Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Installation Manual: Air Conditioner (Multi Type)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 32

+00EH99883601_00Ta.

book

Page 1

Thursday, September 8, 2011

4:34 PM

AIR CONDITIONER (MULTI TYPE)

Installation Manual
Outdoor Unit
Model name:
<Heat Pump Model>

For commercial use


Para uso comercial
Para utilizao comercial

MCY-MAP0604HT8
MCY-MAP0804HT8
MCY-MAP0604HT7
MCY-MAP0804HT7

Installation Manual

1 English

Manual de instalacin

31 Espaol

Manual de instalao

61 Portugus

91

+00EH99883601_00Ta.book

Page 1

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Original instruction

ADOPTION OF NEW REFRIGERANT


This Air Conditioner uses R410A an environmentally friendly refrigerant.

Outdoor Unit

Installation Manual

Precautions for safety


WARNING

General

Contents
1 Precautions for safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2 Accessory parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 Installation of new refrigerant air conditioner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4 Installation conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
5 Refrigerant piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6 Electric wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7 Address setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
8 Test run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
9 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Before starting to install the air conditioner, read through the Installation Manual carefully, and follow its instructions to install
the air conditioner. Otherwise, falling down of the unit may occur, or the unit may cause noise, vibration or water leakage.
Only a qualified installer(*1) or qualified service person(*1) is allowed to do installation work. If installation is carried out by
an unqualified individual, a fire, electric shocks, injury, water leakage, noise and / or vibration may result.
If using separately sold products, make sure to use Toshiba specified products only. Using unspecified products may cause
fire, electric shock, water leak or other failure.
Before opening the service panel of the outdoor unit, set the circuit breaker to the OFF position. Failure to set the circuit
breaker to the OFF position may result in electric shocks through contact with the interior parts. Only a qualified installer(*1)
or qualified service person(*1) is allowed to remove the service panel of the outdoor unit and do the work required.
Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breakers for both the
indoor and outdoor units to the OFF position. Otherwise, electric shock may result.
Place a Work in progress sign near the circuit breaker while the installation, maintenance, repair or removal work is being
carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
Only a qualified installer(*1) or qualified service person(*1) is allowed to undertake work at heights using a stand of 50 cm
or more or to remove the intake grille of the indoor unit to undertake work.
Wear protective gloves and safety work clothing during installation, servicing and removal.
Do not touch the aluminium fin of the outdoor unit. You may injure yourself if you do so. If the fin must be touched for some
reason, first put on protective gloves and safety work clothing, and then proceed.
Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor unit and
result in injury.
When working at height, put a sign in place so that no-one will approach the work location before proceeding with the work.
Parts or other objects may fall from above, possibly injuring a person below. Also, be sure that workers put on helmets.
When cleaning the filter or other parts of the outdoor unit, set the circuit breaker to OFF without fail, and place a Work in
progress sign near the circuit breaker before proceeding with the work.
When working at heights, put a sign in place so that no-one will approach the work location, before proceeding with the
work. Parts and other objects may fall from above, possibly injuring a person below.
The refrigerant used by this air conditioner is the R410A.
You shall ensure that the air conditioner is transported in stable condition. If you find any part of the product broken, contact
your dealer.
Do not disassemble, modify, repair or move the product yourself. Doing so may cause fire, electric shock, injury or water
leaks. Ask a qualified installer or qualified service person to do any repairs or to move the product.

Selection of installation location


If you install the unit in a small room, take appropriate measures to prevent the refrigerant from exceeding the limit
concentration even if it leaks. Consult the dealer from whom you purchased the air conditioner when you implement the
measures. Accumulation of highly concentrated refrigerant may cause an oxygen deficiency accident.
Do not install in a location where flammable gas may leaks are possible. If the gas should leak and accumulate around the
unit, it may ignite and cause a fire.
When transporting the air conditioner, wear shoes with protective toe caps, protective gloves and other protective clothing.
When transporting the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if
the bands should break.
Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure themselves or receive electric
shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running.
Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may
cause imperfect combustion.

Places where the operation sound of the outdoor unit may cause a disturbance. (Especially at the boundary line with
a neighbour, install the air conditioner while considering the noise.)

Installation
Follow the instructions in the Installation Manual to install the air conditioner. Failure to follow these instructions may cause
the product to fall down or topple over or give rise to noise, vibration, water leakage or other failure.
The designated bolts (M10) and nuts (M10) for securing the outdoor unit must be used when installing the unit.
Install the outdoor unit property in a location that is durable enough to support the weight of the outdoor unit. Insufficient
durability may cause the outdoor unit to fall, which may result in injury.
Install the unit in the prescribed manner for protection against strong wind and earthquake. Incorrect installation may result
in the unit falling down, or other accidents.
Be sure to fix the screws back which have been removed for installation or other purposes.

1-EN

2-EN

+00EH99883601_00Ta.book

Page 2

Thursday, September 8, 2011

Outdoor Unit

4:34 PM

Installation Manual

Outdoor Unit

Installation Manual

Refrigerant piping

Relocation

Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor is
operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is over
pressurized, which may cause a injury.
Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a crack in
the flare nut after a long period, which may result in refrigerant leakage.
Ventilate the air if the refrigerant gas leaks during installation. If the leaked refrigerant gas comes into contact with fire, toxic
gas may be produced.
After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and flows near a
fire source, such as a cooking range, noxious gas may be generated.
When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge the air
completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge the air
completely may cause the air conditioner to malfunction.
Nitrogen gas must be used for the airtight test.
The charge hose must be connected in such a way that it is not slack.
If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes
in contact with fire, noxious gas may be generated.

Only a qualified installer(*1) or qualified service person(*1) is allowed to relocate the air conditioner. It is dangerous for the
air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and / or
vibration may result.
When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting
the refrigerant pipe with the service valve left open and the compressor still operating will cause air or other gas to be sucked
in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in rupture, injury or
other trouble.
Never recover the refrigerant into the outdoor unit. Be sure to use a refrigerant recovery machine to recover the refrigerant
when moving or repairing. It is impossible to recover the refrigerant into the outdoor unit. Refrigerant recovery into the
outdoor unit may result in serious accidents such as explosion of the unit, injury or other accidents.
(*1) Refer to the Definition of Qualified Installer or Qualified Service Person.

CAUTION
New refrigerant air conditioner installation

Electrical wiring

This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer.
The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is approx.
1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed.
Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the
refrigerating cycle.
To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the
main unit and installation tools are changed from those for the conventional refrigerant.
Accordingly the exclusive tools are required for the new refrigerant (R410A).
For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter.

Only a qualified installer(*1) or qualified service person(*1) is allowed to carry out the electrical work of the air conditioner.
Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may
result in electric shocks and / or electrical leaks.
When connecting the electrical wires, repairing the electrical parts or undertaking other electrical jobs, wear gloves to
provide protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks.
Failure to wear this protective gear may result in electric shocks.
When executing address setting, test run, or troubleshooting through the checking window on the electrical control box, put
on insulated heat-proof gloves, insulated shoes and other clothing to provide protection from electric shock. Otherwise you
may receive an electric shock.
Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and laws. Use
of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage, smoking and / or a fire.
Check that the product is properly earthed. (grounding work)
Incomplete earthing may cause electric shock.
Do not connect the earth line to a gas pipe, water pipe, lightning conductor, or a telephone earth line.
After completing the repair or relocation work, check that the ground wires are connected properly.
Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations
and laws.
Install the circuit breaker where it can be easily accessed by the agent.
When installing the circuit breaker outdoors, install one which is designed to be used outdoors.
Under no circumstances must the power cable be extended. Connection trouble in the places where the cable is extended
may give rise to smoking and / or a fire.
Electrical wiring work shall be conducted according to law and regulation in the community and installation manual.
Failure to do so may result in electrocution or short circuit.
Do not supply power from the power terminal block equipped on the outdoor unit to another outdoor unit. Capacity overflow
may occur on the terminal block and may result in fire.
When carrying out electric connection, use the wire specified in the Installation Manual and connect and fix the wires
securely to prevent them applying external force to the terminals. Improper connection or fixing may result in fire.

To disconnect the appliance from main power supply.


This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm.

The installation fuse (all type can be used) must be used for the power supply line of this conditioner.

Test run
Before operating the air conditioner after having completed the work, check that the electrical control box cover of the indoor
unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may receive an
electric shock if the power is turned on without first conducting these checks.
When you have noticed that some kind of trouble (such as when an error display has appeared, there is a smell of burning,
abnormal sounds are heard, the air conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner,
do not touch the air conditioner yourself but set the circuit breaker to the OFF position, and contact a qualified service
person. Take steps to ensure that the power will not be turned on (by marking out of service near the circuit breaker, for
instance) until qualified service person arrives. Continuing to use the air conditioner in the trouble status may cause
mechanical problems to escalate or result in electric shocks or other failure.
After the work has finished, be sure to use an insulation tester set (500 V Megger) to check the resistance is 2 M or more
between the charge section and the non-charge metal section (Earth section). If the resistance value is low, a disaster such
as a leak or electric shock is caused at users side.
Upon completion of the installation work, check for refrigerant leaks and check the insulation resistance and water drainage.
Then conduct a test run to check that the air conditioner is operating properly.

EN

Explanations given to user


Upon completion of the installation work, tell the user where the circuit breaker is located. If the user does not know where
the circuit breaker is, he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner.
If you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF
position, and contact a qualified service person(*1) to have the repairs done. Do not set the circuit breaker to the ON position
until the repairs are completed.
After the installation work, follow the Owners Manual to explain to the customer how to use and maintain the unit.

3-EN

4-EN

+00EH99883601_00Ta.book

Page 3

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Shape

Usage

Installation of new refrigerant air


conditioner

This air conditioner adopts the new HFC refrigerant (R410A) which does not deplete the ozone layer.
R410A refrigerant is vulnerable to impurities such as water, oxidizing membranes, or oils because the pressure
of R410A refrigerant is higher than that of the former refrigerant by approximately 1.6 times.
As well as the adoption of the new refrigerant, the refrigerating oil has been also changed. Therefore, pay
attention so that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle of the
new refrigerant air conditioner during installation.
To prevent mixing of refrigerant or refrigerating oil, the size of the charge port of the main unit or connecting
section of the installation tool differs to that of an air conditioner for the former refrigerant.
Accordingly, exclusive tools are required for the new refrigerant (R410A) as shown below.
For connecting pipes, use new and clean piping materials so that water or dust does not enter.

