CARLYLE 104 MM SCREW COMPRESSORS

06N CARLYLE SEMI-HERMETIC COMPRESSORS

131
CARLYLE REFRIGERATION COMPRESSORS
GENERAL NOTES on Refrigeration Screw Compressors 05T & 06T
Compressors are shipped with service valves attached to the compressor pallet and have blankoff pads bolted over service valve open-
ings. Alternate suction and discharge service valves are available.
All 06T screw compressors are suitable for across-the-line or part winding start. Customer is required to hook up terminal plate for appli-
cable voltage. Wiring diagrams and jumpers are included in the compressor terminal box. Compressor part number on nameplate is the
same as the package ordering number.

All 05T and 06T compressors:


a. Are dehydrated and have a dry air holding charge.
b. Have no oil charge. Oil must be added to fill the entire oil system from the oil solenoid at compressor back to the oil separator.

Carlyle requires the following accessories to protect both 05T and 06T compressors:
- oil separator - oil level switch
- oil filter housing - reverse rotation protection switch
- oil pressure differential switch - Carlyle Electronic Module
- high pressure switch - low pressure switch
The 06T Compressor further requires:
- C-Flange - coupling
06T screw compressors provided WITHOUT motor overcurrent protection, which MUST be supplied by the customer. Heinemann cali-
brated circuit breakers specifically selected for each motor and voltage are a required accessory. All 06T compressor models are UL and
CSA approved. The use of authorized overcurrent protection is part of UL recognition.
All 06T compressors are provided with a 5K thermistor installed in the compressor motor to monitor the motor temperature. The CEM is
required with each 06T to monitor this thermistor.
All compressors are painted green.

132
CARLYLE REFRIGERATION COMPRESSORS
05T (74 mm) SCREW COMPRESSOR

P3036

Design Duty: Commercial Refrigeration


Qualified For: HCFC Refrigeration Duty
HFC Refrigeration Duty
R-22/407C Water Cooled Duty
R-134a Air Cooled Duty
cfm @ 60 Hz 33 39 44 49 54 65 78 88
Capacities:
m3 /hr @ 50 Hz
Economizer: Optional on all models
Vi: Dual Vi Option
Configuration: Open Drive
Check Valve: Integral
Oil Filter: External
Motor Type: External

133
CARLYLE REFRIGERATION COMPRESSORS
OPEN DRIVE MODELS - For All Temperature Ranges With Service Valves
DISPLACEMENT (CFM) APPROX.
MOTOR
MODEL NO. 1750 RPM 3500 RPM SHIP. WEIGHT
HP
Motor (4 pole) Motor (2 pole) (kg)
05TRQ033Z3EA-A00 33 65 N/A 91
05TRQ039Z3EA-A00 39 78 N/A 91
05TRQ044Z3EA-A00 44 88 N/A 91
05TRQ048Z3EA-A00 48 N/A N/A 91
05TRQ054Z3EA-A00 54 N/A N/A 91

NOTE: APPLICATION LIMITS.


R-134a - Medium temperature
- Air Condition
R-22 - Low temperature
- Medium temperature
- Air Conditioning
R-404A/R-507 - Low temperature
- Medium temperature

ACCESSORIES FOR 05T MODELS


05T COUPLING PACKAGE
4 POLE MOTOR 2 POLE MOTOR
MOTOR SHAFT APPROX.
COUPLING 1750 Rpm @ 60 Hz 3500 Rpm @ 60 Hz
DIAMETER SHIP. WT
PKG 1450 Rpm @ 50 Hz 3000 Rpm @ 50 Hz
(in.) (kg)
Hp NEMA Frame Size Hp NEMA Frame Size
8TA0868B 1 5/8 15, 20 254TC, 256TC 30 286TC 5
40, 50 324TSC, 326TSC,
8TA0869B 1 7/8 25, 30 284TC, 286TC 5
60, 75 364TSC, 365TSC
8TA0870B 2 1/8 40, 50 324TC, 326TC N/A N/A 5

05T C-FLANGE PACKAGE


4 POLE MOTOR 2 POLE MOTOR
APPROX.
C-FLANGE 1750 Rpm @ 60 Hz 3500 Rpm @ 60 Hz
SHIP. WT
PKG 1450 Rpm @ 50 Hz 3000 Rpm @ 50 Hz
(kg)
Hp NEMA Frame Size Hp NEMA Frame Size
15, 20, 254TC, 256TC,
0TA0929 N/A N/A 25
35, 30 284TC, 286TC
N/A
0TA0930 25, 30 284TC, 286TC N/A 25
60, 75
286TC, 324TSC,
40, 50
0TA0931 N/A N/A 226TSC, 364TSC, 25
60, 75
365TSC

134
CARLYLE REFRIGERATION COMPRESSORS
06T SCREW COMPRESSOR

P3035

CAPACITY (Btu/Hr) @ 60 Hz
Refrigerant R-22 R-507/404A R-22 R-507/404A R-134a
Conditions -25/110/65 -25/110/65 20/110/65 20/110/65 45/130/65
06T**033 51,000 70,900 131,500 143,100 127,900
06T**039 62,700 86,100 161,000 175,000 156,800
06T**044 72,100 98,900 182,800 199,000 177,700
06T**048 80,100 11,000 203,100 221,100 194,300
06T**054 91,900 126,100 233,100 253,700 222,800
06T**065 113,900 156,400 292,500 318,400 284,100
06T**078 140,200 192,000 354,300 385,700 342,400
06T**088 159,800 218,700 400,900 436,300 387,500

Economized (F).

06T Model Number Significance

135
CARLYLE REFRIGERATION COMPRESSORS
COMPRESSOR PHYSICAL DIMENSIONS

P3031 P3032

P3033

136
CARLYLE REFRIGERATION COMPRESSORS
LOW TEMPERATURE DUTY - Semi-Hermetic With Service Valves

VOLTAGE APPROX.
MOTOR
MODEL NO. 3 PHASE SHIP. WEIGHT
HP
60 HZ 50 HZ (kg)
06TRC033B2EA-A00 460 400
F2EA-A00 208/230 200 15 166
C2EA-A00 575 -
06TRD039B2EA-A00 460 400
F2EA-A00 208/230 200 20 172
C2EA-A00 575 -
06TRD044B2EA-A00 460 400
F2EA-A00 208/230 200 20 172
C2EA-A00 575 -
06TRE048B2EA-A00 460 400
F2EA-A00 208/230 200 25 177
C2EA-A00 575 -
06TRE054B2EA-A00 460 400
F2EA-A00 208/230 200 25 177
C2EA-A00 575 -
06TRF065B2EA-A00 460 400
F2EA-A00 208/230 200 30 181
C2EA-A00 575 -
06TRG078B2EA-A00 460 400
F2EA-A00 208/230 200 35 184
C2EA-A00 575 -
06TRH088B2EA-A00 460 400
F2EA-A00 208/230 200 40 184
C2EA-A00 575 -
06TRK108B2EA-A00
n/a 400 50 186
NOTE: 50Hz Applications Only

NOTE: APPLICATION LIMITS.


R-134a - Medium temperature
- Air Conditioning
R-22 - Low temperature
R-404A/R-507 - Low temperature
06TRK model satisfactory for use on high temp, medium temp and low temp applications.

137
CARLYLE REFRIGERATION COMPRESSORS
MEDIUM/HIGH TEMPERATURE DUTY - Semi-Hermetic With Service Valves
VOLTAGE APPROX.
MOTOR
MODEL NO. 3 PHASE SHIP. WEIGHT
HP
60 HZ 50 HZ (kg)
06TAD033B2EA-A00 460 400
F2EA-A00 208/230 200 20 164
C2EA-A00 575 -
06TAE039B2EA-A00 460 400
F2EA-A00 208/230 200 25 171
C2EA-A00 575 -
06TAF044B2EA-A00 460 400
F2EA-A00 208/230 200 30 171
C2EA-A00 575 -
06TAF048B2EA-A00 460 400
F2EA-A00 208/230 200 30 176
C2EA-A00 575 -
06TAG054B2EA-A00 460 400
F2EA-A00 208/230 200 35 176
C2EA-A00 575 -
06TAG065B2EA-A00 460 400
F2EA-A00 208/230 200 35 180
C2EA-A00 575 -
06TAH078B2EA-A00 460 400
F2EA-A00 208/230 200 40 182
C2EA-A00 575 -
06TAK088B2EA-A00 460 400
F2EA-A00 208/230 200 50 187
C2EA-A00 575 -

NOTE: APPLICATION LIMITS.


R-22 - Low temperature
- Air Conditioning (High Temperature)
R-404A/R-507 - Medium temperature

138
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
05T/06T REFRIGERATION COMPRESSOR ACCESSORIES
ELECTRONIC PHASE MONITOR (REVERSE ROTATION PROTECTION)
(See Notes Below)
PART NO. QTY/PKG WEIGHT (kg) USAGE
P251-0090 1 1.5 ALL 05/6T compressors

NOTES:
1. Protects screw compressor from reverse rotation by monitoring 3-phase input power to compressor motor. Will not allow compressor to start if
sequence is incorrect.
2. This phase monitor will not operate with a variable speed drive inverter.
3. May be used in place of reverse rotation switch; (1) per compressor.

RUBBER ISOLATION MOUNTS


(1 Package Per Compressor Recommended)
PART NO. QTY/PKG WEIGHT (kg) USAGE
KA75KR002 4 0.5 ALL 05/6T compressors

MUFFLERS
(1 Per Compressor Required)
PART NO. QTY/PKG WEIGHT (kg) INLET/OUT LENGTH USAGE
All 05/6T
LM10HH162 1 3 1-5/8 9-3/4
compressor

OIL SEPARATORS
(1 Per Rack Required)
PART NO. MOUNTING LINE SIZE (0. WT (kg) DIA. USAGE
KH31ZZ340 VERTICAL 2-1/8 66 12 Single Comp.
KH31ZZ212 VERTICAL 2-5/8 120 14 Multiple Comp.

NOTES:
1. Oil Separators supplied with multiple sight glasses to view oil level.
2. Oil Separators has adapter fitting at bottom to connect KH13LB004 Oil Level Float Switch.

139
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
05T/06T REFRIGERATION COMPRESSOR ACCESSORIES
OIL LEVEL SWITCH
(1 Per Oil Separator Required)
PART NO. QTY/PKG WEIGHT (kg) USAGE
HK13LB004 1 0.5 On vertical oil separators

NOTE:
1. Protects compressor against loss of oil in Oil Separator. Screws into bottom.

HEATER FOR OIL SEPARATOR / OIL RESERVOIR


(2 Per Oil Separator Recommended)
ELECTRICAL CHARACTERISTICS
PART NO. QTY/PKG WEIGHT (kg)
VOLTS WATTS
HK38KN007 1 0.5 115/230 500

NOTE:
1. Heater applied to oil separator to keep refrigerant from accumulating in it during off cycles.
See application guide for application requirements.

AIR-COOLED OIL COOLERS


(See Application Guide for Requirements)
NO. OF COMPS. ELECTRICAL CHARACTERISTICS
PART NO. WEIGHT (kg)
@ LOAD VOLTS/1 PH HZ
KH51ZZ181 2 23 115/230 V - 1 PH 60/50 HZ
KH51ZZ182 3 57 115/230 V - 1 PH 60/50 HZ
KH51ZZ183 4 91 115/230 V - 1 PH 60/50 HZ
KH51ZZ184 5 98 115/230 V - 1 PH 60/50 HZ

OIL FILTER HOUSING ASSEMBLY


(2 Per Rack Required)
PART NO. QTY/PKG WEIGHT (kg) CONNECTION TYPE USAGE
KH18MG002 1 4 7/8 Sweat All 05/6T Compressors

NOTES:
1. Oil Housing which allows replacement of filter cartridge.
2. Filter Housing assembly includes (1) 3 micron filter cartridge.
3. (2) per rack recommended.

