Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
Download as pdf or txt
Download as pdf or txt
You are on page 1of 76

Product 30HXA076-271

30HXC076-271
Data Condenserless
and Fluid-Cooled Chillers
50/60 Hz
75 to 265 Tons (264 to 931 kW)

Fluid-cooled and condenserless chill-


ers designed from the ground up to
meet the needs of today and tomor-
row, including:
• Fits through a standard door with no
disassembly required
• Chlorine-free HFC-134a refrigerant
• Dual circuit independent refrigerant
• Smooth compression using twin
screw compressors
• ARI certified efficiencies to
.53 kW/ton

Features/Benefits
Quality design and
construction make the
30HXC (Fluid Cooled) and the
ComfortLink

TIME
EWT
LWT
SETP

MODE
N AV I G ATO R ™

12.58
54.6°F
44.1°F
44.0°F

Alarm Status
30HXA (Condenserless) units
the preferred choice
Run Status
Service Test

Temperatures
Pressures
Setpoints

Inputs
Outputs
Configuration
ESC
Time Clock
Operating Modes
Alarms

ENTER

Easy installation
The 30HX chiller has a compact de-
sign that fits through a standard door
opening and requires minimal indoor
space. The 30HX chiller is delivered as
a complete package for easy installa-
tion. There are no extra controls,
clocks, starters, or other items to
install.
The 30HX unit also provides a sin-
gle location electrical power entrance
(using the accessory field-installed con-
trol transformer) and quick, easy pip-
ing using either welded or accessory
victaulic-type clamp-on couplings for
the cooler.
The 30HX 208/230-v, 230-v,
460-v and 575-v units are designed in
accordance with UL (Underwriters’
Laboratory, U.S.A.) and CSA (Canadi-
an Standards Association) standards to
minimize electrical inspection time.

Copyright 2000 Carrier Corporation Form 30HX-5PD


A quick start-up is assured once in- through lower electrical costs. All From a service standpoint, the
stallation is complete, since each 30HX units are also rated in accor- 30HX units offer the following
30HX unit is manufactured at an ISO dance with ARI (Air Conditioning and features:
9002-listed manufacturing facility to Refrigeration Institute, U.S.A.) • Use of HFC-134a refrigerant,
guarantee quality. In addition, all standards. The 60 Hz 30HXC units which has no planned phase-out
30HXC units are tested under load at are ARI certified. in its future
the factory to provide reliable start-up. The 30HX controls are fully auto- • Mechanically-cleanable cooler and
Easy operation matic. The leaving-fluid temperature is condenser (30HXC units)
directly controlled, and the entering- • Twin-screw compressors, which
The 30HX units have a quiet, low- fluid temperature is continuously moni- require no routine service or
vibration design featuring screw tored to detect load and flow changes maintenance
compressors. controlling to within .5° F (.3° C). • Easily accessed service information
Efficiency levels of the 30HX units Dual, independent refrigerant cir- includes suction and discharge
exceed minimums established by cuits provide reliable, dependable cool- pressure and temperature using
ASHRAE (American Society of Heat- ing, and the 30HX units use medium- standard Navigator™ display module
ing and Refrigeration Engineers) and pressure HFC-134a refrigerant to min-
CSA for both full- and part-load opera- imize stress on the compressors and
tion, thus saving on operating costs ensure a long life.

DUAL INDEPENDENT REFRIGERANT CIRCUITS NAVIGATOR IN DISPLAY MODE

Com
fort
NA Lin
VIG
ATO k
R™
T IM E
EWT 12.
LW T 54. 58
SETP 44. 6°F
4 4 . 01 ° F
°F

MO
DE
Run Al ar
m St
Statu atu s
ComfortLink s
N AV I G ATO R ™

Servi
TIME
EWT
LWT
12.58
54.6°F
44.1°F ce Te
st
SETP 44.0°F

Temp
MODE
Run Status
Alarm Status

eratur
es
Service Test

Temperatures
Pressures

Pres
Setpoints
Inputs
Outputs

sures
Configuration
ESC
Time Clock
Operating Modes
Alarms

ENTER

Setpo
ints
Inputs
Outpu
ts
Confi
gurat
ion
Time
Cloc
k ESC
Opera
ting
Mode
Alarm s
s

ENT
ER

FITS THROUGH STANDARD DOORWAY


TWIN-SCREW COMPRESSOR DESIGN

2
Table of contents
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,2
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-18
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-27
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-56
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57,58
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59-72
Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74-76

Model number nomenclature

LEGEND
FIOPS — Factory-Installed Options

3
Physical data
ENGLISH
UNIT SIZE 30HX 076 086 096 106 116 126 136 146
UNIT WEIGHT (lb)
Fluid Cooled (HXC) 5700 5723 5855 6177 6415 6465 6688 6718
Condenserless (HXA) 4717 4744 4835 5151 5163 5205 5309 5333
COMPRESSORS Semi-Hermetic, Twin Screw
Quantity 2 2 2 2 2 2 2 2
Nominal Capacity per Compressor (tons) 39/39 46/39 56/39 66/39 66/46 66/56 80/56 80/66
Economizer No No No No No No No No
No. Capacity Steps
Standard 6 6 6 6 6 6 6 6
Optional (maximum) 8 8 8 8 8 8 8 8
Minimum Step Capacity (%)
Standard 20 20 20 20 20 20 20 20
Optional 10 10 10 10 10 10 10 10
REFRIGERANT R-134a
Charge* (lb) Circuit A/Circuit B 60/60 76/65 94/70 110/70 105/76 112/89 124/89 119/100
COOLER Shell and Tube with Enhanced Copper Tubes
Part No. 10HX400- 001 001 002 010 007 007 006 006
Net Fluid Volume (gal) 17.0 17.0 19.0 22.6 21.4 21.4 24.0 24.0
Maximum Refrigerant Pressure (psig) 220 220 220 220 220 220 220 220
Maximum Fluid-Side Pressure (psig) 300 300 300 300 300 300 300 300
Fluid Connections
Inlet and Outlet (in.) 4 4 4 5 4 4 4 4
Drain (in. NPT) 1/
2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

Relief Valve
Connection (in. NPTF) 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4

Flow Capacity (lb air/min) 31.7 31.7 31.7 31.7 31.7 31.7 31.7 31.7
Relief Setting (psig) 220 220 220 220 220 220 220 220
Standard Number of Passes 3 3 3 3 2 2 2 2
30HXA OIL SEPARATOR
Part No. 09RX400- 165 165 166 166 167 167 167 167
Maximum Refrigerant Pressure (psig) 320 320 320 320 320 320 320 320
Refrigerant Connections (in.)
Discharge Circuit A/B 21/8/21/8 21/8/21/8 21/8/21/8 21/8/21/8 21/8/21/8 21/8/21/8 21/8/21/8 21/8/21/8
Liquid Circuit A/B 11/8/11/8 11/8/11/8 11/8/11/8 11/8/11/8 11/8/11/8 11/8/11/8 11/8/11/8 11/8/11/8
Relief Valve
Connection (in. SAE Flare) 5/8 5/8 5/8 5/8 5/8 5/8 5/8 5/8

Flow Capacity (lb air/min) 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6
Relief Setting (psig) 320 320 320 320 320 320 320 320
CONDENSER (HXC) Shell and Tube with Enhanced Copper Tubes
Part No. 09RX400- 173 173 174 174 175 175 176 176
Net Fluid Volume (gal) 16.8 16.8 18.3 18.3 23.9 23.9 27.5 27.5
Maximum Refrigerant Pressure (psig) 220 220 220 220 220 220 220 220
Maximum Water-Side Pressure (psig) 300 300 300 300 300 300 300 300
Water Connections (in.)
Inlet and Outlet 5 5 5 5 5 5 5 5
Drain (NPT) 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

Relief Valve
Connection (in. NPTF) 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4

Flow Capacity (lb air/min) 31.7 31.7 31.7 31.7 31.7 31.7 31.7 31.7
Relief Setting (psig) 220 220 220 220 220 220 220 220
Standard Number of Passes 2 2 2 2 2 2 2 2
DISCHARGE LINE†
Relief Valve
Connection (in. SAE Flare) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8

Flow Capacity (lb air/min) 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3
Setting (psig) 350 350 350 350 350 350 350 350

LEGEND
NPTF — National Pipe Thread Female
SAE — Society of Automotive Engineers
* Charges listed are for 30HXC units. The 30HXA units are shipped with a holding charge only. To determine the refrigerant charge requirements for 30HXA units see the
System Refrigerant Charge table in the Application Data on page 26.
† Only on units with factory-installed suction service valves.

4
ENGLISH (cont)
UNIT SIZE 30HX 161 171 186 206 246 261 271
UNIT WEIGHT (lb)
Fluid Cooled (HXC) 7452 7660 7854 10,581 10,969 10,992 11,029
Condenserless (HXA) 5752 5777 5946 7,485 7,621 7,621 7,621
COMPRESSORS Semi-Hermetic, Twin Screw
Quantity 2 2 2 3 3 3 3
Nominal Capacity per Compressor (tons) 80/56 66/80 80/80 66/39/80 80/56/80 80/66/80 80/80/80
Economizer Yes Yes Yes Yes Yes Yes Yes
No. Capacity Steps
Standard 6 6 6 8 8 8 8
Optional (maximum) 8 8 8 11 11 11 11
Minimum Step Capacity (%)
Standard 20 20 20 13 13 13 13
Optional 10 10 10 7 7 7 7
REFRIGERANT R-134a
Charge* (lb) Circuit A/Circuit B 150/110 119/140 135/135 220/135 220/135 220/135 220/135
COOLER TYPE Shell and Tube with Enhanced Copper Tubes
Part No. 10HX400- 104 012 013 125 126 126 126
Net Fluid Volume (gal) 28.5 28.5 33.4 43.1 47.2 47.2 47.2
Maximum Refrigerant Pressure (psig) 220 220 220 220 220 220 220
Maximum Fluid-Side Pressure (psig) 300 300 300 300 300 300 300
Fluid Connections
Inlet and Outlet (in.) 5 5 5 6 6 6 6
Drain (NPT) 1/2 1/2 1/2 3/4 3/4 3/4 3/4

Relief Valve
Connection (in. NPTF) 3/
4 3/4 3/4 3/4 3/4 3/4 3/4

Flow Capacity (lb air/min) 31.7 31.7 31.7 31.7 31.7 31.7 31.7
Relief Setting (psig) 220 220 220 220 220 220 220
Standard Number of Passes 2 2 2 2 2 2 2
30HXA OIL SEPARATOR
Part No. 09RX400- 167 168 168 106 106 106 106
Maximum Refrigerant Pressure (psig) 320 320 320 320 320 320 320
Refrigerant Connections (in.)
Discharge Circuit A/B 21/8/21/8 21/8/21/8 21/8/21/8 21/8/21/8 21/8/21/8 21/8/21/8 21/8/21/8
Liquid Circuit A/B 13/8/13/8 13/8/13/8 13/8/13/8 15/8/13/8 15/8/13/8 15/8/13/8 15/8/13/8
Relief Valve
Connection (in. SAE Flare) 5/
8 5/8 5/8 5/8 5/8 5/8 5/8

Flow Capacity (lb air/min) 21.6 21.6 21.6 21.6 21.6 21.6 21.6
Relief Setting (psig) 320 320 320 320 320 320 320
CONDENSER (HXC) Shell and Tube with Enhanced Copper Tubes
Part No. 09RX400- 178 178 178 179 180 180 180
Net Fluid Volume (gal) 30.6 37.6 37.6 47.6 55.1 55.1 55.1
Maximum Refrigerant Pressure (psig) 220 220 220 220 220 220 220
Maximum Water-Side Pressure (psig) 300 300 300 300 300 300 300
Water Connections (in.)
Inlet and Outlet 5 5 5 6 6 6 6
Drain (NPT) 1/
2
1/
2
1/
2
3/
4
3/
4
3/
4
3/
4
Relief Valve
Connection (in. NPTF) 3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
Flow Capacity (lb air/min) 31.7 31.7 31.7 31.7 31.7 31.7 31.7
Relief Setting (psig) 220 220 220 220 220 220 220
Standard Number of Passes 2 2 2 2 2 2 2
DISCHARGE LINE†
Relief Valve
Connection (in. SAE Flare) 3/
8
3/
8
3/
8
3/
8
3/
8
3/
8
3/
8
Flow Capacity (lb air/min) 6.3 6.3 6.3 6.3 6.3 6.3 6.3
Setting (psig) 350 350 350 350 350 350 350

LEGEND
NPTF — National Pipe Thread Female
SAE — Society of Automotive Engineers
* Charges listed are for 30HXC units. The 30HXA units are shipped with a holding charge only. To determine the refrigerant charge requirements for 30HXA units see the
System Refrigerant Charge table in the Application Data on page 26.
† Only on units with factory-installed suction service valves.

5
Physical data (cont)
SI
UNIT SIZE 30HX 076 086 096 106 116 126 136 146
UNIT WEIGHT (kg)
Fluid Cooled (HXC) 2586 2597 2657 2803 2911 2933 3034 3048
Condenserless (HXA) 2140 2152 2194 2337 2342 2362 2408 2420
COMPRESSORS Semi-Hermetic, Twin Screw
Quantity 2 2 2 2 2 2 2 2
Nominal Capacity per Compressor (kW) 137/137 162/137 197/137 232/137 232/137 232/197 281/197 281/232
Economizer No No No No No No No No
No. Capacity Steps
Standard 6 6 6 6 6 6 6 6
Optional (maximum) 8 8 8 8 8 8 8 8
Minimum Step Capacity (%)
Standard 20 20 20 20 20 20 20 20
Optional 10 10 10 10 10 10 10 10
REFRIGERANT R-134a
Charge* (kg) Circuit A/Circuit B 27.3/27.3 34.5/29.5 42.7/31.8 50.0/31.8 47.7/34.5 50.9/40.5 56.4/40.5 54.1/45.5
COOLER Shell and Tube with Enhanced Copper Tubes
Part No. 10HX400- 001 001 002 010 007 007 006 006
Net Fluid Volume (L) 64.3 64.3 71.9 85.5 81.0 81.0 90.8 90.8
Maximum Refrigerant Pressure (kPa) 1517 1517 1517 1517 1517 1517 1517 1517
Maximum Fluid-Side Pressure (kPa) 2068 2068 2068 2068 2068 2068 2068 2068
Fluid Connections
Inlet and Outlet (in.) 4 4 4 5 4 4 4 4
Drain (NPT) 1/
2
1/
2
1/
2
1/
2
1/
2
1/
2
1/
2
1/
2
Relief Valve
Connection (in. NPTF) 3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
Flow Capacity (kg air/min) 14.38 14.38 14.38 14.38 14.38 14.38 14.38 14.38
Relief Setting (kPa) 1517 1517 1517 1517 1517 1517 1517 1517
Standard Number of Passes 3 3 3 3 2 2 2 2
30HXA OIL SEPARATOR
Part No. 09RX400- 165 165 166 166 167 167 167 167
Maximum Refrigerant Pressure (kPa) 2205 2205 2205 2205 2205 2205 2205 2205
Refrigerant Connections (in.)
Discharge 21/8 21/8 21/8 21/8 21/8 21/8 21/8 21/8
Liquid 11/8 11/8 11/8 11/8 11/8 11/8 11/8 11/8
Relief Valve
Connection (in. SAE Flare) 5/
8
5/
8
5/
8
5/
8
5/
8
5/
8
5/
8
5/
8
Flow Capacity (kg air/min) 9.80 9.80 9.80 9.80 9.80 9.80 9.80 9.80
Relief Setting (kPa) 2206 2206 2206 2206 2206 2206 2206 2206
CONDENSER (HXC) Shell and Tube with Enhanced Copper Tubes
Part No. 09RX400- 173 173 174 174 175 175 176 176
Net Fluid Volume (L) 63.6 63.6 69.3 69.3 90.5 90.5 104.1 104.1
Maximum Refrigerant Pressure (kPa) 1517 1517 1517 1517 1517 1517 1517 1517
Maximum Water-Side Pressure (kPa) 2068 2068 2068 2068 2068 2068 2068 2068
Water Connections (in.)
Inlet and Outlet 5 5 5 5 5 5 5 5
Drain (NPT) 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

Relief Valve
Connection (in. NPTF) 3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
Flow Capacity (kg air/min) 14.38 14.38 14.38 14.38 14.38 14.38 14.38 14.38
Relief Setting (kPa) 1517 1517 1517 1517 1517 1517 1517 1517
Standard Number of Passes 2 2 2 2 2 2 2 2
DISCHARGE LINE†
Relief Valve
Connection (in. SAE Flare) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8

Flow Capacity (kg air/min) 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
Relief Pressure (kPa) 2413 2413 2413 2413 2413 2413 2413 2413

LEGEND
NPTF — National Pipe Thread Female
SAE — Society of Automotive Engineers
* Charges listed are for 30HXC units. The 30HXA units are shipped with a holding charge only. To determine the refrigerant charge requirements for 30HXA units see the
System Refrigerant Charge table in the Application Data on page 26.
† Only on units with factory-installed suction service valves.

6
SI (cont)
UNIT SIZE 30HX 161 171 186 206 246 261 271
UNIT WEIGHT (kg)
Fluid Cooled (HXC) 3381 3475 3564 4799 4976 4986 5003
Condenserless (HXA) 2610 2621 2698 3395 3457 3457 3457
COMPRESSORS Semi-Hermetic, Twin Screw
Quantity 2 2 2 3 3 3 3
Nominal Capacity per Compressor (kW) 281/197 232/281 281/281 232/137/281 281/197/281 281/232/281 281/281/281
Economizer Yes Yes Yes Yes Yes Yes Yes
No. Capacity Steps
Standard 6 6 6 8 8 8 8
Optional (maximum) 8 8 8 11 11 11 11
Minimum Step Capacity (%)
Standard 20 20 20 13 13 13 13
Optional 10 10 10 7 7 7 7
REFRIGERANT R-134a
Charge* (kg) Circuit A/Circuit B 68.2/50.0 54.1/63.6 61.2/61.2 99.8/61.2 99.8/61.2 99.8/61.2 99.8/61.2
COOLER Shell and Tube with Enhanced Copper Tubes
Part No. 10HX400- 104 012 013 125 126 126 126
Net Fluid Volume (L) 107.9 107.9 126.4 163.2 178.7 178.8 178.7
Maximum Refrigerant Pressure (kPa) 1517 1517 1517 1517 1517 1517 1517
Maximum Fluid-Side Pressure (kPa) 2068 2068 2068 2068 2068 2068 2068
Fluid Connections
Inlet and Outlet (in.) 5 5 5 6 6 6 6
Drain (NPT) 1/
2
1/
2
1/
2
3/
4
3/
4
3/
4
3/
4
Relief Valve
Connection (in. NPTF) 3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
3/
4
Flow Capacity (kg air/min) 14.28 14.38 14.38 14.38 14.38 14.38 14.38
Relief Setting (kPa) 1517 1517 1517 1517 1517 1517 1517
Standard Number of Passes 2 2 2 2 2 2 2
30HXA OIL SEPARATOR
Part No. 09RX400- 167 168 168 106 106 106 106
Maximum Refrigerant Pressure (kPa) 2205 2205 2205 2205 2205 2205 2205
Refrigerant Connections (in.)
Discharge 21/8 21/8 21/8 21/8 (2) 21/8 (2) 21/8 (2) 21/8 (2)
Liquid 13/8 13/8 13/8 15/8/13/8† 15/8/13/8† 15/8/13/8† 15/8/13/8†
Relief Valve
Connection (in. SAE Flare) 5/
8
5/
8
5/
8
5/
8
5/
8
5/
8
5/
8
Flow Capacity (kg air/min) 9.80 9.80 9.80 9.80 9.80 9.80 9.80
Relief Setting (kPa) 2206 2206 2206 2206 2206 2206 2206
CONDENSER (HXC) Shell and Tube with Enhanced Copper Tubes
Part No. 09RX400- 177 178 178 179 179 179 179
Net Fluid Volume (L) 115.8 142.3 142.3 177.9 208.6 208.6 208.6
Maximum Refrigerant Pressure (kPa) 1517 1517 1517 1517 1517 1517 1517
Maximum Water-Side Pressure (kPa) 2068 2068 2068 2068 2068 2068 2068
Water Connections (in.)
Inlet and Outlet 5 5 5 6 6 6 6
Drain (NPT) 1/2 1/2 1/2 3/4 3/4 3/4 3/4

Relief Valve
Connection (in. NPTF) 3/4 3/4 3/4 3/4 3/4 3/4 3/4

Flow Capacity (kg air/min) 14.38 14.38 14.38 14.38 14.38 14.38 14.38
Relief Setting (kPa) 1517 1517 1517 1517 1517 1517 1517
Standard Number of Passes 2 2 2 2 2 2 2
DISCHARGE LINE**
Relief Valve
Connection (in. SAE Flare) 3/8 3/8 3/8 3/8 3/8 3/8 3/8

Flow Capacity (kg air/min) 2.9 2.9 2.9 2.9 2.9 2.9 2.9
Relief Pressure (kPa) 2413 2413 2413 2413 2413 2413 2413

LEGEND
NPTF — National Pipe Thread Female
SAE — Society of Automotive Engineers
* Charges listed are for 30HXC units. The 30HXA units are shipped with a holding charge only. To determine the refrigerant charge requirements for 30HXA units see the
System Refrigerant Charge table in the Application Data on page 26.
† Circuit A/Circuit B.
** Only on units with factory-installed suction service valves.

7
8
30HXC076-106

NOTES:
1. OPERATING WEIGHT INCLUDES WEIGHT OF WATER AND REFRIGERANT.
2. DENOTES CENTER OF GRAVITY.
3. —– DENOTES ACCESSORY OR FACTORY INSTALLED OPTION.
4. DIMENSIONS ARE IN INCHES (MM) AND WEIGHTS ARE IN LB (KG).
5. 36 IN. (914.4) RECOMMENDED SERVICE CLEARANCE AROUND MACHINE.
Dimensions
30HXC116-146
NOTES:
1. OPERATING WEIGHT INCLUDES WEIGHT OF WATER AND REFRIGERANT.
2. DENOTES CENTER OF GRAVITY.
3. —– DENOTES ACCESSORY OR FACTORY INSTALLED OPTION.
4. DIMENSIONS ARE IN INCHES (MM) AND WEIGHTS ARE IN LB (KG).
5. 36 IN. (914.4) RECOMMENDED SERVICE CLEARANCE AROUND MACHINE.

9
10
30HXC161-186

NOTES:
1. OPERATING WEIGHT INCLUDES WEIGHT OF WATER AND REFRIGERANT.
2. DENOTES CENTER OF GRAVITY.
3. —– DENOTES ACCESSORY OR FACTORY INSTALLED OPTION.
4. DIMENSIONS ARE IN INCHES (MM) AND WEIGHTS ARE IN LB (KG).
5. 36 IN. (914.4) RECOMMENDED SERVICE CLEARANCE AROUND MACHINE.
Dimensions (cont)
30HXC206-271

NOTES:
1. OPERATING WEIGHT INCLUDES WEIGHT OF WATER AND REFRIGERANT.
2. DENOTES CENTER OF GRAVITY.
3. —– DENOTES ACCESSORY OR FACTORY INSTALLED OPTION.
4. DIMENSIONS ARE IN INCHES (MM) AND WEIGHTS ARE IN LB (KG).
5. 36 IN. (914.4) RECOMMENDED SERVICE CLEARANCE AROUND MACHINE.

11
12
30HXA076-106

NOTES:
1. OPERATING WEIGHT INCLUDES WEIGHT OF WATER AND REFRIGERANT.
2. DENOTES CENTER OF GRAVITY.
3. —– DENOTES ACCESSORY OR FACTORY INSTALLED OPTION.
4. DIMENSIONS ARE IN INCHES (MM) AND WEIGHTS ARE IN LB (KG).
5. 36 IN. (914.4) RECOMMENDED SERVICE CLEARANCE AROUND MACHINE.
Dimensions (cont)
30HXA116-146

NOTES:
1. OPERATING WEIGHT INCLUDES WEIGHT OF WATER AND REFRIGERANT.
2. DENOTES CENTER OF GRAVITY.
3. —– DENOTES ACCESSORY OR FACTORY INSTALLED OPTION.
4. DIMENSIONS ARE IN INCHES (MM) AND WEIGHTS ARE IN LB (KG).
5. 36 IN. (914.4) RECOMMENDED SERVICE CLEARANCE AROUND MACHINE.

13
14
30HXA161-186
NOTES:
1. OPERATING WEIGHT INCLUDES WEIGHT OF WATER AND REFRIGERANT.
2. DENOTES CENTER OF GRAVITY.
3. —– DENOTES ACCESSORY OR FACTORY INSTALLED OPTION.
4. DIMENSIONS ARE IN INCHES (MM) AND WEIGHTS ARE IN LB (KG).
5. 36 IN. (914.4) RECOMMENDED SERVICE CLEARANCE AROUND MACHINE.
Dimensions (cont)
30HXA206-271
NOTES:
1. OPERATING WEIGHT INCLUDES WEIGHT OF WATER AND REFRIGERANT.
2. DENOTES CENTER OF GRAVITY.
3. —– DENOTES ACCESSORY OR FACTORY INSTALLED OPTION.
4. DIMENSIONS ARE IN INCHES (MM) AND WEIGHTS ARE IN LB (KG).
5. 36 IN. (914.4) RECOMMENDED SERVICE CLEARANCE AROUND MACHINE.

15
Dimensions (cont)
TYPICAL ACCESSORY VICTAULIC NOZZLE*

TYPICAL STANDARD COOLER/CONDENSER CONNECTION*

*30HXA,C116-271 chillers with minus 1 pass cooler option are shipped with Victaulic nozzle on cooler section.

NOTE: Dimensions given in inches.

16
ACCESSORY SOUND ENCLOSURE

NOTES:
1. Dimensions are in inches (millimeters).
2. 36 in. (914.4) recommended service clearance around machine.
3. Unused portion of piping openings to be closed and insulated for acoustic purposes. Use filler panel in accessory package.
4. Field fabricated holes must be closed and insulated for acoustic purposes.
5. Recommended electrical power supply area. Notch to suit and cover/insulate remaining open area for acoustic purposes.
6. Recommended control wiring entry area. Notch to suit and cover/insulate remaining open area for acoustic purposes.
7. Recommended cooler relief valve vent line and 30HXC condenser relief vent line entry area. 30HXA discharge and liquid line
entry areas on opposite side. Notch enclosure to suit particular installation.
8. Model in drawing is typical and represents 30HX116-146 sizes in the 30HX-900---001 accessory.
9. Sound enclosure accessory should be aligned to the center lines of the control panel access and piping openings.

17
Dimensions (cont)
WEIGHT DISTRIBUTION AT MOUNTING PLATES

WEIGHT DISTRIBUTION AT EACH MOUNTING PLATE


30HXC UNITS — lb (kg)

MOUNTING PLATE NO.


UNIT 30HXC
1 2 3 4 5 6
076 738 (335) 943 (428) 595 (270) 1110 (503) 1418 (643) 896 (406)
086 738 (335) 947 (430) 597 (271) 1112 (504) 1427 (647) 902 (409)
096 686 (311) 968 (439) 693 (314) 1027 (466) 1447 (656) 1034 (469)
106 730 (331) 1028 (466) 744 (337) 1073 (487) 1510 (685) 1092 (495)
116 728 (330) 1114 (505) 777 (352) 1053 (478) 1615 (733) 1127 (511)
126 738 (335) 1127 (511) 780 (354) 1061 (481) 1628 (738) 1131 (513)
136 758 (344) 1176 (533) 811 (368) 1083 (491) 1689 (766) 1171 (531)
146 763 (346) 1182 (536) 815 (370) 1085 (492) 1697 (770) 1172 (532)
161 817 (371) 1272 (577) 908 (412) 1219 (553) 1890 (857) 1346 (610)
171 936 (425) 1318 (598) 840 (381) 1379 (626) 1946 (883) 1241 (563)
186 962 (436) 1361 (617) 860 (390) 1410 (640) 1996 (905) 1265 (574)
206 948 (430) 2406 (1091) 1243 (564) 1201 (545) 3133 (1421) 1650 (748)
246 985 (447) 2515 (1141) 1306 (592) 1154 (523) 3276 (1486) 1733 (786)
261 985 (447) 2520 (1143) 1311 (595) 1154 (523) 3283 (1489) 1739 (789)
271 985 (447) 2529 (1147) 1318 (598) 1154 (523) 3294 (1494) 1749 (793)

30HXA UNITS — lb (kg)

MOUNTING PLATE NO.


UNIT 30HXA
1 2 3 4 5 6
076 555 (252) 793 (360) 418 (190) 926 (420) 1326 (601) 699 (317)
086 555 (252) 798 (362) 418 (190) 928 (421) 1340 (608) 705 (320)
096 509 (231) 808 (367) 493 (224) 848 (385) 1350 (612) 827 (375)
106 555 (252) 869 (394) 541 (245) 896 (406) 1410 (640) 880 (399)
116 530 (240) 895 (406) 540 (245) 855 (388) 1456 (660) 887 (402)
126 540 (245) 905 (410) 541 (245) 864 (392) 1468 (666) 887 (402)
136 548 (249) 926 (420) 555 (252) 873 (396) 1498 (679) 908 (412)
146 551 (250) 930 (422) 555 (252) 883 (400) 1506 (683) 908 (412)
161 560 (254) 965 (438) 598 (271) 954 (433) 1650 (748) 1025 (465)
171 627 (284) 968 (439) 534 (242) 1072 (486) 1658 (752) 918 (416)
186 648 (294) 1004 (455) 552 (250) 1110 (504) 1703 (772) 939 (426)
206 671 (304) 1702 (772) 879 (399) 850 (385) 2216 (1005) 1167 (529)
246 681 (309) 1748 (793) 911 (413) 797 (362) 2276 (1032) 1209 (548)
261 681 (309) 1748 (793) 911 (413) 797 (362) 2276 (1032) 1209 (548)
271 681 (309) 1748 (793) 911 (413) 797 (362) 2276 (1032) 1209 (548)
NOTE: See pages 8-15 for center of gravity details.

18
Options and accessories
FACTORY- FIELD- types of reset are available with the main board. However,
ITEM INSTALLED INSTALLED an accessory thermistor is required for outdoor air and/or
OPTION ACCESSORY space temperature reset.) Demand limiting allows the unit
Wye-Delta Start X capacity to be limited during periods of peak energy usage.
Brine X Demand limit requires an external 4 to 20 mA signal or a
Minus-One-Pass Cooler Head X 2-step remote pair of dry contacts. Both the 4 to 20 mA
Plus-One-Pass Cooler Head X and 2-step demand limit percentage values are adjustable.
Control Power Transformer X EMM is also available as a field-installed accessory.
Minimum Load Control X X
Sound Reduction Enclosure X Field-installed accessories
Vibration Isolation X Control power transformer — The transformer is sized
Victaulic Connection X to supply the needs of the control circuit, sourcing power
Temperature Reset Sensor X from the main unit power connection.
Chillervisor™ System Manager III X
Minimum load control — This accessory allows addi-
Cooler Head Insulation X
tional capacity reduction for unit operation below the mini-
Suction Service Valves X
mum step of unloading (down to 10% of the minimum unit
Energy Management Module X X
capacity). Minimum load control is also available as a
Factory-installed options factory-installed option.
Sound reduction enclosure — This kit contains a
Wye-delta start — Generally, Wye-delta start is not sound enclosure that covers the entire unit to reduce sound
required when using multiple compressors since the start- levels.
ing current is generally less than with one larger compres-
sor using Wye-delta start. Wye-delta start is standard on Vibration isolation — Neoprene isolators are field
208/230 v, 60 Hz, 230-3-60, and 230 v, 50 Hz units. It installed to reduce vibration transmission from the com-
is available as a factory-installed option for all other unit pressor through the floor and into the conditioned space.
voltages. Victaulic connection — The kit contains a victaulic-type
Brine — The brine option permits supply liquid tempera- connection to replace the standard weld-type connection
tures to be set below 40 F (4.4 C). Refrigeration circuit for cooler and condenser applications.
components, such as the expansion device, are modified at Temperature reset sensor — This accessory sensor
the factory to correct for the lower refrigeration flow rates. provides temperature reset capability from either the occu-
Minus-One-Pass cooler — This factory-installed option pied space or outdoor-air temperature.
reduces pressure drop for high flow applications and/or NOTE: Temperature reset capability using return tempera-
provides same end inlet and outlet for 076-106 sizes, or ture is standard.
opposite end inlet and outlet on 116-271 sizes. Chillervisor System Manager III — This control can be
Plus-One-Pass cooler — This factory-installed option used to regulate up to eight 30HXA or 30HXC chillers.
improves low temperature brine performance. See Carrier Cooler head insulation — This accessory is designed
30HX electronic catalog for performance data. with flexible, 3/4 in. (19 mm) PVC foam (closed-cell) to
Minimum load control — This option allows additional insulate the cooler heads and economizer vessel to mini-
capacity reduction for unit operation below the minimum mize heat loss and head sweating.
step of unloading (down to 10% of the minimum unit Energy Management Module (EMM) is used for 4 to
capacity). Minimum load control is also available as a field- 20 mA leaving fluid temperature reset, cooling point reset,
installed accessory. 4 to 20 mA demand limit and two-step demand limit. Tem-
Suction service valves — Standard refrigerant dis- perature reset lets the unit reset the leaving fluid tempera-
charge isolation and liquid valves enable service personnel ture to a higher temperature during low load conditions.
to store the refrigerant charge in the cooler or condenser Temperature reset can also be accomplished based on
during servicing. This factory-installed option allows further return fluid, outdoor air or space temperature. (The EMM
isolation of the compressor from the cooler vessel. option is not required when using entering-water, outdoor-
Energy Management Module (EMM) is used for 4 to air, or space temperature for temperature reset. These
20 mA leaving fluid temperature reset, cooling point reset, types of reset are available with the main board. However,
4 to 20 mA demand limit and two-step demand limit. Tem- an accessory thermistor is required for outdoor air and/or
perature reset lets the unit reset the leaving fluid tempera- space temperature reset.) Demand limiting allows the unit
ture to a higher temperature during low load conditions. capacity to be limited during periods of peak energy usage.
Temperature reset can also be accomplished based on Demand limit requires an external 4 to 20 mA signal or a
return fluid, outdoor air or space temperature. (The EMM 2-step remote pair of dry contacts. Both the 4 to 20 mA
option is not required when using entering-water, outdoor- and 2-step demand limit percentage values are adjustable.
air, or space temperature for temperature reset. These EMM is also available as a factory-installed option.

19
Application data
Unit location form of condenser flow control be used to optimize
Unit should be level to assure (particularly in its major performance. Tower pump, bypass valves, or flow
lengthwise dimension) proper oil return. regulating valves may be controlled by a 4 to 20 mA
output from the 30HXC control (60-second open to
The unit should be located indoors in an area of temper-
close time recommended for actuator).
ature greater than 50 F (10 C).
Good acoustic design practice should be followed, i.e., Cooler and fluid-cooled condenser
unit should not be located adjacent to sound sensitive areas temperature rise
unless appropriate consideration has been made. Ratings and performance data in this publication are for a
Cooler fluid temperature cooling temperature rise of 10° F (5.6° C). Units may be
operated at a different temperature rise, provided flow lim-
1. Maximum leaving chilled-fluid temperature (LCWT) is its are not exceeded and corrections to capacity, etc., are
60 F (21 C). Unit can start and pull down with up to made. For minimum flow rates, see the Minimum Flow
95 F (35 C) entering-fluid temperature due to MOP Rates table. High flow rate is limited by pressure drop that
(maximum operating pressure) feature of the expansion can be tolerated.
valve. For sustained operation, it is recommended that
entering fluid temperature not exceed 70 F (21.1 C). Minimum cooler flow — Flow (maximum cooler tem-
perature rise) is shown in the Minimum Flow Rates table.
2. Minimum LCWT is 40 F (4 C) for standard units. Minimum flow rate must be maintained to prevent fouling.
Special-order brine units are required for operation with When gpm (L/s) required is lower (or rise is higher), follow
leaving fluid temperatures in the range of 39 to 12 F recommendations below:
(4 to –9 C). For ratings below 40 F (4 C) LCWT, contact
your local Carrier representative. 1. Multiple smaller chillers can be applied in series, each
providing a portion of the design temperature rise.
3. Minimum entering chilled-fluid temperature (ECWT) is
45 F (7.2 C). Maximum ECWT is 70 F (21.1 C). 2. Chilled fluid can be recirculated to raise flow rate. How-
ever, mixed temperature entering cooler must be main-
Leaving-fluid temperature reset tained at a minimum of at least 5° F (2.8° C) above the
The accessory reset sensor can be applied to the chiller to leaving chilled fluid temperature.
provide reset of LCWT in constant fluid flow systems. 3. Special plus one-pass cooler can be used. Contact your
Reset reduces compressor power usage at part load when Carrier representative for further information.
design LCWT is not necessary. Humidity control should be MINIMUM FLOW RATES
considered, since higher coil temperatures resulting from
reset will reduce latent heat capacity. Three reset applica- DEVICE UNIT SIZE
Type
COOLER
No. of Passes
MINIMUM FLOW
RATE GPM (L/s)
tions are offered: Minus-One-Pass 2 60 (3.8)
076,086 Standard 3 39 (2.4)
From return-fluid temperature — Increases LCWT set Plus-One-Pass 4 33 (2.1)

point as return (or entering) fluid temperature decreases Minus-One-Pass 2 61 (3.8)


096 Standard 3 44 (2.8)
(indicating load decrease). Reset from return fluid may be Plus-One-Pass 4 33 (2.1)
used in any application where return fluid provides accu- Minus-One-Pass 2 74 (4.7)
49 (3.1)
rate load indication. Limitation of return-fluid reset is that 106 Standard 3
41 (2.6)
Plus-One-Pass 4
the LCWT may only be reset to value of design return-fluid Minus-One-Pass 1 103 (6.5)

temperature. No additional hardware is required. 116,126 Standard 2 60 (3.8)


Plus-One-Pass 3 39 (2.4)
From outdoor-air temperature — Increases LCWT as Minus-One-Pass 1 118 (7.4)
61 (3.8)
outdoor ambient temperature decreases (indicating load COOLER 136,146 Standard
Plus-One-Pass
2
3 44 (2.8)
decrease). This reset should be applied only where outdoor Minus-One-Pass 1 138 (8.7)

ambient temperature is an accurate indication of load. A 161,171 Standard 2 74 (4.7)


49 (3.1)
Plus-One-Pass 3
field-supplied thermistor is required. Minus-One-Pass 1 166 (10.5)
87 (5.5)
From occupied space temperature — Increases 186 Standard
Plus-One-Pass
2
3 58 (3.7)
LCWT as space temperature decreases (indicating load Minus-One-Pass 1 191 (12.0)

decrease). This reset should be applied only where space 206 Standard 2 101 (6.3)
65 (4.1)
Plus-One-Pass 3
temperature is an accurate indication of load. A field-sup- Minus-One-Pass 1 212 (13.3)

plied thermistor is required. 246-271 Standard 2 111 (7.0)


Plus-One-Pass 3 83 (5.2)

Condenser fluid temperature 076,086 — 2 105 (6.6)


135 (8.5)
096,106 — 2

1. Maximum leaving condenser fluid temperature is 116,126 — 2 170 (10.7)


195 (12.3)
136,146 — 2
105 F (40.5 C) on all 30HXC units. 161 — 2 235 (14.8)
CONDENSER 255 (16.1)
2. Standard 30HXC units will start at entering con- 171,186
206


2
2 273 (17.2)
denser fluid temperatures above 55 F (12.8 C). In 246 — 2 333 (21.0)

general, however, continuous machine operation with 261 — 2 333 (21.0)


333 (21.0)
271 — 2
entering condenser fluid temperatures below 70 F NOTES:
(21.1 C) is not recommended. When the entering 1. The 30HX units will start with loop temperatures up to 95 F (35 C).
2. Minimum flow rate shown is based on 1 ft/sec minimum velocity and is for reference only. 20 F (11.1 C) is the
condenser fluid temperature is expected to drop maximum cooler temperature differential that will determine actual minimum flow rate.
3. To obtain proper temperature control, loop fluid volume must be at least 3 gal/ton (3.23 L/kW) of chiller nominal
below 70 F (21.1 C), it is recommended that some capacity for air conditioning and at least 6 gal/ton (6.5 L/kW) for process applications.

