Manual Carrier
Manual Carrier
Manual Carrier
30HXA,HXC076-271
Air-Cooled and Water-Cooled Chillers with ComfortL\nk™ Controls
50/60 Hz
Series 6
Controls Start-Up,
Operation, Service, and
Troubleshooting
SAFETY CONSIDERATIONS
A WARNING
Installing, starting up, and servicing this equipment can be hazardous due to system
DO NOT(roof,
pressures, electrical. components, and equipment location attempt to unbraze
elevated factoiy joints when
structures,
servicing should
etc.). Only trained, qualified installers and Service mechanics this equipment. Compressor
install, start up, oil is
and service this equipment. flammabie and there is no way to detect how much
When working on this equipment, observe precautions oil may be in
in the any of theand
literatura, refrig
onerant
tags, lines. Cut lines
stickers, and labels attached to the equipment, and with a tubing
any other cutter
safety as requiiedtliat
precautions when performing
apply. Follow all safety codes. Wear safety glassesservice. Use agloves.
and work pan to catch any oil
Use care inthat may come
handling, rigging, and setting this equipment, out andof in
the handling
lines and asalla gage for how much oil to
electrical
components. add to system. DO NOT re-use compressor oil. Do
NOT leave refrigerant system open to air any
longer than necessary. Seal circuits being serviced
A WARNING DO NOT VENT refrigerant relief valves
and charge with dry nitrogen to prevent oil
withincontamination
a building. Outlet from relief
when timely repairs cannot be
Electrical shock can cause personal valves completed.
must be vented outdoors in
injury and death. Shut off all power to accor- dance with the latest edition of
this equipment during installation and ANSI/ASHRAE (American National
Service. There may be more than one Standards Insdtute/American Society of
disconnect switch. Tag all disconnect Heating, Refrigeration and Air
locations to alert others not to restore Conditioning Engineers) 15 (Safety
power until work is completed. Code for Mechanical Refrigeration). The
accumulation of refrigerant in an
enclosed space can displace oxygen and
A CAUTION cause asphyxiation. Provide adequate
ventilation in enclosed or low overhead
This unit uses a microprocessor-based
areas. Inhalation of high concentrations
electronic control system. Do not use
of vapor is harmful and may cause heart
jumpers or other tools to short out com-
irregularities, unconsciousness or
ponents, or to bypass or otherwise
death. Misuse can be fatal. Vapor is
depart from recom- mended procedures.
heavier than air and reduces the
Any short-to-ground of the control
amount of oxygen available for
board or accompanying wiring may
breathing. Product causes eye and skin
destroy the electronic modules or
irritation. Decomposition producís are
electrical components.
hazardous.
CONTENTS
A WARNING Page
To prevent potential damage to heat
exchanger tubes always run fluid
through heat exchangers when adding
or removing refrigerant charge. Use
appropriatc brine solu- tions ín cooler
and condenser Huid loops to prevent
the freezing of heat exchangers when
Bo a
the
ok equipment is exposed to
Ta 5c
temperatures below 32 F (0o C).
b
PC 903 Catalog No. 533-00052 Printed ¡n U.S.A, Form 30G.H-9T Pg 1 1-04 Roplaces: New
SAFETY CONSIDERATIONS............................................. I
GENERAL.....................................................................2,3
MAJOR SYSTEM COMPONENTS...............................3,4
Main Base Board (MBB).................................................3
Screw Compressor Board (SCB)...................................3
Electronic Expansión Valve (EXV) Board......................3
ComfortLink Compressor Protection
(CCP) Board....................................................................3
Energy Management Module (EMM)..............................3
Enable/Off/Remote Connect Switch..............................3
Emergency On/Off Switch..............................................3
Board Addresses............................................................3
Control Module Communication....................................3
Carrier Comfort Network (CCN) Interface......................3
OPERATION DATA..................................................... 4-40
Electronic Expansión Valve (EXV).................................4
• EXV OPERATION
• ECONOMIZER OPERATION
Oil Pumps......................................................................... 5
Motor Cooling.................................................................. 5
Back Pressure Valve (30GXN,R
and 30HXA only)..............................................................5
Sensors............................................................................ 5
ComforíLink Compressor Protection (CCP) Board 7
• OUTPUTS
• INPUTS
Wye-Delta vs Across-the-Line (XL)
Starting Option................................................................. 8
Capacity Control.............................................................. 8
MINUTES LEFT FOR START MINUTES OFF
TIME LOADING SEQUENCE CLOSE CONTROL
LEAD/LAG DETERMINATION CAPACITY
SEQUENCE DETERMINATION MINIMUM LOAD
VALVE CAPACITY CONTROL OVERRIDES
2
CONTENTS (cont) • CONDENSERLESS UNITS (30HXA)
Page • 09DK AIR-COOLED CONDENSERS
Head Pressure Control...................................................11 • 09AZ AIR-COOLED CONDENSERS
• GENERAL • OPERATION SEQUENCE
• AIR-COOLED UNITS (30GXN,R) • VARIABLE SPEED FAN CONTROL
• WATER-COOLED UNITS (30HXC) • ADJUSTING PID ROUTINES
Control Methods.............................................................17
• SWITCH
• 7-DAY SCHEDULE
• OCCUPANCY
• CCN
Cooling Setpoint Select..................................................17
Ice Mode........................................................................... 17
Cooler and Condenser (30HXC)
Pump Control..................................................................17
• COOLER PUMP CONTROL
• CONDENSER PUMP CONTROL
Flow Sensor..................................................................... 18
Cooler Heater Control.....................................................18
Oil Heater Control............................................................18
Navigator Display Module Usage...................................18
Service Test.....................................................................19
Configuring and Operating Duai Chiller
Control............................................................................. 19
Alarms/Alerts...................................................................36
Run Hours and Starts.....................................................36
Temperature Reset..........................................................36
Demand Limit..................................................................38
• DEMAND LIMIT (2-Stage Switch Controlled)
• EXTERNALLY POWERED DEMAND LIMIT
• DEMAND LIMIT (CCN Loadshed Controlled)
Cooling Set Point (4 to 20 mA).......................................39
TROUBLESHOOTING.................................................41-51
Checking Display Codes.................................................41
Unit Shutoff......................................................................41
Complete Unit Stoppage.................................................41
Single Circuit Stoppage..................................................41
Restart Procedure...........................................................41
• POWER FAILURE EXTERNAL TO THE UNIT
Alarms and Alerts............................................................41
Compressor Alarm/Alert Circuit.....................................42
EXV Troubleshooting Procedure....................................50
• INSPECTING/OPENING ELECTRONIC EXPANSION VALVES
• BRAZED-PLATE ECONOMIZERS
SERVICE.....................................................................52-71
Servicing Coolers and Condensers...............................52
• TUBE PLUGGING
• RETUBING
• TIGHTENING COOLER/CONDENSER HEAD BOLTS
Inspecting/Cleaning Heat Exchangers..........................52
• COOLERS
• CONDENSERS (30HX Only)
Water Treatment..............................................................53
Condenser Coils (30GXN,R Only)..................................53
• COILCLEANING
• CLEANING E-COATED COILS
Condenser Fans (30GXN,R Only)...................................54
Refrigerant Charging/Adding Charge............................55
Oil Charging/Low Oil Recharging..................................56
Oil Filter Maintenance.....................................................57
• REPLACING THE EXTERNAL OIL FILTER
• REPLACING THE INTERNAL OIL FILTER
Compressor Changeout Sequence................................57
Page
• BURNOUT CLEAN-UP PROCEDURE
Moisture-Liquid Indicator..............................................59
Filter Drier...................................................................... 59
Liquid Line Service Valve..............................................59
Thermistors.................................................................... 59
• LOCATION
• THERMISTOR REPLACEMENT
3
Pressure Transducers...................................................65
• TROUBLESHOOTING
• FLOW SENSOR
Safety Devices............................................................... 68
• COMPRESSOR PROTECTION
• OIL SEPARATOR HEATERS (30GX)
• COOLER PROTECTION
Relief Devices................................................................68
• PRESSURE RELIEF VALVES
Control Modules............................................................68
• MAIN BASE BOARD (MBB), SCREW BOARD (CCP), AND THE NAVIGATOR
COMPRESSOR BOARD (SCB), EXPANSION VALVE • REDLED
BOARD (EXV), ENERGY MANAGEMENT MODULE • GREENLED
(EMM), COMFORTLINK™ COMPRESSOR • YELLOW LED
PROTECTION
Carrier Comfort NetWork (CCN) Interface....................69
Replacing Defective Processor Module........................69
Winter Shutdown Preparation.......................................70
Maintenance.................................................................... 70
PRE-START-UP PROCEDURE........................................71
System Check................................................................. 71
START-UP AND OPERATION....................................71,72
Actual Start-up................................................................ 71
Operating Sequence.......................................................71
FIELD WIRING...........................................................72-74
APPENDIX A
(Compressor Must Trip Amps).................................75-84
APPENDIX B
(Capacity Loading Sequence)..................................85-89
APPENDIX C (Available Accessories)......................90,91
APPENDIX D (Building Interface).............................92-94
APPENDIX E (Cooler and conditions. A scheduling funclion can be programmed
Condenser Pressure Drop).....................................95-100 by the user to control the unil’s occupied and
APPENDIX F unoccupied schedules. The control also operates a
(Typical System Components)........................101-112 test function and a manual control funclion that
APPENDIX G (CCN Configuraron).......................113-125 allows the operator
APPENDIX H (30GXN,R Dúplex Combinations).. 126 10 clieck output signáis and ensure components
APPENDIX I (Motormaster® V are operable.
Operation Instructions).........................................127-129
APPENDIX J (Maintenance Log)..................................130 MAJOR SYSTEM COMPONENTS
START-UP CHECKLIST (For 30GX,HX Liquid Chiller)CL-1 Main Base Board (MBB)—This board contains the
to CL-10 majority of the control system operating software and
Controls the operation of the machine, lt has II input
GENERAL channels and
11 output channels.
IMPORTANT: These units use refrigerant R-134a. The MBB continuously monitors input/output
Compressor oil used with R-134a is Castrol Icematic channel in- formation received from all the modules
SW-220, Carrier Specifícation #PP47-32. and Controls all output signáis for all omput
channels. The processor module also Controls the
This publication contains Controls Start-Up, Service, EXV driver module, commanding it to open or close
Operation and Troubleshooting data for the each EXV in order to maintain the proper cooler
30GXN,R080-528 and 30HXA,C076-271 screw level. Information is transmitted between the MBB;
chillers. CoinfortLink™ Compressor Protection (CCP) boards,
Circuits are identified as circuits A and B, and the EXV driver module, the Screw Compressor Board
compressors are identified as Al or A2 in circuit A, (SCB), the Energy Management Module (EMM) and
and B1 or B2 in Circuit B. Refer to Appendix H for the Navigator modules through a 3-wire
Dúplex unit combinations. Communications bus called the Local Equipment
The 30GXN,GXR,HX Series chillers feature Network (LEN). The remóte enhanced display is
microproces- sor-based electronic Controls and connected to the MBB through a 3-wire
electronic expansión valves (EXV) in each Communications bus, but uses a different
refrigeration circuit. communication bus called the Carrier Comfort
The control system cycles compressor loaders Network (CCN). The CCN bus is also used to
and/or com- pressors lo maintain the selected leaving communicate to other CCN devices when the unit is
fluid temperature set point. The system automatically insta!led in a network applícation.
positions the EXV to maintain the specified discharge Screw Compressor Board (SCB) — The SCB has
gas superheat temperature in the circuit. The system 8 inputs along with 2 analog and 5 discrete outputs.
also has capabilities to control a condenser water The SCB module communicates the status of the
valve to maintain suitable discharge pressure for the inputs with the MBB and operates the oil heater
30HXC unit. Safeties are continuously monitored to (30GXN,R only), cooler heater (30GXN,R only) and oil
preveni the unit from operating under unsafe pump outputs.
4
Electronic Expansión Valve (EXV) Board — GREEN LED —The MBB has one green LED. The
The EXV board has 4 inputs and 2 outputs. It receives Local Equipment Network (LEN) LED should aKvays
signáis from the MBB and operates the electronic be blinking whenever power is on. All other boards
expansión devices. The electronic expansión valve havé a LEN LED that should be blinking whenever
board also sends the MBB the status of its 4 input power is on. Check LEN connec- tions for potential
channels. communication errors at the board J3 and/or J4
ComfortL'mk Compressor Protection (CCP) Board — The connectors. Communication between modules is
CCP board monitors the high-pressure switch status, accom- plished by a 3-wire bus. These 3 wires run in
running current and motor temperature for each parallel from module to module. The J5 connector on
compressor. Each CCP board Controls up to 2 the MBB provides both power and communication
compressors. The CCP board also Controls the motor directly to the Navigator. YELLOW LED — The MBB
cooling solenoid, oil solenoid and contactor outputs. has one yellow LED. The Carrier Comfort Network
A pre-punched configuration header for each (CCN) LED will blink during times of network
compressor determines the must trip amps setting. communication.
Each CCP board sends the MBB each cotnpressor's
motor temperature, relay status and running current Carrier Comfort Network (CCN) Interface —
as a percentage of the must trip amps valué. The CCP The 30GXN,R and 30HX chiller units can be
board also communicates any alarm conditions as the connected to the CCN if desired. The eommunieation
feedback valué. bus wiring is a shielded, 3-conductor cable with drain
Energy Management Module (EMM) — The EMM wire and is supplied and installed in the fie Id. The
is available as a factory-installed option or as a field- system elements are connected co the commu-
instulled accessory. The EMM receives 4 to 20 mA nication bus in a daisy chain arrangement. The
inputs for the temperature reset, cooling set point positive pin of each system element communication
reset and demand limit functions. The EMM also connector must be wired to the positive pins of the
receives the switch inputs for the field-installed 2- system elements on either side of it. This is also
stage demand limit and ice done functions. The EMM required for the negative and signal ground pins of
communicates the status of all inputs with the MBB, each system element. Wiring conneclions for CCN
and the MBB adjusts the control point, capacity limit, should be made at TB3. Consult the CCN
and other functions according to the inputs received. Contractor's Manual for fur- ther information.