Owners Manual

Hand this directly to the customer.

Installation Manual

Hand this directly to the customer.

Drain nipple

Waterproof rubber cap

Protective bush

For protecting wires (pipe cover)

It is necessary to prepare the tools and parts for installation as described below. The tools and parts which will be
newly prepared in the following items should be restricted to exclusive use.

Guard material for passage


part

For protecting passage part (pipe cover)

Explanation of symbols
: Newly prepared (It is necessary to use it exclusively with R410A, separately from those for R22 or R407C.)
: Former tool is available.

Joint pipe (19.1 - 22.2)

For the pipe inside the outdoor unit (MCY-MAP0804HT8 / HT7


only)

Joint socket (15.9 - 22.2)

5-EN

Qty

Installation Manual

Outdoor Unit

Accessory parts
Part name

Required tools and cautions on handling

For the pipe inside the outdoor unit (MCY-MAP0804HT8 / HT7


only)

Used tools
Gauge manifold

Usage

Charging hose

Vacuuming, charging refrigerant


and operation check

Charging cylinder

Charging refrigerant

Gas leak detector

Checking gas leak

Vacuum pump

Vacuum drying

Proper use of tools / parts


Exclusive to R410A
Exclusive to R410A
Unusable (Use the Refrigerant charging balance.)
Exclusive to R410A
Usable if a counter-flow preventive adapter is
attached

NOTE

Vacuum pump with counterflow

Vacuum drying

R22 (Existing article)

Before installing the unit, check that the unit has the correct model name to prevent the wrong unit from being installed
in the wrong place.
Before proceeding to weld the refrigerant pipe, be sure to pass nitrogen through the pipe.
Before installing the indoor units, read the instructions in the installation manual provided with the indoor units.
Before installing a branch pipe, read the instructions in the installation manual provided with the branch pipe kit.

Flare tool

Flare processing of pipes

Usable by adjusting size

Bender

Bending processing of pipes

R22 (Existing article)

Refrigerant recovery device

Recovering refrigerant

Exclusive to R410A

Torque wrench

Tightening flare nut

Exclusive to 12.7 mm and 15.9 mm

Pipe cutter

Cutting pipes

R22 (Existing article)

Refrigerant canister

Charging refrigerant

Exclusive to R410A
Enter the refrigerate name for identification

Welding machine / Nitrogen gas


cylinder

Welding of pipes

R22 (Existing article)

Refrigerant charging balance

Charging refrigerant

R22 (Existing article)

6-EN

+00EH99883601_00Ta.book

Page 4

Thursday, September 8, 2011

4:34 PM

Outdoor Unit

Installation Manual

Outdoor Unit

Installation conditions

Installation Manual

Installation location
WARNING

Before installation

Install the outdoor unit properly in a location that is durable enough to support the weight of the outdoor unit.
Insufficient durability may cause the outdoor unit to fall, which may result in injury.
This outdoor unit has a weight of about 125 kg. Pay special attention when installing the unit onto a wall surface.

Be sure to prepare to the following items before installation.

Airtight test

1
2
3

CAUTION

Before starting an airtight test, further tighten the spindle valves on the gas and liquid sides.

Do not install the outdoor unit in a location that is subject to combustible gas leaks.
Accumulation of combustible gas around the outdoor unit may cause a fire.

Pressurize the pipe with nitrogen gas charged from the service port to the design pressure to
conduct an airtight test.
After the airtight test is completed, evacuate the nitrogen gas.

Install the outdoor unit in a location that meets the following conditions after the customers consent is
obtained.
A well-ventilated location free from obstacles near the air intake and air discharge
A location that is not exposed to rain or direct sunlight
A location that does not increase the operating noise or vibration of the outdoor unit
A location that does not produce any drainage problems from discharged water

Air purge
To purge air, use a vacuum pump.
Do not use refrigerant charged in the outdoor unit to purge air. (The air purge refrigerant is not contained in the
outdoor unit.)

Do not install the outdoor unit in the following locations.


A location with a saline atmosphere (coastal area) or one that is full of sulfide gas (hot-spring area) (Special
maintenance is required.)
A location subject to oil, vapor, oily smoke, or corrosive gases
A location in which organic solvent is used
A location where high-frequency equipment (including inverter equipment, private power generator, medical
equipment, and communication equipment) is used
(Installation in such a location may cause malfunction of the air conditioner, abnormal control or problems due
to noise from such equipment.)
A location in which the discharged air of the outdoor unit blows against the window of a neighboring house
A location where the operating noise of the outdoor unit is transmitted
When the outdoor unit is installed in an elevated position, be sure to secure its fixing leg.
A location in which drain water poses any problems.

Electrical wiring
Be sure to fix the power wires, system interconnecting wires and remote controller wires with clamps so that they
do not come into contact with the cabinet, etc.

Earthing
WARNING
Make sure that proper earthing is provided.
Improper earthing may cause an electric shock. For details on how to check earthing, contact the dealer who installed
the air conditioner or a professional installation company.

Proper earthing can prevent charging of electricity on the outdoor unit surface due to the presence of a high
frequency in the frequency converter (inverter) of the outdoor unit, as well as prevent electric shock. If the
outdoor unit is not properly earthed, you may be exposed to an electric shock.
Be sure to connect the earth wire (grounding work).
Incomplete earthing can cause an electric shock.
Do not connect earth wires to gas pipes, water pipes, lightning rods or earth wires for telephone wires.

EN

Test run
Turn on the leakage breaker at least 12 hours before starting a test run to protect the compressor.

CAUTION
Incorrect installation work may result in a malfunction or complaints from customers.

7-EN

8-EN

Page 5

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Installation Manual

Outdoor Unit

Necessary space for installation

CAUTION
1. Install the outdoor unit in a location where the discharge air is not blocked.
2. When an outdoor unit is installed in a location that is always exposed to strong winds like a coast or on the high
stories of a building, secure normal fan operation by using a duct or wind shield.
3. When installing the outdoor unit in a location that is constantly exposed to strong winds such as on the upper
stairs or rooftop of a building, apply the wind-proofing measures referred to in the following examples.
1) Install the unit so that its discharge port faces the wall of the building.
Keep a distance 500 mm or more between the unit and wall surface.

(Unit: mm)

Obstacle at rear side


Upper side is free
1. Single unit installation

2. Obstacles on both right and left sides

150 or more

500 mm

200 or more

+00EH99883601_00Ta.book

150 or more

The height of the obstacle


should be lower than the
height of the outdoor unit.

250 or more

2) Consider the wind direction during the operational season of the air conditioner, and install the unit so that
the discharge port is set at a right angle relative to the wind direction.

200 or more

3. Serial installation of two or more units

150 or
more

250 or
more

250 or
more

250 or
more

The height of the obstacle should be lower than


the height of the outdoor unit.

Obstacle also above unit


500 or more

Strong wind
Strong wind

When installing the unit in an area where snowfalls may be heavy, take steps to prevent the unit from being
adversely affected by the fallen or accumulated snow.
Either make the foundation higher or install a stand (which is high enough to ensure that the unit will be
above the fallen or accumulated snow) and place the unit on it.
Attach a snow shield (locally procured).

150 or
more

Obstacle in front
Above unit is free
1. Single unit installation

2. Serial installation of two or more units

500 or more

Snow shield

Snow shield

1,000 or
more

<Example>

1,000 or more

9-EN

800 or more

Obstacle also at the above unit

10-EN

+00EH99883601_00Ta.book

Page 6

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Installation of outdoor unit

Obstacles in both front and rear of unit


Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the unit, should be lower than the height of the outdoor unit.

Standard installation
1. Single unit installation

Installation Manual

Outdoor Unit

Before installation, check the strength and horizontalness of the base so that abnormal sounds do not emanate.
According to the following base diagram, fix the base firmly with the anchor bolts.
(Anchor bolt, nut: M10 x 4 pairs)

2. Serial installation of two or more units

250 or more

400

365

250 or
more

150

600
Drain hole

1,000
or more

1,000
or more

200 or
more

150 or
more

150

430
40

Knockout
hole

Drain nipple mounting


hole

Serial installation in front and rear


Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the unit should be lower than the height of the outdoor unit.

As shown in the figure below, install vibration-proof rubber pads to directly support the bottom surface of the
fixing leg.
* When installing the foundation for an outdoor unit with downward piping, consider the piping work.

Standard installation

GOOD

GOOD
Absorb vibration with
vibration-proof rubber
pads

Fixing leg
1,000 or
more

300 or
more

1,500 or
more

2,000 or
more

200 or
more

Bottom plate of
outdoor unit

Foundation

Foundation

Support the bottom surface of the


fixing leg that is in contact with and
underneath the bottom plate of the
outdoor unit.

NO GOOD
If only the end of the
fixing leg is supported,
it may deform.

Do not support the outdoor


unit only with the fixing leg.

Foundation

Set the out margin of the anchor bolt to 15 mm or less.

15 or less

11-EN

EN

12-EN

+00EH99883601_00Ta.book

Page 7

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

When water is to be drained through the drain hose, attach the following drain nipple and waterproof rubber cap,
and use the drain hose (Inner diam: 16 mm) sold on the market. Also seal the knockout hole and screws securely
with silicone material, etc., to prevent water from leaking.
Some conditions may cause dewing or dripping of water.
When collectively draining discharged water completely, use a drain pan.

Installation Manual

Outdoor Unit

Refrigerant piping

Knockout of pipe cover


Knockout procedure

Waterproof rubber cap


Drain nipple

Please pay attention to the drain in region with snowfall and cold temperature, as it may be frozen and cause
drainage problems. Punch the knockout holes on the bottom plate to improve drainability. Use a screwdriver and
take off the knockout part outward.

Rear
Pipe cover
Side

Knockout hole
Waterproof rubber cap
Drain nipple

For reference
If a heating operation is to be continuously performed for a long time under the condition that the outdoor
temperature is 0 C or lower, draining defrosted water may be difficult due to the bottom plate freezing, resulting in
trouble with the cabinet or fan.
It is recommended to procure an anti-freeze heater locally in order to safely install the air conditioner.
For details, contact the dealer.

Front
Bottom

The indoor / outdoor connecting pipes can be connected in 4 directions.