20
condenser flow rates must be balanced to ensure proper
RECIRCULATION FLOW flow to each chiller. The standard 30HX ComfortLink™
control can be configured to provide lead/lag control for
two chillers. The accessory Chillervisor™ System Manager
III control may be used for proper leaving chilled fluid tem-
perature control and to ensure proper staging sequence of
up to 8 chillers. Refer to the accessory Chillervisor System
Manager III installation instructions for further details.
Series chillers
Chillers in series may be used for capacities greater than
those supplied by a single 30HX chiller. Using the Minus-
One-Pass Cooler Head option, fluid pressure drop across
the cooler can be held to reasonable levels. The leaving
Maximum cooler flow (> 5 gpm/ton or < 5° F rise fluid temperature sensors need not be relocated. However,
[> 0.09 L/s · kW or < 2.7° C rise]) — Maximum flow the cooler minimum entering fluid temperature limitations
results in practical maximum pressure drop through cooler. should be considered for the chillers located downstream of
Special minus-one-pass cooler can be used to reduce pres- other chillers. The standard 30HX control can control two
sure drop. Contact your Carrier representative. 30HX chillers in series. Condensers should be piped in
Return fluid can bypass the cooler to keep pressure parallel to maximize capacity and efficiency. This should
drop through cooler within acceptable limits. This permits also minimize condenser pressure drop and saturated con-
a higher ∆T with lower fluid flow through cooler and mix- densing temperatures. However, if condensers are piped in
ing after the cooler. Contact your Carrier representative if series, ensure that the leaving water temperature does not
pressure drop appears excessive. exceed 105 F (40.5 C).
Variable cooler flow rates — These variable rates may Energy management
be applied to standard 30HX series chillers. However, the Demand limiting and load shedding are popular techniques
unit will attempt to maintain a constant leaving chilled-fluid used to reduce peak electric demands typically experienced
temperature. In such cases, minimum fluid loop volume during hot summer days when air conditioning loads are
must be in excess of 3 gpm per ton (3.2 L per kW) and highest. When utility electricity demands exceed a certain
flow rate must change in steps of less than 10% per level, electrical loads are turned off to keep the peak
minute. Apply 6 gal per ton (6.5 L per kW) fluid loop vol- demands below a prescribed maximum limit. Compressor
ume minimum if flow rate changes more rapidly. unloading reduces electrical demand while allowing the
Minimum fluid-cooled condenser flow — This value chiller to operate under part-load capacity and to maintain
(maximum rise) is shown in Minimum Flow Rates table. partial chilled fluid cooling.
Ensure leaving-fluid temperature does not exceed 105 F Electrical demand can be limited through demand limit
(40.5 C). input to chiller control which unloads the chiller to a prede-
Oversizing chillers termined percentage of the load. One stage of unloading
can be initiated by a remote signal to significantly reduce
Oversizing chillers by more than 15% at design conditions the chiller power consumption. This power reduction
must be avoided as the system operating efficiency will be applies to the full load power at nominal conditions. The
adversely affected (resulting in greater and/or excessive demand limit control should not be cycled less than
electrical demand and cycling of compressors). When 10 minutes on and 5 minutes off.
future expansion of equipment is anticipated, install a sin-
gle chiller to meet present load requirements, and install a Duty cycling
second chiller to meet the additional load demand. Duty cycling will cycle an electrical load at regular inter-
It is also recommended that the installation of 2 smaller vals, regardless of electrical demand. This reduces the elec-
chillers be considered where operation at minimum load is trical demand by “fooling” demand measuring devices.
critical. The operation of 2 small chillers at higher loading Duty cycling of the entire compressor is NOT recom-
is preferred to operating a single chiller at or near its mini- mended since motor windings and bearings will be dam-
mum recommended value. aged by constant cycling.
The minimum load control accessory should not be used Wye-delta start
as a means to allow oversizing chillers. Minimum load con-
trol should be given consideration where substantial oper- Wye-delta start is standard on 30HX 208/230 v 60 Hz
units and 230 v 50 Hz units and optional on all other
ating time is anticipated below the minimum unloading
30HX units. This feature is not always required on 30HX
step.
units due to the use of multiple compressors that allow
Parallel chillers small electrical load increments, but is available if required.
Where chiller capacities greater than can be supplied by a Maximum instantaneous current flow (see ICF in Electrical
single 30HX chiller are required, or where stand-by cap- Data tables on pages 67-72 should be used in determining
ability is desired, chillers may be installed in parallel. Units need.
may be of the same or different sizes. However, cooler and

21
Application data (cont)
Vibration isolation Use only antifreeze solutions approved for heat
External vibration isolators are available as field-installed exchanger duty. Use of automotive antifreezes is not rec-
accessories. ommended because of the fouling that can occur once
their relatively short-lived inhibitors break down.
Strainers If not protected with an antifreeze solution, draining
A strainer with a minimum screen size of 20 mesh should cooler and outdoor piping is recommended if system will
be installed in both the cooler and condenser fluid lines, not be used during freezing weather conditions.
just ahead of the cooler and condenser, and as close to the
cooler and condenser as possible. For 30HXA units, this 30HXA remote condenser requirements
recommendation applies only to the cooler. 1. Do not manifold independent refrigerant circuits into
a single condenser.
Chilled fluid loop volume
2. Ensure each refrigerant circuit has its own head pres-
The chilled fluid loop volume in circulation must equal or sure control.
exceed 2 gal per nominal ton of cooling (2 L per kW) for
temperature stability and accuracy in normal air condition- 3. Condensing pressure control must be provided on
ing applications. For example, a 30HXC096 with a nomi- condensers used with 30HXA to maintain a minimum
nal capacity of 93.4 tons would require 186.8 gal (707 L) 75 F (24 C) saturated discharge temperature at light
in circulation in the system loop. loads.
For process jobs where accuracy is vital, or for opera- 4. Condenser must provide 15° F (–8.3° C) subcooling,
tion at ambient temperatures below 32 F (0° C) with low a maximum of 40° F (22.2° C) difference between
unit loading conditions, there should be from 6 to 10 gal saturated condensing temperature and outdoor ambi-
per ton (6.5 to 10.8 L per kW). To achieve this volume, it ent temperature (to prevent overload at high ambient
is often necessary to install a tank in the loop. Tank should temperatures), and a minimum of 20° F (–11.1° C)
be baffled to ensure there is no stratification, and that difference (to assure subcooling).
water (or brine) entering tank is adequately mixed with liq- 5. Minimum saturated discharge temperature (SDT) is
uid in the tank. See below. 90 F (32.2 C). Maximum SDT is 135 F (57.2 C) at
full load.
6. Condenser should not be located more than 15 ft
TANK INSTALLATION
(4.6 m) below chiller to maintain subcooling.
7. Design discharge and liquid piping according to
Carrier System Design Manual. Piping must be sized
for HFC-134a. Refer to the ASHRAE Refrigeration
Handbook for R-134a sizing tables. Also see 30HX
Installation instructions and the Typical 30HXA
Refrigerant Piping to Remote Condenser diagram on
page 27.
8. Maximum interconnecting refrigerant line length is
200 ft (61 m) actual.
9. Liquid line solenoid valves required when condenser is
located above chiller and liquid line length exceeds
50 ft (15 m).
Fouling factor
10. If accessory sound enclosure is installed, run lines
The factor used to calculate tabulated ratings for the cooler along the floor so the sound enclosure can be notched
is 0.00010 ft2 · hr · F/Btu (0.000018 m2 · K/W), and for to clear lines.
the condenser is 0.00025 ft2 · hr · F/Btu (.000044 m2 ·
K/W). As fouling factor is increased, unit capacity Refrigerant pipe sizing for 30HXA with Carrier
decreases and compressor power increases. To determine 09D condenser combinations — For refrigerant pipe
selections at other fouling factors, use the chiller program sizing of the 30HXA follow these directions:
in the electronic catalog. Discharge line:
Cooler and fluid-cooled condenser freeze 1. For applications at conditions of 40 F (4.4 C) or
protection higher LWT (leaving water temperature), use the
Refrigerant Line Sizes for 30HXA Chiller/09DK
If chiller refrigerant or fluid lines are in an area where ambi- Condenser Combinations tables on pages 24 and 25.
ent conditions fall below 32 F (0° C), it is recommended
that an antifreeze solution be added to protect the unit and For applications using brine, other condensers, or
fluid piping to a temperature 12° F (–11.1° C) below the LWT below 40 F (4.4 C), size lines using the
lowest anticipated temperature. For corrections to perfor- ASHRAE Refrigeration Handbook, or other suitable
mance, refer to the chiller program in the electronic design guide.
catalog. 2. Install horizontal lines level or pitched slightly toward
the base of discharge riser and the condenser (in the
direction of flow).

22
3. If chiller is below the condenser, loop the discharge required. The solenoid valves must be located close to
line to at least one inch above the top of condenser. the chiller.
4. If chiller is below the condenser, some standard units 5. If sound enclosure is applied, run lines along floor so
and all units with MINIMUM LOAD CONTROL sound enclosure may be notched to clear lines.
require double discharge riser as shown in Double 6. In-line receivers are NOT recommended due to their
Discharge Riser Pipe Sizes table. negative effect on system subcooling. Where the use
5. Minimize line length and restrictions to minimize pres- of a receiver is desired for service purposes, the
sure drop and refrigerant charge. receiver should be piped in parallel with the main liq-
6. If accessory sound enclosure is applied, run lines uid line and equipped with shut-off valves to isolate it
along the floor so sound enclosure may be notched to during unit operation. See sketch below:
clear lines.
7. Lines should not be buried underground.
FROM LIQUID LINE TO
Liquid line: CONDENSER CHILLER

1. For applications at conditions of 40 F (4.4 C) or STORAGE


higher LWT (leaving water temperature), use the RECEIVER
Refrigerant Line Sizes for 30HXA Chiller/09DK
Condenser Combinations tables on pages 24 and 25.
For applications using brine, other condensers, or Relief valve vent lines
LWT below 40 F (4.4 C), size lines using the 1. Vent per local code requirements.
ASHRAE Refrigeration Handbook, or other suitable
2. Each chiller has a minimum of 4 refrigerant relief
design guide.
valves: 2 on the cooler, 2 on the condenser (30HXC)
2. If chiller is above condenser, maximum vertical sepa- or oil separator (30HXA). Units with factory-installed
ration is 15 ft. suction service valves also have 2 relief valves on the
3. Minimize line length and restrictions to minimize pres- compressor discharge line. See Dimensions section
sure drop and refrigerant charge. on pages 8-15 for specific locations.
4. Above 50 ft liquid line length and where chiller is 3. If sound enclosure is applied, run lines along floor so
below condenser, liquid line solenoid valves are sound enclosure may be notched to clear lines.

23
Application data (cont)
REFRIGERANT LINE SIZES FOR 30HXA CHILLER/09DK CONDENSER COMBINATIONS
RECOMMENDED REFRIGERANT PIPE SIZES (in. OD)

TOTAL LENGTH OF INTERCONNECTING PIPING — FT (M)


30HXA UNIT SIZE CKT 0-50 (0-15) 50-100 (15-30) 100-200 (30-60)
Liquid Line* Discharge Line† Liquid Line* Discharge Line† Liquid Line* Discharge Line†
A 11/8 21/8 11/8 21/8 13/8 21/8
076
B 11/8 21/8 11/8 21/8 13/8 21/8
A 11/8 21/8 13/8 21/8 13/8 21/8
086
B 11/8 21/8 11/8 21/8 13/8 21/8
A 11/8 21/8 13/8 21/8 15/8 25/8
096
B 11/8 21/8 11/8 21/8 13/8 21/8
A 13/8 21/8 13/8 25/8 15/8 25/8
106
B 13/8 21/8 11/8 21/8 13/8 21/8
A 13/8 21/8 13/8 25/8 15/8 25/8
116
B 13/8 21/8 13/8 21/8 13/8 21/8
A 13/8 21/8 13/8 25/8 15/8 25/8
126
B 13/8 21/8 13/8 21/8 15/8 25/8
A 13/8 25/8 15/8 25/8 15/8 31/8
136
B 13/8 21/8 13/8 21/8 15/8 25/8
A 13/8 25/8 15/8 25/8 15/8 31/8
146
B 13/8 21/8 13/8 25/8 15/8 25/8
A 13/8 25/8 15/8 25/8 21/8 21/8
161
B 13/8 21/8 13/8 25/8 15/8 25/8
A 13/8 25/8 15/8 25/8 15/8 31/8
171
B 13/8 25/8 15/8 25/8 21/8 31/8
A 13/8 25/8 15/8 25/8 21/8 31/8
186
B 13/8 25/8 15/8 25/8 21/8 31/8
A 15/8 25/8 15/8 31/8 25/8 31/8
206
B 13/8 25/8 15/8 25/8 21/8 31/8
A 21/8 31/8 25/8 31/8 25/8 31/8
246
B 13/8 25/8 15/8 25/8 25/8 31/8
A 21/8 31/8 25/8 31/8 25/8 31/8
261
B 13/8 25/8 15/8 25/8 21/8 31/8
A 21/8 31/8 25/8 31/8 25/8 31/8
271
B 13/8 25/8 15/8 25/8 21/8 31/8
LEGEND NOTES:
OD — Outside Diameter 1. Refrigerant and Double Discharge Riser Pipe Sizes tables are based on equal
chiller and 09DK condenser sizes — i.e., 30HXA096 with 09DK094.
*Above 50 ft liquid line length and where chiller is below condenser, liquid line 2. For other system combinations, size lines per ASHRAE (American Society of
solenoid valve is required.
†Double discharge riser is required on ALL units which have minimum load con- Heating, Refrigerating, and Air Conditioning Engineers) or other R-134a line
trol installed. sizing guide.
3. Refrigerant and Double Discharge Rise Pipe Sizes tables are based on cooler
Values indicate double discharge riser required on STANDARD unit. See leaving water temperatures of 40 F (4.4 C) or above.
Doub Double Discharge Rear Pipe Sizes table on page 25. 4. Line lengths refer to actual line length, not total equivalent length. A 50%
allowance has been included for fittings.

24
REFRIGERANT LINE SIZES FOR 30HXA CHILLER/09DK CONDENSER COMBINATIONS (cont)
DOUBLE DISCHARGE RISER PIPE SIZES (in. OD)

RISER ‘‘A’’ RISER ‘‘B’’


30HXA UNIT SIZE CKT Total Length of Interconnecting Piping — FT (M)*
0-200 (0-60) 0-50 (0-15) 50-100 (15-30) 100-200 (30-60)
A 11/8 15/8 15/8 15/8
076
B 11/8 15/8 15/8 15/8
A 11/8 15/8 15/8 15/8
086
B 11/8 15/8 15/8 15/8
A 11/8 15/8 15/8 21/8
096
B 11/8 15/8 15/8 15/8
A 15/8 15/8 21/8 21/8
106
B 13/8 13/8 13/8 13/8
A 15/8 15/8 21/8 21/8
116
B 13/8 15/8 15/8 15/8
A 15/8 21/8 21/8 21/8
126
B 13/8 15/8 15/8 21/8
A 15/8 21/8 21/8 25/8
136
B 13/8 15/8 15/8 21/8
A 15/8 21/8 21/8 25/8
146
B 15/8 15/8 21/8 21/8
A 15/8 21/8 21/8 25/8
161
B 15/8 15/8 21/8 21/8
A 15/8 21/8 21/8 25/8
171
B 15/8 21/8 21/8 25/8
A 15/8 21/8 21/8 25/8
186
B 15/8 21/8 21/8 25/8
A 15/8 21/8 21/8 25/8
206
B 15/8 21/8 21/8 25/8
A 15/8 21/8 21/8 25/8
246
B 15/8 21/8 21/8 25/8
A 15/8 21/8 21/8 25/8
261
B 15/8 21/8 21/8 31/8
A 15/8 21/8 21/8 25/8
271
B 15/8 21/8 31/8 31/8

LEGEND
A — Riser Without Trap DOUBLE DISCHARGE RISER
B — Riser With Trap CONSTRUCTION DETAIL
OD — Outside Diameter
* Total Length of Interconnecting Piping refers to actual length, not total equiva-
lent length.
TO
NOTE: Horizontal line sections should be sized according to the Total Length of CONDENSER
Interconnecting Piping columns on the Recommended Refrigerant Piping Sizes
table on page 24.

A B

RED.
TEE

FROM
CHILLER

45 DEGREE 90 DEGREE
STR ELLS STR ELLS

LEGEND
RED. TEE — Reducing Tee
STR ELLS — Street Elbows

25
Application data (cont)
For chillers using brine or those matched with other con- System refrigerant charge — The 30HXA units are
densers, the lines must be sized manually using design shipped from the factory with a small holding charge of
guides such as ASHRAE, or curves in the 30HXA installa- R-134a refrigerant. The approximate refrigerant charge
tion instructions. In many 30HXA sizes, the individual required for starting the 30HXA system is listed in the table
refrigerant circuits have unequal capacities. The Circuit below. This initial charge will allow starting of the unit.
Cooling Capacity table below lists the percentage capacity Additional refrigerant may be required to accommodate liq-
of each circuit for line sizing purposes. The Circuit Unload- uid line storage. See the liquid line refrigerant storage
ing Capacity table below indicates the minimum unloading capacity table below for liquid line storage information.
capacities per circuit as well as a sample calculation of the
minimum circuit tonnage for riser design. The example SYSTEM REFRIGERANT CHARGE FOR START-UP
below lists circuit capacity calculations based on the Circuit REFRIGERANT BASE CHARGE
Cooling and Circuit Unloading Capacity tables. 30HXA UNIT (FOR ESTIMATING
CKT PURPOSES ONLY)
SIZE
CIRCUIT COOLING CAPACITY lbs kg
A 75 34
PERCENT OF TOTAL UNIT CAPACITY 076
30HXA UNIT SIZE B 75 34
Circuit A % Circuit B %
A 94 43
076 50 50 086
B 80 36
086 55 45
A 114 52
096 59 41 096
B 80 36
106 64 36
A 134 61
116 60 40 106
B 80 36
126 55 45
A 137 62
136 59 41 116
B 95 43
146 55 45 A 137 62
126
161 59 41 B 116 53
171 47 53 A 147 67
136
186 50 50 B 125 57
206 54 46 A 161 73
146
246 61 39 B 132 60
261 63 37 A 190 86
161
271 64 36 B 132 60
A 154 70
171
CIRCUIT UNLOADING CAPACITY B 186 85
A 186 85
MINIMUM CIRCUIT CAPACITY — 186
PERCENT OF FULL LOAD B 186 85
30HXA UNIT
Standard Unit With Minimum A 224 102
Load Control 206
B 169 77
All Sizes, 40% 20%
All Circuits A 288 131
246
B 169 77
Example Calculation of Circuit Capacities: A 311 141
261
Select (Standard) 30HXA086 Chiller B 168 76
From Electronic catalog (E-cat) selection or balance diagram: A 335 152
Total Unit Capacity = 74 tons (from unit selection at design 271
B 165 75
conditions)
NOTE: Multiply the liquid line length (in feet) by the factor shown
Using the Circuit Cooling Capacity table: below for the refrigerant/ft of the tubing. Add base unit charge to liq-
Ckt “A” design capacity = 74 x 0.55 = 40.7 tons uid line charge to determine approximate refrigerant charge.
Using the Circuit Unloading Capacity table:
Ckt “A” minimum capacity = 40.7 x 0.40 = 16.3 tons LIQUID LINE REFRIGERANT STORAGE CAPACITY
Ckt “B” design capacity = 74 x 0.45 = 33.3 tons REFRIGERANT (lbs) REFRIGERANT (kg)
Ckt “B” minimum capacity = 33.3 x 0.40 = 13.3 tons PIPING SIZE (in.) PER FT OF TUBING PER M OF TUBING
LENGTH LENGTH
11 / 8 0.41 0.61
13 / 8 0.63 0.94
15 / 8 0.89 1.33
21 / 8 1.52 2.26
25 / 8 2.32 3.45

26
TYPICAL 30HXA REFRIGERANT PIPING TO REMOTE CONDENSER

ACCESSORY SOUND ENCLOSURE

RELIEF VALVES
(IF REQUIRED BY CODE)
COMPRESSOR

DOUBLE RISER
(IF REQUIRED)

COOLER

OIL
SEPARATOR

DISCHARGE
LINES

LIQUID LINE LIQUID LINES CONDENSER


SOLENOID VALVES
LIQUID LINE (IF REQUIRED)
ANGLE VALVE MECHANICAL ROOM

27
Selection procedure (with example)
Carrier’s electronic catalog chiller selection program pro- SI (50 Hz)
vides quick, easy selection of Carrier chillers. The program I Determine 30HXC unit size and operating condi-
considers specific temperature and flow requirements and tions required to meet given capacity at given-
other factors, such as fouling and altitude correction. It can conditions.
also select an air-cooled condenser for the condenserless
Given:
30HXA unit to match the required conditions. To select a
30HXA unit, use the electronic catalog or contact your Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . 617 kW
Carrier representative. To select a 30HXC chiller, use the Leaving Chilled Water Temp (LCWT) . . . . . . . . . . 7 C
electronic catalog or follow one of the procedures below. Cooler Water Temp Rise . . . . . . . . . . . . . . . . . 5.6° C
ENGLISH (60 Hz) Condenser Entering Water Temp . . . . . . . . . . . . 30 C
I Determine 30HXC unit size and operating condi- Condenser Water Temp Rise . . . . . . . . . . . . . . 5.6° C
tions required to meet given capacity at given-
conditions. Cooling Fouling Factor . . . . . . . . . . . . . . . . .0.01761
Given: Condenser Fouling Factor . . . . . . . . . . . . . . .0.04403
Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . 175 Tons NOTE: For other than 5.6° C temperature rise, data
corrections must be made using the chiller program in
Leaving Chilled Water Temp (LCWT) . . . . . . . . . .44 F the electronic catalog. On some units, a change of con-
Cooler Water Temp Rise . . . . . . . . . . . . . . . . . . 10° F trols is also necessary.
Condenser Entering Water Temp . . . . . . . . . . . . .85 F II From Cooling Capacities table on page 41 and
Condenser Water Temp Rise . . . . . . . . . . . . . . . 10° F pressure drop curves on pages 55 and 56,
Cooling Fouling Factor . . . . . . . . . . . . . . . . .0.00010 determine operating data for selected unit.
Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 30HXC186
Condenser Fouling Factor . . . . . . . . . . . . . . .0.00025
Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . 628.5 kW
NOTE: For other than 10° F temperature rise, data
corrections must be made using the chiller program in Compressor Motor Power Input . . . . . . . . . . 135.4 kW
the electronic catalog. On some units, a change of con- Cooler Water Flow . . . . . . . . . . . . . . . . . . . .27.0 L/s
trols is also necessary. Cooler Pressure Drop . . . . . . . . . . . . . . . . . 36.1 kPa
II From Cooling Capacities table on page 31 and Condenser Water Flow . . . . . . . . . . . . . . . . .32.6 L/s
pressure drop curves on pages 55 and 56,
determine operating data for selected unit. Condenser Pressure Drop . . . . . . . . . . . . . . 32.0 kPa
Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 30HXC186
Capacity . . . . . . . . . . . . . . . . . . . . . . . . . 177.4 tons
Compressor Motor Power Input . . . . . . . . . . 133.3 kW
Cooler Water Flow . . . . . . . . . . . . . . . . . . 425.2 gpm
Cooler Pressure Drop . . . . . . . . . . . . . 12.1 ft of water
Condenser Water Flow . . . . . . . . . . . . . . . 511.8 gpm
Condenser Pressure Drop . . . . . . . . . . 16.7 ft of water

28
Performance data
30HXC Ratings 3. Condenser fouling factor of .00025 ft2 · hr · F/Btu
All performance data is based on: (.000044 m2 · K/W).
1. Cooler water temperature rise of 10° F (5.6° C). 4. 10° F (5.6° C) subcooling.
2. Cooler fouling factor of .00010 ft2 · hr · F/Btu 5. Refrigerant 134a.
(.000018 m2 · K/W).
30HXC ARI* RATINGS (60 Hz Only)

COOLER CONDENSER CONDENSER


UNIT CAPACITY INPUT COOLER FLOW PRESSURE PRESSURE FULL-LOAD
DROP FLOW DROP IPLV†
SIZE POWER EFFICIENCY (kW/Ton)
30HXC (kW) Ft of Ft of (kW/Ton)
Tons kW Gpm L/s kPa Gpm L/s kPa
Water Water
076 75.3 264.9 55.0 180.8 11.4 12.6 37.6 226.0 14.3 8.0 23.8 0.730 0.528
086 83.0 291.9 61.7 199.2 12.6 15.0 44.8 249.0 15.7 9.6 28.5 0.743 0.540
096 93.9 330.2 68.9 225.3 14.2 14.8 44.3 281.7 17.8 9.9 29.4 0.734 0.529
106 104.2 366.3 77.5 250.0 15.8 13.4 40.0 312.5 19.7 11.9 35.6 0.744 0.548
116 113.5 399.0 82.0 272.3 17.2 11.7 34.8 340.4 21.5 15.2 45.4 0.723 0.525
126 122.9 432.1 89.5 294.9 18.6 13.5 40.2 368.6 23.3 17.6 52.6 0.729 0.528
136 136.4 479.3 100.3 327.3 20.6 12.8 38.3 409.1 25.8 16.7 49.9 0.736 0.546
146 145.8 512.9 108.7 350.0 22.1 14.5 43.3 437.5 27.6 18.9 56.5 0.745 0.554
161 156.6 550.9 116.4 375.9 23.7 12.0 35.7 469.9 29.6 19.4 57.9 0.743 0.585
171 166.1 584.3 122.7 398.7 25.2 13.3 39.7 498.4 31.4 15.9 47.5 0.739 0.564
186 177.6 624.5 132.5 426.2 26.9 12.2 36.3 532.8 33.6 18.2 53.9 0.746 0.592
206 211.7 744.5 151.3 508.1 32.1 12.8 38.2 635.1 40.1 19.0 56.7 0.715 0.527
246 248.8 875.1 178.9 597.2 37.7 14.1 42.2 746.5 47.1 20.1 60.0 0.719 0.538
261 257.5 905.6 186.9 618.0 39.0 15.0 44.9 772.5 48.7 21.5 64.0 0.726 0.540
271 267.7 941.6 196.9 642.6 40.5 16.1 48.1 803.2 50.7 23.1 68.9 0.735 0.543
LEGEND 3. IPLV is a single number part-load efficiency value calculated from
IPLV — Integrated Part-Load Value the system full-load efficiency values and corrected for a typical
building air-conditioning application.
*Air Conditioning and Refrigeration Institute (U.S.A.). 4. All data in this table is rated (60 Hz only) in accordance with ARI
†IPLV shown is for unloading sequence A. Standard 550/590-98 as represented in the ECOLOGIC™ Chiller
Selection Program (E-Cat) version 2.11.
NOTES:
1. Rated (60 Hz only) in accordance with ARI Standard 550/590-98 at
standard rating conditions.
2. Standard rating conditions are as follows:
Cooler Conditions: Rated in accordance with
Leaving water temperature: 44 F (6.7 C) ARI Standard 550/590-98.
Flow: 2.4 gpm per ton (0.043 L/s per kW)
Condenser Conditions:
Entering water temperature: 85 F (29.4 C)
Flow: 3 gpm per ton (0.054 L/s per kW) 60 Hz Only
Fouling Factor (Cooler):
0.00010 hr x sq ft x F per Btuh (0.000018 m2 x K per W)
Fouling Factor (Condenser):
0.00025 hr x sq ft x F per Btuh (0.000044 m2 x K per W).

29
Performance data (cont)
30HXA Ratings 2. Combining 30HXA units with remote condensers
1. All performance data is based on: which have greater than (less than) the 10° F (5.6° C)
subcooling in the ratings, increases (decreases) system
a. Cooler water temperature rise of 10° F (5.6° C). capacity. To adjust capacity, multiply capacity ratings
b. Cooler fouling factor of .00010 ft2 · hr · F/Btu by 0.96; then adjust this result upward by 0.4% for
(.000018 m2 · K/W). each degree F (0.7% for each degree C) of available
c. 10° F (5.6° C) subcooling. subcooling.
d. Refrigerant 134a.

30HXA ARI* RATINGS (60 Hz Only)

CAPACITY COOLER FLOW COOLER AIR COOLED CONDENSER


UNIT SIZE INPUT PRESSURE DROP
30HXA POWER EER
(kW) Ft of
Tons kW Gpm L/s kPa UNIT (QTY)
Water
076 67.5 237.5 76.8 162.1 10.2 10.4 31.0 9.4 09DK084 (1)
086 73.9 259.8 86.9 177.3 11.2 12.2 36.4 9.2 09DK084 (1)
096 82.6 290.5 98.6 198.2 12.5 11.8 35.0 9.1 09DK094 (1)
106 95.2 334.9 109.2 228.6 14.4 11.4 34.0 9.2 09DK074 (1) and (1) 044 (2)
116 102.1 359.1 118.4 245.1 15.5 9.7 28.9 9.1 09DK074 (1) and (1) 054 (2)
126 112.8 396.8 127.1 270.8 17.1 11.6 34.5 9.2 09DK074 (2)
136 122.1 429.5 143.3 293.1 18.5 10.5 31.4 9.0 09DK074 (2)
146 126.6 480.5 151.3 327.9 20.7 12.9 38.4 9.6 09DK084 (2)
161 143.8 505.8 164.8 345.2 21.8 10.3 30.6 9.4 09DK084 (2)
171 154.5 543.2 181.5 307.7 23.4 11.7 34.8 9.2 09DK084 (2)
186 166.3 584.8 205.8 399.1 25.2 10.8 32.3 8.9 09DK084 (2)
206 197.9 696.1 214.1 475.1 30.0 11.4 34.0 9.8 09DK084 (2) and (1) 094 (3)
246 229.9 808.6 254.3 551.8 34.8 12.3 36.6 9.7 09DK094 (3)
261 241.0 847.5 272.5 578.4 36.5 13.4 39.8 9.6 09DK094 (3)
271 252.4 887.7 292.9 605.8 38.2 14.5 43.3 9.4 09DK094 (3)
LEGEND NOTES:
EER — Energy Efficiency Ratio (Capacity [Btuh] ÷ Input Power [W]) 1. Rated in accordance with ARI Standard 550/590-98 at standard rat-
ing conditions.
* Air Conditioning and Refrigeration Institute (U.S.A.). 2. Standard rating conditions are as follows:
Cooler Conditions:
Leaving water temperature: 44 F (6.7 C)
Flow: 2.4 gpm per ton (0.043 L/s per kW)
Condenser Conditions:
Entering air temperature: 95 F (35 C)
3. All data in this table is rated in accordance with ARI Standard 550/
590-98 as represented in the ECOLOGIC™ Chiller Selection Pro-
gram (E-Cat) version 2.11.

30
30HXC COOLING CAPACITIES
60 Hz, ENGLISH

CONDENSER ENTERING WATER TEMPERATURE (F)


80 85 90 95
UNIT
LCWT Cooler Cond Cooler Cond Cooler Cond Cooler Cond
SIZE
(F) Input Flow Flow Input Flow Flow Input Flow Flow Input Flow Flow
30HXC Cap. Cap. Cap. Cap.
kW Rate Rate kW Rate Rate kW Rate Rate kW Rate Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
076 71.5 51.2 171.1 204.5 68.4 54.1 163.8 199.1 65.6 57.1 156.9 194.2 63.3 60.4 151.5 191.0
086 78.8 57.4 188.7 226.0 75.5 60.6 180.8 220.3 72.6 63.9 173.7 215.5 70.1 67.6 187.9 212.1
096 89.1 64.2 213.2 255.0 85.4 67.9 204.3 248.6 82.0 71.6 196.2 242.9 79.3 75.8 189.7 239.3
106 98.9 72.2 236.8 283.8 94.6 76.3 226.5 276.3 90.9 80.8 217.5 270.3 87.9 85.8 210.4 266.5
116 107.6 76.5 257.5 307.3 103.1 81.0 246.8 299.7 98.7 85.6 236.3 292.3 95.5 91.0 228.7 288.2
126 116.5 83.5 278.9 333.2 111.7 88.5 267.5 325.2 107.2 93.6 256.7 317.8 103.7 99.5 248.2 313.3
136 129.2 93.7 309.3 370.4 124.0 98.9 296.9 361.4 119.4 104.2 285.7 353.8 115.7 110.3 276.9 349.1
40 146 138.2 101.5 330.9 397.0 132.4 107.1 317.1 386.9 127.6 113.3 305.5 379.5 123.7 120.2 296.2 374.8
161 147.7 108.1 353.5 423.9 145.0 117.5 347.0 423.5 143.2 127.9 342.7 426.1 142.4 139.8 340.9 432.3
171 156.6 114.4 374.9 449.4 154.1 124.1 368.8 449.7 152.4 134.8 364.8 452.9 151.7 146.9 363.1 459.1
186 167.8 123.7 401.6 482.1 164.8 134.0 394.6 481.9 163.1 145.4 390.5 485.4 162.4 158.3 388.8 492.3
206 199.8 141.0 478.3 570.2 195.8 153.2 468.7 568.7 193.0 166.4 462.1 570.9 191.2 180.9 457.6 576.0
246 234.5 166.8 561.5 670.1 230.6 181.5 552.0 670.4 226.7 197.0 542.8 671.5 225.5 215.2 539.7 680.6
261 242.8 174.2 581.3 694.8 238.9 189.2 571.9 695.4 235.6 205.0 563.9 697.9 234.5 223.7 561.3 707.7
271 252.6 183.7 604.7 724.3 248.6 199.3 595.2 725.2 245.5 215.9 587.6 728.6 244.4 235.5 585.0 739.0
076 74.9 51.7 179.3 212.9 71.7 54.7 171.7 207.3 68.5 57.7 164.2 201.8 65.9 60.9 157.9 197.7
086 82.5 58.0 197.7 235.4 79.1 61.3 189.4 229.2 75.7 64.5 181.4 223.4 73.0 68.2 175.0 219.5
096 93.3 64.8 223.5 265.6 89.4 68.5 214.1 258.7 85.6 72.3 205.1 252.2 82.5 76.4 197.7 247.7
106 103.5 72.8 248.1 295.3 99.2 77.1 237.6 287.7 94.7 81.3 226.9 279.9 91.5 87.3 219.1 276.1
116 112.7 77.0 269.9 319.9 108.1 81.7 258.9 312.1 103.3 86.3 247.5 303.8 99.4 92.2 238.2 298.4
126 122.0 84.0 292.3 346.9 117.0 89.2 280.4 338.5 112.1 94.4 268.6 330.2 107.9 100.8 258.6 324.4
136 135.3 94.5 324.2 385.6 129.8 99.8 311.0 376.0 124.6 105.0 298.5 367.0 120.4 111.2 288.4 361.0
42 146 144.8 102.3 346.8 413.2 138.8 108.1 332.4 402.8 133.2 114.1 319.1 393.5 128.7 121.0 308.4 387.4
161 153.4 107.7 367.4 437.4 150.6 117.3 360.7 437.0 147.9 127.3 354.3 437.3 146.9 139.2 351.9 442.8
171 162.6 114.0 389.5 463.5 160.0 123.9 383.3 463.9 157.7 134.4 377.7 465.4 156.4 146.3 374.7 470.2
186 173.8 123.2 416.4 496.4 171.0 133.7 409.7 496.7 168.4 144.6 403.5 497.7 167.4 157.6 401.0 503.9
206 207.2 141.1 496.3 588.0 203.6 152.9 487.6 587.3 199.9 165.9 478.9 587.2 197.3 180.2 472.6 590.4
246 243.5 165.9 583.5 691.3 239.4 180.9 573.5 691.3 235.1 196.4 563.2 691.4 232.5 214.5 557.0 697.2
261 252.1 173.4 603.8 716.5 247.8 188.7 593.7 716.5 243.9 204.4 584.2 717.6 241.8 222.6 579.2 724.6
271 262.0 183.0 627.6 746.4 257.8 198.7 617.5 746.8 253.8 215.0 608.0 748.1 252.0 234.2 603.6 756.6
076 78.3 52.3 187.8 221.7 75.1 55.2 179.9 215.8 71.8 58.3 172.0 210.0 68.7 61.4 164.6 204.6
086 86.4 58.5 207.0 244.9 82.8 61.9 198.4 238.6 79.2 65.2 190.0 232.4 76.0 68.7 182.2 227.0
096 97.6 65.4 233.9 276.3 93.6 69.2 224.3 269.3 89.6 73.0 214.8 262.3 85.9 77.0 205.9 256.1
106 108.3 73.3 259.7 307.2 103.9 77.8 249.0 299.5 99.2 82.2 237.9 291.4 95.1 89.6 228.1 286.4
116 117.8 77.6 282.4 332.8 113.1 82.4 271.1 324.7 108.3 87.2 259.6 316.4 103.5 92.1 248.2 308.3
126 127.6 84.8 305.8 360.8 122.5 89.9 293.6 352.0 117.3 95.2 281.3 343.3 112.4 100.7 269.5 335.3
136 141.6 95.3 339.5 401.3 136.0 100.7 325.9 391.4 130.4 106.2 312.5 381.7 125.3 111.8 300.3 373.3
44 146 151.4 103.2 363.0 429.9 145.4 109.1 348.5 419.4 139.2 115.1 333.6 408.5 133.9 123.0 321.0 401.2
161 159.1 107.3 381.4 451.0 156.4 117.1 375.0 451.0 153.5 127.2 367.9 450.7 151.5 140.5 363.1 454.6
171 168.5 113.9 404.0 477.8 165.9 123.5 397.7 478.0 163.1 134.0 391.1 478.3 161.3 145.7 386.7 481.7
186 180.0 122.8 431.6 511.2 177.4 133.3 425.2 511.8 174.5 144.5 418.2 512.3 172.6 156.9 413.7 516.0
206 214.7 141.2 514.8 606.4 211.4 152.4 506.7 605.8 207.3 165.6 496.9 604.8 204.2 179.9 489.4 606.8
246 252.2 165.9 604.5 712.2 248.5 180.2 595.7 712.9 244.2 196.2 585.4 713.2 239.9 213.0 575.2 714.2
261 261.0 173.4 625.6 738.0 257.2 188.1 616.5 738.7 253.0 204.3 606.4 739.5 249.3 221.4 597.5 742.0
271 271.4 182.6 650.6 768.9 267.4 198.1 641.0 769.7 263.1 215.0 630.8 770.8 259.7 233.1 622.6 774.7
LEGEND
Cap. — Capacity, Tons of Refrigeration
Cond — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (F)

31
Performance data (cont)
30HXC COOLING CAPACITIES (cont)
60 Hz, ENGLISH (cont)

CONDENSER ENTERING WATER TEMPERATURE (F)