Enable/Off/Remote Contact Switch — The Enable/ NOTE: Conductors and drain wire must be 20 AWG
Off/Remute Contad switch is a 3-position switch used (American Wire Gage) mínimum stranded, tinned
to control the chiller (see Table 1). When switched to copper. Individual conductors must be insulated with
the Enable position the chiller is under its own PVC, PVC/nylon, vinyi, Teflon, or polyethylene. An
control. Move the switch to the Off position to shut aluminum/polyester 100% foil shield and an outer
the chiller down. Move the switch to the Remóte jacket of PVC, PVC/nylon, chrome vinyl, or Teflon
Contact position and a field-installed dry contact can with a mínimum operating temperature range of -20
be used to start the chiller. The contacts must be C to 60 C is required. Wire manufacturad by Alpha
capable of handling a 24-vac, 20-mA load. In the (2413 or 5463), American (A22503). Belden (8772),
Enable and Remóte Contad (dry contacts closed) or Columbia (02525) meets the above mentioned
positions, the chiller is allowed to operate and requirements. It is impor- tant when connecting to a
respond to the scheduling configuration, CCN con- CCN communication bus that a color-coding scheme
figuraron and set point data. be used for the entire network to simplify the
Emergency On/Off Switch — The Emergency On/ Off installation. It is recommended that red be used for
switch should only be used when it is required to the signal positive, black for the signal negative and
shut the chiller off immediately. Power to the MBB, white for the signal ground. Use a similar scheme for
EMM, EXV, SCB and Navigator display is intcmiptcd cables containing different colored wires. At each
when this switch is off and all outputs from these system element, the shields of its communication bus
modules will be tumed off. cables must be tied together. If the communication
bus is entirely within one building, the resulting
Board Addresses — The Main Base Board (MBB) has continuous shield must be connected to a ground at
an Instance jumper that must be set to ‘1’. The EXV, one point only. If the communication bus cable exits
SCB and EMM boards have 4-position DIP switches from one building and enters another, the shields
that must be set to 'On' for all boards. The CCP must be connected to grounds at the lightning
address has a 4-position DIP switch. Switches 3 and suppressor in each building where the cable enters
4 set the address. or exits the building (one point per building only).
Control Module Communication To connect the unit to the network:
RED LED — Proper operation of the control boards 1. Tum off power to the control box.
can be vi- sually checked by looking at the red status 2. Cut the CCN wire and strip the ends of the red
LEDs (lighl- emitting diodes). When operating (+), white (ground), and black (-) conductors.
concctly, the red status LEDs should be blinking in (Substitute appropri- ate colors for different
unisón at a rate of once every 2 seconds. If the red colored cables.)
LEDs are not blinking in unisón, verify the board 3. Connect the red wire to (+) terminal on TB3, the
address and that corred power is being supplied to white wire to COM terminal, and the black wire
all modules. Be sure that the Main Base Board (MBB) to the (-) terminal.
is supplied with the current software. If necessary, 4. The RJ-14 CCN connector on TB3 can also be
reload current software. If the problem still persists, used, but is only intended for temporary
replace the MBB. A board LED that is lit continuously connection (for example: a laptop Computer
or blinking at a rate of once per second or faster running Service Tool).
indicates that the board should be replaced.
5
Table 1 — Unit Mode from Control/Enable/Off/ Remóte Fig. 1 — Electronic Expansión Valve (EXV)
Contact and CCN State
the next initialization, the processor counts the total
SWITCH REMOTE CCN CCN UNIT
POSITION CONTACTS CONFIGURATION STATE MODE number of open and closed steps it has sent to each
DISABIE NR LOCAL ON valve.
ENABLE NR ENABLE RUN CCN ON ECONOMIZER OPERATION — Economizers are
STOP CCN OFF factory installed on 30GXN,R108,118-350 and
OFF NR NR NR LOCAL OFF associated modular units and 30HXA,C161-271 units.
OPEN NR NR LOCAL OFF All other sizes use standard EXVs. The economizer is
REMOTE DISABLE NR LOCAL ON a brazed píate heat exchanger designed to improve
CONTACT CLOSEO ENABLE RUN CCN ON
chiller capacity and efficiency as well as providing
STOP CCN OFF
compressor motor cooling. See Fig. 2. On 30GX
LEGEND
CCN — Carrier Comfort Network NR — Input Not Read by Processor chillers the economizer is active when any
NOTE: If the unit is configured for a clock, then the unit is under ciock control if ¡t is compressor is fully loaded. On 30HXA,C chillers the
in an ON mode. economizer is active all the time.
Liquid refrigerant is supplied from the condenser
OPERATION DATA Electronic Expansión Valve to the top of the economizer. As the refrigerant
(EXV) — The MBB passes through the economizer, its pressure is
Controls the EXV through the EXV board. The EXV reduced to an intermedíate level. Next, the
(electronic expansión valve) is a device that contains refrigerant flows to the EXV which regulates flow to
a linear actuator stepper motor. See Fig. 1. the cooler to maintain the discharge superheat
EXV OPERATION — High-pressure liquid refrigerant setpoint.
enters the valve through the side. A series of The increase in performance is achieved by
calibrated slots are locat- ed inside the orífice diverting a small amount of liquid through a
assembly. As refrigerant passes through the orífice, thermostatic expansión valve to a second circuit in
the pressure drops and the refrigerant changes to a the brazed-plate heat exchanger. This will further
2-phase condition (liquid and vapor). To control subcooling the liquid in the first circuit as the
refrigerant flow for different operating conditions, refrigerant flashes to vapor. This increase in
the sleeve moves up and down over the orífice, subcooling provides addition- al capacity. Also, since
thereby changing orífice size. The sleeve is moved by the additional power required to accom- plish this is
a linear stepper motor. The stepper motor moves in minimal; the efficiency of the machine improves. The
incremente and is controlled directly by the vapor that flashes leaves the top of the economizer
processor module. As the stepper motor rotates, where it passes to the compressor and is used to
motion is transferred into linear movement by the provide motor cooling. After passing over the motor
lead screw. Through the stepper motor and lead windings, the refrigerant reenters the cycle at an
screw, 15,000 discrete steps of motion are obtained. intermedíate port in the compression cycle.
The large number of steps and long stroke result in
very accu- rate control of refrigerant flow.
MOTOR COOLING
Each compressor has a discharge gas temperature
sensor mounted vertically in the top of the muffler
assembly. The discharge gas temperature sensor
monitors the discharge gas temperature leaving each
compressor and sends this informa- tion to the MBB
through LEN communication with the EXV board. At
initial start-up, the EXV position is at zero. After that,
the microprocessor keeps accurate track of the valve
position in order to use this Information as input for
the other control functions. The processor does this
by initializing the EXVs at start-up. The processor
sends out enough closing pulses to the valve to move
it from fully open to fully closed, then resets the
position counter to zero. From this point, until
6
energized to open the oil inlet valve at the compres- oil pump will be started. Just before the oil pump is
sor. The control again reads the pressure from the oil started the control measures the pressure differemial
pressure transducer. If the pump has buili up between the discharge pressure and oil pressure (oil
sufficient oil pressure, the compressor is allowed to system pressure drop). The oil system pressure drop
start after 15 seconds. is saved and used to determine when the oil pump
Once the compressor has started, the oil pump will should be shut off.
continué to run for 120 seconds. When the oil pump is operating, it is capable of
If the pump is not able to build up enough oil ¡ncreasing oil pressure from 0 psi to 50 psi
pressure, the pump is tumed off. Within 3 seconds, depending 011 the oil flow requirements of the
the pump is re-energized and malees two additional compressor. For exaniple. if the compres- sor needs 2
attempts, if necessary, to build oil pressure. The gpm (high pressure differemial condition) and the oil
control generales an alami if the third attempt fails. , pump is capable of 1.2 gpm, there is 110 pressure rise
The oil pump is also used to supplement system and the oil flow will bypass the check valve and
pressure under certain operating conditions. The oil supply the 2 gpm to the compressor. If the
flow requirements of the compressor vary based on compressor requires .75 gpm, the oil pump will
pressure differemial across the compressor. The oil increase pressure to satisfy the oil pressure
pump is designed to provide differemial oil pressure requirement.
during low pressure differemial conditions. It ¡s not The pump will continué to operate until the
designed to overcome Itigh pressure drop across discharge pressure minus economizer pressure is
filters during high pressure differemial conditions. greater then 17 psi plus the oil system pressure drop.
If the differemial oil pressure (oil pressure - Example:
economizer pressure) for a compressor is too low the
Discharge pressure 80 psi
Oil pressure 65 psi
Oil system pressure drop 80 - 65 = 15 psi
Economizer pressure 55 psi
Differemial oil pressure (65 - 55) = 10 psi
Suction pressure 40 psi
Based on the above conditions the oil pump will be lilis can be satisfied ¡s if the discharge pressure
started because differemial oil pressure equals 10 ¡ncrcases or the compressor unloads at which point
psi. See Table 2. the
oil pump will be shut off.
Motor Cooling — Compressor motor winding tempera-
tures are controlled to a set point of 200 F (93.3 C).
The control accomplishes this by cycling the motor
cooling solenoid valve to allow liquid refrigerant to
Dow across the motor windings as needed. On
30GXN.R units equipped with economizers, flash gas
leaves the lop of the economizer (when ihe circuit is
fully ¡oaded for 30GXN.R modelsonly) and
continually flows to the motor windings. All
refrigerant used for motor cooling reenters the
rotors through a port located midway along the
compres- sion cycle and is compressed to discharge
pressure.
Back Pressure Valve (30GXN,R and 30HXA only) — This
valve is located on the oil separator outlet on
30GXN.R units and mounted on the oil separator
shell of 30HXA units. The valve's function is to
Fig. 3 — Oil Pump ensure that there is sufficient system differemial
pressure to allow for oil to be driven back to the
Table 2 — Oil Pump Suction Pressure Requirements compressor. A small copper line (economizer
SUCTION PRESSURE (SP) OIL PUMP TURNS ON WHEN pressure) is connected to the top of the valve, which
DIFFERENTIAL PRESSUREIS
LESSTHAN: contains an interna] spring that closes a pistón if the
< 35 psig 12 psig pressure in the oil separator is not at least 15 psig
35 psig < SP < 51 psig 14.5 psig greater than the economizer pressure.
5 51 psig 17 psig Sensors — The 30GXN,GXR,HX Co/n/ortLink™
control system gathers ¡nformation from sensors to
Tile oil pump will continué lo operate until the control the operation of the chiller. The units use up
discharge pressure minus economizer pressure to 10 standard pressure transduc- ers and up to 10
(which equals 25) is greater than 17 plus 15 (oil standard thermistors (including 4 motor temperature
system loss before pump was started). The only way thermistors). The sensors are listed in Table 3.
Table 3 — Thermistor and Transducer Locations
THERMISTORS
Sensor Descrlption Location Connection Termináis
T1 Cooler Leaving Fluid Temp Cooler Head Leaving Fluid Side MBB, J8-13.14
T2 Cooler Entering Fluid Temp Cooler Head Entering Fluid Side MBB, J8-11,12
Motor Temp A1 Motor Temperature A1 Compressor A1 Junction Box CCP1, plug J5
Motor Temp A2* Molor Temperature A2 Compressor A2 Junction Box CCP2, plug J5
7
Motor Temp B1 Motor Temperature B1 Compressor B1 Junction Box CCP1, plug J9
Motor Temp B2t Motor Temperature B2 Compressor B2 Junction Box CCP2, plug J9
T5 Discharge Gas Temp Comp A1 Top of Comp A1 Discharge Line EXV, J5-11,12
T6 Discharge Gas Temp Comp B1 Top of Comp B1 Discharge Une EXV, J5-9.10
T3- Discharge Gas Temp Comp A2 Top of Comp A2 Discharge Line EXV, J5-7.8
T4f Discharge Gas Temp Comp B2 Top of Comp B2 Discharge Line EXV, J5-5.6
T9 (optlonal)** Outdoor Air Thermistor/Dual LWT Outside Air Stream/Common Leaving Fluid TB5, termináis 7,8
T10 (optlonal)** Space Temperature Conditioned Space TB5, termináis 5,6
COND EWT (optlonal)" Condenser Entering Water Thermistor Condenser Entering Fluid Line TB2, termináis 1,2
COND LWT (optlonal)** Condenser Leaving Water Thermistor Condenser Leaving Fluid Line TB2, termináis 3,4
PRESSURE TRANSDUCERS
Sensor Description Location Connection Termináis
DPT-A Discharge Pressure Circuit A Top of Condenser Separator Circuit A MBB, J8-21,22,23
SPT-A Suction Pressure Circuit A Top of Cooler Circuit A MBB, J8-24,25,26
EPT-A Economizer Pressure Circuit A Economizer Line Entering Comp A SCB. J5-7.8.9
OPT-A1 Oil Pressure Compressor A1 Compressor A1 Oil Connection SCB, J5-4,5,6
OPT-A2* Oil Pressure Compressor A2 Compressor A2 Oil Connection SCB, J5-1.2.3
DPT-B Discharge Pressure Circuit B Top of Oil Separator Circuit B MBB, J8-15,16,17
SPT-B Suction Pressure Circuit B Top of Cooler Circuit B MBB, J8-18.19.20
EPT-B Economizer Pressure Circuit B Economizer Line Entering Comp B SCB. J6-7.8.9
OPT-B1 Oil Pressure Compressor B1 Compressor B1 Oil Connection SCB, J6-4.5.6
OPT-B2f Oil Pressure Compressor B2 Compressor B1 Oil Connection SCB, J6-1,2,3
8
s 0 0
LEGEND
LED — Light-Emitting Diode
MBB — Main Base Board
MTA — Must Trip Amps
L — LEN (Local Equipment Network)
S — SIO (Sensor Input/Output)
NOTES:
1. The red LED blinks continuously when the module Is operating properly.
2. The green LED blinks continuously when com- municating prope rly with MBB.
3. On all connectors, pin 1 Is Identified by a
4. Control power to CCP board must be off before making any changes to DIP switch settings.
5. DIP switch 2 disables compressor ground current protection, ON = DISABLE.
9
and
located on the board. The red LED blinks at a rate of windings when Wye connected. The compressor will
once every 1 to 2 seconds. This indicates that the attain about 100% of its normal operating speed
module is powered and operating correctly. The (approximately 3 to 5 seconds) before the CCP
green LED blinks when the module is satisfactorily module deenergizes the S contactor and energizes
com- municating with the MBB. The CCP the 2M contactor, switching the compressor
communicates status of its inputs and outputs and windings to a Delta wiring configuration. The S and
reports 13 different alarm conditions to the MBB. 2M contactors in the starter assembly are both
mechanically and electrically interlocked so that they
A CAUTION will not both be ener- gized at the same time.
