Carlyle 104mm Screw-Refrig
Carlyle 104mm Screw-Refrig
Carlyle 104mm Screw-Refrig
131
CARLYLE REFRIGERATION COMPRESSORS
GENERAL NOTES on Refrigeration Screw Compressors 05T & 06T
Compressors are shipped with service valves attached to the compressor pallet and have blankoff pads bolted over service valve open-
ings. Alternate suction and discharge service valves are available.
All 06T screw compressors are suitable for across-the-line or part winding start. Customer is required to hook up terminal plate for appli-
cable voltage. Wiring diagrams and jumpers are included in the compressor terminal box. Compressor part number on nameplate is the
same as the package ordering number.
Carlyle requires the following accessories to protect both 05T and 06T compressors:
- oil separator - oil level switch
- oil filter housing - reverse rotation protection switch
- oil pressure differential switch - Carlyle Electronic Module
- high pressure switch - low pressure switch
The 06T Compressor further requires:
- C-Flange - coupling
06T screw compressors provided WITHOUT motor overcurrent protection, which MUST be supplied by the customer. Heinemann cali-
brated circuit breakers specifically selected for each motor and voltage are a required accessory. All 06T compressor models are UL and
CSA approved. The use of authorized overcurrent protection is part of UL recognition.
All 06T compressors are provided with a 5K thermistor installed in the compressor motor to monitor the motor temperature. The CEM is
required with each 06T to monitor this thermistor.
All compressors are painted green.
132
CARLYLE REFRIGERATION COMPRESSORS
05T (74 mm) SCREW COMPRESSOR
P3036
133
CARLYLE REFRIGERATION COMPRESSORS
OPEN DRIVE MODELS - For All Temperature Ranges With Service Valves
DISPLACEMENT (CFM) APPROX.
MOTOR
MODEL NO. 1750 RPM 3500 RPM SHIP. WEIGHT
HP
Motor (4 pole) Motor (2 pole) (kg)
05TRQ033Z3EA-A00 33 65 N/A 91
05TRQ039Z3EA-A00 39 78 N/A 91
05TRQ044Z3EA-A00 44 88 N/A 91
05TRQ048Z3EA-A00 48 N/A N/A 91
05TRQ054Z3EA-A00 54 N/A N/A 91
134
CARLYLE REFRIGERATION COMPRESSORS
06T SCREW COMPRESSOR
P3035
CAPACITY (Btu/Hr) @ 60 Hz
Refrigerant R-22 R-507/404A R-22 R-507/404A R-134a
Conditions -25/110/65 -25/110/65 20/110/65 20/110/65 45/130/65
06T**033 51,000 70,900 131,500 143,100 127,900
06T**039 62,700 86,100 161,000 175,000 156,800
06T**044 72,100 98,900 182,800 199,000 177,700
06T**048 80,100 11,000 203,100 221,100 194,300
06T**054 91,900 126,100 233,100 253,700 222,800
06T**065 113,900 156,400 292,500 318,400 284,100
06T**078 140,200 192,000 354,300 385,700 342,400
06T**088 159,800 218,700 400,900 436,300 387,500
Economized (F).
135
CARLYLE REFRIGERATION COMPRESSORS
COMPRESSOR PHYSICAL DIMENSIONS
P3031 P3032
P3033
136
CARLYLE REFRIGERATION COMPRESSORS
LOW TEMPERATURE DUTY - Semi-Hermetic With Service Valves
VOLTAGE APPROX.
MOTOR
MODEL NO. 3 PHASE SHIP. WEIGHT
HP
60 HZ 50 HZ (kg)
06TRC033B2EA-A00 460 400
F2EA-A00 208/230 200 15 166
C2EA-A00 575 -
06TRD039B2EA-A00 460 400
F2EA-A00 208/230 200 20 172
C2EA-A00 575 -
06TRD044B2EA-A00 460 400
F2EA-A00 208/230 200 20 172
C2EA-A00 575 -
06TRE048B2EA-A00 460 400
F2EA-A00 208/230 200 25 177
C2EA-A00 575 -
06TRE054B2EA-A00 460 400
F2EA-A00 208/230 200 25 177
C2EA-A00 575 -
06TRF065B2EA-A00 460 400
F2EA-A00 208/230 200 30 181
C2EA-A00 575 -
06TRG078B2EA-A00 460 400
F2EA-A00 208/230 200 35 184
C2EA-A00 575 -
06TRH088B2EA-A00 460 400
F2EA-A00 208/230 200 40 184
C2EA-A00 575 -
06TRK108B2EA-A00
n/a 400 50 186
NOTE: 50Hz Applications Only
137
CARLYLE REFRIGERATION COMPRESSORS
MEDIUM/HIGH TEMPERATURE DUTY - Semi-Hermetic With Service Valves
VOLTAGE APPROX.
MOTOR
MODEL NO. 3 PHASE SHIP. WEIGHT
HP
60 HZ 50 HZ (kg)
06TAD033B2EA-A00 460 400
F2EA-A00 208/230 200 20 164
C2EA-A00 575 -
06TAE039B2EA-A00 460 400
F2EA-A00 208/230 200 25 171
C2EA-A00 575 -
06TAF044B2EA-A00 460 400
F2EA-A00 208/230 200 30 171
C2EA-A00 575 -
06TAF048B2EA-A00 460 400
F2EA-A00 208/230 200 30 176
C2EA-A00 575 -
06TAG054B2EA-A00 460 400
F2EA-A00 208/230 200 35 176
C2EA-A00 575 -
06TAG065B2EA-A00 460 400
F2EA-A00 208/230 200 35 180
C2EA-A00 575 -
06TAH078B2EA-A00 460 400
F2EA-A00 208/230 200 40 182
C2EA-A00 575 -
06TAK088B2EA-A00 460 400
F2EA-A00 208/230 200 50 187
C2EA-A00 575 -
138
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
05T/06T REFRIGERATION COMPRESSOR ACCESSORIES
ELECTRONIC PHASE MONITOR (REVERSE ROTATION PROTECTION)
(See Notes Below)
PART NO. QTY/PKG WEIGHT (kg) USAGE
P251-0090 1 1.5 ALL 05/6T compressors
NOTES:
1. Protects screw compressor from reverse rotation by monitoring 3-phase input power to compressor motor. Will not allow compressor to start if
sequence is incorrect.