80 85 90 95
UNIT
LCWT Cooler Cond Cooler Cond Cooler Cond Cooler Cond
SIZE
(F) Input Flow Flow Input Flow Flow Input Flow Flow Input Flow Flow
30HXC Cap. Cap. Cap. Cap.
kW Rate Rate kW Rate Rate kW Rate Rate kW Rate Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
076 80.1 52.7 192.0 226.1 76.8 55.5 184.2 220.2 73.4 58.6 176.1 214.2 70.2 61.6 168.2 208.4
086 88.3 58.8 211.8 249.9 84.7 62.2 203.0 243.4 81.0 65.6 194.3 237.0 77.6 69.0 186.1 231.0
096 99.7 65.9 239.2 281.8 95.7 69.5 229.5 274.7 91.6 73.4 219.7 267.5 87.7 77.3 210.3 260.7
106 110.8 73.6 265.6 313.2 106.2 78.2 254.7 305.4 101.6 82.6 243.6 297.3 97.1 89.0 232.8 290.7
116 120.5 78.0 288.9 339.4 115.7 82.7 277.4 331.1 110.8 87.6 265.7 322.7 105.9 92.4 253.9 314.2
126 130.4 85.2 312.7 367.9 125.3 90.2 300.4 359.0 120.1 95.6 288.0 350.2 115.0 101.1 275.7 341.6
136 144.7 96.0 347.0 409.1 139.1 101.1 333.5 399.1 133.3 106.7 319.7 389.1 127.9 112.3 306.8 380.0
45 146 154.8 103.7 371.1 438.2 148.8 109.5 356.7 427.7 142.4 115.6 341.4 416.6 136.8 124.5 327.9 409.0
161 161.9 107.4 388.2 457.7 159.4 116.9 382.1 458.0 156.3 127.2 374.9 457.6 153.8 140.3 368.8 460.1
171 171.4 113.9 411.0 484.7 169.0 123.3 405.3 485.3 166.1 134.0 398.3 485.4 164.1 145.6 393.4 488.3
186 183.1 122.8 439.1 518.6 180.6 133.1 433.2 519.5 177.6 144.4 425.8 519.7 175.2 156.5 420.1 522.1
206 218.7 141.1 524.4 615.8 215.3 152.3 516.3 615.3 211.2 165.5 506.5 614.2 207.8 179.7 498.3 615.5
246 256.6 166.1 615.3 722.9 253.1 179.7 607.0 723.7 248.5 195.9 596.0 723.5 244.2 212.7 585.5 724.3
261 265.5 173.7 636.6 749.1 261.9 187.6 628.0 749.9 257.3 204.0 617.0 749.8 253.3 221.1 607.5 751.7
271 276.0 182.8 661.9 780.3 272.1 197.7 652.5 780.8 267.7 214.8 642.0 781.7 263.7 232.5 632.3 783.9
076 81.8 53.1 196.3 230.6 78.6 55.7 188.5 224.6 75.1 58.9 180.2 218.5 71.8 62.0 172.2 212.6
086 90.3 59.3 216.5 254.8 86.6 62.4 207.7 248.2 82.9 65.9 198.8 241.7 79.3 69.3 190.2 235.3
096 101.9 66.4 244.5 287.4 97.9 69.8 234.9 280.1 93.7 73.8 224.8 272.7 89.7 77.7 215.1 265.7
106 113.2 74.1 271.4 319.4 108.7 78.4 260.7 311.5 104.0 83.0 249.4 303.3 99.1 87.5 237.8 294.8
116 123.1 78.5 295.3 346.1 118.3 82.9 283.8 337.6 113.4 88.0 271.9 329.1 108.3 92.8 259.8 320.3
126 133.3 85.6 319.7 375.1 128.2 90.5 307.4 366.1 122.8 96.1 294.6 357.1 117.5 101.5 281.9 348.1
136 147.9 96.6 354.7 417.2 142.3 101.4 341.3 407.0 136.3 107.1 327.0 396.7 130.8 112.8 313.6 387.1
46 146 158.2 104.1 379.4 446.7 152.1 109.9 364.9 436.1 145.7 116.1 349.4 424.9 139.7 124.6 335.0 416.2
161 164.7 107.5 395.1 464.7 162.3 116.6 389.3 464.9 159.3 127.1 382.1 464.6 156.4 139.0 375.1 465.6
171 174.4 113.9 418.3 492.0 172.1 123.0 412.8 492.6 169.1 133.9 405.7 492.7 166.8 145.3 400.0 494.7
186 186.2 123.0 446.7 526.3 183.9 132.7 441.1 527.2 180.7 144.2 433.5 527.2 178.1 156.2 427.2 528.9
206 222.6 141.1 533.9 625.2 219.3 152.4 526.0 624.9 215.2 165.3 516.1 623.7 211.4 179.4 507.0 624.0
246 261.0 166.1 626.1 733.7 257.6 179.3 617.8 734.2 253.1 195.5 607.1 734.4 248.7 212.6 596.4 735.0
261 270.0 173.9 647.7 760.2 266.5 187.2 639.2 760.7 262.0 203.8 628.3 760.9 257.9 221.1 618.6 762.7
271 280.8 183.1 673.6 792.0 277.1 197.2 664.7 792.6 272.4 214.4 653.5 792.9 268.4 232.5 643.7 795.2
076 85.5 53.8 205.1 239.8 82.2 56.3 197.2 233.7 78.6 59.5 188.7 227.3 75.1 62.7 180.2 221.0
086 94.2 60.2 226.1 264.9 90.6 62.9 217.4 258.2 86.7 66.6 208.0 251.3 82.9 70.2 199.0 244.6
096 106.3 67.4 255.2 298.7 102.4 70.4 245.7 291.3 98.1 74.5 235.3 283.7 93.8 78.6 225.1 276.2
106 118.1 75.0 283.4 331.8 113.6 79.0 272.6 323.7 108.8 83.8 261.1 315.5 103.8 88.4 249.2 306.7
116 128.5 79.4 308.4 359.6 123.7 83.5 296.9 351.0 118.6 88.6 284.6 342.2 113.4 93.8 272.2 333.3
126 139.1 86.6 333.7 389.7 133.9 91.3 321.4 380.6 128.4 96.8 308.2 371.1 123.0 102.4 295.1 361.7
136 154.3 97.9 370.3 433.5 148.8 102.2 357.0 423.3 142.7 108.1 342.4 412.7 136.7 114.0 328.1 402.3
48 146 165.0 105.4 396.0 464.0 159.0 110.8 381.5 453.3 152.5 117.2 366.1 442.1 145.8 123.6 350.0 430.4
161 170.5 107.7 409.1 478.6 168.2 116.2 403.7 478.9 165.4 126.8 396.9 479.2 162.1 137.9 389.1 478.8
171 180.4 114.1 432.9 506.5 178.1 123.0 427.3 507.0 175.3 133.5 420.6 507.3 172.4 144.9 413.9 508.2
186 192.5 123.3 461.9 541.5 190.2 132.3 456.5 542.2 187.2 143.8 449.4 542.7 184.3 156.1 442.4 543.9
206 229.4 141.0 550.6 641.7 227.1 152.5 545.0 643.8 223.2 164.8 535.7 642.8 219.0 179.1 525.6 642.3
246 270.0 166.2 647.9 755.3 266.7 179.2 640.1 756.3 262.5 194.9 630.0 756.7 257.9 212.2 618.9 757.1
261 279.1 174.2 669.9 790.3 276.0 187.1 662.3 783.6 271.7 203.3 651.9 784.0 267.2 220.9 641.1 785.0
271 290.3 183.3 696.6 814.9 286.9 196.6 688.6 816.0 282.4 213.8 677.8 816.6 277.9 232.2 666.9 818.0
LEGEND
Cap. — Capacity, Tons of Refrigeration
Cond — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (F)

32
30HXC COOLING CAPACITIES (cont)
60 Hz, ENGLISH (cont)

CONDENSER ENTERING WATER TEMPERATURE (F)


80 85 90 95
UNIT
LCWT Cooler Cond Cooler Cond Cooler Cond Cooler Cond
SIZE
(F) Input Flow Flow Input Flow Flow Input Flow Flow Input Flow Flow
30HXC Cap. Cap. Cap. Cap.
kW Rate Rate kW Rate Rate kW Rate Rate kW Rate Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
076 89.0 54.4 213.6 248.7 85.8 57.1 206.0 243.0 82.3 59.9 197.5 236.4 78.5 63.3 188.6 229.8
086 98.2 61.0 235.8 275.1 94.6 63.8 227.1 268.4 90.7 67.2 217.7 261.3 86.7 70.9 208.1 254.2
096 110.8 68.2 266.1 310.1 106.9 71.5 256.6 302.8 102.6 75.1 246.3 295.0 98.1 79.3 235.4 287.0
106 123.1 75.8 295.6 344.4 118.6 79.8 284.7 336.3 113.8 84.4 273.2 327.9 108.7 89.3 261.0 319.0
116 133.7 80.0 320.9 372.5 129.2 84.5 310.2 364.8 124.1 89.1 297.9 355.7 118.7 94.6 285.0 346.6
126 144.6 87.3 347.1 403.3 139.8 92.1 335.7 395.3 134.3 97.4 322.5 385.7 128.6 103.3 308.8 376.0
136 160.8 99.0 386.1 449.9 155.3 103.8 372.8 439.9 149.3 108.9 358.4 429.0 142.9 115.1 343.1 418.0
50 146 171.8 106.4 412.6 481.1 166.0 111.9 398.5 470.8 159.5 118.0 383.0 459.5 152.6 124.8 366.5 447.6
161 176.2 107.6 423.1 492.4 174.1 116.4 417.9 493.2 171.4 126.5 411.4 493.4 168.2 137.8 403.8 493.4
171 185.6 114.0 445.6 519.0 184.3 122.9 442.5 522.0 181.6 133.0 436.0 522.3 178.6 144.7 428.8 523.0
186 198.7 123.3 477.1 556.5 196.7 132.7 472.3 558.0 193.9 143.4 465.5 558.5 190.7 155.8 458.0 559.3
206 236.2 140.7 567.0 657.7 235.2 152.5 564.7 663.4 231.4 164.8 555.6 662.6 227.2 178.8 545.4 661.8
246 277.5 165.2 666.4 772.9 275.8 179.7 662.2 778.4 272.1 193.9 653.3 779.3 267.3 211.6 641.8 779.5
261 287.3 173.5 689.8 801.7 285.2 187.8 684.8 806.4 281.5 202.4 675.8 807.2 276.6 220.4 664.1 807.6
271 299.1 182.8 718.1 835.9 296.5 197.4 711.8 839.5 292.5 212.9 702.3 840.5 287.5 231.6 690.4 841.1
076 93.0 54.8 223.5 258.6 90.5 58.1 217.6 255.0 87.0 60.8 209.1 248.3 83.2 64.1 199.9 241.4
086 103.7 61.8 249.3 288.9 100.8 65.3 242.2 284.2 96.9 68.1 232.9 277.0 92.7 71.9 222.8 269.4
096 116.8 68.8 280.7 324.8 113.9 73.0 273.7 320.7 109.5 76.3 263.3 312.6 103.5 80.3 248.8 300.8
106 130.0 76.5 312.5 361.5 126.3 81.3 303.6 355.9 121.5 85.4 292.0 347.2 116.3 90.5 279.6 338.3
116 141.8 80.4 340.8 392.4 138.8 86.2 333.6 389.1 133.6 90.6 321.1 379.7 128.1 95.7 307.9 370.1
126 154.8 88.0 372.1 428.5 151.5 94.3 364.2 425.0 144.4 98.9 347.0 411.0 138.4 104.7 332.8 400.7
136 170.5 100.0 409.7 473.8 166.8 106.0 400.8 469.1 160.7 110.9 386.2 457.9 154.3 116.8 370.7 446.5
55 146 184.2 107.5 442.8 511.6 179.9 114.3 432.5 506.1 173.4 119.9 416.8 494.4 164.5 126.5 395.3 477.4
161 184.3 106.3 443.0 511.2 184.4 116.6 443.2 518.2 182.0 125.9 437.4 518.8 178.9 137.2 430.1 519.1
171 194.5 112.9 467.6 540.0 194.8 123.3 468.3 547.7 192.9 132.8 463.6 549.5 190.0 144.0 456.6 550.1
186 206.4 122.2 496.1 574.4 206.5 133.0 496.3 581.9 204.1 142.9 490.6 582.9 200.9 155.3 482.9 583.6
206 245.4 139.5 589.9 679.3 245.6 152.7 590.4 688.8 243.1 164.7 584.4 691.0 239.0 178.1 574.4 690.0
246 287.9 162.8 692.0 796.4 289.4 179.2 695.5 810.9 286.3 194.1 688.0 813.6 282.1 210.5 677.9 814.6
261 297.9 171.5 715.9 825.9 299.6 187.8 720.1 841.1 296.0 202.6 711.5 842.5 291.7 219.3 701.1 843.5
271 309.9 180.6 744.9 860.7 311.3 197.5 748.3 875.4 307.6 212.7 739.3 876.9 303.1 230.6 728.5 878.1
076 93.1 54.9 223.9 258.8 90.6 58.2 218.0 255.2 87.1 60.8 209.5 248.6 83.2 64.1 200.2 241.6
086 103.8 61.8 249.7 289.1 100.9 65.3 242.7 284.6 97.0 68.2 233.4 277.3 92.8 71.9 223.3 269.7
096 116.9 68.8 281.2 325.0 112.6 72.8 270.9 317.5 108.3 76.0 260.6 309.4 103.6 80.3 249.3 301.1
106 130.1 76.5 313.0 361.8 126.5 81.3 304.2 356.3 121.6 85.4 292.6 347.6 115.5 90.4 277.8 336.2
116 141.9 80.4 341.5 392.8 139.0 86.2 334.3 389.5 132.1 90.3 317.8 376.0 126.6 95.6 304.6 366.3
126 153.6 88.1 369.5 425.6 150.1 94.2 361.1 421.4 144.5 99.0 347.7 411.4 138.6 104.7 333.4 401.1
136 170.6 100.0 410.5 474.2 167.0 106.1 401.7 469.6 160.9 111.0 387.0 458.5 152.5 116.5 366.8 442.0
60 146 184.4 107.5 443.6 512.1 178.1 114.0 428.5 501.6 171.7 119.5 413.1 490.0 164.7 126.6 396.1 477.9
161 183.2 106.5 440.8 508.7 182.9 116.6 440.0 514.7 180.5 125.8 434.2 515.2 177.4 137.4 426.8 515.4
171 193.6 113.2 465.7 537.8 193.9 123.4 466.3 545.4 191.6 132.7 460.9 546.3 188.6 144.2 453.7 546.8
186 206.6 122.2 496.9 574.7 206.7 133.0 497.2 582.4 204.3 142.9 491.5 583.4 201.1 155.3 483.8 584.1
206 245.6 139.5 590.7 679.7 245.8 152.7 591.3 689.2 243.3 164.8 585.3 691.4 239.2 178.1 575.3 690.5
246 288.1 162.7 693.0 796.8 289.5 179.2 696.5 811.4 286.5 194.1 689.2 814.2 279.2 210.8 671.5 807.7
261 298.0 171.4 717.0 826.3 299.8 187.8 721.2 841.6 296.3 202.6 712.7 843.1 292.0 219.3 702.4 844.1
271 310.1 180.6 746.0 861.1 311.6 197.5 749.5 876.1 307.9 212.7 740.6 877.5 303.4 230.5 729.8 878.7
LEGEND
Cap. — Capacity, Tons of Refrigeration
Cond — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (F)

33
Performance data (cont)
30HXC COOLING CAPACITIES (cont)
60 Hz, SI

CONDENSER ENTERING WATER TEMPERATURE (C)


25 30 35
UNIT
LCWT Cooler Cond Cooler Cond Cooler Cond
SIZE
(C) Input Flow Flow Input Flow Flow Input Flow Flow
30HXC Cap. Cap. Cap.
kW Rate Rate kW Rate Rate kW Rate Rate
(L/s) (L/s) (L/s) (L/s) (L/s) (L/s)
076 253.0 49.4 10.8 12.8 234.0 54.5 10.0 12.2 218.8 60.3 9.3 11.8
086 278.9 55.4 11.9 14.1 258.5 61.0 11.0 13.5 242.6 67.4 10.3 13.1
096 315.1 61.8 13.4 15.9 292.1 68.3 12.4 15.2 274.1 75.7 11.7 14.8
106 350.1 69.4 14.9 17.7 323.4 76.9 13.8 16.9 304.1 85.6 13.0 16.5
116 380.5 73.6 16.2 19.2 352.4 81.6 15.0 18.3 330.4 90.8 14.1 17.8
126 412.0 80.3 17.5 20.8 382.3 89.2 16.3 19.9 358.7 99.3 15.3 19.3
136 449.1 89.1 19.2 22.8 424.6 99.6 18.1 22.2 400.1 110.1 17.0 21.6
4 146 488.8 97.9 20.8 24.8 453.9 108.1 19.3 23.7 428.0 120.0 18.2 23.1
161 516.7 102.9 22.0 26.2 500.2 119.6 21.3 26.2 494.7 140.2 21.1 26.8
171 547.7 109.0 23.3 27.8 533.0 126.5 22.7 27.9 526.8 147.2 22.4 28.5
186 585.8 118.0 25.0 29.8 569.6 136.4 24.3 29.8 564.2 158.7 24.0 30.5
206 698.0 134.8 29.7 35.2 676.1 156.0 28.8 35.2 663.7 181.3 28.3 35.7
246 820.5 158.6 34.9 41.4 795.3 184.9 33.9 41.4 783.1 215.9 33.4 42.2
261 849.3 166.0 36.2 42.9 824.9 192.6 35.1 43.0 814.6 224.3 34.7 43.9
271 883.5 175.1 37.6 44.8 858.7 202.8 36.6 44.9 849.1 236.1 36.2 45.8
076 263.7 49.8 11.2 13.3 244.0 55.0 10.4 12.6 227.0 60.7 9.7 12.2
086 290.7 55.8 12.4 14.7 269.4 61.6 11.5 14.0 251.6 68.0 10.7 13.5
096 328.4 62.3 14.0 16.5 304.4 69.0 13.0 15.8 284.4 76.2 12.1 15.2
106 364.7 69.9 15.5 18.4 337.5 77.6 14.4 17.5 315.3 86.2 13.4 17.0
116 396.5 74.1 16.9 19.9 367.8 82.4 15.7 19.0 342.6 91.4 14.6 18.3
126 429.2 80.9 18.3 21.6 398.5 89.9 17.0 20.7 371.9 99.9 15.9 19.9
136 476.2 91.0 20.3 24.0 442.4 100.5 18.9 23.0 414.9 110.8 17.7 22.2
5 146 509.3 98.6 21.7 25.7 472.4 108.9 20.1 24.6 443.6 120.8 18.9 23.8
161 534.6 102.5 22.8 27.0 517.5 119.5 22.1 26.9 508.7 139.7 21.7 27.4
171 566.2 109.0 24.1 28.6 550.0 126.1 23.4 28.6 541.6 146.8 23.1 29.1
186 605.7 117.5 25.8 30.6 588.4 136.1 25.1 30.6 579.9 158.2 24.7 31.2
206 721.9 134.9 30.8 36.3 699.1 155.7 29.8 36.2 683.0 180.8 29.1 36.5
246 847.5 158.5 36.1 42.6 823.3 184.5 35.1 42.6 805.2 214.9 34.3 43.1
261 877.4 165.7 37.4 44.1 853.0 192.3 36.4 44.2 837.4 223.5 35.7 44.8
271 912.8 174.5 38.9 46.0 887.6 202.5 37.8 46.1 872.6 235.2 37.2 46.8
076 274.4 50.5 11.7 13.8 254.3 55.5 10.8 13.1 235.5 61.1 10.0 12.5
086 302.6 56.4 12.9 15.2 280.6 62.2 12.0 14.5 260.9 68.5 11.1 13.9
096 341.8 63.2 14.6 17.1 317.2 69.6 13.5 16.4 294.8 76.7 12.6 15.7
106 379.6 70.5 16.2 19.1 352.0 78.3 15.0 18.2 326.7 88.9 13.9 17.6
116 412.7 74.8 17.6 20.6 383.5 83.0 16.4 19.7 355.1 92.7 15.1 18.9
126 446.8 81.6 19.1 22.4 415.4 90.7 17.7 21.4 385.4 101.0 16.4 20.6
136 495.7 92.2 21.1 24.9 460.9 101.3 19.7 23.8 430.0 111.5 18.3 22.9
6 146 530.3 99.5 22.6 26.6 492.6 109.8 21.0 25.5 459.8 121.4 19.6 24.6
161 552.3 102.5 23.6 27.7 535.5 119.4 22.8 27.7 523.0 139.3 22.3 28.0
171 584.4 108.9 24.9 29.3 569.1 126.0 24.3 29.4 556.7 146.2 23.7 29.7
186 624.8 117.6 26.6 31.4 608.2 135.9 25.9 31.5 595.8 157.5 25.4 31.8
206 745.7 134.8 31.8 37.3 723.9 155.5 30.9 37.2 703.1 180.3 30.0 37.4
246 874.9 158.7 37.3 43.8 851.4 184.0 36.3 43.8 828.0 214.6 35.3 44.1
261 905.3 166.2 38.6 45.4 881.4 191.8 37.6 45.4 860.9 222.5 36.7 45.8
271 941.6 175.0 40.2 47.3 916.7 201.9 39.1 47.3 896.8 234.1 38.2 47.8

LEGEND
Cap. — Capacity, Tons of Refrigeration
Cond — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (C)

34
30HXC COOLING CAPACITIES (cont)
60 Hz, SI (cont)

CONDENSER ENTERING WATER TEMPERATURE (C)


25 30 35
UNIT
LCWT Cooler Cond Cooler Cond Cooler Cond
SIZE
(C) Input Flow Flow Input Flow Flow Input Flow Flow
30HXC Cap. Cap. Cap.
kW Rate Rate kW Rate Rate kW Rate Rate
(L/s) (L/s) (L/s) (L/s) (L/s) (L/s)
076 285.5 51.2 12.2 14.3 265.1 56.0 11.3 13.6 244.5 61.6 10.4 12.9
086 314.8 57.2 13.4 15.7 292.6 63.1 12.5 15.1 270.4 68.9 11.5 14.4
096 355.4 64.0 15.2 17.8 330.6 70.2 14.1 17.0 305.7 77.2 13.0 16.2
106 394.7 71.4 16.8 19.7 366.9 79.0 15.7 18.9 338.5 89.5 14.4 18.1
116 429.1 75.6 18.3 21.4 399.5 83.6 17.0 20.5 368.9 92.4 15.7 19.5
126 464.7 82.4 19.8 23.2 432.7 91.3 18.5 22.2 400.5 101.0 17.1 21.2
136 515.3 93.3 22.0 25.8 480.3 102.2 20.5 24.6 445.8 112.1 19.0 23.6
7 146 551.3 100.4 23.5 27.6 513.6 110.7 21.9 26.4 476.7 124.2 20.3 25.4
161 569.6 102.8 24.3 28.5 554.2 119.1 23.6 28.5 537.6 140.8 22.9 28.7
171 602.9 109.0 25.7 30.1 588.0 125.6 25.1 30.2 573.2 145.8 24.5 30.4
186 644.0 117.9 27.5 32.2 628.4 135.5 26.8 32.3 612.3 156.8 26.1 32.5
206 768.3 134.9 32.8 38.2 748.7 155.0 31.9 38.3 725.6 180.0 31.0 38.3
246 902.6 158.8 38.5 44.9 880.4 183.3 37.6 45.0 852.6 213.1 36.4 45.1
261 933.7 166.4 39.8 46.6 911.1 191.3 38.9 46.7 884.9 221.5 37.8 46.8
271 970.8 175.3 41.4 48.5 947.4 201.4 40.4 48.6 921.5 233.0 39.3 48.8
076 296.8 51.8 12.7 14.8 276.3 56.5 11.8 14.1 254.6 62.2 10.9 13.4
086 327.2 57.9 14.0 16.3 304.5 63.3 13.0 15.6 281.2 69.5 12.0 14.8
096 369.4 64.8 15.8 18.4 344.3 70.8 14.7 17.6 318.1 77.9 13.6 16.8
106 410.1 72.1 17.5 20.4 382.1 79.5 16.3 19.5 351.8 87.7 15.0 18.6
116 446.1 76.2 19.0 22.1 416.2 84.1 17.8 21.2 384.2 93.1 16.4 20.2
126 482.4 83.2 20.6 24.0 450.7 91.8 19.2 23.0 416.7 101.7 17.8 21.9
136 535.5 94.3 22.9 26.7 500.4 102.8 21.4 25.5 463.7 113.1 19.8 24.4
8 146 572.8 101.4 24.5 28.6 535.0 111.4 22.8 27.4 495.1 124.6 21.1 26.2
161 587.6 102.8 25.1 29.2 572.9 118.7 24.5 29.3 553.6 138.5 23.6 29.3
171 620.4 109.0 26.5 30.9 607.6 125.2 25.9 31.0 590.3 145.4 25.2 31.1
186 663.5 118.1 28.3 33.1 648.5 135.1 27.7 33.2 630.3 156.3 26.9 33.3
206 789.2 134.6 33.7 39.1 774.0 154.9 33.0 39.3 748.3 179.6 31.9 39.3
246 928.1 158.4 39.6 46.0 909.2 182.6 38.8 46.2 880.8 212.7 37.6 46.3
261 961.6 166.4 41.1 47.8 940.7 190.5 40.2 47.9 914.3 221.4 39.2 48.1
271 1000.7 175.4 42.7 49.8 978.2 200.6 41.8 49.9 950.3 232.7 40.6 50.1
076 307.2 52.2 13.1 15.2 287.7 56.9 12.3 14.6 265.2 62.8 11.3 13.9
086 339.4 58.6 14.5 16.9 317.1 63.7 13.5 16.1 292.8 70.3 12.5 15.4
096 382.7 65.4 16.3 19.0 358.5 71.2 15.3 18.2 331.1 78.7 14.1 17.3
106 425.5 72.7 18.2 21.1 397.8 80.0 17.0 20.2 366.7 88.6 15.7 19.3
116 461.3 76.7 19.7 22.8 433.3 84.6 18.5 21.9 400.6 93.9 17.1 20.9
126 499.0 83.6 21.3 24.7 469.1 92.5 20.0 23.8 434.1 102.6 18.5 22.7
136 554.7 95.1 23.7 27.5 521.1 103.4 22.3 26.5 482.7 114.2 20.6 25.3
9 146 593.1 102.2 25.3 29.5 556.9 112.1 23.8 28.3 514.9 123.8 22.0 27.0
161 604.5 102.6 25.8 30.0 591.6 118.3 25.3 30.1 572.2 138.0 24.4 30.1
171 636.7 108.8 27.2 31.6 626.5 125.1 26.8 31.8 608.5 145.1 26.0 31.9
186 681.9 117.9 29.1 33.9 669.2 134.5 28.6 34.0 650.3 156.2 27.8 34.1
206 810.2 134.2 34.6 40.0 798.7 155.1 34.1 40.4 772.9 179.3 33.0 40.3
246 950.5 157.3 40.6 46.9 938.6 182.2 40.1 47.5 910.1 212.4 38.9 47.5
261 984.0 165.5 42.0 48.7 971.2 190.0 41.5 49.2 942.6 221.1 40.3 49.3
271 1024.8 174.5 43.8 50.8 1009.8 199.6 43.1 51.2 980.4 232.4 41.9 51.3

LEGEND
Cap. — Capacity, Tons of Refrigeration
Cond — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (C)

35
Performance data (cont)
30HXC COOLING CAPACITIES (cont)
60 Hz, SI (cont)

CONDENSER ENTERING WATER TEMPERATURE (C)


25 30 35
UNIT
LCWT Cooler Cond Cooler Cond Cooler Cond
SIZE
(C) Input Flow Flow Input Flow Flow Input Flow Flow
30HXC Cap. Cap. Cap.
kW Rate Rate kW Rate Rate kW Rate Rate
(L/s) (L/s) (L/s) (L/s) (L/s) (L/s)
076 316.8 52.5 13.5 15.6 299.2 57.7 12.8 15.1 276.1 63.4 11.8 14.4
086 350.6 59.0 15.0 17.4 329.9 64.4 14.1 16.7 304.6 71.0 13.0 15.9
096 394.6 65.8 16.9 19.5 372.8 72.1 15.9 18.9 344.6 79.4 14.7 18.0
106 439.5 73.1 18.8 21.7 413.7 80.6 17.7 20.9 382.0 89.4 16.3 20.0
116 476.0 76.8 20.3 23.4 450.6 85.4 19.3 22.7 417.2 94.7 17.8 21.7
126 515.6 83.9 22.0 25.4 487.7 93.2 20.8 24.6 452.0 103.4 19.3 23.5
136 571.8 95.6 24.4 28.3 541.8 104.7 23.2 27.4 502.3 115.2 21.5 26.2
10 146 613.3 102.8 26.2 30.3 579.0 113.1 24.7 29.3 536.4 124.9 22.9 28.0
161 618.8 101.9 26.4 30.5 610.4 118.2 26.1 30.9 591.3 137.9 25.3 30.9
171 652.9 108.4 27.9 32.3 646.2 125.0 27.6 32.7 628.0 144.9 26.8 32.7
186 697.3 117.1 29.8 34.5 690.0 134.6 29.5 34.9 670.7 156.0 28.7 35.0
206 830.6 133.4 35.5 40.9 824.5 155.0 35.2 41.5 798.7 179.1 34.1 41.4
246 972.0 155.9 41.5 47.8 967.7 182.5 41.4 48.7 939.8 211.9 40.2 48.8
261 1006.0 164.3 43.0 49.6 1000.9 190.7 42.8 50.5 972.6 220.7 41.6 50.5
271 1047.1 173.1 44.7 51.7 1040.3 200.4 44.5 52.6 1011.1 231.9 43.2 52.6
076 333.3 52.7 14.3 16.4 318.4 58.9 13.6 16.0 294.9 64.3 12.6 15.2
086 371.5 59.5 15.9 18.3 351.2 65.9 15.0 17.7 321.6 71.8 13.8 16.7
096 414.1 66.1 17.7 20.4 395.6 73.7 16.9 19.9 367.1 80.5 15.7 19.0
106 462.6 73.2 19.8 22.7 435.3 81.9 18.6 21.9 403.6 90.4 17.3 20.9
116 502.7 77.0 21.5 24.6 482.3 87.2 20.6 24.1 444.4 95.6 19.0 22.9
126 549.0 84.1 23.5 26.9 522.7 95.2 22.4 26.2 486.2 104.7 20.8 25.0
136 604.0 96.1 25.8 29.7 579.8 107.0 24.8 29.1 540.0 116.8 23.1 27.8
13 146 653.1 103.0 27.9 32.1 626.0 115.4 26.8 31.4 577.7 126.6 24.7 29.8
161 644.9 100.1 27.6 31.6 645.1 118.6 27.6 32.4 627.5 137.5 26.8 32.4
171 681.1 106.8 29.1 33.4 683.8 125.5 29.3 34.3 667.1 144.3 28.5 34.4
186 722.1 115.6 30.9 35.5 723.3 135.2 30.9 36.4 705.3 155.5 30.2 36.5
206 867.5 132.2 37.1 42.4 868.2 155.3 37.1 43.4 846.3 178.2 36.2 43.4
246 1006.1 153.4 43.0 49.2 1013.0 182.6 43.3 50.7 987.6 210.9 42.2 50.8
261 1036.1 162.2 44.3 50.8 1041.3 191.0 44.5 52.2 1015.3 219.9 43.4 52.4
271 1086.5 170.3 46.5 53.3 1093.5 200.8 46.8 54.9 1067.1 230.8 45.6 55.0
076 330.2 52.7 14.1 16.2 314.8 58.7 13.5 15.8 291.3 64.1 12.5 15.1
086 368.2 59.5 15.8 18.1 350.6 65.9 15.0 17.7 324.8 71.9 13.9 16.8
096 414.5 66.1 17.7 20.4 396.1 73.7 17.0 19.9 362.7 80.3 15.5 18.8
106 461.3 73.2 19.8 22.7 439.5 82.1 18.8 22.1 407.6 90.6 17.5 21.1
116 503.2 76.9 21.5 24.6 482.9 87.1 20.7 24.2 449.0 95.8 19.2 23.1
126 549.3 84.0 23.5 26.9 521.7 95.2 22.3 26.2 485.2 104.8 20.8 25.0
136 604.7 96.2 25.9 29.7 580.5 107.1 24.9 29.1 540.7 116.8 23.1 27.9
16 146 653.4 103.0 28.0 32.1 626.4 115.5 26.8 31.5 576.5 126.6 24.7 29.8
161 645.0 100.1 27.6 31.6 645.3 118.6 27.6 32.4 627.7 137.5 26.9 32.4
171 681.0 106.9 29.2 33.4 683.2 125.4 29.3 34.3 666.5 144.2 28.5 34.4
186 726.1 115.4 31.1 35.7 728.6 135.3 31.2 36.6 704.9 155.5 30.2 36.5
206 860.9 132.4 36.9 42.1 861.5 155.4 36.9 43.1 838.0 178.4 35.9 43.1
246 1008.1 153.5 43.2 49.3 1014.6 182.6 43.4 50.8 989.3 210.8 42.4 50.9
261 1041.8 161.8 44.6 51.0 1048.9 191.1 44.9 52.6 1023.3 219.7 43.8 52.7
271 1083.8 170.5 46.4 53.2 1089.9 200.8 46.7 54.7 1063.3 230.9 45.5 54.9

LEGEND
Cap. — Capacity, kW
Cond — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (C)

36
30HXC COOLING CAPACITIES (cont)
50 Hz, ENGLISH

CONDENSER ENTERING WATER TEMPERATURE (F)


80 85 90 95
UNIT
LCWT Cooler Cond Cooler Cond Cooler Cond Cooler Cond
SIZE
(F) Input Flow Flow Input Flow Flow Input Flow Flow Input Flow Flow
30HXC Cap. Cap. Cap. Cap.
kW Rate Rate kW Rate Rate kW Rate Rate kW Rate Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
076 70.0 50.1 167.7 200.3 67.0 52.9 160.5 195.0 64.2 55.8 153.8 190.2 62.0 59.1 148.4 187.0
086 78.5 57.2 187.9 225.1 75.4 60.5 180.6 220.0 72.5 63.9 173.6 215.3 70.0 67.5 167.5 211.7
096 89.4 64.5 214.0 256.0 86.1 68.5 206.1 250.8 82.8 72.4 198.3 245.6 80.0 76.6 191.5 241.6
106 98.0 71.4 234.6 281.1 93.8 75.5 224.5 273.7 90.1 80.1 215.8 268.0 87.4 85.3 209.3 265.0
116 107.8 76.7 258.0 307.9 103.5 81.4 247.8 300.9 99.2 86.0 237.4 293.6 96.1 91.6 230.0 289.9
126 117.6 84.5 281.5 336.5 113.0 89.7 270.5 329.0 108.4 94.9 259.6 321.6 105.0 100.9 251.3 317.2
136 130.4 94.7 312.1 373.8 125.5 100.2 300.3 365.7 120.8 105.7 289.2 358.2 117.0 111.8 280.0 353.1
40 146 138.1 101.4 330.5 396.5 132.3 107.0 316.6 386.4 127.7 113.3 305.6 379.6 124.0 120.5 296.7 375.5
161 147.8 108.2 353.7 424.2 145.0 117.6 347.2 423.8 143.3 128.0 343.0 426.5 142.5 139.9 341.2 432.6
171 156.2 114.0 373.8 448.0 153.6 123.7 367.7 448.3 152.0 134.4 363.8 451.6 151.2 146.4 362.0 457.7
186 167.8 123.7 401.6 482.1 164.8 134.0 394.6 481.9 163.1 145.4 390.5 485.4 162.4 158.3 388.8 492.3
206 199.8 141.0 478.3 570.2 196.1 153.4 469.3 569.5 193.6 166.9 463.3 572.4 191.9 181.7 459.4 578.4
246 234.7 166.9 561.7 670.5 230.7 181.7 552.2 670.8 226.9 197.1 543.0 671.8 225.6 215.4 540.0 680.9
261 242.4 173.9 580.2 693.5 238.5 188.8 570.9 694.1 235.1 204.6 562.9 696.6 234.1 223.3 560.3 706.4
271 252.6 183.7 604.7 724.3 248.6 199.3 595.2 725.2 245.5 215.9 587.6 728.6 244.4 235.5 585.0 739.0
076 73.4 50.5 175.8 208.6 70.2 53.4 168.2 203.0 67.2 56.3 160.9 197.7 64.6 59.5 154.7 193.6
086 82.0 57.5 196.4 233.7 78.9 61.1 188.9 228.7 75.7 64.5 181.3 223.3 72.9 68.1 174.7 219.2
096 93.3 64.8 223.6 265.7 90.0 69.1 215.6 260.6 86.5 73.1 207.1 254.7 83.4 77.3 199.7 250.2
106 102.6 72.0 245.8 292.6 98.3 76.3 235.4 285.1 93.8 80.5 224.8 277.3 90.9 86.6 217.7 274.2
116 112.6 76.9 269.8 319.8 108.4 82.0 259.6 313.0 103.8 86.8 248.6 305.3 99.9 92.7 239.4 299.9
126 122.9 84.8 294.4 349.5 118.3 90.4 283.3 342.1 113.4 95.8 271.8 334.2 109.2 102.1 261.5 328.2
136 136.3 95.2 326.4 388.3 131.2 101.0 314.4 380.1 126.1 106.5 302.2 371.6 121.8 112.6 291.8 365.4
42 146 144.6 102.1 346.4 412.7 138.6 108.0 332.0 402.3 133.1 114.0 318.9 393.2 128.9 121.2 308.7 387.8
161 153.5 107.8 367.7 437.7 150.7 117.4 361.0 437.4 148.0 127.4 354.6 437.6 147.0 139.3 352.2 443.1
171 162.1 113.6 388.3 462.1 159.5 123.5 382.2 462.5 157.2 134.0 376.6 464.0 155.9 145.9 373.6 468.8
186 173.8 123.2 416.4 496.4 171.0 133.7 409.7 496.7 168.4 144.6 403.5 497.7 167.4 157.6 401.0 503.9
206 207.1 141.0 496.0 587.7 203.7 153.0 488.1 587.8 200.4 166.3 480.0 588.5 198.0 180.9 474.3 592.6
246 243.7 165.9 583.7 691.6 239.5 181.0 573.8 691.7 235.2 196.5 563.5 691.7 232.7 214.8 557.6 697.9
261 251.6 173.0 602.8 715.2 247.4 188.3 592.6 715.2 243.4 204.0 583.2 716.3 241.3 222.1 578.1 723.3
271 262.0 183.0 627.6 746.4 257.8 198.7 617.5 746.8 253.8 215.0 608.0 748.1 252.0 234.2 603.6 756.6
076 76.8 51.1 184.0 217.2 73.6 53.9 176.4 211.4 70.3 57.0 168.6 205.7 67.3 60.0 161.2 200.4
086 85.5 57.9 205.0 242.5 82.4 61.6 197.6 237.6 79.2 65.2 189.8 232.2 75.9 68.7 182.0 226.8
096 97.4 65.2 233.5 275.8 93.9 69.5 225.2 270.4 90.4 73.8 216.6 264.6 86.8 77.9 208.1 258.9
106 107.3 72.6 257.3 304.3 102.9 76.9 246.8 296.8 98.3 81.4 235.8 288.7 94.4 88.9 226.2 284.1
116 117.6 77.4 281.8 332.0 113.3 82.6 271.6 325.2 108.7 87.6 260.6 317.6 104.0 92.5 249.3 309.7
126 128.2 85.4 307.3 362.7 123.6 91.0 296.4 355.5 118.7 96.5 284.5 347.4 113.7 102.1 272.6 339.2
136 142.3 95.9 341.1 403.2 137.2 101.8 328.8 395.0 131.9 107.6 316.1 386.2 126.8 113.4 304.0 378.0
44 146 151.2 103.1 362.6 429.3 145.2 109.0 348.1 418.9 139.0 114.9 333.2 408.0 133.9 123.0 321.1 401.3
161 159.2 107.4 381.7 451.3 156.5 117.2 375.3 451.4 153.6 127.4 368.1 451.0 152.0 141.1 364.3 456.3
171 168.1 113.6 402.9 476.5 165.5 123.1 396.6 476.6 162.7 133.6 390.0 476.9 160.8 145.2 385.6 480.3
186 180.0 122.8 431.6 511.2 177.4 133.3 425.2 511.8 174.5 144.5 418.2 512.3 172.6 156.9 413.7 516.0
206 214.5 141.0 514.2 605.7 211.4 152.4 506.8 606.0 207.6 165.9 497.7 605.8 204.8 180.5 490.9 608.7
246 252.3 166.0 604.8 712.5 248.6 180.3 596.0 713.2 244.3 196.3 585.6 713.5 240.1 213.1 575.5 714.6
261 260.5 173.1 624.4 736.7 256.7 187.7 615.4 737.4 252.5 203.9 605.3 738.1 248.8 221.0 596.4 740.6
271 271.4 182.6 650.6 768.9 267.4 198.1 641.0 769.7 263.1 215.0 630.8 770.8 259.7 233.1 622.6 774.7