140
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
05T/06T REFRIGERATION COMPRESSOR ACCESSORIES
OIL FILTER CARTRIDGE
PART NO. QTY/PKG WEIGHT (kg) USAGE
KH39MG002 1 0.5 Replacement Cartridge for KH18MG002 housing

NOTE:
1. Carlyle recommends (3) cartridges be left at the job site per oil filter housing. Several changeouts will be necessary before the system is free of
contaminant. If the job is a remodel, more changeouts may be necessary.
2. Each cartridge is supplied with (1) filter housing O ring.

DESUPERHEATING
(1 Per Compressor for R-22 <-32 C & R-404A/R507 <-43C SST Systems)
PART NO. QTY/PKG WEIGHT (kg) SIZE USAGE
EA02ZD001 1 1 1 ton
EA02ZD002 1 1 1.5 ton All 05/6T
EA02ZD030 1 1 2 ton Compressors
EA02ZD050 1 1 3 ton
EA02ZD100 1 1 5 ton

SOLENOID COILS - FOR UNLOADING AND Vi CONTROL


(1 Per 06TA Compressor Required)
(2 Per 05/6TR Compressor Required)
PART NO. QTY/PKG WEIGHT (kg) ELECTRICAL USAGE
EF19ZE120 1 0.5 120-1-50/60
All 05/6T Compressors
EF19ZE240 1 0.5 208/240-1-50/60
EF19ZE024 1 0.5 24-1-50/60

NOTES:
1. Solenoid Coil operates either capacity control unloading mechanism or variable volume (Vi) control.
2. 06TR Models require (2) per compressor, 06TA models require (1) per compressor.

CARLYLE ELECTRONIC MODULE (CEM)


(1 Per Compressor Required)
PART NO. QTY/PKG WEIGHT (kg) ELECTRICAL USAGE
120/240-1-60 All 05/6T Compressors
3TA0796B 1 0.5
100/200-1-50

NOTES:
1. Module uses (2) 5K Thermistors, (1) embedded in motor windings and (1) strapped on discharge line (thermistor purchased separately.)
2. The modules control motors and discharge cooling and acts as a safety for overheating protection.

141
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
05T/06T REFRIGERATION COMPRESSOR ACCESSORIES
5K THERMISTOR
(1 Per Compressor Required)
PART NO. QTY/PKG WEIGHT (kg) ELECTRICAL USAGE
HH79NZ065 1 0.5 115/240-1-60 All 05/6T Compressors

NOTE: One required per compressor for use with CEM to monitor discharge temperature.

MOTOR COOLING VALVES


(1 Per Compressor Required)
PART NO. QTY/PKG WEIGHT (kg) EVRP SIZE USAGE
EF28BZ007 1 0.5 1.4 All 05/6T Compressors

NOTE: Used for motor and discharge gas cooling of screw compressors.

SOLENOID COILS FOR MOTOR COOLING VALVES


(1 Per Compressor Required)
PART NO. QTY/PKG WEIGHT (kg) ELECTRICAL USAGE
P510-XV120D 1 0.5 120-1-50/60
All 05/6T Compressors
P510-XV208D 1 0.5 208/240-1-50/60
P510-XV024D 1 0.5 24-1-50/60

REVERSE ROTATION PROTECTION SWITCH


(1 Per Compressor Required)
PART NO. QTY/PKG WEIGHT (kg) USAGE
HK01CB002 1 1 All 05/6T Compressors

NOTE: Protects screw compressor from reverse rotation.

142
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
05T/06T REFRIGERATION COMPRESSOR ACCESSORIES
OIL PRESSURE DIFFERENTIAL SWITCH(1 Per Compressor Required)
VOLTAGE
PART NO. QTY/PKG WEIGHT (kg) CONNECTION USAGE
INPUT
HK06ZB006 1 2 1/4 FLARE 115 or 230 ALL 05/6T compressors

NOTES:
1. Senses oil differential between discharge pressure and oil feed to the compressor.
2. Switch setting is for cutout when differential pressure above (45 psid) and has a 30 second time delay.

OIL FILTER DIFFERENTIAL SWITCH


(1 Per Oil System Recommended)
VOLTAGE
PART NO. QTY/PKG WEIGHT (KG) CONNECTION USAGE
INPUT
HK06CA051 1 2 1/4 FLARE 115 or 230 ALL 05/6T compressors

NOTES:
1. Senses oil differential across filters.
2. Switch setting is for cutout when differential pressure exceeds 45 psid and has a 30 second time delay.

SUCTION AND DISCHARGE SERVICE VALVE PACKAGES


PART NO. SIZE ODF QTY/PKG WEIGHT (kg) USAGE
06TA660001 1-5/8 1 2
06TA660002 1-3/8 1 2 ALL 05/6T compressors
06TA660003 1-1/8 1 2 05T/06T 65, 78, 88 CFM
06TA680005 1-5/8 1 2

NOTES:
1. (2) 06TA660001 packages are supplied with each compressor.
2. All service Valve are 4 bolt, 2-1/2 square bolt spacing. Service Valve Package contains (1) service valve (1) gasket, and (4) metric hex
head cap screws (M12 x 1,75 x 60mm).
3. These Service Valve packages (except 06TA68005) are the same as the respective 06D/E packages except the mounting bolts have
metric threads.

ECONOMIZER SERVICE VALVE


(See Notes Below)
PART NO. SIZE ODF QTY/PKG WEIGHT (kg) USAGE
06TA660004 7/8 1 2 ALL 05/6T compressors

NOTES:
1. (1) 06TA660004 package is supplied with each compressor.
2. All Economizer Service Valve contain (1) Rotalock * valve, (1) O-ring, (1) seal, and (1) connection fitting.

143
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
06T REFRIGERATION COMPRESSOR ACCESSORIES
CALIBRATED CIRCUIT BREAKERS
(1 Per 06T Compressor)
COMPRESSOR VOLTAGE
QTY/PKG WEIGHT (kg) CIRCUIT BREAKER
MODULE USAGE 3 PHASE
06TRC033B2EA-A00 460-3-60 & 400-3-50 2 HH83XA463
F2EA-A00 230-3-60 & 200-3-50 1 2 HH83XB356
C2EA-A00 575-3-60 2 HH83XA460
06TRD039B2EA-A00 460-3-60 & 400-3-50 2 HH83XA424
F2EA-A00 230-3-60 & 200-3-50 1 2 HH83XB336
C2EA-A00 575-3-60 2 HH83XA461
06TRD044B2EA-A00 460-3-60 & 400-3-50 2 HH83XA424
F2EA-A00 230-3-60 & 200-3-50 1 2 HH83XB336
C2EA-A00 575-3-60 2 HH83XA461
06TRE048B2EA-A00 460-3-60 & 400-3-50 2 HH83XA426
F2EA-A00 230-3-60 & 200-3-50 1 3 HH83XC509
C2EA-A00 575-3-60 2 HH83XA469
06TRE054B2EA-A00 460-3-60 & 400-3-50 2 HH83XA426
F2EA-A00 230-3-60 & 200-3-50 1 3 HH83XC509
C2EA-A00 575-3-60 2 HH83XA469
06TRF065B2EA-A00 460-3-60 & 400-3-50 2 HH83XA474
F2EA-A00 230-3-60 & 200-3-50 1 3 HH83XC573
C2EA-A00 575-3-60 2 HH83XB617
06TRG078B2EA-A00 460-3-60 & 400-3-50 2 HH83XA476
F2EA-A00 230-3-60 & 200-3-50 1 3 HH83XC574
C2EA-A00 575-3-60 2 HH83XB618
06TRH088B2EA-A00 460-3-60 & 400-3-50 2 HH83XA476
F2EA-A00 230-3-60 & 200-3-50 1 3 HH83XC575
C2EA-A00 575-3-60 2 HH83XB619
06TRK108B2EA-A00 400-3-50 1 2 HH83XA477

NOTES:
1. Circuit breaker selections are based on across-the-line start.
2. Overcurrent protection required per General Note.
3. Heinemann circuit breaker not required with 05T compressor.

144
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
06T REFRIGERATION COMPRESSOR ACCESSORIES
CALIBRATED CIRCUIT BREAKERS
(1 Per 06T Compressor)
COMPRESSOR VOLTAGE
QTY/PKG WEIGHT (kg) CIRCUIT BREAKER
MODULE USAGE 3 PHASE
06TAD033B2EA-A00 460-3-60 & 400-3-50 4 HH83XA424
F2EA-A00 230-3-60 & 200-3-50 4 HH83XB336* or
1
HH83XB625
C2EA-A00 575-3-60 4 HH83XA461
06TAE039B2EA-A00 460-3-60 & 400-3-50 4 HH83XA426
F2EA-A00 230-3-60 & 200-3-50 1 4 HH83XC509
C2EA-A00 575-3-60 4 HH83XA469
06TAF044B2EA-A00 460-3-60 & 400-3-50 4 HH83XA425
F2EA-A00 230-3-60 & 200-3-50 1 4 HH83XC539
C2EA-A00 575-3-60 4 HH83XA430
06TAF048B2EA-A00 460-3-60 & 400-3-50 4 HH83XA425
F2EA-A00 230-3-60 & 200-3-50 1 4 HH83XC539
C2EA-A00 575-3-60 4 HH83XA430
06TAG054B2EA-A00 460-3-60 & 400-3-50 4 HH83XA547
F2EA-A00 230-3-60 & 200-3-50 1 4 HH83XC532
C2EA-A00 575-3-60 4 HH83XA453
06TAG065B2EA-A00 460-3-60 & 400-3-50 4 HH83XA475
F2EA-A00 230-3-60 & 200-3-50 1 6 HH83XC574
C2EA-A00 575-3-60 4 HH83XB618
06TAH078B2EA-A00 460-3-60 & 400-3-50 4 HH83XA476
F2EA-A00 230-3-60 & 200-3-50 1 6 HH83XC575
C2EA-A00 575-3-60 4 HH83XB619
06TAK088B2EA-A00 460-3-60 & 400-3-50 4 HH83XA477
F2EA-A00 230-3-60 & 200-3-50 1 6 HH83XC576
C2EA-A00 575-3-60 4 HH83XB610
*These breakers are supplied without compression lugs. Customer must provide connectors or use our Power Terminal Parts Connectors for HH83XB
Circuit Breakers shown below.
NOTES:
1. Circuit breakers selections are based on across-the-line start.
2. Overcurrent protection required per General Note.
3. Heinemann circuit breaker not required with 05T compressor.

POWER TERMINAL PARTS CONNECTORS FOR HH83XB CIRCUIT BREAKER


PART NO. USAGE SHIP WEIGHT (kg)
06EA660152 #1 - #2 Wire 0.5
06EA660153 #4 Wire 0.5

HH83XB series circuit breakers require customer supplied power wire connections at circuit breaker.
Kit includes ring terminal, cap screws and lock washers. Not required for XA, XC, C or B series circuit breakers.

TERMINAL PARTS PACKAGES


PART NO. QTY/PKG WEIGHT (kg) USE WITH USAGE
06EA900132 1 0.5 #6 Wire
06EA900102 1 0.5 #4 Wire All 06T
06EA900112 1 0.5 #2 Wire Compressors
06EA900122 1 0.5 #1/0 Wire

Package Contents: (6) Ring Terminal to connect power wiring to compressor terminal studs, plus (3) spare (2-hole) jumper bars.

145
CARLYLE REFRIGERATION COMPRESSORS
GUIDE TO 06D PART NUMBERING SYSTEM:
VARIABLES
NOTES:
1. SPECIAL ORDER SERVICE COMPRESSORS FOR BRYANT

CHARACTERISTIC
VORELOADS & INTERNAL
MAY BE PROCESSED AS 9 NAMEPLATED 6 (8TH DIGIT).

