

Typical applications All dimensions in mm

UKR 200,UKRA 200


when locating cables

Flat configuration
(Results of testing with 2 turns
of steel band).

UKR 200 with fixing


brackets UKRF.

Max Ø 275

UKR 200 with one fixing


L [m] bracket, UKRF.
max

îs = Short circuit current (peak value)


C-C = Distance between cable centres
L max = Distance between clamps

UKR 200 with fixing bracket, UKRF


UKRA 200
îs [kA]

Trefoil configuration L

General accessories

Max Ø 140
L [m] UKR 200 with two
max fixing brackets,
UKRF.

î = Short circuit current (peak value)


D = Outer diameter of cable
L max = Distance between clamps

UKR 200 with fixing bracket,


UKRF
îs [kA]

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 109
Kabeldon cable accessories
List of contents
Notes
1 kV

List of contents in alphabetical order

Designation Page No. Designation Page No.

A H
A-TBF 87 HBS 10 34
AF 89 HDC 250 49
AFT 90 HDC 630 51
ADAPTER 43 HU 150 60
AK 250 30, 50 HU 200 60
AK-ADAS 20 HUF 60
AK-ASA 62 HUS 60
APECB 84-420 82
APECB-P 84-300 82
APED 12-84 kV 79 I
APED-P 72 kV 79 IA 1003 70
APEGA 84-420 GIS 88 IA 1701 74
APEGA TRF 84-420 90 IA 1706 74
APSEA 52-72 85 IA 1710 74
ARM 57, 104 IA 2112 70
AV 6220 76, 105 IA 2113 70
IA 2333 72
IA 2337 72
IA 2338 72
C IA 2339 72
CST 84-420 90 IA 2342 72
CU 250 30 IA 2343 72
CW 59 IA 2352 72
IA 2362 72
IA 2421 72
D IA 2441 72
DMT1 91 IA 2443 72
IA 2444 72
IA 2502 70
F IA 2508 70
FBS-1722 1 76 IA 2518 70
FK 58 IA 2519 70
FKFB 58 IG 1201 71
FP 69 IG 1601 71
FPA 69 IG 1604 71
FPMP 69 IG 1717 71
IG 1718 71
G IG 1801-1807
IH SOC 250
105
30, 50
GAP-APECB 84
GAP-APED 81 IH SOC 400 32
GB-M20 76 IH SOC 630 34, 52
GC 70 IK 1002 71
GEX 62 K 1003 71

110 We reserve the right to alter the design and range of our products. Kabeldon, 2009 Edition 1
Kabeldon cable accessories
List of contents
1 kV

List of contents in alphabetical order

Designation Page No. Designation Page No.

I L
IK 1105, 1106, 1107, 1108, 1109 73 LBR 250 30
IK 1401 73 LPH 17
IK 1405 73 LXAC 18
IK 1407 73
IK 1502 73
IK 2221 73 M
IK 2230 74 MA 250 30, 50
IK 2233 73 MA 630 34, 52
IKP 70 MB 1 106
Installation cone 100, 102 MBR 250 74
Installation kit for JS/JX 95 Model 1700 Series 76
IP 250 30, 50
IP 400 32
IP 630 34, 52
O
OKJ 97
IS 17, 18
OKT 84, 91
OTIA 152 61

J
JP 250 30 P
JP-250-HDC 50 PC 630 34, 52
JP 400 32 PC 630 L 34, 52
JP 630 34 PC 630/250 34, 52
JP 630-HDC 52 PG 630 34
JPA 630-HDC 52 PIU-APEC 84
JPA V 52 PIU-APED 81
JS/JX 52-123 92 PPC 13
JS/JX 245 96 Pressure ring 89
JSA 1 103 PSSK 53
JSA 4-6 55 PXS 64
JSA 10-16 56 PXSA 64
JXT 1-3 55
R
K RE-APED 81
KA 250 50 RE-APEGA 91
KA 630 52 RKM 1055 75
K-TBF 30 SKR 87 RKM 1055 K 75
K-TBF 40 SKR 87 RKM 123 95
KAL 11 19 RKM 130 105
KAP 300 U 38 RKM 170 100
KAP 630 36 RKM 245 97
List of contents

K-ASA 62 RKM 362 102


K-ASB 62 RKM 402 70

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 111
Kabeldon cable accessories
List of contents
Notes
1 kV

List of contents in alphabetical order

Designation Page No. Designation Page No.

