J&E Hall
J&E Hall
J&E Hall
Application Manual
HSS 3100 Series Application Manual
©
J & E Hall International 2005
All rights reserved. No part of this publication may be reproduced or transmitted in any form or by
any means, electronic or mechanical, including photocopying, recording or by any information
storage or retrieval system, without permission in writing from the copyright holder.
The copyright in this publication shall be and remain the sole property of J & E Hall International.
Contents
1. General Description ...................................................................................................5
1.1. Main Features......................................................................................................................... 5
1.2. Construction............................................................................................................................ 5
1.2.1. Internal Relief Valve........................................................................................................... 6
1.3. The Compression Process ..................................................................................................... 7
2. Capacity Control and Volume Ratio...........................................................................9
2.1. Slide Valve Actuation ........................................................................................................... 10
2.2. Continuously Variable Capacity Control .............................................................................. 10
2.2.1. Controlled Stop and Start ................................................................................................ 10
2.2.2. Uncontrolled Stop, Restarting After an Uncontrolled Stop.............................................. 10
2.3. Minimum/Maximum Load Indication..................................................................................... 12
2.3.1. Single Compressor Systems ........................................................................................... 12
2.3.2. Multiple Compressor Systems......................................................................................... 12
3. Economiser Facility..................................................................................................14
3.1. Subcooling of Liquid Refrigerant .......................................................................................... 15
3.2. Side Load Operation ............................................................................................................ 15
4. Compressor Lubrication, Sealing and Cooling .........................................................17
4.1. Lubrication Functions ........................................................................................................... 17
4.1.1. Capacity Control Actuation .............................................................................................. 17
4.1.2. Bearing Lubrication .......................................................................................................... 17
4.1.3. Oil Injection for Sealing and Cooling ............................................................................... 17
5. Oil Support System..................................................................................................18
5.1. Oil Drain................................................................................................................................ 18
5.1.1. Oil Heater ......................................................................................................................... 18
5.2. Oil Differential Pressure Monitoring ..................................................................................... 18
5.2.1. ODP1 ............................................................................................................................... 19
5.2.2. ODP2 ............................................................................................................................... 19
5.3. Maintaining Discharge Pressure at Start up ........................................................................ 19
5.4. Liquid Injection Cooling ........................................................................................................ 19
5.4.1. Deciding if Liquid Injection is Required ........................................................................... 21
5.4.2. Liquid Injection Valve Selection....................................................................................... 21
6. Lubricating Oils........................................................................................................23
6.1. Lubricant Types .................................................................................................................... 23
6.1.1. Mineral Oils ...................................................................................................................... 23
6.1.2. Synthetic Lubricants ........................................................................................................ 23
6.1.3. Semi Synthetic Lubricants ............................................................................................... 24
7. Three Function Valve for HSS 3100 Series Compressors .......................................25
8. Integration into the Refrigeration Circuit...................................................................26
8.1. Oil System ............................................................................................................................ 26
8.2. Suction Line .......................................................................................................................... 26
8.3. Liquid Separation in the Suction Line .................................................................................. 26
8.4. Discharge Superheat............................................................................................................ 26
8.5. Safety Requirements for Compressor Protection ................................................................ 26
9. Electrical Connections .............................................................................................27
9.1. Compressor Starting............................................................................................................. 27
9.2. Motor Wiring Connections .................................................................................................... 27
9.3. Thermistors........................................................................................................................... 27
9.4. Capacity Control Solenoids .................................................................................................. 27
List of Figures
Fig 1 Compression Process...................................................................................................................... 8
Fig 2 Capacity Control Mechanism........................................................................................................... 9
Fig 3 Continuously Variable Capacity Control........................................................................................ 11
Fig 4 Economiser Cycle on Pressure/Enthalpy (p-h) Diagram .............................................................. 14
Fig 5 Economiser Arrangements: Wiring to Liquid Line Solenoid Valves.............................................. 16
Fig 6 Oil Differential Pressure Monitoring............................................................................................... 18
Fig 7 Liquid Injection Cooling ................................................................................................................. 20
Fig 8 Typical Methods of Providing Preferential Supply for Injection .................................................... 21
Fig 9 Deciding if Liquid Injection is Required ......................................................................................... 22
Fig 10 Three Function Valve Application for HSS 3100 Series Compressors ...................................... 25
Fig 11 Motor Terminal Box Wiring .......................................................................................................... 28
Fig 12 HSS 3100 Series Compressors Oil Support System .................................................................. 36
List of Tables
Table 1 Minimum Specification of Mineral Oils and Polyolester Lubricants .......................................... 23
1. General Description
The J & E Hall International HSS 3100 series of semi-hermetic integral
compressors are the latest addition to the HallScrew family of oil injected,
positive displacement, single screw compressors. Reflecting the very
latest innovations in screw compressor technology, they are designed for
incorporation into factory built chillers and compressor packs using HFC
refrigerants or R22.