Do not alter the factory-installed power wiring
The CCP module has many features that are from the control box terminal block to the
specifically designed to protect the compressor, compressor junction block. Doing so will cause
including reverse rota- tion protection. Do not permanent damage to the compressor and will
attempt to bypass or alter any of the factory require that the compressor be replaced.
wiring. Any compressor operation in the reverse Capacity Control — The control system cycles com-
direction will result in a compressor failure that pressors, loaders, and mínimum load control valves
will require compressor replacement. to maintain the user-configured leaving chilled fluid
The MBB will generate an alert when it receives temperature set point. Entering fluid temperature is
used by the microprocessor to determine the
an alarm input from the CCP. The alert will be
temperature drop across the cooler and is used in
generated as T051, T052, T055, or T056 (for determining the optimum time to add or subtract
Compressors Al, A2, Bl, B2 respectively). Press the capacity stages. The chilled fluid temperature set
buttons on the point can be automati- cally reset by the retum fluid
Navigator simultaneously to expand the ful! temperature, space temperature or outdoor-air
meaning of the alert. For example, the Navigator temperature reset features. It can also be reset from
an external 4 to 20 mA signal (requires optional
will read: T055 CIRCUIT B, COMPRESSOR 1 EMM), or from a network signal.
FAILURE-HIGH PRESSURE SWITCH TRIP. The capacity control algorithm runs every 30
The high-pressure switch is wired in series with seconds. The algorithm attempts to maintain the
the relay coils of the 8 relays on the CCP. If this Control Point at the desired set point. Each time it
switch opens during operation, all relays on the CCP runs, the control reads the entering and leaving fluid
are deenergized and the compressor is stopped. The temperatures. The control determines the rate at
failure is reported to the MBB and the processor which conditions are changing and calcúlales 2
module locks off the compressor from restarting variables based on these conditions. Next, a capacity
until the alarm is manually reset. ratio (SMZ, Outputs under Sub-mode GEN.O) is
calculated using the 2 variables to determine
Wye-Delta vs Across-the-Line (XL) Starting Option whether or not to make any changes to the current
— All 30GXN,R and 30HX chillers operating at stages of capacity. This ratio valué ranges from -100
voltages of 230-3-60, 208/230-3-60 or 230-3-50 (4, 5, to + 100%. If the next stage of capacity is a
or 8 at compressor, the control starts (stops) a compressor
Position 12 in model number) are supplied with when the ratio reaches + 100% (-100%). If the next
factory- installed Wye-Delta starters. All other stage of capacity is a loader, the control energizes
voltage options can be ordered with either Wye-Delta (deenergizes) a loader when the ratio reaches + 60%
or XL starting options. The XL starting method is the (-60%). Loaders are allowed to cycle faster than
most cost effective and simply starts the compressor compressors, to minimize the number of starts and
motor in a Delta configuration (the motors are stops on each compressor. A delay of 90 seconds
designed for continuous operation in this occurs after each capacity step change. MINUTES
configuration) using a single contactor. See Fig. 5. LEFT FOR START — This valué is displayed in the
This is the simplest starting method to use and is Status subfunction and represents the amount of
ideal where starting current does not require time to elapse before the unit is started. This valué
limiting. can be zero without the machine running in many
Where current limitations exist, the Wye-Delta situations. This can include being unoccupied,
option may be used. See Fig. 6. This option uses a Remóte Contact/Off/Enable switch in the OFF
factory-installed starter assembly for each position, CCN not allowing unit to start, Demand
compressor, which consists of 3 contactors labelled Limit in effect, no cali for cooling due to no load, and
1M, 2M, and S. As the compressor is started, the alarm or alert conditions present. If the machine
CCP module energizes contactors 1M and S, which should be running and none of the above are true, a
Connects and energizes the motor windings in a Wye mínimum off time may be in effect. The machine
configuration. The starting current required will be should start normally once the time limit has
approximately 60% less than that required for an XL expired.
start due to the higher impedance of the motor
1
0
TERMINAL BLOCK COMPRESSOR CONTACTOR
COMPRESSOR JUNCTION
BOX
JUMPER BARS
Fig. 5 — Across-the-Line (XL) Compressor Wiring
1
1
On 30HX206-271 and 30GXN.R204-350
units set for staged loading, the control
fully loads the lead circuit before starting
the lag circuit and unloads the lag circuit
first. When these units are set for equal
loading, the control maintains nearly
equal capacities in each circuit when the
chiller is loading and unloading.
CAPACITY SEQUENCE DETERMINATION
(LOAD. Configuration mode, under sub-
mode OPT2) — This is «infigurable as
equal circuit londing or staged circuit
loading with the default set at staged. The
control determines the order in which the
steps of capacity for each circuit are
changed. This control choice does NOT
have any impact on machines with only 2
compressors.
12
MINIMUM LOAD VALVE (MLVS, again. The minimum
Configuration mode under sub-mode
OPT1) — When this option is installed load valve output will be tumed on.
and configured, the first stage of Both circuits’ solenoids are tumed on
capacity is altered by energizing the
Mínimum Load valve relay. Once the at the same time.
control requires more capacity, the 7. Press EWEn, followed by ▼ and ENTE"
minimum load valve is deenergized and again to tum
normal capacity staging resumes with the valve output off.
loaders and compressors. Similarly, the
Minimum Load valve relay will be ener- Adjust Setting of Minimum Load Ball
gized for the last stage of capacity to be Valve — The minimum load ball valve
used before the circuit is shut down. must be adjusted to suit the application.
Calibrate one circuit at a time as follows:
Configure Unit for Minimum Load
Control — The chiller must be configured 1. Adjust the ball valve so that it is
approximately half open.
for minimum load control operation.
2. Operate the chiller in Manual
This may be done using the Navigator.
and Control mode, with one circuit
Set the Enable/Off/Remote Contact then operating, and all compressor
switch in the Off
loaders deenergized.
and position.
3. Record the cooler AT (the
1. keys and Press until‘Select a
Menú Item’is difference between cooler entering
press fluid temperature and cooler leaving
displayed.
fluid temperature) at this fully
2. Press [▼) to illuminate the unloaded condition.
Configuration mode LED.
4. Use the Manual Control feature to
3. Press |E"TEn| and |^| to select ‘OPT1’. enable the minimum load valve for
Press [▼] to select ‘MLV\ the circuit that is operating.
5. Observe and record the cooler AT
4. with the minimum load valve
Press energized.
enter the Password (use arrow for each 6. Adjust the minimum load ball valve
digit) if required. until the cooler temperature
difference reading from Step 5 is
4. Use {▲] to change the flashing equal to half of the temperature
‘No’ to ‘Yes’. Press and the difference reading from Step 3.
display says ‘MLV Yes’. 7. Open the ball valve to decrease the
temperature difference or cióse the
The chiller is now configured for ball valve to increase the
minimum load valve control. Test temperature difference (AT). When
Minimum Load Relay Outputs — After the valve is adjusted correctly, the
the unit is configured, test the operation difference between cooler entering
of the relay and solenoid valve using the and leaving fluid tem- peratures
Service Test mode. when the minimum load control is
energized must be at least half of the
Switch the Enable/Off/Remote temperature difference when the
Contact switch to the ‘Off’ position. minimum load control is
Press deenergized. For example, if the
on the Navigator to display ‘Select a difference between the cooler
entering and leaving water
Menú Item’ and press (▼] to temperature is 3o F with the valve
illuminate the Service Test LED. deenergized, then the difference
ENT between cooler entering and leaving
Press ™ and ‘TEST OFF’ will be water temperature must be at least
displayed.
1.5° F with the valve energized.
(enter Password if required), [▲] and then Once the outputs have been tested and
Press the ball valve adjusted, the installation is
|mTE"| to display ‘TEST ON’. complete. Disable manual control and
Switch the EOR (Enable/Off/Remote retum chiller to desired operational
Contact) switch to the “Enable” status.
position, CAPACITY CONTROL OVERRIDES — The
following over- rides will modify the
5. Press ]▼] to select ‘COMP’ and press normal operation of the routine.
|EIJIE"|.
Deadband Multiplier — The user
6. Press [▼] to select ‘MLV OFF’. Press configurable Deadband Multiplier (Z.GN,
[ENTEH| foliowed by Q and Configuration mode under sub-mode
11
SLCT) has a default valué of 2.0. The
range is from 1.0 to 4.0. When set to
other than 1.0, this factor is applied to
the capacity Load/ Unload Factor. The
larger this valué is set, the longer the
control will delay between adding or
removing stages of capacity. Figure 7
shows how compressor starts can be
reduced over time if the leaving water
temperature is allowed to drift a larger
amount above and below the set point.
This valué should be set in the range of
3.0 to 4.0 for systems with small loop
volumes. The Main Base Board (MBB)
closely follows the rate of compressor
cycling for each circuit.
First Stage Override — If the current
capacity stage is zero, the control will
modify the routine with a 1.2 factor on
adding the first stage to reduce cycling.
This factor is also applied when the
control is attempting to remove the last
stage of capacity.
Slow Change Override — The control
prevents the capacity stages from being
changed when the leaving fluid
temperature is cióse to the set point
(within an adjustable deadband) and
moving towards the set point.
Ramp Loading — (RL.S, Configuration
mode under sub- mode SLCT) — Limits
the rate of change of leaving fluid
temperature. If the unit is in a Cooling
mode and configured for Ramp Loading,
the control makes 2 comparisons before
deciding to change stages of capacity.
The control calculates a temperature
difference between the control point and
leaving fluid temperature. If the
difference is greater than 4° F (2.2° C)
and the rate of change (°F or °C per
minute) is more than the configured
Cooling Ramp Loading valué (CRMP,
Configura- don mode under sub-mode
SLCT), the control does not allow any
changes to the cunrent stage of capacity.
Low Entering Fluid Temperature
Unloading — When the entering fluid
temperature is below the control point,
the control will attempt to remove 25% of
the current stages being used. If exactly
25% cannot be removed, the control
removes an amount greater than 25%,
but no more than necessary. The lowest
stage will not be removed.
Low Discharge Superheat — If a circuit’s
discharge superheat is less than 15° F
(8.3° C), the control does not increase the
current capacity stage. If the discharge
superheat is less than 5o F (2.8° C) and
decreasing, the circuit is unloaded every
30 seconds until the superheat is greater
than 5° F (2.8° C). The final capacity
stage is not unloaded unless an alarm
condition exists. This override is ignored
for the first 3 minutes after a compressor
is started.
14
LWT — 2
DEADBAND EXAMPLE STARTS
Fig. 7 — Deadband Multiplier
-J 6
—
11
head pressure set point by adding 15° F
(8.3° C) for 35 seconds. A fan stage will
be removed when the Saturated
Condensing Temperature has been less
than the Head Pressure Set Point minus
35° F (19.4° C) for 2 minutes. The control
uses the higher of the 2 Saturated
Condensing Temperature valúes for
30GXN.R080-160 units. For the
30GXN.R153, 163-350 units, each
circuit’s fan stages are independently
controlled based on the circuit Saturated
Condensing Temperature. Refer to Table
8 for condenser fan control infomiation.
See Fig. 9A for operational information.
With Motormaster V Control — For low-
ambient operation, the lead fan in each
circuit can be equipped with the optional
or accessory Motormaster head pressure
controller. If factory installed, the
controller will be configured for 4 to 20
mA control. With the Variable Head
Pressure Select option set to 1 (4 to 20
mA), the MBB module calcúlales the
required output based on Saturated
Condensing temperature. Head Pressure
set point, and a PID (proportional integral
derivative) loop calcula- ñon. This 4 to 20
mA output is driven through the SCB.
Proportional. Integral, and Derivative
gain parameters for air-cooled Controls are
adjustable and can be found in the SERV
sub-mode under the Configuration mode.
Only certified Carrier Comfort Network
technicians should perform checkout and
adjustment of the PID loop. To obtuin this
accessory for field installation, order by
pan number 30GX-900—071, 072, 073 for
a single controller package
(30GXN,R080-160). Order part number
30GX-900—074, 075, 076 for a dual
controller package (30GXN.R153, 163-
350). These packages contain all the
hardware required to install this
accessory. See Fig. 9B for operational
information.
16
The control will use the higher of the 2 (Split System). The Head Pressure
Saturated Condensing Temperature Control Type (HPCT under sub-mode
valúes for 30GXN,R080-160 units. For the OPT1) must be configured to 1 (air-
30GXN,R153, 163-350 units, each cooled), and Condenser Pump control
circuit’s fan stages are independently must be set to 0 (CNPC must be set to No
controlled based on the circuit's control, Configuration mode under sub-
Saturated Condensing Temperature. mode OFT1).
Refer to Table 9 for condenser fan Low ambient head pressure control
staging information. can be accomplished with fan cycling
WATER-COOLED UNITS (30HXC) — The pressure switches (09DK054-094),
30HXC chiller can be configured to tempera- ture switches (09DK044, 074-
control direct acting water valves that 094), and Motormaster® control. The
are controlled by a 4 to 20 mA (2 to 10 Motormaster control requires a
vdc) signal. A 0 to 20 mA (0 to 10 vdc) or temperature sensor input to control
20 to 0 mA (10 to 0 vdc) can also be condenser fan cycling. The Motormaster
configured. Installing a 500-ohm V2 watt V control also requires a temperature
resistor across the 2 output termináis of sensor input or the 4 to 20 mA output
the mA signal enables the use of the vdc signal from the Comforñink™ control
signal. Set this configuration (VHPT, system. See accessory installation
configuration mode under sub-mode instructions for further information.