FUTURE DESIGN
DISPLACEMENT

SUCTION VALUE & M.E.


2. SERVICE MODELS WITH C IN THE 10th DIGIT REPLACE ALL

COVER ORIENTATION
KEY NUMBER

ELECTRICAL
PRODUCT

VARIATIONS

VARIATIONS

VARIATIONS
PACKAGING
A, C AND E ORIGINAL EQUIPMENT MODELS AND D

VARIABLES
UNLOADER
SERIES SERVICE MODELS REPLACE 8 & F MODELS. TERMINAL

THERMOSTAT
MOTOR
BOXES AND OVERLOADS ARE TO BE RE-USED OR
REPLACED IF DAMAGED.

SIZE

CFM
3. 09 IN THE 11TH & 12TH DIGITS HAS BEEN USED IN THE
MODEL 0 6 D A 3 1 6 0 0 A 3 2 0 0 PAST FOR 400-3-50 MOTORS AND IS NO LONGER USED, SO
AS TO AVOID CONFUSION IN SERVICE THESE DIGITS ARE
VARIABLE DIGIT I 2 3 4 5 6 7 8 9 10 11 12 13 14 TO BE LEFT ON THIS CHART BUT ARE NOT TO BE RE-USED.

1ST, 2ND, 3RD DIGITS


SIGNIFY 06D HERMETIC
14TH
RECIP. COMPRESSOR PACKAGING VARIATIONS
DIGIT
SERVICE UNIT SINGLE PACK -
0
BASE UNIT UNPACKAGES
4TH DIGIT UNLOADER VARIABLE 13TH FUTURE DESIGN SINGLE PACK - DOMESTIC
I
S DIGIT VARIABLES LESS SERVICE VALVE
S 2 MULTI-PACK - DOMESTIC
L T 0 ORIGINAL DESIGN A/C & REFRIG.
E 3 EXPORT - I UNIT
E A B 1 2ND GENERATION REFRIG,
R 4 MULTI-PACK
T N O CPRSR. W/NEW VALVE PLATE
V DESCRIPTION 5 PALLETIZED
T D T 2 MED. RANGE A/C CPRSR. WITH
I 6 GOVERNMENT PACK
E A H REFRIG. CHARACTERISTICS
C SINGLE PACK - DOMESTIC
R R 3 LOW CLEARANCE VOLUME 7
E WITH SERVICE VALVE
D 4 SUCTION CUT-OFF 1 STEP
A X NO HOT GAS BY-PASS UNLOADERS ELECTRIC UNLOADERS MATCHED COMPONENTS -
B X ELECTRIC UNLOADERS 1 STEP 5 OILLESS 8 CONSISTS OF SEPARATE
C X 2 STEP 6 EXPORT PACKAGE PIECES
D X PRESSURE UNLOADERS 1 STEP 7 DOMESTIC MULTI-PACK &
9
E X 2 STEP MCMINNVILLE
F X SUCTION CUT-OFF 1 STEP
G X ELECTRIC UNLOADERS 2STEP
ELECTRICAL
M X MED. TEMPERATURE, REPLACES 11TH
CHARACTERISTICS
ALL As IN SERVICE & 12TH START
VOLTS-PHASE-
N X 2 SHAVED HDS. - SPECIAL ORDER DIGITS
HERTZ
R X REFRIGERATION
00 XL
W X AIC - 2 PLUGGED HDS. REPLACES OVERLOAD & TSTAT. VARIABLE SEE NOTE 2
10TH 01 575 - 3 - 60 XL
ALL C&E SERVICE SPEC. ORDERS EXTL. INTL.
DIGIT DESCRIPTION 02 200 - 1 - 60 XL
X X 1 PLUGGED HEAD - REPLACES ALL OVLDS. TRAT.
03 230 - 1 - 60 XL
B, C, D & E PROD. MODELS IN A YES YES
04 200 - 3 - 60 XL
SERVICE B YES NO
05 230 - 3 - 60 XL
Y X REFR. - 2 PLUGGED HDS. SERVICE C NO YES
06 400/460 - 3 - 50/60 XL
SPEC. ORDER D NO NO
07 230 - 1 - 50 XL
S X HI-EFF SERVICE MOD. w/I BLOCKED E YES YES 1ST OVERLOAD VARIATION
08 220 - 3 - 50 XL
UNLDR HD - REPLACES F, G, H & J F YES NO 1ST OVERLOAD VARIATION
09 SEE NOTE 3 XL
H X SUCTON CUT-OFF PRES- 1 STEP G YES YES MANUAL RESET OVERLOADS
10 230 - 2 - 60 XL
J X SURE UNLOADERS! 2 STEP T NO YES TECUMSEH SERVICE MODELS
11 480 - 3 - 60 XL
12 2081230 - 3 - 60 XL
5TH DIGIT MOTOR SIZES 13 380 - 3 - 60 XL
VARIABLE 2 CYL 4 CYL 6 CYL 14 200 - 3 - 60 P/W
0 3 HP 15 230 - 3 - 60 P/W
1 2 HP 5 HP 18 220 - 3 - 50 P/W
2 24 LBFT 19 230/460 - 3 - 60 XL
3 5 HP 27 LBFT 21 575 - 3 - 60 XL
4 31/2 HP 26 400/460 - 3 - 50/60 XL
5 51/2 HP 38 LBFT 31 575 - 3 - 60 XL
6 32 208/230 - 3 - 60 XL
7 5 HP 20 LBFT 36 400/460 - 3 - 50/60 XL
8 3 HP 20 LBFT 24 LBFT 38 415 - 3 - 50 P/W
9 39 415 - 3 - 50 XL
33 208/230 - 1 - 60 XL
34 220 - 3 - 50 XL
6TH & 7TH CRANKCASE
CYL
DIGITS ASSEMBLY 8TH
BORE KEY NO. SIGNIFICANCE
CFM NO. DIGIT
07 6D20-249 1-13/16 0 PROD. MOD. W/T-BOX 9TH SUCTION SERVICE VALVE VARIABLES
08 6D23-249 2 1 PKG. CPRSR. & CONTROL BOX DIGIT LOC. OF VALVE M.E.COV. DESC. VALVE ORIENTATION
09 6D23-249 2 2 OEM A/C CPRSR. A MOTOR END 2 BOLT 30
0
13 6D48-249 2 3 TYLER MODELS B MOTOR END 4 BOLT 30
16 6D48-249 2 4 TECUMSEH OEM MODELS C MOTOR END 2 BOLT 90
18 6D48-249 2 5 FUTURE USE D MOTOR END 4 BOLT 90 OR 180 270 90
20 6D48-249 2 6 REMAN. SERVICE CPRSR. E MOTOR END 2 BOLT 150
24 6D68-259 2 7 NEWMAN SERVICE GPRSR. F PUMP END PLAIN 270
28 6D75-249 2 6 SPECIAL ORDER ONLY 180
G PUMP END PLAIN 225
37 6D75-249 2 9 SERV. SPEC. OR SEE NOTE 1

146
CARLYLE REFRIGERATION COMPRESSORS
06D REFRIGERATION AND MEDIUM TEMPERATURE DUTY COMPRESSOR
APPLICATION DATA

For mounting configuration,


dimensions and weight refer to
outline drawings on previous
pages.
P912

CAPACITY (000 BTUH)


CFM -25 SST 20 SST 15 SST 40 SST
NO. SUCTION TEMP. RANGE*
MODEL @ 110 SCT 120 SCT 110 SCT 120 SCT
HP OF (F)
NO. 1750 65 SGT 65 SGT 65 SGT 60 SGT
CYL.
RPM 0 SC 0 SC 0 SC 0 SC
R-502 R-12 R-22 R-502 R-502 R-12/R134a R-22
06DR109 2 2 8.7 -40 to 0** -10 to 40 - 9.9 - 14.6/ - -
06DM808 3 2 8.0 -10 to 40 - -10 to 50 - 23.1 - 35.6
06DR013 3 4 13.1 -40 to 0** -10 to 40 - 11.7 - 22.7/19.5 -
06DM313 5 4 13.1 -10 to 40 -10 to 40 -10 to 50 - 35.1 20.4/ - 55.6
06DR316 5 4 15.9 -40 to 10** -10 to 40 - 16.2 - 29.1/26.9 -
06DM316 5 4 15.9 -10 to 40 -10 to 40 -10 to 50 - 45.0 26.6/ - 69.0
06DR718 5 4 18.3 -40 to 10** -10 to 40 - 20.4 - 33.7/31.9 -
06DR820 6-1/2 4 20.0 -40 to 40** -10 to 40 -10 to 50 22.3 - 37.4/35.6 92.5
06DR724 6-1/2 6 23.9 -40 to 40** -10 to 40 -10 to 50 25.6 - 43.7/40.1 109.6
06DR228 7-1/2 6 28.0 -40 to 40** -10 to 40 -10 to 50 31.0 - 51.3/49.2 128.2
06DR337 10 6 37.1 -40 to 10** -10 to 40 - 42.7 - 69.3/67.7 -
06DM337 10 6 37.1 -10 to 30 -10 to 40 -10 to 35 - 111.1 65.6/ - 165.9
*Condensing temperature range 80 to 120 F.
**Cylinder Head Cooling Fan is required to operate at minimum suction temperatures.

06D COMPRESSOR DATA - SINGLE PHASE


MED. TEMP - NO UNLOADING
OIL
COMPRESSOR MAX. MAX.
VOLT HP CFM CHG. MTA LRA
MODEL NO. WATTS RLA
PINTS
2 CYLINDER... MEDIUM TEMP ... 60 HZ
06DM8086-0350 230 3 8 3.5 2800 17.0 22.0 70.0
06DM1096-0350 230 2 8.7 3.5 2800 12.5 15.6 50.0
4 CYLINDER... MEDIUM TEMP ... 60 HZ
06DM3136-0350 230 5 13.1 5 6600 28.0 35.0 100.0
06DM3166-0350 230 5 15.9 5 6600 28.0 35.0 100.0
06DM3186-0350 230 5 18.3 7 6600 28.0 35.0 100.0
06DM5186-0350 230 5.5 18.3 7 7700 36.8 46.0 148.0
06DM7186-0350 230 5 18.3 7 6600 28.0 35.0 100.0

147
CARLYLE REFRIGERATION COMPRESSORS
06D COMPRESSOR DATA - THREE PHASE
MED. TEMP. - NO UNLOADING
OIL
COMPRESSOR MAX. MAX.
VOLT HP CFM CHG. MTA LRA
MODEL NO. WATTS RLA*
PINTS
2 CYLINDER... MEDIUM TEMP ... 60 HZ
06DM8086-3150 575 3 8 3.5 4,100 5.6 7.0 28.4
06DM8086-3250 208/230 3 8 3.5 4,100 14.0 17.4 71.0
06DM8086-3650 460 3 8 3.5 4,100 7.0 8.7 35.5
2 CYLINDER... MEDIUM TEMP ... 50 HZ
06DM8086-3650 400 3 6.7 3.5 3,400 7.0 8.7 35.5
4 CYLINDER... MEDIUM TEMP ... 60 HZ
06DM3136-3150 575 5 13.1 5 6,250 8.6 10.8 40.0
06DM3136-3250 208/230 5 13.1 5 6,250 21.5 27.0 100.0
06DM3136-3650 460 5 13.1 5 6,250 10.8 13.5 50.0
06DM3166-3150 575 5 15.9 5 6,250 8.6 10.8 40.0
06DM3166-3250 208/230 5 15.9 5 6,250 21.5 27.0 100.0
06DM3166-3650 460 5 15.9 5 6,250 10.8 13.5 50.0
4 CYLINDER...MEDIUM TEMP ... 60 HZ
06DM3136-3650 400 5 11 5 5,200 10.8 13.5 50.0
06DM3166-3650 400 5 13 5 5,200 10.8 13.5 50.0
6 CYLINDER...MEDIUM TEMP ... 60 HZ
06DM3376-3150 575 10 37.1 10 16,500 17.9 25.0 91.0
06DM3376-3650 460 10 37.1 10 16,500 22.1 31.0 114.0
06DM3376-3250 208.230 10 37.1 10 16,500 44.3 62.0 228.0
6 CYLINDER...MEDIUM TEMP ... 50 HZ
06DM3376-3650 400 8 31.0 10 13,700 22.1 31.0 114.0
*This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in much lower
RLA values.