HSS 3100 series compressors are capable of operating without cooling
over a limited range, but when indicated, a suitable cooling system is
required; cooling by liquid injection is the recommended method.
1.1. Main Features
• For use with R134a, R407c and R22.
• Integral oil separator.
• Single-piece casing.
• Designed and tested to international standards.
• Robust construction.
• Improved machine clearance control for maximum efficiency.
• Oil injected for maximum reliability.
• Enhanced slide valve geometry for capacity modulation with
minimum loss of efficiency. Infinite adjustment between
maximum (100 %) and minimum load (nominal 25 %).
• Simple, built-in capacity control using two solenoid valves.
• Economiser facility provided to improve operating efficiency,
especially at high compression ratios.
• Internal suction/discharge safety relief valve.
• High efficiency built in 3 phase, 2 pole motor unit for reliable
operation. Three different motor power options. Available
for 50 Hz or 60 Hz operation.
• Motor designed for star/delta or soft-start.
• Thermistor high temperature protection to motor.
• Thermistor discharge gas high temperature protection.
• Built-in oil filter.
1.2. Construction
The compressor is driven by a specially designed motor mounted on one
end of the compressor main shaft.
The compressor consists of two cast-iron castings which are bolted
together. The first casting is divided into two parts: the main casing,
encloses the motion work comprising the main rotor and star rotor, the
motor housing encloses the 3 phase, 2 pole motor. Returning suction
vapour flows around the start/rotor unit, cooling the windings in the
process, before entering the main rotor flutes. The second casing
provides three functions: a delivery end cover, a separator and an oil filter
housing.
Thermistor probes, buried deep in each phase of the stator windings,
provide protection against high temperatures. Phase wiring and
thermistor terminations are made to a terminal plate inside an enclosure
mounted on the top of the motor housing.
The motion work, i.e. that part of the machine which performs the
compression function, consists of two rotating parts; there are no
eccentric or reciprocating motions. These fundamental components
comprise the cylindrical main rotor in which are formed six-start, helically
grooved screw threads with a spherical (hourglass) root form. The main
rotor meshes with a toothed wheel having eleven teeth. This wheel (or
'star rotor' as it is called owing to the shape), is made from a special
synthetic material. The star is located above the main rotor with its axis
at right angles to the main rotor axis. As the main rotor turns, it imparts a
freely rotating motion to the star rotor.
The star rotor is supported by a metal backing which is cast in one-piece
with the star rotor shafts. Although it is located in place on the backing,
the star is allowed to 'float' a small amount in a rotational sense. This
floating action, combined with the low inertia and negligible power
transmission between the main rotor and star rotor, ensures compliance
of the star/main rotor combination. The star rotor shafts are supported at
each end by taper roller bearings.
The main rotor is supported on a shaft the other end of which carries the
motor rotor. The shaft is supported by an arrangement of rolling element
bearings at two positions. This entire assembly is dynamically balanced.
The main rotor and star rotor is housed inside the main casing. The
inside of this main casing has a somewhat complex shape, but
essentially consists of a specially shaped cylindrical annulus, which
encloses the main rotor leaving a small clearance. Part of the annulus is
cutaway at the suction end to allow the suction gas to enter the rotor. In
addition there is a slot to allow the star tooth to mesh with the main rotor
flutes. The discharge port is positioned at the other end of the annulus
and conveys the compressed gas into the discharge chamber. Suction
pressure prevails throughout the main casing up to the discharge port.