2. This phase monitor will not operate with a variable speed drive inverter.
3. May be used in place of reverse rotation switch; (1) per compressor.
MUFFLERS
(1 Per Compressor Required)
PART NO. QTY/PKG WEIGHT (kg) INLET/OUT LENGTH USAGE
All 05/6T
LM10HH162 1 3 1-5/8 9-3/4
compressor
OIL SEPARATORS
(1 Per Rack Required)
PART NO. MOUNTING LINE SIZE (0. WT (kg) DIA. USAGE
KH31ZZ340 VERTICAL 2-1/8 66 12 Single Comp.
KH31ZZ212 VERTICAL 2-5/8 120 14 Multiple Comp.
NOTES:
1. Oil Separators supplied with multiple sight glasses to view oil level.
2. Oil Separators has adapter fitting at bottom to connect KH13LB004 Oil Level Float Switch.
139
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
05T/06T REFRIGERATION COMPRESSOR ACCESSORIES
OIL LEVEL SWITCH
(1 Per Oil Separator Required)
PART NO. QTY/PKG WEIGHT (kg) USAGE
HK13LB004 1 0.5 On vertical oil separators
NOTE:
1. Protects compressor against loss of oil in Oil Separator. Screws into bottom.
NOTE:
1. Heater applied to oil separator to keep refrigerant from accumulating in it during off cycles.
See application guide for application requirements.
NOTES:
1. Oil Housing which allows replacement of filter cartridge.
2. Filter Housing assembly includes (1) 3 micron filter cartridge.
3. (2) per rack recommended.
140
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
05T/06T REFRIGERATION COMPRESSOR ACCESSORIES
OIL FILTER CARTRIDGE
PART NO. QTY/PKG WEIGHT (kg) USAGE
KH39MG002 1 0.5 Replacement Cartridge for KH18MG002 housing
NOTE:
1. Carlyle recommends (3) cartridges be left at the job site per oil filter housing. Several changeouts will be necessary before the system is free of
contaminant. If the job is a remodel, more changeouts may be necessary.
2. Each cartridge is supplied with (1) filter housing O ring.
DESUPERHEATING
(1 Per Compressor for R-22 <-32 C & R-404A/R507 <-43C SST Systems)
PART NO. QTY/PKG WEIGHT (kg) SIZE USAGE
EA02ZD001 1 1 1 ton
EA02ZD002 1 1 1.5 ton All 05/6T
EA02ZD030 1 1 2 ton Compressors
EA02ZD050 1 1 3 ton
EA02ZD100 1 1 5 ton
NOTES:
1. Solenoid Coil operates either capacity control unloading mechanism or variable volume (Vi) control.
2. 06TR Models require (2) per compressor, 06TA models require (1) per compressor.
NOTES:
1. Module uses (2) 5K Thermistors, (1) embedded in motor windings and (1) strapped on discharge line (thermistor purchased separately.)
2. The modules control motors and discharge cooling and acts as a safety for overheating protection.
141
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
05T/06T REFRIGERATION COMPRESSOR ACCESSORIES
5K THERMISTOR
(1 Per Compressor Required)
PART NO. QTY/PKG WEIGHT (kg) ELECTRICAL USAGE
HH79NZ065 1 0.5 115/240-1-60 All 05/6T Compressors
NOTE: One required per compressor for use with CEM to monitor discharge temperature.
NOTE: Used for motor and discharge gas cooling of screw compressors.
142
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
05T/06T REFRIGERATION COMPRESSOR ACCESSORIES
OIL PRESSURE DIFFERENTIAL SWITCH(1 Per Compressor Required)
VOLTAGE
PART NO. QTY/PKG WEIGHT (kg) CONNECTION USAGE
INPUT
HK06ZB006 1 2 1/4 FLARE 115 or 230 ALL 05/6T compressors
NOTES:
1. Senses oil differential between discharge pressure and oil feed to the compressor.
2. Switch setting is for cutout when differential pressure above (45 psid) and has a 30 second time delay.
NOTES:
1. Senses oil differential across filters.
2. Switch setting is for cutout when differential pressure exceeds 45 psid and has a 30 second time delay.
NOTES:
1. (2) 06TA660001 packages are supplied with each compressor.
2. All service Valve are 4 bolt, 2-1/2 square bolt spacing. Service Valve Package contains (1) service valve (1) gasket, and (4) metric hex
head cap screws (M12 x 1,75 x 60mm).
3. These Service Valve packages (except 06TA68005) are the same as the respective 06D/E packages except the mounting bolts have
metric threads.
NOTES:
1. (1) 06TA660004 package is supplied with each compressor.
2. All Economizer Service Valve contain (1) Rotalock * valve, (1) O-ring, (1) seal, and (1) connection fitting.
143
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
06T REFRIGERATION COMPRESSOR ACCESSORIES
CALIBRATED CIRCUIT BREAKERS
(1 Per 06T Compressor)
COMPRESSOR VOLTAGE
QTY/PKG WEIGHT (kg) CIRCUIT BREAKER
MODULE USAGE 3 PHASE
06TRC033B2EA-A00 460-3-60 & 400-3-50 2 HH83XA463
F2EA-A00 230-3-60 & 200-3-50 1 2 HH83XB356
C2EA-A00 575-3-60 2 HH83XA460
06TRD039B2EA-A00 460-3-60 & 400-3-50 2 HH83XA424
F2EA-A00 230-3-60 & 200-3-50 1 2 HH83XB336
C2EA-A00 575-3-60 2 HH83XA461
06TRD044B2EA-A00 460-3-60 & 400-3-50 2 HH83XA424
F2EA-A00 230-3-60 & 200-3-50 1 2 HH83XB336
C2EA-A00 575-3-60 2 HH83XA461
06TRE048B2EA-A00 460-3-60 & 400-3-50 2 HH83XA426
F2EA-A00 230-3-60 & 200-3-50 1 3 HH83XC509
C2EA-A00 575-3-60 2 HH83XA469
06TRE054B2EA-A00 460-3-60 & 400-3-50 2 HH83XA426
F2EA-A00 230-3-60 & 200-3-50 1 3 HH83XC509
C2EA-A00 575-3-60 2 HH83XA469
06TRF065B2EA-A00 460-3-60 & 400-3-50 2 HH83XA474
F2EA-A00 230-3-60 & 200-3-50 1 3 HH83XC573
C2EA-A00 575-3-60 2 HH83XB617
06TRG078B2EA-A00 460-3-60 & 400-3-50 2 HH83XA476
F2EA-A00 230-3-60 & 200-3-50 1 3 HH83XC574
C2EA-A00 575-3-60 2 HH83XB618
06TRH088B2EA-A00 460-3-60 & 400-3-50 2 HH83XA476
F2EA-A00 230-3-60 & 200-3-50 1 3 HH83XC575
C2EA-A00 575-3-60 2 HH83XB619
06TRK108B2EA-A00 400-3-50 1 2 HH83XA477
NOTES:
1. Circuit breaker selections are based on across-the-line start.
2. Overcurrent protection required per General Note.
3. Heinemann circuit breaker not required with 05T compressor.
144
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
06T REFRIGERATION COMPRESSOR ACCESSORIES
CALIBRATED CIRCUIT BREAKERS
(1 Per 06T Compressor)
COMPRESSOR VOLTAGE
QTY/PKG WEIGHT (kg) CIRCUIT BREAKER
MODULE USAGE 3 PHASE
06TAD033B2EA-A00 460-3-60 & 400-3-50 4 HH83XA424
F2EA-A00 230-3-60 & 200-3-50 4 HH83XB336* or
1
HH83XB625
C2EA-A00 575-3-60 4 HH83XA461
06TAE039B2EA-A00 460-3-60 & 400-3-50 4 HH83XA426
F2EA-A00 230-3-60 & 200-3-50 1 4 HH83XC509
C2EA-A00 575-3-60 4 HH83XA469
06TAF044B2EA-A00 460-3-60 & 400-3-50 4 HH83XA425
F2EA-A00 230-3-60 & 200-3-50 1 4 HH83XC539
C2EA-A00 575-3-60 4 HH83XA430
06TAF048B2EA-A00 460-3-60 & 400-3-50 4 HH83XA425
F2EA-A00 230-3-60 & 200-3-50 1 4 HH83XC539
C2EA-A00 575-3-60 4 HH83XA430
06TAG054B2EA-A00 460-3-60 & 400-3-50 4 HH83XA547
F2EA-A00 230-3-60 & 200-3-50 1 4 HH83XC532
C2EA-A00 575-3-60 4 HH83XA453
06TAG065B2EA-A00 460-3-60 & 400-3-50 4 HH83XA475
F2EA-A00 230-3-60 & 200-3-50 1 6 HH83XC574
C2EA-A00 575-3-60 4 HH83XB618
06TAH078B2EA-A00 460-3-60 & 400-3-50 4 HH83XA476
F2EA-A00 230-3-60 & 200-3-50 1 6 HH83XC575
C2EA-A00 575-3-60 4 HH83XB619
06TAK088B2EA-A00 460-3-60 & 400-3-50 4 HH83XA477
F2EA-A00 230-3-60 & 200-3-50 1 6 HH83XC576
C2EA-A00 575-3-60 4 HH83XB610
*These breakers are supplied without compression lugs. Customer must provide connectors or use our Power Terminal Parts Connectors for HH83XB
Circuit Breakers shown below.
NOTES:
1. Circuit breakers selections are based on across-the-line start.
2. Overcurrent protection required per General Note.
3. Heinemann circuit breaker not required with 05T compressor.
HH83XB series circuit breakers require customer supplied power wire connections at circuit breaker.
Kit includes ring terminal, cap screws and lock washers. Not required for XA, XC, C or B series circuit breakers.
Package Contents: (6) Ring Terminal to connect power wiring to compressor terminal studs, plus (3) spare (2-hole) jumper bars.
145
CARLYLE REFRIGERATION COMPRESSORS
GUIDE TO 06D PART NUMBERING SYSTEM:
VARIABLES
NOTES:
1. SPECIAL ORDER SERVICE COMPRESSORS FOR BRYANT
CHARACTERISTIC
VORELOADS & INTERNAL
MAY BE PROCESSED AS 9 NAMEPLATED 6 (8TH DIGIT).
FUTURE DESIGN
DISPLACEMENT
COVER ORIENTATION
KEY NUMBER
ELECTRICAL
PRODUCT
VARIATIONS
VARIATIONS
VARIATIONS
PACKAGING
A, C AND E ORIGINAL EQUIPMENT MODELS AND D
VARIABLES
UNLOADER
SERIES SERVICE MODELS REPLACE 8 & F MODELS. TERMINAL
THERMOSTAT
MOTOR
BOXES AND OVERLOADS ARE TO BE RE-USED OR
REPLACED IF DAMAGED.
SIZE
CFM
3. 09 IN THE 11TH & 12TH DIGITS HAS BEEN USED IN THE
MODEL 0 6 D A 3 1 6 0 0 A 3 2 0 0 PAST FOR 400-3-50 MOTORS AND IS NO LONGER USED, SO
AS TO AVOID CONFUSION IN SERVICE THESE DIGITS ARE
VARIABLE DIGIT I 2 3 4 5 6 7 8 9 10 11 12 13 14 TO BE LEFT ON THIS CHART BUT ARE NOT TO BE RE-USED.
146
CARLYLE REFRIGERATION COMPRESSORS
06D REFRIGERATION AND MEDIUM TEMPERATURE DUTY COMPRESSOR
APPLICATION DATA
147
CARLYLE REFRIGERATION COMPRESSORS
06D COMPRESSOR DATA - THREE PHASE
MED. TEMP. - NO UNLOADING
OIL
COMPRESSOR MAX. MAX.
VOLT HP CFM CHG. MTA LRA
MODEL NO. WATTS RLA*
PINTS
2 CYLINDER... MEDIUM TEMP ... 60 HZ
06DM8086-3150 575 3 8 3.5 4,100 5.6 7.0 28.4
06DM8086-3250 208/230 3 8 3.5 4,100 14.0 17.4 71.0
06DM8086-3650 460 3 8 3.5 4,100 7.0 8.7 35.5
2 CYLINDER... MEDIUM TEMP ... 50 HZ
06DM8086-3650 400 3 6.7 3.5 3,400 7.0 8.7 35.5
4 CYLINDER... MEDIUM TEMP ... 60 HZ
06DM3136-3150 575 5 13.1 5 6,250 8.6 10.8 40.0
06DM3136-3250 208/230 5 13.1 5 6,250 21.5 27.0 100.0
06DM3136-3650 460 5 13.1 5 6,250 10.8 13.5 50.0
06DM3166-3150 575 5 15.9 5 6,250 8.6 10.8 40.0
06DM3166-3250 208/230 5 15.9 5 6,250 21.5 27.0 100.0
06DM3166-3650 460 5 15.9 5 6,250 10.8 13.5 50.0
4 CYLINDER...MEDIUM TEMP ... 60 HZ
06DM3136-3650 400 5 11 5 5,200 10.8 13.5 50.0
06DM3166-3650 400 5 13 5 5,200 10.8 13.5 50.0
6 CYLINDER...MEDIUM TEMP ... 60 HZ
06DM3376-3150 575 10 37.1 10 16,500 17.9 25.0 91.0
06DM3376-3650 460 10 37.1 10 16,500 22.1 31.0 114.0
06DM3376-3250 208.230 10 37.1 10 16,500 44.3 62.0 228.0
6 CYLINDER...MEDIUM TEMP ... 50 HZ
06DM3376-3650 400 8 31.0 10 13,700 22.1 31.0 114.0
*This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in much lower
RLA values.