06D COMPRESSOR DATA - SINGLE PHASE


LOW TEMP REFRIGERATION
OIL
COMPRESSOR MAX. MAX.
VOLT HP CFM CHG. MTA LRA
MODEL NO. WATTS RLA*
PINTS
2 CYLINDER... LOW TEMP REFRIGERATION ... 60 HZ
06DR1096-3350 208/230-1 2 8.7 3.5 3,400 17.0 24.0 110.0
4 CYLINDER... LOW TEMP REFRIGERATION ... 60 HZ
06DR0136-3350 208/230-1 3 13.1 5 4,800 23.3 32.6 100.0
06DR3166-3350 208/230-1 5 15.9 5 6,400 28.6 40.0 150.0
06DR7186-3350 208/230-1 5 18.3 7 6,400 28.6 40.0 150.0

148
CARLYLE REFRIGERATION COMPRESSORS
06D COMPRESSOR DATA - THREE PHASE
LOW TEMP REFRIGERATION
OIL
COMPRESSOR MAX. MAX.
VOLT HP CFM CHG. MTA LRA
MODEL NO. WATTS RLA*
PINTS
2 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ
06DR1096-3150 575 2 8.7 3.5 3,100 3.1 4.4 21.3
06DR1096-3250 280/230 2 8.7 3.5 3,100 8.8 12.1 53.3
06DR1096-3650 460 2 8.7 3.5 3,100 3.8 5.5 26.6
2 CYLINDER... LOW TEMP. REFRIGERATION ... 50 HZ
06DR109-3650 400 2 7.5 3.5 2,600 3.8 5.5 26.6
4 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ
06DR0136-3150 575 3 13.1 5 4,300 5.6 7.0 28.4
06DR0136-3250 208/230 3 13.1 5 4,300 14.0 17.4 71.0
06DR0136-3650 460 3 13.1 5 4,300 7.0 8.7 35.5
06DR3166-3150 575 5 15.9 5 6,250 8.6 10.8 40.0
06DR3166-3250 208/230 5 15.9 5 6,250 21.5 27.0 100.0
06DR3166-3650 460 5 15.9 5 6,250 10.8 13.5 50.0
06DR7186-3150 575 5 18.3 7 6,250 8.6 10.8 40.0
06DR7186-3250 208/230 5 18.3 7 6,250 21.5 27.0 100.0
06DR7186-3650 460 5 18.3 7 6,250 10.8 13.5 50.0
06DR8206-3150 575 6.5 20 7 9,800 12.6 17.6 64.0
06DR8206-3250 208/230 6.5 20 7 9,800 31.5 44.0 160.0
06DR8206-3650 460 6.5 20 7 9,800 15.7 22.0 80.0
4 CYLINDER... LOW TEMP. REFRIGERATION ... 50 HZ
06DR013-3650 400 3 11 5 3,400 7.0 8.7 35.5
06DR316-3650 400 5 13 5 5,200 10.8 13.5 50.0
06DR718-3650 400 5 15 7 5,200 10.8 13.5 50.0
06DR820-3650 400 6.5 16.7 7 8,200 31.5 44.0 160.0
6 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ
06DR7246-3150 575 6.5 23.9 10 9,800 12.6 17.6 64.0
06DR7246-3250 208/230 6.5 23.9 10 9,800 31.5 44.0 160.0
06DR7246-3650 460 6.5 23.9 10 9,800 15.7 22.0 80.0
06DR2286-3150 575 7.5 28 10 12,800 15.9 22.2 79.0
06DR2286-3250 208/230 7.5 28 10 12,800 39.7 55.5 198.0
06DR2286-3650 460 7.5 28 10 12,800 19.9 27.8 99.0
06DR3376-3150 575 10 37.1 10 1,6500 17.9 25.0 91.0
06DR3376-3250 208/230 10 37.1 10 16,500 44.3 62.0 228.0
06DR3376-3650 460 10 37.1 10 16,500 22.1 31.0 114.0
6 CYLINDER... LOW TEMP. REFRIGERATION ... 50 HZ
06DR724-3650 400 6.7 20 10 8,200 15.7 22.0 80.0
06DR228-3650 400 8 23.3 10 10,700 19.9 27.8 99.0
06DR337-3650 400 9 31 10 13,700 22.1 31.0 114.0
*This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in much
lower RLA values.

149
CARLYLE REFRIGERATION COMPRESSORS
REQUIRED CIRCUIT BREAKERS: 06D ... 60 HZ (REF. DUTY)
CIRCUIT CIRCUIT CIRCUIT
COMPRESSOR COMPRESSOR COMPRESSOR
BREAKERS BREAKERS BREAKERS
MODEL NO. MODEL NO. MODEL NO.
P/N P/N P/N
06DR1096-3100 HH83XB498 06DR2286-3200 HH83XB307 06DM3166-3200 HH83XB316
06DR1096-3200 HH83XB492 06DR2286-3600 HH83XB438 06DM3166-3600 HH83XB443
06DR1096-3600 HH83XB495 06DR3376-3100 HH83XB451 06DM8186-0100 HH83XB450
06DR0136-3100 HH83XB496 06DR3376-3200 HH83XB305 06DM8186-0600 HH83XB419
06DR0136-3200 HH83XB490 06DR3376-3600 HH83XB452 06DM8186-1200 HH83XB306
06DR0136-3600 HH83XB494 06DM8086-0300 HH83XB480 06DM8246-0100 HH83XB419
06DR3166-3100 HH83XB497 06DM1096-0300 HH83XB481 06DM8246-0600 HH83XB400
06DR3166-3200 HH83XB415 06DM8096-0300 HH32XB480 06DM8246-1200 HH83XB423
06DR3166-3600 HH83XB443 06DM3136-0300 HH83XB483 06DM3376-3100 HH83XB451
06DR7186-3100 HH83XB497 06DM3166-0300 HH83XB483 06DM3376-3600 HH83XB452
06DR7186-3200 HH83XB415 06DM3186-0300 HH83XB483 06DM3376-3200 HH83XB305
06DR7186-3600 HH83XB443 06DM5186-0300 HH83XB484 06DM3376-1400 HH83XE630
06DR8206-3100 HH83XB450 06DM7186-0300 HH83XB483 06DM3376-1500 HH83XE604
06DR8206-3200 HH83XB306 06DM8086-3200 HH83XB490 06DM5376-0100 HH83XB440
06DR8206-3600 HH83XB419 06DM8086-3600 HH83XB494 06DM5376-0600 HH83XB422
06DR7246-3100 HH83XB450 06DM3136-3100 HH83XB497 06DM5376-1200 HH83XB311
06DR7246-3200 HH83XB306 06DM3136-3200 HH83XB316 06DM5376-1400 HH83XE633
06DR7246-3600 HH83XB419 06DM3136-3600 HH83XB443 06DM5376-1500 HH83XE643
06DR2286-3100 HH83XB419 06DM3166-3100 HH83XB497

REQUIRED CIRCUIT BREAKERS: 06D ... 50 HZ

CIRCUIT CIRCUIT CIRCUIT


COMPRESSOR COMPRESSOR COMPRESSOR
BREAKERS BREAKERS BREAKERS
MODEL NO. MODEL NO. MODEL NO.
P/N P/N P/N
06DR109-3600 HH83XB495 06DR724-3600 HH83XB419 06DM316-3600 HH83XB443
06DR013-3600 HH83XB494 06DR228-3600 HH83XB438 06DM818-0600 HH83XB419
06DR316-3600 HH83XB443 06DR337-3600 HH83XB452 06DM824-0600 HH83XB400
06DR718-3600 HH83XB415 06DM808-3600 HH83XB494 06DM337-3600 HH83XB452
06DR820-3600 HH83XB419 06DM313-3600 HH83XB443 06DM537-0600 HH83XB422

150
CARLYLE REFRIGERATION COMPRESSORS
REQUIRED ACCESSORIES - 06D
OPTIONAL ACCESSORIES
ALTERNATE ALTERNATE
SUCTION DISCHARGE
COMPRESSOR TERMINAL SUCTION DISCHARGE MOUNTING
SERVICE SERVICE SUSPENSION KIT
MODEL NO. BOX KIT SERVICE SERVICE VALVE PLATE KIT
VALVE KIT VALVE KIT
VALVE KIT KIT
06DR109 06DA660075 06DA660061 - 06DA660060 06DA660059 06DA660058 06EA660096
- - 06DA660061
013 06DA660078 06DA660064 - 06DA660056
316 06DA660064 - 06DA660056
718 06DA660065 06EA660090 06DA660056
820 06DA660065 06EA660090 06DA660056
724 06DA660065 06EA660090 06DA660062 06DA660064 06DA660057
228 06EA660090 - 06DA660062 06DA660064 06DA660057
337 06EA660090 - 06DA660062 06DA660064 06DA660057
06DM808 06DA660075 06DA660061 - 06DA660060 06DA660059 06DA660058
- - 06DA660061
809 06DA660061 - 06DA660058
( )313 06DA660078 06DA660064 - 06DA660056
( )316 06DA660078 06DA660062 06DA660064 06DA660056
518 06DA660078 06DA660064 - 06DA660061 - 06DA660056 06EA660096
( )818 06DA660064 - 06DA660061 - 06DA660056
06D( )724 06DA660063** 06DA660065** 06DA660062 06DA660064 06DA660057
- 06EA660090** - -
06DA660064* - - -
( )824 06DA660063** 06DA660065** 06DA660062 06DA660064
- 06EA660090** - -
06DA660064* - - -
( )337 06DA660065 06EA660090 06DA660064 -
* -- 2 BOLT ** -- 4 BOLT

COMPRESSOR SERVICE VALVE KITS BY VALVE SIZE

KIT CONSISTS OF:


SERVICE VALVE, GASKET AND BOLTS
NOTE: Service Valve contained in kits cannot be ordered separately.

P419

VALVE MUELLER - SERVICE VALVE HENRY - SERVICE VALVE


VALVE
MOUNTING ADAPTER/ ADAPTER/
SIZE KIT VALVE CAP KIT VALVE CAP
(BOLT HOLE TAILPIECE TAILPIECE
(in.) P/N P/N P/N P/N P/N P/N
CENTER-IN) P/N P/N
5/8 FLARE 2 BOLT (1-5/8) NR 06DA660059 EN26AA211 EN99ZA001 - - - -
5/8 SWEAT 2 BOLT (1-5/8) NR 06DA660060 EN32AA250 EN99ZA001 - - - -
2-BOLT (1 -5/8) 06DA660061 EN07AA271 06DA660061 EN07AA271
NR NR NA
7/8 SWEAT 2 BOLT (1 -3/4) 06DA660062 EN07AA284 EN99ZA006 06DA660062 EN07AA284
2 BOLT (2-3/4) EN99ZC027 - EN07AA390 - - - -
4 BOLT (2-1/2) NR 06DA660063 EN07EA033 06DA660063 EN07EA033
NR
1-1/8 SWEAT 2 BOLT (1 -3/4) 06DA660064 EN07AA348 EN99ZA006 06DA660064 EN07AA348
EN99ZA013
2 BOLT (2-3/4) EN99ZC033 - EN07AA395 NA - EN07EC341
1-3/8 SWEAT 4 BOLT (2-1/2) NR 06DA660065 EN07EA039 EN99ZA006 NR - - -
4 BOLT (2-1/2) NR 06EA660090 EN07EA041 EN99ZA006 NR 06EA60090 EN07EA041
1-5/8 SWEAT EN99ZA013
NR - EN13HA045 NA NA - EN13HA045
- EM13FE051
2-1/8 SWEAT 4 BOLT (3-1/16) EM99AA516 EN99ZA009 EP29VC540 06EA660091 EM13FE051 EN99ZA022
- EM13FA516
2-5/8 SWEAT 4 BOLT (3-1/16) EM99AA518 - EM13FA518 - - - - -
3-1/8 SWEAT 4 BOLT (3-7/8) EM99AA520 - EM13FA520 EN99ZA011 EP29VC660 - EM13FE520 EN99ZA018
4-1/8 SWEAT 4 BOLT (4-13/16) NA - EM13FA524 NA NA - EM13FES24 EN99ZA025

NR= Not Required.