Delivery pressure is maintained in the discharge port, discharge chamber
and oil reservoir.
A cover at the top of the main casing is provided to allow easy access to
the star rotor, star rotor shafts and bearings, without disturbing working
tolerances.
The compressor is fitted with an integral suction strainer, built into the
suction end cover, designed to trap any dirt circulating with the refrigerant
which might otherwise enter and damage the compressor.
The cyclone type separator removes the majority of entrained oil from the
discharge gas stream. Two sight-glasses are provided to check the level
of oil in the reservoir at the bottom of the compressor. The reservoir is
fitted with a 250 W heater.
The discharge connection on the integral oil separator can be fitted with a
specially designed valve which combines the functions of a stop valve,
non-return valve and head pressure control valve in one compact
assembly; for further details refer to 7. Three Function Valve for HSS
3100 Series Compressors.
1.2.1. Internal Relief Valve
The compressor is fitted with an internal suction/discharge relief valve to
protect against overpressure, for example, in the event of operation with
a closed delivery valve in the system. Adequate system relief valves
designed to match the plant design pressure must be retained.
1. and 2. Suction 1.
Main rotor flutes 'a', 'b' and 'c' are in
communication at one end with the suction
chamber via the bevelled rotor end face, and
are sealed at the other end by the star rotor
teeth. As the main rotor turns, the effective
length of the flutes increases with a
corresponding increase in the volume open to c Suction
the suction chamber: Diagram 1 clearly Gas
b
shows this process. As flute 'a' assumes the a
position of flutes 'b' and 'c' its volume
increases, inducing suction vapour to enter
the flute.
Upon further rotation of the main rotor , the
flutes which have been open to the suction
chamber engage with the star teeth. This
coincides with each flute being progressively
sealed by the main rotor. Once the flute
2.
volume is closed off from the suction chamber,
the suction stage of the compression cycle is
complete.
c
b
a
3. Compression 3.
As the main rotor turns, the volume of gas
trapped within the flute is reduced as the
length of the flute shortens and compression
occurs.
c
b
a
4. Discharge 4.
As the star rotor tooth approaches the end of
a flute, the pressure of the trapped vapour
reaches a maximum value occurring when the
leading edge of the flute begins to overlap the Discharge
triangular shaped discharge port. Gas
B A
Unload Load
Slide Spring
Discharge pressure acts
on this side of piston
B A
Spring Force + Discharge Pressure > Cylinder Pressure = Slide Valve Moves Towards Unload
B A
Cylinder Pressure > Discharge Pressure + Spring Force = Slide Valve Moves Towards Load
1
CAPACITY CONTROL ACTION SOLENOID VALVE A SOLENOID VALVE B
Load compressor
High pressure oil is admitted to the capacity control cylinder. Oil pressure
overcomes the force of the spring supplemented by discharge pressure De-energise (close) Energise (open)
acting on the unload side of the piston, moving the slide valve towards the
maximum load position.
Unload compressor
Oil is vented from the capacity control cylinder. The force of the spring Energise (open) De-energise (close)
supplemented by discharge pressure acting on the unload side of the piston
moves the slide valve towards the minimum load position.
Hold slide valve position
De-energise (close) De-energise (close)
The slide valve is hydraulically locked at the desired load position.
At start up, when the compressor is at minimum load and the unload
solenoid valve is permanently energised (open), the capacity indicator
pressure will be the same as suction pressure because the cylinder is
vented to suction. As the compressor loads to some intermediate slide
valve position, then the pressure in the cylinder will be at some
intermediate pressure between suction and oil pressure. When the
compressor loads to maximum, the load (oil supply) solenoid valve will
continue to be pulsed without the piston moving. The pressure in the
cylinder will then assume the same pressure as the oil pressure
supplying it. Similarly, when the compressor unloads to minimum, the
unload solenoid valve will continue to pulse and the cylinder will assume
suction pressure again.