148
CARLYLE REFRIGERATION COMPRESSORS
06D COMPRESSOR DATA - THREE PHASE
LOW TEMP REFRIGERATION
OIL
COMPRESSOR MAX. MAX.
VOLT HP CFM CHG. MTA LRA
MODEL NO. WATTS RLA*
PINTS
2 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ
06DR1096-3150 575 2 8.7 3.5 3,100 3.1 4.4 21.3
06DR1096-3250 280/230 2 8.7 3.5 3,100 8.8 12.1 53.3
06DR1096-3650 460 2 8.7 3.5 3,100 3.8 5.5 26.6
2 CYLINDER... LOW TEMP. REFRIGERATION ... 50 HZ
06DR109-3650 400 2 7.5 3.5 2,600 3.8 5.5 26.6
4 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ
06DR0136-3150 575 3 13.1 5 4,300 5.6 7.0 28.4
06DR0136-3250 208/230 3 13.1 5 4,300 14.0 17.4 71.0
06DR0136-3650 460 3 13.1 5 4,300 7.0 8.7 35.5
06DR3166-3150 575 5 15.9 5 6,250 8.6 10.8 40.0
06DR3166-3250 208/230 5 15.9 5 6,250 21.5 27.0 100.0
06DR3166-3650 460 5 15.9 5 6,250 10.8 13.5 50.0
06DR7186-3150 575 5 18.3 7 6,250 8.6 10.8 40.0
06DR7186-3250 208/230 5 18.3 7 6,250 21.5 27.0 100.0
06DR7186-3650 460 5 18.3 7 6,250 10.8 13.5 50.0
06DR8206-3150 575 6.5 20 7 9,800 12.6 17.6 64.0
06DR8206-3250 208/230 6.5 20 7 9,800 31.5 44.0 160.0
06DR8206-3650 460 6.5 20 7 9,800 15.7 22.0 80.0
4 CYLINDER... LOW TEMP. REFRIGERATION ... 50 HZ
06DR013-3650 400 3 11 5 3,400 7.0 8.7 35.5
06DR316-3650 400 5 13 5 5,200 10.8 13.5 50.0
06DR718-3650 400 5 15 7 5,200 10.8 13.5 50.0
06DR820-3650 400 6.5 16.7 7 8,200 31.5 44.0 160.0
6 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ
06DR7246-3150 575 6.5 23.9 10 9,800 12.6 17.6 64.0
06DR7246-3250 208/230 6.5 23.9 10 9,800 31.5 44.0 160.0
06DR7246-3650 460 6.5 23.9 10 9,800 15.7 22.0 80.0
06DR2286-3150 575 7.5 28 10 12,800 15.9 22.2 79.0
06DR2286-3250 208/230 7.5 28 10 12,800 39.7 55.5 198.0
06DR2286-3650 460 7.5 28 10 12,800 19.9 27.8 99.0
06DR3376-3150 575 10 37.1 10 1,6500 17.9 25.0 91.0
06DR3376-3250 208/230 10 37.1 10 16,500 44.3 62.0 228.0
06DR3376-3650 460 10 37.1 10 16,500 22.1 31.0 114.0
6 CYLINDER... LOW TEMP. REFRIGERATION ... 50 HZ
06DR724-3650 400 6.7 20 10 8,200 15.7 22.0 80.0
06DR228-3650 400 8 23.3 10 10,700 19.9 27.8 99.0
06DR337-3650 400 9 31 10 13,700 22.1 31.0 114.0
*This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in much
lower RLA values.
149
CARLYLE REFRIGERATION COMPRESSORS
REQUIRED CIRCUIT BREAKERS: 06D ... 60 HZ (REF. DUTY)
CIRCUIT CIRCUIT CIRCUIT
COMPRESSOR COMPRESSOR COMPRESSOR
BREAKERS BREAKERS BREAKERS
MODEL NO. MODEL NO. MODEL NO.
P/N P/N P/N
06DR1096-3100 HH83XB498 06DR2286-3200 HH83XB307 06DM3166-3200 HH83XB316
06DR1096-3200 HH83XB492 06DR2286-3600 HH83XB438 06DM3166-3600 HH83XB443
06DR1096-3600 HH83XB495 06DR3376-3100 HH83XB451 06DM8186-0100 HH83XB450
06DR0136-3100 HH83XB496 06DR3376-3200 HH83XB305 06DM8186-0600 HH83XB419
06DR0136-3200 HH83XB490 06DR3376-3600 HH83XB452 06DM8186-1200 HH83XB306
06DR0136-3600 HH83XB494 06DM8086-0300 HH83XB480 06DM8246-0100 HH83XB419
06DR3166-3100 HH83XB497 06DM1096-0300 HH83XB481 06DM8246-0600 HH83XB400
06DR3166-3200 HH83XB415 06DM8096-0300 HH32XB480 06DM8246-1200 HH83XB423
06DR3166-3600 HH83XB443 06DM3136-0300 HH83XB483 06DM3376-3100 HH83XB451
06DR7186-3100 HH83XB497 06DM3166-0300 HH83XB483 06DM3376-3600 HH83XB452
06DR7186-3200 HH83XB415 06DM3186-0300 HH83XB483 06DM3376-3200 HH83XB305
06DR7186-3600 HH83XB443 06DM5186-0300 HH83XB484 06DM3376-1400 HH83XE630
06DR8206-3100 HH83XB450 06DM7186-0300 HH83XB483 06DM3376-1500 HH83XE604
06DR8206-3200 HH83XB306 06DM8086-3200 HH83XB490 06DM5376-0100 HH83XB440
06DR8206-3600 HH83XB419 06DM8086-3600 HH83XB494 06DM5376-0600 HH83XB422
06DR7246-3100 HH83XB450 06DM3136-3100 HH83XB497 06DM5376-1200 HH83XB311
06DR7246-3200 HH83XB306 06DM3136-3200 HH83XB316 06DM5376-1400 HH83XE633
06DR7246-3600 HH83XB419 06DM3136-3600 HH83XB443 06DM5376-1500 HH83XE643
06DR2286-3100 HH83XB419 06DM3166-3100 HH83XB497
150
CARLYLE REFRIGERATION COMPRESSORS
REQUIRED ACCESSORIES - 06D
OPTIONAL ACCESSORIES
ALTERNATE ALTERNATE
SUCTION DISCHARGE
COMPRESSOR TERMINAL SUCTION DISCHARGE MOUNTING
SERVICE SERVICE SUSPENSION KIT
MODEL NO. BOX KIT SERVICE SERVICE VALVE PLATE KIT
VALVE KIT VALVE KIT
VALVE KIT KIT
06DR109 06DA660075 06DA660061 - 06DA660060 06DA660059 06DA660058 06EA660096
- - 06DA660061
013 06DA660078 06DA660064 - 06DA660056
316 06DA660064 - 06DA660056
718 06DA660065 06EA660090 06DA660056
820 06DA660065 06EA660090 06DA660056