Take off the knockout of the pipe cover or bottom plate where the pipes or wires will pass through.
Without detaching the pipe cover, tap on the knockout section a few times with the shank of a screwdriver. A
knockout hole can easily be punched.
As shown in the figure below, it is easier to punch out the knockout hole when the pipe cover is left in place rather
than when the cover is removed from the unit.
In knocking out the hole, the knockout section can easily be removed by hand once the bottom of the three
locations where the section is joined along the guide lines is broken using a screwdriver.
After punching out the knockout hole, remove burrs from the hole, and install the protective bush and guard
material around the passage hole provided as accessories in order to protect the wires and pipes. Also be sure
to attach the pipe covers after connecting the pipes. The pipe covers can be easily attached by cutting off the
slits at the lower part of the covers.

* Be sure to wear heavy work gloves while working.

13-EN

14-EN

+00EH99883601_00Ta.book

Page 8

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Optional installation parts (locally procured)


Parts name

Connecting the pipe at the gas side (MCY-MAP0804HT8 / HT7


only)

Qty

Refrigerant piping
Liquid side: 9.5 mm
Gas side: 19.1 mm and 22.2 mm

Pipe insulating material


(polyethylene foam, 10 mm thick)

Putty, PVC tape

Installation Manual

Outdoor Unit

REQUIREMENT

One each

Connecting the main pipe (19.1) directly to the gas valve (19.1) may lower the performance.
To connect the main pipe (22.2) to the gas valve (19.1), use the joint pipe (19.1 - 22.2) and joint socket (15.9
- 22.2) that come with the outdoor unit.
Before welding the refrigerant pipe, be sure to pass nitrogen through the pipe to prevent oxidation inside the pipes.
Failure to observe this precaution may cause the refrigerant pipe to become clogged due to oxidation scale.

1
One each

REQUIREMENT
Follow the instructions in the installation manual provided with the branch pipe kit and the instructions in the installation
manual of the indoor unit to connect the refrigerant pipe between the branch pipe and indoor unit.

Gas side ball valve 19.1

Flare connection

Refrigerant piping connection


CAUTION
Take note of these 4 important points below for piping work
1. Keep dust and moisture away from inside the connecting pipes.
2. Tightly connect the connection between pipes and the unit.
3. Evacuate the air in the connecting pipes using a VACUUM PUMP.
4. Check for gas leaks at connection points.

Joint socket (straight, supplied)


Branch pipe

Joint pipe (L-shape, supplied)


Solder

22.2 pipe (locally procured)

Flaring
1. Cut the pipe with a pipe cutter.

Connection procedure
Roughness

Obliquity

90

Warp

To connect at the front, sides, or back

1
2

2. Remove the burr inside of the pipe.


When removing the burr, be careful so that chips do not fall into the pipe.
3. Remove the flare nuts attached to the outdoor / indoor unit, then insert them into each of the pipes.
4. Flare the pipes.
See the following table for the projection margin (A) and flaring size (B).
A

3
4

Braze the supplied joint pipe to the main pipe (22.2).


Remove the nut from the valve at the gas side, insert the nut into the supplied joint pipe, then flare
the tip of the pipe.
Tighten the supplied joint pipe to the valve at the gas side using a nut by the specified torque in
the same direction as removing the outdoor unit pipe.
Connect and braze the supplied joint socket between the main pipe (22.2) and branch pipe
(15.9).

To connect downward
Pipe

Outside
diameter

Thickness

mm
9.5
19.1

mm
0.8
1.2

Rigid
(clutch type)
R410A tool
mm
0 to 0.5
0 to 0.5

B
Imperial
(wing nut type)
R410A tool
mm
1.0 to 1.5
1.0 to 1.5

Width across
flat
mm
13.2
24.0

1
2

Flare Nut

mm
22
36

Tighten torque
Nm
33 to 42
100 to 120

kgfm
3.3 to 4.2
10.0 to 12.0

3
4

* In case of flaring for R410A with the conventional flare tool, pull the tool out approx. 0.5 mm more than that for
R22 to adjust it to the specified flare size.
The copper pipe gauge is useful for adjusting the projection margin size.

15-EN

Cut the supplied joint pipe, then braze the main pipe (22.2).

EN

Remove the nut from the valve at the gas side, insert the nut into the supplied joint pipe, then flare
the tip of the pipe.
Tighten the supplied joint pipe to the valve at the gas side using a nut by the specified torque.
Connect and braze the supplied joint socket between the main pipe (22.2) and branch pipe
(15.9).

16-EN

+00EH99883601_00Ta.book

Page 9

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Tightening of connecting part

Installation Manual

Outdoor Unit

Coupling size of brazed pipe

1. Align the centers of the connecting pipes and fully tighten the flare nut with your fingers. Then fix the nut with a
wrench as shown in the figure and tighten it with a torque wrench.
Half union or packed valve

Connected section
External size

Internal size

Flare nut

G
F

Internally
threaded side

Externally
threaded side
Fix with wrench.

(Unit: mm)

Tighten with torque


wrench.

2. As shown in the figure, be sure to use two wrenches to loosen or tighten the flare nut of the valve on the gas
side. If you use a single wrench, the flare nut cannot be tightened to the required tightening torque.
On the other hand, use a single wrench to loosen or tighten the flare nut of the valve on the liquid side.
Cover

Cap

Piping valve

Loosened

Tightened

Connected section
Standard outer dia.
of connected
copper pipe

External size

Internal size

6.35

6.35 (0.03)

6.45 ( +0.04
-0.02 )

9.52

9.52 (0.03)

9.62 ( +0.04
-0.02 )

12.70

12.70 (0.03)

12.81 ( +0.04
-0.02 )

15.88

15.88 (0.03)

19.05
22.22

Min. depth of
insertion

Oval value

Min. thickness
of coupling

0.06 or less

0.50

0.08 or less

0.60

0.10 or less

0.70

16.00 ( +0.04
-0.02 )

0.13 or less

0.80

19.05 (0.03)

19.19 ( +0.03
-0.03 )

11

10

0.15 or less

0.80

22.22 (0.03)

22.36 ( +0.03
-0.03 )

11

10

0.16 or less

0.82

Standard outer dia.


(Allowable difference)

Flare nut

Valve at gas side

CAUTION
1.Do not put the wrench on the cap or cover.
The valve may break.
2.If applying excessive torque, the nut may break according to some installation conditions.
Cover

NO GOOD
Cap

After the installation work, be sure to check for gas leaks of the pipe connections with nitrogen.
Pressure of R410A is higher than that of R22 (Approx. 1.6 times).
Therefore, using a torque wrench, tighten the flare pipe connecting sections that connect the indoor / outdoor
units at the specified tightening torque.
Incomplete connections may cause not only a gas leak, but also trouble with the refrigeration cycle.
Do not apply refrigerant oil to the flared surface.

17-EN

18-EN

+00EH99883601_00Ta.book

Page 10

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Installation Manual

Outdoor Unit

Selection of pipe materials and size

Selection of refrigerant piping

Selection of pipe material


Material: Phosphorus deoxidation seam-less pipe

Outdoor unit

Capacity code of indoor and outdoor units


For the indoor unit, the capacity code is decided at each capacity rank.
The capacity codes of the outdoor units are decided at each capacity rank.
The maximum No. of connectable indoor unit and the total value of capacity codes of the indoor units are also
decided.

Liquid pipe

Gas pipe
Main pipe

Branching
header

Branching
pipe

1st branching
section
(4)

(5)

(2)

(1)

Minimum wall thickness for R410A application


Soft

Harf Hard or Hard

OD (Inch)

OD (mm)

Minimum wall thickness (mm)

OK

OK

1/4

6.35

0.80

OK

OK

3/8

9.52

0.80

OK

OK

1/2

12.70

0.80

OK

OK

5/8

15.88

1.00

NG *

OK

3/4

19.05

1.00

NG *

OK

7/8

22.2

1.00

* If the pipe size is


19.0 or more, use a
suitable material.

Branching
pipe

Table1

(2)

Equivalent to HP

Equivalent to
capacity

Indoor
unit

Y-shaped
branching joint
(4)

(4)

(2)

007 type

0.8

2.2

009 type

2.8

012 type

1.25

3.6

015 type

1.7

4.5

018 type

5.6

024 type

2.5

7.1

027 type

030 type

3.2

036 type

11.2

048 type

14

056 type

16

(3)
(3)

No.

(1)

Equivalent to HP

No. of connectable
indoor units

Name

Selection of pipe size

Remarks

Outdoor unit

1st branching
section

Main pipe

Out door unit capacity type

Gas pipe

Liquid pipe

0604 type

OD 19.1

OD 9.5

0804 type

OD 22.2*

OD 9.5

Same as connecting
pipe size of the
outdoor unit.

* OD 19.1 can be used, but may lower the performance.


Pipe size between branching sections

Total capacity codes of indoor


units at downstream side

(2)
Capacity code

Piping parts

Indoor
unit

(3)

Connecting pipe size of outdoor unit

Table2
Total capacity code of connectable indoor
units
Min. (HP)

Max. (HP)

0604 type

2 to 8

4.8

7.8

0804 type

2 to 8

6.4

10.4

Branching section

Branching pipe
Branching section

Gas
pipe

Liquid
pipe

Below 6.6

12.7

9.5

2.4 to below 6.4

6.6 to below 18.0

15.9

9.5

6.4 or more

18.0 or more

19.1

9.5

Equivalent to HP

Equivalent to
capacity

Below 2.4

Pipe size differs based


on the total capacity
code value of indoor
units at the
downstream side. If
the total value
exceeds the capacity
code of the outdoor
unit, apply the
capacity code of the
outdoor unit. (See
Table 1 and 2.)

EN

Connecting pipe size of indoor unit

(3)

19-EN

(3)

(3)

Capacity code

Indoor unit capacity


type

Outdoor unit capacity


type

(3)

(3)

10

Branching section
Indoor unit

connecting pipe
Indoor unit

Capacity rank

Gas pipe

Liquid
pipe

007 to 012 type

9.5

6.4

015 to 018 type

12.7

6.4

024 to 056 type

15.9

9.5

20-EN

+00EH99883601_00Ta.book

Page 11

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

No.

Piping parts

Name

Selection of pipe size

11

Installation Manual

Outdoor Unit

Selection of refrigerant piping for quiet place (with PMV Kit)

Selection of branching section (Y-shaped branching joint)

(4)

Branching section

Y-shaped
branching joint

Model name
Y-shape branching joint

RBM-BY55E

Outdoor unit

Selection of branching section (Branching header)

Model name

(5)

Branching section Branching header

Branching header*1

For 4 branches

RBM-HY1043E

For 8 branches

RBM-HY1083E

Gas pipe

*1: Up to a total of 6.0 maximum equivalent to HP capacity codes is connectable to one line
after branching of header.