LEGEND
Cap. — Capacity, Tons of Refrigeration
Cond — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (F)

37
Performance data (cont)
30HXC COOLING CAPACITIES (cont)
50 Hz, ENGLISH (cont)

CONDENSER ENTERING WATER TEMPERATURE (F)


80 85 90 95
UNIT
LCWT Cooler Cond Cooler Cond Cooler Cond Cooler Cond
SIZE
(F) Input Flow Flow Input Flow Flow Input Flow Flow Input Flow Flow
30HXC Cap. Cap. Cap. Cap.
kW Rate Rate kW Rate Rate kW Rate Rate kW Rate Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
076 78.5 51.5 188.2 221.5 75.3 54.2 180.5 215.7 72.0 57.2 172.6 209.8 68.7 60.2 164.8 204.1
086 87.3 58.1 209.4 247.0 84.2 61.8 201.9 242.0 80.9 65.5 193.9 236.5 77.6 69.0 186.0 230.9
096 99.4 65.7 238.5 281.0 96.0 69.7 230.1 275.4 92.4 74.1 221.5 269.7 88.6 78.1 212.4 263.4
106 109.7 72.9 263.1 310.3 105.3 77.3 252.4 302.6 100.7 81.8 241.4 294.5 96.3 88.2 230.8 288.2
116 120.1 77.7 287.9 338.3 115.8 82.7 277.6 331.3 111.2 88.0 266.7 323.9 106.4 92.9 255.1 315.7
126 130.9 85.6 313.9 369.4 126.3 91.2 303.0 362.2 121.4 96.9 291.1 354.1 116.3 102.5 278.9 345.7
136 145.3 96.4 348.4 410.8 140.2 102.0 336.2 402.4 134.8 108.0 323.2 393.5 129.5 113.9 310.6 384.8
45 146 154.6 103.5 370.6 437.6 148.6 109.3 356.2 427.2 142.2 115.4 341.0 416.0 136.7 124.4 327.9 408.9
161 162.0 107.5 388.5 458.1 159.5 117.0 382.4 458.3 156.5 127.3 375.2 458.0 154.4 141.0 370.1 461.9
171 170.9 113.6 409.8 483.3 168.5 122.9 404.1 483.9 165.6 133.5 397.2 484.0 163.6 145.1 392.3 486.9
186 183.1 122.8 439.1 518.6 180.6 133.1 433.2 519.5 177.6 144.4 425.8 519.7 175.2 156.5 420.1 522.1
206 218.4 140.9 523.6 614.9 215.3 152.3 516.4 615.4 211.5 165.7 507.2 615.1 208.4 180.3 499.6 617.2
246 256.7 166.2 615.6 723.2 253.2 179.8 607.2 724.0 248.7 196.0 596.3 723.9 244.3 212.8 585.8 724.6
261 265.0 173.4 635.4 747.7 261.4 187.3 626.9 748.5 256.8 203.6 615.9 748.4 252.9 220.7 606.4 750.4
271 276.0 182.8 661.9 780.3 272.1 197.7 652.5 780.8 267.7 214.8 642.0 781.7 263.7 232.5 632.3 783.9
076 80.2 51.9 192.4 225.9 77.0 54.4 184.7 220.0 73.6 57.5 176.6 214.0 70.3 60.6 168.7 208.2
086 89.2 58.5 213.9 251.7 86.0 62.0 206.4 246.5 82.7 65.8 198.3 241.1 79.2 69.3 190.1 235.2
096 101.5 66.1 243.5 286.3 98.0 69.8 235.1 280.4 94.4 74.4 226.4 274.8 90.6 78.5 217.3 268.4
106 112.1 73.3 268.9 316.4 107.7 77.6 258.3 308.6 103.0 82.1 247.1 300.5 98.2 86.6 235.6 292.0
116 122.6 78.1 294.1 344.7 118.3 82.9 283.8 337.6 113.7 88.3 272.7 330.2 108.8 93.3 261.0 321.8
126 133.7 85.9 320.6 376.2 129.1 91.3 309.6 368.9 124.1 97.3 297.6 360.9 118.9 103.0 285.2 352.3
136 148.4 97.0 355.9 418.6 143.3 102.2 343.6 409.9 137.8 108.5 330.6 401.1 132.4 114.4 317.5 392.0
46 146 158.0 103.9 378.9 446.1 151.9 109.7 364.4 435.5 145.5 115.9 349.0 424.4 139.6 124.5 334.8 415.8
161 164.8 107.6 395.4 465.0 162.4 116.7 389.6 465.3 159.4 127.2 382.4 465.0 156.7 139.5 376.0 466.8
171 173.9 113.5 417.1 490.5 171.6 122.7 411.7 491.2 168.6 133.4 404.5 491.3 166.3 144.9 398.9 493.2
186 186.2 123.0 446.7 526.3 183.9 132.7 441.1 527.2 180.7 144.2 433.5 527.2 178.1 156.2 427.2 528.9
206 222.2 140.9 533.0 624.2 219.2 152.4 525.8 624.8 215.4 165.5 516.7 624.4 211.9 180.0 508.3 625.6
246 261.2 166.2 626.4 734.0 257.7 179.4 618.2 734.6 253.2 195.6 607.4 734.7 248.8 212.7 596.7 735.4
261 269.5 173.6 646.5 758.8 266.0 186.8 638.0 759.3 261.5 203.3 627.2 759.4 257.4 220.6 617.5 761.3
271 280.8 183.1 673.6 792.0 277.1 197.2 664.7 792.6 272.4 214.4 653.5 792.9 268.4 232.5 643.7 795.2
076 83.7 52.6 201.0 234.9 80.5 55.0 193.3 228.9 77.1 58.1 185.0 222.7 73.6 61.2 176.6 216.5
086 93.0 59.3 223.1 261.3 89.7 62.3 215.4 255.7 86.3 66.3 207.2 250.3 82.8 70.1 198.7 244.3
096 105.8 67.0 253.9 297.1 102.2 70.2 245.3 290.8 98.5 74.8 236.4 284.9 94.6 79.3 227.0 278.7
106 117.0 74.3 280.8 328.7 112.6 78.1 270.2 320.8 107.8 82.9 258.7 312.6 102.9 87.5 247.0 303.9
116 127.8 78.9 306.8 357.7 123.4 83.3 296.3 350.2 118.8 88.9 285.2 342.9 113.9 94.2 273.3 334.6
126 139.3 86.8 334.3 390.3 134.6 91.9 323.0 382.6 129.7 97.9 311.2 374.8 124.3 103.8 298.4 366.0
136 154.6 98.2 371.1 434.4 149.5 102.8 358.8 425.4 144.0 109.3 345.5 416.5 138.3 115.5 331.8 407.0
48 146 164.8 105.2 395.5 463.4 158.8 110.6 381.1 452.7 152.3 117.0 365.6 441.5 145.7 123.4 349.6 429.9
161 170.6 107.8 409.4 479.0 168.3 116.3 403.9 479.2 165.5 126.9 397.1 479.5 162.3 138.0 389.4 479.2
171 179.8 113.7 431.6 505.0 177.6 122.7 426.1 505.5 174.7 133.0 419.4 505.8 171.9 144.5 412.6 506.7
186 192.5 123.3 461.9 541.5 190.2 132.3 456.5 542.2 187.2 143.8 449.4 542.7 184.3 156.1 442.4 543.9
206 228.8 140.6 549.2 640.0 226.9 152.3 544.5 643.3 223.4 164.9 536.0 643.2 219.4 179.5 526.7 643.6
246 270.1 166.3 648.3 755.7 266.9 179.3 640.5 756.7 262.7 195.0 630.3 757.1 258.0 212.3 619.2 757.5
261 278.6 173.8 668.7 780.9 275.4 186.7 660.9 781.9 271.2 202.8 650.8 782.6 266.7 220.5 640.0 783.6
271 290.3 183.3 696.6 814.9 286.9 196.6 688.6 816.0 282.4 213.8 677.8 816.6 277.9 232.2 666.9 818.0

LEGEND
Cap. — Capacity, Tons of Refrigeration
Cond — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (F)

38
30HXC COOLING CAPACITIES (cont)
50 Hz, ENGLISH (cont)

CONDENSER ENTERING WATER TEMPERATURE (F)


80 85 90 95
UNIT
LCWT Cooler Cond Cooler Cond Cooler Cond Cooler Cond
SIZE
(F) Input Flow Flow Input Flow Flow Input Flow Flow Input Flow Flow
30HXC Cap. Cap. Cap. Cap.
kW Rate Rate kW Rate Rate kW Rate Rate kW Rate Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
076 87.2 53.1 209.4 243.6 84.1 55.9 201.9 238.0 80.7 58.6 193.7 231.6 77.0 61.8 184.9 225.1
086 96.7 59.9 232.3 270.9 93.5 63.0 224.5 265.2 90.1 66.6 216.3 259.5 86.5 70.7 207.6 253.6
096 110.1 67.6 264.4 308.0 106.5 71.2 255.7 301.7 102.7 75.2 246.5 295.3 98.8 80.0 237.1 289.1
106 121.9 75.0 292.8 341.1 117.5 79.0 282.2 333.2 112.7 83.5 270.7 324.8 107.7 88.4 258.6 316.1
116 132.8 79.4 318.9 370.1 128.7 84.1 308.9 363.4 124.0 89.1 297.8 355.6 119.1 95.0 285.9 347.7
126 144.6 87.3 347.1 403.4 140.3 92.5 336.8 396.6 135.3 98.3 324.9 388.6 129.9 104.7 312.0 380.0
136 161.0 99.1 386.5 450.4 155.8 104.2 374.1 441.4 150.3 109.8 360.8 432.1 144.4 116.5 346.8 422.6
50 146 171.6 106.2 412.1 480.5 165.8 111.7 398.0 470.2 159.3 117.8 382.5 458.9 152.4 124.6 366.0 447.0
161 176.3 107.7 423.4 492.8 174.2 116.5 418.3 493.6 171.5 126.6 411.7 493.8 168.3 137.9 404.1 493.7
171 185.0 113.6 444.2 517.4 183.8 122.5 441.2 520.4 181.1 132.6 434.8 520.8 178.1 144.3 427.6 521.5
186 198.7 123.3 477.1 556.5 196.7 132.7 472.3 558.0 193.9 143.4 465.5 558.5 190.7 155.8 458.0 559.3
206 235.3 140.2 565.1 655.5 234.8 152.2 563.9 662.4 231.4 164.9 555.6 662.7 227.5 179.1 546.2 662.8
246 277.7 165.3 666.7 773.3 275.9 179.8 662.5 778.8 272.2 194.0 653.7 779.7 267.4 211.7 642.1 779.9
261 286.8 173.2 688.5 800.1 284.7 187.5 683.6 804.9 281.0 202.0 674.6 805.7 276.1 220.0 662.9 806.1
271 299.1 182.8 718.1 835.9 296.5 197.4 711.8 839.5 292.5 212.9 702.3 840.5 287.5 231.6 690.4 841.1
076 91.1 53.6 218.9 253.2 88.7 56.8 213.3 249.8 85.3 59.4 204.9 243.3 81.5 62.6 195.9 236.5
086 102.0 60.6 245.2 284.0 99.4 64.2 238.9 280.2 95.9 67.3 230.5 274.0 92.2 71.5 221.6 268.0
096 115.9 68.3 278.7 322.4 113.2 72.5 272.1 318.7 109.3 76.1 262.6 311.8 105.2 80.7 252.8 305.1
106 128.8 75.7 309.5 358.0 125.2 80.4 300.8 352.6 120.4 84.5 289.4 344.0 114.3 89.5 274.8 332.8
116 140.8 79.8 338.4 389.6 137.9 85.5 331.5 386.7 133.1 90.2 319.9 378.3 128.1 95.7 307.9 370.0
126 154.7 87.9 371.8 428.2 149.9 94.2 360.4 421.0 144.8 99.3 348.0 412.2 139.4 105.6 335.0 403.5
136 170.6 100.1 410.0 474.1 167.0 106.2 401.3 469.7 161.3 111.4 387.6 459.6 155.3 117.7 373.4 449.8
55 146 184.0 107.3 442.2 510.9 179.7 114.2 431.9 505.4 173.2 119.8 416.3 493.7 164.3 126.3 394.8 476.7
161 184.5 106.4 443.4 511.6 184.5 116.7 443.5 518.7 182.1 126.1 437.7 519.2 179.1 137.4 430.4 519.5
171 194.0 112.6 466.2 538.4 194.3 122.9 466.9 546.0 192.3 132.3 462.3 547.9 187.8 143.8 451.5 544.7
186 206.4 122.2 496.1 574.4 206.5 133.0 496.3 581.9 204.1 142.9 490.6 582.9 200.9 155.3 482.9 583.6
206 244.4 138.9 587.4 676.5 245.1 152.3 589.0 687.2 243.0 164.6 584.1 690.6 239.2 178.3 574.9 690.7
246 288.1 162.9 692.4 796.8 289.5 179.3 695.8 811.4 286.4 194.2 688.4 814.1 282.2 210.6 678.3 815.0
261 297.3 171.1 714.6 824.3 299.0 187.4 718.7 839.5 295.5 202.2 710.2 840.9 291.2 218.9 699.9 841.9
271 309.9 180.6 744.9 860.7 311.3 197.5 748.3 875.4 307.6 212.7 739.3 876.9 303.1 230.6 728.5 878.1
076 91.2 53.6 219.3 253.4 88.8 56.8 213.7 250.1 85.3 59.4 205.3 243.6 81.6 62.6 196.3 236.7
086 102.1 60.6 245.6 284.3 99.5 64.3 239.3 280.5 96.0 67.3 230.9 274.2 92.3 71.5 222.1 268.2
096 116.0 68.3 279.2 322.7 113.3 72.5 272.6 319.0 108.1 75.8 260.1 308.9 104.0 80.6 250.3 302.4
106 128.9 75.7 310.0 358.3 125.3 80.5 301.5 353.0 119.6 84.3 287.7 342.0 114.5 89.5 275.3 333.1
116 140.9 79.8 339.1 389.9 138.1 85.5 332.2 387.1 131.6 90.0 316.6 374.5 126.6 95.6 304.5 366.3
126 153.5 88.0 369.2 425.3 150.1 94.2 361.1 421.5 144.9 99.3 348.7 412.6 139.5 105.6 335.7 403.9
136 170.8 100.1 410.8 474.6 167.2 106.2 402.1 470.2 161.5 111.4 388.4 460.1 153.6 117.5 369.4 445.3
60 146 184.2 107.3 443.0 511.4 177.9 113.9 428.0 500.9 171.5 119.3 412.5 489.3 164.5 126.4 395.6 477.2
161 183.4 106.6 441.2 509.2 183.1 116.7 440.3 515.1 180.6 125.9 434.6 515.6 177.5 137.5 427.1 515.8
171 193.0 112.8 464.3 536.2 193.3 123.0 465.0 543.8 191.0 132.3 459.6 544.7 188.0 143.8 452.3 545.1
186 206.6 122.2 496.9 574.7 206.7 133.0 497.2 582.4 204.3 142.9 491.5 583.4 201.1 155.3 483.8 584.1
206 244.5 138.8 588.2 676.8 245.2 152.3 589.9 687.5 243.2 164.6 585.0 691.0 239.4 178.3 575.9 691.1
246 288.2 162.8 693.4 797.2 289.7 179.3 696.9 811.8 286.7 194.2 689.6 814.6 279.3 210.9 671.8 808.1
261 297.5 171.1 715.6 824.7 299.2 187.4 719.8 839.9 295.7 202.2 711.4 841.6 291.4 218.8 701.1 842.5
271 310.1 180.6 746.0 861.1 311.6 197.5 749.5 876.1 307.9 212.7 740.6 877.5 303.4 230.5 729.8 878.7

LEGEND
Cap. — Capacity, Tons of Refrigeration
Cond — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (F)

39
Performance data (cont)
30HXC COOLING CAPACITIES (cont)
50 Hz, SI

CONDENSER ENTERING WATER TEMPERATURE (C)


25 30 35
UNIT
LCWT Cooler Cond Cooler Cond Cooler Cond
SIZE
(C) Input Flow Flow Input Flow Flow Input Flow Flow
30HXC Cap. Cap. Cap.
kW Rate Rate kW Rate Rate kW Rate Rate
(L/s) (L/s) (L/s) (L/s) (L/s) (L/s)
076 248.1 48.1 10.7 12.6 229.4 53.2 9.8 12.0 214.4 58.9 9.2 11.6
086 277.2 54.9 11.9 14.2 258.4 60.9 11.1 13.6 242.1 67.2 10.4 13.2
096 315.7 61.9 13.6 16.1 295.1 69.0 12.7 15.5 276.7 76.3 11.9 15.0
106 347.1 68.6 14.9 17.7 320.6 76.0 13.8 16.9 302.7 85.1 13.0 16.5
116 380.7 73.5 16.3 19.4 354.3 82.0 15.2 18.6 332.6 91.4 14.3 18.1
126 415.4 81.0 17.8 21.2 387.0 90.4 16.6 20.3 363.4 100.6 15.6 19.8
136 460.3 91.1 19.8 23.5 430.0 100.9 18.5 22.6 404.8 111.4 17.4 22.0
4 146 488.5 97.7 21.0 25.0 453.7 107.9 19.5 23.9 429.1 120.2 18.4 23.4
161 517.1 102.8 22.2 26.4 500.6 119.5 21.5 26.4 495.1 140.1 21.3 27.0
171 546.3 108.6 23.5 27.9 531.5 125.9 22.8 28.0 525.3 146.5 22.6 28.6
186 585.9 117.9 25.2 30.0 569.7 136.2 24.5 30.1 564.2 158.5 24.2 30.8
206 697.7 134.6 30.0 35.5 677.5 156.1 29.1 35.5 666.5 181.9 28.6 36.1
246 821.0 158.5 35.2 41.8 795.9 184.8 34.2 41.8 783.5 215.7 33.6 42.5
261 848.0 165.4 36.4 43.2 823.6 191.9 35.4 43.3 813.1 223.6 34.9 44.1
271 883.7 174.9 37.9 45.1 858.8 202.6 36.9 45.2 849.1 235.8 36.5 46.2
076 258.5 48.7 11.1 13.1 239.2 53.7 10.3 12.5 222.5 59.3 9.6 12.0
086 288.2 55.2 12.4 14.6 269.1 61.5 11.6 14.1 251.3 67.8 10.8 13.6
096 327.2 69.2 14.1 16.7 307.2 69.6 13.2 16.1 287.2 77.0 12.3 15.5
106 361.5 69.2 15.5 18.4 334.6 76.7 14.4 17.5 313.5 85.6 13.5 17.0
116 396.0 73.9 17.0 20.0 369.4 82.7 15.9 19.3 344.6 91.8 14.8 18.6
126 431.9 81.4 18.6 21.9 403.3 91.1 17.3 21.1 376.5 101.2 16.2 20.3
136 478.9 91.5 20.6 24.3 447.7 101.7 19.2 23.4 416.5 111.9 17.8 22.5
5 146 508.9 98.4 21.9 25.9 472.1 108.6 20.3 24.7 444.5 120.9 19.1 24.1
161 535.1 102.4 23.0 27.2 518.0 119.4 22.3 27.2 509.1 139.6 21.9 27.6
171 564.6 108.5 24.3 28.7 548.5 125.6 23.6 28.7 540.1 146.2 23.2 29.2
186 605.8 117.4 26.0 30.8 588.5 136.0 25.3 30.9 579.9 158.0 24.9 31.4
206 721.3 134.5 31.0 36.5 700.3 155.8 30.1 36.5 685.6 181.4 29.5 36.9
246 848.1 158.4 36.4 42.9 823.9 184.4 35.4 43.0 805.7 214.8 34.6 43.5
261 875.9 165.2 37.6 44.4 851.6 191.6 36.6 44.5 835.9 222.7 35.9 45.1
271 912.9 174.3 39.2 46.4 887.7 202.2 38.1 46.5 872.6 234.9 37.5 47.2
076 269.1 49.3 11.6 13.6 249.4 54.2 10.7 12.9 230.7 59.7 9.9 12.4
086 299.4 55.7 12.9 15.1 280.0 62.0 12.0 14.6 260.7 68.3 11.2 14.0
096 340.9 62.9 14.7 17.2 319.6 70.1 13.7 16.6 298.0 77.5 12.8 16.0
106 376.3 69.8 16.2 19.0 349.0 77.4 15.0 18.2 324.5 88.1 13.9 17.6
116 411.5 74.4 17.7 20.7 384.9 83.3 16.5 20.0 356.9 93.0 15.3 19.2
126 448.6 81.9 19.3 22.6 419.3 92.1 18.1 21.8 390.0 102.2 16.8 21.0
136 497.8 92.5 21.4 25.2 466.1 102.5 20.0 24.2 435.4 113.0 18.7 23.4
6 146 529.9 99.3 22.8 26.8 492.3 109.5 21.2 25.7 460.3 121.4 19.8 24.8
161 552.7 102.5 23.8 28.0 536.0 119.3 23.0 27.9 523.5 139.3 22.5 28.2
171 582.8 108.4 25.1 29.5 567.5 125.4 24.4 29.5 555.1 145.6 23.9 29.9
186 624.9 117.5 26.9 31.7 608.4 135.7 26.2 31.7 595.8 157.3 25.6 32.1
206 744.6 134.4 32.0 37.5 724.8 155.5 31.2 37.5 705.5 180.7 30.3 37.8
246 875.4 158.6 37.6 44.1 852.0 183.9 36.6 44.2 829.1 214.6 35.6 44.5
261 903.8 165.7 38.9 45.6 880.0 191.2 37.8 45.7 859.3 221.7 36.9 46.1
271 941.7 174.9 40.5 47.6 916.8 201.7 39.4 47.7 896.8 233.8 38.6 48.2

LEGEND
Cap. — Capacity, kW
Cond — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (C)

40
30HXC COOLING CAPACITIES (cont)
50 Hz, SI (cont)

CONDENSER ENTERING WATER TEMPERATURE (C)


25 30 35
UNIT
LCWT Cooler Cond Cooler Cond Cooler Cond
SIZE
(C) Input Flow Flow Input Flow Flow Input Flow Flow
30HXC
Cap. Cap. Cap.
kW Rate Rate kW Rate Rate kW Rate Rate
(L/s) (L/s) (L/s) (L/s) (L/s) (L/s)
076 279.9 50.0 12.0 14.1 260.1 54.7 11.2 13.4 239.6 60.1 10.3 12.8
086 310.9 56.4 13.4 15.7 291.4 62.5 12.5 15.1 270.4 68.8 11.6 14.5
096 353.8 63.6 15.2 17.8 332.2 70.5 14.3 17.2 309.0 78.0 13.3 16.5
106 391.2 70.6 16.8 19.7 363.8 78.0 15.6 18.8 335.8 88.5 14.4 18.1
116 427.4 75.1 18.4 21.4 400.5 83.8 17.2 20.7 370.8 92.8 15.9 19.8
126 465.8 82.6 20.0 23.4 437.1 92.3 18.8 22.6 405.4 102.4 17.4 21.6
136 516.9 93.5 22.2 26.0 485.1 103.2 20.9 25.1 451.6 113.7 19.4 24.1
7 146 550.9 100.2 23.7 27.8 513.4 110.4 22.1 26.6 476.9 124.0 20.5 25.6
161 570.1 102.7 24.5 28.7 554.6 119.1 23.9 28.7 539.6 141.2 23.2 29.0
171 601.3 108.6 25.9 30.3 586.4 125.1 25.2 30.4 571.6 145.2 24.6 30.6
186 644.1 117.8 27.7 32.5 628.5 135.4 27.0 32.6 612.4 156.6 26.3 32.8
206 766.5 134.4 33.0 38.5 749.2 154.9 32.2 38.6 727.8 180.4 31.3 38.7
246 903.1 158.7 38.8 45.3 881.0 183.2 37.9 45.4 853.2 213.0 36.7 45.5
261 932.1 165.9 40.1 46.9 909.6 190.7 39.1 46.9 883.4 220.7 38.0 47.1
271 970.9 175.1 41.8 48.9 947.5 201.2 40.8 49.0 921.6 232.7 39.6 49.2
076 290.9 50.5 12.5 14.6 270.9 55.1 11.7 13.9 249.6 60.7 10.7 13.2
086 322.8 56.9 13.9 16.2 302.8 62.8 13.0 15.6 281.2 69.5 12.1 15.0
096 367.2 64.3 15.8 18.4 345.1 70.8 14.9 17.7 321.3 78.7 13.8 17.1
106 406.6 71.3 17.5 20.4 378.8 78.6 16.3 19.5 348.8 86.8 15.0 18.6
116 443.7 75.7 19.1 22.2 416.5 84.0 17.9 21.4 386.2 93.5 16.6 20.5
126 483.0 83.2 20.8 24.2 454.4 92.6 19.6 23.3 421.9 103.1 18.2 22.4
136 536.6 94.4 23.1 26.9 504.4 103.6 21.7 25.9 469.6 114.6 20.2 24.9
8 146 572.3 101.2 24.6 28.7 534.7 111.1 23.0 27.6 494.9 124.2 21.3 26.4
161 588.1 102.8 25.3 29.5 573.4 118.7 24.7 29.5 554.3 138.4 23.9 29.5
171 618.6 108.5 26.6 31.0 605.9 124.7 26.1 31.2 588.6 144.8 25.3 31.3
186 663.6 117.9 28.6 33.4 648.6 134.9 27.9 33.4 630.4 156.2 27.1 33.5
206 786.8 134.0 33.9 39.3 774.1 154.8 33.3 39.7 750.2 179.8 32.3 39.7
246 928.6 158.3 40.0 46.4 909.8 182.4 39.2 46.6 881.4 212.6 37.9 46.7
261 959.7 165.8 41.3 48.1 939.1 189.9 40.4 48.2 918.5 214.0 39.5 48.3
271 1000.8 175.2 43.1 50.2 978.3 200.4 42.1 50.3 950.5 232.5 40.9 50.5
076 300.9 50.9 13.0 15.0 282.1 55.6 12.1 14.4 260.0 61.3 11.2 13.7
086 334.1 57.5 14.4 16.7 314.6 63.0 13.5 16.1 292.4 70.1 12.6 15.5
096 380.0 64.8 16.4 19.0 358.4 71.1 15.4 18.3 334.2 79.4 14.4 17.6
106 421.5 71.9 18.1 21.1 394.4 79.1 17.0 20.2 363.5 87.6 15.6 19.2
116 458.4 76.0 19.7 22.8 432.8 84.3 18.6 22.1 402.3 94.3 17.3 21.2
126 499.1 83.6 21.5 24.9 472.0 93.1 20.3 24.1 439.2 103.9 18.9 23.2
136 555.3 95.1 23.9 27.8 524.2 104.0 22.6 26.8 488.4 115.6 21.0 25.8
9 146 592.6 101.9 25.5 29.7 556.5 111.8 24.0 28.5 514.6 123.5 22.2 27.2
161 604.9 102.6 26.0 30.2 592.1 118.3 25.5 30.3 572.8 138.0 24.7 30.3
171 634.8 108.4 27.3 31.7 624.8 124.6 26.9 32.0 606.8 144.5 26.1 32.1
186 681.9 117.7 29.4 34.1 669.3 134.4 28.8 34.3 650.5 156.1 28.0 34.4
206 807.1 133.5 34.7 40.2 798.4 154.8 34.4 40.7 774.6 179.5 33.3 40.7
246 950.9 157.1 40.9 47.3 939.2 182.1 40.4 47.9 910.6 212.2 39.2 47.9
261 982.0 164.9 42.3 49.0 969.5 189.4 41.7 49.5 941.1 220.4 40.5 49.6
271 1024.7 174.2 44.1 51.2 1009.9 199.4 43.5 51.6 980.6 232.2 42.2 51.8

LEGEND
Cap. — Capacity, kW
Cond — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (C)

41
Performance data (cont)
30HXC COOLING CAPACITIES (cont)
50 Hz, SI (cont)

CONDENSER ENTERING WATER TEMPERATURE (C)


25 30 35
UNIT
LCWT Cooler Cond Cooler Cond Cooler Cond
SIZE
(C) Input Flow Flow Input Flow Flow Input Flow Flow
30HXC
Cap. Cap. Cap.
kW Rate Rate kW Rate Rate kW Rate Rate
(L/s) (L/s) (L/s) (L/s) (L/s) (L/s)
076 310.4 51.2 13.4 15.4 293.4 56.3 12.6 14.9 270.8 61.8 11.7 14.2
086 344.9 57.8 14.9 17.2 326.5 63.6 14.1 16.7 304.1 70.7 13.1 16.0
096 391.9 65.2 16.9 19.5 371.9 71.9 16.0 19.0 347.3 80.0 15.0 18.2
106 435.4 72.3 18.8 21.7 410.1 79.7 17.7 20.9 378.8 88.4 16.3 19.9
116 472.7 76.1 20.4 23.5 449.3 85.0 19.4 22.8 418.7 95.0 18.0 21.9
126 515.3 83.8 22.2 25.6 489.8 93.6 21.1 24.9 456.9 104.7 19.7 24.0
136 572.3 95.5 24.7 28.5 544.1 105.1 23.4 27.7 507.9 116.5 21.9 26.7
10 146 612.7 102.5 26.4 30.5 578.6 112.9 24.9 29.5 536.1 124.6 23.1 28.2
161 619.2 101.9 26.7 30.8 611.0 118.2 26.3 31.1 591.9 137.9 25.5 31.1
171 650.9 107.9 28.0 32.4 644.4 124.5 27.8 32.8 626.3 144.3 27.0 32.9
186 697.2 117.0 30.0 34.8 690.1 134.5 29.7 35.2 670.8 155.8 28.9 35.3
206 826.8 132.5 35.6 41.0 823.7 154.6 35.5 41.8 800.1 179.1 34.5 41.8
246 972.4 155.8 41.9 48.2 968.3 182.4 41.7 49.2 940.4 211.7 40.5 49.2
261 1003.9 163.7 43.2 49.9 999.2 190.1 43.0 50.8 971.0 220.0 41.8 50.9
271 1046.9 172.9 45.1 52.1 1040.1 200.2 44.8 53.0 1011.2 231.6 43.6 53.1
076 326.5 51.4 14.1 16.1 312.3 57.5 13.5 15.8 289.2 62.7 12.5 15.0
086 362.7 58.2 15.6 18.0 346.7 64.8 14.9 17.6 320.3 71.4 13.8 16.7
096 411.1 65.5 17.7 20.4 393.9 73.2 17.0 20.0 368.5 80.7 15.9 19.2
106 458.3 72.3 19.8 22.7 437.2 81.3 18.9 22.2 400.1 89.4 17.3 20.9
116 499.3 76.2 21.5 24.6 479.7 86.5 20.7 24.2 444.9 95.6 19.2 23.1
126 548.6 84.0 23.7 27.0 523.4 95.2 22.6 26.4 490.0 105.6 21.1 25.4
136 617.8 96.6 26.5 30.5 580.9 107.1 25.0 29.4 544.0 117.6 23.5 28.3
13 146 652.4 102.7 28.1 32.3 619.9 114.9 26.7 31.4 577.2 126.3 24.9 30.1
161 645.4 100.0 27.8 31.9 645.7 118.6 27.8 32.7 628.1 137.4 27.1 32.7
171 679.1 106.3 29.3 33.6 681.9 124.9 29.4 34.5 665.3 143.6 28.7 34.6
186 722.0 115.5 31.1 35.8 723.3 135.1 31.2 36.7 705.4 155.3 30.4 36.8
206 863.0 131.3 37.2 42.5 866.5 154.8 37.4 43.7 841.2 178.3 36.3 43.6
246 1006.6 153.3 43.4 49.6 1013.6 182.5 43.7 51.1 988.3 210.7 42.6 51.2
261 1034.0 161.6 44.6 51.1 1039.5 190.4 44.8 52.6 1013.6 219.1 43.7 52.7
271 1086.3 170.1 46.8 53.7 1093.5 200.6 47.2 55.3 1067.2 230.5 46.0 55.5
076 323.4 51.4 14.0 16.0 308.8 57.3 13.3 15.6 285.8 62.6 12.3 14.9
086 362.2 58.2 15.6 18.0 346.2 64.8 14.9 17.6 323.4 71.5 14.0 16.9
096 411.6 65.5 17.8 20.4 394.2 73.2 17.0 20.0 368.8 80.7 15.9 19.2
106 457.0 72.3 19.7 22.6 435.7 81.2 18.8 22.1 404.0 89.6 17.4 21.1
116 499.8 76.1 21.6 24.6 480.5 86.5 20.7 24.2 449.2 95.7 19.4 23.3
126 548.9 83.9 23.7 27.1 522.3 95.2 22.5 26.4 488.8 105.6 21.1 25.4
136 605.2 96.2 26.1 30.0 581.7 107.2 25.1 29.4 544.9 117.7 23.5 28.3
16 146 652.7 102.8 28.2 32.3 625.9 115.2 27.0 31.7 576.0 126.3 24.9 30.0
161 645.4 100.1 27.9 31.9 645.9 118.6 27.9 32.7 628.3 137.4 27.1 32.7
171 679.0 106.5 29.3 33.6 681.4 124.9 29.4 34.5 659.1 143.8 28.4 34.3
186 726.0 115.2 31.3 35.9 728.7 135.1 31.4 36.9 705.0 155.3 30.4 36.8
206 856.6 131.5 37.0 42.2 859.9 154.9 37.1 43.4 839.0 178.4 36.2 43.5
246 1008.5 153.4 43.5 49.7 1015.3 182.5 43.8 51.2 990.0 210.6 42.7 51.3
261 1039.8 161.3 44.9 51.3 1047.1 190.5 45.2 52.9 1021.6 218.9 44.1 53.0
271 1083.7 170.3 46.8 53.6 1090.0 200.6 47.0 55.2 1063.5 230.6 45.9 55.3

LEGEND
Cap. — Capacity, kW
Cond — Condenser
kW — Compressor Motor Input Power at Rated Voltage
LCWT — Leaving Chilled-Water Temperature (C)

42
COMBINATION RATINGS
60 Hz, ENGLISH

CONDENSER ENTERING AIR TEMPERATURE (F)


09DK
85 95 105 115 125
UNIT AIR-COOLED
LCWT Cooler Cooler Cooler Cooler Cooler
(F) SIZE CONDENSER
30HXA Input Flow Input Flow Input Flow Input Flow Input Flow
Cap. Cap. Cap. Cap. Cap.
Unit (Qty) kW Rate kW Rate kW Rate kW Rate kW Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
076 084 (1) 67.4 69.3 161.4 62.4 73.5 149.3 56.9 77.8 136.3 51.3 83.7 122.8 46.7 91.3 111.7
086 084 (1) 73.9 78.6 177.0 68.3 83.3 163.5 62.3 88.6 149.1 56.4 95.6 134.9 51.0 103.4 122.2
096 094 (1) 82.7 89.2 198.1 76.5 94.3 183.1 69.7 101.0 166.9 63.4 108.7 151.7 57.4 116.9 137.5
106 074 (1) and 044 (1) 94.9 99.0 227.2 88.0 104.8 210.6 80.5 111.4 192.8 73.2 120.0 175.3 66.6 129.9 159.5
116 074 (1) and 054 (1) 101.8 107.4 243.7 94.3 113.7 225.7 86.5 121.0 207.0 78.7 130.7 188.3 71.4 140.7 170.8
126 074 (2) 112.2 115.2 268.5 104.2 122.1 249.5 95.7 129.8 229.1 87.2 140.1 208.9 79.2 151.5 189.7
136 074 (2) 121.9 130.2 291.8 113.0 137.5 270.6 103.8 146.7 248.4 94.9 158.2 227.1 86.3 170.5 206.6
40 146 084 (2) 135.5 137.8 324.4 126.2 145.5 302.1 116.2 154.2 278.1 106.2 166.2 254.3 96.9 179.5 232.0
161 084 (2) 140.6 145.8 336.5 134.3 159.4 321.5 127.5 174.4 305.2 121.0 192.3 289.6 109.8 213.7 262.9
171 084 (2) 150.8 161.0 361.0 143.9 175.5 344.5 136.7 191.8 327.2 129.6 212.2 310.2 120.4 236.7 288.3
186 084 (2) 163.8 182.4 392.1 154.8 198.6 370.5 147.7 216.5 353.6 139.9 239.9 334.9 124.6 266.6 298.3
206 084 (2) and 094 (1) 192.2 189.9 460.2 184.9 208.0 442.5 176.0 227.7 421.4 166.5 250.7 398.6 157.3 278.9 376.5
246 094 (3) 223.3 225.8 534.6 214.7 246.4 514.1 203.0 269.1 485.8 192.9 295.9 461.9 182.1 329.4 436.0
261 094 (3) 234.1 242.2 560.3 224.3 264.2 536.8 212.4 288.2 508.6 201.9 317.8 483.3 190.6 353.4 456.3
271 094 (3) 246.1 260.7 589.2 234.6 283.8 561.6 223.0 309.0 533.8 211.8 341.6 507.1 199.9 380.1 478.5
076 084 (1) 70.1 70.8 167.8 65.0 75.1 155.8 59.4 79.4 142.3 53.6 85.0 128.5 48.6 92.3 116.5
086 084 (1) 76.7 80.3 183.8 71.0 85.1 170.2 64.9 90.4 155.5 58.7 97.0 140.6 53.1 104.7 127.3
096 094 (1) 86.0 91.2 206.0 79.5 96.5 190.4 72.6 102.8 174.0 66.0 110.4 158.0 59.0 118.2 141.3
106 074 (1) and 044 (1) 98.5 101.1 236.0 91.6 106.9 219.5 84.0 113.3 201.2 76.4 121.7 183.0 69.4 131.5 166.2
116 074 (1) and 054 (1) 105.6 109.6 253.1 98.2 115.9 235.4 90.1 123.0 215.8 82.0 132.4 196.4 74.3 142.7 178.1
126 074 (2) 116.4 117.5 278.9 108.5 124.6 259.9 99.7 132.0 238.8 90.8 142.1 217.5 82.6 153.4 197.9
136 074 (2) 126.6 132.8 303.3 117.6 140.2 281.6 108.0 149.2 258.7 98.6 160.6 236.3 88.8 172.2 212.7
42 146 084 (2) 140.7 140.5 337.1 131.4 148.4 314.7 121.0 156.7 289.9 110.5 168.5 264.7 101.0 181.8 241.8
161 084 (2) 145.2 148.3 347.7 139.0 162.1 333.0 132.1 177.0 316.4 125.2 195.0 299.8 111.6 214.4 267.3
171 084 (2) 156.1 163.3 373.9 149.0 178.4 357.0 141.4 194.8 338.8 134.2 214.7 321.4 122.5 237.7 293.4
186 084 (2) 169.3 185.6 405.6 160.4 202.1 384.2 152.9 219.7 366.3 144.9 243.4 347.1 124.7 266.4 298.8
206 084 (2) and 094 (1) 198.6 192.8 475.7 191.3 211.1 458.3 182.7 231.1 437.7 172.5 254.3 413.2 162.9 281.3 390.2
246 094 (3) 230.5 229.4 552.3 222.3 250.3 532.5 210.4 273.4 504.1 199.8 299.4 478.6 188.6 332.7 451.9
261 094 (3) 241.8 245.8 579.2 232.8 268.0 557.6 219.9 292.9 526.7 209.0 321.6 500.6 197.4 357.2 472.8
271 094 (3) 254.1 265.1 608.7 243.4 288.2 583.1 230.6 314.3 552.5 219.2 346.2 525.2 207.0 383.7 495.8
076 084 (1) 72.9 72.5 174.7 67.5 76.8 161.9 61.9 81.1 148.5 56.1 86.4 134.4 50.6 93.5 121.2
086 084 (1) 79.6 82.2 190.9 73.9 86.9 177.1 67.6 92.0 162.0 61.2 98.4 146.6 55.2 106.1 132.4
096 094 (1) 89.2 93.4 213.8 82.6 98.6 198.0 75.7 104.7 181.5 68.7 112.1 164.7 60.1 118.7 144.0
106 074 (1) and 044 (1) 102.3 103.3 245.3 95.2 109.2 228.3 87.4 115.4 209.6 79.6 123.5 190.7 72.2 133.3 173.0
116 074 (1) and 054 (1) 109.7 111.9 262.9 102.1 118.4 244.8 93.8 125.0 224.8 85.2 134.4 204.3 77.4 144.5 185.7
126 074 (2) 120.9 119.9 289.9 112.8 127.1 270.4 103.9 134.4 249.0 94.5 144.2 226.6 86.0 155.4 206.0
136 074 (2) 131.4 135.8 314.9 122.1 143.3 292.8 112.4 152.1 269.4 102.7 163.0 246.2 89.4 172.3 214.3
44 146 084 (2) 146.0 143.4 350.0 136.6 151.3 327.5 126.1 159.5 302.4 115.1 170.9 276.0 105.0 184.4 251.7
161 084 (2) 149.8 150.9 359.2 143.8 164.8 344.8 136.8 179.9 327.9 129.5 197.9 310.4 113.3 215.2 271.6
171 084 (2) 161.0 166.1 386.0 154.5 181.5 370.3 146.3 198.2 350.7 138.7 217.6 332.5 124.5 239.0 298.6
186 084 (2) 174.7 189.2 418.9 166.3 205.8 398.6 158.0 223.9 378.7 149.8 247.1 359.2 124.8 266.7 299.1
206 084 (2) and 094 (1) 205.1 195.6 491.7 197.9 214.1 474.5 189.4 234.6 454.1 178.6 257.9 428.2 168.7 284.2 404.4
246 094 (3) 237.9 233.0 570.4 229.9 254.3 551.1 218.2 277.9 523.0 206.7 304.1 495.5 195.3 336.8 468.1
261 094 (3) 249.6 249.7 598.3 241.0 272.5 577.7 227.7 297.9 545.9 216.2 325.5 518.3 204.2 361.7 489.6
271 094 (3) 262.4 269.4 629.1 252.4 292.9 605.1 238.4 319.8 571.6 226.8 350.6 543.7 214.1 388.9 513.3