724 06DA660065 06EA660090 06DA660062 06DA660064 06DA660057
228 06EA660090 - 06DA660062 06DA660064 06DA660057
337 06EA660090 - 06DA660062 06DA660064 06DA660057
06DM808 06DA660075 06DA660061 - 06DA660060 06DA660059 06DA660058
- - 06DA660061
809 06DA660061 - 06DA660058
( )313 06DA660078 06DA660064 - 06DA660056
( )316 06DA660078 06DA660062 06DA660064 06DA660056
518 06DA660078 06DA660064 - 06DA660061 - 06DA660056 06EA660096
( )818 06DA660064 - 06DA660061 - 06DA660056
06D( )724 06DA660063** 06DA660065** 06DA660062 06DA660064 06DA660057
- 06EA660090** - -
06DA660064* - - -
( )824 06DA660063** 06DA660065** 06DA660062 06DA660064
- 06EA660090** - -
06DA660064* - - -
( )337 06DA660065 06EA660090 06DA660064 -
* -- 2 BOLT ** -- 4 BOLT
P419
151
CARLYLE REFRIGERATION COMPRESSORS
GUIDE TO 06E PART NUMBERING SYSTEM:
DESIGN VARIABLES
SIZE
CHARACTERISTICS
FUTURE DESIGN
CFM
ELECTRICAL
MODEL AND
PACKAGING
CPRSRS
USAGE
PRODUCT
SERIES HOM.H.P.
CPRSR
UNITS
MODEL 0 6 E A 1 5 0 3 4 0
DIGIT 1 2 3 4 5 6 7 8 9 10
SEE NOTE 2
REVERSED
6 J X ONE UNLOADER - ELECTRIC SORS & TAPPED CYL. HDS. MOTOR PROTEC-
7 K X TWO UNLOADERS - ELECTRIC TION KIT REQD. FOR THERMOTECTOR
8 L X ONE UNLOADER - PRESSURE APPLICATION
9 N X TWO UNLOADERS - PRESSURE 6 REMANUFACTURED SERVICE COMPRESSOR
7 REMANUFACTUREO SERVICE COMPRESSOR
G X NO UNLOADERS - PRESSURE
USED BY CAC
CPRSR WITH
MED. TEMP.
FOR UNITS
152
CARLYLE REFRIGERATION COMPRESSORS
06E REFRIGERATION AND MEDIUM TEMPERATURE DUTY COMPRESSOR
APPLICATION DATA
153
CARLYLE REFRIGERATION COMPRESSORS
06E COMPRESSOR DATA - THREE PHASE
LOW TEMP. & MED. TEMP. REFRIGERATION
OIL
COMPRESSOR MAX. MAX.
VOLT HP CFM CHG. MTA LRA
MODEL NO. WATTS RLA*
PINTS
4 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ
06EY150-140 575 15 50.3 14 22,000 31 38 98
06EY150-340 208-230/460 15 50.3 14 22,000 72/36 90/45 283/142
06EY166-140 575 20 66 14 25,300 36 45 120
06EY166-340 208-230/460 20 66 14 25,300 87/44 108/54 345/173
06EY166-640 ** 460 20 66 14 25,300 45 56 150
4 CYLINDER ... LOW TEMP. REFRIGERATION ... 50 HZ
06EY150-340 200/400 15 41.7 14 18,300 72/36 90/45 283/142
06EY166-340 200/400 20 55 14 28,000 87/44 108/54 345/173
06EY166-640 ** 400 20 55 14 28,000 45 56 150
6 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ
06EY165-140 575 20 65 19 25,300 36 45 120
06EY165-340 208-230/460 20 65 19 25,300 87/44 108/54 345/173
06EY165-640 ** 460 20 65 19 25,300 44 54 173
06EY175-140 575 20 75.4 19 25,300 36 45 120
06EY175-340 208-230/460 20 75.4 19 25,300 87/44 108/54 345/173
06EY175-640 ** 460 20 75.4 19 25,300 45 56 150
06EY099-140 575 30 99 19 39,100 52 65 176
06EY099-340 208-230/460 30 99 19 39,100 135/68 168/84 506/253
06EY099-640 ** 460 30 99 19 39,100 65 81 220
6 CYLINDER ... LOW TEMP. REFRIGERATION ... 50 HZ
06EY165-340 200/400 20 54 19 21,100 87/44 108/54 345/173
06EY165-640 ** 400 20 54 19 21,100 44 54 173
06EY175-340 200/400 20 62.5 19 21,100 87/44 108/54 345/173
06EY175-640 ** 400 20 62.5 19 21,100 45 56 150
06EY099-340 200/400 30 82.5 19 32,600 135/68 168/84 506/253
06EY099-640 ** 400 30 82.5 19 32,600 65 81 220
4 CYLINDER ... MEDIUM TEMP. REFRIGERATION ... 60 HZ
06EZ150-170 575 15 50.3 14 22,000 31 38 98
06EZ150-370 208-230/460 15 50.3 14 22,000 72/36 90/45 283/142
06EZ266-170 575 25 66 14 33,600 46 57 164
06EZ266-370 208-230/460 25 66 14 33,600 112/56 140/170 446/223
06EZ266-670 ** 460 25 66 14 33,600 57 71 205
4 CYLINDER ... MEDIUM TEMP. REFRIGERATION ... 50 HZ
06EZ150-370 200/400 15 41.7 14 18,300 72/36 90/45 283/142
06EZ266-370 200/400 25 55 14 28,000 112/56 140/170 446/223
06EZ266-670 ** 400 25 55 14 28,000 57 71 205
6 CYLINDER ... MEDIUM TEMP. REFRIGERATION ... 60 HZ
06EZ175-170 575 25 75.4 19 33,600 46 57 164
06EZ175-370 208-230/460 25 75.4 19 33,600 112/56 140/70 446/223
06EZ175-670 ** 460 25 75.4 19 33,600 57 71 205
06EZ199-170 575 35 99 19 47,600 65 82 212
06EZ199-370 208-230/460 35 99 19 47,600 155/77 193/96 610/305
06EZ199-670 ** 460 35 99 19 47,600 82 102 265
6 CYLINDER ... MEDIUM TEMP. REFRIGERATION ... 50 HZ
06EZ175-370 200/400 25 62.5 19 28,000 112/56 140/170 446/223
06EZ175-670 ** 400 25 62.5 19 28,000 57 71 205
06EZ199-370 200/400 35 82.5 19 39,700 155/77 193/96 610/305
06EZ199-670 ** 400 35 82.5 19 39,700 82 102 265
*This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in much lower
RLA values.