Liquid pipe

Main pipe
(1)

1st branching
section
(4)

Branching
header

Branching
pipe

(5)

(2)

PMV Kit

(6)

(6)

(6)

(3)

(3)
Y-shaped
branching joint

(2)

(4)

(4)

(2)

(6)

(6)

Piping parts

(6)
Indoor
unit

Branching
pipe

(3)

(3)

No.

(3)

(3)

Name

(3)

(6)
Indoor
unit

Selection of pipe size

Remarks

Connecting pipe size of outdoor unit

(1)

Outdoor unit

1st branching
section

Main pipe

Out door unit capacity type

Gas pipe

Liquid pipe

0604 type

OD 19.1

OD 9.5

0804 type

OD 22.2*

OD 9.5

Same as connecting
pipe size of the
outdoor unit.

* OD 19.1 can be used, but may lower the performance.


Pipe size between branching sections

Total capacity codes of indoor


units at downstream side

(2)

Branching section

Branching pipe
Branching section

Equivalent to HP

Equivalent to
capacity

Gas
pipe

Liquid
pipe

Below 2.4

Below 6.6

12.7

9.5

2.4 to below 6.4

6.6 to below 18.0

15.9

9.5

6.4 or more

18.0 or more

19.1

9.5

Pipe size differs based


on the total capacity
code value of indoor
units at the
downstream side. If
the total value
exceeds the capacity
code of the outdoor
unit, apply the
capacity code of the
outdoor unit. (See
Table 1 and 2.)

Connecting pipe size of indoor unit

(3)

21-EN

Branching section
Indoor unit

connecting pipe
Indoor unit

Capacity rank

Gas pipe

Liquid
pipe

007 to 012 type

9.5

6.4

015 to 018 type

12.7

6.4

024 to 056 type

15.9

9.5

22-EN

+00EH99883601_00Ta.book

Page 12

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

No.

Piping parts

(4)

Branching section

Name

Installation Manual

Outdoor Unit

Allowable length / height difference of refrigerant piping

Selection of pipe size


Selection of branching section (Y-shaped branching joint)

Y-shaped
branching joint

Model name
Y-shape branching joint

Outdoor unit

RBM-BY55E

Selection of branching section (Branching header)

Model name

(5)

Branching section Branching header

Branching header*1

For 4 branches

RBM-HY1043E

For 8 branches

RBM-HY1083E

Main pipe
L1

Selection of PMV Kit

(6)

PMV Kit

PMV Kit

Indoor unit capacity type

RBM-PMV0362E

015, 018, 024 type

RBM-PMV0902E

1st branching
section

Model name

007, 009, 012 type

Branching
header

Branching pipe L2

*1: Up to a total of 6.0 maximum equivalent to HP capacity codes is connectable to one line
after branching of header.

Height difference
between indoor and
outdoor units H1

Branching pipe

Indoor unit

L3

Equivalent length corresponded to farthest piping L


Equivalent length corresponded to farthest piping after 1st branching Li

Height
difference
between
indoor units
H2

L4

Y-shaped
branch joint

Total extension of pipe (liquid pipe, real length)


Farthest piping length L
(*1)

Real length
Equivalent length

Piping Length Max. real length of main pipe

Height
Difference

A *1

Allowable
value

Pipes

100 m

L1 + L2 + L3 + L4 + a + b + c + d + e + f + g

50 m
60 m
30 m

L1 + L3 + L4 + g
L1

Max. real length of furthest piping from 1st branching Li


(*1)

20 m

L3 + L4 + g

Max. real length of indoor unit connecting pipe

10 m

a, b, c, d, e, f, g

Upper outdoor unit

15 m

Lower outdoor unit

15 m

10 m

Height between indoor


and outdoor units H1

Height between indoor units H2


*1: Furthest indoor unit from 1st branch to be named A.

EN

23-EN

12

24-EN

+00EH99883601_00Ta.book

Page 13

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Allowable length / height difference of refrigerant piping for quiet places


(with PMV Kit)

13

Installation Manual

Outdoor Unit

NOTE
Do not connect two or more indoor units to one PMV Kit. Arrange one indoor unit and one PMV Kit set to 1 by 1.

NO GOOD
Outdoor unit

OK

PMV Kit

PMV Kit

Indoor unit
Main
pipe
L1

Branching
header

Branching pipe L2

1st branching
section
Height
difference
between
indoor and
outdoor
units
H1

Indoor unit

PMV Kit

Height difference
between indoor
unit and PMV Kit
H2 *
* Between
highest unit and
lower units.

Indoor unit

Branching pipe
L3

Example)
Equivalent length corresponded to farthest piping L
Equivalent length corresponded to farthest piping after 1st branching Li

H2

L4

e
Y-shape
branch joint

H2

n
A *1
H2

Total extension of pipe (Liquid pipe,


real length)
Furthest piping
length L (*1)
Piping Length

Pipes

100 m

L1 + L2 + L3 + L4
+ a + b + c + d + e + f + g+ h + i + j + k + l + m + n

Real length

50 m

Equivalent length

60 m

L1 + L3 + L4 + g + n

Max. real length of main pipe

30 m

L1

Max. real length of furthest piping from


1st branching Li (*1)

15 m

L3 + L4 + g + n

Max. real length of indoor unit


connecting pipe

10 m

a + h, b + i, c + j, d + k, e + l, f + m. g + n

2 m or more
Below 10 m

h, i, j, k, l, m, n

Upper outdoor
unit

15 m

Lower outdoor
unit

15 m

10 m

Real length between PMV KIT and


indoor unit

Height
Difference

Allowable
value

Height between
indoor and
outdoor units H1

Height between indoor unit and PMV


kit H2
*1: Furthest indoor unit from 1st branch to be named A.

25-EN

26-EN

+00EH99883601_00Ta.book

Page 14

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Outdoor Unit

Airtight test

Installation Manual

REQUIREMENT
When pressure decrease is detected in steps 1-3, check the leakage at the connecting points.
Check the leakage using a foaming agent or other measures and seal the leak with re-brazing, flare retightening or other
methods. After sealing, execute an airtight test again.

Before starting an airtight test, further tighten the spindle valves on the gas side and liquid side.
Pressurize the pipe with nitrogen gas charged from the service port to the design pressure to conduct the airtight
test.
After the airtight test is completed, evacuate the nitrogen gas.
Apply pressure from the service ports of the packed valves (or ball valves) at liquid side, discharge gas side and
suction gas side.
An air tight test can be only performed to the service ports at liquid side, discharge gas side, and suction gas
side of the outdoor unit.
Close fully valves at liquid side, discharge gas side, and suction gas side. As there is possibility that nitrogen gas
enters in the refrigerant cycle, re-tighten the valve rods before applying pressure.
(Re-tightening of the valve rods are unnecessary for valves at discharge gas side because they are ball valves.)
For each refrigerant line, apply pressure gradually with steps at liquid side, discharge gas side, and suction gas
side.
Apply pressure to suction gas side, discharge gas side, and liquid side.
REQUIREMENT
Do not use Oxygen, Flammable gas and Noxious gas in an airtight test.
Low pressure
guage

Connected to indoor unit


Ball valve fully closed
(gas side)

Main pipe

Outdoor unit

High pressure
guage

Gauge
manifold

Brazed

Service port

6.4
Copper pipe

Reducing
valve

Fully closed

Service port
Packed valve fully closed
(liquid side)

6.4
Copper pipe

Nitrogen gas

To detect a gross leakage


1. Apply pressure 0.3 MPa (3.0 kg / cm2G) for 3 minutes or more.
2. Apply pressure 1.5 MPa (15 kg / cm2G) for 3 minutes or more.

EN

To detect a slow leakage


3. Apply pressure 3.73 MPa (38 kg / cm2G) for approx. 24 hours.
Check pressure down.
No pressure down: Accepted
Pressure down: Check the leaked position.
NOTE
However, if the environmental temperature changes from the moment of applying pressure to 24 hours after that, the
pressure will change by about 0.01 MPa (0.1 kg / cmG) per 1 C. Consider the pressure change when checking the
test result.

27-EN

14

28-EN

+00EH99883601_00Ta.book

Page 15

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Air purge

15

Installation Manual

Outdoor Unit

Adding refrigerant
After finishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging of
refrigerant.

NOTE
For the air purge at installation time (Discharge of air in connecting pipes), use Vacuum pump method from viewpoint
of the protection of the earths environment.
For protection of the earths environment, do not discharge the refrigerant gas in the air.
Eliminate the remaining air (nitrogen gas, etc.) in the unit by using a vacuum pump.
If gas remains, performance and reliability of the unit may be reduced.

After the airtight test, discharge nitrogen gas. Then connect the gauge manifold to the service ports at suction gas
side, discharge gas side and liquid side, and connect the vacuum pump as shown in the following figure.
Perform vacuuming for suction gas side, discharge gas side and liquid side.
Perform vacuuming from both suction gas side, discharge gas side and liquid side.
Perform vacuuming from both liquid and gas sides.
Use a vacuum pump with counter-flow preventive function so that oil in the pump does not back up in the pipe
of the air conditioner when the pump has been stopped. (If oil in the vacuum pump enters in to the air conditioner
with R410A refrigerant, an error may occur in the refrigeration cycle.)
Low pressure
guage

Connected to indoor unit


Ball valve fully closed
(gas side)

Main pipe

Outdoor unit

High pressure
guage

Gauge
manifold

Calculation of additional refrigerant charge amount


Default refrigerant amount does not include the refrigerant for pipes at the local site.
For refrigerant to be charged in pipes at the local site, calculate the amount and charge it additionally.
NOTE
Do not degas the refrigerant from the air conditioner when the result of additional refrigerant charge amount
calculation is negative valve.
Outdoor unit type

MAP060

Charging amount (kg)

Additional refrigerant
charge amount at local
site

Real length of liquid


pipe

Additional refrigerant
charge amount per 1 m
liquid pipe
(Table 1)

Corrective amount of
refrigerant depending
on the indoor units
(Table 2)

Compensation by
outdoor HP
(Table 3)

Table 1
Liquid pipe dia. (mm)
Additional refrigerant amount / 1 m
liquid pipe (kg / m)

Brazed

MAP080
3.9

6.4

9.5

0.025

0.055

Table 2
Service port
Fully closed

4-way cassette
Service port
Packed valve fully closed
(liquid side)

Vacuum pump

Use a vacuum pump that has a high vacuum (below -755 mmHg) and a large exhaust gas amount (over 40 L /
minute).
Perform vacuuming for 2 or 3 hours though time differs due to pipe length.
In this time, check all valves at liquid and gas sides are fully closed.
If vacuuming valve amount is not decreased to below -755 mmHg even after vacuuming for 2 hours or more,
continue vacuuming for 1 hour or more.
If -755 mmHg or less cannot be obtained by 3 hours or more vacuuming, detect and repair the leak.
When the vacuuming valve has reached -755 mmHg or less after vacuuming for 2 hours or more, close valves
VL and VH on the gauge manifold fully. Stop the vacuum pump, leave it as it is for 1 hour and then check the
vacuum does not change. If it does change then there may be a leak within the system.
After the above procedure for vacuuming has finished, exchange the vacuum pump with a refrigerant cylinder
and advance to the additional charging of refrigerant.