3. Economiser Facility
The HallScrew compressor is provided with an economiser facility. This
enables an additional charge of gas to be handled by the compressor,
over and above that which is normally pumped. It is, in effect, a form of
supercharging which has the net result of increasing refrigerating
capacity by a significantly greater percentage than power consumption,
hence improving the coefficient of performance (kW refrigeration/kW
power input) or Coefficient of Performance (COP) of the compressor.
The economiser principle is illustrated on a pressure/enthalpy (p-h)
diagram in Fig 4.
Suction gas is drawn into the main rotor flutes, these are sealed off in
sequence by the star rotor teeth and compression begins. An extra
charge of gas now enters the sealed flute through a port in the casing
enclosing the main rotor. This gas supply is taken from an intermediate
source at a slightly higher pressure than that prevailing in the flute at the
instant the gas is introduced, hence the gas is induced to enter the flute.
The original and additional charges of gas are then compressed and
discharged in the normal way. The full load pumping capacity of the
compressor at suction conditions is not affected by the additional flow
through the economiser connection.
In common with all screw compressors. as the compressor unloads, the
pressure at the economiser port falls towards suction pressure and the
additional capacity and improved efficiency economiser system is no
longer available.
As a guide to this effect, approximately half of the improvement due to
using an economiser system will be lost by the time the compressor
unloads to 90 % capacity, and falls to zero at around 70 % capacity.
Pressure
Subcooling
Condenser
Compressor
Economiser
Evaporator
Enthalpy
Economiser
TEV
Equaliser Evaporator
Line
Typical Single
Compressor Application
Condenser
** * *
SOLENOID VALVE IN MAIN LIQUID LINE SOLENOID VALVE BEFORE THE REGULATOR
THROUGH THE ECONOMISER (THERMOSTATIC EXPANSION VALVE SHOWN)
Electrically interlocked to energise (open) when Electrically interlocked to energise (open) when
compressor x starts, de-energise (close) when compressor x capacity > 50 %, de-energise
compressor x stops. (close) when compressor x capacity < 50 %.
LP
HP
Discharge
Suction
Under normal operating conditions this oil is supplied via the difference in
pressure between discharge and suction pressures. On starting the
suction/discharge pressure differential across the compressor builds
rapidly. However, this pressure difference must be monitored to ensure it
achieves the correct value within a specified time. Oil differential
pressure monitoring must continue all the while the compressor is
running in case operating conditions cause the differential to fall to an
unacceptable level. Under these conditions operation of the compressor
must be prevented or alternative oil injection arrangements made.
The oil system must be protected by monitoring two oil differential
pressures: ODP1 and ODP2. Two different methods are available:
• Electro-mechanical oil differential pressure switches.
• Transducers sensing the required pressures, connected to
the plant controller with the differential pressure calculation
performed by the software programme.
5.2.1. ODP1
This is the differential between oil pressure (or discharge pressure) and
suction pressure and determines if there is sufficient pressure difference
for adequate oil injection to occur.
ODP1 = Oil injection/lubrication pressure – Suction pressure
Because oil injection takes place into a sealed flute during the
compression process an estimate of the pressure in this flute must be
made. This pressure is a ratio of the suction pressure and for maximum
safety should be taken as twice suction pressure. If ODP1 is sensed by
transducers then the pressure ratio from suction to oil (discharge) should
be set to 2. If an oil differential pressure switch is used, this should be
set to the maximum intended operating suction gauge, thus the switch
will trip when the oil pressure is below twice the maximum operating
suction pressure. On start up there is no system pressure differential,
therefore, ODP1 must be timed out. The standard time out period is 30
seconds. If ODP1 is not achieved after this period alternative
arrangements must be made. Refer to J & E Hall International for advice
on the appropriate action.
5.2.2. ODP2
This is the differential across the oil injection line and should be set to
2.0 bar in order to prevent operation in the event of a blocked oil filter or
similar obstruction in the oil injection line.
ODP2 = Discharge pressure - Oil injection/lubrication pressure
5.3. Maintaining Discharge Pressure at Start up
Because oil pressure is generated by discharge pressure, a minimum
discharge pressure must be maintained, this minimum pressure
increases as suction pressure increases in order to maintain the required
pressure differential.
