User Manual - YCZ-A003 PDF
User Manual - YCZ-A003 PDF
0150511210-A
Content
Brief1
Explanation5
Operation instructions6
Installation and connections13
Troubleshooting18
3rd Party connection port19
Brief
Main features and functions
indoor
unit
indoor
unit
indoor
unit
indoor
unit
indoor
unit
indoor
unit
igu05
outdoor
unit
indoor
unit
indoor
unit
indoor
unit
indoor
unit
indoor
unit
indoor
unit
igu05
outdoor
unit
indoor
unit
indoor
unit
indoor
unit
indoor
unit
indoor
unit
indoor
unit
igu05
wired
controller
wired
controller
max 16 units
no.128 group
wired
controller
YCZ-A003
YCZ-A003
central controller
Brief
Part name and function explanation
Central controller YCZ-A003 Mainly design for Amazon series system.
Can control and monitor the indoor units condition ,maximum can control 128
groups ,each group can maximum connect to 16 indoor units. All the controls,
such as individual control ,zone control, time setting, timer setting etc. ,can be
realized by touch screen. Connecting diagram as follows:
Font cover
Colorful LCD
Group
NO.1 GROUP
wired controller
NO.2 GROUP
max 16
NO.3 GROUP
wired controller
wired controller
Use one wired controller controlled one or several sets(maximum 16) indoor
unit as one unit ,they use the same central control address ,the Central
controller think one unit.
Set one group only can use one mode control ,can*t control one set of the
group individually.
One group minimum has one set indoor unit, maximum 16 sets indoor units.
2
Brief
Zone
NO.1 GROUP
wired controller
NO.1 GROUP
wired controller
NO.2 GROUP
max 16
NO.3 GROUP
wired controller
wired controller
NO.2 GROUP
max 16
NO.3 GROUP
wired controller
wired controller
We can set several group with same function or near position as one zone.
We can control the whole zone ,also can control one group individually. Default
group can put into one corresponding zone.
Minimum one zone has one group ,maximum one zone can have 128 groups.
Brief
The indoor unit be checked will display in this page ,if one page can't display
all the units ,we can use page up/down button check .
use green color standard unit in operation ,use brown color standard for stop
unit ,use RED color standard for the unit with malfunction.
Zone display
Default design are: each indoor unit stay at the corresponding number zone,
such as No.1 unit stay no.1 zone ,No.2 unit stay at zone 2,No. 128 unit stay at
no.128 zone.
When the indoor unit in communications, the zone can be displayed.
When select one zone ,the right side condition frames will display the indoor
unit condition with smallest no. of this zone.
Explanation
Display and LCD explanation
menu
machine
no.
display
area
control
area
Button Explanation:
Monitor: Main View
Zone Setup: Zone set
Schedule Setup: Weekly timer setting
Unit->Zone: From Unit no. display change to Zone display
Zone-> unit: From Zone display to Unit no. display
Start All: All ON
Stop All: All OFF
Show Zone Schedule: Display the indoor unit no.
On/Off: Unit On/Off
Operation Mode: Operation mode and setting
Set Temperature: Temp. display and setting
Fan Speed: Fan speed display and setting
TC1 Temp: Indoor gas pipe temp.
TC2 Temp: Indoor liquid pipe temp.
Room Temp: Indoor real temp.
Error Code: Error code
OK: All the condition setting finished, press OK send out order;
Cancel: Cancel
Icons
grey: Operation
Brown :Stop
Red: malfunction
Operation instructions
Date and time setting
Press "set time", the timer setting interface will pop-up. adjust the year/month
/date and time by pressing the up/down button.
Operation instructions
Select the zone no. to be changes, press "change name",enter the zone name
interface.
Input name and press set ,then the setting finished, pls. notice: Maximum 12
letters permitted.
Control explanation
Individual indoor unit setting
Operation instructions
Set the indoor unit
Use ON/OFF to set start/stop the unit setting;
ON= Start the unit ,OFF=stop the unit ,No change=don't change the condition;
Use Mode to set the operation setting; Auto=auto, Heat=heating,
Cool=Cooling, Dry=dehumidify ,Fan =Airflow ; no change =don't change the
current mode, Use temp. to set the temperature(16~30degree),set no change
=don't change current temp, fan =set airflow speed, auto=auto, high=High
speed airflow ,middle =middle speed airflow, low=low speed airflow ,no
change=don't change the current airflow.
The date displayed is current setting condition.
Zone indoor unit setting
Operation instructions
Press the indoor unit to be controlled ,control the indoor unit from right size
frame, the control method is the same as individual control.
All the indoor unit setting
Press "All on",all the indoor units start to operation ,keep all the status before
start ,press "All off", stop all the indoor units ,the previous setting status don't
change.
Operation instructions
Schedule setting
Type : Select indoor no. setting or zone setting,. Select "zone"= setting as
zone, select "group"= setting as indoor unit no.