0.8

MMU-AP****H
MMU-AP****MH(-E)

1.0 1.25 1.7

2.0

2.5

3.0

3.2

4.0

5.0

6.0

0.4

0.4

0.8

0.8

0.8

0.8

1.2

1.2

1.2

0.8

0.4

0.4

0.4

0.6

0.6

0.4

0.4

0.4

0.5

0.7

0.7

0.7

0.7

1.1

1.1

1.1

1-way cassette MMU-AP****YH(-E) / SH(-E)

0.4

0.4

0.4

0.5

0.5

0.6

MMD-AP****BH(-E)

0.3

0.3

0.3

0.5

0.5

0.8

0.8

0.8

1.1

1.1

1.1

MMD-AP****SPH(-E)

0.3

0.3

0.3

0.5

0.5

0.8

1.0

1.0

1.0

1.3

MMD-AP****H(-E)
Ceiling
High wall

Floor standing

MMC-AP****H(-E)

0.5

0.5

0.7

0.7

1.1

1.1

MMK-AP****3H(-T)

0.5

0.5

0.5

0.7

0.7

0.7

MMK-AP****4MH-E / 2H

0.3

0.3

0.3

1.3

MMF-AP****H(-E)

0.7

0.7

1.0

1.0

1.3

1.3

MML-AP****H(-E)

0.5

0.5

0.5

0.5

0.8

0.8

MML-AP****BH(-E)

0.3

0.3

0.3

0.5

0.5

0.7

MML-AP****NH-E

0.5

0.5

0.5

0.5

0.5

(kg)

Table 3
Outdoor unit type
Compensation by outdoor HP (kg)

29-EN

007 009 012 015 018 024 027 030 036 048 056

Equivalent to HP

2-way cassette MMU-AP****WH

Duct
Indoor unit
model name

Capacity rank

MAP 060

MAP 080

- 1.6

- 1.0

30-EN

+00EH99883601_00Ta.book

Page 16

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Installation Manual

Outdoor Unit

How to open the valve

Example: (0804 type)

Open or close the valve.

Liquid side
Open the valve with a 4 mm hexagon wrench.

L3

L2

L1

L5

L4

L7

L6

Gas side
A

L1

9.5: 10 m

L2

9.5: 10 m

L3

9.5: 5 m

L5

6.4: 3 m

L6

6.4: 4 m

L7

6.4: 5 m

MMU-AP0272H

MMU-AP0182H

MMU-AP0184MH-E

Valve unit

L4

9.5: 3 m

MMU-AP0094SPH-E

Turn it
counterclockwise by
90 until it hits the
stopper with a slotted
screwdriver. (full open)

Additional charge amount R (kg)


= (Lx 0.025 kg/m) + (Ly 0.055 kg/m) + (a + b + c + d) + (- 1.0 kg)
= (12 m 0.025 kg/m) + (28 m 0.055 kg/m) + (0.8 kg + 0.8 kg + 0.6 kg + 0.3 kg) + (- 1.0 kg)
Lx:
Ly:
a:
b:
c:
d:

Opened fully

Closed completely
Stopper pin

Charge port

Real total length of liquid pipe 6.4 (m)


Real total length of liquid pipe 9.5 (m)
Corrective amount of refrigerant depending on the unit A (kg)
Corrective amount of refrigerant depending on the unit B (kg)
Corrective amount of refrigerant depending on the unit C (kg)
Corrective amount of refrigerant depending on the unit D (kg)

Flare nut

Main stopper

Movable part of valve (stem)

2
Handle position
While the valve is fully opened, after the screwdriver has reached the stopper, do not apply torque exceeding 5
Nm. Applying excessive torque may damage the valve.

Charging of refrigerant
Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the
liquid side.
If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and
gas sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas
side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.

Valve handling precautions


Open the valve stem until it strikes the stopper.
It is unnecessary to apply further force.
Securely tighten the cap with a torque wrench.
Cap tightening torque
9.5 mm

33 to 42 Nm
(3.3 to 4.2 kgfm)

19.1 mm

20 to 25 Nm
(2.0 to 2.5 kgfm)

Valve size

Charge port

14 to 18 Nm
(1.4 to 1.8 kgfm)

EN

31-EN

16

32-EN

+00EH99883601_00Ta.book

Page 17

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Electric wiring

17

Installation Manual

Outdoor Unit

Specifications for communication wiring

WARNING

Design of communication wiring

The appliance shall be installed in accordance with national wiring regulations.


Capacity shortages of the power circuit or an incomplete installation may cause an electric shock or fire.

Summary of communication wiring


Outdoor unit

CAUTION
Perform wiring of power supply complying with the rules and regulations of the local electric company.
Do not connect 380 V power to the terminal blocks for control cables (U1, U2, U3, U4); otherwise, the unit may
break down.
Be sure that electric wiring does not come into contact with high-temperature parts of piping; otherwise, the
coating of cables may melt and cause an accident.
After connecting wires to the terminal block, take off the traps and fix the wires with cord clamps.
Follow the same structure for both the control wiring and refrigerate piping.
Do not conduct power to indoor units until vacuuming of the refrigerant pipes has finished.
For the wiring of power to indoor units and that between indoor and outdoor units, follow the instructions in the
installation manual of each indoor unit.

U1 U2 U3 U4

Central controller
U1 U2
U3 U4

Communication wiring between indoor and outdoor units


(shield wire)
Communication wiring between indoor units (shield wire)

Power wiring selection


Standard model

U1 U2 A B

MCA: Maximum Circuit Amps


MOCP: Maximum Overcurrent Protection (Amps)
Model
MCY-MAP0604HT8
MCY-MAP0804HT8
MCY-MAP0604HT7
MCY-MAP0804HT7

Power Supply
Phase and frequency

Nominal Voltage

MCA
(A)

MOCP
(A)

3N~ 50 Hz

380-415 V

16.5

25

3N~ 60 Hz

380 V

16.5

25

U1 U2 A B

Indoor unit

Indoor unit

Indoor unit

A B

Remote controller

U1 U2 A B

A B

Remote controller

U1 U2 A B

Indoor unit

A B

Remote controller
(group control)

Communication wiring and central control wiring use 2-core non-polarity wires.
Use 2-core shield wires to prevent noise trouble.
In this case, for the system grounding, close (connect) the end of shield wires, and isolate the end of terminal.
Use 2-core non-polarity wire for remote controller. (A, B terminals)
Use 2-core non-polarity wire for wiring of group control. (A, B terminals)

Circuit breaker
(earth leakage breaker)

33-EN

Main switch
(fuse)

34-EN

+00EH99883601_00Ta.book

Page 18

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Installation Manual

Outdoor Unit

Group control through a remote controller

Keep the rule of below tables about size and length of communication wiring.

Group control of multiple indoor units (8 units) through a single remote controller

Central
controller

S-MMS
(Super modular multi system)

MiNi-SMMS

U1 U2
U3 U4

Table-1

L4

Outdoor unit

U3 U4

Indoor unit No.1

U3 U4

U1 U2

Follower
unit

Header
unit

U1 U2

U3 U4

U3 U4

U1 U2 U5 U6

U1 U2 U5 U6

Table-1

L5

AB

Remote controller

No.2
AB

No.3
AB

No.4

No.7

AB

AB

No.8
AB

(A.B)

Table-2

L1
L2

Indoor unit

U1 U2

U1 U2

A B

U1 U2

A B

U1 U2

A B

Table-3

Connection of power wires and communication wires

L3

A B

U1 U2
A B

L7

U1 U2

U1 U2

A B

A B

U1 U2
A B

Table-1

A B

L7
L6

L6

Remote controller

Remote controller

Remove knockouts on the piping / wiring panel on the front of the unit or the panel on the bottom to get the power
and communication wires through the holes.

U1 U2

Remote controller

Control wiring between indoor and outdoor units (L1, L2, L3), Central control wiring (L4)

Wiring

2-core, non-polarity

Type

Shield wire

Size / Length *1

1.25 mm2: Up to 1000 m


2.0 mm2: Up to 2000 m

Piping / wiring panel

Knockout for the communication wires


and refrigerant piping

(*1): Total of control wiring length for all refrigerant circuits ( L1 + L2 + L3 + L4 )

Table-2
Wiring

2-core, non-polarity

Type

Shield wire

Size / Length

1.25 mm2 to 2.0 mm2


Up to 100 m (L5)

Table-3
Wire

35-EN

Control wiring between outdoor units (L5) (S-MMS-i)

Knockout for the power wire

NOTE
Separate the power wire and communication wires.

Remote controller wiring (L6, L7)


2-core

Size

0.5 mm2 to 2.0 mm2

Length

Up to 500 m (L6 + L7)


Up to 400 m with of wireless remote controller in group control.
Up to 200 m total length of control wiring between indoor units ( L6 )

EN

18

36-EN

+00EH99883601_00Ta.book

Page 19

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Communication
terminal block

19

Installation Manual

Outdoor Unit

2. Use round-type crimping terminals for power connection.


Also, apply insulating sleeves to the crimping parts. Use a driver of appropriate size to fix the terminal screws.
Power supply
terminal block
L1

L2

L3

Earth screw
L1

L2

L3

Cord clamps

Power supply
wires

10 mm or
more

Power supply wire


Earth wire

Communication
wires

Protective bush
(accessory)
Wire size*

Power supply wire connection


1. Insert the power supply wire through the cutout on the side of the electrical control box and connect the power
supply wire to the power supply terminal block and the earth wire to the earth screw. After that, fix the power
supply wire with the 2 cord clamps.