NA = Vendor part number available upon request.

151
CARLYLE REFRIGERATION COMPRESSORS
GUIDE TO 06E PART NUMBERING SYSTEM:

DESIGN VARIABLES
SIZE

CHARACTERISTICS

FUTURE DESIGN
CFM

ELECTRICAL

MODEL AND
PACKAGING
CPRSRS

USAGE
PRODUCT
SERIES HOM.H.P.
CPRSR
UNITS

MODEL 0 6 E A 1 5 0 3 4 0
DIGIT 1 2 3 4 5 6 7 8 9 10

1ST, 2HD, 3RD DIGITS


O6E HERMETIC COMPRESSOR
10TH DIGIT PACKAGING
0 MODEL 4
MULTI PACK EXP
NO.
1 LESS 5
4TH DIGIT 4TH DIGIT UHLDADER VARIABLE SINGLE PACK PALLETIZED LESS VALVE
VALVE
SUCTION S
S 2 MULTI PACK DOM 7 PALLETIZED WITH VALVE
CUTOFF L T
E 3 WITH 9 MULTI PACK MC MINN
UNLOADING E A B SINGLE PACK
R VALVE
T N O
V DESCRIPTION
T D T
I
E A H
C
R R
E
D 9TH DIGIT SERVICE DESIGN VARIABLE
A X NO UNLOADERS 1 THERMOTECTOR PROTECTION OLD STYLE
2 B X ONE UNLOADER - ELECTRIC CRANKCASE
2 NEW MANUFACTURE SERVICE COMPRESSOR
3 C X TWO UNLOADERS - ELECTRIC
3 FUTURE USE
4 D X ONE UNLOADER - PRESSURE
4 REMANUFACTURED SERVICE COMPRESSOR
5 E X TWO UNLOADERS - PRESSURE LOW TEMP
F X NO UNLOADERS 5 OLD STYLE CRANKCASE ROBERTSHAW SEN-
HEAD 6 CYL.

SEE NOTE 2
REVERSED

6 J X ONE UNLOADER - ELECTRIC SORS & TAPPED CYL. HDS. MOTOR PROTEC-
7 K X TWO UNLOADERS - ELECTRIC TION KIT REQD. FOR THERMOTECTOR
8 L X ONE UNLOADER - PRESSURE APPLICATION
9 N X TWO UNLOADERS - PRESSURE 6 REMANUFACTURED SERVICE COMPRESSOR
7 REMANUFACTUREO SERVICE COMPRESSOR
G X NO UNLOADERS - PRESSURE
USED BY CAC
CPRSR WITH

MED. TEMP.
FOR UNITS

P X ONE UNLOADER - ELECTRIC


CONT BOX

U X TWO UNLOADERS - ELECTRIC


V X ONE UNLOADER - PRESSURE
9TH DIGIT PROD. DESIGN VARIABLE
W X TWO UNLOADERS - PRESSURE
0 OEM MODEL
M X MEDIUM TEMP. - NO UNLOADERS
1 ELECTRICAL REDESIGN
R X REFRIGERATION - NO UNLOADERS 2
SERVICE CMPRSR. w/ 3 FIRST REDESIGN
REPLACES 2,
T X (1) BLOCKED SUCTION CUT- LONG STROKE CRANKCASE
3,4, 5, 6, 7, 8 & 9
OFF UNLOADER HEAD 4 SECOND DESIGN
REPLACES A, ROBERTSHAW MOTOR PROTECTION
SERVICE COMPRESSOR -
X X B,C, D, E, F J, K, 5
AIR CONDITION.
L&N 6 CPRSR. MODEL LESS MOTOR PROTECTION
Y X SVC. CPRSR. - REFRIG. REPLACES R 7 MEDIUM TEMP. ROBERTSHAW MOTOR PRO-
TECTION
8
9 CEMAK MODEL

5TH DIGIT USAGE


0 LIGHT DUTY CPRSR. OR 5
CPRSR. UNIT TONNAGE 6
1 MEDIUM DUTY CPRSR. 7
2 HEAVY DUTY CPRSR. 8 SPECIAL ORDER
3 OILLESS 9
4
SYMBOLS:

= SAMPLE PART NO. 06E215O36O


8TH DIGIT ELECT NOTES:
6TH & 7TH DIGIT COMPRESSOR SIZE
1 575 - 3 - 60 4. 220-3-60 UNIT DESIGNED FOR USE ON 198 to 242 V
NO. STD. LONG STROKE LONG STROKE SHORT
2 200 - 1 - 60 380-3-60 342 418 V
CYL. PROD. STD. CLEARANCE HI CLEARANCE STROKE
3 208/230/460 - 3 - 60 575-3-60 518 660 V
4 50 CFM 66 CFM 60 CFM --
4 200 - 3 - 60 460-3-60 414 529 V
6 75 CFM 99 CFM -- 65 CFM
5 230 - 3 - 60 230-3-60 198 264 V
6 400 - 3 - 50 230-3-50 198 264 V
460 -3 - 60 400-3-50 342 457 V
COMPRESSOR UNITS (CAC USAGE) 7 230 - 1 - 50 200-3-60 180 229 V
NO 8 230 - 3 - 50 5. RVS HD CPRSR -- ORIGINAL DESIGN NO. 4TH DIGIT A, B, C, D, CRF
STD. PROD. CPRSR. LONG STROKE CPRSR.
CYL. 9 220/380 - 3 - 60 9TH DIGIT
4 22 (NOM TONS) -- 0 208/230 - 3 - 60 REDESIGN NO. 4TH DIGIT F, J, K. L OR N
6 33 (NOM TONS) 44 (NOM TONS) A 415 - 3 - 50 9TH DIGIT SAME AS STANDARD

152
CARLYLE REFRIGERATION COMPRESSORS
06E REFRIGERATION AND MEDIUM TEMPERATURE DUTY COMPRESSOR
APPLICATION DATA

For mounting configuration,


dimensions and weight refer to
outline drawings on previous
pages.
P52

CAPACITY (000 BTUH)


20 SST
CFM -25 SST 15 SST 40 SST
NO. SUCTION TEMP. RANGE* 120
MODEL @ 110 SCT 110 SCT 120 SCT
HP OF (F) SCT
NO. 1750 65 SGT 65 SGT 60 SGT
CYL. 65 SGT
RPM 0 SC 0 SC 0 SC
0 SC
R-502 R-12 R-22 R-502 R-502 R-12 R-22
06EY150 15 4 50.3 -40 to 10** -10 to 40 - 54.5 - 92.1 -
06EZ150 15 4 50.3 -10 to 40 -10 to 40 -10 to 40 - 139.0 82.6 219.7
06EY166 20 4 66.0 -40 to 10** -10 to 40 - 68.0 - 109.0 -
06EZ266 25 4 66.0 -10 to 40 - -10 to 50 - 180.0 - 277.0
06EY165 20 6 65.0 -40 to 10** -10 to 40 - 68.3 - 121.7 -
06EY175 20 6 75.4 -40 to 1** -10 to 40 - 78.6 - 135.7 -
06EZ175 25 6 75.4 -10 to 40 -10 to 40 -10 to 50 - 207.5 121.0 323.8
06EY099 30 6 99.0 -40 to 10** -10 to 40 - 104.0 - 172.4 -
06EZ199 35 6 99.0 -10 to 40 -10 to 40 -10 to 50 - 280.0 163.4 422.6
*Condensing temperature range 80 to 120 F.
**Cylinder Head Cooling Fan is required to operate at minimum suction temperatures.

153
CARLYLE REFRIGERATION COMPRESSORS
06E COMPRESSOR DATA - THREE PHASE
LOW TEMP. & MED. TEMP. REFRIGERATION
OIL
COMPRESSOR MAX. MAX.
VOLT HP CFM CHG. MTA LRA
MODEL NO. WATTS RLA*
PINTS
4 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ
06EY150-140 575 15 50.3 14 22,000 31 38 98
06EY150-340 208-230/460 15 50.3 14 22,000 72/36 90/45 283/142
06EY166-140 575 20 66 14 25,300 36 45 120
06EY166-340 208-230/460 20 66 14 25,300 87/44 108/54 345/173
06EY166-640 ** 460 20 66 14 25,300 45 56 150
4 CYLINDER ... LOW TEMP. REFRIGERATION ... 50 HZ
06EY150-340 200/400 15 41.7 14 18,300 72/36 90/45 283/142
06EY166-340 200/400 20 55 14 28,000 87/44 108/54 345/173
06EY166-640 ** 400 20 55 14 28,000 45 56 150
6 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ
06EY165-140 575 20 65 19 25,300 36 45 120
06EY165-340 208-230/460 20 65 19 25,300 87/44 108/54 345/173
06EY165-640 ** 460 20 65 19 25,300 44 54 173
06EY175-140 575 20 75.4 19 25,300 36 45 120
06EY175-340 208-230/460 20 75.4 19 25,300 87/44 108/54 345/173
06EY175-640 ** 460 20 75.4 19 25,300 45 56 150
06EY099-140 575 30 99 19 39,100 52 65 176
06EY099-340 208-230/460 30 99 19 39,100 135/68 168/84 506/253
06EY099-640 ** 460 30 99 19 39,100 65 81 220
6 CYLINDER ... LOW TEMP. REFRIGERATION ... 50 HZ
06EY165-340 200/400 20 54 19 21,100 87/44 108/54 345/173
06EY165-640 ** 400 20 54 19 21,100 44 54 173
06EY175-340 200/400 20 62.5 19 21,100 87/44 108/54 345/173
06EY175-640 ** 400 20 62.5 19 21,100 45 56 150
06EY099-340 200/400 30 82.5 19 32,600 135/68 168/84 506/253
06EY099-640 ** 400 30 82.5 19 32,600 65 81 220
4 CYLINDER ... MEDIUM TEMP. REFRIGERATION ... 60 HZ
06EZ150-170 575 15 50.3 14 22,000 31 38 98
06EZ150-370 208-230/460 15 50.3 14 22,000 72/36 90/45 283/142
06EZ266-170 575 25 66 14 33,600 46 57 164
06EZ266-370 208-230/460 25 66 14 33,600 112/56 140/170 446/223
06EZ266-670 ** 460 25 66 14 33,600 57 71 205
4 CYLINDER ... MEDIUM TEMP. REFRIGERATION ... 50 HZ
06EZ150-370 200/400 15 41.7 14 18,300 72/36 90/45 283/142
06EZ266-370 200/400 25 55 14 28,000 112/56 140/170 446/223
06EZ266-670 ** 400 25 55 14 28,000 57 71 205
6 CYLINDER ... MEDIUM TEMP. REFRIGERATION ... 60 HZ
06EZ175-170 575 25 75.4 19 33,600 46 57 164
06EZ175-370 208-230/460 25 75.4 19 33,600 112/56 140/70 446/223
06EZ175-670 ** 460 25 75.4 19 33,600 57 71 205
06EZ199-170 575 35 99 19 47,600 65 82 212
06EZ199-370 208-230/460 35 99 19 47,600 155/77 193/96 610/305
06EZ199-670 ** 460 35 99 19 47,600 82 102 265
6 CYLINDER ... MEDIUM TEMP. REFRIGERATION ... 50 HZ
06EZ175-370 200/400 25 62.5 19 28,000 112/56 140/170 446/223
06EZ175-670 ** 400 25 62.5 19 28,000 57 71 205
06EZ199-370 200/400 35 82.5 19 39,700 155/77 193/96 610/305
06EZ199-670 ** 400 35 82.5 19 39,700 82 102 265
*This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in much lower
RLA values.
**Order the discrete 400/460-3-50/60 volt compressor for part wind start applications only. When ordering, place the letters PW after the model num-
ber, (i.e., 06EX299660PW).

Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.

154
CARLYLE REFRIGERATION COMPRESSORS
REQUIRED CIRCUIT BREAKERS: 06E ... 60 HZ
CIRCUIT CIRCUIT CIRCUIT
COMPRESSOR COMPRESSOR COMPRESSOR
BREAKERS BREAKERS BREAKERS
MODEL NO. MODEL NO. MODEL NO.
P/N P/N P/N
06EY150-140 HH83XA460 06EY175-140 HH83XA461 HH83XE621
HH83XE633 HH83XE622 06EZ266-370 HH83XC409
06EY150-340 HH83XB360 06EY175-340 HH83XB336 HH83XA426
HH83XA463 HH83XA424 06EZ266-670 HH83XE630
06EY166-140 HH83XA461 06EY175-640 HH83XE626 06EZ175-170 HH83XA469
HH83XE622 06EY099-140 HH83XA430 HH83XE621
06EY166-340 HH83XB336 HH83XE652 06EZ175-370 HH83XC409
HH83XA424 06EY099-340 HH83XC439 HH83XA426
06EY166-640 HH83XE626 HH83XA425 06EZ175-670 HH83XE630
06EY165-140 HH83XA461 06EY099-640 HH83XE642 06EZ199-170 HH83XA453
HH83XE622 06EZ150-170 HH83XA460 HH83XE609
06EY165-340 HH83XB336 HH83XE633 06EZ199-370 HH83XC432
HH83XB437 06EZ150-370 HH83XB356 HH83XA547
06EY165-640 HH83XE626 HH83XA463 06EZ199-670 HH83XE623
06EZ266-170 HH83XA469

REQUIRED CIRCUIT BREAKERS: 06E ... 50 HZ

CIRCUIT CIRCUIT CIRCUIT


COMPRESSOR COMPRESSOR COMPRESSOR
BREAKERS BREAKERS BREAKERS
MODEL NO. MODEL NO. MODEL NO.
P/N P/N P/N
HH83XE633 06EY175-640* HH83XE626 06EZ266-670 HH83XE630
06EY150-340 HH83XB360 HH83XE652 HH83XE621
HH83XA463 06EY099-340 HH83XC439 06EZ175-370 HH83XC409
HH83XE622 HH83XA425 HH83XA426
06EY166-340 HH83XB336 06EY099-640 HH83XE642 06EZ175-670 HH83XE630
HH83XA424 HH83XE633 HH83XE609
06EY166-640 HH83XE626 06EZ150-370 HH83XB356 06EZ199-370 HH83XC432
HH83XE622 HH83XA463 HH83XA547
06EY165-340 HH83XB336 HH83XE621 06EZ199-670 HH83XE623
HH83XB437 06EZ266-370 HH83XC409
06EY165-640 HH83XE626 HH83XA426
HH83XE622
06EY175-340 HH83XB336
HH83XA424

NOTE: Circuit breakers listed for Discrete 460V Compressors are sized for part wind start.
This circuit breaker is used when Multi-Volt Compressor is connected for 208/230V PWS operation.

This circuit breaker is used when Multi-Volt Compressor is connected for 208/230V XL operation.

This circuit breaker is used when Multi-Volt Compressor is connected for 460V XL operation.
Accessory Screw Package for Circuit Breakers (Required) - P/N 06EA660102 (not used with HH83XA4_- Series Breakers).

Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.

155
CARLYLE REFRIGERATION COMPRESSORS
REQUIRED ACCESSORIES - 06E
OPTIONAL ACCESSORIES
ALTERNATE ALTERNATE
SUCTION DISCHARGE
COMPRESSOR TERMINAL SUCTION DISCHARGE SUSPENSION MOUNTING
SERVICE SERVICE
MODEL NO. BOX KIT SERVICE SERVICE KIT PLATE KIT
VALVE KIT VALVE KIT
VALVE KIT VALVE KIT
06EY150 06EA660095 06EA660091 - 06DA660064 - 06EA660089 06EA660096
166 - 06DA660064 -
175 - 06DA660065 06EA660090
099 - 06DA660065 06EA660090
06EZ150 - 06DA660064 -
266 - 06DA660064 -
175 - 06DA660065 06EA660090
199 - 06DA660065 06EA660090

156
VALVES
COMPRESSOR SERVICE VALVE KITS BY VALVE SIZE

KIT CONSISTS OF:


SERVICE VALVE, GASKET AND BOLTS
NOTE: Service Valve contained in kits cannot be ordered separately.

P419

VALVE MUELLER - SERVICE VALVE HENRY - SERVICE VALVE


VALVE
MOUNTING ADAPTER/ ADAPTER/
SIZE KIT VALVE CAP KIT VALVE CAP
(BOLT HOLE TAILPIECE TAILPIECE
(in.) P/N P/N P/N P/N P/N P/N
CENTER-IN) P/N P/N
5/8 FLARE 2 BOLT (1-5/8) NR 06DA660059 EN26AA211 EN99ZA001 - - - -
5/8 SWEAT 2 BOLT (1-5/8) NR 06DA660060 EN32AA250 EN99ZA001 - - - -
2-BOLT (1 -5/8) 06DA660061 EN07AA271 06DA660061 EN07AA271
NR NR NA
7/8 SWEAT 2 BOLT (1 -3/4) 06DA660062 EN07AA284 EN99ZA006 06DA660062 EN07AA284
2 BOLT (2-3/4) EN99ZC027 - EN07AA390 - - - -
4 BOLT (2-1/2) NR 06DA660063 EN07EA033 06DA660063 EN07EA033
NR
1-1/8 SWEAT 2 BOLT (1 -3/4) 06DA660064 EN07AA348 EN99ZA006 06DA660064 EN07AA348
EN99ZA013
2 BOLT (2-3/4) EN99ZC033 - EN07AA395 NA - EN07EC341
1-3/8 SWEAT 4 BOLT (2-1/2) NR 06DA660065 EN07EA039 EN99ZA006 NR - - -
4 BOLT (2-1/2) NR 06EA660090 EN07EA041 EN99ZA006 NR 06EA60090 EN07EA041
1-5/8 SWEAT EN99ZA013
NR - EN13HA045 NA NA - EN13HA045
- EM13FE051
2-1/8 SWEAT 4 BOLT (3-1/16) EM99AA516 EN99ZA009 EP29VC540 06EA660091 EM13FE051 EN99ZA022
- EM13FA516
2-5/8 SWEAT 4 BOLT (3-1/16) EM99AA518 - EM13FA518 - - - - -
3-1/8 SWEAT 4 BOLT (3-7/8) EM99AA520 - EM13FA520 EN99ZA011 EP29VC660 - EM13FE520 EN99ZA018
4-1/8 SWEAT 4 BOLT (4-13/16) NA - EM13FA524 NA NA - EM13FES24 EN99ZA025

NR= Not Required.


NA = Vender part number available upon request.

157
CARLYLE REFRIGERATION COMPRESSORS
TOTALINE COMPRESSOR OILS - FOR CARLYLE AND TOTALINE COMPRESSORS

REFRIGERANT R-507,
REFRIGERANT R-12, R-22 REFRIGERANT R-507, REFRIGERANT R-134A
R-404A
COMPRESSOR (L & H TEMP.) R-404A (LOW. TEMP (M & H TEMP)
(MED. TEMP)
MODEL
TOTALINE TOTALINE TOTALINE TOTALINE
OIL MODEL OIL MODEL OIL MODEL OIL MODEL
PART NO. PART NO. PART NO. PART NO.

Carlyle 06D, E semi- Zerol 150 SW68 E68 SW68


P903-2001 P903-1001 P903-1725 P903-1001
hermetic (Do not use
P903-2005 P903-1025 P903-1701 P903-1025
SW-68 for Low
P903-2025 P903-1005 P903-1705 P903-1005
Temp)

RO 15 P903-0101
P903-0105
P903-0155

Carlyle 5F/H open Zerol 150 SW68 E68 SW 68


P903-2001 P903-1001 P903-1725 P903-1001
(Do not use
P903-2005 P903-1025 P903-1701 P903-1025
SW-68 for Low
P903-2025 P903-1005 P903-1705 P903-1005
Temp)
RO 15 P903-0101
P903-0105
P903-0155

Carlyle 05T/06T E-100 P903-1501 E-100 P903-1501 E-100 P903-1501 E-100 P903-1501
Screw (74) P903-1505 P903-1505 P903-1505 P903-1505
P903-1525 P903-1525 P903-1525 P903-1525

Carlyle 06N Screw N/A N/A N/A N/A N/A N/A SW-220 P903-1201
(104 mm Global Chiller) (R-134a Only) P903-1225
P903-1205

Millennium Scroll Zerol 150 P903-2001 N/A N/A N/A N/A Mobil Arctic 68
Technologies P903-2005 Model now
P903-2025 obsolete

158
OILS
TOTALINE OILS
MINERAL REFRIGERATION OILS VACUUM PUMP OIL

This is a refined oil used specifically A highly purified purpose vacuum


for air conditioning and refrigera- pump oil that cleans and lubricates.
tion. The low moisture content The quart bottle (9.5 liters) has a
means less failure. A non-foaming, convenient flip-top-cap.
wax-free oil to prevent plugged cap-
illaries and sticking expansion
valves. OEM approved by most
manufacturers.