LEGEND
Cap. — Capacity, Tons of Refrigeration
kW — Compressor Motor Input Power at Rated Voltages
LCWT — Leaving Chilled-Water Temperature (F)

43
Performance data (cont)
COMBINATION RATINGS (cont)
60 Hz, ENGLISH (cont)

CONDENSER ENTERING AIR TEMPERATURE (F)


09DK
85 95 105 115 125
UNIT AIR-COOLED
LCWT Cooler Cooler Cooler Cooler Cooler
(F) SIZE CONDENSER
30HXA Input Flow Input Flow Input Flow Input Flow Input Flow
Cap. Cap. Cap. Cap. Cap.
Unit (Qty) kW Rate kW Rate kW Rate kW Rate kW Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
076 084 (1) 74.3 73.3 178.1 68.9 77.6 165.2 63.3 81.9 151.8 57.3 87.0 137.4 51.6 93.8 123.8
086 084 (1) 81.1 83.1 194.6 75.3 87.8 180.6 69.0 92.8 165.6 62.4 99.2 149.7 56.4 106.7 135.1
096 094 (1) 90.8 94.4 217.7 84.2 99.7 202.0 77.3 105.7 185.3 70.2 112.9 168.2 60.5 119.1 145.1
106 074 (1) and 044 (1) 104.3 104.4 250.0 97.1 110.4 232.8 89.3 116.5 214.2 81.2 124.5 194.8 73.7 133.9 176.8
116 074 (1) and 054 (1) 111.8 112.9 268.1 104.1 119.5 249.7 95.7 126.3 229.4 87.0 135.4 208.6 79.0 145.5 189.4
126 074 (2) 123.2 121.2 295.4 115.0 128.4 275.7 105.9 135.8 254.0 96.5 145.3 231.5 87.7 156.4 210.3
136 074 (2) 133.7 137.4 320.7 124.4 144.9 298.3 114.7 153.5 275.0 104.8 164.2 251.2 90.2 172.7 216.3
45 146 084 (2) 148.8 144.8 356.8 139.2 152.9 333.7 128.6 161.2 308.4 117.6 172.2 281.9 107.2 185.6 257.0
161 084 (2) 152.3 152.1 365.1 146.3 166.1 350.8 139.2 181.4 333.8 131.7 199.3 315.9 114.2 215.6 273.8
171 084 (2) 163.6 167.6 392.2 157.1 183.1 376.6 148.8 199.9 356.9 141.1 219.2 338.3 125.6 239.7 301.1
186 084 (2) 177.5 191.0 425.6 169.4 207.5 406.1 160.6 225.8 385.2 152.4 248.7 365.4 124.8 266.6 299.3
206 084 (2) and 094 (1) 208.4 196.9 499.8 201.4 215.5 482.8 192.9 236.4 462.5 181.7 259.7 435.8 171.6 285.8 411.5
246 094 (3) 241.7 234.7 579.6 233.8 256.3 560.7 222.1 280.0 532.7 210.2 306.3 504.2 198.6 338.8 476.3
261 094 (3) 253.5 251.7 607.9 245.0 274.7 587.5 231.8 300.4 555.9 219.9 328.0 527.4 207.7 364.1 498.0
271 094 (3) 266.6 271.6 639.4 257.0 295.1 616.3 242.4 322.5 581.3 230.6 352.8 553.1 217.7 391.8 522.0
076 084 (1) 75.6 74.2 181.4 70.3 78.4 168.6 64.6 82.8 154.9 58.5 87.8 140.2 52.7 94.3 126.4
086 084 (1) 82.7 84.0 198.3 76.7 88.8 184.0 70.4 93.7 168.7 63.8 99.9 152.9 57.6 107.2 138.1
096 094 (1) 92.4 95.5 221.7 85.8 100.7 205.9 78.7 106.7 188.9 71.6 113.8 171.7 61.1 119.3 146.5
106 074 (1) and 044 (1) 106.2 105.5 254.6 99.0 111.5 237.4 91.0 117.8 218.4 82.8 125.6 198.7 75.1 134.9 180.2
116 074 (1) and 054 (1) 113.8 114.1 272.9 106.1 120.8 254.5 97.5 127.7 233.9 88.8 136.4 213.1 80.6 146.5 193.2
126 074 (2) 125.5 122.5 301.0 117.1 129.7 280.9 108.2 137.1 259.5 98.6 146.4 236.5 89.5 157.5 214.6
136 074 (2) 136.2 138.9 326.6 126.8 146.4 304.1 116.9 155.0 280.3 106.8 165.5 256.2 91.0 173.2 218.3
46 146 084 (2) 151.6 146.3 363.5 141.8 154.4 340.1 131.2 162.9 314.7 120.0 173.5 287.9 109.3 186.7 262.2
161 084 (2) 154.7 153.3 371.0 148.7 167.4 356.8 141.6 183.0 339.6 134.0 200.6 321.4 115.1 215.9 276.1
171 084 (2) 166.1 169.1 398.5 159.7 184.7 383.0 151.5 201.6 363.3 143.4 220.9 344.1 126.6 240.3 303.7
186 084 (2) 180.4 192.6 432.6 172.3 209.4 413.4 163.2 228.0 391.5 154.9 250.4 371.6 124.9 266.6 299.5
206 084 (2) and 094 (1) 211.8 198.3 507.9 204.7 217.2 491.1 196.0 238.2 470.2 185.0 261.5 443.8 174.6 287.5 418.7
246 094 (3) 245.5 236.5 588.9 237.7 258.2 570.3 226.1 282.1 542.4 213.8 308.6 512.9 200.9 340.0 481.8
261 094 (3) 257.4 253.9 617.4 249.1 276.9 597.4 235.9 303.1 565.8 223.6 330.6 536.4 210.0 365.4 503.8
271 094 (3) 270.9 273.7 649.8 261.6 297.3 627.5 246.5 325.4 591.2 234.6 354.9 562.6 217.7 391.9 522.3
076 084 (1) 78.5 75.9 188.4 73.0 80.0 175.3 67.3 84.4 161.4 61.0 89.1 146.4 54.7 95.7 131.3
086 084 (1) 85.7 85.8 205.7 79.7 90.6 191.3 73.2 95.6 175.6 66.4 101.4 159.4 59.8 108.7 143.5
096 094 (1) 95.8 97.6 229.9 89.1 102.9 213.8 81.9 108.6 196.6 74.4 115.7 178.7 62.1 120.0 149.1
106 074 (1) and 044 (1) 110.1 107.7 264.2 102.7 113.9 246.5 94.7 120.2 227.4 86.3 127.6 207.0 78.1 136.7 187.4
116 074 (1) and 054 (1) 118.0 116.4 283.1 110.0 123.5 264.0 101.4 130.3 243.4 92.5 138.5 221.9 83.7 148.6 200.9
126 074 (2) 130.0 125.2 312.0 121.6 132.4 291.9 112.3 140.0 269.6 102.6 148.7 246.2 93.1 159.6 223.4
136 074 (2) 141.1 142.0 338.6 131.6 149.4 315.9 121.5 157.8 291.7 111.0 168.0 266.4 92.7 174.0 222.5
48 146 084 (2) 157.1 149.4 376.9 147.2 157.6 353.2 136.4 166.2 327.4 125.0 176.3 299.9 113.6 189.4 272.7
161 084 (2) 159.5 155.8 382.9 153.8 170.0 369.1 146.5 185.8 351.5 138.4 203.5 332.2 116.9 216.7 280.6
171 084 (2) 171.4 172.0 411.3 165.1 187.7 396.1 156.7 205.1 376.0 148.2 224.3 355.7 128.8 241.3 309.1
186 084 (2) 186.0 196.0 446.5 178.4 213.0 428.1 168.6 232.2 404.6 160.0 254.0 383.9 124.9 266.6 299.8
206 084 (2) and 994 (1) 218.6 201.1 524.7 211.6 220.5 507.8 202.4 242.0 485.8 191.8 264.9 460.2 178.2 289.9 427.6
246 094 (3) 253.2 239.9 607.7 245.5 262.1 589.3 234.3 286.6 562.4 221.0 313.3 530.5 205.3 342.2 492.6
261 094 (3) 265.4 257.8 637.0 257.2 281.5 617.1 244.5 308.0 586.7 231.1 336.0 554.6 214.7 368.1 515.2
271 094 (3) 279.3 278.1 670.3 270.1 302.7 648.1 255.4 331.0 613.0 242.3 360.5 581.6 217.9 391.7 522.9

LEGEND
Cap. — Capacity, Tons of Refrigeration
kW — Compressor Motor Input Power at Rated Voltages
LCWT — Leaving Chilled-Water Temperature (F)

44
COMBINATION RATINGS (cont)
60 Hz, ENGLISH (cont)

CONDENSER ENTERING AIR TEMPERATURE (F)


09DK
85 95 105 115 125
UNIT AIR-COOLED
LCWT Cooler Cooler Cooler Cooler Cooler
(F) SIZE CONDENSER
30HXA Input Flow Input Flow Input Flow Input Flow Input Flow
Cap. Cap. Cap. Cap. Cap.
Unit (Qty) kW Rate kW Rate kW Rate kW Rate kW Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
076 084 (1) 81.3 77.7 195.1 75.8 81.7 181.9 69.9 86.1 167.9 63.6 90.8 152.6 57.1 97.2 137.1
086 084 (1) 88.8 87.7 213.1 82.6 92.6 198.4 76.1 97.6 182.7 69.1 103.2 165.8 60.9 109.5 146.3
096 094 (1) 99.3 99.7 238.4 92.4 105.1 221.9 85.0 110.8 204.2 77.3 117.8 185.7 63.4 120.8 152.3
106 074 (1) and 044 (1) 114.0 110.3 273.8 106.5 116.3 255.7 98.5 122.7 236.4 89.8 129.8 215.7 81.2 138.8 194.9
116 074 (1) and 054 (1) 122.1 119.3 293.1 114.0 126.2 273.7 105.4 133.1 253.0 96.1 140.8 230.8 87.0 150.6 208.9
126 074 (2) 134.7 128.0 323.3 126.0 135.2 302.6 116.8 142.8 280.5 106.8 151.0 256.4 96.7 161.9 232.2
136 074 (2) 146.1 145.2 350.7 136.4 152.6 327.6 126.2 160.7 303.0 115.3 170.8 276.8 94.4 175.1 226.6
50 146 084 (2) 162.8 152.8 390.8 152.6 160.8 366.5 141.7 169.6 340.3 130.0 179.1 312.1 118.0 192.0 283.4
161 084 (2) 164.5 158.3 395.0 158.8 172.7 381.4 151.2 189.0 363.0 143.0 206.6 343.4 117.6 217.4 282.5
171 084 (2) 176.7 174.9 424.2 170.4 190.9 409.2 161.9 208.8 388.8 153.1 227.6 367.5 129.9 241.9 311.9
186 084 (2) 191.8 199.6 460.5 184.6 216.7 443.3 173.9 236.5 417.6 165.3 257.3 396.8 123.9 266.7 297.6
206 084 (2) and 094 (1) 225.5 204.2 541.5 218.2 224.2 523.9 209.1 245.8 502.1 198.6 269.0 476.9 181.8 292.5 436.5
246 094 (3) 260.9 243.3 626.5 253.2 266.4 607.9 242.7 291.1 582.6 228.4 318.7 548.4 209.8 344.7 503.8
261 094 (3) 273.5 261.7 656.6 265.2 286.3 636.7 253.2 313.0 608.0 238.6 341.9 573.0 219.4 370.7 526.8
271 094 (3) 287.5 282.7 690.4 278.5 308.4 668.7 264.6 336.6 635.3 250.2 367.2 600.7 217.9 392.0 523.2
076 084 (1) 85.1 79.8 204.6 79.3 83.8 190.7 73.3 88.5 176.1 66.8 93.3 160.6 60.2 99.1 144.6
086 084 (1) 93.6 90.7 224.9 87.1 95.6 209.5 79.7 100.1 191.6 72.6 105.5 174.6 62.1 110.4 149.4
096 094 (1) 103.6 102.3 248.9 96.6 107.9 232.1 88.9 113.8 213.8 81.2 120.4 195.1 65.4 121.9 157.1
106 074 (1) and 044 (1) 120.2 114.0 289.0 111.6 119.6 268.3 103.4 126.2 248.8 93.5 132.1 224.6 83.4 140.3 200.5
116 074 (1) and 054 (1) 129.5 124.0 311.3 119.9 129.8 288.1 111.0 137.0 266.8 101.5 144.1 243.8 90.0 152.6 216.2
126 074 (2) 142.9 132.6 343.4 133.8 139.9 321.5 124.2 147.8 298.6 113.0 155.2 271.5 101.3 164.6 243.4
136 074 (2) 153.5 149.5 368.9 143.6 157.2 345.1 132.9 165.4 319.4 121.6 175.6 292.4 97.5 176.6 234.2
55 146 084 (2) 172.6 158.2 414.9 162.0 166.3 389.4 150.8 175.5 362.5 138.7 184.7 333.5 125.1 196.1 300.7
161 084 (2) 173.2 162.5 416.2 167.4 177.6 402.3 158.1 193.2 380.1 150.1 211.0 360.8 121.4 220.0 291.8
171 084 (2) 184.9 179.5 444.5 178.7 196.1 429.6 170.4 214.5 409.5 160.6 233.7 386.0 129.0 241.9 310.0
186 084 (2) 200.5 204.8 482.0 193.6 222.8 465.3 182.9 243.2 439.6 171.8 263.1 413.0 124.1 266.5 298.4
206 084 (2) and 094 (1) 235.4 208.5 565.7 227.9 229.5 547.7 219.0 251.4 526.4 208.2 275.6 500.4 184.4 294.1 443.1
246 094 (3) 270.2 247.4 649.5 262.4 271.7 630.7 252.1 297.1 606.0 237.8 325.1 571.5 214.4 348.3 515.4
261 094 (3) 285.8 267.4 687.0 277.5 293.4 666.9 266.6 320.7 640.8 247.8 348.9 595.7 222.0 372.3 533.5
271 094 (3) 300.4 289.1 722.0 291.5 316.6 700.6 278.6 345.2 669.7 262.3 377.2 630.4 218.1 391.9 524.3
076 084 (1) 85.2 79.9 204.9 79.4 83.9 190.9 73.4 88.5 176.5 66.9 93.3 161.0 59.6 98.8 143.3
086 084 (1) 93.6 90.8 225.1 86.4 95.1 208.0 79.7 100.2 191.8 72.0 105.1 173.3 62.3 110.3 149.8
096 094 (1) 103.7 102.4 249.4 96.5 108.1 232.2 89.0 113.8 214.2 81.2 120.5 195.4 65.4 121.9 157.3
106 074 (1) and 044 (1) 119.6 113.7 287.6 111.7 119.7 268.7 102.3 125.5 246.1 93.5 132.2 225.0 83.5 140.4 200.8
116 074 (1) and 054 (1) 128.3 123.3 308.7 120.0 129.9 288.6 111.1 137.0 267.2 100.8 143.6 242.4 90.0 152.6 216.5
126 074 (2) 143.0 132.7 344.1 133.9 139.9 322.2 124.4 147.9 299.1 113.1 155.2 272.0 101.4 164.6 243.8
136 074 (2) 153.7 149.5 369.7 143.8 157.2 345.9 133.1 165.4 320.1 121.8 175.6 293.0 98.6 177.4 237.1
60 146 084 (2) 172.8 158.3 415.7 162.2 166.4 390.1 151.0 175.5 363.6 137.8 184.0 331.4 125.2 196.1 301.2
161 084 (2) 171.9 161.7 413.5 166.1 176.7 399.6 158.3 193.3 380.8 150.2 211.1 361.4 120.6 219.3 290.0
171 084 (2) 185.1 179.6 445.2 178.9 196.1 430.4 170.5 214.6 410.2 160.7 233.8 386.6 130.1 241.8 313.0
186 084 (2) 200.7 205.0 482.8 193.7 223.1 465.9 181.5 242.2 436.7 171.9 263.3 413.6 124.2 266.6 298.7
206 084 (2) and 094 (1) 235.5 208.6 566.6 228.0 229.5 548.6 219.2 251.5 527.2 208.3 275.7 501.2 184.5 294.1 443.9
246 094 (3) 270.4 247.6 650.5 262.6 271.9 631.6 252.3 297.2 607.0 238.0 325.2 572.4 214.6 348.5 516.2
261 094 (3) 286.0 267.5 688.0 277.7 293.5 668.0 264.0 319.3 635.1 248.0 349.0 596.5 222.1 372.5 534.3
271 094 (3) 300.6 289.2 723.1 291.7 316.7 701.7 278.9 345.4 670.8 262.5 377.3 631.5 218.2 392.3 524.9

LEGEND
Cap. — Capacity, Tons of Refrigeration
kW — Compressor Motor Input Power at Rated Voltages
LCWT — Leaving Chilled-Water Temperature (F)

45
Performance data (cont)
COMBINATION RATINGS (cont)
60 Hz, SI

CONDENSER ENTERING AIR TEMPERATURE (C)


09DK
30 35 40 45 50
UNIT AIR-COOLED
LCWT Cooler Cooler Cooler Cooler Cooler
(C) SIZE CONDENSER
30HXA Input Flow Input Flow Input Flow Input Flow Input Flow
Cap. Cap. Cap. Cap. Cap.
Unit (Qty) kW Rate kW Rate kW Rate kW Rate kW Rate
(L/s) (L/s) (L/s) (L/s) (L/s)
076 084 (1) 231.7 69.2 9.9 216.1 72.9 9.2 198.6 76.7 8.5 181.2 81.9 7.7 166.4 88.5 7.1
086 084 (1) 254.3 78.4 10.8 236.2 82.6 10.1 217.3 87.5 9.3 198.8 93.6 8.5 182.0 100.5 7.8
096 094 (1) 284.3 89.1 12.1 264.7 93.6 11.3 243.5 99.6 10.4 223.3 106.5 9.5 204.7 114.1 8.7
106 074 (1) and 044 (1) 326.4 98.8 13.9 304.5 103.9 13.0 281.1 109.9 12.0 258.4 117.4 11.0 237.3 126.2 10.1
116 074 (1) and 044 (1) 350.2 107.1 14.9 326.4 112.7 13.9 301.7 119.4 12.8 277.4 127.9 11.8 254.4 137.0 10.8
126 074 (2) 386.0 114.9 16.4 360.7 121.2 15.4 333.7 128.2 14.2 307.5 137.1 13.1 282.6 147.2 12.0
136 074 (2) 418.9 130.0 17.8 391.3 136.5 16.7 362.0 144.8 15.4 334.2 154.9 14.2 307.2 165.9 13.1
4 146 084 (2) 466.3 137.5 19.9 436.6 144.4 18.6 405.3 152.1 17.3 373.9 162.7 15.9 345.0 174.5 14.7
161 084 (2) 485.5 146.3 20.7 465.8 158.5 19.8 444.4 171.7 18.9 424.1 187.5 18.1 402.9 206.8 17.2
171 084 (2) 521.1 161.4 22.2 498.8 174.5 21.2 476.3 189.0 20.3 454.6 206.6 19.4 432.3 228.5 18.4
186 084 (2) 564.4 182.9 24.0 536.9 197.1 22.9 514.8 213.2 21.9 490.5 233.9 20.9 465.6 258.3 19.8
206 084 (2) and 094 (1) 665.3 190.3 28.3 641.2 206.8 27.3 613.6 224.2 26.1 583.6 244.7 24.9 555.1 268.7 23.6
246 094 (3) 772.8 226.4 32.9 743.9 245.0 31.7 707.4 265.1 30.1 676.2 288.4 28.8 643.0 317.4 27.4
261 094 (3) 810.1 242.7 34.5 777.0 262.6 33.1 740.5 283.8 31.5 707.8 309.5 30.1 673.0 340.6 28.7
271 094 (3) 851.7 260.9 36.3 812.7 282.1 34.6 777.3 304.2 33.1 742.6 333.0 31.6 705.9 365.4 30.1
076 084 (1) 240.0 70.5 10.2 224.4 74.2 9.6 206.6 78.2 8.8 188.7 83.1 8.0 172.7 89.4 7.4
086 084 (1) 263.1 79.9 11.2 245.1 84.1 10.4 225.6 89.0 9.6 206.4 94.9 8.8 188.7 101.7 8.0
096 094 (1) 294.6 90.7 12.6 274.0 95.5 11.7 252.7 101.2 10.8 232.1 107.9 9.9 212.1 115.6 9.0
106 074 (1) and 044 (1) 337.9 100.6 14.4 315.8 105.8 13.5 292.1 111.5 12.5 268.2 119.0 11.4 246.2 127.7 10.5
116 074 (1) and 054 (1) 362.3 109.1 15.4 338.4 114.8 14.4 313.1 121.2 13.3 287.7 129.6 12.3 264.2 138.6 11.3
126 074 (2) 399.2 117.1 17.0 373.8 123.4 15.9 346.8 129.9 14.8 318.8 138.9 13.6 293.0 149.0 12.5
136 074 (2) 433.6 132.3 18.5 405.4 138.8 17.3 375.4 147.0 16.0 346.6 157.0 14.8 318.5 168.0 13.6
5 146 084 (2) 482.3 140.0 20.6 453.2 146.9 19.3 420.8 154.3 17.9 387.9 164.7 16.5 357.9 176.6 15.3
161 084 (2) 500.7 148.2 21.3 480.3 160.8 20.5 458.9 174.0 19.6 437.5 189.8 18.6 415.5 208.6 17.7
171 084 (2) 537.5 163.6 22.9 515.1 176.9 22.0 491.5 191.4 20.9 469.0 208.9 20.0 445.7 230.1 19.0
186 084 (2) 583.3 185.5 24.9 553.9 200.3 23.6 531.2 215.9 22.6 506.4 236.8 21.6 480.2 260.1 20.5
206 084 (2) and 094 (1) 685.0 193.1 29.2 661.5 209.5 28.2 634.3 227.3 27.0 602.6 247.8 25.7 573.0 270.7 24.4
246 094 (3) 795.7 229.6 33.9 768.7 248.3 32.8 730.8 268.9 31.1 697.8 291.8 29.7 663.6 320.5 28.3
261 094 (3) 834.1 246.1 35.5 803.7 266.1 34.3 763.9 288.0 32.6 730.3 312.9 31.1 694.4 344.2 29.6
271 094 (3) 876.6 265.1 37.4 840.2 286.1 35.8 801.4 309.0 34.2 766.4 336.7 32.7 728.4 369.5 31.0
076 084 (1) 248.7 71.8 10.6 232.3 75.7 9.9 214.3 79.7 9.1 196.1 84.3 8.4 179.0 90.4 7.6
086 084 (1) 272.2 81.5 11.6 253.8 85.8 10.8 234.3 90.4 10.0 214.5 96.1 9.1 196.0 102.7 8.4
096 094 (1) 304.7 92.6 13.0 283.9 97.4 12.1 262.2 103.0 11.2 240.4 109.5 10.3 219.7 117.0 9.4
106 074 (1) and 044 (1) 349.7 102.5 14.9 327.3 107.9 14.0 302.8 113.5 12.9 278.2 120.6 11.9 255.4 129.1 10.9
116 074 (1) and 054 (1) 374.6 111.2 16.0 350.9 116.9 15.0 324.9 122.9 13.9 298.2 131.2 12.7 273.9 140.3 11.7
126 074 (2) 413.1 119.2 17.6 387.7 125.6 16.5 359.6 132.0 15.3 330.6 140.8 14.1 303.9 150.8 13.0
136 074 (2) 448.7 134.7 19.1 419.9 141.4 17.9 389.2 149.5 16.6 359.2 159.1 15.3 330.0 170.2 14.1
6 146 084 (2) 499.0 142.5 21.3 469.4 149.5 20.0 436.3 156.9 18.6 402.3 167.0 17.2 371.1 178.7 15.8
161 084 (2) 515.5 150.5 22.0 495.6 163.1 21.1 473.6 176.7 20.2 451.2 192.3 19.2 428.7 210.7 18.3
171 084 (2) 554.1 165.8 23.6 531.9 179.6 22.7 506.7 194.4 21.6 483.4 211.4 20.6 459.2 232.3 19.6
186 084 (2) 601.2 188.5 25.6 572.4 203.5 24.4 547.4 219.6 23.3 522.4 239.9 22.3 495.6 262.9 21.1
206 084 (2) and 094 (1) 705.3 195.7 30.1 682.2 212.3 29.1 655.5 230.4 28.0 621.8 251.0 26.5 591.4 273.4 25.2
246 094 (3) 818.3 232.9 34.9 792.6 251.9 33.8 755.2 272.8 32.2 719.8 295.8 30.7 684.8 324.0 29.2
261 094 (3) 858.6 249.6 36.6 830.9 269.6 35.4 788.3 292.3 33.6 753.2 316.6 32.1 716.4 347.9 30.6
271 094 (3) 902.4 269.1 38.5 868.5 290.2 37.0 825.8 313.8 35.2 790.1 340.6 33.7 751.3 374.1 32.0

LEGEND
Cap. — Capacity, kW
kW — Compressor Motor Input Power at Rated Voltages
LCWT — Leaving Chilled-Water Temperature (C)

46
COMBINATION RATINGS (cont)
60 Hz, SI (cont)

CONDENSER ENTERING AIR TEMPERATURE (C)


09DK
30 35 40 45 50
UNIT AIR-COOLED
LCWT Cooler Cooler Cooler Cooler Cooler
(C) SIZE CONDENSER
30HXA Input Flow Input Flow Input Flow Input Flow Input Flow
Cap. Cap. Cap. Cap. Cap.
Unit (Qty) kW Rate kW Rate kW Rate kW Rate kW Rate
(L/s) (L/s) (L/s) (L/s) (L/s)
076 084 (1) 257.3 73.4 11.0 240.4 77.3 10.3 222.6 81.2 9.5 204.0 85.5 8.7 185.3 91.3 7.9
086 084 (1) 281.2 83.2 12.0 262.8 87.5 11.2 243.1 91.9 10.4 222.5 97.4 9.5 202.9 103.9 8.7
096 094 (1) 314.9 94.5 13.4 293.7 99.3 12.5 272.3 104.6 11.6 249.7 110.9 10.7 227.8 118.3 9.7
106 074 (1) and 044 (1) 361.6 104.5 15.4 338.7 109.9 14.5 314.4 115.4 13.4 288.8 122.4 12.3 264.7 130.6 11.3
116 074 (1) and 054 (1) 387.5 113.2 16.5 363.4 119.1 15.5 336.6 125.2 14.4 309.3 133.2 13.2 283.7 142.1 12.1
126 074 (2) 427.4 121.3 18.2 401.3 127.9 17.1 372.7 134.6 15.9 343.2 142.8 14.6 315.1 152.6 13.4
136 074 (2) 464.0 137.4 19.8 434.3 144.2 18.5 403.5 152.0 17.2 372.3 161.3 15.9 341.9 172.3 14.6
7 146 084 (2) 516.2 144.9 22.0 485.8 152.3 20.7 452.5 159.8 19.3 417.7 169.3 17.8 384.5 180.9 16.4
161 084 (2) 530.3 152.9 22.6 511.1 165.5 21.8 488.9 179.2 20.9 465.0 195.0 19.8 433.5 211.2 18.5
171 084 (2) 569.9 168.3 24.3 548.7 182.4 23.4 522.9 197.5 22.3 498.1 214.6 21.3 473.4 234.9 20.2
186 084 (2) 618.9 191.7 26.4 591.2 206.9 25.2 564.0 223.1 24.1 538.3 243.0 23.0 498.3 263.3 21.3
206 084 (2) and 094 (1) 725.9 198.3 31.0 703.4 214.9 30.0 676.6 233.5 28.9 642.4 254.0 27.4 610.2 276.6 26.0
246 094 (3) 842.4 236.1 35.9 816.8 255.5 34.9 780.1 276.7 33.3 742.3 299.7 31.7 706.3 327.5 30.1
261 094 (3) 883.5 253.1 37.7 856.0 273.8 36.5 814.0 296.9 34.7 776.4 321.1 33.1 738.8 351.8 31.5
271 094 (3) 928.9 273.1 39.6 897.4 294.3 38.3 850.9 318.6 36.3 814.4 344.5 34.8 774.3 378.9 33.0
076 084 (1) 266.1 74.9 11.4 249.0 78.7 10.6 231.1 82.6 9.9 211.8 86.7 9.0 192.3 92.4 8.2
086 084 (1) 290.7 84.8 12.4 272.2 89.1 11.6 251.7 93.6 10.7 230.7 98.9 9.8 210.1 105.3 9.0
096 094 (1) 325.4 96.4 13.9 304.2 101.2 13.0 281.9 106.3 12.0 258.6 112.7 11.0 236.2 119.9 10.1
106 074 (1) and 044 (1) 373.6 106.6 16.0 350.5 112.0 15.0 325.7 117.6 13.9 299.8 124.2 12.8 274.2 132.3 11.7
116 074 (1) and 054 (1) 400.4 115.3 17.1 375.8 121.3 16.0 348.8 127.5 14.9 321.1 135.0 13.7 294.2 143.8 12.6
126 074 (2) 441.4 123.7 18.8 415.2 130.2 17.7 386.4 137.0 16.5 356.3 144.8 15.2 326.5 154.4 13.9
136 074 (2) 479.9 140.2 20.5 449.4 147.0 19.2 417.9 154.5 17.8 385.3 163.6 16.5 350.2 173.8 14.9
8 146 084 (2) 533.4 147.7 22.8 502.7 155.0 21.5 468.9 162.7 20.0 433.4 171.7 18.5 398.3 183.1 17.0
161 084 (2) 545.7 155.2 23.3 526.7 167.9 22.5 504.1 181.9 21.5 479.4 197.3 20.5 442.7 212.7 18.9
171 084 (2) 586.2 171.0 25.0 565.6 185.1 24.1 539.3 200.6 23.0 513.6 217.4 21.9 479.5 235.7 20.5
186 084 (2) 636.2 194.8 27.2 610.4 210.1 26.1 580.6 226.9 24.8 554.6 246.0 23.7 505.2 264.9 21.6
206 084 (2) and 094 (1) 747.2 200.8 31.9 724.7 217.9 30.9 696.5 236.9 29.7 663.6 257.1 28.3 629.3 280.3 26.9
246 094 (3) 866.5 239.4 37.0 841.8 258.9 35.9 805.9 280.4 34.4 765.1 303.8 32.7 728.3 330.9 31.1
261 094 (3) 908.4 256.8 38.8 881.8 277.8 37.6 840.6 301.3 35.9 800.1 325.9 34.2 761.5 355.8 32.5
271 094 (3) 955.8 277.1 40.8 926.2 298.3 39.5 878.7 323.6 37.5 839.2 349.4 35.8 798.3 383.3 34.1
076 084 (1) 275.1 76.5 11.7 257.6 80.2 11.0 239.9 84.1 10.2 219.8 88.3 9.4 199.6 93.9 8.5
086 084 (1) 300.5 86.5 12.8 281.4 90.8 12.0 260.8 95.3 11.1 239.2 100.4 10.2 217.9 106.7 9.3
096 094 (1) 335.9 98.4 14.3 314.5 103.1 13.4 291.8 108.2 12.5 267.8 114.5 11.4 239.6 120.5 10.2
106 074 (1) and 044 (1) 386.0 108.6 16.5 362.6 114.1 15.5 337.6 119.8 14.4 310.8 126.2 13.3 284.1 134.1 12.1
116 074 (1) and 054 (1) 431.7 117.4 17.7 388.2 123.8 16.6 361.0 130.0 15.4 332.7 136.9 14.2 304.2 145.7 13.0
126 074 (2) 456.1 126.1 19.5 429.0 132.7 18.3 400.3 139.5 17.1 369.4 146.8 15.8 338.3 156.4 14.5
136 074 (2) 494.5 143.1 21.1 464.7 149.8 19.8 432.5 157.1 18.5 399.1 165.9 17.0 355.2 174.5 15.2
9 146 084 (2) 551.0 150.4 23.5 519.5 157.9 22.2 485.5 165.7 20.7 449.4 174.1 19.2 412.8 185.5 17.6
161 084 (2) 561.1 157.4 24.0 542.7 170.2 23.2 519.4 184.5 22.2 494.3 199.8 21.1 447.6 213.5 19.1
171 084 (2) 602.7 173.7 25.7 582.3 188.0 24.9 556.0 203.6 23.7 528.9 220.3 22.6 489.7 237.6 20.9
186 084 (2) 654.2 198.0 27.9 629.7 213.4 26.9 597.5 230.8 25.5 571.1 248.8 24.4 503.8 264.6 21.5
206 084 (2) and 094 (1) 768.8 203.3 32.8 746.5 220.8 31.9 717.4 240.3 30.6 685.2 260.6 29.3 648.6 283.8 27.7
246 094 (3) 890.8 242.6 38.0 866.2 262.6 37.0 832.1 284.4 35.5 788.5 308.4 33.7 750.2 334.7 32.0
261 094 (3) 933.8 260.5 39.9 907.2 282.0 38.7 868.2 305.7 37.1 824.0 331.0 35.2 784.1 359.5 33.5
271 094 (3) 982.8 281.0 42.0 952.7 303.3 40.7 907.4 328.6 38.8 863.9 355.2 36.9 821.9 387.3 35.1

LEGEND
Cap. — Capacity, kW
kW — Compressor Motor Input Power at Rated Voltages
LCWT — Leaving Chilled-Water Temperature (C)

47
Performance data (cont)
COMBINATION RATINGS (cont)
60 Hz, SI (cont)

CONDENSER ENTERING AIR TEMPERATURE (C)