In circumstances where the minimum discharge pressure is difficult to
achieve, it is recommend to use the J & E Hall International three function
valve; refer to 7. Three Function Valve for HSS 3100 Series
Compressors.
5.4. Liquid Injection Cooling
The standard method of cooling for HSS 3100 series compressors is by
direct injection of liquid refrigerant into the compressor main rotor flute,
part-way through the compression process; a small reduction in
compressor capacity may result.
Discharge Line
Liquid
Inlet
LO
Visual indication that the line is full of liquid and provides early
Sight-glass (in line)
indication of a choked strainer.
LP System – Liquid Receiver with Sump LP System – Liquid Receiver with Weir
Liquid fills sump to provide preferential supply. Liquid fills weir side of receiver to provide preferential
Remainder flows to evaporator. supply. Remainder over-flows weir to evaporator.
Condensate From
Condenser
Sump
Main Liquid Supply Main Liquid Supply
to Evaporator to Evaporator
Liquid to
Injection Valve
Step 1 Example 1
Plot the design operating conditions at maximum load on 70
If load limiting is applied, ask J & E Hall International for the 25 % to 100 %
correct slide valve position to achieve this.
Compressor capacity is infinitely variable from 100 % to 20
approximately 25 % of full load (depends on the operating In this Example, Liquid injection is Required at
conditions). Minimum (25 %) Load. Unloading Limited to
50 % For No Liquid Injection.
10
-20 -15 -10 -5 0 5 10 15
6. Lubricating Oils
Lubricants used in the HallScrew compressor not only provide sealing
and cooling functions. The grade and type of lubricant chosen must
provide these functions at the actual operating environment existing
inside the compressor. In addition, as no oil separation system can be
100 % effective, the refrigeration system must be designed to adequately
return any oil carried over into the system to the compressor. Therefore,
the lubricant must be compatible with the refrigerant and the refrigeration
system as a whole.
The lubrication criteria can be met for standard operating conditions by
using a refrigeration quality oil as specified in Table 1 which is generally
in accordance with BS 2626 : 1992 Lubricating Oils for Refrigeration
Compressors. Depending on the refrigerant, the compressor is supplied
with the appropriate mineral oil or synthetic lubricant to this specification.
If the end user desires to use a different lubricant, approval MUST be
obtained from J & E Hall International if guarantees are not to be
invalidated. Different types and makes of oils must not be mixed.
POLYOLESTER
MINERAL OILS
LUBRICANTS
PARAMETER 2 3
1 LIQUID LIQUID INJECTION
EXTERNAL
INJECTION AND EXTERNAL
OIL COOLING
OIL COOLING OIL COOLING
4
Minimum ISO viscosity grade 68 100 68
Minimum viscosity index 45 33 45
Maximum pour point -30 °C -20 °C -25 °C
Including liquid injection oil cooling where the condensing temperature is below 45 °C.
1
3N1 Three
Function Valve Pilot Line Sensing Suction Pressure
Discharge Line
Connection to Suction
Pressure Gauge
→
Suction Line
Discharge Connection on
3N1 3 Function Valve:
2” NB (2 1/8” OD)
Pilot Line to Connection
on Compressor Sensing
Suction Pressure
Discharge
Discharge Connection
on Integral Separator
Fig 10 Three Function Valve Application for HSS 3100 Series Compressors
9. Electrical Connections
9.1. Compressor Starting
The HSS 3100 series compressor motor is wired for star/delta, soft-start
or inverter drive; these are the starting methods recommended by J & E
Hall International.
9.2. Motor Wiring Connections
Terminal box wiring is illustrated in Fig 11. Refer to Appendix 1 for motor
data. The standard terminal box rating is IP54.
9.3. Thermistors
Compressor motor and discharge high temperature thermistors are fitted
as standard and should be wired as illustrated in Fig 11.
9.4. Capacity Control Solenoids
The solenoids must be connected to a suitable plant controller that will
energise the appropriate coil to load or unload the compressor via
changes to the operation of the system into which the compressor is
fitted. The measured variable may be chilled water temperature, suction
gauge pressure, etc.
