USER'S GUIDE FOR
CARRIER SA ECG-UG-00-001 Page:2 /89
30GX & 30 HX PRO_DIALOG 4 Rev: Original
CONTENTS
1 - INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 - About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 4.2.4.7 - Service 4 configuration from Service
1.2 - Manual Structure and contents . . . . . . . . . . . . . . . . . 4 Tool . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.2.4.8 - Service 4 configuration from Main
2 - GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . 4 Interface, runtime sub menu . . . . . 31
2.1 - Generalities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 - Software Reference Number . . . . . . . . . . . . . . . . . . 7
2.3 - Abbreviations Used . . . . . . . . . . . . . . . . . . . . . . . . . . 7 4.2.5 - User Configuration . . . . . . . . . . . . . . . . . . . . 32
© CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER
ORGANIZATION
USER'S GUIDE FOR
CARRIER SA ECG-UG-00-001 Page:3 /89
30GX & 30 HX PRO_DIALOG 4 Rev: Original
CONTENTS
6 - CCN COMPATIBILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
© CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER
ORGANIZATION
USER'S GUIDE FOR
CARRIER SA ECG-UG-00-001 Page: 4/89
30GX & 30 HX PRO_DIALOG 4 Rev: Original
1 - INTRODUCTION
1.1 - ABOUT THIS MANUAL
This manual is intended to be used as an additional guide for using and configuring the Pro-Dialog control for
the 30GX & HX chillers. The use of this document does not substitute the IOM.
This manual is intended for use by Service organizations inside the Carrier corporation. It is delivered
on the express condition that it is not to be disclosed, reproduced in whole or in part, or used for
manufacture by anyone other than Carrier Corporation.
The hardware section provides complete information on boards, devices and connections used by the product.
The control description section is divided in several subsections. First provides a main description of hardware
configuration. This subsection provides sufficient information to runs the control in the most operating cases.
For more complete information, use the remaining sections and also IOM. Second subsection describes all the
unit configuration and the methods to modify it. The last subsections describe the unit control logic’s.
2 - GENERAL DESCRIPTION
2.1 - GENERALITIES
Safety circuits in the unit are constantly monitored by PRO-DIALOG to ensure its safe operation. PRO-DIALOG
also gives access to a Quick Test program covering all inputs and outputs excepted compressors outputs.
The control features of the 30GX&HX Pro-Dialog Plus are divided into standard features and options
(additional board needed):
© CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER
ORGANIZATION
USER'S GUIDE FOR
CARRIER SA ECG-UG-00-001 Page: 5/89
30GX & 30 HX PRO_DIALOG 4 Rev: Original
Standard features:
Z Local control
Z CCN control
Z Compressor & loader sequence control (up to 4 compressors - two loaders per compressor)
Z Ramp loading
Z Delay at startup
Z Temperature reset
Z Diagnostics function
Z Alarm POC
Z Reclaim sensors
© CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER
ORGANIZATION
USER'S GUIDE FOR
CARRIER SA ECG-UG-00-001 Page: 6/89
30GX & 30 HX PRO_DIALOG 4 Rev: Original
© CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER
ORGANIZATION
USER'S GUIDE FOR
CARRIER SA ECG-UG-00-001 Page: 7/89
30GX & 30 HX PRO_DIALOG 4 Rev: Original
CSA-SR-208410XX
The two last digits (XX) provides the software version (e.g. 1.0).
15 digits reference number can be displayed in the CCN configuration Ctrl_ID table through the Building
Supervisor, the Network Service Tool or the 30GX&HX Downloader.
Unit Main Interface Configuration Menu allows to display the software version: item #13, user 1 menu.
In this manual, the refrigeration circuits are called circuit A and circuit B. The compressors in circuit A are
labeled A1, and A2. Those in circuit B are B1 and B2.