P893 P894

P/N SIZE VISCOSITY P/N SIZE


P903-0101 1 GAL (3.8 liters) 150 P903-0632 1 QT (.95 liters)
P903-0105 5 GAL (18.9 liters) 150 P903-0601 1 GAL (3.8 liters
P903-0155 55 GAL (208.2 liters) 150 P903-0605 5 GAL (18.9 liters)
P903-0201 1 GAL (3.8 liters) 300 P903-0655 55 GAL (208.2 liters)
P903-0205 5 GAL (18.9 liters) 300
P903-0255 55 GAL (208.2 liters) 300
P903-0301 1 GAL (3.8 liters) 500
P903-0305 5 GAL (18.9 liters) 500 ALKYLBENZENE REFRIGERATION OILS
P903-0355 55 GAL (208.2 liters) 500

POLYOL-ESTER OILS

P1545

The Z-Series are high quality synthetic Alkylbenzene Refrigera-


P1544
tion fluids for us with HCFC, CFC and ammonia refrigerants in
refrigeration and air conditioning applications.
These environmentally friendly products are specifically formu-
lated to use with the non-CFC refrigerant R-134a. The base flu- Due to superior miscibility, Totaline Z-Series lubricants are excel-
ids have been engineered to be totally miscible with R134a over lent for systems utilizing environmentally sound refrigerants
a very wide temperature range while maintaining excellent lubri- MP39, MP60, HP80 or HP81. Totaline Z-Series are superior
cating properties. products for all R-22, R-123 and R-502 Systems, particularly at
low temperatures.
Z-200TD is formulated with a unique additive package providing
P/N SIZE TYPE extreme pressure (EP) lubricity and foam control at operating
P903-1025 1 QT (,95 liters) SW68 conditions.
P903-1001 1 GAL (3.8 liters) SW68
P903-1005 5 GAL (18.9 liters) SW68 P/N SIZE TYPE
P903-1125 1 QT (.95 liters) SW32 P903-2025 1 QT (,95 liters) Z-150
P903-1101 1 GAL (3.8 liters) SW32 P903-2001 1 GAL (3.8 liters) Z-150
P903-1105 5 GAL (18.9 liters) SW32 P903-2005 5 GAL (18.9 liters) Z-150
P903-1225 1 QT (,95 liters) SW220 P903-2125 1 QT (.95 liters) Z-200TD
P903-1201 1 GAL (3.8 liters SW220 P903-2101 1 GAL (3.8 liters) Z-200TD
P903-1205 5 GAL (18.9 liters) SW220 P903-2105 5 GAL (18.9 liters) Z-200TD
P903-2225 1 QT (.95 liters) Z-300
P903-2201 1 GAL (3.8 liters Z-300
P903-2205 5 GAL (18.9 liters) Z-300

159
CARLYLE REFRIGERATION COMPRESSORS
06CY REFRIGERATION DUTY COMPRESSOR APPLICATION DATA
CARLYLE COMPOUND COOLINGTM ...
An innovative approach to low temperature refrigeration from Carlyle.

TWO-STAGE COMPRESSION IN A SINGLE COMPRESSOR USES R-22 WITH THE


EFFICIENCY AND RELIABILITY OF R-502

LOW COMPRESSION RATIOS CONSTANT CAPACITY REDUCES


TWO-STAGE BOOSTER STRESS RESULTING FROM SHORT
PERFORMANCE CYCLING
P53
SAME CAPACITIES AS R-502 IDENTICAL OIL CONTROL TO R-502
COMPRESSORS RACK SYSTEMS
For mounting configuration, dimen- EASY APPLICATION OF LOW OIL CIRCULATION RATES
sions and weight refer to outline SUBCOOLING SIMILAR DIMENSIONS TO OTHER
drawings on following page. CARLYLE MODELS FOR EASY FIT
SUBCOOLING CONTROL ALLOWS
CONSTANT CAPACITY OVER A
WIDE OPERATING RANGE

HOW COMPOUND COOLINGTM WORKS


A variation of the two-stage booster system, the internally compounded compressor has both the high and low stages built into one
compressor body. In this arrangement, compression is accomplished in two stages, safely and economically.
All nine Compound Cooling models have six cylinders. Four cylinders, acting as the low stage, boost the suction pressure from the
refrigeration load to the intermediate pressure. The remaining two cylinders, acting as the high stage, complete the compression to
normal condensing temperatures. The result is lower internal losses and a compressor that delivers more capacity in the same dis-
placement. The lower losses also produce operating efficiencies that are substantially higher than the competition.

R-22 CAPACITY
(000 BTUH)
NO. CFM SUCTION TEMP. RANGE* OIL
-25 SST
MODEL NO. HP OF @ (DEGREES F) CHARGE
110 SCT
CYL. RPM R-22 (PINTS)
65 SGT
40 LIQUID
06CY016 5.0 6 16 -40 to -15 17.6 10
06CY018 5.0 6 18 -40 to -15 22.6 10
06CY124 6.5 6 24 -40 to -15 24.6 10
06CY228 7.5 6 28 -40 to -15 29.5 10
06CY337 10.0 6 37 -40 to -15 39.9 10
06CY550 15.0 6 50 -40 to -15 56.3 19
06CY665 20.0 6 65 -40 to -15 71.4 19
06CY675 20.0 6 75 -40 to -15 80.6 19
06CY899 30.0 6 99 -40 to -15 103.4 19
*Condensing temperature range 60 to 130 F Cylinder Head Cooling Fans recommended for all applications.

160
CARLYLE REFRIGERATION COMPRESSORS
06CY OUTLINE DRAWINGS
NOTE: COMPRESSORS SHOWN WITH OPTIONAL ACCESSORIES - CONTACT YOUR DISTRIBUTOR FOR DETAILS.
06CC COMPRESSORS
06CY016 06CY018 06CY228 06CY337
MOTOR HORSEPOWER 5 5 7.5 10
NO. OF CYLINDERS 6* 6* 6* 6*
BORE AND STROKE (in.) 2.0 x 2.0 x 2.0 x 1.47 2.0 x 1.94
DISPLACEMENT CFM AT 1750 RPM 16 18 28 37
OIL, CHARGE, PINTS CPP33-2 10 10 10 10
DRY WEIGHT LESS SERVICE VALVES 340 LBS 340 LBS 340 LBS 345 LBS

* 4 FIRST STAGE, 2 SECOND STAGE.

06CC COMPRESSORS
06CY550 06CY665 06CY675 06CY899
MOTOR HORSEPOWER 15.0 20.0 50.0 30.0
NO. OF CYLINDERS 6* 6* 6* 6*
BORE AND STROKE (in.) 2.69 x 2.16 2.69 x 1.96 2.69 x 2.19 2.69 x 2.87
DISPLACEMENT CFM AT 1750 RPM 50 65 75 99
OIL, CHARGE, PINTS CPP33-2 19 19 19 19
DRY WEIGHT LESS SERVICE VALVES 545 LBS 555 LBS 555 LBS 580 LBS

* 4 FIRST STAGE, 2 SECOND STAGE.

161
CARLYLE REFRIGERATION COMPRESSORS
06CY COMPRESSOR DATA - THREE PHASE
LOW TEMP. REFRIGERATION - COMPOUND COOLING MODELS
OIL
COMPRESSOR MAX. MAX.
VOLT HP CFM CHG. MTA LRA
MODEL NO. WATTS RLA*
PINTS
6 CYLINDER ... LOW TEMP. REFRIGERATION ... 60 HZ
06CY016-D103 208/230 5.0 16 10 4,600 19.3 27.0 100
06CY016-G103 460 5.0 16 10 4,600 9.6 13.5 50.0
06CY016-J103 575 5.0 16 10 4,600 7.7 10.8 40.0
06CY018-DI03 208/230 5.0 18 10 5,000 19.3 27.0 100
06CY018-G103 460 5.0 18 10 5,000 9.6 13.5 50.0
06CY018-J103 575 5.0 18 10 5,000 7.7 10.8 40.0
06CY124-D103 208/230 6.5 24 10 6,500 23.6 33.0 160
06CY124-G103 460 6.5 24 10 6,500 11.8 16.5 80.0
06CY124-J103 575 6.5 24 10 6,500 9.4 13.2 64.0
06CY228-D103 208/230 7.5 28 10 7,600 29.7 41.6 198
06CY228-G103 460 7.5 28 10 7,600 14.9 20.9 99.0
06CY228-J103 575 7.5 28 10 7,600 11.9 16.7 79.0
06CY337-D103 208/230 10 37 10 10,000 33.2 46.5 228.0
06CY337-G103 460 10 37 10 10,000 16.6 23.3 114.0
06CY337-J103 575 10 37 10 10,000 13.4 18.8 91.0
06CY550-E103 208-230/460 15 50 19 13,000 37.1/18.6 52/26 283/142
06CY550-F103 460 15 50 19 13,000 18.6 26.0 142
06CY550-J103 575 15 50 19 13,000 15.0 21.0 98.0
06CY665-E103 208-230/460 20 65 19 16,800 60.7/30.0 85/42 345/173
06CY665-F103 460 20 65 19 16,800 30.0 42.0 173
06CY665-J103 575 20 65 19 16,800 23.6 33.0 120
06CY675-E103 208-230/460 20 75 19 19,000 60.7/30.0 85/42 345/173
06CY675-F103 460 20 75 19 19,000 30.0 42.0 173
06CY675-J103 575 20 75 19 19,000 26.4 33.0 120
06CY899-E103 208-230/460 30 99 19 26,000 92.9/46.4 130/65 506/253
06CY899-F103 460 30 99 19 26,000 46.4 65.0 253
06CY899-J103 575 30 99 19 26,000 37.1 52.0 175
6 CYLINDER ... LOW TEMP. REFRIGERATION ... 50 HZ
06CY016-G103 400 5 13.2 10 3,800 9.6 13.5 50.0
06CY018-G103 400 5 15.0 10 4,200 9.6 13.5 50.0
06CY124-G103 400 6.5 20.0 10 5,400 11.8 16.5 80.0
06CY228-G103 400 7.5 23.3 10 6,300 14.9 20.9 99.0
06CY337-G103 400 10 30.8 10 8,300 16.6 23.3 114.0
06CY550-E103 200/400 15 41.7 19 11,000 37.1/18.6 52.0/26.0 283/142
06CY550-F103 400 15 41.7 19 11,000 18.6 26.0 142
06CY665-E103 200/400 20 54 19 14,000 60.7/30.0 85.0/42.0 345/173
06CY665-F103 400 20 54 19 14,000 30.0 42.0 173
06CY675-E103 200/400 20 62.5 19 14,000 60.7/30.0 85.0/42.0 345/173
06CY675-F103 400 20 62.5 19 14,000 30.0 42.0 173
06CY899-E103 200/400 30 82.5 19 2,1700 92.9/46.4 130/65.0 506/253
06CY899-F103 400 30 82.5 19 21,700 46.4 65.0 253
*This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in much
lower RLA values.

Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.

162
CARLYLE REFRIGERATION COMPRESSORS
REQUIRED CIRCUIT BREAKERS: 06CY ... 60 HZ
CIRCUIT CIRCUIT CIRCUIT
COMPRESSOR COMPRESSOR COMPRESSOR
BREAKERS BREAKERS BREAKERS
MODEL NO. MODEL NO. MODEL NO.
P/N P/N P/N
HH83XB560 06CY665-F100 HH83XB447 HH83XB346
06CY550-E100 06CY899-E100
HH83XB548 06CY665-J100 HH83XB555 HH83XB402
06CY550-F100 HH83XB548 HH83XB376 06CY899-F100 HH83XB402
06CY675-E100
06CY550-J100 HH83XB547 HH83XB559 06CY899-J100 HH83XB437
HH83XB376 06CY675-F100 HH83XB559
06CY665-E100
HH83XB447 06CY675-J100 HH83XB430

REQUIRED CIRCUIT BREAKERS: 06CY ... 50 HZ


CIRCUIT CIRCUIT CIRCUIT
COMPRESSOR COMPRESSOR COMPRESSOR
BREAKERS BREAKERS BREAKERS
MODEL NO. MODEL NO. MODEL NO.
P/N P/N P/N
HH83XB560 HH83XB376 HH83XB346
06CY550-E100 06CY675-E100 06CY899-E100
HH83XB548 HH83XB559 HH83XB402
06CY550-F100 HH83XB548 06CY675-F100 HH83XB559 06CY899-F100 HH83XB402
HH83XB376
06CY665-E100
HH83XB447
06CY665-F100 HH83XB447

NOTE: Circuit breakers listed for Discrete 460V Compressors are sized for part wind start.
This circuit breaker is used when Multi-Volt Compressor is connected for 208/230V PWS operation.
This circuit breaker is used when Multi-Volt Compressor is connected for 208/230V XL operation.
This circuit breaker is used when Multi-Volt Compressor is connected for 460V XL operation.

Accessory Screw Package for Circuit Breakers (Required) - P/N 06EA660102 (not used with HH83XA4_- Series Breakers).

Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.