Power must be supplied to the solenoid via a suitable pulse timer that
must be capable of supplying a minimum pulse length of 0.1 second.
Operation of the solenoid with load is not linear, more pulses will be
required at low loads for the same change in load compared with
operation at high load.
Star/Delta
L3
NOTE: circuit must be
connected as shown to
L2 ensure correct rotation
of the motor/compressor
L1
C Motor D S
Thermistor
5
Terminal
Plate
Motor
Thermistor Discharge Fitted as standard
Thermistor
Thermistors may be
connected in series to a
common thermistor
controller or separately
to individual controllers,
but must NOT be
connected in parallel
Thermistor
Controller Not J & E Hall
International supply
L1 L2 L3
For applications using a soft-starter or
inverter, equipment must be carefully
selected to match the operating conditions
and must be able to accelerate the
Soft-start or inverter compressor smoothly to full load/speed
without stalling.
5
Terminal
Plate
Refrigerants
A = R134a
B = R22
C = R407c
For other refrigerants refer to
J & E Hall International.
Motor Voltages
Q = 400/460 V 3 ph 50/60 Hz
U = 380 V 3 ph 60 Hz
B = 208 V 3 ph 60 Hz
D = 500/575 V 3 ph 50/60 Hz
V = 230 V 3 ph 60 Hz
X = Special voltage
Motor Power
A = 82 kW
F = 43 kW
G = 60 kW
Lubricating Oil
E = Ester oil
M = Mineral oil
18, 20, 21 or 22
3 = Series 3000
Application
S = Semi-hermetic compressor with
integral oil separator for air
conditioning application
HS = HallScrew
Physical Data
Compressor Type Single screw, integral, semi-hermetic.
Compressor Rotation Clockwise looking on the motor end. Under no circumstances should the compressor
run in the reverse direction.
Method of Drive Suction gas cooled 3-phase, 2-pole start/rotor arranged for start/delta, soft-start or
inverter drive. Maximum of 6 starts per hour. Refer to Motor Data for kW ratings.
Speed Range Depends on the supply frequency, 50 Hz or 60 Hz, refer to Motor Data.
Physical Dimensions Refer to Physical Dimensions and Connections.
Capacity and Power Refer to selection data.
Capacity Control Compressor capacity infinitely variable from 100 % to approximately 25 % of full load
(depends on the operating conditions).
Capacity Control Solenoids 115 V or 240 V ac (other voltages available on request – delete all manuals). Terminal
box rating IP65.
Suction Strainer Integral. 60 mesh x 37 SWG.
Motor Terminal Box Rating IP54.
Integral Oil Separator 250 W heater.
Oil reservoir capacity 10 litres.
3
Swept Volume SWEPT VOLUME (M /HR) HSS 3118 HSS 3120 HSS 3121 HSS 3122
Compressor running @ 50 Hz
175 213 250 292
(2 pole speed)
Compressor running @ 60 Hz
210 256 300 350
(2 pole speed)
1
Weights COMPRESSOR WEIGHT (KG)
1
Sound Pressure Levels TOTAL CENTRE FREQUENCY – HZ
@ 50 Hz (2 pole speed) COMPRESSOR
DB ‘A’
125 250 500 1K 2K 4K 8K
HSS 3118 78 63 75 71 74 69 65 63
HSS 3120 78 63 76 71 75 70 67 66
HSS 3121 79 63 76 74 76 72 68 68
HSS 3122 79 63 76 74 76 72 68 68
1
Sound pressure level data refers to free-field conditions at a distance of 1 metre from the compressor periphery. It is
important to remember that on a specific installation the actual sound pressure level is considerably affected by the size and
type of room, material of construction and plant design. Adjoining pipework, including suction, can have a very substantial
effect on the noise level.
-5 2
Sound pressure levels given in dB refer to 2 x 10 N/m RMS.
Starting current (locked rotor) in Y (A) @ 400 V 151 195 151 195
Starting current (locked rotor) in ∆ (A) @ 400 V 476 643 476 643
Starting current (locked rotor) in ∆ (A) @ 400 V 643 906 643 906
Starting current (locked rotor) in ∆ (A) @ 460 V 466 675 466 675
Starting current (locked rotor) in ∆ (A) @ 460 V 675 893 675 893
Limits of Operation
Pressure Limits The pressure limits detailed below MUST NOT be exceeded during installation,
commissioning or operation of the plant.