3 - HARDWARE DESCRIPTION
COMPONENT USAGE
UNIT TYPE : AIR COOLED - MORE THAN 2 FAN STAGES PER CIRCUIT
NUMBER OF
COMPONENTS COMPRESSORS
2 3 4
PD4 - BASIC BOARD 1 1 1
PD4 - SCPM BOARD 2 3 4
PD4 - EXV BOARD 1 1 1
4x DO BOARD 2 2 2
NRCP BASIC BOARD 1 ** 1 ** 1 **
4 x AI-2xAO BOARD 1* 1* 1*
* - additional 4 x AI - 2 x AO board is required for varifan or reclaim sensors or water valve option or
split system
** additional NRCP board is required for reclaim option or cooler heater option.
© CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER
ORGANIZATION
USER'S GUIDE FOR
CARRIER SA ECG-UG-00-001 Page: 9/89
30GX & 30 HX PRO_DIALOG 4 Rev: Original
The PD4 - Basic board is 24VAC power supplied. It contains 8 Discrete Inputs (Switch type), 8 Digital Outputs
(5 triacs and 3 relays), 10 Analog Inputs (five thermistors and four pressure transducers) and 1 analog input
(0-10 Vdc) . See the schemes in Appendix E. The software is contained in a Flash EPROM (downloadable only
with Downloader). All the setpoints, runtime and configuration parameters are contained in an EEPROM (data
storage at power down).
analog inputs
© CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER
ORGANIZATION
USER'S GUIDE FOR
CARRIER SA ECG-UG-00-001 Page: 10/89
30GX & 30 HX PRO_DIALOG 4 Rev: Original
J4 & J5 15 a & 15 b Cooler flow switch & customer interlock (lock_1) All
J5 16 a & 16 b Electrical box thermostat & network power reverse phase All
detection
J3 26 Unused All
The PD4 - Global chiller controller has a small option board that can be connected to the Basic Board via a
single 10 pin header and 4 metal standoff. This option board contains one RS-485 driver for CCN
communication, a real time clock and super cap for two weeks backup. There are two connectors for CCN. One
is a 3 pin screw connector ( 1= + signal, 2 = ground signal, 3 = - signal) and the other is a 6 pins phone jack.
© CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER
ORGANIZATION
USER'S GUIDE FOR
CARRIER SA ECG-UG-00-001 Page: 11/89
30GX & 30 HX PRO_DIALOG 4 Rev: Original
This board shall monitor compressor pressure transducer, temperature sensors, oil level, high pressure switch,
motor cooling solenoids, oil pumps, motor current, compressor wye-delta startup and compressor protection.
© CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER
ORGANIZATION
USER'S GUIDE FOR
CARRIER SA ECG-UG-00-001 Page: 12/89
30GX & 30 HX PRO_DIALOG 4 Rev: Original
N.B :Only Y dip switch of the 4 is used to configure start-delta startup procedure (when in
ON position), the 3 others shall remain OFF ! If not, MTA header configuration alarm will
occur.
© CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER
ORGANIZATION
USER'S GUIDE FOR
CARRIER SA ECG-UG-00-001 Page: 13/89
30GX & 30 HX PRO_DIALOG 4 Rev: Original
The 4xDO board has 4 digital outputs capable of switching 24 VAC at 1 amp numbered from 1 to 4 on
connector J4. They have a common point numbered 12 on connector J4.
D0 #1 shall support 1 fan
D0 #2 shall support 1 fan
D0 #3 shall support 1 fan if circuit has less than 5 fans. It shall support 2 fans if circuit has more than 4 fans.
D0 #4 shall support 1 fan if circuit has less than 6 fans. It shall support
2 fans if circuit has 6 fans.
Control LEDs
Address Selector
4xDO BOARD
© CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER
ORGANIZATION
USER'S GUIDE FOR
CARRIER SA ECG-UG-00-001 Page: 14/89
30GX & 30 HX PRO_DIALOG 4 Rev: Original
DO #1 TO CONTACTOR # 1
DO #2 TO CONTACTOR # 2
DO #4 TO OTHER CONTACTORS
11 12 12 4 3 2 1 TERMINAL J4
24 VAC DO
POWER SUPPLY
TRIAC
pins 12 are connected together
TRIAC
TRIAC
TRIAC
© CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER
ORGANIZATION
USER'S GUIDE FOR
CARRIER SA ECG-UG-00-001 Page: 15/89
30GX & 30 HX PRO_DIALOG 4 Rev: Original
The EXV board shall be able to drive both unipolar and bipolar stepper motors via a common connector. The
default configuration shall be unipolar, 30 steps/s step rates and 1500 steps range such as to allow easy retrofit
with Pro-Dialog phase 1, 2 and 3 units fitted with Mueller Brass EXV’s. It shall be able to handle 12V @ 0.5 A
per coil and maintain a step rate of at least 200 steps per second (unipolar or bipolar).