09DK
30 35 40 45 50
UNIT AIR-COOLED
LCWT Cooler Cooler Cooler Cooler Cooler
(C) SIZE CONDENSER
30HXA Input Flow Input Flow Input Flow Input Flow Input Flow
Cap. Cap. Cap. Cap. Cap.
Unit (Qty) kW Rate kW Rate kW Rate kW Rate kW Rate
(L/s) (L/s) (L/s) (L/s) (L/s)
076 084 (1) 284.2 78.1 12.1 266.5 81.7 11.4 248.0 85.7 10.6 227.8 90.0 9.7 207.6 95.1 8.9
086 084 (1) 310.3 88.2 13.3 290.6 92.6 12.4 269.7 97.2 11.5 248.1 101.9 10.6 225.6 108.1 9.6
096 094 (1) 346.9 100.3 14.8 325.0 105.1 13.9 301.7 110.3 12.9 277.7 116.4 11.9 243.2 121.0 10.4
106 074 (1) and 044 (1) 398.6 110.7 17.0 374.6 116.3 16.0 349.0 122.2 14.9 322.0 128.2 13.8 294.5 135.9 12.6
116 074 (1) and 054 (1) 426.7 119.8 18.2 401.1 126.1 17.1 373.7 132.4 16.0 344.7 138.8 14.7 315.0 147.5 13.5
126 074 (2) 470.7 128.6 20.1 443.3 135.2 18.9 414.1 142.1 17.7 382.6 149.2 16.3 350.5 158.5 15.0
136 074 (2) 510.4 145.9 21.8 479.9 152.7 20.5 447.3 159.8 19.1 413.0 168.8 17.6 363.9 176.1 15.6
10 146 084 (2) 568.7 153.5 24.3 536.8 160.8 22.9 502.6 168.7 21.5 465.4 176.9 19.9 427.5 188.0 18.3
161 084 (2) 576.7 159.8 24.6 558.7 172.7 23.9 534.3 187.5 22.8 509.3 202.8 21.8 452.6 214.5 19.3
171 084 (2) 619.3 176.5 26.5 599.3 190.9 25.6 572.6 206.9 24.5 544.3 223.4 23.3 496.1 238.4 21.2
186 084 (2) 672.1 201.3 28.7 649.3 216.8 27.7 615.1 234.6 26.3 587.5 252.8 25.1 502.1 264.2 21.5
206 084 (2) and 094 (1) 790.8 206.1 33.8 767.5 224.1 32.8 738.9 243.5 31.6 707.1 264.3 30.2 668.2 287.4 28.6
246 094 (3) 915.2 245.7 39.1 890.5 266.4 38.1 857.3 288.7 36.6 813.3 313.2 34.8 772.5 339.3 33.0
261 094 (3) 959.2 264.2 41.0 932.5 286.4 39.8 895.9 310.3 38.3 848.2 336.1 36.2 807.4 363.4 34.5
271 094 (3) 1008.9 285.2 43.1 979.6 308.3 41.9 936.4 333.6 40.0 889.2 361.0 38.0 846.1 391.7 36.2
076 084 (1) 299.4 80.6 12.8 281.1 84.2 12.0 259.5 88.0 11.1 237.1 91.7 10.1 216.0 96.5 9.2
086 084 (1) 323.6 90.6 13.8 303.6 94.9 13.0 282.4 99.6 12.1 259.8 104.2 11.1 237.0 110.1 10.1
096 094 (1) 364.2 103.4 15.6 341.7 108.5 14.6 318.0 113.6 13.6 290.2 118.8 12.4 249.7 122.1 10.7
106 074 (1) and 044 (1) 415.6 113.9 17.8 391.0 119.3 16.7 365.1 125.3 15.6 337.3 131.1 14.4 308.7 138.6 13.2
116 074 (1) and 054 (1) 448.0 123.8 19.2 421.5 129.9 18.0 393.7 136.3 16.8 363.7 142.5 15.6 332.9 150.8 14.2
126 074 (2) 498.9 133.3 21.3 470.1 139.8 20.1 440.1 147.0 18.8 404.0 153.1 17.3 370.4 161.8 15.8
136 074 (2) 540.0 150.9 23.1 508.5 157.9 21.8 474.5 165.3 20.3 439.8 173.9 18.8 373.2 177.4 16.0
13 146 084 (2) 607.6 159.7 26.0 569.3 166.2 24.4 534.3 174.4 22.9 496.5 182.7 21.2 452.0 191.9 19.3
161 084 (2) 602.0 163.2 25.8 583.5 176.8 25.0 559.2 191.6 23.9 534.0 207.4 22.8 461.6 216.1 19.7
171 084 (2) 652.2 181.8 27.9 632.3 196.8 27.0 606.9 213.3 26.0 575.2 230.6 24.6 503.4 240.1 21.5
186 084 (2) 702.1 206.4 30.0 679.4 222.8 29.1 646.0 241.0 27.6 614.6 259.8 26.3 501.8 264.1 21.5
206 084 (2) and 094 (1) 830.4 211.1 35.5 799.3 229.4 34.2 766.7 247.9 32.8 733.9 269.3 31.4 688.8 291.1 29.5
246 094 (3) 953.4 250.6 40.8 928.3 272.6 39.7 896.6 295.3 38.4 852.3 320.3 36.5 798.6 344.8 34.2
261 094 (3) 994.1 268.9 42.5 967.6 291.9 41.4 933.4 316.3 39.9 883.4 343.1 37.8 834.6 369.6 35.7
271 094 (3) 1054.9 292.0 45.1 1016.3 315.0 43.5 976.4 340.4 41.8 923.8 368.7 39.5 866.1 395.5 37.0
076 084 (1) 296.7 80.1 12.7 278.3 83.7 11.9 259.3 87.9 11.1 239.2 92.1 10.2 217.9 96.9 9.3
086 084 (1) 326.1 91.0 14.0 305.8 95.4 13.1 282.0 99.5 12.1 259.5 104.2 11.1 236.8 109.9 10.1
096 094 (1) 360.9 102.8 15.5 338.7 107.8 14.5 315.0 112.9 13.5 290.4 118.8 12.4 249.6 121.9 10.7
106 074 (1) and 044 (1) 419.2 114.4 17.9 394.1 119.9 16.9 368.4 125.8 15.8 333.8 130.4 14.3 305.7 137.9 13.1
116 074 (1) and 054 (1) 451.6 124.4 19.3 420.8 129.6 18.0 392.6 136.1 16.8 362.5 142.3 15.5 331.9 150.6 14.2
126 074 (2) 498.3 133.1 21.3 469.5 139.6 20.1 439.4 146.8 18.8 407.2 153.9 17.4 373.7 162.4 16.0
136 074 (2) 535.3 150.1 22.9 503.9 156.9 21.6 470.3 164.3 20.1 435.1 173.1 18.6 376.2 178.0 16.1
16 146 084 (2) 602.2 158.7 25.8 568.5 166.1 24.3 533.4 174.3 22.8 495.7 182.5 21.2 456.0 192.5 19.5
161 084 (2) 605.9 163.9 25.9 587.4 177.6 25.2 558.1 191.2 23.9 532.9 207.2 22.8 465.0 216.8 19.9
171 084 (2) 647.1 181.0 27.7 627.5 195.8 26.9 601.7 212.3 25.8 570.0 229.7 24.4 503.0 240.1 21.5
186 084 (2) 701.7 206.4 30.0 679.4 222.5 29.1 646.1 240.7 27.7 609.4 258.7 26.1 501.3 264.1 21.5
206 084 (2) and 094 (1) 823.5 210.4 35.3 799.7 229.2 34.2 772.2 248.6 33.1 739.4 270.0 31.7 689.3 291.2 29.5
246 094 (3) 954.7 250.5 40.9 920.9 271.4 39.4 888.8 294.2 38.1 844.4 319.0 36.2 791.6 343.3 33.9
261 094 (3) 1000.6 269.7 42.8 973.9 293.1 41.7 939.9 317.5 40.2 890.2 344.2 38.1 827.6 367.9 35.4
271 094 (3) 1051.8 291.5 45.0 1023.1 316.2 43.8 983.7 341.6 42.1 930.1 370.1 39.8 867.7 396.1 37.2

LEGEND
Cap. — Capacity, kW
kW — Compressor Motor Input Power at Rated Voltages
LCWT — Leaving Chilled-Water Temperature (C)

48
COMBINATION RATINGS (cont)
50 Hz, ENGLISH

CONDENSER ENTERING AIR TEMPERATURE (F)


09DK
85 95 105 115 125
UNIT AIR-COOLED
LCWT Cooler Cooler Cooler Cooler Cooler
(F) SIZE CONDENSER
30HXA Input Flow Input Flow Input Flow Input Flow Input Flow
Cap. Cap. Cap. Cap. Cap.
Unit (Qty) kW Rate kW Rate kW Rate kW Rate kW Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
076 084 (1) 67.9 68.0 162.4 62.8 72.0 150.5 57.2 76.3 137.0 51.6 82.0 123.6 47.1 89.3 112.7
086 084 (1) 74.4 78.3 178.2 68.8 82.9 164.6 62.7 88.3 150.1 56.8 95.2 135.9 51.4 103.2 123.1
096 094 (1) 83.1 88.1 198.9 76.8 93.2 183.7 70.0 99.7 167.6 63.6 107.4 152.3 57.7 115.5 138.1
106 074 (1) and 044 (1) 94.8 97.2 226.9 87.9 102.9 210.4 80.5 109.4 192.6 73.1 117.8 175.1 66.6 127.4 159.4
116 074 (1) and 054 (1) 101.8 106.5 243.7 94.3 112.9 225.7 86.4 120.3 206.8 78.6 129.9 188.3 71.3 139.9 170.7
126 074 (2) 111.9 113.7 267.9 104.0 120.6 249.1 95.5 128.2 228.6 87.1 138.4 208.5 79.1 149.4 189.5
136 074 (2) 121.0 127.9 289.6 112.4 135.1 269.0 103.3 144.1 247.2 94.6 155.2 226.5 86.4 166.4 206.7
40 146 084 (2) 133.9 134.8 320.5 124.9 142.6 299.0 115.2 151.0 275.7 105.4 162.7 252.4 96.3 175.6 230.6
161 084 (2) 139.4 145.3 333.7 132.9 159.0 318.2 126.1 174.1 301.8 119.0 191.3 284.9 110.5 211.8 264.6
171 084 (2) 149.3 159.6 357.5 142.1 174.4 340.2 135.0 190.6 323.1 127.4 209.9 305.1 119.8 233.3 286.8
186 084 (2) 161.3 180.5 386.2 151.8 196.8 363.5 144.8 215.2 346.5 136.0 236.6 325.5 125.9 261.7 301.5
206 084 (2) and 094 (1) 190.2 188.1 455.4 182.8 206.2 437.5 174.0 226.0 416.5 164.1 248.0 392.9 154.4 274.9 369.7
246 094 (3) 221.0 224.7 529.1 212.1 245.3 507.8 200.0 268.4 478.8 189.6 294.8 453.8 177.8 326.1 425.5
261 094 (3) 231.3 240.4 553.6 221.3 262.2 529.7 209.2 286.7 500.8 198.1 315.1 474.3 185.9 348.4 444.9
271 094 (3) 242.4 258.4 580.2 230.5 281.6 551.7 218.7 307.5 523.5 206.4 338.4 494.1 193.0 372.9 462.1
076 084 (1) 70.5 69.4 168.9 65.4 73.6 156.6 59.8 77.9 143.2 54.0 83.3 129.3 48.9 90.5 117.2
086 084 (1) 77.3 80.0 185.2 71.5 84.7 171.3 65.4 89.9 156.6 59.1 96.6 141.6 53.5 104.5 128.3
096 094 (1) 86.3 90.2 206.6 79.8 95.3 191.1 72.9 101.6 174.7 66.3 109.1 158.7 59.3 116.8 141.9
106 074 (1) and 044 (1) 98.4 99.3 235.7 91.5 105.0 219.2 83.9 111.3 201.1 76.3 119.5 182.8 69.3 129.1 166.0
116 074 (1) and 054 (1) 105.7 108.8 253.1 98.2 115.2 235.2 90.1 122.2 215.8 82.0 131.5 196.3 74.3 141.8 178.0
126 074 (2) 116.3 115.9 278.6 108.3 123.0 259.4 99.5 130.3 238.4 90.6 140.3 217.1 82.5 151.4 197.5
136 074 (2) 125.7 130.5 301.1 116.9 137.8 280.1 107.5 146.6 257.6 98.4 157.5 235.8 89.7 169.1 214.8
42 146 084 (2) 139.0 137.5 333.1 130.1 145.3 311.6 119.9 153.5 287.3 109.7 164.9 262.9 100.4 177.8 240.5
161 084 (2) 143.9 147.8 344.7 137.6 161.6 329.6 130.5 176.9 312.7 123.2 194.1 295.1 111.2 212.3 266.4
171 084 (2) 154.3 162.3 369.7 147.3 177.3 352.9 139.7 193.6 334.6 131.9 212.6 316.1 122.9 234.8 294.4
186 084 (2) 166.6 184.0 399.0 157.4 200.5 377.2 149.8 218.7 358.8 140.8 240.4 337.4 126.0 261.7 301.9
206 084 (2) and 094 (1) 196.5 191.0 470.7 189.2 209.1 453.2 180.5 229.2 432.4 170.0 251.7 407.3 160.0 277.3 383.2
246 094 (3) 228.1 228.2 546.5 219.5 249.1 525.9 207.4 272.5 496.7 196.4 298.6 470.5 184.1 329.9 441.1
261 094 (3) 238.9 243.9 572.2 229.6 266.1 550.1 216.3 291.0 518.3 205.2 319.2 491.6 192.5 352.5 461.2
271 094 (3) 250.3 262.6 599.7 239.2 286.0 572.9 226.0 312.3 541.3 213.9 343.0 512.4 199.9 377.4 478.9
076 084 (1) 73.3 71.0 175.7 68.0 75.3 162.9 62.3 79.5 149.4 56.4 84.7 135.1 50.9 91.6 122.0
086 084 (1) 80.2 81.8 192.3 74.3 86.6 178.2 68.0 91.7 163.1 61.7 98.1 147.8 55.7 105.8 133.5
096 094 (1) 89.5 92.2 214.6 82.9 97.5 198.8 76.0 103.5 182.2 69.0 110.8 165.3 60.3 117.4 144.5
106 074 (1) and 044 (1) 102.2 101.4 245.0 95.1 107.3 228.0 87.3 113.4 209.4 79.5 121.3 190.5 72.2 130.8 173.0
116 074 (1) and 054 (1) 109.7 111.0 262.9 102.1 117.6 244.8 93.8 124.2 224.8 85.2 133.5 204.3 77.4 143.7 185.5
126 074 (2) 120.7 118.4 289.4 112.6 125.5 269.9 103.7 132.7 248.5 94.3 142.4 226.1 85.8 153.4 205.7
136 074 (2) 130.4 133.5 312.5 121.5 140.9 291.2 112.0 149.3 268.5 102.5 159.9 245.6 90.4 169.0 216.8
44 146 084 (2) 144.4 140.3 346.0 135.1 148.3 323.9 124.9 156.5 299.5 114.4 167.3 274.3 104.5 180.2 250.5
161 084 (2) 148.5 150.4 356.0 142.4 164.2 341.3 135.1 179.7 323.9 127.5 197.1 305.7 114.0 213.6 273.2
171 084 (2) 159.2 165.1 381.7 152.6 180.2 365.8 144.4 197.0 346.1 136.5 215.5 327.1 125.0 236.1 299.6
186 084 (2) 171.8 187.6 411.9 163.3 203.9 391.4 154.7 222.5 370.7 145.8 244.3 349.5 126.1 261.8 302.3
206 084 (2) and 094 (1) 202.9 193.7 486.5 195.7 212.1 469.2 187.0 232.5 448.4 176.1 255.3 422.2 165.7 280.5 397.2
246 094 (3) 235.4 231.8 564.2 227.0 253.2 544.2 214.9 276.8 515.1 203.2 303.1 487.1 190.7 334.4 457.2
261 094 (3) 246.5 247.8 590.9 237.6 270.5 569.6 224.0 295.9 536.9 212.4 323.5 509.3 199.3 357.5 477.7
271 094 (3) 258.4 267.0 619.4 248.0 290.5 594.5 233.3 317.2 559.4 221.5 347.8 530.9 207.0 383.2 496.3

LEGEND
Cap. — Capacity, Tons of Refrigeration
kW — Compressor Motor Input Power at Rated Voltages
LCWT — Leaving Chilled-Water Temperature (F)

49
Performance data (cont)
COMBINATION RATINGS (cont)
50 Hz, ENGLISH (cont)

CONDENSER ENTERING AIR TEMPERATURE (F)


09DK
85 95 105 115 125
UNIT AIR-COOLED
LCWT Cooler Cooler Cooler Cooler Cooler
(F) SIZE CONDENSER
30HXA Input Flow Input Flow Input Flow Input Flow Input Flow
Cap. Cap. Cap. Cap. Cap.
Unit (Qty) kW Rate kW Rate kW Rate kW Rate kW Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
076 084 (1) 74.8 71.8 179.3 69.3 76.1 166.2 63.7 80.3 152.8 57.7 85.3 138.3 52.0 92.0 124.6
086 084 (1) 81.7 82.7 195.9 75.8 87.5 181.9 69.5 92.4 166.7 63.0 98.8 151.1 56.7 106.5 136.1
096 094 (1) 91.2 93.3 218.6 84.5 98.5 202.7 77.5 104.5 186.0 70.4 111.6 168.9 60.8 117.6 145.8
106 074 (1) and 044 (1) 104.1 102.5 249.7 97.0 108.4 232.5 89.2 114.5 213.9 81.1 122.3 194.6 73.6 131.6 176.5
116 074 (1) and 054 (1) 111.8 112.1 268.0 104.1 118.7 249.7 95.6 125.4 229.4 87.0 134.5 208.7 79.0 144.6 189.4
126 074 (2) 123.0 119.6 294.9 114.8 126.8 275.2 105.7 134.2 253.5 96.3 143.5 231.0 87.5 154.5 209.9
136 074 (2) 132.8 135.0 318.4 123.8 142.4 296.8 114.2 150.7 274.0 104.4 161.2 250.5 91.1 169.5 218.6
45 146 084 (2) 147.1 141.8 352.7 137.7 149.8 330.3 127.5 158.1 305.8 116.8 168.7 280.0 106.6 181.3 255.7
161 084 (2) 150.8 151.7 361.7 144.8 165.6 347.1 137.4 181.1 329.5 129.7 198.7 311.0 114.9 214.0 275.4
171 084 (2) 161.7 166.6 387.8 155.2 181.6 372.2 146.9 198.6 352.3 138.8 217.3 332.8 126.0 236.6 302.2
186 084 (2) 174.5 189.4 418.5 166.2 205.7 398.5 157.1 224.3 376.8 148.3 246.1 355.7 126.2 261.7 302.5
206 084 (2) and 094 (1) 206.2 195.2 494.4 199.0 213.6 477.3 190.3 234.1 456.4 179.2 257.2 429.7 168.6 282.2 404.2
246 094 (3) 239.1 233.5 573.3 230.8 255.1 553.5 218.7 278.9 524.5 206.7 305.4 495.6 194.1 336.5 465.5
261 094 (3) 250.4 249.8 600.3 241.6 272.7 579.2 228.0 298.1 546.7 216.1 326.0 518.1 202.8 359.8 486.3
271 094 (3) 262.5 269.0 629.5 252.5 292.7 605.4 237.0 319.7 568.3 225.4 350.2 540.4 210.7 385.9 505.2
076 084 (1) 76.1 72.7 182.5 70.7 76.8 169.6 65.0 81.1 155.8 58.9 86.0 141.2 53.0 92.5 127.2
086 084 (1) 83.2 83.7 199.6 77.2 88.4 185.3 70.9 93.2 170.0 64.2 99.6 154.0 58.0 107.0 139.0
096 094 (1) 92.8 94.3 222.7 86.1 99.6 206.6 79.1 105.4 189.7 71.9 112.4 172.4 61.3 117.9 147.1
106 074 (1) and 044 (1) 106.0 103.6 254.3 98.8 109.6 237.1 90.9 115.8 218.1 82.7 123.3 198.5 75.0 132.5 180.0
116 074 (1) and 054 (1) 113.8 113.3 272.9 106.1 120.0 254.5 97.6 126.7 234.0 88.7 135.6 212.9 80.5 145.7 193.0
126 074 (2) 125.2 120.9 300.4 116.9 128.1 280.4 107.9 135.5 258.8 98.4 144.6 236.1 89.3 155.5 214.1
136 074 (2) 135.2 136.5 324.2 126.1 143.9 302.5 116.4 152.2 279.2 106.6 162.3 255.7 91.9 170.0 220.5
46 146 084 (2) 149.8 143.2 359.4 140.3 151.4 336.6 130.1 159.7 312.1 119.2 170.0 286.0 108.8 182.5 260.9
161 084 (2) 153.2 152.9 367.5 147.2 166.9 353.0 139.7 182.5 335.2 132.0 200.1 316.5 115.7 214.4 277.6
171 084 (2) 164.3 168.0 394.0 157.8 183.2 378.5 149.4 200.3 358.4 141.2 219.0 338.6 127.1 237.3 304.8
186 084 (2) 177.3 190.9 425.3 169.2 207.4 405.8 159.6 226.2 382.8 150.9 247.9 361.9 126.2 261.8 302.7
206 084 (2) and 094 (1) 209.5 196.4 502.6 202.4 215.3 485.4 193.4 235.8 463.9 182.5 259.0 437.9 171.5 283.9 411.4
246 094 (3) 242.8 235.2 582.5 234.7 257.0 562.9 222.6 280.9 533.9 210.1 307.7 504.1 197.6 338.6 473.9
261 094 (3) 254.2 251.8 609.8 245.5 275.0 588.8 232.1 300.4 556.6 219.7 328.4 527.1 206.3 362.2 494.9
271 094 (3) 266.7 271.1 639.6 256.8 295.2 615.9 241.2 322.4 578.5 229.3 352.7 549.9 214.4 388.8 514.2
076 084 (1) 78.9 74.4 189.5 73.5 78.4 176.3 67.7 82.8 162.4 61.4 87.4 147.3 55.0 93.8 132.1
086 084 (1) 86.3 85.4 207.2 80.3 90.2 192.6 73.7 95.2 177.0 66.9 101.2 160.5 60.2 108.5 144.5
096 094 (1) 96.2 96.5 230.8 89.4 101.7 214.6 82.2 107.4 197.4 74.7 114.3 179.3 62.5 118.5 150.0
106 074 (1) and 044 (1) 110.0 105.8 263.9 102.6 111.9 246.2 94.7 118.1 227.2 86.2 125.3 207.0 78.0 134.3 187.2
116 074 (1) and 054 (1) 118.0 115.6 283.1 110.0 122.7 263.9 101.4 129.5 243.3 92.4 137.8 221.7 83.6 147.8 200.7
126 074 (2) 129.8 123.6 311.4 121.4 130.8 291.3 112.2 138.3 269.3 102.5 146.8 245.9 92.8 157.7 222.8
136 074 (2) 140.1 139.6 336.3 131.0 146.9 314.3 121.1 154.9 290.6 110.8 164.7 266.0 93.6 170.9 224.5
48 146 084 (2) 155.3 146.5 372.6 145.6 154.5 349.5 135.3 162.9 324.8 124.2 172.6 298.0 113.1 185.0 271.4
161 084 (2) 158.0 155.3 379.2 152.2 169.4 365.2 144.5 185.2 346.7 136.4 203.1 327.3 116.5 214.7 279.7
171 084 (2) 169.4 170.9 406.5 163.0 186.2 391.2 154.5 203.5 370.7 146.0 222.3 350.3 128.2 238.0 307.6
186 084 (2) 182.9 194.2 438.8 175.0 211.1 420.0 164.6 229.9 395.0 156.0 251.4 374.4 126.3 261.8 303.1
206 084 (2) and 094 (1) 216.3 199.2 519.0 209.0 218.7 501.6 199.7 239.5 479.4 189.3 262.6 454.2 177.5 288.0 425.9
246 094 (3) 250.4 238.5 600.8 242.2 261.2 581.2 230.7 285.2 553.7 217.0 312.3 520.8 203.1 341.9 487.5
261 094 (3) 262.0 255.8 628.8 253.2 279.7 607.8 240.5 305.3 577.1 226.9 333.7 544.5 212.1 365.5 509.1
271 094 (3) 274.7 275.5 659.2 264.8 300.7 635.5 249.9 327.8 599.8 236.5 358.6 567.6 218.0 391.2 523.3

LEGEND
Cap. — Capacity, Tons of Refrigeration
kW — Compressor Motor Input Power at Rated Voltages
LCWT — Leaving Chilled-Water Temperature (F)

50
COMBINATION RATINGS (cont)
50 Hz, ENGLISH (cont)

CONDENSER ENTERING AIR TEMPERATURE (F)


09DK
85 95 105 115 125
UNIT AIR-COOLED
LCWT Cooler Cooler Cooler Cooler Cooler
(F) SIZE CONDENSER
30HXA Input Flow Input Flow Input Flow Input Flow Input Flow
Cap. Cap. Cap. Cap. Cap.
Unit (Qty) kW Rate kW Rate kW Rate kW Rate kW Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
076 084 (1) 81.8 76.1 196.3 76.2 80.0 183.0 70.4 84.4 169.0 63.9 89.1 153.5 57.4 95.4 137.9
086 084 (1) 89.3 87.3 214.5 83.2 92.2 199.7 76.6 97.2 183.9 69.5 103.1 166.9 60.7 109.0 145.9
096 094 (1) 99.6 98.6 239.2 92.7 103.9 222.6 85.4 109.5 205.0 77.6 116.4 186.4 63.7 119.4 152.9
106 074 (1) and 044 (1) 113.9 108.3 273.5 106.4 114.3 255.4 98.3 120.6 236.1 89.8 127.5 215.5 81.1 136.4 194.6
116 074 (1) and 054 (1) 122.1 118.5 293.1 114.1 125.2 273.9 105.4 132.2 253.0 96.1 139.9 230.8 86.9 150.0 208.6
126 074 (2) 134.4 126.5 322.7 125.8 133.5 302.1 116.6 141.1 279.9 106.6 149.2 256.0 96.5 159.9 231.8
136 074 (2) 145.2 142.6 348.5 135.8 150.0 326.0 125.8 157.8 302.0 115.1 167.5 276.4 95.3 171.8 228.8
50 146 084 (2) 160.9 149.8 386.3 151.1 157.6 362.8 140.6 166.3 337.6 129.2 175.4 310.1 117.6 187.5 282.3
161 084 (2) 162.9 157.7 391.1 157.1 172.1 377.2 149.2 188.3 358.2 141.0 206.3 338.4 118.4 215.4 284.3
171 084 (2) 174.6 173.6 419.3 168.3 189.4 404.0 159.6 206.7 383.1 150.7 225.8 361.9 130.4 239.0 313.0
186 084 (2) 188.4 197.7 452.4 181.0 214.7 434.6 169.7 234.0 407.6 161.1 255.5 386.7 126.4 261.8 303.4
206 084 (2) and 094 (1) 223.0 202.3 535.4 215.6 222.0 517.6 206.4 243.2 495.5 195.8 266.6 470.1 181.1 290.4 434.9
246 094 (3) 257.9 241.8 619.2 249.7 265.2 599.6 238.8 289.8 573.3 224.2 317.3 538.4 207.7 344.7 498.7
261 094 (3) 269.9 259.6 647.9 261.1 284.2 627.0 249.0 310.3 597.9 234.0 339.2 561.8 216.8 368.5 520.5
271 094 (3) 282.7 280.1 678.9 273.0 306.0 655.5 258.8 333.4 621.4 243.8 364.4 585.4 218.1 391.3 523.6
076 084 (1) 85.6 78.2 205.7 79.9 82.1 191.9 73.7 86.8 177.2 67.2 91.5 161.6 60.5 97.2 145.5
086 084 (1) 94.2 90.2 226.4 87.7 95.1 210.9 80.2 99.8 192.8 73.1 105.4 175.7 62.0 109.7 149.1
096 094 (1) 103.9 101.1 249.8 96.9 106.8 232.8 89.3 112.4 214.7 81.4 119.1 195.7 65.7 120.4 157.8
106 074 (1) and 044 (1) 120.0 112.1 288.5 111.5 117.5 268.0 103.3 124.0 248.3 93.4 129.8 224.4 84.2 138.5 202.4
116 074 (1) and 054 (1) 129.5 123.2 311.3 119.8 129.0 288.0 111.0 136.1 266.8 101.4 143.3 243.8 90.9 152.7 218.5
126 074 (2) 142.6 131.0 342.8 133.5 138.2 321.0 124.0 146.1 298.1 112.7 153.3 270.9 101.1 162.6 243.0
136 074 (2) 152.5 146.9 366.6 143.0 154.4 343.6 132.5 162.6 318.5 121.6 172.1 292.3 98.4 173.3 236.5
55 146 084 (2) 170.7 155.1 410.3 160.5 163.1 385.7 149.6 172.0 359.7 137.9 180.9 331.4 124.6 191.5 299.5
161 084 (2) 171.3 162.0 411.8 164.0 176.1 394.1 156.1 192.4 375.2 147.3 224.5 354.0 122.1 218.1 293.5
171 084 (2) 182.7 178.3 439.0 176.3 194.4 423.7 167.9 212.5 403.5 157.0 255.2 377.3 130.4 239.1 313.5
186 084 (2) 196.8 203.0 473.1 189.4 220.7 455.2 177.2 239.2 425.9 166.1 286.4 399.3 125.5 261.4 301.6
206 084 (2) and 094 (1) 232.7 206.5 559.2 225.0 227.3 540.9 216.1 248.5 519.4 204.8 279.9 492.1 183.7 292.1 441.4
246 094 (3) 267.2 245.8 642.1 258.7 270.5 621.8 248.0 295.6 596.1 233.0 329.5 559.9 211.5 365.7 508.4
261 094 (3) 282.0 265.2 677.8 273.2 291.1 656.6 261.9 317.7 629.4 242.5 352.8 582.8 219.3 370.2 527.1
271 094 (3) 295.3 286.3 709.7 285.6 314.0 686.6 272.4 341.5 654.8 254.4 391.2 611.4 218.3 391.3 524.7
076 084 (1) 85.7 78.3 206.1 79.8 82.2 192.0 73.8 86.8 177.6 67.3 91.5 161.9 59.9 96.9 144.2
086 084 (1) 94.2 90.3 226.7 87.0 94.6 209.3 80.2 99.9 192.9 72.5 104.9 174.5 62.1 109.8 149.3
096 094 (1) 104.0 101.2 250.3 96.9 106.9 233.0 89.4 112.4 215.1 81.6 119.1 196.2 65.7 120.5 158.1
106 074 (1) and 044 (1) 120.2 112.1 289.1 111.6 117.6 268.4 102.2 123.3 246.0 93.4 129.8 224.8 84.3 138.6 202.7
116 074 (1) and 054 (1) 128.3 122.4 308.7 119.9 129.1 288.5 111.1 136.2 267.2 101.5 143.3 244.3 90.0 152.0 216.5
126 074 (2) 142.7 131.1 343.4 133.7 138.2 321.6 124.2 146.2 298.7 112.9 153.4 271.5 101.2 162.6 243.5
136 074 (2) 152.7 147.0 367.3 143.0 154.6 344.1 132.7 162.6 319.2 121.7 172.1 292.8 99.3 174.3 238.8
60 146 084 (2) 170.9 155.2 411.1 160.6 163.2 386.4 149.8 172.1 360.4 136.9 180.2 329.3 124.7 191.6 300.0
161 084 (2) 170.2 161.2 409.3 164.1 176.1 394.8 156.2 192.5 375.8 147.3 226.2 354.4 122.2 218.1 294.0
171 084 (2) 182.8 178.4 439.8 176.4 194.5 424.4 168.1 212.5 404.3 157.0 258.0 377.7 130.6 239.0 314.1
186 084 (2) 196.9 203.3 473.7 188.2 219.8 452.6 177.3 239.3 426.6 166.2 289.1 399.7 125.5 261.5 302.0
206 084 (2) and 094 (1) 232.9 206.5 560.1 225.2 227.3 541.7 216.2 248.6 520.1 204.9 279.9 492.9 184.9 293.0 444.9
246 094 (3) 267.3 246.0 643.1 258.8 270.7 622.7 248.2 295.6 597.1 233.1 329.8 560.8 211.6 367.0 509.0
261 094 (3) 282.3 265.2 679.0 273.4 291.2 657.6 259.6 316.1 624.5 242.6 353.1 583.7 219.5 370.2 527.9
271 094 (3) 295.5 286.3 710.9 285.9 314.1 687.7 272.7 341.6 655.9 252.4 382.0 607.1 218.4 391.5 525.3

LEGEND
Cap. — Capacity, Tons of Refrigeration
kW — Compressor Motor Input Power at Rated Voltages
LCWT — Leaving Chilled-Water Temperature (F)

51
Performance data (cont)
COMBINATION RATINGS (cont)
50 Hz, SI

CONDENSER ENTERING AIR TEMPERATURE (C)


09DK
30 35 40 45 50
UNIT AIR-COOLED
LCWT Cooler Cooler Cooler Cooler Cooler
(C) SIZE CONDENSER
30HXA Input Flow Input Flow Input Flow Input Flow Input Flow
Cap. Cap. Cap. Cap. Cap.
Unit (Qty) kW Rate kW Rate kW Rate kW Rate kW Rate
(L/s) (L/s) (L/s) (L/s) (L/s)
076 084 (1) 233.3 67.8 9.9 217.4 71.4 9.3 199.8 75.2 8.5 182.1 80.2 7.8 167.5 86.7 7.1
086 084 (1) 256.1 78.0 10.9 238.1 82.2 10.1 218.8 87.1 9.3 200.2 93.2 8.5 183.4 100.2 7.8
096 094 (1) 285.3 88.0 12.2 265.5 92.5 11.3 244.3 98.4 10.4 224.3 105.2 9.6 205.6 112.7 8.8
106 074 (1) and 044 (1) 325.9 97.0 13.9 304.1 102.0 13.0 280.8 107.9 12.0 258.1 115.3 11.0 237.0 123.9 10.1
116 074 (1) and 054 (1) 350.4 106.2 14.9 326.5 111.9 13.9 301.7 118.6 12.9 277.5 127.1 11.8 254.3 136.1 10.8
126 074 (2) 385.3 113.4 16.4 360.0 119.6 15.3 333.1 126.5 14.2 306.7 135.5 13.1 282.1 145.3 12.0
136 074 (2) 416.0 127.7 17.7 388.8 134.1 16.6 360.3 142.2 15.3 333.2 152.1 14.2 307.1 162.4 13.1
4 146 084 (2) 460.8 134.6 19.6 432.1 141.5 18.4 401.7 148.9 17.1 371.0 159.3 15.8 342.9 170.7 14.6
161 084 (2) 481.6 145.8 20.5 460.8 158.0 19.6 439.6 171.5 18.7 417.6 186.6 17.8 394.8 204.7 16.8
171 084 (2) 515.7 160.1 22.0 492.8 173.4 21.0 470.4 187.9 20.0 447.3 204.6 19.1 423.6 225.0 18.0
186 084 (2) 555.7 181.1 23.7 526.6 195.6 22.4 504.7 211.9 21.5 477.4 231.0 20.3 449.9 252.6 19.2
206 084 (2) and 094 (1) 658.2 188.5 28.0 634.0 204.9 27.0 606.5 222.6 25.8 575.5 242.1 24.5 545.6 264.7 23.2
246 094 (3) 764.7 225.3 32.6 735.0 243.8 31.3 697.4 264.3 29.7 665.3 287.4 28.3 628.6 314.6 26.8
261 094 (3) 800.1 240.9 34.1 766.7 260.6 32.7 729.4 282.3 31.1 695.2 307.3 29.6 657.3 336.1 28.0
271 094 (3) 838.6 258.7 35.7 799.0 279.6 34.0 762.6 302.8 32.5 725.0 330.0 30.9 683.3 359.5 29.1
076 084 (1) 241.6 69.1 10.3 225.5 72.8 9.6 207.6 76.7 8.8 189.8 81.4 8.1 173.9 87.6 7.4
086 084 (1) 265.0 79.6 11.3 246.8 83.8 10.5 227.4 88.5 9.7 207.9 94.4 8.9 190.3 101.3 8.1
096 094 (1) 295.6 89.6 12.6 275.2 94.3 11.7 253.6 100.1 10.8 232.7 106.7 9.9 213.0 114.2 9.1
106 074 (1) and 044 (1) 337.4 98.8 14.4 315.4 104.0 13.4 291.7 109.6 12.4 267.9 116.9 11.4 246.2 125.3 10.5
116 074 (1) and 054 (1) 362.4 108.3 15.4 338.4 114.0 14.4 313.1 120.3 13.3 287.8 128.6 12.3 264.3 137.7 11.3
126 074 (2) 398.6 115.5 17.0 373.4 121.8 15.9 346.0 128.3 14.7 318.2 137.1 13.6 292.5 147.1 12.5
136 074 (2) 430.8 130.0 18.4 403.3 136.3 17.2 373.7 144.4 15.9 345.7 154.1 14.7 318.4 164.6 13.6
5 146 084 (2) 476.7 137.0 20.3 448.3 144.0 19.1 417.0 151.2 17.8 384.8 161.3 16.4 355.6 172.8 15.2
161 084 (2) 496.4 147.8 21.2 475.6 160.4 20.3 453.8 173.9 19.3 430.8 189.2 18.4 407.4 206.6 17.4
171 084 (2) 531.8 162.5 22.7 508.7 175.7 21.7 485.6 190.3 20.7 461.6 207.0 19.7 436.8 226.9 18.6
186 084 (2) 574.1 183.7 24.5 543.9 198.7 23.2 520.9 214.8 22.2 493.0 234.1 21.0 463.7 255.1 19.8
206 084 (2) and 094 (1) 677.7 191.2 28.9 654.0 207.7 27.9 626.7 225.5 26.7 594.2 245.3 25.3 563.2 267.3 24.0
246 094 (3) 787.3 228.4 33.6 759.2 247.1 32.4 720.4 268.1 30.7 686.6 291.0 29.3 649.2 318.2 27.7
261 094 (3) 823.8 244.3 35.1 792.9 264.1 33.8 751.8 286.2 32.0 717.6 310.8 30.6 678.6 340.2 28.9
271 094 (3) 863.3 262.7 36.8 826.2 283.7 35.2 785.5 307.1 33.5 748.5 334.0 31.9 705.6 364.2 30.1
076 084 (1) 250.3 70.3 10.7 233.6 74.2 10.0 215.8 78.1 9.2 197.2 82.7 8.4 180.1 88.6 7.7
086 084 (1) 274.2 81.1 11.7 255.7 85.4 10.9 236.0 90.0 10.1 216.1 95.7 9.2 196.9 102.6 8.4
096 094 (1) 305.8 91.4 13.0 284.8 96.2 12.1 263.2 101.8 11.2 241.7 108.1 10.3 220.9 115.5 9.4
106 074 (1) and 044 (1) 349.2 100.6 14.9 326.9 105.9 13.9 302.7 111.4 12.9 278.1 118.5 11.9 255.0 126.9 10.9
116 074 (1) and 054 (1) 374.7 110.3 16.0 350.9 116.1 15.0 324.9 122.1 13.9 298.0 130.3 12.7 273.7 139.5 11.7
126 074 (2) 412.2 117.6 17.6 387.0 124.0 16.5 358.9 130.4 15.3 330.1 139.0 14.1 303.4 148.8 12.9
136 074 (2) 445.7 132.4 19.0 417.5 139.0 17.8 387.7 146.8 16.5 358.3 156.2 15.3 330.0 166.7 14.1
6 146 084 (2) 493.3 139.4 21.0 464.6 146.5 19.8 432.5 153.8 18.4 399.5 163.6 17.0 368.8 174.9 15.7
161 084 (2) 510.8 150.1 21.8 490.6 162.7 20.9 468.1 176.4 20.0 444.7 191.7 19.0 420.2 209.2 17.9
171 084 (2) 547.8 164.7 23.4 525.6 178.4 22.4 500.2 193.3 21.3 475.9 209.6 20.3 450.4 229.1 19.2
186 084 (2) 591.1 186.9 25.2 561.9 201.9 24.0 536.1 218.4 22.9 508.8 237.4 21.7 478.8 258.0 20.4
206 084 (2) and 094 (1) 697.8 193.9 29.8 674.3 210.4 28.8 647.5 228.5 27.6 613.6 248.4 26.2 581.5 270.0 24.8
246 094 (3) 809.9 231.7 34.5 782.6 250.8 33.4 744.2 271.8 31.7 708.0 295.0 30.2 670.2 322.0 28.6
261 094 (3) 848.0 247.7 36.2 819.2 267.7 34.9 775.7 290.4 33.1 740.5 314.6 31.6 700.4 344.2 29.9
271 094 (3) 888.3 266.7 37.9 853.6 287.7 36.4 808.8 311.5 34.5 772.6 338.1 32.9 728.4 369.0 31.1

LEGEND
Cap. — Capacity, kW
kW — Compressor Motor Input Power at Rated Voltages
LCWT — Leaving Chilled-Water Temperature (C)

52
COMBINATION RATINGS (cont)
50 Hz, SI (cont)

CONDENSER ENTERING AIR TEMPERATURE (C)