OPT1) to 1 (4 to 20 mA or 2 to 10 vdc), 2 The Head Pressure Control Type
(0 to 20 mA or 0 to 10 vdc), or 3 (20 to 0 (HPCT under sub-mode OPT1) may be set
mA or 10 to 0 vdc) as desired depending to control various types of head pressure
on valve type. Signal connections are control devices. HPCT may be set to 0
made at terminal block TB2, termináis 14 (No Control), 1 (Air Cooled), 3 (Common
and 15. The control scheme reads the Condenser), or 4 (Independent
saturated condensing temperature and Condenser).
uses a PID (proportional integral The 30HXA chillers also support the
derivative) loop to control the head use of a 4 to 20 mA (2 to 10 vdc), 0 to 20
pressure. Proportional, Integral and mA (0 to 10 vdc), or 20 to 0 mA (10 to
Derivative gain parameters for the water- 1 vdc) for fan speed control. Installing a
cooled Controls are adjustable and can be 500-ohm V2 watt resistor across the 2
found in the SERV sub-mode under the output termináis of the mA signal enables
Configuration mode. Only certified the use of the vdc signal. Set this
Carrier Comfort Network technicians configuration (VHPT, configuration mode
should perform checkout and adjustment under sub-mode OFT1) to 1 (4 to 20 mA
of the PID loop. or 2 to 10 vdc), 2 (0 to 20 mA or 0 to 10
CONDENSERLESS UNITS (30HXA) — vdc), or 3 (20 to 0 mA or 10 to 0 vdc) as
The 30HXA unit is oñen applied with an desired depending on control type. For
09DK air-cooled condenser. The remóte common output applications (single
condenser fans are controlled by 2 relay output for both circuits), the signal
outputs. These connections are in the connections are made at terminal block
30HXA control box. See Field Wiring TB2, termináis 14 and 15. For
section on page 72 for wiring details. The independent (one output for each circuit)
30HXA control must be configured to tum applications, the signal connections are
the 09DK fans on and/or off. To set the made at terminal block TB2, termináis 14
30HXA control for this configuration, Unit and 15 for circuit A, and termináis 12 and
Type (TYPE, Configuration mode under 13 for circuit B.
sub-mode UNIT) must be configured to 3
11
UNIT CONFIGURATION OPTION DESCRIPTION POINT ÑAME FACTOR Y CONFIGURATION
Head Pressure Control Type Method of controlling head pressure HPCT Air Cooled (30GX Default, Do not modify)
Fan Staging Select Method of controlling fan staging FAN.S See Table 7
30GX Variable Head Pressure Select Method of controlling variable head VHPT 1 = None (Default)
pressure 2 = 4 to 20 mA (Default if Motormaster FIOP is
installed.)
Set to 4 to 20 mA if Motormaster accessory is installed.
Head Pressure Control Type Method of controlling head pressure HPCT Water Cooled (30HXC Default, Do not modify)
30HXC Variable Head Pressure Select Method of controlling variable head VHPT 0=None
pressure 1 = 4 to 20 mA (*2 to 10 vdc)
2 = 0 to 20 mA (*0 to 10 vdc)
3 = 20 to 0 mA (*10 to 0 vdc)
30HXA Head Pressure Control Type Method of controlling head pressure HPCT No Control
Air Cooled (30HXA Default) Common Condenser
Independent Condenser
Variable Head Pressure Select Method of controlling variable head VHPT 0=None
pressure 1 = 4 to 20 mA (*2 to 10 vdc)
2 = 0 to 20 mA (*0 to 10 vdc)
3 = 20 to 0 mA (*10 to 0 vdc)
*A vdc signal can be generated by installing a 500-ohm 1/2-watt resistor across the 2 output termináis of the mA signai.
18
Table 7 — Fan Staging Select Configuration Settings for Air Cooled (30GXN,R) Units
UNIT 30GXN,R COMPUTER SOFTWARE NAVIGATOR DISPLAY DESCRIPTION
DISPLAY
080,090* 6 (1 STAGE COM) 1st stage compressor status and SCT set point 2nd stage common
control based on highest SCT
083,093,106,108, 7 (2 STAGE COM) 1st stage compressor status and SCT set point
114,125,135* 2nd and 3rd stage common control based on highest SCT
118,128,138, 8 (3 STAGE COM) 1st stage compressor status and SCT set point
150,160* 2nd through 4th stage common control based on highest SCT
153,174, 4 (A2B1 IND) 1 st stage each circuit, compressor status
204,225* 2nd stage Circuit B independent
2nd and 3rd stage Circuit A independent •
163,178* 2 (2 STAGE IND) 1 st stage each circuit, compressor status 2nd and 3rd stage each
circuit independent
249,264* 5 (A3B2 IND) 1st stage each circuit, compressor status
2nd stage Circuit B independent
2nd, 3rd and 4th stage Circuit A independent
208,228 3 (3 STAGE IND) 1 st stage each circuit, compressor status 2nd, 3rd and 4th stage each
253.268.281-350* circuit independent
X
\ \/
\/
" cf o ó o' •o o ó
CONTROL X CONTROL \
BOX BOX CONTROL
to BOX
.O O o PQ
,
P C
END 1/ \ e* END
00 -----
,OPO QO ooo o-,
END END ------- . ,1
-------L.
,
30GXN,R153, 174, 204, 225* 30GXN.R249, 264*
12
\ 1
0
OOO OOOO
CONTROL rA----------—W
rA—\ \ 000 BOX
\ \ / 000
LEGEND
SCT — Saturated Condensing Temperature *And
ooo OOOO
000 0 0 0 ^
associated modular sizes. l\\
.
30GXN.R080,
// 090* 30GXN.R118, 128, 138. 150,
160*
19
30GXN,R163, 178' 30GXN.R208, 228"
12 10 8 6 4 14 12 Í0 8 6
CONTRO
L
BOX
END
Fig. 8 — 30GX Condenser Fan Locations
11 9 7 5 13 11 9
20
30GXN.R UNITS — MOTORMASTER V CONTROL NOT INSTALLED
1Dual set point switch input used. CSP1 used when switch input is open. CSP2 used when switch input is closed. tCooling set
point determined from 4 to 20 mA input to Energy Management Module (EMM) to termináis TB6-3.5.
Fan 2 FC-2, 2A 3.4
083, 093,106-114,125,135 Standard ■ Fan 1 FC-1 1.2
Fan 2 FC-2 3.4
Fan 3 FC-3 5.6
High Static Fan 1 FC-1, 1A 1.2
Fan 2 FC-2, 2A 3.4
Fan 3 FC-3, 3A 5,6
118, 128, 138, 150, 160 Standard Fan 1 FC-1 1.2
Fan 2 FC-2 3,4
Fan 3 FC-3 5, 6
Fan 3 FC-4 7,8
High Static Fan 1 FC-1. 1A 1,2
Fan 2 FC-2, 2A 3.4
Fan 3 FC-3, 3A 5.6
Fan 3 FC-4, 4A 7, 8
153,174, 204, 225 Standard Comp. B1 contador” FC-1 1.2
Fan 2 FC-2 3.4
Fan 3 FC-3 5.6
Comp. A1/A2 contactor* FC-4 7, 8
Fan 1 FC-5 9, 10
High Static Comp, B1 contactor1 FC-1, 1A 1.2
Fan 2 FC-2, 2A 3.4
Fan 3 FC-3. 3A 5.6
Comp. A1/A2 contactor* FC-4, 4A 7.8
Fan 1 FC-5. 5A 9, 10
163, 178 Standard Comp, B1 contacto r* FC-1 1,2
Fan 2 FC-2 3.4
Fan 4 FC-3 5.6
Comp. A1 contactor” FC-4 7.8
Fan i FC-5 9,10
Fan 3 FC-6 11, 12
High Static Comp B1 contactor* FC-1, 1A ■ 1,2
Fan 2 FC-2, 2A 3.4
Fan 4 FC-3, 3A 5,6
Comp. A1 contactor FC-4. 4A 7.8
Fan 1 FC-5, 5A 9,10
Fan 3 FC-6, 6A 11.12
249, 264 Standard Comp. B1 contador’ FC-1 1.2
Fan 2 FC-2 3.4
Fan 1 FC-3 5.6
Comp. A1/A2 contactor' FC-4 7.8
Fan 3 FC-5 9. 10
Fan 3 FC-6 11. 12
High Static Comp. B1 contactor' FC-1,1A 1.2
Fan 2 FC-2, 2A 3.4
Fan 1 FC-3. 3A 5.6
Comp. A1/A2 contactor * FC-4, 4A 7.8
Fan 3 FC-5, 5A 9, 10
Fan 3 FC-6, 6A 11, 12
208, 228 Standard Comp. B1 contactor* FC-1 1
Fan 1 FC-2 2, 4
Fan 2 FC-3 3
Fan 4 FC-4 5, 7
Fan 3 FC-5 6. 8
Comp. A1/A2 contador* FC-6 9. 10
Fan 3 FC-7 11, 12
Fan 3 FC-8 13, 14
High Static Como. B1 contactor* FC-1 1
Fan 1 FC-2. 2A 2.4
Fan 2 FC-3 3
Fan 4 FC-4, 4A 5,7
Fan 3 FC-5, 5A 6. 8
Comp. A1/A2 contactor* FC-6, 6A 9. 10
Fan 3 FC-7, 7A 11,12
Fan 3 FC-8. 8A 13, 14
LEGEND ‘Proper rotation of these fans to be checked when compressor(s) ¡s running.
p ________ Compressor
Com ®ee 8 ,or con< enser ,an
^ locations when viewing from the control box
end
FC — Fan Contactor '
NOTE: For 30GXN.R153, 163-350 units, fan relays Fan 1 and Fan 3 energlze
Circuit A fans. Fan relays Fan 2 and Fan 4 energize Circuit B fans.
Table 9 — 30GXN,R080-350 Condenser Fan Staging (Main Base Board Controlled) (cont)
30GXN,R UNIT SIZE FAN TYPE NAVIGATOR OUTPUT POINT ÑAME FAN CONTACTOR FANS CONTROLLED
09DK AIR-COOLED CONDENSERS 09DK044 Units air temperature results in a lower saturated
— The 09DK044 units have accessory provisión for condensing temperature. When outdoor-air
fully automatic intermediate-season head pressure temperature drops below the minimum temperature
control through condenser fan cycling. Fan number for standard units, additional head pressure control
2 and 3 cycling is controlled by outdoor-air is required.
temperature through air temperature switches (ATS) Model 09DK units have fully automatic
1 and 2. intermediate- season head pressure control through
The air temperature switches are located in the condenser fan cycling using electromechanica] fan
lower divider panel undemeath the coil header. The cycling Controls. Standard head pressure Controls
sensing element is exposed to air entering the no. 1 regúlate the 100 and 50/50% condenser capacity
fan compartment through a hole in the panel. Fan applications. Head pressure can also be controlled by
no. 1 is non-cycling. fan cycling Controls supplemented by the accessory
The air temperature switch Controls the fans as Motormaster® V solid-state head pressure control.
shown in Table 10. See Motor- master V installation instructions for
Table 10 — Air Temperature Switch Control (09DK044 more information.
Units) In the standard control scheme, fans 1 and 2 are
on when there is a cali for cooling from the
FAN FAN SWITCH TEMPERATURE
respective coil circuits. Fans
Above 65 + 3 F (18.3 ± 1.7 C) 2 and 2 are non-cycling. On 054 and 064 units, fans 3
FAN 2 ON Between 55 and 65 F (12.8 and 18.3 C) and and 4 are controlled by using a fan cycling pressure
temporature falling
switch on each of the primary coil circuits in
Below 55 ±3 F (12.6±1.7C)
response to condensing pressure. Fan cycling
OFF Between 55 and 65 F (12.8 and 18.3 C) and
temperature rising switches must be replaced with the switches
Above 80 ±3 F (26.7±1.7 C) supplied in the control box of the 30HXA chiller.
FAN 3 ON Between 70 and 80 F (21.1 and 26.7 C) and The fan cycling pressure switch Controls the fans
temperature talling as follows: Fans 3 and 4 are on above 185 ±10 psig
Below 70 ±3 F (21,1 ±1.7 C) (1276 + 69 kPa) and off below 97 ± 10 psig (669 ±
OFF Between 70 and 80 F (21.1 and 26,7 C) and 69 kPa). If pressure is rising be- tween 97 psig (669
temperature rising kPa) and 185 psig (1276 kPa), fans 3 and 4 are off. If
09DK054-094 — The capacity of an air-cooled pressure is falling from 185 psig (1276 kPa) to 97
LEGEND Comp. — * Proper rotation of these fans to be checked when compressor(s) ¡s running.
Compressor FC — Fan See Fig 0 for condenser fan locations when viewing from the control box end.
Contactor psig (669 kPa) fans 3 and 4 are on.
condenser increases with increased temperature The 09DK054-094 condensers are supplied with
difference (defined as saturated condensing fan cycling pressure switches suitable l'or use with
temperature minus entering outdoor-air R-22 refrigerant. Fan cycling pressure switches thal
temperature) and decreases with decreased are compatible with R-134a refrigerant pressures
temperature difference. A drop in entering outdoor- 23 are shipped with the 30HXA chillers. These fan
cycling pressure switches must be instalied in place For more information on tuning PID loops, consult
of the 09DK factory-installed switches before the Comfort Controller Installation manual, catalog
charging to ensure proper head pressure control. number 808-890. Follow the instructions under
The air temperature switch Controls the fans as Tuning Control loops.
follows: On the 074-094 condensers, below 70 ± 3 F Control Methods
(21.1 ± 1.7 C) outdoor ambient, fans 5 and 6 are ofF; SWITCH — Unit is started and stopped manually by
above 80 ± 3 F (26.7 ± 1.7 C) fans 5 and 6 are on. switch- ing the EN A B LE/OFF/RE M OTE CONTACT
Between 70 F (21.1 C) and 80 F (26.7 C), wheth- er switch from OFF to ENABLE or by extemal contacts
fans 5 and 6 are on or off depends on whether with the switch in the
temperature is rising or falling. If the temperature is REMOTE position. The unit can be enabled and
rising from 70 F (21.1 C) to 80 F (26.7 C), fans 5 and disabled by this action or all control methods.
6 are off. If the temperature is falling from 80 F
7-DAY SCHEDULE — Unit is started and stopped in
(26.7 C) to 70 F (21.1 C), fans 5 and 6 are on.
accor- dance with the schedule configured under
09AZ AIR-COOLED CONDENSERS — The
Time Clock mode. This schedule can be configured
09AZV091- 182 units are designed to operate
from the Navigator or from CCN.
specifically with 30HXA chillers, using R-134a
OCCUPANCY — Unit is started and stopped in
refrigerant. Units with 8 fans have
accordance with the local occupancy schedule
3 direct controlled (applied to optional variable
accessible only from CCN. Schedule Number in Table
speed), 4 refrigerant pressure and 2 ambient
SCHEDOVR must be configured to 1 to utilize the
temperature controlled fans. Units with 10 fans have
local occupancy schedule, or 65-99 to utilize a global
2 direct controlled (applied to optional variable
schedule. If the Schedule Number is set to 0 the unit
speed), 4 refrigerant pressure and 4 ambient
will operate in a continuous 24-hr Occupied mode.
temperature controlled fans. Units with 12 fans have
CCN — Unit is started and stopped by
2 direct controlled (applied to optional variable
communication over the CCN bus. The CHIL_S_S
speed), 6 refrigerant pressure and 4 ambient
point in the A_UNIT table is provided for this
temperature controlled fans. Field adjust 09AZ
purpose.
switch settings as follows:
Table 8 illustrates how the control method and
PRESSURE AMBIENT cooling setpoint select variables direct the operation
Cut in 175 psi Cut in 70 F of the chiller and the set point to which it Controls.