Note: board shall be able to handle a total coil load of 1 Amp for unipolar and 2 Amps for bipolar.
Connection to the EXV shall be done through two Molex, 5 pin, 3.91 pitch (one per EXV) [J2A & J2B].
© CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER
ORGANIZATION
USER'S GUIDE FOR
CARRIER SA ECG-UG-00-001 Page: 16/89
30GX & 30 HX PRO_DIALOG 4 Rev: Original
This board provides 4 analog inputs (labeled AI #1, AI #2, AI #3, and AI #4 on the terminal J2) and 2 analog
outputs (labeled AO #1 and AO #2 on the terminal J1). It allows to use the following features:
Z Optional reclaim thermistors when reclaim option is not used
Z Remote discharge transducer on remote condenser on split units.
Z Optional varifan on air cooled units or water valve on water cooled units
Each input can be independently configured with a bridge allowing to close 3 pair of pins named T,C or V.
J2
C unused 1-R 1: +
R: -
C unused 1-R 1: +
R: -
© CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER
ORGANIZATION
USER'S GUIDE FOR
CARRIER SA ECG-UG-00-001 Page: 17/89
30GX & 30 HX PRO_DIALOG 4 Rev: Original
Each output can be independently configured with a bridge allowing to close 2 pair of pins named C or V.
J1
ANALOG BRIDGE FUNCTION PINS REMARKS
OUTPUT POSITION
Address Selector
Control LEDs
SIO Bus
4xAI-2xAO BOARD
© CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER
ORGANIZATION
USER'S GUIDE FOR
CARRIER SA ECG-UG-00-001 Page: 18/89
30GX & 30 HX PRO_DIALOG 4 Rev: Original
This board is used on global chiller as slave board for air cooled units with reclaim option or cooler heater
option. It contains 8 Discrete Inputs (switch type), 10 Digital Outputs (8 triacs and 2 relays), 6 Analog Inputs
(four 5K or 10K thermistors and two active pressure transducer types) and 1 analog output (0-10 Vdc).
© CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER
ORGANIZATION
USER'S GUIDE FOR
CARRIER SA ECG-UG-00-001 Page: 19/89
30GX & 30 HX PRO_DIALOG 4 Rev: Original
Z Suction pressure
Z Economizer pressure
Z Economizer pressure on first compressor and also in the second compressor if unit is not equipped
with economizer
They are electronic sensors which linearise the output signal and deliver a 0 to 5 Vdc to either the basic board
or to an analog board. Three types of sensors are used.
They are used to measure discharge pressure and oil pressures when large band oil pressure transducer is not
selected. Carrier part: OP12DA039
4
Voltage (VDC)
0 50 100 150 200 250 300 350 400 450 500 PSI
345 689 1034 1379 1724 2068 2414 2758 3103 3447 kPa
Pressure
They are used to measure oil pressures for unit operating with low ambient (when large band oil pressure
transducer is selected). Carrier part: OP12DA057
4
Voltage (VDC)
-6.6 50 100 155 215 276 327 387 420 500 PSI
-45 345 689 1068 1484 1904 2252 2670 2895 3447 kPa
Pressure
© CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER
ORGANIZATION
USER'S GUIDE FOR
CARRIER SA ECG-UG-00-001 Page: 20/89
30GX & 30 HX PRO_DIALOG 4 Rev: Original
These are in the low pressure side. Suction pressure transducer takes the place of the low pressure switches,
low pressure gauges and the low pressure safety switch (where these are usually fitted). Economizer pressure
is used to measure the intermediary pressure between low and high pressure. The oil pressure is subtracted
from this pressure to determine the oil differential pressure for oil pressure safety purpose.
4
Voltage (VDC)
3.3 - THERMISTORS
All thermistor, excepted the reset sensor, have similar characteristics (see next page).
They have Carrier Part No. HH 79 NZ 047
This is installed on the discharge pipe of each compressor. It is used to control the discharge superheat. The
discharge gas temperature (lowest discharge compressor temperature or average discharge temperature of
both compressors) is subtracted to the saturated condensing temperature to determine the discharge
superheat.
© CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER
ORGANIZATION