09DK
30 35 40 45 50
UNIT AIR-COOLED
LCWT Cooler Cooler Cooler Cooler Cooler
(C) SIZE CONDENSER
30HXA Input Flow Input Flow Input Flow Input Flow Input Flow
Cap. Cap. Cap. Cap. Cap.
Unit (Qty) kW Rate kW Rate kW Rate kW Rate kW Rate
(L/s) (L/s) (L/s) (L/s) (L/s)
076 084 (1) 258.9 71.9 11.0 241.9 75.7 10.3 224.0 79.6 9.6 205.4 83.8 8.8 186.6 89.5 8.0
086 084 (1) 283.3 82.8 12.1 264.6 87.1 11.3 244.8 91.5 10.4 224.1 97.1 9.6 204.3 103.7 8.7
096 094 (1) 316.1 93.3 13.5 294.8 98.1 12.6 273.4 103.3 11.7 250.8 109.6 10.7 228.7 116.9 9.8
106 074 (1) and 044 (1) 361.1 102.6 15.4 338.4 108.0 14.4 314.0 113.4 13.4 288.5 120.3 12.3 264.2 128.4 11.3
116 074 (1) and 054 (1) 387.5 112.4 16.5 363.3 118.2 15.5 336.6 124.3 14.4 309.1 132.3 13.2 283.5 141.3 12.1
126 074 (2) 426.5 119.8 18.2 400.5 126.3 17.1 372.0 132.9 15.9 342.8 141.0 14.6 314.5 150.7 13.4
136 074 (2) 460.7 135.0 19.7 432.1 141.8 18.4 402.0 149.3 17.2 371.5 158.3 15.9 341.9 168.7 14.6
7 146 084 (2) 510.3 141.9 21.8 480.8 149.2 20.5 448.7 156.6 19.1 415.0 165.7 17.7 382.5 176.9 16.3
161 084 (2) 525.4 152.5 22.4 505.9 165.0 21.6 482.7 178.9 20.6 458.7 194.3 19.6 433.5 211.7 18.5
171 084 (2) 563.5 167.3 24.0 542.0 181.2 23.1 515.9 196.3 22.0 490.9 212.5 20.9 464.2 232.0 19.8
186 084 (2) 607.7 190.2 25.9 580.5 205.0 24.8 551.8 221.6 23.5 525.1 240.6 22.4 493.9 261.9 21.1
206 084 (2) and 094 (1) 718.2 196.5 30.6 695.3 213.1 29.7 667.8 231.3 28.5 634.1 251.6 27.1 600.1 273.4 25.6
246 094 (3) 833.1 234.9 35.6 806.5 254.3 34.4 768.3 275.5 32.8 730.0 298.8 31.2 691.8 325.7 29.5
261 094 (3) 872.4 251.2 37.2 844.0 271.8 36.0 800.9 294.6 34.2 763.3 319.1 32.6 722.6 348.3 30.8
271 094 (3) 914.2 270.6 39.0 881.7 291.8 37.6 833.0 315.8 35.5 796.9 342.5 34.0 751.4 374.0 32.1
076 084 (1) 267.6 73.5 11.4 250.8 77.1 10.7 232.5 81.0 9.9 213.0 85.0 9.1 193.5 90.6 8.3
086 084 (1) 292.9 84.4 12.5 273.9 88.7 11.7 253.4 93.1 10.8 232.2 98.6 9.9 211.6 105.0 9.0
096 094 (1) 326.6 95.3 13.9 305.4 100.0 13.0 283.0 105.1 12.1 259.6 111.3 11.1 237.2 118.5 10.1
106 074 (1) and 044 (1) 373.0 104.7 15.9 350.2 110.0 15.0 325.4 115.6 13.9 299.5 122.0 12.8 273.7 130.0 11.7
116 074 (1) and 054 (1) 400.4 114.5 17.1 375.9 120.5 16.0 348.6 126.7 14.9 321.2 134.1 13.7 293.9 143.0 12.5
126 074 (2) 440.6 122.1 18.8 414.3 128.6 17.7 385.7 135.3 16.5 355.5 143.0 15.2 325.8 152.5 13.9
136 074 (2) 475.8 137.8 20.3 446.9 144.5 19.1 416.4 151.7 17.8 384.7 160.4 16.4 354.0 170.9 15.1
8 146 084 (2) 527.3 144.6 22.5 497.2 152.0 21.2 464.9 159.5 19.8 430.3 168.2 18.4 396.2 179.1 16.9
161 084 (2) 540.3 154.8 23.1 521.2 167.4 22.3 497.6 181.2 21.2 472.8 196.9 20.2 442.7 213.3 18.9
171 084 (2) 579.4 170.0 24.7 558.6 183.8 23.8 531.9 199.1 22.7 505.7 215.8 21.6 478.5 234.8 20.4
186 084 (2) 625.1 193.2 26.7 598.8 208.3 25.6 567.5 224.9 24.2 541.3 243.9 23.1 505.0 264.7 21.6
206 084 (2) and 094 (1) 739.2 198.9 31.6 716.4 215.9 30.6 687.5 234.4 29.4 655.1 254.9 28.0 619.1 277.1 26.4
246 094 (3) 856.8 238.0 36.6 830.8 257.8 35.5 793.9 279.1 33.9 751.9 302.9 32.1 713.8 329.5 30.5
261 094 (3) 896.9 254.8 38.3 869.0 275.8 37.1 827.4 298.8 35.3 786.1 323.8 33.6 745.5 352.4 31.8
271 094 (3) 940.5 274.4 40.2 908.6 296.4 38.8 860.1 320.7 36.7 820.0 347.6 35.0 775.3 378.8 33.1
076 084 (1) 276.7 75.0 11.8 259.2 78.6 11.1 241.1 82.5 10.3 221.2 86.6 9.4 201.1 92.0 8.6
086 084 (1) 302.6 86.1 12.9 283.3 90.4 12.1 262.6 94.9 11.2 240.9 100.1 10.3 219.4 106.5 9.4
096 094 (1) 337.5 97.2 14.4 315.5 102.0 13.5 292.9 106.9 12.5 269.0 113.2 11.5 240.6 119.0 10.3
106 074 (1) and 044 (1) 385.5 106.6 16.5 362.1 112.2 15.5 337.2 117.7 14.4 310.5 123.9 13.3 283.8 131.8 12.1
116 074 (1) and 054 (1) 413.6 116.5 17.7 388.4 122.9 16.6 360.9 129.1 15.4 332.4 136.1 14.2 304.0 144.9 13.0
126 074 (2) 455.2 124.5 19.4 428.3 131.1 18.3 399.5 137.8 17.1 368.7 145.0 15.7 337.6 154.5 14.4
136 074 (2) 491.5 140.6 21.0 462.3 147.2 19.7 431.1 154.2 18.4 398.0 162.9 17.0 358.8 171.6 15.3
9 146 084 (2) 544.7 147.5 23.3 514.2 154.8 22.0 481.7 162.4 20.6 446.5 170.6 19.1 410.4 181.4 17.5
161 084 (2) 555.6 156.9 23.7 536.9 169.6 22.9 512.5 183.7 21.9 487.3 199.7 20.8 447.6 214.1 19.1
171 084 (2) 595.7 172.6 25.4 575.1 186.6 24.6 548.0 201.9 23.4 521.2 218.7 22.3 488.6 236.7 20.9
186 084 (2) 642.6 196.3 27.4 617.7 211.5 26.4 583.4 228.2 24.9 557.5 247.2 23.8 503.5 264.3 21.5
206 084 (2) and 094 (1) 760.5 201.4 32.5 737.3 219.0 31.5 708.1 237.8 30.2 675.9 258.3 28.9 638.1 280.8 27.3
246 094 (3) 880.7 241.1 37.6 854.4 261.5 36.5 819.9 283.0 35.0 774.6 307.3 33.1 735.3 333.4 31.4
261 094 (3) 921.6 258.5 39.4 893.4 280.1 38.2 854.2 303.1 36.5 808.6 328.5 34.5 767.8 356.3 32.8
271 094 (3) 966.2 278.5 41.3 934.2 301.2 39.9 888.1 325.5 37.9 843.0 352.7 36.0 798.1 383.2 34.1

LEGEND
Cap. — Capacity, kW
kW — Compressor Motor Input Power at Rated Voltages
LCWT — Leaving Chilled-Water Temperature (C)

53
Performance data (cont)
COMBINATION RATINGS (cont)
50 Hz, SI (cont)

CONDENSER ENTERING AIR TEMPERATURE (C)


09DK
30 35 40 45 50
UNIT AIR-COOLED
LCWT Cooler Cooler Cooler Cooler Cooler
(C) SIZE CONDENSER
30HXA Input Flow Input Flow Input Flow Input Flow Input Flow
Cap. Cap. Cap. Cap. Cap.
Unit (Qty) kW Rate kW Rate kW Rate kW Rate kW Rate
(L/s) (L/s) (L/s) (L/s) (L/s)
076 084 (1) 285.8 76.5 12.2 268.1 80.1 11.5 249.4 84.1 10.7 229.2 88.2 9.8 208.7 93.4 8.9
086 084 (1) 312.4 87.8 13.3 292.3 92.2 12.5 271.8 96.7 11.6 249.6 101.8 10.7 227.3 108.0 9.7
096 094 (1) 348.1 99.1 14.9 326.1 103.9 13.9 302.8 109.0 12.9 278.6 115.0 11.9 244.1 119.6 10.4
106 074 (1) and 044 (1) 398.1 108.8 17.0 374.1 114.3 16.0 348.6 120.0 14.9 321.7 125.9 13.7 294.0 133.6 12.6
116 074 (1) and 054 (1) 426.8 119.0 18.2 401.2 125.3 17.1 373.6 131.5 16.0 344.5 138.1 14.7 315.1 146.8 13.5
126 074 (2) 469.9 127.1 20.1 442.5 133.5 18.9 413.4 140.4 17.7 381.8 147.4 16.3 349.9 156.6 15.0
136 074 (2) 507.2 143.4 21.7 477.6 150.0 20.4 445.8 157.0 19.1 412.4 165.6 17.6 363.9 172.4 15.6
10 146 084 (2) 562.5 150.5 24.0 531.5 157.6 22.7 498.5 165.4 21.3 462.4 173.3 19.8 425.5 183.8 18.2
161 084 (2) 570.9 159.2 24.4 552.6 172.0 23.6 527.5 186.7 22.5 501.8 202.6 21.4 452.7 215.0 19.3
171 084 (2) 612.1 175.2 26.2 591.8 189.3 25.3 564.5 205.0 24.1 536.0 222.0 22.9 494.8 237.5 21.1
186 084 (2) 660.2 199.5 28.2 636.5 214.7 27.2 601.1 232.1 25.7 572.7 251.2 24.5 502.0 263.9 21.5
206 084 (2) and 094 (1) 781.9 204.2 33.4 758.1 222.1 32.4 729.3 240.9 31.2 697.0 261.8 29.8 657.5 284.3 28.1
246 094 (3) 904.6 244.2 38.7 878.4 265.2 37.5 843.8 287.4 36.1 798.8 311.6 34.1 756.7 337.9 32.3
261 094 (3) 946.5 262.1 40.4 918.3 284.2 39.2 881.3 307.5 37.7 831.8 333.2 35.5 790.5 360.6 33.8
271 094 (3) 991.6 282.7 42.4 960.3 305.9 41.0 916.2 330.5 39.2 866.3 357.8 37.0 822.1 388.0 35.1
076 084 (1) 301.0 79.0 12.9 282.8 82.5 12.1 258.8 85.8 11.1 238.6 89.9 10.2 217.2 94.8 9.3
086 084 (1) 325.8 90.1 13.9 305.6 94.5 13.1 284.2 99.2 12.2 261.4 104.1 11.2 238.4 110.1 10.2
096 094 (1) 365.6 102.2 15.6 342.9 107.3 14.7 319.1 112.3 13.7 291.3 117.4 12.5 250.7 120.7 10.7
106 074 (1) and 044 (1) 415.1 111.9 17.8 390.6 117.3 16.7 364.7 123.1 15.6 337.4 128.8 14.4 308.4 136.2 13.2
116 074 (1) and 054 (1) 448.1 122.9 19.2 421.4 129.0 18.0 393.6 135.4 16.8 363.7 141.8 15.6 332.8 150.1 14.2
126 074 (2) 501.9 132.3 21.5 469.3 138.1 20.1 439.6 145.2 18.8 403.2 151.3 17.2 369.9 159.8 15.8
136 074 (2) 536.7 148.3 23.0 506.2 155.2 21.7 473.1 162.5 20.2 439.0 170.7 18.8 377.1 174.4 16.1
13 146 084 (2) 601.1 156.5 25.7 563.7 163.0 24.1 530.0 171.0 22.7 493.3 179.1 21.1 450.1 187.5 19.3
161 084 (2) 595.9 162.6 25.5 576.5 176.2 24.7 552.0 190.8 23.6 523.4 222.3 22.4 461.5 216.8 19.7
171 084 (2) 644.1 180.5 27.6 623.5 195.1 26.7 598.2 211.2 25.6 560.7 231.8 24.0 502.2 239.1 21.5
186 084 (2) 689.4 204.5 29.5 665.0 220.6 28.4 631.1 238.2 27.0 593.9 286.1 25.4 501.6 263.8 21.5
206 084 (2) and 094 (1) 813.4 208.5 34.8 784.4 226.3 33.6 756.6 245.1 32.4 722.8 267.0 30.9 678.2 288.2 29.0
246 094 (3) 942.1 249.0 40.3 915.2 271.4 39.2 882.0 293.9 37.7 831.4 318.3 35.6 780.6 355.4 33.4
261 094 (3) 980.7 266.7 42.0 952.7 289.6 40.8 917.2 313.5 39.2 866.0 340.5 37.0 814.5 386.4 34.8
271 094 (3) 1027.0 287.8 43.9 996.0 312.4 42.6 955.0 336.8 40.9 898.5 365.5 38.4 841.9 392.4 36.0
076 084 (1) 298.2 78.5 12.8 279.8 82.0 12.0 260.8 86.2 11.2 240.6 90.3 10.3 219.1 95.1 9.4
086 084 (1) 328.3 90.6 14.1 307.8 95.0 13.2 283.8 99.1 12.2 261.4 104.0 11.2 238.4 109.9 10.2
096 094 (1) 362.2 101.6 15.5 339.9 106.6 14.6 316.0 111.7 13.5 291.6 117.4 12.5 250.5 120.5 10.7
106 074 (1) and 044 (1) 418.6 112.4 17.9 393.6 117.8 16.9 367.9 123.7 15.8 333.4 128.1 14.3 305.4 135.5 13.1
116 074 (1) and 054 (1) 451.6 123.6 19.3 420.5 128.8 18.0 392.7 135.2 16.8 362.3 141.6 15.5 331.8 150.0 14.2
126 074 (2) 497.5 131.5 21.3 468.7 137.9 20.1 438.7 145.0 18.8 406.6 152.0 17.4 373.0 160.5 16.0
136 074 (2) 532.0 147.5 22.8 501.6 154.2 21.5 468.9 161.5 20.1 434.5 169.8 18.6 376.2 174.3 16.1
16 146 084 (2) 595.7 155.6 25.5 563.0 162.9 24.1 529.4 170.8 22.7 492.5 178.9 21.1 453.9 188.2 19.4
161 084 (2) 599.7 163.3 25.7 580.4 176.8 24.9 550.9 190.5 23.6 524.0 213.0 22.4 465.0 217.4 19.9
171 084 (2) 639.3 179.7 27.4 618.9 194.1 26.5 593.2 210.2 25.4 559.5 238.2 24.0 501.9 239.0 21.5
186 084 (2) 689.0 204.6 29.5 664.8 220.5 28.5 631.1 238.0 27.0 591.7 267.0 25.3 501.1 263.7 21.5
206 084 (2) and 094 (1) 814.0 208.4 34.9 789.7 227.0 33.8 761.8 245.9 32.6 728.2 267.2 31.2 683.3 289.5 29.3
246 094 (3) 943.4 249.0 40.4 907.8 270.3 38.9 874.6 292.6 37.4 828.4 317.9 35.5 778.9 350.0 33.3
261 094 (3) 987.1 267.6 42.3 958.9 290.7 41.1 923.5 314.6 39.5 862.8 339.7 36.9 813.5 374.1 34.8
271 094 (3) 1033.6 288.8 44.3 1002.6 313.6 42.9 962.2 338.0 41.2 905.2 366.1 38.8 — — —

LEGEND
Cap. — Capacity, kW
kW — Compressor Motor Input Power at Rated Voltages
LCWT — Leaving Chilled-Water Temperature (C)

54
COOLER PRESSURE DROP

ENGLISH
100

136, 146
116, 126 161, 171
076, 086 106
186
096
206
246-271
PRESSURE DROP (FT WG)

10

1
100 1000
COOLER FLOW RATE (GPM)

— Unit size range


NOTE: Ft of water = 2.31 x change in psig.

SI
1000

136, 146
116, 126
106 161, 171
076, 086 096 186
100
PRESSURE DROP (KPA)

206
246-271

10

1
1 10 100
COOLER FLOW RATE (L/S)

— Unit size range

55
Performance data (cont)
30HXC CONDENSER PRESSURE DROP

ENGLISH

— Unit size range


NOTE: Ft of water = 2.31 x change in psig.

SI

— Unit size range

56
TO EXPANSION FD
TANK FD
FROM FD
COOLING FD FIELD
TOWER CHILLED WATER POWER
FIELD-SUPPLIED PUMP POWER SUPPLY
SHUT-OFF VALVE FIELD SUPPLIED
TO COOLING SHUT-OFF VALVE ST ST
TOWER ST
STRAINER*

FAN
MOTOR
POWER

SEE BASE UNIT


INSTALLATION
INSTRUCTIONS
FOR CONNECTION
TYPE
FIELD-
SUPPLIED
Typical piping and wiring

SHUT-OFF CHILLED TER PUM P


VALVES WATER PUMP

FROM ADDITIONAL
AIR HANDLING UNITS
STRAINER*
Cooler (30HXA, HXC) and condenser (30HXC only)

CONDENSER
WA TO ADDITIONAL
AIR HANDLING UNITS

AIR HANDLING
UNIT

30HXC
CHILLER

LEGEND NOTES:
1. Chiller must be installed levelly to maintain proper compressor oil return.
Airflow Through Air-Handling Unit 2. Wiring and piping shown are general points-of-connection guides only and are not intended for a specific installation.
Wiring and piping shown are for a quick overview of system and are not in accordance with recognized standards.
Power Wiring 3. All wiring must comply with applicable local and national codes.
4. All piping must follow standard piping techniques. Refer to Carrier System Design Manual or appropriate ASHRAE
Chilled Fluid Wiring (American Society of Heating, Refrigeration, and Air Conditioning Engineers) handbook for details.
ST — Starter 5. See Application Data section on page 20 for minimum cooler loop volume. This system may require the addition of a
FD — Field-Supplied Disconnect holding tank to ensure adequate volume.
* Field Supplied.

57
58
POWER AND CONTROL WIRING

NOTES:
Typical piping and wiring (cont)

LEGEND

A — Alarm LLSV — Liquid Line Solenoid Valve


CCN — Carrier Comfort Network LWT — Leaving Water Temperature
CFR — Condenser Fan Relay NEC — National Electrical Code
CNFS — Condenser Flow Switch OAT — Outdoor Air Temperature
CNPI — Condenser Pump Interlock SPT — Space Temperature
CNPR — Condenser Water Pump TB — Terminal Block
CWFS — Chilled Water Flow Switch ——— Factory Installed Wiring
CWP — Chilled Water Pump –—– Field Control Wiring
CWPI — Chilled Water Pump Interlock –––– Field Power Wiring
Electrical data
COMPRESSOR ELECTRICAL DATA, 30HXC UNITS

NAMEPLATE COMPRESSOR NUMBERS


UNIT SIZE 30HXC V-Hz A1 B1
(3 Phase) RLA LRA RLA LRA
208/230-60 * * * *
230-60 * * * *
460-60 44.3 330 44.3 330
076-XL 575-60 35.4 264 35.4 264
380-60 53.7 365 53.7 365
230-50 * * * *
380/415-50 55.8 344 55.8 344
208/230-60 98.1 209 98.1 209
230-60 88.3 209 88.3 209
460-60 44.3 104 44.3 104
076-WD 575-60 35.4 83 35.4 83
380-60 53.7 115 53.7 115
230-50 92.1 174 92.1 174
380/415-50 55.8 109 55.8 109
208/230-60 * * * *
230-60 * * * *
460-60 53.6 330 44.3 330
086-XL 575-60 42.8 264 35.4 264
380-60 64.9 365 53.7 365
230-50 * * * *
380/415-50 67.7 423 55.8 344
208/230-60 118.6 209 98.1 209
230-60 106.7 209 88.3 209
460-60 53.6 104 44.3 104
086-WD 575-60 42.8 83 35.4 83
380-60 64.9 115 53.7 115
230-50 111.8 213 92.1 174
380/415-50 67.7 134 55.8 109
208/230-60 * * * *
230-60 * * * *
460-60 65.5 405 44.3 330
096-XL 575-60 52.3 324 35.4 264
380-60 79.2 448 53.7 365
230-50 * * * *
380/415-50 81.7 506 55.8 344
208/230-60 144.9 256 98.1 209
230-60 130.4 256 88.3 209
460-60 65.5 128 44.3 104
096-WD 575-60 52.3 102 35.4 83
380-60 79.2 141 53.7 115
230-50 134.9 255 92.1 174
380/415-50 81.7 160 55.8 109
208/230-60 * * * *
230-60 * * * *
460-60 79.2 485 44.3 330
106-XL 575-60 63.3 388 35.4 264
380-60 95.9 536 53.7 365
230-50 * * * *
380/415-50 97.8 605 55.8 344
208/230-60 175.4 307 98.1 209
230-60 157.9 307 88.3 209
460-60 79.2 153 44.3 104
106-WD 575-60 63.3 123 35.4 83
380-60 95.9 169 53.7 115
230-50 161.7 305 92.1 174
380/415-50 97.8 191 55.8 109
LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD — Wye-Delta Start
XL — Across-the-Line Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

59
Electrical data (cont)
COMPRESSOR ELECTRICAL DATA, 30HXC UNITS (cont)

NAMEPLATE COMPRESSOR NUMBERS


UNIT SIZE 30HXC V-Hz A1 B1
(3 Phase) RLA LRA RLA LRA
208/230-60 * * * *
230-60 * * * *
460-60 79.2 485 53.6 330
116-XL 575-60 63.3 388 42.8 264
380-60 95.9 536 64.9 365
230-50 * * * *
380/415-50 87.8 605 67.7 423
208/230-60 175.4 307 118.6 209
230-60 157.9 307 106.7 209
460-60 79.2 153 53.6 104
116-WD 575-60 63.3 123 42.8 83
380-60 95.5 169 64.9 115
230-50 161.7 305 111.8 213
380/415-50 97.8 191 67.7 134
208/230-60 * * * *
230-60 * * * *
460-60 79.2 485 65.5 405
126-XL 575-60 63.3 388 42.3 324
380-60 95.9 536 79.2 448
230-50 * * * *
380/415-50 97.8 605 81.7 506
208/230-60 175.4 307 144.9 256
230-60 157.9 307 130.4 256
460-60 79.2 153 65.5 128
126-WD 575-60 63.3 123 52.3 102
380-60 95.9 169 79.2 141
230-50 161.7 305 134.9 255
380/415-50 97.8 191 81.7 160
208/230-60 * * * *
230-60 * * * *
460-60 94.9 580 65.5 405
136-XL 575-60 75.8 484 52.3 324
380-60 114.9 641 79.2 448
230-50 * * * *
380/415-50 118.8 715 81.7 506
208/230-60 210.0 367 144.9 256
230-60 189.0 367 130.4 256
460-60 94.6 183 65.5 128
136-WD 575-60 75.8 147 52.3 102
380-60 114.9 203 79.2 141
230-50 196.3 361 134.9 255
380/415-50 118.8 226 81.7 160
208/230-60 * * * *
230-60 * * * *
460-60 94.9 580 79.2 485
146-XL 575-60 75.8 484 63.3 388
380-60 114.9 641 95.9 536
230-50 * * * *
380/415-50 118.8 715 97.8 605
208/230-60 210.0 367 175.4 307
230-60 189.0 367 157.9 307
460-60 94.9 183 79.2 153
146-WD 575-60 75.8 147 63.3 123
380-60 114.9 203 95.9 169
230-50 196.3 361 161.7 305
380/415-50 118.8 226 97.8 191
LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD — Wye-Delta Start
XL — Across-the-Line Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

60
COMPRESSOR ELECTRICAL DATA, 30HXC UNITS (cont)

NAMEPLATE COMPRESSOR NUMBERS


UNIT SIZE 30HXC V-Hz A1 B1
(3 Phase) RLA LRA RLA LRA
208/230-60 * * * *
230-60 * * * *
460-60 103.1 685 71.2 525
161-XL 575-60 82.4 548 56.9 420
380-60 124.8 757 86.2 580
230-50 * * * *
380/415-50 128.6 856 88.2 600
208/230-60 228.8 433 157.6 350
230-60 205.5 433 141.8 350
460-60 103.1 216 71.2 175
161-WD 575-60 82.4 173 56.9 140
380-60 124.8 239 86.2 193
230-50 212.5 432 145.7 348
380/415-50 128.6 270 88.2 200
208/230-60 * * * *
230-60 * * * *
460-60 86.1 580 103.1 685
171-XL 575-60 68.8 484 82.4 548
380-60 104.2 641 124.8 757
230-50 * * * *
380/415-50 105.8 715 128.6 856
208/230-60 190.6 367 228.8 433
230-60 171.5 367 205.5 433
460-60 86.1 183 103.1 216
171-WD 575-60 68.8 147 82.4 173
380-60 104.2 203 124.8 239
230-50 174.8 361 212.5 432
380/415-50 105.8 233 128.6 270
208/230-60 * * * *
230-60 * * * *
460-60 103.1 685 103.1 685
186-XL 575-60 82.4 548 82.4 548
380-60 124.8 757 124.8 757
230-50 * * * *
380/415-50 128.6 856 128.6 856
208/230-60 228.8 433 228.8 433
230-60 205.5 433 205.5 433
460-60 103.1 216 103.1 216
186-WD 575-60 82.4 173 82.4 173
380-60 124.8 239 124.8 239
230-50 212.5 432 212.5 432
380/415-50 128.6 270 128.6 270
LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD — Wye-Delta Start
XL — Across-the-Line Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

61
Electrical data (cont)
COMPRESSOR ELECTRICAL DATA, 30HXC UNITS (cont)

NAMEPLATE COMPRESSOR NUMBERS


UNIT SIZE
V-Hz A1 A2 B1
30HXC
(3 Phase) RLA LRA RLA LRA RLA LRA
208/230-60 * * * * * *
230-60 * * * * * *
460-60 86.1 580 44.3 330 103.1 685
206-XL 575-60 68.8 484 35.4 264 82.4 548
380-60 104.2 641 53.7 365 124.8 757
230-50 * * * * * *
380/415-50 105.8 715 55.8 344 128.6 856
208/230-60 190.6 367 98.1 209 228.8 433
230-60 171.5 367 205.5 433 96.1 233
460-60 86.1 183 44.3 104 103.1 216
206-WD 575-60 68.8 147 35.4 83 82.4 173
380-60 104.2 203 53.7 115 124.8 239
230-50 174.8 361 92.1 174 212.5 432
380/415-50 105.8 233 55.8 109 128.6 270
208/230-60 * * * * * *
230-60 * * * * * *
460-60 103.1 685 71.2 525 103.1 685
246-XL 575-60 82.4 548 56.9 420 82.4 548
380-60 124.8 757 86.2 580 124.8 757
230-50 * * * * * *
380/415-50 128.6 856 88.2 600 128.6 856
208/230-60 228.8 433 157.6 350 228.8 433
230-60 205.5 433 205.5 433 141.8 307
460-60 103.1 216 71.2 175 103.1 216
246-WD 575-60 82.4 173 56.9 140 82.4 173
380-60 124.8 239 86.2 193 124.8 239
230-50 212.5 432 145.7 348 212.5 432
380/415-50 128.6 270 88.2 200 128.6 270
208/230-60 * * * * * *
230-60 * * * * * *
460-60 103.1 685 86.1 580 103.1 685
261-XL 575-60 82.4 548 68.8 484 82.4 548
380-60 124.8 757 104.2 641 124.8 757
230-50 * * * * * *
380/415-50 128.6 856 105.8 715 128.6 856
208/230-60 228.8 433 190.6 367 228.8 433
230-60 205.5 433 205.5 433 171.5 367
460-60 103.1 216 86.1 183 103.1 216
261-WD 575-60 82.4 173 68.8 147 82.4 173
380-60 124.8 239 104.2 203 124.8 239
230-50 212.5 432 174.8 361 212.5 432
380/415-50 128.6 270 105.8 233 128.6 270
208/230-60 * * * * * *
230-60 * * * * * *
460-60 103.1 685 103.1 685 103.1 685
271-XL 575-60 82.4 548 82.4 548 82.4 548
380-60 124.8 757 124.8 757 124.8 757
230-50 * * * * * *
380/415-50 128.6 856 128.6 856 128.6 856
208/230-60 228.8 433 228.8 433 228.8 433
230-60 205.5 433 205.5 433 205.5 433
460-60 103.1 216 103.1 216 103.1 216
271-WD 575-60 82.4 173 82.4 173 82.4 173
380-60 124.8 239 124.8 239 124.8 239
230-50 212.5 432 212.5 432 212.5 432
380/415-50 128.6 270 128.6 270 128.6 270
LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD — Wye-Delta Start
XL — Across-the-Line Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

62
COMPRESSOR ELECTRICAL DATA, 30HXA UNITS

NAMEPLATE COMPRESSOR NUMBERS


UNIT SIZE 30HXA V-Hz A1 B1
(3 Phase) RLA LRA RLA LRA
208/230-60 * * * *
230-60 * * * *
460-60 64.9 485 64.9 485
076-XL 575-60 51.9 388 51.9 388
380-60 78.7 536 78.7 536
230-50 * * * *
380/415-50 81.5 605 81.5 605
208/230-60 143.8 307 143.8 307
230-60 129.4 307 129.4 307
460-60 64.9 153 64.9 153
076-WD 575-60 51.9 123 51.9 123
380-60 78.7 169 78.7 169
230-50 134.8 305 134.8 305
380/415-50 81.5 191 81.5 191
208/230-60 * * * *
230-60 * * * *
460-60 77.6 580 64.9 485
086-XL 575-60 62.1 484 51.9 388
380-60 94.0 641 78.7 536
230-50 * * * *
380/415-50 99.2 715 81.5 605
208/230-60 171.9 367 143.8 307
230-60 154.7 367 129.4 307
460-60 77.6 183 64.9 153
086-WD 575-60 62.1 147 51.9 123
380-60 94.0 203 78.7 169
230-50 163.9 361 134.8 305
380/415-50 99.2 226 81.5 191
208/230-60 * * * *
230-60 * * * *
460-60 94.8 685 64.9 485
096-XL 575-60 75.7 548 51.9 388
380-60 114.7 757 78.7 536
230-50 * * * *
380/415-50 119.9 856 81.5 685
208/230-60 209.8 433 143.8 307
230-60 188.8 433 129.4 307
460-60 94.8 216 64.9 153
096-WD 575-60 75.5 173 51.9 123
380-60 114.7 239 78.7 169
230-50 198.2 432 134.8 305
380/415-50 119.9 270 81.5 191
208/230-60 * * * *
230-60 * * * *
460-60 115.4 820 64.9 485
106-XL 575-60 92.2 656 51.9 388
380-60 139.7 906 78.7 536
230-50 * * * *
380/415-50 145.4 960 81.5 605
208/230-60 255.5 518 143.8 307
230-60 230.0 518 129.4 307
460-60 115.4 259 64.9 153
106-WD 575-60 92.2 207 51.9 123
380-60 139.7 286 78.7 169
230-50 240.2 485 134.8 305
380/415-50 145.4 303 81.5 191
LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD — Wye-Delta Start
XL — Across-the-Line Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

63
Electrical data (cont)
COMPRESSOR ELECTRICAL DATA, 30HXA UNITS (cont)

NAMEPLATE COMPRESSOR NUMBERS


UNIT SIZE 30HXA V-Hz A1 B1
(3 Phase) RLA LRA RLA LRA
208/230-60 * * * *
230-60 * * * *
460-60 115.4 820 77.6 580
116-XL 575-60 92.2 656 62.1 484
380-60 139.7 906 94.0 641
230-50 * * * *
380/415-50 145.4 960 99.2 715
208/230-60 255.5 578 171.9 367
230-60 230.0 518 154.7 367
460-60 115.4 259 77.6 183
116-WD 575-60 92.2 207 62.1 147
380-60 139.7 286 94.0 203
230-50 240.2 485 163.9 361
380/415-50 145.4 303 99.2 226
208/230-60 * * * *
230-60 * * * *
460-60 115.4 820 94.8 685
126-XL 575-60 92.2 656 75.7 548
380-60 139.7 906 114.7 757
230-50 * * * *
380/415-50 145.4 960 119.9 856
208/230-60 255.5 518 209.8 447
230-60 230.0 518 188.8 433
460-60 115.4 259 94.8 216
126-WD 575-60 92.2 207 75.7 173
380-60 139.7 286 114.7 239
230-50 240.2 485 198.2 432
380/415-50 145.4 303 119.9 270
208/230-60 * * * *
230-60 * * * *
460-60 140.7 920 94.8 685
136-XL 575-60 112.4 736 75.7 548
380-60 170.2 1017 114.7 757
230-50 * * * *
380/415-50 178.8 1226 119.9 856
208/230-60 311.4 581 209.8 433
230-60 280.3 581 188.8 433
460-60 140.7 291 94.8 216
136-WD 575-60 112.4 233 75.7 173
380-60 170.2 321 114.7 239
230-50 295.3 619 198.2 432
380/415-50 178.8 387 119.9 276
208/230-60 * * * *
230-60 * * * *
460-60 140.7 920 115.4 820
146-XL 575-60 112.4 736 92.2 656
380-60 170.2 1017 139.7 906
230-50 * * * *
380/415-50 178.8 1226 145.4 960
208/230-60 311.4 581 255.5 518
230-60 280.3 581 230.0 518
460-60 140.7 291 115.4 259
146-WD 575-60 112.4 233 92.2 207
380-60 170.2 321 139.7 286
230-50 295.3 619 240.2 485
380/415-50 178.8 387 145.4 303
LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD — Wye-Delta Start
XL — Across-the-Line Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

64
COMPRESSOR ELECTRICAL DATA, 30HXA UNITS (cont)

NAMEPLATE COMPRESSOR NUMBERS


UNIT SIZE 30HXA V-Hz A1 B1
(3 Phase) RLA LRA RLA LRA
208/230-60 * * * *
230-60 * * * *
460-60 157.9 1175 106.6 790
161-XL 575-60 126.2 940 85.1 630
380-60 191.2 1299 129.0 870
230-50 * * * *
380/415-50 201.2 1265 133.4 1045
208/230-60 349.6 743 235.9 527
230-60 314.6 743 212.3 527
460-60 157.9 371 106.6 263
161-WD 575-60 126.2 297 85.1 211
380-60 191.2 410 129.0 290
230-50 332.3 638 220.3 607
380/415-50 201.2 400 133.4 348
208/230-60 * * * *
230-60 * * * *
460-60 129.6 920 157.9 1175
171-XL 575-60 103.6 736 126.2 940
380-60 156.9 1017 191.2 1299
230-50 * * * *
380/415-50 161.7 1226 201.2 1265
208/230-60 286.9 581 349.6 743
230-60 258.2 581 314.6 743
460-60 129.6 291 157.9 371
171-WD 575-60 103.6 233 126.2 297
380-60 156.9 321 191.2 410
230-50 267.2 619 332.3 638
380/415-50 161.7 387 201.2 400
208/230-60 * * * *
230-60 * * * *
460-60 157.9 1175 157.9 1175
186-XL 575-60 126.2 940 126.2 940
380-60 191.2 1299 191.2 1299
230-50 * * * *
380/415-50 201.2 1265 201.2 1265
208/230-60 349.6 743 349.6 743
230-60 314.6 743 314.6 743
460-60 157.9 371 157.9 371
186-WD 575-60 126.2 297 126.2 297
380-60 191.2 410 191.2 410
230-50 332.3 638 332.3 638
380/415-50 201.2 400 201.2 400
LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD — Wye-Delta Start
XL — Across-the-Line Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

65
Electrical data (cont)
COMPRESSOR ELECTRICAL DATA, 30HXA UNITS (cont)

NAMEPLATE COMPRESSOR NUMBERS


UNIT SIZE
V-Hz A1 A2 B1
30HXA
(3 Phase) RLA LRA RLA LRA RLA LRA
208/230-60 * * * * * *
230-60 * * * * * *
460-60 129.6 920 73.1 580 157.9 1175
206-XL 575-60 103.6 736 58.5 484 126.2 940
380-60 156.9 1017 88.5 641 191.2 1299
230-50 * * * * * *
380/415-50 161.7 1226 92.0 715 201.2 1265
208/230-60 286.9 581 162.0 367 349.6 743
230-60 258.2 581 303.8 743 145.8 367
460-60 129.6 291 73.1 183 157.9 371
206-WD 575-60 103.6 233 58.5 147 126.2 297
380-60 156.9 321 88.5 203 191.2 410
230-50 267.2 619 152.0 361 332.3 638
380/415-50 161.7 387 92.0 226 201.2 400
208/230-60 * * * * * *
230-60 * * * * * *
460-60 157.9 1175 106.6 820 157.9 1175
246-XL 575-60 126.2 940 85.1 656 126.2 940
380-60 191.2 1299 129.0 906 191.2 1299
230-50 * * * * * *
380/415-50 201.2 1265 133.4 960 201.2 1265
208/230-60 349.6 743 235.9 518 349.6 743
230-60 303.8 743 303.8 743 212.3 518
460-60 157.9 371 106.6 259 157.9 371
246-WD 575-60 126.2 297 85.1 207 126.2 297
380-60 191.2 410 129.0 286 191.2 410
230-50 332.3 638 220.3 485 332.3 638
380/415-50 201.2 400 133.4 303 201.2 400
208/230-60 * * * * * *
230-60 * * * * * *
460-60 157.9 1175 129.6 920 157.9 1175
261-XL 575-60 126.2 940 103.6 736 126.2 940
380-60 191.2 1299 156.9 1017 191.2 1299
230-50 * * * * * *
380/415-50 201.2 1265 161.7 1226 201.2 1265
208/230-60 349.6 743 286.9 581 349.6 743
230-60 303.8 743 303.8 743 258.2 581
460-60 157.9 371 129.6 291 157.9 371
261-WD 575-60 126.2 297 103.6 233 126.2 297
380-60 191.2 410 156.9 321 191.2 410
230-50 332.3 638 267.2 619 332.3 638
380/415-50 201.2 400 161.7 387 201.2 400
208/230-60 * * * * * *
230-60 * * * * * *
460-60 157.9 1175 157.9 1175 157.9 1175
271-XL 575-60 126.2 940 126.2 940 126.2 940
380-60 191.2 1299 191.2 1299 191.2 1299
230-50 * * * * * *
380/415-50 201.2 1265 201.2 1265 201.2 1265
208/230-60 349.6 743 349.6 743 349.6 743
230-60 303.8 743 303.8 743 303.8 743
460-60 157.9 371 157.9 371 157.9 371
271-WD 575-60 126.2 297 126.2 297 126.2 297
380-60 191.2 410 191.2 410 191.2 410
230-50 332.3 638 332.3 638 332.3 638
380/415-50 201.2 400 201.2 400 201.2 400
LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD — Wye-Delta Start
XL — Across-the-Line Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

66
ELECTRICAL DATA, 30HXC UNITS
UNIT VOLTAGE CONTROL CIRCUIT
UNIT Supplied POWER ICF Rec Fuse Size Supplied
V-Hz V-Hz MCA and
30HXC SUPPLY MCA MOCP
(3 Ph) Min Max XL WD XL WD (Single Ph) Min Max MOCP
QTY REQ’D
230-60 207 253 1 198.7 250 — 297.3 — 225 115-60 104 127 15
208/230-60 187 253 1 220.7 300 — 307.1 — 250 115-60 104 127 15
460-60 414 506 1 99.7 125 374.3 148.3 125 125 115-60 104 127 15
076 575-60 518 633 1 79.7 110 299.4 118.4 90 90 115-60 104 127 15
380-60 342 418 1 120.8 150 418.7 168.7 150 150 230-60 207 254 15
380/415-50 342 440 1 125.6 175 399.8 164.8 150 150 230-50 198 254 15
230-50 207 253 1 207.2 250 — 266.1 — 250 230-50 207 254 15
230-60 207 253 1 221.7 300 — 297.3 — 250 115-60 104 127 15
208/230-60 187 253 1 246.4 350 — 307.1 — 300 115-60 104 127 15
460-60 414 506 1 111.3 150 374.3 148.3 125 125 115-60 104 127 15
086 575-60 518 633 1 88.9 125 299.4 118.4 100 100 115-60 104 127 15
380-60 342 418 1 134.8 175 418.7 168.7 175 175 230-60 207 254 15
380/415-50 342 440 1 140.4 200 478.8 189.8 175 175 230-50 198 254 15
230-50 207 253 1 231.9 300 — 305.1 — 300 230-50 207 254 15
230-60 207 253 1 251.3 350 — 344.3 — 300 115-60 104 127 15
208/230-60 187 253 1 279.2 400 — 354.1 — 350 115-60 104 127 15
460-60 414 506 1 126.2 175 449.3 172.3 150 150 115-60 104 127 15
096 575-60 518 633 1 100.8 150 359.4 137.4 125 125 115-60 104 127 15
380-60 342 418 1 152.7 225 501.7 194.7 175 175 230-60 207 254 15
380/415-50 342 440 1 157.9 225 561.8 215.8 200 200 230-50 198 254 15
230-50 207 253 1 260.7 350 — 347.1 — 300 230-50 207 254 15
230-60 207 253 1 285.6 400 — 395.3 — 350 115-60 104 127 15
208/230-60 187 253 1 317.4 450 — 405.1 — 400 115-60 104 127 15
460-60 414 506 1 143.3 200 529.3 197.3 175 175 115-60 104 127 15
106 575-60 518 633 1 114.5 175 423.4 158.4 150 150 115-60 104 127 15
380-60 342 418 1 173.6 250 589.7 222.7 200 200 230-60 207 254 15
380/415-50 342 440 1 178.1 250 660.8 246.8 225 225 230-50 198 254 15
230-50 207 253 1 294.2 450 — 397.1 — 350 230-50 207 254 15
230-60 207 253 1 304.1 450 — 413.7 — 350 115-60 104 127 15
208/230-60 187 253 1 337.9 500 — 425.6 — 400 115-60 104 127 15
460-60 414 506 1 152.6 225 538.6 206.6 175 175 115-60 104 127 15
116 575-60 518 633 1 121.9 175 430.8 165.8 150 150 115-60 104 127 15
380-60 342 418 1 184.8 250 600.9 233.9 225 225 230-60 207 254 15
380/415-50 342 440 1 190.0 250 672.7 258.7 225 225 230-50 198 254 15
230-50 207 253 1 313.9 450 — 416.8 — 400 230-50 207 254 15
230-60 207 253 1 327.7 450 — 437.4 — 400 115-60 104 127 15
208/230-60 187 253 1 364.2 500 — 451.9 — 450 115-60 104 127 15
460-60 414 506 1 164.5 225 550.5 218.5 200 200 115-60 104 127 15
126 575-60 518 633 1 131.4 175 440.3 175.3 150 150 115-60 104 127 15
380-60 342 418 1 199.1 250 615.2 248.2 225 225 230-60 207 254 15
380/415-50 342 440 1 204.0 300 686.7 272.7 250 250 230-50 198 254 15
230-50 207 253 1 337.0 450 — 439.9 — 400 230-50 207 254 15
LEGEND NOTES:
FLA — Full Load Amps 1. Each main power source must be supplied from a field-supplied fused electri-
ICF — Maximum Instantaneous Current Flow during start-up (the point cal service with a (factory- or field-installed) disconnect located in sight from
in the starting sequence where the sum of the LRA for the start- the unit.
up compressor, plus the total RLA for all running compressors) 2. Control circuit power must be supplied from a seperate source through a field-
LRA — Locked Rotor Amps supplied disconnect (except for 380/415-50 units). An accessory control trans-
MCA — Minimum Circuit Ampacity (for wire sizing) former may be used to provide control circuit power from the main unit power
MOCP — Maximum Overcurrent Protection supply.
RLA — Rated Load Amps 3. Maximum incoming wire size for each terminal block is 500 kcmil.
WD — Wye-Delta Start 4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.
XL — Across-the-Line Start 5. Use copper conductors only.
6. The MOCP is calculated as follows:
*May require multiple parallel conductors.
MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the fuse one
size down from the result. The RLAs are listed on the nameplate.