Cut out 145 psi Cut out 60 F The illustration also shows the ON/OFF State of the
OPERATION - All condenser fans machine for the given combinations.
SEQUENCE - are al- Cooling Set Point Select
lowed to operate once a cali for cooling comes from SINGLE — Unit operation is based on Cooling
the chillen Direct fans will operate while refrigerant Setpoint 1 (CSP1).
pressure and ambient temperature control fans DUAL SWITCH — Unit operation is based on Cooling
maintain refrigerant head pressure based on Setpoint 1 (CSP.l) when the Dual Setpoint switch
existing refrigerant pressure and ambient contacts are open and Cooling Setpoint 2 (CSP.2)
temperature conditions. Optional variable speed when they are closed. DUAL 7 DAY — Unit operation
control will ramp direct fan motor speed for is based on Cooling Setpoint
improved low ambient performance. VARIABLE 1 (CSP.l) during the occupied mode and Cool
SPEED FAN CONTROL — All units, when ordered Setpoint 2 (CSP.2) during the unoccupied mode as
with fan head pressure control are fumished with configured under Time Clock mode. Control method
the number 1 condenser motor as a single-phase must be configured for Switch. DUAL CCN
motor for use with head pressure control. The OCCUPIED — Unit operation is based on Cooling
optional factory-mounted motor head pressure Setpoint 1 (CSP.l) during the Occupied mode and
control contains a fan head pressure control device Cooling Setpoint 2 (CSP.2) during the Unoccupied
acdvated by a pressure sensor. The kit Controls mode as configured under the local occupancy
condenser-fan motor speed in response to the schedule accessible only from CCN. Schedule
saturated condensing pressure. Number in Table SCHEDOVR must be configured to
ADJUSTING PID ROUTINES — The 30GXN,R, 1. If the Schedule Number is set to 0 the unit will
30HXA and 30HXC head pressure control ro til mes operate in a continuous 24-hr Occupied mode.
use PID (propor- lional integral derivative) loops to Control method must be configured for Switch.
maintain a user-configurable head pressure set 4 TO 20 mA INPUT — Unit operation is based on an
point. Gain defaults valúes are located in the SERV exter- nal 4 to 20 mA signal input to the Energy
sub-mode under the Configuraron mode (items Management Module (EMM).
H.PGN, Ice Mode — When Ice Mode is enabled Cooling
H. IGN and H.DGN). The control calculates a Setpoint Select must be set to Dual Switch, Dual 7
new fan speed (30GXN,R) or water valve position day or Dual CCN Occupied and the Energy
(30HXC) every 5 seconds based on these gain valúes Management Module (EMM) must be instalied. Unit
and an error terni equal to saturated condensing operation is based on Cooling Setpoint 1 (CSP.l)
temperature minus head pressure set point. If the during the Occupied mode, Ice Setpoint (CSP.3) dur-
control routine is not responding fast enough to ing the Unoccupied mode with the lee Done contacts
large changes (circuit starting, for example), open and Cooling Setpoint 2 (CSP.2) during the
increase the propoitional term. Unoccupied mode with the Ice Done contacts closed.
When the routine is making too great a change to These 3 set points can be utilizcd to develop your
valve position or fan speed, decrease the specific control strategy.
proportional term. To minimize hunting, keep the Cooler and Condenser (30HXC) Pump Control — The
integral term positive and as low as possibie. This 30GXN,R and 30HX chillers can be configured for
valué is used to control “droop,” which is common in cooler and condenser (30HXC) pump control. Inputs
master/submaster control schemes. The default for for a cooler pump interlock and condenser flow
the derivative term is zero. The valué should not switch or interlock are provided.
need to be changed. COOLER PUMP CONTROL (CPC, Configuration
Mode/ sub-mode OFT1) — Proper configuration of
24
the cooler pump control is required to prevent 30HXC brine applications below 32 F (0 o C)
possibie cooler freeze-up. A cooler flow switch is leaving brine temperature require condenser pump
factory instalied to prevent operation without flow control to be configured to “ON WHEN OCCUPIED”
through the cooler. It is also recommended that the and condenser pump interlock to be “ON”. A
chiller be interlocked with the chiller water pump condenser water flow switch must be installed and
starter to provide additional protection. See page 72 wired to TB2 termináis 5 and 6. The condenser pump
of the Field Wiring section for proper connection of output remains energized for 30 minutes after the
the cooler pump interlock. Enable/Off/Remote Contact switch is placed in the
The factory default setting for cooler pump control “OFF” position or the Remóte Contacts are opened
is “OFF.” It is recommended for all chillers that the allowing refrigerant pressure equalization.
cooler pump control be utilized unless the chilled BRN.L (Configuration Mode, sub-mode SLCT)
water pump runs continuously or the chilled water must be configured to YES if Brine FIOP is installed.
system contains a suitable antifreeze solution. This will energize liquid line solenoid valves on brine
When the cooler pump control is “ON,” the cooler units when the condenser pump is “ON” and when
pump relay will be energized when the chiller enters the compressors are “OFF”. Liquid line solenoids are
an “ON” mode (i.e., ON LOCAL, ON TIME, ON CCN). included as part of the Brine FIOP.
The cooler pump relay will remain energized for 30
seconds after all compressors stop due to off FlOW Sensor — The factory-installed flow
command. In the event a freeze protection alarm is sensor/switch should not require adjustment.
generated, the cooler pump relay will be energized Proper operation of this sensor/switch is necessary
whether cooler pump control is configured “ON” or to allow the unit to operate and provide running
“OFF.” The cooler pump relay is also energized freeze protection for the unit. When power is
anytime a compressor is started as well as when supplied to the switch, the amber LED in the center
certain alarms are generated. The cooler pump relay of the display will be illuminated.
should be used as an override to the external pump When there is chilled water flow, but the flow is
control if cooler pump control is not utilized. inadequate to cióse the switch and allow unit
operation, one red LED will illuminate. A red LED
IMPORTANT: If the cooler pump control relay can also indicate inoperative pump(s), closed valve,
output is not wired to control or override the clogged strainer or air in the system.
operation of the chilled water pump an OFF When the first green LED is illuminated, the
DELAY of 10 minutes must be provided after the switch is closed and the unit will start and run.
chiller is disabled to maintain cooler water flow Various conditions can cause variations in flow and
during the pump down period. allow the switch to open and cause a “nuisance trip”.
Greater constant flow will help reduce nuisance tips.
30HXC brine applications below 32 F (0 o C) Measure the pressure drop across the cooler and
leaving brine temperature require cooler pump use Appendix E to determine the cooler flow rate
control. To reduce the possi- bility of condenser then determine if the flow rate is adequate for the
freeze-up the cooler pump must be stopped or application. A green LED does not mean minimum
isolation valve closed in the event of loss of flow requirements have been met.
condenser water flow.
If cooler pump control is tumed “OFF’ or “ON” Cooler Heater Control — Factory-installed cooler heat-
and the chilled water flow switch/interlock does not ers can be ordered for the 30GXN,R chillers. The
cióse within 5 minutes after the unit is enabled and number of heaters depends on the size of the
in an “ON” mode, alarm A200 will be generated. If machine. The control system operates the heaters in
cooler pump control is tumed “ON” and the chilled response to the saturated suction temperature of
water flow switch/interlock is closed when the unit is each circuits as well as Entering and Leaving Water
enabled and enters an “ON” mode alarm A202 will Temperature.
be generated. Alarm A201 will be generated The cooler heater will be energized if the unit is
whenever the cooler pump interlock is open for at OFF (no mechanical cooling) and either of the
least 10 seconds during chiller operation. following two conditions has been met:
CONDENSER PUMP CONTROL (CNP.I AND CNPC, • The Saturated Suction Temperature in either
Configuration Mode/sub-mode OPT1) — Factory circuit is less than BR.FZ Brine Freeze Point
defaults for both condenser pump control and (Configuration Mode, Sub-mode SERV), and the
condenser flow switch are set to “NO CONTROL” and unit has been off for more than 30 seconds.
“OFF,” respectively. The condenser pump can be • Entering or Leaving Water Temperature is less
controlled in one of two ways: In the first method, than BR.FZ + 3 °F (1.7 °C). The heaters will
(CNPC set to “ON WHEN OCCUPIED”) the pump can remain on until both Entering and Leaving Water
be controlled like the cooler pump. It is turned on Temperatures equal or exceed 120 °F (48.9 °C).
whenever the machine is in an “ON” mode and The heaters will energize again when both water
tumed off 30 seconds after all compressors stop and temperatures are below 110 °F (43.3 °C). Cooler
the machine is in an “OFF’ mode. The second method flow must be established in order to de-energize
(CNPC set to “ON WITH COMPRESSORS”), will the cooler heaters.
energize the condenser pump output when the first • If the Entering or Leaving Water Thermistor has
compressor is started and deenergize the output 30 failed, the heaters will stay on.
seconds after the last compressor stops. If after 15 minutes of operation, the Saturáted
When configured for a condenser flow Suction Temperature for both circuits is not greater
switch/interlock (CNP.I set to “ON”), an alarm A159 than BR.FZ + 10 °F (5.6 °C), the Cooler Pump will be
is generated if the input does not cióse within one commanded ON in attempt to increase the water
minute after the machine enters an “ON” mode, or temperature.
within one minute after the condenser pump relay is The cooler heaters will be deenergized if the unit
energized when configured “ON”. Alarm A159 is also is ON (mechanical cooling is ON) or if the Saturated
generated if the flow switch/interlock opens for more Suction Temperature for both circuits is greater than
than BR.FZ + 10 °F (5.6 °C) for at least 10 minutes.
10 seconds during chiller operation.
25
Oil Heater Control (30GXN,R Units Only) — key until ‘Select a Menú Item’ is displayed to move
Standard feature that Controls oil temperature based
through the top 11 mode levels indicated by LEDs on
on the discharge gas temperature (DGT) thermistor.
Heaters tum on when DGT < 95 F (35 C) and tum off the left side of the
when DGT > 100 F (37.8 C) and compressors are off. display.
The heater is deenergized if the oil level switch is Pressing the |ES<=«PE| and e TE
" " keys
open. simultaneously will put the Navigator into expanded
Navigator Display Module Usage (See Fig. 10 and Tables text mode where full meaning of all sub-modes, items
11-24B) — The Navigator module provides a mobile and their valúes can be displayed. Pressing the |
user interface to the Com/oríLink™ control system. ESCftPE
| and ™ keys when the display says ‘Select a
The display has up and down arrow keys, an |esc»pe| Menú Item’ (Mode LED level) will retum the
key, and an |ENim| key. These keys are used to navigate Navigator to its default menú of rotating display
through the different levels of the display structure. items (those items in the VIEW sub-mode under the
See Table 11. Press the Run Status mode). In addition, the
26
Two items, OAT Outside Air Temperature
(Temperature Mode, Sub-mode UNIT) and SPT
Space Temperature (Temperature Mode, Sub-
mode UNIT) can be forced to a valué at the
Navigator. If one of these two points has been
forced, a flashing “f ’ will appear next to the valué
indicating a forced valué. To remove the forcé,
select the item and press the
key so that the valué is flashing. Press the up and
down arrow keys simultaneously and the forcé will
be removed.
Service Test (See Table 13) — Both main power and
control circuit power must be on. The Service
Test function should be used to veriiy proper
operation of the compressors, loaders, pumps,
solenoids, fans, heaters, etc. To access the Service
Test mode, the Enable/Off/Remote Contact switch
must be in the Off position. Use the display keys to
enter the Service Test mode and display ‘TEST
OFF’. Press the
Fig. 10 — Navigator Module key and ‘Off’ will flash (Enter the password if
required). Use either arrow key to change the ‘Off’
to ‘On' and press
UTXL
FLUID CHILLER G ' LLBL, LLBD and LLDY.
FLUID It is recommended to set the cooling set points to
SLAVE
CHILLER the same setting on both Master and Slave chillers for
INSTALL DUAL CHILLER LWT
LEAVING FLUID series flow (Dúplex) applications. If outdoor air reset
TEMPERATURE is required the outdoor air thermistor must be
THERMISTOR (T9) HERE
connected to the Slave chiller (TB5 term. 7 and 8).
' Depending on piping sizes, use either: Outdoor Air Broadcast (BCST, OAT.B) must be
HH79NZ014sensor/10HB50106801 well (3-¡n. sensor/well) configured “ON”. Remóte contacts should be connect -
HH79NZ029 sensor/10HB50106802 well (4-in. sensor/well)
ed to both Master and Slave to control unit operation.
Fig. 12 — Dual Chiller Thermistor Location Parallel Fluid Optional control inputs and Energy Management
Flow Module (EMM) should be connected to the Master
chiller.