No: Zone no. or indoor unit No.
Setting: set timer setting method and indoor unit no. or zone no., select ""
before the day no. ,then set Time, ON/OFF,MODE, airflow speed, then press
ADD ,one setting will finished.
Edit: select the items to be edited ,right size frame will display all the
parameters, change the parameter ,then press Edit, the revise will be finished.
Delete :Select the items to be deleted, press "delete", the operation will be
finished.
10
Operation instructions
Zone Setting
11
Operation instructions
Off Power Clock setting
If power off time less than 192 hours, the internal time no need to reset;
If the power off time more than 192 hours ,the internal clock will stop , all the
time will disappear and need to reset the time.
Notice:
If the power off time more than 192 hours, and don't reset the clock ,the system
will supply wrong time schedule.
Press "Set time", the date setting interface will pop-up ,adjust the time by using
, button.
How to choice the 3 operation modes for connecting to Amazon-Unitary SmartMultiupgrade.
Switch on the unit
Select the desired operation mode in the window
Follow the indication to reboot the system (switch off the power supply).
12
Connecting board
Central controller
13
After connecting wirings, insert the central controller into the back cover ,open
the front cover , fix the central controller to the back cover by using 4 screws
according to the above pictures shows ,then cover the front cover.
Wiring Connection
220AC
Outdoor communication
terminal
with polarity
Outdoor communication
terminal
with polarity
Cautions:
Wrong connections that power supply leads to the part of PCB burned and fire
14
15
6
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
7
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
8
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Preserved
Preserved
Preserved
4
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
5
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
16
6
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
7
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
8
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Preserved
Preserved
Preserved
Wiring size
0.3mm2
0.5mm2
0.75mm2
1.25x2mm2
2x2mm2
And one end of the shield level must connect to the earth .
17
Troubleshooting
phenomenon
Reason
Solutions
Malfunction happens
because of static
electricity
Malfunction happens
because of static
electricity
18
connect to indoor
and outdoor
communication
wire P, Q
19
stop bit
checkout
data bit
baud rate
3rd Party
connection port
2 core screen wire
with polarity
connect to indoor
and outdoor
communication
wire P, Q
Connector:
L,N: power supply 220VAC 50HZ
GND: preset
PTC: preset
485B3 (B3) : preset
485A3 (A3) : preset
485B2 /BUS(B2) : connect to indoor P,Q
485A2 /BUS (A2) : connect to indoor P,Q
485B1 (B1) : connect to YCZ-A003 485B1
485A1 (A1) : connect to YCZ-A003 485A1
Function:
protocol transfer: -----home bus transfer to 485
Home bus: 2400bps and 9600bps baud rate, you need restart the power
supply after change the baud rate
485: 9600bps
1: One outdoor system need use one IGU05
2: One central controller can connect 32 piece of IGU05 maximum
3: If only have one outdoor system also need connect IGU05
20
connect IGU05
baud rate
data bit
checkout
stop bit
Connector definition:
L,N: power supply 220VAC 50HZ
GND: preset
PTC: preset
485B3 (B3) : preset
485A3 (A3) : preset
485B2 /BUS(B2) : connect to exterior equipment "-"
485A2 /BUS (A2) : connect to exterior equipment "+"
485B1 (B1) : connect to IGU05 485B1
485A1 (A1) : connect to IGU05 485A1
Function:
1. control-single unit control, zone control, total control
2. zone setting and zone naming
3. weekly timer-can set single unit ,zone ,total unit
4. the exterior equipment modbus rtu connector
The exterior equipment connector slave address default:1
21
description
protocol
protocol
annex type state1
address
address
40005
DO
Total open/close
40005
setting
DO
preset
preset
40005
DI
preset
40005
DI
preset
40005
preset
40005
preset
40005
preset
40005
preset
40005
10
preset
40005
11
preset
40005
10
12
preset
40005
11
13
preset
40005
12
14
preset
40005
13
15
preset
40005
14
16
preset
40005
15
0:
close
22
1:
open
remark
state4
remark
No.