The recommended fuse size in amps (RFA) is calculated as follows:

RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the fuse one size
up from the result. The RLAs are listed on the nameplate.

67
Electrical data (cont)
ELECTRICAL DATA, 30HXC UNITS (cont)
UNIT VOLTAGE CONTROL CIRCUIT
UNIT Supplied POWER ICF Rec Fuse Size Supplied
V-Hz V-Hz MCA and
30HXC SUPPLY MCA MOCP
(3 Ph) Min Max XL WD XL WD (Single Ph) Min Max MOCP
QTY REQ’D
230-60 207 253 1 366.7 500 — 497.4 — 450 115-60 104 127 15
208/230-60 187 253 1 407.4 600 — 511.9 — 500 115-60 104 127 15
460-60 414 506 1 183.8 250 645.5 248.5 225 225 115-60 104 127 15
136 575-60 518 633 1 147.1 200 536.3 199.3 175 175 115-60 104 127 15
380-60 342 418 1 222.8 300 720.2 282.2 300 300 230-60 207 254 15
380/415-50 342 440 1 230.2 300 796.7 307.7 300 300 230-50 198 254 15
230-50 207 253 1 380.3 500 — 495.9 — 450 230-50 207 254 15
230-60 207 253 1* 394.1 500 — 524.9 — 450 115-60 104 127 15
208/230-60 187 253 1* 437.9 600 — 524.4 — 500 115-60 104 127 15
460-60 414 506 1 197.5 250 659.2 262.2 225 225 115-60 104 127 15
146 575-60 518 633 1 158.1 225 547.3 210.3 200 200 115-60 104 127 15
380-60 342 418 1 239.5 350 736.9 298.9 300 300 230-60 207 254 15
380/415-50 342 440 1 246.3 350 812.8 323.8 300 300 230-50 198 254 15
230-50 207 253 1 407.1 600 — 522.7 — 500 230-50 207 254 15
230-60 207 253 1* 398.7 600 — 574.8 — 500 115-60 104 127 15
208/230-60 187 253 1* 443.0 600 — 590.6 — 600 115-60 104 127 15
460-60 414 506 1 200.1 300 756.2 287.2 250 250 115-60 104 127 15
161 575-60 518 633 1 159.9 225 604.9 229.9 200 200 115-60 104 127 15
380-60 342 418 1 242.2 350 843.2 325.2 300 300 230-60 207 254 15
380/415-50 342 440 1 249.0 350 944.2 358.2 300 300 230-50 198 254 15
230-50 207 253 1 411.3 600 — 577.7 — 500 230-50 207 254 15
230-60 207 253 1* 428.4 600 — 604.5 — 500 115-60 104 127 15
208/230-60 187 253 1* 476.0 700 — 623.6 — 600 115-60 104 127 15
460-60 414 506 1 215.0 300 771.1 302.1 250 250 115-60 104 127 15
171 575-60 518 633 1 171.8 250 616.8 241.8 200 200 115-60 104 127 15
380-60 342 418 1 260.2 350 861.2 343.2 300 300 230-60 207 254 15
380/415-50 342 440 1 266.6 350 961.8 375.8 300 300 230-50 198 254 15
230-50 207 253 1 440.4 600 — 606.8 — 500 230-50 207 254 15
230-60 207 253 1* 462.3 600 — 638.5 — 600 115-60 104 127 15
208/230-60 187 253 1* 513.7 700 — 661.3 — 600 115-60 104 127 15
460-60 414 506 1 232.0 300 788.1 319.1 300 300 115-60 104 127 15
186 575-60 518 633 1 185.4 250 630.4 255.4 225 225 115-60 104 127 15
380-60 342 418 1 280.8 400 881.8 363.8 350 350 230-60 207 254 15
380/415-50 342 440 1 289.4 400 984.6 398.6 350 350 230-50 198 254 15
230-50 207 253 1 478.1 600 — 644.5 — 600 230-50 207 254 15
LEGEND NOTES:
FLA — Full Load Amps 1. Each main power source must be supplied from a field-supplied fused electri-
ICF — Maximum Instantaneous Current Flow during start-up (the point cal service with a (factory- or field-installed) disconnect located in sight from
in the starting sequence where the sum of the LRA for the start- the unit.
up compressor, plus the total RLA for all running compressors) 2. Control circuit power must be supplied from a seperate source through a field-
LRA — Locked Rotor Amps supplied disconnect (except for 380/415-50 units). An accessory control trans-
MCA — Minimum Circuit Ampacity (for wire sizing) former may be used to provide control circuit power from the main unit power
MOCP — Maximum Overcurrent Protection supply.
RLA — Rated Load Amps 3. Maximum incoming wire size for each terminal block is 500 kcmil.
WD — Wye-Delta Start 4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.
XL — Across-the-Line Start 5. Use copper conductors only.
6. The MOCP is calculated as follows:
*May require multiple parallel conductors.
MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the fuse one
size down from the result. The RLAs are listed on the nameplate.

The recommended fuse size in amps (RFA) is calculated as follows:

RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the fuse one size
up from the result. The RLAs are listed on the nameplate.

68
ELECTRICAL DATA, 30HXC UNITS (cont)
UNIT VOLTAGE CONTROL CIRCUIT
UNIT Supplied POWER ICF Rec Fuse Size Supplied
V-Hz V-Hz MCA and
30HXC SUPPLY MCA MOCP
(3 Ph) Min Max XL WD XL WD (Single Ph) Min Max MOCP
QTY REQ’D
230-60 207 253 1* 524.5 700 — 700.7 — 600 115-60 104 127 15
208/230-60 187 253 1* 582.8 800 — 730.4 — 700 115-60 104 127 15
460-60 414 506 1 263.2 350 819.3 350.3 300 300 115-60 104 127 15
206 575-60 518 633 1 210.4 250 655.4 280.4 250 250 115-60 104 127 15
380-60 342 418 1 318.6 400 919.6 401.6 350 350 230-60 207 254 15
380/415-50 342 440 1 326.8 450 1022.0 436.0 400 400 230-50 198 254 15
230-50 207 253 1 539.8 700 — 706.2 — 600 230-50 207 254 15
230-60 207 253 1* 604.1 800 — 780.3 — 700 115-60 104 127 15
208/230-60 187 253 1* 671.3 800 — 818.9 — 800 115-60 104 127 15
460-60 414 506 1 303.2 400 859.3 390.3 350 350 115-60 104 127 15
246 575-60 518 633 1 242.3 300 687.3 312.3 300 300 115-60 104 127 15
380-60 342 418 1 367.0 450 968.0 450.0 400 400 230-60 207 254 15
380/415-50 342 440 1 377.6 500 1072.8 486.8 450 450 230-50 198 254 15
230-50 207 253 1 623.8 800 — 790.2 — 700 230-50 207 254 15
230-60 207 253 1* 633.8 800 — 810.0 — 700 115-60 104 127 15
208/230-60 187 253 1* 704.3 800 — 851.9 — 800 115-60 104 127 15
460-60 414 506 1 318.1 400 874.2 405.2 350 350 115-60 104 127 15
261 575-60 518 633 1 254.2 300 699.2 324.2 300 300 115-60 104 127 15
380-60 342 418 1 385.0 500 986.0 468.0 450 450 230-60 207 254 15
380/415-50 342 440 1 395.2 500 1090.4 504.4 450 450 230-50 198 254 15
230-50 207 253 1 652.9 800 — 819.3 — 800 230-50 207 254 15
230-60 207 253 1* 667.8 800 — 843.9 — 800 115-60 104 127 15
208/230-60 187 253 1* 742.0 800 — 889.6 — 800 115-60 104 127 15
460-60 414 506 1 335.1 400 891.2 422.2 400 400 115-60 104 127 15
271 575-60 518 633 1 267.8 350 712.8 337.8 300 300 115-60 104 127 15
380-60 342 418 1 405.6 500 1006.6 488.6 450 450 230-60 207 254 15
380/415-50 342 440 1 418.0 500 1113.2 527.2 500 500 230-50 198 254 15
230-50 207 253 1 690.6 800 — 857.0 — 800 230-50 207 254 15
LEGEND NOTES:
FLA — Full Load Amps 1. Each main power source must be supplied from a field-supplied fused electri-
ICF — Maximum Instantaneous Current Flow during start-up (the point cal service with a (factory- or field-installed) disconnect located in sight from
in the starting sequence where the sum of the LRA for the start- the unit.
up compressor, plus the total RLA for all running compressors) 2. Control circuit power must be supplied from a seperate source through a field-
LRA — Locked Rotor Amps supplied disconnect (except for 380/415-50 units). An accessory control trans-
MCA — Minimum Circuit Ampacity (for wire sizing) former may be used to provide control circuit power from the main unit power
MOCP — Maximum Overcurrent Protection supply.
RLA — Rated Load Amps 3. Maximum incoming wire size for each terminal block is 500 kcmil.
WD — Wye-Delta Start 4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.
XL — Across-the-Line Start 5. Use copper conductors only.
6. The MOCP is calculated as follows:
*May require multiple parallel conductors.
MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the fuse one
size down from the result. The RLAs are listed on the nameplate.

The recommended fuse size in amps (RFA) is calculated as follows:

RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the fuse one size
up from the result. The RLAs are listed on the nameplate.

69
Electrical data (cont)
ELECTRICAL DATA, 30HXA UNITS
UNIT VOLTAGE CONTROL CIRCUIT
UNIT Supplied POWER ICF Rec Fuse Size Supplied
V-Hz V-Hz MCA and
30HXA SUPPLY MCA MOCP
(3 Ph) Min Max XL WD XL WD (Single Ph) Min Max MOCP
QTY REQ’D
230-60 207 253 1 291.2 400 — 436.4 — 350 115-60 104 127 15
208/230-60 187 253 1 323.6 450 — 450.8 — 400 115-60 104 127 15
460-60 414 506 1 146.0 200 549.9 217.9 175 175 115-60 104 127 15
076 575-60 518 633 1 116.8 150 439.9 174.9 150 150 115-60 104 127 15
380-60 342 418 1 177.1 250 614.7 247.7 200 200 230-60 207 254 15
380/415-50 342 440 1 183.4 250 686.5 272.5 225 225 230-50 198 254 15
230-50 207 253 1 303.3 400 — 439.8 — 350 230-50 207 254 15
230-60 207 253 1 322.8 450 — 496.4 — 400 115-60 104 127 15
208/230-60 187 253 1 358.7 500 — 510.8 — 450 115-60 104 127 15
460-60 414 506 1 161.9 225 644.9 247.9 200 200 115-60 104 127 15
086 575-60 518 633 1 129.5 175 535.9 198.9 150 150 115-60 104 127 15
380-60 342 418 1 196.2 250 719.7 281.7 225 225 230-60 207 254 15
380/415-50 342 440 1 205.5 300 796.5 307.5 250 250 230-50 198 254 15
230-50 207 253 1 339.7 500 — 495.8 — 400 230-50 207 254 15
230-60 207 253 1 365.4 500 — 562.4 — 450 115-60 104 127 15
208/230-60 187 253 1* 406.1 600 — 576.8 — 500 115-60 104 127 15
460-60 414 506 1 183.4 250 749.9 280.9 225 225 115-60 104 127 15
096 575-60 518 633 1 146.5 200 599.9 224.9 175 175 115-60 104 127 15
380-60 342 418 1 222.1 300 835.7 317.7 300 300 230-60 207 254 15
380/415-50 342 440 1 231.4 350 937.5 351.5 300 300 230-50 198 254 15
230-50 207 253 1 382.6 500 — 566.8 — 450 230-50 207 254 15
230-60 207 253 1* 416.9 600 — 647.4 — 500 115-60 104 127 15
208/230-60 187 253 1* 463.2 700 — 661.8 — 600 115-60 104 127 15
460-60 414 506 1 209.2 300 884.9 323.9 250 250 115-60 104 127 15
106 575-60 518 633 1 167.2 250 707.9 258.9 200 200 115-60 104 127 15
380-60 342 418 1 253.3 350 984.7 364.7 300 300 230-60 207 254 15
380/415-50 342 440 1 263.3 400 1041.5 384.5 300 300 230-50 198 254 15
230-50 207 253 1 435.1 600 — 619.8 — 500 230-50 207 254 15
LEGEND NOTES:
FLA — Full Load Amps 1. Each main power source must be supplied from a field-supplied fused electri-
ICF — Maximum Instantaneous Current Flow during start-up (the point cal service with a (factory- or field-installed) disconnect located in sight from
in the starting sequence where the sum of the LRA for the start- the unit.
up compressor, plus the total RLA for all running compressors) 2. Control circuit power must be supplied from a seperate source through a field-
LRA — Locked Rotor Amps supplied disconnect (except for 380/415-50 units). An accessory control trans-
MCA — Minimum Circuit Ampacity (for wire sizing) former may be used to provide control circuit power from the main unit power
MOCP — Maximum Overcurrent Protection supply.
RLA — Rated Load Amps 3. Maximum incoming wire size for each terminal block is 500 kcmil.
WD — Wye-Delta Start 4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.
XL — Across-the-Line Start 5. Use copper conductors only.
6. The MOCP is calculated as follows:
*May require multiple parallel conductors.
MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the fuse one
size down from the result. The RLAs are listed on the nameplate.

The recommended fuse size in amps (RFA) is calculated as follows:

RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the fuse one size up
from the result. The RLAs are listed on the nameplate.

70
ELECTRICAL DATA, 30HXA UNITS (cont)
UNIT VOLTAGE CONTROL CIRCUIT
UNIT Supplied POWER ICF Rec Fuse Size Supplied
V-Hz
30HXA V-Hz (3 Ph) SUPPLY MCA MOCP
Min Max XL WD XL WD (Single Ph) Min Max
QTY REQ’D
230-60 207 253 1 442.1 600 — 672.7 — 500 115-60 104 127
208/230-60 187 253 1* 491.3 700 — 689.9 — 600 115-60 104 127
460-60 414 506 1* 221.9 300 897.6 336.6 300 300 115-60 104 127
116 575-60 518 633 1 177.4 250 718.1 269.1 225 225 115-60 104 127
380-60 342 418 1 268.6 400 1000.0 380.0 350 350 230-60 207 254
380/415-50 342 440 1 281.0 400 1059.2 402.2 350 350 230-50 198 254
230-50 207 253 1 464.2 700 — 648.9 — 600 230-50 207 254
230-60 207 253 1* 476.3 700 — 706.8 — 600 115-60 104 127
208/230-60 187 253 1* 529.2 700 — 727.8 — 600 115-60 104 127
460-60 414 506 1 239.1 350 914.8 353.8 300 300 115-60 104 127
126 575-60 518 633 1 191.0 250 731.7 282.7 225 225 115-60 104 127
380-60 342 418 1 289.3 400 1020.7 400.7 350 350 230-60 207 254
380/415-50 342 440 1 301.7 400 1079.9 422.9 350 350 230-50 198 254
230-50 207 253 1 498.5 700 — 683.2 — 600 230-50 207 254
230-60 207 253 1* 539.1 800 — 769.8 — 700 115-60 104 127
208/230-60 187 253 1* 599.1 800 — 790.8 — 700 115-60 104 127
460-60 414 506 1 270.7 400 1014.8 385.8 350 350 115-60 104 127
136 575-60 518 633 1 216.2 300 811.7 308.7 250 250 115-60 104 127
380-60 342 418 1 327.5 450 1131.7 435.7 400 400 230-60 207 254
380/415-50 342 440 1 343.4 500 1345.9 506.9 400 400 230-50 198 254
230-50 207 253 1 567.3 800 — 817.2 — 700 230-50 207 254
230-60 207 253 1* 580.3 800 — 811.0 — 700 115-60 104 127
208/230-60 187 253 1* 644.8 800 — 836.5 — 800 115-60 104 127
460-60 414 506 1 291.3 400 1035.4 406.4 350 350 115-60 104 127
146 575-60 518 633 1 232.7 300 828.2 325.2 300 300 115-60 104 127
380-60 342 418 1 352.5 500 1156.7 460.7 400 400 230-60 207 254
380/415-50 342 440 1 368.9 500 1371.4 532.4 450 450 230-50 198 254
230-50 207 253 1 609.3 800 — 859.2 — 700 230-50 207 254
230-60 207 253 1* 605.6 800 — 955.3 — 700 115-60 104 127
208/230-60 187 253 1* 672.9 1000 — 978.9 — 800 115-60 104 127
460-60 414 506 1 304.0 450 1281.6 477.6 350 350 115-60 104 127
161 575-60 518 633 1 242.9 350 1025.1 382.1 300 300 115-60 104 127
380-60 342 418 1 368.0 500 1428.0 539.0 450 450 230-60 207 254
380/415-50 342 440 1 384.9 500 1398.4 533.4 450 450 230-50 198 254
230-50 207 253 1* 635.7 800 — 858.3 — 800 230-50 207 254
230-60 207 253 1* 651.5 800 — 1001.2 — 800 115-60 104 127
208/230-60 187 253 1* 723.9 1000 — 1029.9 — 1000 115-60 104 127
460-60 414 506 1 327.0 450 1304.6 500.6 400 400 115-60 104 127
171 575-60 518 633 1 261.4 350 1043.6 400.6 300 300 115-60 104 127
380-60 342 418 1* 395.9 500 1455.9 566.9 450 450 230-60 207 254
380/415-50 342 440 1* 413.2 600 1426.7 561.7 500 500 230-50 198 254
230-50 207 253 1* 682.6 1000 — 905.2 — 800 230-50 207 254
LEGEND NOTES:
FLA — Full Load Amps 1. Each main power source must be supplied from a field-supplied fused electri-
ICF — Maximum Instantaneous Current Flow during start-up (the point cal service with a (factory- or field-installed) disconnect located in sight from
in the starting sequence where the sum of the LRA for the start- the unit.
up compressor, plus the total RLA for all running compressors) 2. Control circuit power must be supplied from a seperate source through a field-
LRA — Locked Rotor Amps supplied disconnect (except for 380/415-50 units). An accessory control trans-
MCA — Minimum Circuit Ampacity (for wire sizing) former may be used to provide control circuit power from the main unit power
MOCP — Maximum Overcurrent Protection supply.
RLA — Rated Load Amps 3. Maximum incoming wire size for each terminal block is 500 kcmil.
WD — Wye-Delta Start 4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.
XL — Across-the-Line Start 5. Use copper conductors only.
6. The MOCP is calculated as follows:
*May require multiple parallel conductors.
MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the fuse one
size down from the result. The RLAs are listed on the nameplate.

The recommended fuse size in amps (RFA) is calculated as follows:

RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the fuse one size up
from the result. The RLAs are listed on the nameplate.

71
Electrical data (cont)
ELECTRICAL DATA, 30HXA UNITS (cont)
UNIT VOLTAGE CONTROL CIRCUIT
UNIT Supplied POWER ICF Rec Fuse Size Supplied
V-Hz MCA and
30HXA V-Hz (3 Ph) SUPPLY MCA MOCP
Min Max XL WD XL WD (Single Ph) Min Max MOCP
QTY REQ’D
230-60 207 253 1* 707.9 1000 — 1057.6 — 800 115-60 104 127 15
208/230-60 187 253 2* 437.0/ 700/700 — 743.0/ — 600/600 115-60 104 127 15
437.0 743.0
460-60 414 506 1 355.3 500 1332.9 528.9 400 400 115-60 104 127 15
186 575-60 518 633 1 284.0 400 1066.2 423.2 350 350 115-60 104 127 15
380-60 342 418 1* 430.2 600 1490.2 601.2 500 500 230-60 207 254 15
380/415-50 342 440 1* 452.7 600 1466.2 601.2 600 600 230-50 198 254 15
230-50 207 253 1* 747.7 1000 — 970.3 — 1000 230-50 207 254 15
230-60 207 253 2* 468.6/ 700/600 — 726.8/ — 600/500 115-60 104 127 15
379.8 743.0
208/230-60 187 253 2* 520.6/ 800/700 — 743.0/ — 600/600 115-60 104 127 15
422.0 743.0
460-60 414 506 1* 400.1 500 1377.7 573.7 450 450 115-60 104 127 15
206 575-60 518 633 1 319.9 400 1102.1 459.1 400 400 115-60 104 127 15
380-60 342 418 1* 484.4 600 1544.4 655.4 600 600 230-60 207 254 15
380/415-50 342 440 1* 505.2 700 1518.7 653.7 600 600 230-50 198 254 15
230-50 207 253 2* 486.0/ 700/600 — 771.0/ — 600/500 230-50 207 254 15
415.4 638.0
230-60 207 253 2* 592.1/ 800/600 — 955.3/ — 700/500 115-60 104 127 15
379.8 743.0
208/230-60 187 253 2* 657.9/ 800/700 — 978.9/ — 800/600 115-60 104 127 15
422.0 743.0
460-60 414 506 1 461.9 600 1439.5 635.5 600 600 115-60 104 127 15
246 575-60 518 633 1 369.1 450 1151.3 508.3 450 450 115-60 104 127 15
380-60 342 418 1* 559.2 700 1619.2 730.2 700 700 230-60 207 254 15
380/415-50 342 440 1* 586.1 700 1599.6 734.6 700 700 230-50 198 254 15
230-50 207 253 2* 653.7/ 800/700 — 858.3/ — 800/500 230-50 207 254 15
415.4 638.0
230-60 207 253 2* 638.0/ 800/600 — 1001.2/ — 800/500 115-60 104 127 15
379.8 743.0
208/230-60 187 253 2* 708.9/ 1000/ — 1029.9/ — 800/600 115-60 104 127 15
422.0 700 743.0
460-60 414 506 1* 484.9 600 1462.5 658.5 600 600 115-60 104 127 15
261 575-60 518 633 1* 387.6 500 1169.8 526.8 450 450 115-60 104 127 15
380-60 342 418 1* 587.1 700 1647.1 758.1 700 700 230-60 207 254 15
380/415-50 342 440 1* 614.4 800 1627.9 762.9 700 700 230-50 198 254 15
230-50 207 253 2* 682.6/ 1000/ — 905.2/ — 800/500 230-50 207 254 15
415.4 700 638.0
230-60 207 253 2* 683.6/ 800/600 — 1046.8/ — 800/500 115-60 104 127 15
379.8 743.0
208/230-60 187 253 2* 759.6/ 1000/ — 1080.6/ — 1000/ 115-60 104 127 15
422.0 700 743.0 600
460-60 414 506 1* 513.2 600 1490.8 686.8 600 600 115-60 104 127 15
271 575-60 518 633 1* 410.2 500 1192.4 549.4 450 450 115-60 104 127 15
380-60 342 418 1* 621.4 800 1681.4 792.4 700 700 230-60 207 254 15
380/415-50 342 440 1* 653.9 800 1667.4 802.4 800 800 230-50 198 254 15
230-50 207 253 2* 747.7/ 1000/ — 970.3/ — 1000/ 230-50 207 254 15
415.4 700 638.0 500
LEGEND NOTES:
FLA — Full Load Amps 1. Each main power source must be supplied from a field-supplied fused electri-
ICF — Maximum Instantaneous Current Flow during start-up (the point cal service with a (factory- or field-installed) disconnect located in sight from
in the starting sequence where the sum of the LRA for the start- the unit.
up compressor, plus the total RLA for all running compressors) 2. Control circuit power must be supplied from a seperate source through a field-
LRA — Locked Rotor Amps supplied disconnect (except for 380/415-50 units). An accessory control trans-
MCA — Minimum Circuit Ampacity (for wire sizing) former may be used to provide control circuit power from the main unit power
MOCP — Maximum Overcurrent Protection supply.
RLA — Rated Load Amps 3. Maximum incoming wire size for each terminal block is 500 kcmil.
WD — Wye-Delta Start 4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.
XL — Across-the-Line Start 5. Use copper conductors only.
6. The MOCP is calculated as follows:
*May require multiple parallel conductors. MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the fuse one
size down from the result. The RLAs are listed on the nameplate.
The recommended fuse size in amps (RFA) is calculated as follows:
RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the fuse one size up
from the result. The RLAs are listed on the nameplate.

72
Controls
The standard microprocessor-based control in the 30HX NOTE: Which compressor starts first is determined by the
units provides the following functions: automatic lead/lag feature.
• leaving fluid temperature control (using both entering If the entering fluid temperature is 85 F (29 C) or higher,
and leaving fluid sensors) the maximum operating pressure (MOP) feature limits the
• 7-day time sequence of both pump and chiller suction pressure to keep the chiller on line.
• temperature reset from return fluid (standard) or from Normal operation — The entering fluid temperature
outdoor ambient (accessory), occupied space tempera- sensor monitors changes in entering fluid temperature to
ture (accessory), 4 to 20 mA signal (accessory), or via anticipate changes in the cooling load. Based on leaving
the optional Carrier Comfort Network (CCN) fluid temperature, the control adds or subtracts capacity to
• automatic compressor lead-lag switching based on com- maintain a constant leaving fluid temperature.
pressor accumulated run times and number of cycles
Transition to off — The chiller unloads once the “time-
• automatic temperature range across the cooler
adjustment to-stop” signal has been given. This signal can be either
internal or external.
• fully automatic control of the chiller components
Safeties — The 30HX control as shipped from the fac-
A 4-line, 20-character per line display is used to accom-
plish the following (see figure below): tory automatically deenergizes any active compressor that
experiences any of the following:
• set schedules and set points
• electrical overload
• identify operating mode
• thermal overload protection
• display current temperatures and pressures being used
by the control for internal calculations • high pressure
• low oil pressure
• identify abnormal (alarm or alert) conditions
• loss of refrigerant charge
Sequence of operation • loss of phase protection
The control has a 44 F (6.2 C) leaving fluid temperature • reverse rotation (control prevents compressor start)
(LWT) set point as shipped from the factory. If temperature • current imbalance
reset or demand limiting is in effect, this set point may • ground current
change. • low chilled fluid temperature
Start-up — The chiller will start when the circulating Additional information
pump is energized. (If the flow switch is applied, the chiller Detailed information on controls and operation is available
starts after the flow has been proven.) The compressor in the Controls, Start-Up, Operation and Troubleshooting
starts unloaded. guide included with each unit. Packaged Service Training
programs are also available. Contact your Carrier repre-
sentative for more information.
NAVIGATOR™ DISPLAY MODULE — STANDARD

Com
fort
NA Lin
VIG
ATO k
R™
T IM E
EWT 12.
LW T 54. 58
SETP 44. 6°F
4 4 . 01 ° F
°F

MO
DE
Run Al ar
m St
Statu atu s
s
Servi
ce Te
st
Temp
eratur
es
Pres
sures
Setpo
ints
Inputs
Outpu
ts
Confi
gurat
ion
Time
Cloc
k ESC
Opera
ting
Mode
Alarm s
s

ENT
ER

73
Guide specifications
Fluid-Cooled and Condenserless 2. Shall be mechanically cleanable shell-and-tube
type with removable heads.
Liquid Chillers 3. Tubes shall be internally enhanced, seamless-
HVAC Guide Specifications copper type, and shall be rolled into tube
Size Range: 75 to 265 Tons (264 to 931 kW) sheets.
Carrier Model Number: 30HXA — Condenserless 4. Shall be equipped with weld-on fluid
connections.
30HXC — Fluid Cooled
5. Shell shall be insulated with ¾-in. (19-mm)
Part 1 — General closed-cell, polyvinyl-chloride foam with a maxi-
1.01 SYSTEM DESCRIPTION mum K factor of 0.28. Heads may require field
Microprocessor controlled, fluid-cooled (30HXC) or insulation.
condenserless (30HXA) liquid chiller utilizing screw 6. Shall have a cooler drain and vent.
compressors and electronic expansion valves. 7. Design shall incorporate 2 independent refrig-
1.02 QUALITY ASSURANCE erant circuits.
A. Unit shall be rated in accordance with ARI Standard D. Condenser (30HXC units):
550/590, latest revision (U.S.A.). The 60 Hz 1. Shall be tested and stamped in accordance with
30HXC units shall be ARI certified for performance. ASME code (U.S.A.) for a refrigerant working-
B. Unit construction shall comply with ASHRAE 15 side pressure of 220 psig (1517 kPa).
Safety Code, NEC, and ASME applicable codes Water-side pressure rating shall be 300 psig
(U.S.A. codes). (2068 kPa). In Canada, maximum water-side
C. Unit shall be manufactured at an ISO 9002 regis- pressure shall be 250 psig (1725 kPa), per the
tered facility. Canadian National Registry.
D. 208/230 v, 230 v, 460 v, 575 v, 60 Hz units shall 2. Shall be mechanically cleanable shell-and-tube
be constructed in accordance with UL or CSA type with removable heads.
standards and shall be tested and listed by ETL or 3. Tubes shall be internally enhanced, seamless-
ETL, Canada, as conforming to those standards. copper type, and shall be rolled into tube
Units shall carry the ETL and ETL, Canada, labels. sheets.
1.03 DELIVERY, STORAGE, AND HANDLING 4. Shall be equipped with weld-on water
A. Unit controls shall be capable of withstanding connections.
150 F (66 C) storage temperatures in the control 5. Design shall incorporate 2 independent refrig-
compartment. erant circuits.
B. Unit shall be stored and handled per unit manufac- E. Oil Separator (30HXA Units):
turer’s recommendations. 1. Shall be tested and stamped in accordance with
Part 2 — Products ASME Code (U.S.A.) for a refrigerant working-
2.01 EQUIPMENT side pressure of 320 psig (2206 kPa).
A. General: 2. Design shall incorporate 2 independent refrig-
Factory assembled, single-piece, fluid-cooled erant circuits.
(30HXC) or condenserless (30HXA) liquid chiller F. Refrigeration Components:
with dual (2) independent refrigerant circuits. Con- Refrigerant circuit components shall include oil sep-
tained within the unit cabinet shall be all factory wir- arator, high and low side pressure relief devices, dis-
ing, piping, controls, refrigerant charge (HFC-134a) charge and liquid line shutoff valves, filter drier,
(30HXA units shipped with holding charge only), moisture indicating sight glass, expansion valve,
and special features required prior to field start-up. refrigerant economizer (unit sizes 161-271), and
B. Compressors: complete charge of compressor oil. The 30HXC
1. Semi-hermetic twin-screw compressors with units shall have a complete operating charge of
internal muffler and check valve. refrigerant HFC-134a; 30HXA units shall have a
holding charge only.
2. Each compressor shall be equipped with a dis-
charge shutoff valve. G. Controls, Safeties, and Diagnostics:
C. Cooler: 1. Controls:
1. Shall be tested and stamped in accordance with a. Unit controls shall include as a minimum:
ASME code (U.S.A.) for a refrigerant working- Microprocessor, ON/OFF/ENABLE switch,
side pressure of 220 psig (1517 kPa). 4-line, 20-character per line diagnostic dis-
Water-side pressure rating shall be 300 psig play with keypad.
(2068 kPa). In Canada, maximum water-side
pressure shall be 250 psig (1725 kPa), per the
Canadian National Registry.

74
b. Shall be capable of performing the following 4. Unit shall be shipped with factory control and
functions: power wiring installed.
1) Automatic compressor lead/lag J. Special Features:
switching. Certain standard features are not applicable when
2) Capacity control based on leaving the features designated by * are specified. For assis-
chilled fluid temperature with return fluid tance in amending the specifications, contact your
temperature sensing. local Carrier Sales office.
3) Limit the chilled fluid temperature pull-
* 1. Wye-Delta Starter:
down rate at start-up to an adjustable
range of 0.2° F to 2° F (0.1° C to Unit shall have a factory-installed, Wye-Delta
1.1° C) per minute to prevent excessive starter to minimize electrical inrush current.
demand spikes at start-up. 2. Sound Reduction Enclosure:
4) Seven-day time scheduling of pump(s) Unit shall have field-installed sound reduction
and chiller(s). enclosure which covers the entire unit to muffle
c. Dual chiller control shall be capable of con- compressor noise.
trolling two independent units in series or 3. Vibration Isolation:
parallel flow through a single control
connection. Unit shall be supplied with rubber-in-shear
vibration isolators for field installation.
2. Diagnostics:
4. Control Power Transformer:
a. Display module shall be capable of display-
ing set points, time, system status (including Unit shall be supplied with a field installed trans-
temperatures, pressures, and percent load- former that will supply control circuit power
ing), and any alarm or alert conditions. from the main unit power supply.
b. Control module, in conjunction with the 5. Victaulic Connection:
microprocessor, shall be capable of display- Unit shall be supplied with victaulic-type cooler
ing the output of a run test to verify opera- or condenser connections (field installed).
tion of every switch, sensor, potentiometer, 6. Temperature Reset Sensor:
and compressor before chiller is started. Unit shall reset leaving chilled fluid temperature
3. Safeties: based on outdoor ambient temperature or
Unit shall be equipped with all necessary com- space temperature when this sensor is installed.
ponents, and in conjunction with the control * 7. Brine Option:
system shall provide the unit with protection
Unit shall be factory modified to start and oper-
against the following:
ate at leaving chilled fluid temperatures of
a. Loss of refrigerant charge. between 15 F (–9 C) and 40 F (5 C).
b. Reverse rotation. * 8. Minimum Load Control:
c. Low chilled fluid temperature. Unit shall be equipped with factory (or field)
d. Low oil pressure. installed, microprocessor-controlled, minimum-
e. Voltage imbalance. load control that shall permit unit operation
down to 10% of full capacity.
f. Ground current.
9. Multi-Chiller Control:
g. Thermal overload.
Control shall enable management of multiple
h. High pressure. chillers (up to 8) in a single system.
i. Electrical overload. 10. Minus-One-Pass Cooler:
j. Loss of phase. Factory-installed option shall reduce pressure
k. Loss of chilled water flow. drop for high flow applications. Shall also pro-
H. Operating Characteristics: vide same end inlet and outlet for 076-106
sizes, and opposite end inlet for 116-271 sizes.
Unit shall be capable of starting up with 95 F (35 C)
entering fluid temperature to the cooler. 11. Plus-One-Pass Cooler:
I. Electrical Requirements: Factory-installed option shall enhance low tem-
perature brine performance.
1. Unit primary electrical power supply shall enter
the unit at a single location (some units have 12. Suction Service Valves:
multiple power poles). Unit shall be supplied with factory-installed suc-
2. Unit shall operate on 3-phase power at the volt- tion service valves.
age shown in the equipment schedule.
3. Control voltage shall be 115-v (60 Hz) or 230-v
(50 Hz), single-phase, separate power supply.

75
Guide specifications (cont)
13. Cooler Head Insulation: 14. Energy Management Module:
Unit shall be supplied with field-installed Shall be factory- or field-installed and capable
cooler insulation that shall cover the cooler of 4 to 20 mA leaving fluid temperature
heads. reset, cooling set point reset, 4 to 20 mA
demand limit, and 2-step demand limit.

Carrier Corporation • Syracuse, New York 13221 03-00


Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 New Book 3 Pg 76 Catalog No. 523-060 Printed in U.S.A. PC 903 Form 30HX-5PD