To configure the two chillers for operation, follow termináis on TB3 in both chillers. The master
the example shown in Tables 24A and 24B. The chiller will determine which chiller will be Lead
master chiller will be configured with a slave chiller and which will be Lag. The master chiller
at address 2. Also in this example, the master chiller Controls the slave chiller by forcing the slave
will be configured to use Lead/Lag Balance to even chiller ON and OFF, and forcing the control
out the chiller runtimes weekly. The Lag Start Delay
feature will be set to 10 minutes. The chillers will be O
configured for parallel fluid flow. The master and 0.6
1
slave chillers cannot have the same CCN address 1/4 N.P.T. DIA
(CCNA, Configuration mode under OPT2). In addition,
the chillers must be connected together on the same Fig. 13 — Dual 6' MINIMUM Leaving
CCN bus. Connections can be made to the CCN screw Water Thermistor CLEARANCE FOR Well
THERMISTOR REMO
VAL
Service
Conliguration
(SERV)
Broadcast
Conliguration
(BCST)
LEGEND Ckt — Circuit
Table 12 — Configuration Mode and Sub-Mode Directory
SUB- KEYPAD ITEM DISPLAY ITEM COMMENT
MODE ENTRY EXPANSION
DISP ENTER| TEST ON/OFF TEST DISPLAY LEDs See Backllght and Contrast adjustment in Tables 21 and 22.
s
METR ON/OFF METRIC DISPLAY Off = English On = Metric
3
LANG X LANGUAGE SELECTION Default: English
English
Español
Francais
Portuguese
▼ PAS.E ENBL/DSBL PASSWORD ENABLE
UNIT EN TYPE X UNIT TYPE Air Cooled (GXN.R) Water Cooled (HXC) Split (HXA)
TE Heat Machine
R Heat Reclaim
s
1 CARA XXX % CIRCUIT A % CAPACITY 30GXN.R
080, 083, 135, 138= 54
090, 093, 108, 114, 125, 128, 153 = 59
106 = 63
150 (60 Hz) = 41
160 = 45
174, 178, 281-350= 50 204 = 64
225 = 61 118,163 = 55 249,253 = 71 208 = 70 264, 268 = 67
228 = 72
30HXA.C
076, 186 = 50
086, 126 = 54
096, 116, 136, 161 =59
106, 246 = 63
146 = 55
171 =45
206 = 57
261 = 65
271 = 67
s
CMP.A X NUMBER CIRC A COMPRESSOR HXA,C076-186 = 1 HXA.C206-271 = 2 GXN.R080-178 = 1
GXN.R204-350 = 2
a
CMP.B X NUMBER CIRC B COMPRESSOR HXA.C076-271 = 1 GXN.R080-268 = 1 GXN,R281-350 = 2
s
DIS.S XX.X °F DISCHARGE SUPER SETPOINT Default: 22“ F DISCHARGE SUPERHEAT
ENTE
F CM.A1 XXX AMPS COMPR. A1 MUST TRIP AMPS Verify with Appendix A
ENTE
F CM.A2 XXX AMPS COMPR. A2 MUST TRIP AMPS Verify with Appendix A
ENTER CM.B1 XXX AMPS COMPR. B1 MUST TRIP AMPS Verify with Appendix A
ENT
EF CM.B2 XXX AMPS COMPR. B2 MUST TRIP AMPS Verify with Appendix A
31
Table 12 — Configuration Mode and Sub-Mode Directory (cont)
SUB- KEYPAD ITEM DISPLAY ITEM COMMENT
MODE ENTRY EXPANSION
OPT1 IOT FLUD X COOLER FLUID Default: Water Water
E* Médium Temperature Brine Low Temperature Brine (30HX
only)
a
HPCT X HEAD PRESS CONTROL TYPE No Control
Air Cooled (30GXN,R, 30HXA default)
Water Cooled (30HXC default)
Common Cond (30HXA Common Condenser) Ind Cond
(30HXA Independeni Condenser)
a
VHPT X VAR HEAD PRESSURE SELECT None (30HX, 30GX No Motormaster)
4-20 mA (2-10 vdc)(30GX with Motormaster) 0-20 m A (0-
10 vdc)
20-0 mA (10-0 vdc)
H PRTS YES/NO PRESSURE TRANSDUCERS Default: Yes
a
CNP.I ON/OFF CONDENSER PUMP INTERLOCK Default: Off
(Does not require condenser pump control)
▼ CNPC X CONDENSER PUMP CONTROL Default: No Control No Control On when occupied On with
compressor(s)
a
CCNB XXX CCN BUS NUMBER Default: 0 Range: 0 to 239
a
BAUD X CCN BAUD RATE Default: 9600
2400
4800
9600
19,200
38,400
a
LOAD X LOADING SEQUENCE SELECT Default: Equal
Equal
Staged
a
LLCS X LEAD/LAG SEQUENCE SELECT Default: Automatic Automatic Circuit A Leads Circuit B
Leads
a
CP.SQ X COMPRESSOR SEQUENCE Default: Automatic Automatic
Compressor 1 Leads Compressor 2 Leads
a
LCWT XX.X AF HIGH LCW ALERT LIMIT Default: 60 Range: 2 to 60 F
a
DELY XX MINUTES OFF TIME Default: 0 Minutes Range: 0 to 15 Minutes
a
CLS.C ENBUDSBL CLOSE CONTROL SELECT Default: Disable
a
W.MSG ENBUDSBL WINTERIZE ALERT CONFIG Default: Enable
a
ALR.C X ALARM RELAY USAGE Default: Alerts + Alarms Alerts + Alarms Alarms Only Off
)
Table 12 — Configuration Mode and Sub-Mode Directory (cont)
SUB- KEYPAD ITEM DISPLAY ITEM COMMENT
MODE ENTRY EXPANSION
RSET ENT
EF CRST X COOLING RESET TYPE Default: No Reset No Reset 4 to 20 mA Input Outdoor
Air Temperature Return Fluid Space Temperature
a
CRT1 XXX. X °F NO COOL RESET TEMP Default: 125 F
Range: 0o to 125 F
For return fluid reset use cooler AT
a
CRT2 XXX.X °F FULLCOOLRESETTEMP Default: 0° F
Range: 0° to 125 F
For return fluid reset use cooler AT
a
DGRC XX.X AF DEGREES COOL RESET Default: 0° F Range: -30 to 30 F
a
HRST X HEATING RESET TYPE Default: No Reset No Reset 4 to 20 mA Input Outdoor
Air Temperature Return Fluid Space Temperature
a
HRT1 XXX.X °F NO HEAT RESET TEMP Default: 0° F Range: 0o to 125 F
a
HRT2 XXX.X °F FULL HEAT RESET TEMP Default: 125 F Range: 0° to 125 F
a
DMDC X DEMAND LIMIT SELECT Default: None
None
Switch
4 to 20 mA Input CCN Loadshed
a
SHDL XXX % LOADSHED DEMAND DELTA Default: 0% Range: 0 to 60%
a
SHTM XXX MAXIMUM LOADSHED TIME Default: 60 Minutes Range: 0 to 120 Minutes
a
DLS1 XXX % DEMAND LIMIT SWITCH 1 Default: 80% Range: 0 to 100%
a
DLS2 XXX % DEMAND LIMIT SWITCH 2 Default: 50% Range: 0 to 100%
a
MSSL SLVE/MAST MASTER/SLAVE SELECT Default: Master
a
SLVA XXX SLAVE ADDRESS Default: 0 Range: 0 to 239
a
LLBL X LEAD/LAG BALANCE SELECT Default: Master Leads Master Leads Slave Leads
Automatic
a
LLBD XXX LEAD/LAG BALANCE DELTA Default: 168 hours Rancie: 40 to 400 hours
a
LLDY XXX LAG START DELAY Default: 5 minutes Range: 0 to 30 minutes
a
PARA YES/NO PARALLEL CONFIGURATION Default: No (Series Flow)
a
RL.S ENBL/DSBL RAMP LOAD SELECT Default: Enable
&
CRMP X.X COOLING RAMP LOADING Default: 1.0 Range: 0.2 to 2.0
33
a
HRMP x.x HEATING RAMP LOADING Default: 1.0 Range: 0.2 to 2.0
a
HCSW COOL/HEAT HEAT COOL SELECT Default: Cool
Table 13 — Service Test Mode and Sub-Mode Directory
▼
Z.GN X.X DEADBAND MULTIPLIER Default: 2.0 Range: 1.0 to 4.0
]
SERV IN H.PGN XX.X HEAD PRESSURE P GAIN Default: 1.0 Range: -20 to 20
T{I
a
H.IGN XX.X HEAD PRESSURE I GAIN Default: 0.1 Range: -20 to 20
a
H.DGN XX.X HEAD PRESSURE D GAIN Default: 0.0 Range: -20 to 20
▼
H.MIN XXX.X WATER VALVE MINIMUM POS. Default: 20% Range: 0 to 100%
▼
MT.SP XXX.X “F MOTOR TEMP SETPOINT Default: 200 F (170 F for Brine)
▼
BR.FZ XXX.X °F BRINE FREEZE POINT Default: 34 F Range: -20 to 34 F
a
MC.SP XXX.X “F MAX. COND. TEMP SETPOINT Default: 152 F(GXN,R) 145 F (HXA)
118 F (HXC) Range: 100 F To Default
a
EX.S.A XX.X % EXVA START POSITION Default: 20 % Range: 0 T0 40 %
a
EX.S.B XX.X % EXVB START POSITION Default: 20 % Range: 0 To 40 %
a
EN.A1 ENBL/DSBL ENABLE COMPRESSOR A1 Default: Enable (All)
&
EN.A2 ENBL/DSBL ENABLE COMPRESSOR A2 Disable (HX076-186, GXN,R080-178) Enable
(HX206-271, GXN.R204-350)
a
EN.B1 ENBL/DSBL ENABLE COMPRESSOR 81 Default: Enable (All)
a
EN.B2 ENBL/DSBL ENABLE COMPRESSOR B2 Disable (HX076-271, GXN.R080-268 Enable
(GXN.R281-350)
a
W.DNE YES/NO WINTERIZATION PERFORMED
a
ECON YES/NO ECONOMIZED No (30HX076-146, 30GXN,R080-106,114) Yes
(30HX161 -271,30GXN,R108,118-350)
a
EVPS X NUMBER OF EVAP. PASSES Range: 1 To 4
a
LWTC A/B CIRCUIT WITH LWT SENSOR According to number of cooler passes.
a
OAT.B ON/OFF CCN OATBROADCAST Default: Off
34
MC.B1 ON/OFF MOTOR COOLING SOLENOID B1
S
FAN3 ON/OFF FAN 3 RELAY Fans 5, 6 (083, 093-160, 174, 204, 225) Fans 6, 8 (253,
268)
Fans 7, 8(118, 128, 138, 150, 160) Fans 9, 10(249, 264)
Fans 11, 12 (163, 178, 208, 228-268) Fans 13, 14 (208,
228, 253, 268-350) Fans 15, 16(281-350)
fe FAN4 ON/OFF FAN 4 RELAY Fans 5, 7 (208, 228, 253, 268) Fans 5, 6,7, 8 (281-350)
Fans 11, 12(163, 178)
COMP ENT
E I CC.A1 ON/OFF COMPRESSOR A1 RELAY
35
Table 14 — Temperature Mode and Sub-Mode Directory
SUB-MODE KEYPAD ITEM DISPLAY ITEM COMMENT
ENTRY EXPANSION
UNIT EN CEWT XXX.X °F COOLER ENTERING FLUID
TE
í
a
CLWT XXX.X °F COOLER LEAVING FLUID
a
OAT XXX.X °F OUTSIDE AIR TEMPERATURE
a
DLWT XXX.X °F LEAD/LAG LEAVING FLUID
a
SST.A XXX.X °F SATURATED SUCTION TEMP
a
SH.A XXX.X AF DISCHARGE SUPERHEAT TEMP
▼ DGT.A XXX.X "F DISCHARGE GAS TEMP Average of A1/A2 valúes for
GXN.R204-350 and HX206-271
a
DGA.2 XXX.X °F DISCHARGE GAS TEMP - A2 GXN.R204-350 and HX206-271
only
a
MT.A1 XXX.X °F A1 MOTOR TEMPERATURE
a
MT.A2 XXX.X °F A2 MOTOR TEMPERATURE GXN.R204-350 and HX206-271
only
a
SST.B XXX.X °F SATURATED SUCTION TEMP
a
SH.B XXX.X AF DISCHARGE SUPERHEAT TEMP
a
DGT.B XXX.X °F DISCHARGE GAS TEMP Average of B1/B2 valúes for
GXN.R281-350
a
DGB.1 XXX.X °F DISCHARGE GAS TEMP - B1
a
DGB.2 XXX.X °F DISCHARGE GAS TEMP - B2 GXN.R281-350 only
a
MT.B1 XXX.X °F B1 MOTOR TEMPERATURE
a
MT.B2 XXX.X °F B2 MOTOR TEMPERATURE GXN,R281-350 only
a
D0.A1 XXX.X PSI A1 OIL PRESSURE DIFF. Equals oil pressure minus
Economizer pressure
a
DO.A2 XXX.X PSI A2 OIL PRESSURE DIFF. Equals oil pressure minus
Economizer pressure
a
FD.A1 XXX.X PSI A1 OIL FILTER DIFF. PRESS Equals discharge pressure minus oil
pressure
a
FD.A2 XXX.X PSI A2 OIL FILTER DIFF. PRESS Equals discharge pressure minus oil
pressure
a
PS.A1 XX.X PSI CALCULATED OIL PRESS A1 CKT A olí pressure setpolnt 1 (See
notes for Table 32)
36
Table 15 — Pressure Mode and Sub-Mode Directory
a
PS.A2 XX.X PSI CALCULATED OIL PRESS A2 CKT A oil pressure setpoint 2 (See
notes for Table 32)
PRC.B :NTEI DP.B XXX.X PSIG DISCHARGE PRESSURE
a
SP.B XXX.X PSIG SUCTION PRESSURE
a
ECN.B XXX.X PSIG ECONOMIZER PRESSURE
a
OP.B1 XXX.X PSIG B1 OIL PRESSURE
a
OP.B2 XXX.X PSIG B2 OIL PRESSURE
a
DO.B1 XXX.X PSI B1 OIL PRESSURE DIFF. Equals oil pressure minus
Economizer pressure
a
DO.B2 XXX.X PSI B2 0IL PRESSURE DIFF. Equals oil pressure minus
Economizer pressure
a
FD.B1 XXX.X PSI B1 OIL FILTER DIFF. Equals discharge pressure minus oil
pressure
▼ FD.B2 XXX.X PSI B2 OIL FILTER DIFF. Equals discharge pressure minus oil
pressure
a
PS.B1 XX.X PSI CALCULATED OIL PRESS B1 CKT B oil pressure setpoint 1 (See
notes for Table 32)
a
PS.B2 XX.X PSI CALCULATED OIL PRESS B2 CKT B oil pressure setpoint 2 (See
notes for Table 32)
HEAD EU HD.P.A XXX.X 'F HEAD PRESSURE SETPOINT A Default: 113 F (30GX.HXA) 85 F
Tfc (30HXC)
n
▼ HD.P.B XXX.X °F HEAD PRESSURE SETPOINT B Default: 113 F (30GX.HXA) 85 F
(30HXC)
SUB-MODE KEYPAD ITEM DISPLAY ITEM COMMENT
ENTRY EXPANSION
GEN.I EfíT
E STST STRT/STOP START/STOP SWITCH
0
DLS2 ON/OFF DEMAND LIMIT SWITCH 2
a
ICED ON/OFF ICE DONE
B
DUAL ON/OFF DUAL SETPOINT SWITCH
CRCT ENT
EF FKA1 ON/OFF COMPRESSOR A1 FEEDBACK
a