163
CARLYLE REFRIGERATION COMPRESSORS
REQUIRED ACCESSORIES - 06CY

REQUIRED ACCESSORIES - 06CY OPTIONAL ACCESSORIES


ALTERNATE ALTERNATE
SUCTION SUCTION DISCHARGE DISCHARGE
SERVICE SERVICE SERVICE SERVICE SUSPENSION MOUNTING
COMPRESSOR VALVE KIT VALVE KIT VALVE KIT VALVE KIT KIT PLATE KIT
MODEL NO. P/N P/N P/N P/N P/N P/N
06CY016 06DA660063 06DA660065 06DA660062 06DA660064 06DA660057 06EA660096
06EA660090 - -
06CY018 06DA660065 06EA660090 06DA660062 06DA660064
06DA660063 - -
06CY124 06DA660065 06EA660090 06DA660062 06DA660064
06DA660063 - -
06CY228 06DA660065 06EA660090 06DA660062 06DA660064
06DA660063 - -
06CY337 06DA660090 06EA660065 06DA660064 06DA660062
06DA660063 - -
06CY550 06EA660090 - 06DA660065 06EA660090 06EA660089
06CY665 06EA660090 - 06DA660065 06EA660090
06CY675 06EA660090 - 06DA660065 06EA660090
06CY899 06EA660090 - 06DA660065 06EA660090

164
HERMETIC REFRIGERATION COMPRESSORS
COPELAND AFTERMARKET REFRIGERATION COMPRESSORS

P6 P7

Nominal Performance 5% After 72 Run-In


60 Hertz Conditions (F) Evap/Cond/Return Gas/Liquid/Ambient
Amperage
R404A/507 Extended Med Temp. 20/120/40/120/95 F -10/120/40/120/95 F Ratings
WATT
Copeland P/N HP Volt/Phase CFM BTUH WATTS AMPS EER BTUH AMPS EER RLA LRA MCC
S
RS43C1E-CAA-958 0.5 115-1 113 4,170 944 10.6 4.4 1,720 600 7.2 2.9 10.1 51 14.2
RS43C1E-IAA-958 0.5 115-1 113 4,170 944 10.6 4.4 1,720 596 8.1 2.9 10.1 51 14.2
RS43C1E-CAV-958 0.5 208/230-1 113 4,170 944 5.6 4.4 1,720 600 4.3 2.9 5.4 24.1 7.5
RS43C1E-IAV-958 0.5 208/230-1 113 4,170 944 5.6 4.4 1,720 600 4.3 2.9 5.7 24.1 8
RS64C1E-CAA-958 0.75 115-1 162 6,460 1470 12.9 4.4 2,860 1050 9.3 2.7 15.2 59 21.2
RS64C1E-IAA-958 0.75 115-1 162 6,460 1470 12.9 4.4 2,860 1050 9.3 2.7 17.5 76.7 24.5
RS64C1E-PAA-958 0.75 115-1 162 6,460 1470 12.9 4.4 2,860 1050 9.3 2.7 15.2 59 21.2
RS64C1E-CAV-958 0.75 208/230-1 162 6,450 1460 6.4 4.4 2,860 1050 4.6 2.7 7.7 37 10.8
RS64C1E-IAV-958 0.75 208/230-1 162 6,450 1460 8.6 4.4 2,860 1050 6.2 2.7 9.2 45 12.9
RS97C1E-CAA-959 1.5 115-1 245 9,590 1940 19.4 4.9 3,820 1250 14.4 3.1 19.6 95 29
RS97C1E-CAV-959 1.5 208/230-1 245 9,590 1940 9.7 4.9 3,820 1250 7.2 3.1 11 51 15.4
RS97C1E-TFC-959 1.5 208/230-1 245 9,400 1890 6.3 5 3,750 1210 4.7 3.1 7 35 9.8
CS12K6E-PFV-970 2 208/230-1 320 12,000 1930 8.8 6.2 3,990 1120 5.4 3.6 10.9 56 15.3
CS12K6E-PFJ-970 2 265-1 320 12,000 1930 7.6 6.2 3,990 1120 4.7 3.6 10.9 55 15.2
CS12K6E-TF5-970 2 208/230-3 320 11,700 1860 5.8 6.3 3,830 1090 3.6 3.5 7.5 51 10.5
CS14K6E-PFV-970 2.5 208/230-1 350 14,100 2280 10.3 6.2 5,440 1420 6.6 3.8 12.4 61 17.4
CS14K6E-PFJ-970 2.5 265-1 350 14,100 2280 8.9 6.2 5,440 1420 5.7 3.8 12.5 58 17.5
CS14K6E-TF5-970 2.5 208/230-3 350 13,800 2210 6.9 6.2 5,330 1370 4.5 3.9 9.1 55 12.8
CS14K6E-TFD-970 2.5 208/230-3 350 13,800 2210 3.4 6.2 5,330 1370 2.2 3.9 4.7 28 6.6
CS20K6E-PFV-970 3 208/230-1 535 20,000 3120 14.9 6.4 7,050 1850 10 3.8 18.6 96 26
CS20K6E-TF5-970 3 208/230-3 535 19,600 3030 10 6.5 6,910 1800 6.7 3.8 11.4 75 16
CS20K6E-TFD-970 3 460-3 535 19,600 3030 5 6.5 6,910 1800 3.4 3.8 5.1 40 7.1
CS27K3E-PFV-970 4 208/230-1 665 26,500 4420 20.3 6 9,370 4460 12.2 3.8 23.9 95.4 33.5
CS27K3E-TF5-970 4 208/230-3 665 26,000 4290 13.1 6.1 9,070 2495 8.1 3.6 15.6 82 21.4
CS27K3E-TFD-970 4 460-3 665 26,000 4290 6.6 6.1 9,070 2495 4.1 3.6 8.5 41 11.8
CS33K3E-PFV-970 5 2230/230-1 756 31,600 5290 25.3 6 11,500 3070 15.8 3.8 30.7 125 43
CS33K3E-TF5-970 5 208/230-3 756 31,200 5190 15.2 6 11,700 2920 9.9 4 20.7 90 29
CS33K3E-TFD-970 5 380/460-3 756 31,200 5190 7.6 6 11,700 2920 5 4 9.9 45 13.8

165
HERMETIC REFRIGERATION COMPRESSORS
COPELAND AFTERMARKET REFRIGERATION COMPRESSORS (cont)
Nominal Performance
60 Hertz Conditions (F): Evap/Cond/Return Gas/Liquid/Ambient
Amperage
R-22 High Temp. 45/130/65/95 F 20/120/65/120/95 F Ratings*
Copeland P/N HP Volt/Phase CFM BTUH WATTS AMPS EER BTUH WATTS AMPS EER RLA LRA MCC
JRF4-0050-IAA-958 0.5 115-1 113 7,360 1090 13 6.8 4320 850 11.6 5.1 13.6 71 19
JRF4-0050-IAV-958 0.5 208/230-1 113 7,360 1090 7 6.8 4320 850 5.8 5.1 6.4 34 9
RRGA-0100-PAA-950 1 115-1 161 10,800 1390 12.6 7.8 6170 1050 9.8 5.9 13.2 60 18.5
RRGA-0100-PAV-950 1 208/230-1 161 10,800 1390 6.3 7.8 6170 1050 4.9 5.9 6 33.5 8.4
CRA1-0150-PFV-970 1.5 208/230-1 242.5 16,960 1870 8.3 9.1 9430 1430 6 6.6 10.8 48 15.1
CRA1-0150-TF5-970 1.5 208/230-1 242.5 17,190 1810 5.8 9.5 9690 1350 5 7.2 9.3 58 13
CRA1-0150-TFC-970 1.5 208/230-1 242.5 17,190 1810 2.9 9.5 9690 1350 3 7.2 4.1 17.4 5.7
REK3-0125-PFV-959 1.25 115-1 174.7 12,500 1440 6 8.7 7090 1110 5.1 6.4 7 34.2 9.8
REK3-0125-TFC-959 1.25 208/230-1 174.7 12,400 1370 3.8 9.1 7370 1020 3.1 7.2 4.7 31 6.6
RSE4-0075-IAA-958 0.75 115-1 135 8,620 1250 15.2 6.9 5060 940 13.2 5.4 14.3 66.3 20
RSE4-0075-IAV-958 0.75 208/230-1 135 8,620 1250 15.2 6.9 5060 940 6.6 5.4 7.1 35.5 10
R-22 Medium Temp. 20/120/40/120/95 F 0/110/40/110/95 F
Copeland P/N HP Volt / Phase CFM BTUH WATTS AMPS EER BTUH WATTS AMPS EER RLA LRA MCC
RSE4-0075-IAA-958 0.75 115-1 135.3 4770 930 6.5 5.1 2630 690 5.8 3.8 14.3 66.3 20
RSE4-0075-IAV-958 0.75 208/230-1 135.3 4770 930 3.3 5.1 2630 690 2.9 3.8 7.1 35.5 10
RSN6-0075-IAA-958 0.75 115-1 162.4 6200 1190 15 5.2 3680 870 13 4.2 14.3 66.3 20
RSN6-0075-IAV-958 0.75 208/230-1 162.4 6200 1190 7.5 5.2 3680 870 6.5 4.2 6.9 45 9.6
RSL2-0101-CAA-959 1 115-1 244.5 9620 1760 18.2 5.5 5500 1300 14.8 4.2 18 78 25.2
RSL2-0101-CAV-959 1 208/230-1 244.5 9620 1760 9.1 5.5 5500 1300 7.4 4.2 10.4 51 14.5

Nomenclature
Compressor Motor Types
Phase Description Code
Copeland Compressor 1 Capacitor Run - Capacitor Start C Bill of Material*
Family Series 1 Induction Run - Capacitor Start I (See Opposite Page)
Either a number or a letter Compressor nominal 1 Capacitor Run - Permanent P
established for each capacity at rating Split Capacitor
product model. conditions to two 3 Three Phase T
significant digits.

X X X X X X E - X X X - X X X

Capacity Indicates
Comp. Motor Rating compressors
Nominal (HP) Code Multiplier
C = 100 with polyolester oil. Electrical Codes
1/2 0050
K = 1000 60 Hz 50 Hz Codes
3/4 0075
1 0100 Code Description 115-1 - A
Compressor Motor Protection 208/230-3 200/220-3 C
1-1/4 0125 R = High Temperature
Type Protection Code 460-3 380/420-3 D
1-1/2 0150 S = Medium Temperature
1-3/4 0175 External Thermal Protection - 575-3 550-3 E
F = Low Temperature
2 0200 One Protector (Line Break) A 265-1 220/240-1 J
T = Two Speed
2-1/4 0225 Use with Contactor Internal - 380/420-3 M
2-3/4 0275 Inherent Protection - 208/230-1 200-1 V
3 0275 One Protector (Line Break) F - 220/240-1 Z
3-1/2 0350 Use with Contactor
Model Variation 200/230-3 200/240-3 5
4 0400
4-1/2 0450 A number or letter,
5 0500 assigned to indicate
7-1/2 7500 different model
9 0900 types within any
10 1000 one family series.
12 1200

166
HERMETIC REFRIGERATION COMPRESSORS
BILL OF MATERIAL INFORMATION
xxxx-xxxx-xxx- The last 3 digits of any model is a unique bill of material.
xxxx-xxxx-xxx- xxs Wholesaler service compressors used to replaces the above bills of material in most
examples: -959 or -970 situations which include oil, protector, terminal box cover, and mounting parts in a
single carton.
The Second Digit xxxx-xxxx-xxx-x x Rotalock connection(s) or a valve welded on the suction side.
xxxx-xxxx-xxx-x x Sweat connections with terminal flag kit, no electrical components.
Copeland CR Compressors primarily
The Third Digit xxxx-xxxx-xxx-xx No electrical components with the compressor.
xxxx-xxxx-xxx-xx Electrical components mounted.
xxxx-xxxx-xxx-xx Electrical components remote, in the box with the service compressor.