37-EN

2.5 mm2

* Design 60245 IEC66


Screw size and tightening torque
Screw size

Tightening torque
(Nm)

Power supply terminal

M4

0.9 to 1.5

Earth screw

M4

0.9 to 1.5

38-EN

+00EH99883601_00Ta.book

Page 20

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Installation Manual

Outdoor Unit

Communication wire connection


Get the communication wire through the cutout on the side of the electrical control box and connect it to the
communication wire terminals, then fix it with the communication cable clamp.

Address setting

On this unit, it is required to set the addresses of the indoor units before starting air conditioning.
Set the addresses following the steps below.

CAUTION
Be sure to complete the electric wiring before setting the addresses.
If you turn on the outdoor unit before turning on the indoor units, the CODE No. [E19] is indicated on the 7-segment
display on the interface P.C. board of the outdoor unit until the indoor units are turned on. This is not a malfunction.
It may take up to ten minutes (normally about five minutes) to address one refrigerant line automatically.
Settings on the outdoor unit are required for automatic addressing. (Address setting is not started simply by turning
on the power.)
Running the unit is not required for address setting.
The addresses can be set manually.
Automatic addressing:
Manual addressing:

U1

U2

To indoor
unit

U3

U4

To central
controller

setting addresses using SW15 on the interface P.C. board on the outdoor unit
setting addresses on the wired remote controller.
* When setting an address manually, the wired remote controller must temporarily be
paired with an indoor unit one-to-one. (when the system is organized for group
operation and no Remote controller)

Automatic address setting


U3, U4: Central control device

No central control:
Central control of 2 or more refrigerant lines:

go to Address setting procedure 1


go to Address setting procedure 2

U1, U2: Communication wiring between Indoor / Outdoor unit

Screw size and tightening torque

Communication wire terminal

(Example)
Screw size

Tightening torque
(Nm)

M3.5

0.80 to 0.96

When controlling a single refrigerant line


centrally

When controlling 2 or more refrigerant lines


centrally

To procedure 1

To procedure 2

Address setting
procedure

System wiring
diagram

Outdoor

Central
controller

Outdoor

Indoor

Indoor

Indoor

Remote
controller

Remote
controller

Remote
controller

Central
controller

Indoor

Outdoor

Outdoor

Indoor

Indoor

Indoor

Remote
controller

Remote
controller

Remote
controller

Central
controller

Indoor

Address setting procedure 1

1
2
3

39-EN

20

EN

Turn on indoor units first, and then turn on outdoor units.


About one minute after turning the power on, confirm that the 7-segment display on the interface
P.C. board of the outdoor unit indicates U. 1. L08 (U. 1. flash) .
Press SW 15 to start the automatic address setting.
(It may take up to 10 minutes (normally about 5 minutes) to complete one lines setting.)

40-EN

+00EH99883601_00Ta.book

Page 21

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

The 7-segment display indicates Auto 1 Auto 2 Auto 3 .


After the indication, U. 1. - - - (U. 1. flash) starts flashing on the display.
When the flashing stops and U. 1. - - - (U. 1. light) remain lit on the display, the setting is

21

Installation Manual

Outdoor Unit

Interface P.C. board on the outdoor unit

SW06

SW07

SW09

SW10

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

SW11

SW12

SW13

SW14

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

complete.
Interface P.C. board on the outdoor unit

SW04

SW05

SW15

D600 D601 D602 D603 D604

SW01

SW02

3
2,4
Switch settings for a line (system) address on the interface P.C. board on the outdoor unit
(: switch ON, : switch OFF)

SW03

Line (system) address

REQUIREMENT
When 2 or more refrigerant lines are controlled as a group, be sure to turn on all the indoor units in the group
before setting addresses.
If you set the unit addresses of each line separately, each lines header indoor unit is set separately. In that case,
the CODE No. L03 (indoor header unit overlap) is indicated as running starts. Change the group address to
make one unit the header unit using wired remote controller.
(Example)

Controlling 2 or more refrigerant lines as a group

Outdoor

System wiring
diagram

Indoor

Remote
controller

Outdoor

Indoor

Indoor

Indoor

(Group control)

Address setting procedure 2

Set a system address for each system using SW 13 and 14 on the interface P.C. board on the
outdoor unit of each system.
(factory default: Address 1)

NOTE
Be sure to set a unique address on each system. Do not use a same address as another system (refrigerant line)
or a custom side.

SW13

SW14

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

: not used for system address setting (Do not change their positions.)

41-EN

42-EN

+00EH99883601_00Ta.book

Page 22

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Installation Manual

Outdoor Unit

Be sure to disconnect the relay connectors between the [U1,U2] and [U3,U4] terminals on all the
outdoor units that will be connected to the central control. (factory default: disconnected)

Connect the relay connectors between the [U1, U2] and [U3, U4] terminals of the outdoor unit of
each refrigerant line.

9
2

U1

U2

To indoor
unit

3
4
5
6

U3

U4

U1

To central
controller

To indoor
unit

U3

U4

To central
controller

10 Set the central control address.

Turn on indoor units first, and then turn on outdoor units.

(For the setting of the central control address, refer to the installation manuals of the central control devices.)

About 1 minute after turning the power on, confirm that the 7-segment display on the interface
P.C. board of the outdoor unit indicates U. 1. L08 (U. 1. flash) .

Header unit interface P.C. board

Press SW 15 to start the automatic address setting.


(It may take up to 10 minutes (normally about 5 minutes) to complete one lines setting.)

SW15

The 7-segment display indicates Auto 1 Auto 2 Auto 3 .


After the indication, U. 1. - - - (U. 1. flash) starts flashing on the display.
When the flashing stops and U. 1. - - - (U. 1. light) , remains lit on the display, the setting is

SW04 SW05

7-segment
display

complete.

7
8

U2

SW13

Repeat steps 4 to 6 for other refrigerant lines.

SW14

D600 D601 D602 D603 D604

SW01 SW02 SW03

After completing address setting of all systems, turn off dip switch 2 of SW30 on the interface P.C.
boards of all the outdoor units connected to the same central control, except the unit that has the
lowest address.
(For unifying the termination of the wiring for the central control of indoor and outdoor units)

SW30
1 2

43-EN

22

EN

44-EN

+00EH99883601_00Ta.book

Page 23

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Switch setting (setting example when controlling 2 or more refrigerant lines centrally)
Outdoor units (setting manually)
*The items in bold font must be set manually.
Outdoor units interface
P.C. board

Outdoor unit

Outdoor unit

Outdoor unit

Factory default

SW13, 14
(line (system) address)

Dip switch 2 of SW30


(terminator of indoor /
outdoor communication
line and central control
line)

ON

Set to OFF after setting


addresses.

Set to OFF
after setting
addresses.

ON

Connect after setting


addresses.

Connect after setting


addresses.

Connect after
setting
addresses.

Open

Relay connector

U3 U4

U3 U4

U1 U2

Relay
connector

U1 U2

Relay
connector

Relay
connector

U1 U2

U1 U2

U1 U2

A B

A B

A B

Remote
controller

Remote
controller

Remote
controller

Individual

U1 U2

Manual address setting with the remote controller


Procedure when setting indoor units addresses first under the condition that indoor wiring has been completed and
outdoor wiring has not been started (manual setting using the remote controller)

Wiring example of 2 refrigerant lines

Outdoor
unit

Outdoor
unit

Indoor unit 1

Indoor unit 3

Indoor unit 2

Line (system) address

Indoor unit address

1
Header unit

2
Follower unit

2
Follower unit

2
Follower unit

2
Follower unit

Group address

In the example above, disconnect the remote controller connections between the indoor units and connect
a wired remote controller to the target unit directly before address setting.

U1 U2

A B

CODE No.
SET DATA SETTING

A B

UNIT No.

2, 5, 8
4, 7, 10
11

Group

Indoor unit address

Group address

CAUTION
Relay connector connection
Never connect relay connectors between the [U1, U2] and [U3, U4] terminals before completing address setting of all
the refrigerant lines. Otherwise, the addresses cannot be set correctly.

R.C.

SET DATA

Remote
controller

Line (system) address

Indoor unit 2

Indoor unit 1
Remote
controller

Indoor units
(automatic setting)

45-EN

Refrigerant line 2

Refrigerant line 1

U3 U4

U1 U2

Installation Manual

Outdoor Unit

Central
controller

Outdoor unit

Outdoor unit

Outdoor unit

23

TEMP.

No.

CODE No.
ON / OFF

TIMER SET

3, 6, 9

TIME
FILTER
RESET TEST

SET

CL

Pair the indoor unit to set and the remote controller one-to-one.
Turn on the power.

Push and hold the


LCD starts flashing.

SET

CL

, and

TEST

buttons at the same time for more than 4 seconds.

46-EN

+00EH99883601_00Ta.book

Page 24

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Confirming the indoor unit addresses and the position of an


indoor unit using the remote controller

<Line (system) address>

2
3
4

Push the TEMP.

buttons repeatedly to set the CODE No. to

Push the TIME


/
buttons repeatedly to set a system address.
(Match the address with the address on the interface P.C. board of the outdoor unit in the same refrigerant
line.)

Confirming the numbers and positions of indoor units

SET

To see the indoor unit address of an indoor unit which you know the position of

Push
button.
(It is OK if the display turns on.)

When the unit is individual (the indoor unit is paired with a wired remote controller one-to-one), or
it is a group-controlled one.

<Indoor unit address>

5
6
7

Push the TEMP.


Push the TIME

/
/

Installation Manual

Outdoor Unit

buttons repeatedly to set the CODE No. to

buttons repeatedly to set an indoor unit address.

CODE No.
UNIT No.

SET

Push the
button.
(It is OK if the display turns on.)

TEMP.

<Group address>

8
9

Push the TIME


/
set the address to

10 Push the

SET

: 0000
: 0001
: 0002

buttons repeatedly to set the CODE No. to

TIME
FILTER
RESET TEST

buttons repeatedly to set a group address. If the indoor unit is individual,


; header unit,
; follower unit,
.

11 Push the

In case of group
control

1
2

button.
SETTING

has disappeared.)