OIL.A OPEN/CLSE OIL LEVEL SWITCH
a
A1.CR XXX AMPS COMPA1 RUNNING CURRENT
a
A2.CR XXX AMPS COMP A2 RUNNING CURRENT
37
Table 18 — Outputs Mode and Sub-Mode Directory
a
FKB2 ON/OFF COMPRESSOR B2 FEEDBACK
a
OIL.B OPEN/CLSE OIL LEVEL SWITCH
a
B2.CR XXX AMPS COMP B2 RUNNING CURRENT
a
HSP XX.X MA 4-20 MA HEATING SETPOINT
38
Table 18 — Outputs Mode and Sub-Mode Directory
SUB-MODE KEYPAD ITEM DISPLAY ITEM COMMENT
ENTRY EXPANSION
39
Table 19 — Operating Mode and Sub-Mode Directory
GEN.0 ENT
EF FAN1 ON/OFF FAN 1 RELAY
a
FAN2 ON/OFF FAN 2 RELAY
a
FAN4 ON/OFF FAN 4 RELAY
a
MLV ON/OFF MINIMUM LOAD VALVE
a
C.PMP ON/OFF COOLER PUMP RELAY
a
CNDP ON/OFF CONDENSER PUMP RELAY
CIR.A ENT
EI CC.A1 ON/OFF COMPRESSOR A1 RELAY
a
CC.A2 ON/OFF COMPRESSOR A2 RELAY
a
LD.A1 ON/OFF LOADER A1 RELAY
a
LD.A2 ON/OFF LOADER A2 RELAY
a
OL.P.A ON/OFF OIL PUMP
a
MC.A1 ON/OFF MOTOR COOLING A1 SOLENOID
a
MC.A2 ON/OFF MOTOR COOLING A2 SOLENOID
a
OL.A2 ON/OFF OIL SOLENOID A2
a
VH.PA XXX % VARIABLE HEAD PRESS %
CIR.B ENT
E CC.B1 ON/OFF COMPRESSOR B1 RELAY
a
CC.B2 ON/OFF COMPRESSOR B2 RELAY
&
LD.B2 ON/OFF LOADER B2 RELAY
a
OL.P.B ON/OFF OIL PUMP
a
MC.B1 ON/OFF MOTOR COOLING B1 SOLENOID
a
MC.B2 ON/OFF MOTOR COOLING B2 SOLENOID
a
OL.H.B ON/OFF OIL HEATER
a
OL.B1 ON/OFF OIL SOLENOID B1
a
OL.B2 ON/OFF OIL SOLENOID B2
a
EXV.B XXX % EXV % OPEN
a
VH.PB XXX % VARIABLE HEAD PRESS %
40
Table 20 — Run Status Mode and Sub-Mode Directory
SUB-MODE KEYPAD ITEM DISPLAY ITEM COMMENT
ENTRY EXPANSION
MODE ENT
E MD01 ON/OFF CSM CONTROLUNG CHILLER
a
MD05 ON/OFF RAMP LOAD LIMITED
a
MD07 ON/OFF LOW COOLER SUCTION TEMPA
a
MD08 ON/OFF LOW COOLER SUCTION TEMPB
a
MD09 ON/OFF SLOW CHANGE OVERRIDE
a
MD10 ON/OFF MINIMUM OFF TIME ACTIVE
a
MD11 ON/OFF LOW DISCHRGE SUPERHEAT A
a
MD12 ON/OFF LOW DISCHRGE SUPERHEAT B
a
MD13 ON/OFF DUAL SETPOINT
a
MD14 ON/OFF TEMPERATURE RESET
a
MD15 ON/OFF DEMAND LIMIT IN EFFECT
a
MD16 ON/OFF COOLER FREEZE PROTECTION
a
MD17 ON/OFF LOW TMP COOL/HI TMP HEAT
a
MD19 ON/OFF MAKING ICE
a
MD20 ON/OFF STORING ICE
a
MD22 ON/OFF HIGH SCT CIRCUIT B
a
MD25 ON/OFF CKT A OFF REF FLOW DELAY*
a
MD26 ON/OFF CKT B OFF REF FLOW DELAY*
a
MD27 ON/OFF CIRCUIT A — PUMPING OUT SHUTDOWN IN PROGRESS
a
MD28 ON/OFF CIRCUIT B — PUMPOUT OUT SHUTDOWN IN PROGRESS
a
MD29 ON/OFF UNIT OFF: NO WATER FLOW
“Recycle restart pending 15-minute delay due to loss of refrigerant flow detected at start-up.
SUB-MODE KEYPAD ITEM DISPLAY ITEM COMMENT
ENTRY EXPANSION
VIEW iNTE
F EWT XXX.X °F ENTERING FLUID TEMP
a
LWT XXX.X °F LEAVING FLUID TEMP
a
SETP XXX.X °F ACTIVE SETPOINT
a
CTPT XXX.X °F CONTROL POINT
41
Table 19 — Operating Mode and Sub-Mode Directory
a
STAT X CONTROL MODE SERVICE TEST OFF LOCAL OFF
CCN OFF TIME OFF EMRGCY ON
LOCAL ON CCN ON TIME
a
MODE YES/NO OVERRIDE MODES IN EFFECT
a
CAP XXX % PERCENT TOTAL CAPACITY
a
DEM.L XXX % ACTIVE DEMAND LIMIT
a
TIME XX.XX TIME OF DAY 00.00-23.59
a
MNTH XX MONTH OF YEAR January, February, etc.
a
DATE XX DAY OF MONTH 01-31
a
YEAR XX YEAR
a
STR.U XXXX MACHINE STARTS
HOUR ENT
GI HRS.A XXXX HRS CIRCUIT A RUN HOURS
a
HRS.B XXXX HRS CIRCUIT B RUN HOURS
a
HR.A1 XXXX HRS COMPRESSOR A1 RUN HOURS
a
HR.A2 XXXX HRS COMPRESSOR A2 RUN HOURS
a
HR.B1 XXXX HRS COMPRESSOR B1 RUN HOURS
a
HR.B2 XXXX HRS COMPRESSOR B2 RUN HOURS
a
ST.A1 XXXX COMPRESSOR A1 STARTS
a
ST.A2 XXXX COMPRESSOR A2 STARTS
a
ST.B1 XXXX COMPRESSOR B1 STARTS
42
Table 20 — Run Status Mode and Sub-Mode Directory (cont)
SUB-MODE KEYPAD ITEM DISPLAY ITEM COMMENT
ENTRY EXPANSION
VERS ENT
EF MBB CESR-131344-xx-xx xx-xx is Versión number
a
CP1 100233-1 R1-xx-xx xx-xx is Versión number
a
CP2 100233-1 R1-xx-xx xx-xx is Versión number
a
SCB CESR-131226-xx-xx xx-xx is Versión number
ENT
E Enter Enter password as required using ENTER key after
Password each number.
TEST 1111
OFF 'OFF will be flashing.
▲ TEST ON Change valué to ‘ON’ (‘ON1 flashes).
ENT
E TEST ON Display Test is Enabled. The alarm and all mode
LED's light up. The Navigator will display all block
segmenta.
V Press arrow keys at the same time. The Navigator
will display ‘Adjust Brightness.'
aa
Use the up arrow key to brighten the backlight and
the down arrow key to dim the backlight. Press the
ESCAPE key when fin- ished to exit the mode.
Exren TEST ON Display Test is Enabled. The alarm and all mode
LED’s light up. The Navigator will display all block
segments.
fcNTfcfl &CAP£ Press Enter and Escape keys at the same time. The
Navigator will display ‘ADJUST CONTRAST’ with a
percentaae indication.
aa
Use the up arrow key to increase contrast and the
down arrow key to decrease the contrast. Press the
ESCAPE key when fin- ished to exit the mode.
a
DATE MNTH XX MONTH OF YEAR January, February, ele.
43
Table 24A — Example of Configuring Dual Chiller Control (Master Chiller)
▼ YEAR XXXX YEAR
DST ENT
ER STR.M XX MONTH Default: 4 Range: 1-12
a
STR.W X WEEK Default: 1 Ranae: 1-5
a
STR.D X DAY Default: 7 Range: 1-7
a
MIN.A XX MINUTES TO ADD Default: 60 Range: 0-99
a
STP.M XX MONTH Default: 10 Range: 1-12
a
STP.W XX WEEK Default: 5 Range: 1-5
a
STR.D XX DAY Default: 7 Range: 1-7
SCHD ENT
EI MON.O XX.XX MONDAY OCCUPIED TIME Default: 00.00 Range: 00.00 to 23.59
▼l MON.U XX.XX MONDAY UNOCCUIPED TIME Default: 00.00 Range: 00.00 to 23.59
a
TUE.O XX.XX TUESDAY OCCUPIED TIME Defaull: 00.00 Range: 00.00 to 23.59
▼ TUE.U XX.XX TUESDAY UNOCCUPIED TIME Defaull: 00.00 Range: 00.00 to 23.59
a
WED.O XX.XX WEDNESDAY OCCUPIED TIME Defaull: 00.00 Range: 00.00 to 23.59
a
WED.U XX.XX WEDNESDAY UNOCCUPIED TIME Delault: 00.00 Range: 00.00 to 23.59
a
THU.O XX.XX THURSDAY OCCUPIED TIME Defaull: 00.00 Range: 00.00 to 23.59
a
THU.U XX.XX THURSDAY UNOCCUPIED TIME Default: 00,00 Range: 00.00 to 23.59
a
FRI.O XX.XX FRIDAY OCCUPIED TIME Defaull: 00.00 Range: 00.00 to 23.59
▼ FRI.U XX.XX FRIDAY UNOCCUPIED TIME Default: 00.00 Range: 00.00 to 23.59
▼ SAT.O XX.XX SATURDAY OCCUPIED TIME Defaull: 00.00 Range: 00.00 to 23.59
▼ SAT.U XX.XX SATURDAY UNOCCUPIED TIME Default: 00.00 Range: 00.00 to 23.59
a
SUN.O XX.XX SUNDAY OCCUPIED TIME Defaull: 00.00 Range: 00.00 to 23.59
a
SUN.U XX.XX SUNDAY UNOCCUPIED TIME Default: 00.00 Range: 00.00 to 23.59
CCNA aí*nt
»
1 DEFAULT 1
!
CCNA Er* 1 CCN ADDRESS CHANGE IF REQUIRED
r£n
CCNB a 0 DEFAULT 0
▼ (▼ 15 ITEMS
44
Table 23 — Time Clock Mode and Sub-Mode Directory
jtmti DSBL VALUE FLASHES
a
MSSL
a
SLVA SLAVE ADDRESS
a
2 SELECT2
LLBL a
:
NI6
MASTER LEADS LEAD/LAG BALANCE SELECT VALUE FLASHES
f
▲ AUTOMATIC SELECT AUTOMATIC
LLBD a
jfcNU»| 168 LEAD/LAG BALANCE DELTA DEFAULT 168
tmtf
LLDY a
fcN
ffc
5 LAG START DELAY
M
tmíf 5 VALUE FLASHES
i
W
10 SELECT10
a
YES SELECT YES
1. The desired control method should be configured for the Master only. The slave is aiways configured for switch control.
2, Yes = Parallel piping configuration. No = Series piping configuration. Master and Slave chillers must both be configured for the same piping configuration.
45
Table 24B — Example of Configuring Dual Chiller Control (Slave Chiller)
SUB-MODE ITEM KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENT
OPT2 ORT2 tíffÉ
Fl
CTRL EK SWITCH CONTROL METHOD SEE NOTE 1
Ten
LQ SWITCH
CA
FE
SC CTRL
AP
CTRL S
▼ CCNA
▼ CCNB
a
MSSL MASTER/SLAVE SELECT
a
SLVE SELECT SLAVE
a
y 5 ITEMS
46
Table 27 — Configuring Temperature Reset
not automatically reset are not deleted until the to 20 mA signal. Accessory sensors must be used for
problem is corrected and the machine is reset. To ÓAT and SPT reset (HH79NZ023 for OAT and
clear manual reset alarms from the CCP modules, HH51BX006 for SPT). The Energy Management
press the reset button located on the CCP board Module (EMM) must be used for temperature reset
generating the alarm, for using a 4 to 20 mA signal.
5 seconds, (CCP1 for compressors Al or Bl, CCP2 To use the retum reset, four variables must be
for compressors A2 or B2). Next, follow the example configured. In the Configuration mode under the
in Table 26 to clear the alarm from the Main Base sub-mode RSET, items CRST, CRT1, CRT2, and
Board (MBB) history. DGRC must be set properly. See Tables 27 and 28 on
Alarm rélay usage alerts and alarms are page 37 for correct configuration.
configurable in (CONFIGURATION MODE, SUB- To reset the retum fluid temperature, the unit set
MODE OPT2) to be both one or the other or off point is reset from full load based on the chilled
paragraph. fluid retum tempera- ture. The example uses a reset
valué of 10 degrees at full reset. Full reset is at a 2-
Run Hours and Starts — The HOUR and STRT sub- degree temperature difference across the cooler
modes under the Run Status mode contain items for and no reset would be at a 10 F difference across
number of hours for each Circuit and each the cooler. See Fig. 14-17 and Table 29.
compressor and the total number of starts for each Under normal operation, the chiller will maintain
compressor. All items are password protected, but a constant leaving fluid temperature approximately
can be changed if a replacement MBB is installed. equal to the chilled fluid set point. As the cooler
Press Ei-mE" t0 make the current valué flash. Use load varíes, the entering cooler fluid will change in
the arrow keys to configure the correct valué and proportion to the load as shown in Fig. 14. Usually
press the key again. Record the current valúes from the chiller size and leaving-fluid temperature set
point are selected based on a full-load condition. At
the MBB before remov- ing the module or part load, the fluid temperature set point may be
downloading new software. colder than required. If the leaving fluid
Temperature Reset — The control system is capable temperature was allowed to increase at part load,
of handling leaving-fluid temperature reset based on the efficiency of the machine would increase.
retum cooler fluid temperature. Because the change Retum temperature reset allows for the leaving
in temperature through the cooler is a measure of temperature set point to be reset upward as a
the building load, the retum tempera- ture reset is function of the retum fluid temperature or, in effect,
in effect an average building load reset method. The the building load.
control system is also capable of temperature reset Figure 14 is an example of no reset. Figures 15,
based on outdoor-air temperature (OAT), space 16, and 17 are examples of outdoor air, space and
temperature (SPT), or from an extemally powered 4 retum water tempera- ture resets.