description
17
No.1 indoor
mode setting
40006
AO
0:
auto
1:
fan
2:
4:
3:
read/write
cooling dehumidify heating
18
No.2 indoor
mode setting
40007
AO
0:
auto
1:
fan
2:
4:
3:
read/write
cooling dehumidify heating
19
No.3 indoor
mode setting
40008
AO
0:
auto
1:
fan
2:
4:
3:
read/write
cooling dehumidify heating
20
No.4 indoor
mode setting
40009
AO
0:
auto
1:
fan
2:
4:
3:
read/write
cooling dehumidify heating
21
No.5 indoor
mode setting
40010
AO
0:
auto
1:
fan
3:
2:
4:
read/write
cooling dehumidify heating
23
No.125 indoor
40130
mode setting
AO
0:
auto
1:
fan
2:
4:
3:
read/write
cooling dehumidify heating
24
No.126 indoor
40131
mode setting
AO
0:
auto
1:
fan
3:
2:
4:
read/write
cooling dehumidify heating
25
No.127 indoor
40132
mode setting
AO
0:
auto
1:
fan
2:
4:
3:
read/write
cooling dehumidify heating
26
No.128 indoor
40133
mode setting
AO
0:
auto
1:
fan
2:
4:
3:
read/write
cooling dehumidify heating
27
AO
16-30
28
AO
16-30
29
AO
16-30
30
AO
16-30
31
AO
16-30
33
No.125 indoor
40258
set temperature
AO
16-30
34
No.126 indoor
40259
set temperature
AO
16-30
35
No.127 indoor
40260
set temperature
AO
16-30
22
32
23
description
protocol
protocol
annex type state1
address
address
state2
state3
state4
remark
36
No.128 indoor
40261
set temperature
AO
37
AO
0:
auto
read/write
38
AO
0:
auto
read/write
39
AO
0:
auto
read/write
40
AO
0:
auto
read/write
41
AO
0:
auto
read/write
43
AO
0:
auto
read/write
44
AO
0:
auto
read/write
45
AO
0:
auto
read/write
46
AO
0:
auto
read/write
16-30
42
47
No.1 indoor
ambient
temperature
40390
AI
only read
48
No.2 indoor
ambient
temperature
40391
AI
only read
49
No.3 indoor
ambient
temperature
40392
AI
only read
50
No.4 indoor
ambient
temperature
40393
51
No.5 indoor
ambient
temperature
40394
52
24
remark
No.
description
53
No.125 indoor
ambient
temperature
40514
54
No.126 indoor
ambient
temperature
40515
55
No.127 indoor
ambient
temperature
40516
56
No.128 indoor
ambient
temperature
40517
57
No.1 indoor
on/off
40518
DI
0: off
1: on
read/write
58
No.2 indoor
on/off
40518
DI
0: off
1: on
read/write
59
No.3 indoor
on/off
40518
DI
0: off
1: on
read/write
60
No.4 indoor
on/off
40518
DI
read/write
61
No.5 indoor
on/off
40518
DI
read/write
63
No.125 indoor
on/off
40525
12
64
No.126 indoor
on/off
40525
13
65
No.127 indoor
on/off
40525
14
66
No.128 indoor
on/off
40525
15
67
No.1 indoor
error
40526
0:
normal
1:
error
only read
68
No.2 indoor
error
40526
0:
normal
1:
error
only read
69
No.3 indoor
error
40526
0:
normal
1:
error
only read
62
25
description
protocol
protocol
annex type state1
address
address
remark
70
No.4 indoor
error
40526
DI
only read
71
No.5 indoor
error
40526
DI
only read
73
No.125 indoor
error
40533
12
74
No.126 indoor
error
40533
13
No.127 indoor
error
40533
14
76
No.128 indoor
error
40533
15
77
AI
only read
78
AI
only read
79
AI
only read
80
AI
only read
81
AI
only read
83
No.125 indoor
40662
TC1 temperature
AI
only read
84
No.126 indoor
40663
TC1 temperature
AI
only read
85
No.127 indoor
40664
TC1 temperature
AI
only read
86
No.128 indoor
40665
TC1 temperature
AI
only read
87
AI
only read
88
No.2 indoorTC2
40667
temperature
AI
only read
72
82
26
description
protocol
protocol
annex type state1 state2 state3 state4
address
address
remark
89
AI
only read
90
AI
only read
91
AI
only read
93
No.125 indoor
40790
TC2 temperature
AI
only read
94
No.126 indoor
40791
TC2 temperature
AI
only read
No.127 indoor
95 TC2 temperature 40792
AI
only read
No.128 indoor
40793
TC2 temperature
AI
only read
92
96
27
slave address: 1
1.total on/off
central control mode setting
total on/off setting
40005
DO
0: off
1: on
28
read/write
AO
0:
1: 2:
3:
4:
read/write
auto fan cooling dehumidify heating
29
40134
AO
16-30; write
40135
AO
16-30; write
30
AO
2:
1:
3:
0:
auto low speed middle speed high speed
No.2 fan
40263
speed set
AO
2:
1:
3:
0:
auto low speed middle speed high speed
No. 3indoor high speed*the same as wired controller display. Fan speed
display and set ok.
31
32
1: on
read/write
No.2 indoor
40518 0 DI 0: off
on/off state
1: on
read/write
No.3 indoor
40518 0 DI 0: off
on/off state
1: on
read/write
33
1:
error
only read
0:
No.2 indoor
40526 1 DI
normal
error
1:
error
only read
0:
No.3 indoor
40526 2 DI
normal
error
1:
error
only read
34
www.johnsoncontrols.com
Doc. No.130704
Johnson Controls reserve the right to change product features without prior notice.