NOTE
1. Do not use address numbers 29 or 30 when setting system addresses using the remote controller.
These 2 address numbers cannot be used on outdoor units and the CODE No. [E04] (Indoor / outdoor
communication error) will appear if they are mistakenly used.
2. If you set addresses to indoor units in 2 or more refrigerate lines manually using the remote controller and will
control them centrally, set the outdoor unit of each line as below.
Set a system address for the outdoor unit of each line with SW13 and 14 of their interface P.C. boards.
Turn off dip switch 2 of SW30 on the interface P.C. boards of all the outdoor units connected to the same
central control, except the unit that has the lowest address. (For unifying the termination of the wiring for the
central control of indoor and outdoor units)
Connect the relay connectors between the [U1, U2] and [U3, U4] terminals on the outdoor unit of each
refrigerate line.
After finishing all the settings above, set the address of the central control devices. (For the setting of the
central control address, refer to the installation manuals of the central control devices.)

Push the

ON / OFF

button if the units stop.

Push the
button (left side of the button).
A unit numbers
is indicated on the LCD (it will disappear after a few seconds). The indicated number
shows the system address and indoor unit address of the unit.
When 2 or more indoor units are connected to the remote controller (group-controlled units), a number of other
connected units appears each time you push the
button (left side of the button).

To find an indoor units position from its address


When checking unit numbers controlled as a group

CODE No.
SET DATA SETTING
UNIT No.

R.C.

TEMP.

Stop

1
47-EN

CL

(Execute it while the units are running.)

button.

The address setting is complete.


( SETTING flashes. You can control the unit after

SET

(It is OK if the display turns on.)


TEST

Starts
running

TIMER SET

Push the TEMP.

Individual
Header unit
Follower unit

ON / OFF

24

No.

EN
ON / OFF

TIMER SET
TIME
FILTER
RESET TEST

SET

CL

2
48-EN

+00EH99883601_00Ta.book

Page 25

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

25

Installation Manual

Outdoor Unit

(Execute it while the units are stopped.)


The indoor unit numbers in a group are indicated one after another. The fan and louvers of the indicated units are
activated.

To select another system address

2
3

VENT

Push and hold the


and TEST buttons at the same time for more than 4 seconds.

appears on UNIT No. on the LCD display.


The fans and louvers of all the indoor units in the group are activated.
Push the
button (left side of the button). Each time you push the button, the indoor unit
numbers are indicated one after another.
The first-indicated unit number is the address of the header unit.
Only the fan and louvers of the indicated indoor unit are activated.
Push the TEST button to finish the procedure.
All the indoor units in the group stop.

Push the CL button to return to step 2.


After returning to step 2, select another system address and check the indoor unit addresses of the line.
Push the

TEST

button to finish the procedure.

Changing the indoor unit address using a remote controller


To change an indoor unit address using a wired remote controller.
The method to change the address of an individual indoor unit (the indoor unit is paired with a wired
remote controller one-to-one), or an indoor unit in a group.
(The method is available when the addresses have already been set automatically.)

To check all the indoor unit addresses using an arbitrary wired remote controller.
(When communication wirings of 2 or more refrigerant lines are interconnected for central control)

CODE No.
SET DATA SETTING
UNIT No.

R.C.

CODE No.
UNIT No.

R.C.

No.

TEMP.

ON / OFF

TIMER SET

2
4
5

TIME
FILTER
RESET TEST

SET

CL

6
3

(Execute it while the units are stopped.)


You can check indoor unit addresses and positions of the indoor units in a single refrigerant line.
When an outdoor unit is selected, the indoor unit numbers of the refrigerant line of the selected unit are indicated
one after another and the fan and louvers of the indicated indoor units are activated.

1
2
3
4

49-EN

Push and hold the TIME


and
At first, the line 1 and CODE No.
an outdoor unit.)
Push the
address.

TEST

buttons at the same time for more than 4 seconds.


(Address Change) are indicated on the LCD display. (Select

(left side of the button) and

SWING/FIX

buttons repeatedly to select a system

SET

Push the
button to confirm the system address selection.
The address of an indoor unit connected to the selected refrigerant line is indicated on the LCD display and
its fan and louvers are activated.
Push the
button (left side of the button). Each time you push the button, the indoor unit
numbers of the selected refrigerant line are indicated one after another.
Only the fan and louvers of the indicated indoor unit are activated.

TEMP.

3
5
8

SET DATA SETTING

No.

ON / OFF

TIMER SET
TIME
FILTER
RESET TEST

SET

CL

Finish

2, 6, 7

(Execute it while the units are stopped.)

1
2
3
4
5
6
7
8

SET

Push and hold the


, CL , and TEST buttons at the same time for more than 4 seconds.
(If 2 or more indoor units are controlled in a group, the first indicated UNIT No. is that of the head unit.)
Push the
button (left side of the button) repeatedly to select an indoor unit number to
change if 2 or more units are controlled in a group. (The fan and louvers of the selected indoor
unit are activated.)
(The fan of the selected indoor unit is turned on.)
Push the TEMP.

Push the TIME


/
to that you want.
Push the

SET

buttons repeatedly to select

for CODE No..

buttons repeatedly to change the value indicated in the SET DATA section

button.

Push the
button (left side of the button) repeatedly to select another indoor UNIT No. to
change.
Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.
Push the

button (left side of the button) to check the changed addresses.

If the addresses have been changed correctly, push the

TEST

button to finish the procedure.

50-EN

+00EH99883601_00Ta.book

Page 26

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

To change all the indoor unit addresses using an arbitrary wired remote controller.
(The method is available when the addresses have already been set automatically.)
(When communication wirings of 2 or more refrigerant lines are interconnected for central control)

5
6

NOTE
You can change the addresses of indoor units in each refrigerant line using an arbitrary wired remote controller.
* Enter the address check / change mode and change the addresses.

7
CODE No.
SET DATA SETTING

UNIT No.

R.C.

No.

TEMP.

ON / OFF

TIME
FILTER
RESET TEST

SET

Cancels the line selection

If no number appears on UNIT No., no outdoor unit exists on the line. Push
following step 2.

CL

button and select another line

2
3

Push and hold the TIME


and
At first, the line 1 and CODE No.
Push

TEST

1
buttons at the same time for more than 4 seconds.
(Address Change) are indicated on the LCD display.

(left side of the button) and

SWING/FIX

SET

button to confirm the new address on SET DATA.

Push the
button (left side of the button) repeatedly to select another address to change.
Each time you push the button, the indoor unit numbers in a refrigerant line are indicated one
after another. Only the fan and louvers of the selected indoor unit are activated.
Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.
SET

Push the
button.
(All the segments on the LCD display light up.)
Push the

TEST

button to finish the procedure.

Method 2
Clearing all the indoor unit addresses on a refrigerate line at once from the outdoor unit.

(Execute it while the units are stopped.)

Push the

Method 1
Clearing each address separately using a wired remote controller.
Set the system address, indoor unit address and group address to 0099 using a wired remote controller.
(For the setting procedure, refer to the address setting procedures using the wired remote controller on the
previous pages.)

CL

Push the TIME


/
buttons repeatedly to change the value of the indoor unit address in SET
DATA.
Change the value in SET DATA to that of a new address.

Resetting the address


(Resetting to the factory default (address undecided))

TIMER SET

Installation Manual

Outdoor Unit

buttons repeatedly to select a system address.

Turn off the refrigerant line to reset to the factory default and set the outdoor unit of the line as
below.
1) Disconnect the relay connectors between the [U1, U2] and [U3, U4] terminals.
(Leave them as they are if they have already been disconnected.)
2) Turn on dip switch 2 of SW30 on the interface P.C. board of the outdoor unit if the switch is OFF.
(Leave it as it is if it has already been set to ON.)

SET

Push the
button.
The address of one of the indoor units connected to the selected refrigerant line is indicated on the LCD
display and the fan and louvers of the unit are activated.
At first, the current indoor unit address is displayed in SET DATA.
(No system address is indicated.)

Central controller

Outdoor
unit

Outdoor
unit

U3 U4

U1 U2
U3 U4

Outdoor
unit

U3 U4

U3 U4

CODE No.
SET DATA SETTING
UNIT No.

R.C.

TEMP.

4
8

Finish

U1 U2

No.

U1 U2

U1 U2

EN

ON / OFF

TIMER SET

U1 U2

TIME
FILTER
RESET TEST

SET

CL

5, 7

Press to finish
setting.

U1 U2

U1 U2

A B

A B

A B

Remote
controller

Remote
controller

Remote
controller

U1 U2
A B

U1 U2
A B
Remote
controller

Indoor units to have their addresses initialized

51-EN

26

52-EN

+00EH99883601_00Ta.book

Page 27

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Turn on the indoor and outdoor units of the refrigerant line for which you want to initialize the
addresses. About one minute after turning on the power, confirm that the 7-segment display on
the outdoor unit indicates U.1. - - - and operate the interface P.C. board on the outdoor unit of
the refrigerant line as follows.

SW01

SW02

SW03

Confirm that the 7-segment display indicates


A.d.buS and turn SW04 ON for more than five
seconds.

System / indoor unit / group address

Confirm that the 7-segment display indicates


A.d.nEt and turn SW04 ON for more than five
seconds.

Central control address

3
4

SW04

Clearable addresses

Confirm that the 7-segment display indicates A.d. c.L. and set SW01, SW02 and SW03 to 1, 1, 1
respectively.
After a time U.1.L08 appears on the 7-segment display if the address clearing has been
completed successfully.
If the 7-segment display indicates A.d. n.G., the outdoor unit may still connected with other
refrigerant lines. Check the connection of the relay connectors between [U1, U2] and [U3, U4].

27

Installation Manual

Outdoor Unit

Test run

Before test run


Confirm that the valve of the refrigerate pipe of the outdoor unit is OPEN.
Before turning on the power, confirm that the resistance between the terminal block of power supply and the
earth is more than 1 M using a 500 V megohmmeter.
Do not run the unit if it is less than 1 M.

CAUTION
Turn on the power and turn on the case heater of the compressor.
To save the compressor when it is activated, leave the power on for more than 12 hours.

Methods of test run

NOTE
Take care to carry out the procedure above correctly; otherwise, addresses in other refrigerate lines may also be
cleared.

Set the addresses again after finishing the clearance.

When executing a test run using a remote controller


Operate the system normally to check the running condition using the wired remote controller. Follow the
instructions in the supplied owners manual when operating the unit.
If you use a wireless remote controller for operations, follow the instructions in the installation manual supplied with
the indoor unit.
To execute a test run forcibly under the condition that the thermostat automatically turns the unit off due to the
indoor temperature, follow the procedure below.
The forcible test run will automatically stop after 60 minutes to prevent continuous forcible running and return to
normal running.