**Order the discrete 400/460-3-50/60 volt compressor for part wind start applications only. When ordering, place the letters PW after the model num-
ber, (i.e., 06EX299660PW).
Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.
154
CARLYLE REFRIGERATION COMPRESSORS
REQUIRED CIRCUIT BREAKERS: 06E ... 60 HZ
CIRCUIT CIRCUIT CIRCUIT
COMPRESSOR COMPRESSOR COMPRESSOR
BREAKERS BREAKERS BREAKERS
MODEL NO. MODEL NO. MODEL NO.
P/N P/N P/N
06EY150-140 HH83XA460 06EY175-140 HH83XA461 HH83XE621
HH83XE633 HH83XE622 06EZ266-370 HH83XC409
06EY150-340 HH83XB360 06EY175-340 HH83XB336 HH83XA426
HH83XA463 HH83XA424 06EZ266-670 HH83XE630
06EY166-140 HH83XA461 06EY175-640 HH83XE626 06EZ175-170 HH83XA469
HH83XE622 06EY099-140 HH83XA430 HH83XE621
06EY166-340 HH83XB336 HH83XE652 06EZ175-370 HH83XC409
HH83XA424 06EY099-340 HH83XC439 HH83XA426
06EY166-640 HH83XE626 HH83XA425 06EZ175-670 HH83XE630
06EY165-140 HH83XA461 06EY099-640 HH83XE642 06EZ199-170 HH83XA453
HH83XE622 06EZ150-170 HH83XA460 HH83XE609
06EY165-340 HH83XB336 HH83XE633 06EZ199-370 HH83XC432
HH83XB437 06EZ150-370 HH83XB356 HH83XA547
06EY165-640 HH83XE626 HH83XA463 06EZ199-670 HH83XE623
06EZ266-170 HH83XA469
NOTE: Circuit breakers listed for Discrete 460V Compressors are sized for part wind start.
This circuit breaker is used when Multi-Volt Compressor is connected for 208/230V PWS operation.
This circuit breaker is used when Multi-Volt Compressor is connected for 208/230V XL operation.
This circuit breaker is used when Multi-Volt Compressor is connected for 460V XL operation.
Accessory Screw Package for Circuit Breakers (Required) - P/N 06EA660102 (not used with HH83XA4_- Series Breakers).
Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.
155
CARLYLE REFRIGERATION COMPRESSORS
REQUIRED ACCESSORIES - 06E
OPTIONAL ACCESSORIES
ALTERNATE ALTERNATE
SUCTION DISCHARGE
COMPRESSOR TERMINAL SUCTION DISCHARGE SUSPENSION MOUNTING
SERVICE SERVICE
MODEL NO. BOX KIT SERVICE SERVICE KIT PLATE KIT
VALVE KIT VALVE KIT
VALVE KIT VALVE KIT
06EY150 06EA660095 06EA660091 - 06DA660064 - 06EA660089 06EA660096
166 - 06DA660064 -
175 - 06DA660065 06EA660090
099 - 06DA660065 06EA660090
06EZ150 - 06DA660064 -
266 - 06DA660064 -
175 - 06DA660065 06EA660090
199 - 06DA660065 06EA660090
156
VALVES
COMPRESSOR SERVICE VALVE KITS BY VALVE SIZE
P419
157
CARLYLE REFRIGERATION COMPRESSORS
TOTALINE COMPRESSOR OILS - FOR CARLYLE AND TOTALINE COMPRESSORS
REFRIGERANT R-507,
REFRIGERANT R-12, R-22 REFRIGERANT R-507, REFRIGERANT R-134A
R-404A
COMPRESSOR (L & H TEMP.) R-404A (LOW. TEMP (M & H TEMP)
(MED. TEMP)
MODEL
TOTALINE TOTALINE TOTALINE TOTALINE
OIL MODEL OIL MODEL OIL MODEL OIL MODEL
PART NO. PART NO. PART NO. PART NO.
RO 15 P903-0101
P903-0105
P903-0155
Carlyle 05T/06T E-100 P903-1501 E-100 P903-1501 E-100 P903-1501 E-100 P903-1501
Screw (74) P903-1505 P903-1505 P903-1505 P903-1505
P903-1525 P903-1525 P903-1525 P903-1525
Carlyle 06N Screw N/A N/A N/A N/A N/A N/A SW-220 P903-1201
(104 mm Global Chiller) (R-134a Only) P903-1225
P903-1205
Millennium Scroll Zerol 150 P903-2001 N/A N/A N/A N/A Mobil Arctic 68
Technologies P903-2005 Model now
P903-2025 obsolete
158
OILS
TOTALINE OILS
MINERAL REFRIGERATION OILS VACUUM PUMP OIL
P893 P894
POLYOL-ESTER OILS
P1545
159
CARLYLE REFRIGERATION COMPRESSORS
06CY REFRIGERATION DUTY COMPRESSOR APPLICATION DATA
CARLYLE COMPOUND COOLINGTM ...
An innovative approach to low temperature refrigeration from Carlyle.
R-22 CAPACITY
(000 BTUH)
NO. CFM SUCTION TEMP. RANGE* OIL
-25 SST
MODEL NO. HP OF @ (DEGREES F) CHARGE
110 SCT
CYL. RPM R-22 (PINTS)
65 SGT
40 LIQUID
06CY016 5.0 6 16 -40 to -15 17.6 10
06CY018 5.0 6 18 -40 to -15 22.6 10
06CY124 6.5 6 24 -40 to -15 24.6 10
06CY228 7.5 6 28 -40 to -15 29.5 10
06CY337 10.0 6 37 -40 to -15 39.9 10
06CY550 15.0 6 50 -40 to -15 56.3 19
06CY665 20.0 6 65 -40 to -15 71.4 19
06CY675 20.0 6 75 -40 to -15 80.6 19
06CY899 30.0 6 99 -40 to -15 103.4 19
*Condensing temperature range 60 to 130 F Cylinder Head Cooling Fans recommended for all applications.