R134A
1 2
Maximum Design Pressures High side 23.6 bar g
Low side 10.1 bar g
3
Operational Pressures 3.0 VR 3.5 bar g
Maximum compressor operating suction pressure
4.9 VR 3.5 bar g
Temperature Limits For normal refrigeration and air conditioning applications, the following temperature limits
should be observed.
Temperature Limits With Liquid Discharge temperature 100 °C (standard)
Injection Oil Cooling (Standard) 120 °C (special)
Discharge minimum superheat 20.0 °C
Maximum compressor High Pressure transducers and Pressure ratio If a programmable controller
operating pressure ratio programmable controller with (discharge/ is not used, set HP cut-out to
(discharge/suction) suitable analogue inputs suction) discharge pressure = 7 x
suction pressure (if this is
Set according to below the maximum setting
operating above)
conditions
Discharge temperature High Thermistor (fitted as standard) 100 °C (standard) Standard recommended
120 °C (special) when liquid injection is
controlled to 75 °C or within
25 °C of discharge gauge
Suction pressure Low LP cut-out or pressure According to the Prevents operation at low
transducer and programmable operating suction gauge pressures
controller with suitable conditions
analogue inputs
Oil differential pressure 1 Low Preferred method: Pressure ratio 2 Oil pressure should be twice
suction pressure
Oil injection pressure/suction Pressure transducers and
pressure programmable controller with
suitable analogue inputs
Alternative method: Differential equal -
to highest
Differential pressure switch operational
suction pressure
Oil differential pressure 2 High Differential pressure switch or 2 bar (max) 30 second delay required on
programmable controller with starting only
Discharge pressure - oil suitable analogue inputs
injection/lubrication pressure
Oil separator oil level Low Level switch or sensor Trip on low level Time delay (5 secs max)
required during operation to
prevent spurious trips
Oil temperature High Thermistor or HT cut-out 80 °C Mandatory requirement if
compressor fitted with
external oil cooling
Compressor motor high High Thermistor (fitted as standard) - -
temperature
Compressor motor current High Current limiter, or current Set according to Prevents motor operation
transformer and programmable motor size above maximum rated power
controller with suitable
analogue inputs
Y X
Suction
Lifting Eybolt
L
Z
Discharge Gauge
Connection
Dimensions in mm unless otherwise stated. Data provided as a guide only, refer to J & E Hall International certified drawing
DESCRIPTION SIZE
Length L 1274 mm
Overall Height H 643 mm
Width W 389 mm
Dimensions
A 280 mm
Holding-down bolt centres
B 410 mm
Holding-down bolts - 4 off M12 x 50 mm
X H
Oil Heater
Oil Drain
Y Liquid
Injection/Economiser
Suction
HP
PI PSL ODP PI
LP
Oil
PT
Evacuation
Suction
Discharge
HT (Del) TE
Discharge
PSI PS
TE HT (Oil)
Normally Closed
Normally Open Locked Open Normally Closed
and Capped
70
60
43 kW Motor:
HSS 3118 and HSS 3120
60 kW Motor:
HSS 3121 and HSS 3122
50
3.0 VR
Discharge Gauge °C