R S
RKM 670 75, 105 SOT 25
RKM 672 75, 105 SPT1 91
RKM 850 95 SPV1 91
RKM-FV 105 SSH 54
RKM-PM 105 STOP 43, 48
RKS 1607 054 75 SV 106
RULLE 72

S T
730 R 75, 105 TB-A 35
SAGA 11 Y 14 THS, THSA 87
SCK 2 103 TS 43
SH 106 TSH 54
SH-SKRM 59
SKALUS 74
SKKB 104
U
UKJ 107
SKSA 59
UKR 90 107
SKSB 59
UKR 200 108
SMARTA 13
UKRA 90 107
SMILA 16
UKRA 200 108
SMKC 15
UKRF 108
SMPGB 145-170 98
UKS 107
SMPGB 362-420 101
UKRS 90 107
SMPGB BOX 145-170 98
UKRS 200 108
SMPGB-C 145-170 98
SMTA 67
SMTD 63 W
SMTPA 67 WIM 1 48
SMTXB 65 WIM 2 48
SMTXD 66 WIM 3 44, 48
SMULA 16 WIM 4 44, 48
SMXB 46 WIM 5 44
SOC 250 29 WIM 6 44
SOC 400 31
SOC 630 33
SOJ 40
SOJ CSWS 40
SOJ R 42
SOJ RWI 40
SOJ RWIT 40

112 We reserve the right to alter the design and range of our products. Kabeldon, 2009 Edition 1
Kabeldon cable accessories
List of contents
1 kV

List of contents by category :


Cable terminations and
Cable connectors

See page
Outdoor, LPH 17
1 kV
Outdoor, LXAC 18

10-36 kV
XLPE- Premoulded indoor/outdoor, SOT 10-36 kV 25
insulated
cable
Terminations

12-36 kV
paper- Indoor, OTIA 12 kV 61
insulated
cable

Porcelain insulator, APED 36-84 kV 79


Composite insulator, APED-P 72 kV 79
52-420 kV Porcelain insulator, APECB 84-420 kV 82
XLPE- Composite insulator, APECB-P 84-300 kV 82
insulated
cable Flexible, made of rubber, APSEA 52-72 kV 85
GIS, APEGA 84-420 kV 88
TRF, APEGA 84-420 kV 90

Enclosed connection protection, KAL 19


1 kV
Connectors

Prefabricated cable connection for extension of


Al cable, AK-ADAS 20

12-24 kV Premoulded screened separable, 250-630 A, SOC 29


terminations

Shrouded termination, 12 kV indoor, TB-A 35


Shrouded

12-24 kV
Shrouded termination, 12-24 kV indoor, KAP 38
List of contents

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 113
Kabeldon cable accessories
List of contents
Notes
1 kV

List of contents by category:


Cable joints
See page
Cast resin for plastic-, paper-insulated and
signal cable, SMARTA 13
Branch joint for plastic-insulated cable,
SAGA Y 14

1 kV Heat shrink for plastic-insulated cable, SMKC 15


Tape for plastic-insulated cable with screen,
SMILA 16
Tape for plastic-insulated cable without screen,
SMULA 16

12-36 kV Premoulded, SOJ 12-24 40


XLPE-insulated
Tape, SMXB 12-36 46
cable
Cable Joints

Joint, SMTD 12 kV 63
Repair joint, SMTD-RK 12 kV 63
Transition joint, SMTXB 12 kV 65
12-36 kV
Paper-insulated Transition joint, SMTXD 24-36 kV 66
cable Joint, SMTA 24-36 kV 67
Joint, separated lead-sheathed cable,
SMTPA 52 kV 67

Premoulded, JS 52-123 kV 92
Premoulded, JS 245 kV 96
52-362 kV
XLPE-insulated Premoulded, screen interruption JX 52-123 kV 92
cable Premoulded, screen interruption JX 245 kV 96
Premoulded, SMPGB, SMPGB-C and
SMPGB BOX 145-170 kV 98
Premoulded SMPGB 362 kV 101

12-36 kV Kabeldon cable cabinet 250 A, HDC 250 49


Cable distribution
cabinet Kabeldon cable cabinet 630 A, HDC 630 51

114 We reserve the right to alter the design and range of our products. Kabeldon, 2009 Edition 1
Kabeldon cable accessories
List of contents
1 kV

List of contents by category:


Accessories for cable accessories

See page
Screen separation kit, PSSK, PSSK-E 53
Branch seal for 3-core cable terminations 54
Earthing kit for terminations, JSA 4-6
Accessories for and JXT 1-3 55
XLPE-insulated Screen connection for joints, JSA 10-16 56
Cable accessories
Armouring kit, ARM 57
12-36 kV
Overhead line clamp, FK 120 och FK 300 58
Screw cable lug, SKSA, SKSB 59
Screw connector, SH-SKRM 59

Accessories for
Spring-loaded gaskets, FPA, FP och FPMP 69
paper-insulated
cable accessories General accessories 70
12-36 kV
Accessories

Bird protection 60
General Tapes 72
accessories Other accessories 73
12-36 kV
Tools 75

Accessories for Earthing kits for cable terminations 103


cable accessories
Armouring kit, ARM 104
52-362 kV
Tools and oil 105

UKR 90 107
UKRA 90 107
Universal clamps
UKR 200 108
UKRA 200 108
List of contents

Kabeldon 2009, edition 1 We reserve the right to alter the design and range of our products. 115
Kabeldon cable accessoriesNotes
1 kV
Introduction
Kabeldon cable accessories 52-420
Notes
kV
Kabeldon cable accessoriesNotes
1 kV
® Copyright 2009 ABB. All rights reserved.

ABB AB
Kabeldon
Box 531
SE-441 15 Alingsås, Sweden
Tel: +46 322 770 00
Fax: +46 322 770 01
www.abb.se/kabeldon

You might also like