160
CARLYLE REFRIGERATION COMPRESSORS
06CY OUTLINE DRAWINGS
NOTE: COMPRESSORS SHOWN WITH OPTIONAL ACCESSORIES - CONTACT YOUR DISTRIBUTOR FOR DETAILS.
06CC COMPRESSORS
06CY016 06CY018 06CY228 06CY337
MOTOR HORSEPOWER 5 5 7.5 10
NO. OF CYLINDERS 6* 6* 6* 6*
BORE AND STROKE (in.) 2.0 x 2.0 x 2.0 x 1.47 2.0 x 1.94
DISPLACEMENT CFM AT 1750 RPM 16 18 28 37
OIL, CHARGE, PINTS CPP33-2 10 10 10 10
DRY WEIGHT LESS SERVICE VALVES 340 LBS 340 LBS 340 LBS 345 LBS
06CC COMPRESSORS
06CY550 06CY665 06CY675 06CY899
MOTOR HORSEPOWER 15.0 20.0 50.0 30.0
NO. OF CYLINDERS 6* 6* 6* 6*
BORE AND STROKE (in.) 2.69 x 2.16 2.69 x 1.96 2.69 x 2.19 2.69 x 2.87
DISPLACEMENT CFM AT 1750 RPM 50 65 75 99
OIL, CHARGE, PINTS CPP33-2 19 19 19 19
DRY WEIGHT LESS SERVICE VALVES 545 LBS 555 LBS 555 LBS 580 LBS
161
CARLYLE REFRIGERATION COMPRESSORS
06CY COMPRESSOR DATA - THREE PHASE
LOW TEMP. REFRIGERATION - COMPOUND COOLING MODELS
OIL
COMPRESSOR MAX. MAX.
VOLT HP CFM CHG. MTA LRA
MODEL NO. WATTS RLA*
PINTS
6 CYLINDER ... LOW TEMP. REFRIGERATION ... 60 HZ
06CY016-D103 208/230 5.0 16 10 4,600 19.3 27.0 100
06CY016-G103 460 5.0 16 10 4,600 9.6 13.5 50.0
06CY016-J103 575 5.0 16 10 4,600 7.7 10.8 40.0
06CY018-DI03 208/230 5.0 18 10 5,000 19.3 27.0 100
06CY018-G103 460 5.0 18 10 5,000 9.6 13.5 50.0
06CY018-J103 575 5.0 18 10 5,000 7.7 10.8 40.0
06CY124-D103 208/230 6.5 24 10 6,500 23.6 33.0 160
06CY124-G103 460 6.5 24 10 6,500 11.8 16.5 80.0
06CY124-J103 575 6.5 24 10 6,500 9.4 13.2 64.0
06CY228-D103 208/230 7.5 28 10 7,600 29.7 41.6 198
06CY228-G103 460 7.5 28 10 7,600 14.9 20.9 99.0
06CY228-J103 575 7.5 28 10 7,600 11.9 16.7 79.0
06CY337-D103 208/230 10 37 10 10,000 33.2 46.5 228.0
06CY337-G103 460 10 37 10 10,000 16.6 23.3 114.0
06CY337-J103 575 10 37 10 10,000 13.4 18.8 91.0
06CY550-E103 208-230/460 15 50 19 13,000 37.1/18.6 52/26 283/142
06CY550-F103 460 15 50 19 13,000 18.6 26.0 142
06CY550-J103 575 15 50 19 13,000 15.0 21.0 98.0
06CY665-E103 208-230/460 20 65 19 16,800 60.7/30.0 85/42 345/173
06CY665-F103 460 20 65 19 16,800 30.0 42.0 173
06CY665-J103 575 20 65 19 16,800 23.6 33.0 120
06CY675-E103 208-230/460 20 75 19 19,000 60.7/30.0 85/42 345/173
06CY675-F103 460 20 75 19 19,000 30.0 42.0 173
06CY675-J103 575 20 75 19 19,000 26.4 33.0 120
06CY899-E103 208-230/460 30 99 19 26,000 92.9/46.4 130/65 506/253
06CY899-F103 460 30 99 19 26,000 46.4 65.0 253
06CY899-J103 575 30 99 19 26,000 37.1 52.0 175
6 CYLINDER ... LOW TEMP. REFRIGERATION ... 50 HZ
06CY016-G103 400 5 13.2 10 3,800 9.6 13.5 50.0
06CY018-G103 400 5 15.0 10 4,200 9.6 13.5 50.0
06CY124-G103 400 6.5 20.0 10 5,400 11.8 16.5 80.0
06CY228-G103 400 7.5 23.3 10 6,300 14.9 20.9 99.0
06CY337-G103 400 10 30.8 10 8,300 16.6 23.3 114.0
06CY550-E103 200/400 15 41.7 19 11,000 37.1/18.6 52.0/26.0 283/142
06CY550-F103 400 15 41.7 19 11,000 18.6 26.0 142
06CY665-E103 200/400 20 54 19 14,000 60.7/30.0 85.0/42.0 345/173
06CY665-F103 400 20 54 19 14,000 30.0 42.0 173
06CY675-E103 200/400 20 62.5 19 14,000 60.7/30.0 85.0/42.0 345/173
06CY675-F103 400 20 62.5 19 14,000 30.0 42.0 173
06CY899-E103 200/400 30 82.5 19 2,1700 92.9/46.4 130/65.0 506/253
06CY899-F103 400 30 82.5 19 21,700 46.4 65.0 253
*This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in much
lower RLA values.
Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.
162
CARLYLE REFRIGERATION COMPRESSORS
REQUIRED CIRCUIT BREAKERS: 06CY ... 60 HZ
CIRCUIT CIRCUIT CIRCUIT
COMPRESSOR COMPRESSOR COMPRESSOR
BREAKERS BREAKERS BREAKERS
MODEL NO. MODEL NO. MODEL NO.
P/N P/N P/N
HH83XB560 06CY665-F100 HH83XB447 HH83XB346
06CY550-E100 06CY899-E100
HH83XB548 06CY665-J100 HH83XB555 HH83XB402
06CY550-F100 HH83XB548 HH83XB376 06CY899-F100 HH83XB402
06CY675-E100
06CY550-J100 HH83XB547 HH83XB559 06CY899-J100 HH83XB437
HH83XB376 06CY675-F100 HH83XB559
06CY665-E100
HH83XB447 06CY675-J100 HH83XB430
NOTE: Circuit breakers listed for Discrete 460V Compressors are sized for part wind start.