43 kW Motor:
40 HSS 3118 and HSS 3120
60 kW Motor:
HSS 3121 and HSS 3122
30 2.2 VR
20
10
-20 -15 -10 -5 0 5 10 15
Suction Gauge °C
70
60
43 kW Motor:
HSS 3118 and HSS 3120
60 kW Motor:
HSS 3121 and HSS 3122
50
3.0 VR
Discharge Gauge °C
40
30
20
10
-20 -15 -10 -5 0 5 10 15
Suction Gauge °C
70
60
60 kW Motor:
HSS 3118 and HSS 3120
82 kW Motor:
HSS 3121 and HSS 3122
50
3.0 VR
Discharge Gauge °C
60 kW Motor:
40
HSS 3118 and HSS 3120
82 kW Motor:
HSS 3121 and HSS 3122
30
2.2 VR
20
10
-20 -15 -10 -5 0 5 10 15
Suction Gauge °C
70
60
60 kW Motor:
HSS 3118 and HSS 3120
82 kW Motor:
HSS 3121 and HSS 3122
50
Discharge Gauge °C
3.0 VR
40
30
20
10
-20 -15 -10 -5 0 5 10 15
Suction Gauge °C
70
60
60 kW Motor:
HSS 3118 and HSS 3120
82 kW Motor:
HSS 3121 and HSS 3122
50
3.0 VR
60 kW Motor:
Discharge Gauge °C
30
2.2 VR
20
10
-20 -15 -10 -5 0 5 10 15
Suction Gauge °C
70
60
60 kW Motor:
HSS 3118 and HSS 3120
82 kW Motor:
HSS 3121 and HSS 3122
50
3.0 VR
Discharge Gauge °C
40
30
20
10
-20 -15 -10 -5 0 5 10 15
Suction Gauge °C
70
60
Full Load
Only
75 % to 100 %
50
Discharge Gauge °C
50 % to 100 %
40
30
25 % to 100 %
20
10
-20 -15 -10 -5 0 5 10 15
Suction Gauge °C
70
60
Full Load
Only
75 % to 100 %
50
Discharge Gauge °C
50 % to 100 %
40
30
25 % to 100 %
20
10
-20 -15 -10 -5 0 5 10 15
Suction Gauge °C
70
60
Liquid Injection Cooling
Always Required Above
This Line
50
75 % to 100 %
Discharge Gauge °C
Full Load
Only
40
50 % to 100 %
30
25 % to 100 %
20
10
-20 -15 -10 -5 0 5 10 15
Suction Gauge °C
70
50
75 % to 100 %
Discharge Gauge °C
Full Load
Only
40
50 % to 100 %
30
25 % to 100 %
20
10
-20 -15 -10 -5 0 5 10 15
Suction Gauge °C
70
50
75 % to 100 %
Full Load
Discharge Gauge °C
Only
40
50 % to 100 %
30
25 % to 100 %
20
10
-20 -15 -10 -5 0 5 10 15
Suction Gauge °C
70
50
75 % to 100 %
Full Load
Discharge Gauge °C
Only
40
50 % to 100 %
30
25 % to 100 %
20
10
-20 -15 -10 -5 0 5 10 15
Suction Gauge °C
16
Discharge Gauge °C
60 °C
14
12
50 °C Available Injection
Pressure Difference Injection Port Pressure
10
Liquid Injection Pressure bar
40 °C
8
6
30 °C
4
20 °C
0
-50 -40 -30 -20 -10 0 10 20
Suction Gauge °C
25
Discharge Gauge °C
60 °C
20
50 °C Available Injection
Pressure Difference
15
Liquid Injection Pressure bar
40 °C
10
30 °C
20 °C
0
-50 -40 -30 -20 -10 0 10 20
Suction Gauge °C
25
Discharge Gauge °C
60 °C
20
50 °C
Available Injection Injection Port Pressure
Pressure Difference
15
Liquid Injection Pressure bar
40 °C
10
30 °C
20 °C
0
-50 -40 -30 -20 -10 0 10 20
Suction Gauge °C
30
Discharge Gauge °C
60 °C
25
50 °C
20
Available Injection
Pressure Difference Injection Port Pressure
Liquid Injection Pressure bar
40 °C
15
30 °C
10
20 °C
0
-50 -40 -30 -20 -10 0 10 20
Suction Gauge °C
30
Discharge Gauge °C
60 °C
25
Available Injection
50 °C Pressure Difference
20
Injection Port Pressure
Liquid Injection Pressure bar
40 °C
15
30 °C
10
20 °C
0
-50 -40 -30 -20 -10 0 10 20
Suction Gauge °C
Questor House, 191 Hawley Road, Dartford, Kent DA1 1PU England
Telephone: +44 (0) 1322 223 456 Facsimile: +44 (0) 1322 291 458
www.jehall.co.uk