CAUTION
Do not use forcible running except for a test run as it overloads the unit.

TEMP.

ON / OFF

TIMER SET
TIME
FILTER
RESET TEST

SET

2, 4
3

CL

1, 5

53-EN

54-EN

+00EH99883601_00Ta.book

Page 28

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Installation Manual

Outdoor Unit

When executing a test run using the interface P.C. board on the outdoor
unit

Push and hold the TEST button for more than 4 seconds. TEST appears on the LCD display and the
unit enters the test mode.
(TEST is indicated on the LCD display during the test run.)

You can execute a test run by operating switches on the interface P.C. board of the outdoor unit.
Individual test run, which tests each indoor unit separately, and corrective test run, which tests all the indoor
units connected, are available.

TEST

<Individual test run>

2
3

Starting operation
Push the
Push the

ON / OFF
MODE

button.

button to switch the running mode to COOL or HEAT.

Set the running mode to COOL or HEAT on the remote controller of the indoor unit to be
tested.
(The unit will run in the current mode unless you set the mode otherwise.)

NOTE
7-segment display

Do not run the unit in any mode other than COOL or HEAT.
You cannot change the temperature setting during the test run.
Errors are detected as usual.

[A]

TEST

4
5

[B]

[U1]

ON / OFF
Push the
button to stop running after finishing the test run.
The indication on the LCD display returns to the status of procedure 1.

Push the TEST button to exit the test mode.


(TEST disappears on the LCD display and the status changes to normal stopped mode.)

Set the rotary switches on the interface P.C. board of the outdoor unit: SW01 to [16], SW02 and
SW03 to the address of the indoor unit to be tested.
SW02

SW03

1 to 16

1 to 16

Set number of SW02

Indoor unit address

1 to 16

17 to 32

Set number of SW02 + 16

1 to 16

33 to 48

Set number of SW02 + 32

1 to 16

49 to 64

Set number of SW02 + 48

7-segment display
[A]
[

[B]
]

Address display of the


corresponding indoor unit

Push and hold SW04 for more than 10 seconds.


7-segment display
[A]
[

[B]
]

Address display of the


corresponding indoor unit

]


[FF] is displayed for 5


seconds.

EN

NOTE

55-EN

28

The running mode follows the mode setting on the remote controller of the target indoor unit.
You cannot change the temperature setting during the test run.
Errors are detected as usual.
The unit does not perform test run for 3 minutes after turning the power on or stopping running.

56-EN

+00EH99883601_00Ta.book

Page 29

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Finishing operation

29

Installation Manual

Outdoor Unit

Stop operation

Set the rotary switches on the interface P.C. board of the outdoor unit back: SW01 to [1], SW02 to
[1] and SW03 to [1].

Set the rotary switches on the interface P.C. board of the outdoor unit back:
SW01 to [1], SW02 to [1] and SW03 to [1].

7-segment display

7-segment display

[A]
[U1]

[B]
[

[A]
[U1]

[B]
[

<Corrective test run>


Interface PC board

Start operation

Set the rotary switches on the interface P.C. board of the outdoor unit as below.
When in COOL mode: SW01=[2], SW02=[5], SW03=[1].
When in HEAT mode: SW01=[2], SW02=[6], SW03=[1].
7-segment display

SW04 SW05 SW15

Push switch

Push switch
D600 D601 D602 D603 D604

7-segment
display [B]

7-segment
display [A]
SW01 SW02 SW03

[A]
[C ]
[H ]

[B]
[
[

]
]

Rotary switches

Push and hold SW04 for more than 2 seconds.


7-segment display
[A]
[C ]
[H ]

[
[

[B]
- C
- H

]
]

NOTE
You cannot change the temperature setting during the test run.
Errors are detected as usual.
The unit does not perform test run for 3 minutes after turning the power on or stopping running.

57-EN

58-EN

+00EH99883601_00Ta.book

Page 30

Thursday, September 8, 2011

4:34 PM

Installation Manual

Outdoor Unit

Troubleshooting

Check code
Indication on 7-segment display on the outdoor unit

In addition to the CODE No. on the remote controller of an indoor unit, you can diagnose failure type of an outdoor
unit by checking the 7-segment display on the interface P.C. board.
Use the function for various checks.
Set every dip switch to OFF after checking.

Rotary switch setting value


D600 D601 D602 D603 D604

SW01

SW02

SW03

LED
A

Outdoor unit check code

H06

Low pressure proctive operation

L04

Outdoor system address duplication

L06

Number of prior indoor units

L08

Indoor unit group / address unset

L10

Outdoor unit capacity unset.

L29

IPDU number information(*1)

IPDU quantity error

L30

Detected indoor unit address

External interlock of indoor unit

L31

Other compressor errors

Discharge temperature TD error

Outdoor unit number


(U1)

P05

Check code display*

P07

* If a check code has an auxiliary code, the display indicates the check code for three seconds and the auxiliary
code for one second alternately.

P10

Check code

59-EN

Number of indoor units which received normally

Detected indoor unit address

01: TS condition
02: TD condition

P19

Detected outdoor unit number

Check code name

E07

E08

Duplicated indoor addresses

Duplication of indoor addresses.

E12

Automatic addressing start error

E15

No indoor unit during automatic addressing

P22

Indoor / outdoor communication circuit error

E16

00: Capacity over


01~: Number of connected units

Capacity over / number of connected indoor units

E20

01: Other line outdoor connected


02: Other line indoor connected

Other lines connected during automatic addressing

E31

IPDU quantity information(*1)

IPDU communication error

F04

TD sensor error

F06

TE sensor error

F07

TL sensor error

F08

TO sensor error

F12

TS sensor error

F13

TH sensor (Board installed) error

F15

Outdoor temp. sensor miswiring (TE, TL)

F16

Outdoor pressure sensor miswiring (Pd, Ps)

F23

Ps sensor error

F24

Pd sensor error

F31

Outdoor EEPROM error

H01

Compressor breaking down

H02

Compressor error (Locked)

H03

Current detection circuit error

H05

TD sensor miswiring

Inverter DC voltage error (on compressor)

P20

Decrease of number of indoor units

Phase missing / power failure detection

01: Compressor

P15

Auxiliary code
E06

00:

P13

Check code (indicated on the 7-segment display on the outdoor unit)


Indicated when SW01 = [1], SW02 = [1], and SW03 = [1].

Duplication of indoor units with priority

P03

Indication on 7-segment display on the outdoor unit

Check code name

Auxiliary code

7-Segment display and check code

Indication

Installation Manual

Outdoor Unit

Heat sink overheat error


Indoor overflow error
Outdoor unit flow back error detected
Gas leak detection

0:IGBT circuit
1: Position detection circuit error
3: Motor lock error
4: Motor current detected
C: TH sensor temp.error
D: TH sensor error
E: Inverter DC voltage error
(outdoor units fan)

4-way valve inverse error


High-pressure protective operation

Outdoor fan IPDU error


(NOTE)
Ignore 0-F appearing in the position of .

P26

G-TR short protection error

P29

Compressor position detecting circuit error

*1PDU number information


01:Compressor
08:Fan
09:Compressor and fan

EN

30

60-EN

+00EH99883601_00Ta.book

Page 61

Thursday, September 8, 2011

4:34 PM

WARNINGS ON REFRIGERANT LEAKAGE


Check of Concentration Limit
The room in which the air conditioner is to be installed
requires a design that in the event of refrigerant gas
leaking out, its concentration will not exceed a set limit.
The refrigerant R410A which is used in the air conditioner is
safe, without the toxicity or combustibility of ammonia, and is
not restricted by laws to be imposed which protect the ozone
layer. However, since it contains more than air, it poses the
risk of suffocation if its concentration should rise excessively.
Suffocation from leakage of R410A is almost non-existent.
With the recent increase in the number of high concentration
buildings, however, the installation of multi air conditioner
systems is on the increase because of the need for effective
use of floor space, individual control, energy conservation by
curtailing heat and carrying power etc.
Most importantly, the multi air conditioner system is able to
replenish a large amount of refrigerant compared with
conventional individual air conditioners. If a single unit of the
multi conditioner system is to be installed in a small room,
select a suitable model and installation procedure so that if
the refrigerant accidentally leaks out, its concentration does
not reach the limit (and in the event of an emergency,
measures can be made before injury can occur).
In a room where the concentration may exceed the limit,
create an opening with adjacent rooms, or install mechanical
ventilation combined with a gas leak detection device.
The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m3)
Concentration limit (kg/m3)

Important
NOTE 2 :

The standards for minimum room volume are as


follows.
(1) No partition (shaded portion)

(2) When there is an effective opening with the adjacent


room for ventilation of leaking refrigerant gas (opening
without a door, or an opening 0.15 % or larger than the
respective floor spaces at the top or bottom of the door).
Outdoor unit
Refrigerant piping
Indoor unit

(3) If an indoor unit is installed in each partitioned room and


the refrigerant piping is interconnected, the smallest
room of course becomes the object. But when a
mechanical ventilation is installed interlocked with a gas
leakage detector in the smallest room where the density
limit is exceeded, the volume of the next smallest room
becomes the object.
Refrigerant piping

The concentration limit of R410A which is used in multi air


conditioners is 0.30 kg/m3.
NOTE 1 :
If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should be as
charged in each independent device.

Outdoor unit
Very
small
room

Indoor unit
Small
room

Medium
room

Large room

Mechanical ventilation device - Gas leak detector


e.g., charged
amount (10 kg)

Outdoor unit
e.g.,
charged amount (15 kg)

NOTE 3 :
The minimum indoor floor area compared with the amount of
refrigerant is roughly as follows:
(When the ceiling is 2.7 m high)

m2
Room A Room B Room C Room D Room E Room F

EH99883601

Min. indoor floor area

Indoor unit

For the amount of charge in this example:


The possible amount of leaked refrigerant gas in rooms A,
B and C is 10 kg.
The possible amount of leaked refrigerant gas in rooms
D, E and F is 15 kg.

Range below the


of
20 density limit
0.30 kg/m3
(countermeasures
15 not needed)

10
5
0

Range above the


density limit of
0.30 kg/m3
(countermeasures
needed)

10
20
Total amount of refrigerant

kg

You might also like