This circuit breaker is used when Multi-Volt Compressor is connected for 208/230V PWS operation.
This circuit breaker is used when Multi-Volt Compressor is connected for 208/230V XL operation.
This circuit breaker is used when Multi-Volt Compressor is connected for 460V XL operation.
Accessory Screw Package for Circuit Breakers (Required) - P/N 06EA660102 (not used with HH83XA4_- Series Breakers).
Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.
163
CARLYLE REFRIGERATION COMPRESSORS
REQUIRED ACCESSORIES - 06CY
164
HERMETIC REFRIGERATION COMPRESSORS
COPELAND AFTERMARKET REFRIGERATION COMPRESSORS
P6 P7
165
HERMETIC REFRIGERATION COMPRESSORS
COPELAND AFTERMARKET REFRIGERATION COMPRESSORS (cont)
Nominal Performance
60 Hertz Conditions (F): Evap/Cond/Return Gas/Liquid/Ambient
Amperage
R-22 High Temp. 45/130/65/95 F 20/120/65/120/95 F Ratings*
Copeland P/N HP Volt/Phase CFM BTUH WATTS AMPS EER BTUH WATTS AMPS EER RLA LRA MCC
JRF4-0050-IAA-958 0.5 115-1 113 7,360 1090 13 6.8 4320 850 11.6 5.1 13.6 71 19
JRF4-0050-IAV-958 0.5 208/230-1 113 7,360 1090 7 6.8 4320 850 5.8 5.1 6.4 34 9
RRGA-0100-PAA-950 1 115-1 161 10,800 1390 12.6 7.8 6170 1050 9.8 5.9 13.2 60 18.5
RRGA-0100-PAV-950 1 208/230-1 161 10,800 1390 6.3 7.8 6170 1050 4.9 5.9 6 33.5 8.4
CRA1-0150-PFV-970 1.5 208/230-1 242.5 16,960 1870 8.3 9.1 9430 1430 6 6.6 10.8 48 15.1
CRA1-0150-TF5-970 1.5 208/230-1 242.5 17,190 1810 5.8 9.5 9690 1350 5 7.2 9.3 58 13
CRA1-0150-TFC-970 1.5 208/230-1 242.5 17,190 1810 2.9 9.5 9690 1350 3 7.2 4.1 17.4 5.7
REK3-0125-PFV-959 1.25 115-1 174.7 12,500 1440 6 8.7 7090 1110 5.1 6.4 7 34.2 9.8
REK3-0125-TFC-959 1.25 208/230-1 174.7 12,400 1370 3.8 9.1 7370 1020 3.1 7.2 4.7 31 6.6
RSE4-0075-IAA-958 0.75 115-1 135 8,620 1250 15.2 6.9 5060 940 13.2 5.4 14.3 66.3 20
RSE4-0075-IAV-958 0.75 208/230-1 135 8,620 1250 15.2 6.9 5060 940 6.6 5.4 7.1 35.5 10
R-22 Medium Temp. 20/120/40/120/95 F 0/110/40/110/95 F
Copeland P/N HP Volt / Phase CFM BTUH WATTS AMPS EER BTUH WATTS AMPS EER RLA LRA MCC
RSE4-0075-IAA-958 0.75 115-1 135.3 4770 930 6.5 5.1 2630 690 5.8 3.8 14.3 66.3 20
RSE4-0075-IAV-958 0.75 208/230-1 135.3 4770 930 3.3 5.1 2630 690 2.9 3.8 7.1 35.5 10
RSN6-0075-IAA-958 0.75 115-1 162.4 6200 1190 15 5.2 3680 870 13 4.2 14.3 66.3 20
RSN6-0075-IAV-958 0.75 208/230-1 162.4 6200 1190 7.5 5.2 3680 870 6.5 4.2 6.9 45 9.6
RSL2-0101-CAA-959 1 115-1 244.5 9620 1760 18.2 5.5 5500 1300 14.8 4.2 18 78 25.2
RSL2-0101-CAV-959 1 208/230-1 244.5 9620 1760 9.1 5.5 5500 1300 7.4 4.2 10.4 51 14.5
Nomenclature
Compressor Motor Types
Phase Description Code
Copeland Compressor 1 Capacitor Run - Capacitor Start C Bill of Material*
Family Series 1 Induction Run - Capacitor Start I (See Opposite Page)
Either a number or a letter Compressor nominal 1 Capacitor Run - Permanent P
established for each capacity at rating Split Capacitor
product model. conditions to two 3 Three Phase T
significant digits.
X X X X X X E - X X X - X X X
Capacity Indicates
Comp. Motor Rating compressors
Nominal (HP) Code Multiplier
C = 100 with polyolester oil. Electrical Codes
1/2 0050
K = 1000 60 Hz 50 Hz Codes
3/4 0075
1 0100 Code Description 115-1 - A
Compressor Motor Protection 208/230-3 200/220-3 C
1-1/4 0125 R = High Temperature
Type Protection Code 460-3 380/420-3 D
1-1/2 0150 S = Medium Temperature
1-3/4 0175 External Thermal Protection - 575-3 550-3 E
F = Low Temperature
2 0200 One Protector (Line Break) A 265-1 220/240-1 J
T = Two Speed
2-1/4 0225 Use with Contactor Internal - 380/420-3 M
2-3/4 0275 Inherent Protection - 208/230-1 200-1 V
3 0275 One Protector (Line Break) F - 220/240-1 Z
3-1/2 0350 Use with Contactor
Model Variation 200/230-3 200/240-3 5
4 0400
4-1/2 0450 A number or letter,
5 0500 assigned to indicate
7-1/2 7500 different model
9 0900 types within any
10 1000 one family series.
12 1200
166
HERMETIC REFRIGERATION COMPRESSORS
BILL OF MATERIAL INFORMATION
xxxx-xxxx-xxx- The last 3 digits of any model is a unique bill of material.
xxxx-xxxx-xxx- xxs Wholesaler service compressors used to replaces the above bills of material in most
examples: -959 or -970 situations which include oil, protector, terminal box cover, and mounting parts in a
single carton.
The Second Digit xxxx-xxxx-xxx-x x Rotalock connection(s) or a valve welded on the suction side.
xxxx-xxxx-xxx-x x Sweat connections with terminal flag kit, no electrical components.
Copeland CR Compressors primarily
The Third Digit xxxx-xxxx-xxx-xx No electrical components with the compressor.
xxxx-xxxx-xxx-xx Electrical components mounted.
xxxx-xxxx-xxx-xx Electrical components remote, in the box with the service compressor.
167