HIST ENTE
R AXXX or TXXX ALARM HISTORY Alarms are shown as AXXX. Alerts are
shown as TXXX.
CRNT JENTEF AXXX or TXXX CURRENTLY ACTIVE ALARMS ACTIVE ALARMS (AXXX) OR ALERTS (TXXX)
DISPLAYED.’
CRNT ESCAPE
s
NO Use to clear active alarms/alerts
a
YES Select YES
EmE ESC,F
Press | "| and | j simultaneously to display expanded alarm description.
47
MODE KEYPAD SUB-MODE KEYPAD ITEM DISPLAY ITEM COMMENT
ENTRY ENTRY EXPANSION
CONFIGURATION |
fiKTgñ DISP EMTEI* TEST ON/OFF TEST DISPLAY LEDs
s
UNIT TYPE X UN IT TYPE
a
OPT1 RNTtR FLUD X COOLER FLUID
a
OPT2 errEf! CTRL X CONTROL METHOD
a
RSET j&UTSf
t CRST X COOLING RESET TYPE 1 = No Reset
2 = 4 to 20 mA Input (EMM required)
(Connect to EMM J6-2.5)
3 = Outdoor-Air Temperature
(Connect to TB5-7.8)
4 = Return Fluid
5 = Space Temperature
(Connect to TB5-5.6)
s
CRT1 XXX.X F NO COOL RESET TEMP Default: 125 F (51.7 C)
Range: 0° to125 F
Set to 4.0 for CRST= 1
No Cool Reset AT for CRST=3
a
CRT2 XXX.X F FULL COOLRESETTEMP Default: 0° F (-17.8 C)
Range: 0° to 125 F
Set to 20.0 for CRST=1
Full Cool Reset AT for CRST=3
s
DGRC XX.X AF DEGREES COOL RESET Default: 0o F (0o C)
Range: -30 to 30 F (-16.7 to 16.7 C)
RSET ENTE
R CRST 3 COOLING RESET TYPE 1 = no reset
2 = 4 to 20 mA input
3 = Outdoor air temp
4 = Return Fluid
5 = Space Temperature
a
CRT1 10.0 F (5.5 NO COOL RESET TEMP Default: 125 F (51.7 C) Range: 0° to 125 F
C)
a
CRT2 2.0 F (1.1 FULLCOOL RESETTEMP Default: 0o F (-17.8 C)
C) Range: 0° to 125 F
a
DGRC 5.0 AF DEGREES COOL RESET Default: 0°F (0o C)
(2.8 AC) Range: -30 to 30 F (-16.7 to 16.7 C)
2I.I
12.
2 18.
3
1
£ I5.6
1.
1
O
UJ
10. |
0
9 I0.
=> 6.7
0
5.6
§,2
OUTSIDE TEMPERATURE (F)
4.4
% UNIT L0A01NG 4.4 7.2 10.0 12.8 15.6 18.3 21.1 23.9 26.7 29.4 32.2
LEGEND OUTSIDE TEMPERATURE (C)
EWT — Eníering Water (Fluid) Temperature LWT LEGEND
— Leaving Water (Fluid) Temperature LWT — Leaving Water (Fluid) Temperature
Fig. 15 — Outdoor-Air Temperature Reset
Fig. 14 — Cooling Return Water — No Reset
5.5
10
O 5.0 Ü. 9
w w
LU
LU 8
LU
4.4
^
LU § 7
- q
3 8
O
3.3 '
O6
Z 2.8 O
5
Z
2.2
< 1.7 04
H
LU -| -i
CO l
EWT
1,1
LU
LWT
tr .55 a h Fig. 18 — 4 to 20 mA Demand Limiting
ability to limit the current operating capacity to
máximum and further reduce the capacity if
required.
NOTE: The 2-stage switch control and 4- to 20-mA
input signal types of demand limiting require the
Energy Management Module (EMM).
To use Demand Limit, select the type of demand
limiting to use. Then configure the Demand Limit
set points based on the type selected.
DEMAND LIMIT (2-Stage Switch Controlled) — To
configure Demand Limit for 2-stage switch control
set the Demand Limit Select (DMDC) to 1. Then
configure the 2 Demand Limit Switch points (DLS1
SPACE TEMPERATURE (F)
and DLS2) to the desired capacity limit. See Table
18.3 18.9 19,4 20,0 206 21.1 21.7 22.2 22.8 23.3 29. Capacity steps are controlled by 2 relay switch
SPACE TEMPERATURE (C) inputs field wired to TB6.
LEGEND For Demand Limit by 2-stage switch control,
LWT — Leaving Water (Fluid) Temperature closing the first stage demand limit contact will put
Fig. 16 — Space Temperature Reset the unit on the first demand limit level. The unit
will not exceed the percentage of capacity entered
as Demand Limit Switch 1 set point. Closing
contacts on the second demand limit switch
prevenís the unit from exceeding the capacity
entered as Demand Limit Switch
FULL COOL 2 set point. The demand limit stage that is set to
^/nt at i i the lowest demand takes priority if both demand
limit inputs are closed. If the demand limit
t
CHANGE IN ,/A
RESET
VIUUI
percentage does not match unit staging, the unit
will limit capacity to the closest capacity stage.
POINT N \0 COOL
To disable demand limit configure the DMDC to
ESET AT
0. See Table 29.
EXTERNALLY POWERED DEMAND LIMIT (4 to 20
DESIGN RISE mA Controlled) — To configure Demand Limit for 4
to 20 mA
control
set the
Demand
Limit
Select
(DMDC)
to 2.
Then
01 2 3 4 5 6 7 8 9 1 0
TEMPERATURE DIFFERENCE (EWT-LWT) DEGREES F I
I I IIIIIIII
0 . 5 5 1 . 1 1 . 7 2 . 2 2 . 8 3 . 3 3 . 9 4 . 4
5 . 0 5 . 5
TEMPERATURE DIFFERENCE (EWT-LWT) DEGREES C configure the Demand Limit at 20 mA (DM20) to
the máximum loadshed valué desired. The control
LEGEND Entering Water (Fluid) Temperature Leaving
will reduce allowable capacity to this level for the
Water (Fluid) Temperature
20 mA signal. DEMAND LIMIT (CCN Loadshed
Fig. 17 — Return Water Reset Controlled) — To configure Demand Limit for CCN
Loadshed control set the Demand Limit Select
Demand Limit — Demand Limit is a feature that (DMDC) to 3. Then configure the Loadshed Group
allows the unit capacity to be limited during periods Number (SHNM), Loadshed Demand Delta (SHDL),
of peak energy us- age. See Fig. 18. There are 3 and Máximum Loadshed Time (SHTM). See Table
types of demand limiting that can be configured. 29.
The first type is through 2-stage switch control, The Loadshed Group number is established by
which will reduce the máximum capacity to 2 user- the CCN system designer. The ComfortLink™
configurable percentages. The second type is by 4 Control will respond to a Redline command from
to 20 mA signal input which will reduce the the Loadshed control. When the Red- line command
máximum capacity linearly between 100% at a 4 is received, the current stage of capacity is set to
mA input signal (no reduction) down to the user- the máximum stages available. Should the loadshed
configurable level at a 20 mA input signal. The third control send a Loadshed command, the
type uses the CCN Loadshed module and has the ComfortLink Control will
reduce the current stages by the valué entered Cooling Set Point (4 to 20 mA) — Unit operation is
for Loadshed Demand delta. The Máximum based on an extemal 4 to 20 mA signa) input to the
Loadshed Time is the defines the máximum length Energy Management Module (EMM). The signal is
of time that a loadshed condition is allowed to connected to TB6-3.5 (+,-). Figure 19 shows how
exist. The control will disable the Redline/Loadshed the 4 to 20 mA signal is linearly calculated on an o
command if no Cancel command has been received ve ral i 10 F to 80 F for both Water and Médium
within the configured máximum loadshed time Temperature Brine COOLER FLUID conftgura-
limit. tions. See Table 30 for configuration instructions.
Fig. 19 — Cooling Set Point (4 to 20 mA)
MODE KEYPAD SUB-MODE KEYPAD ITEM DISPLAY ITEM EXPANSION COMMENT
ENTRY ENTRY
CONFIGURATION ENT
ER DISP ENT
ER TEST ON/OFF Test Display LEDs
▼ UNIT ENT
ER TYPE X Unit Type
_ OPT1 ENT
ER FLUD X Cooler Fluid
a
OPT2 ENT
Ef CTRL X Control Method
a
CRT1 XXX.X °F No Cool Reset Temperature
a
CRT2 XXX.X °F Full Cool Reset Temperature
a
DMDC X Demand Limit Select Default: 0
1 = None
2 = Switch
3 = 4 to 20 mA Input
4 = CCN Loadshed
▼ DM20 XXX% Demand Limit at 20 mA Default: 100% Range: 0 to
100
a
SHNM XXX Loadshed Group Number Default: 0 Range: 0 to 99
a
SHDL XXX% Loadshed Demand Delta Default: 0% Range: 0 to 60%
a
SHTM XXX MIN Máximum Loadshed Time Default: 80 min. Range: Oto
120 min.
a
DLS1 XXX % Demand Limit Switch 1 Default: 80% Range: 0 to
100%
a
4 6.3 8.6 10.9 13.1 15.4 DLS2 17.7 XXX% 20 Demand Limit Switch 2 Default: 50% Range: 0 to
4 TO 20 mA SIGNAL TO EMM 100%
a
UNIT
a
OPT1
a
OPT2
▼ RSET
a
SLCT cwit CLSP 0 COOLING SETPOINT SELECT
n
tNI 0 Scrolling Stops
CH
0 Flashing '0'
a 4 Select ‘4'
51
Table 29 — Configuring Demand Limit
chiller is properly configured, including transducer failure alarm condi ti on from
options and/or accessories, using the CCP module Stoppage of one circuit by a
Configuration mode. For checklng specific safety device action does not affect other
items, refer to the Mode/Sub-Mode directoiy circuit. When a safety device trips, the
(Table 11). circuit is
Checking Display Codes — To determine shut down immediately and EXV closes.
how the machine has been programmed to Refer to Table 31 for typical stoppage faults
operate, check the diagnostic informaron and reset types.
displayed in the Status function and the
configuration información displayed in the A CAUTION
Service function.
If a stoppage occurs more than once as a
Unit Shutoff — To shut the unit off, move the result of any of the preceding safety
Enable/ Off/Remote Contact switch to the Off devices, determine and correct the cause
position. Both circuits will complete a before attempting another restart.
pumpdown cycle and all compressors and
solenoids will shut off. For extreme cases,
move the Emergency On/Off switch to the Off Restart Procedure — After the cause for
position. All compressors, solenoids and stoppage has been corrected, restart is
other outputs will stop immediately. either automatic or manual, depending on
Complete Unit Stoppage — Complete unit the fault. Manual reset requires that the
stoppage can be caused by any of the alarm(s) be reset via the Navigator. Select
following conditions: the RCRN item under the Alarms mode.
cooling load satisfied Press |enteb t |^j and
remóte on/off contacts again to reset all
open programmed
schedule emergency stop cunrent alarms and alerts. A password entry
command from CCN may be required. Some typical fault
general power failure conditions are described in Table 31. For a
blown fuse in control power complete list of fault conditions, codes and
feed disconnect open control reset type, see Table 32.
circuit fuse(s)
POWER FAILURE EXTERNAL TO THE UNIT
Enable/Off/Remote Contact switch moved
— Unit restarts automatically when power is
to Off position
restored.
freeze protection trip low flow protection
trip open contacts in chilled water flow Alarms and Alerts — These are wamings of
switch Open contacts in any auxiliary abnorma) or fault conditions and may cause
interlock. Termináis that are jumpcred either one circuit or the whole unit to shut
froin factory are in series with control down. They are assigned code numbers and
switch. Opening the circuit between these a detailed descriplion of tac!) alarm/alert
termináis places unit in Stop mode, code error including possibie causes is
similar to moving the control switch to Off shown in Table 32. The alarm descriptions
position. Unit cainiot start if these are displayed on the Navigator under the
contacts are open. If ihey open while unit ‘CRNT’ or ‘HIST’ sub-modes of the Alarms
is running, the unit stops mode. The Main Base Board also recognizes
cooler entering or leaving fluid thermistor and repoits illegal configurations as shown in
failure low/high transducer supply voltage Table 32.
loss of Communications between the Main When an alarm or alert is activated
Base Board (MBB) and either the EXV confígurable, the alarm relay output (MBB
board, SCB board or either CCP module relay K7, termináis TB5-11,12) is ener- gized.
low refrigerant pressure off-to-on delay is The alarms and alerts indícate failures that
in effect cause the unit to shut down, terminate an
option (such as reset) or result in the use of
A CAUTION a default valué such as a set point. Refer to
If a stoppage occurs more than once as a Table 32 for more information.
result of any of the above safety devices, Up to 50 alarms/alerts can be stored at
determine and correct the cause before once. Use Alarm and Alert tables to view and
attempting another restart. clear alarms. ComfortLink™ Compressor
Protection (CCP) module alarms require an
Single Circuit Stoppage — Single circuit additional step to reset alarms. To clear
stoppage can be caused by the following: these alarms, first find and correct the cause
of the alarm. Then press and hold the reset
low oil pressure button on the CCP board for 5 seconds. This
open contacts in high pressure switch low action will reset only the al arme d circuit or
refrigerant pressure thermistor failure compressor, and clear the CCP. Next, reset
52
the alarm(s) using the Navigator as shown in configuration header problem and restore
Table 26. For configuration header fault unit control power.
alarms from the CCP module, move the
Enable/Off/Remote Contact switch lo the Off Table 31 — Typical Stoppage Faults and Reset
position. Wait for all compressors to stop. Types
Turn off the unit control power. Correct the
53
Compressor Alarm/Alert Circuit — Each compres- fault condition for a compressor alert is included as
part of the
sor is directly controlled by a CCP module. Compressor faults alert description displayed on the Navigator.
Press [j™] and
(T051, T052, T055, T056) are reported as alerts. The specific 1ESCH simultaneously to display description.
Compressor A1 Low Oil Po-Ps < Oil Set Point 2. Comp A1 shut down Manual Low Water Temperature, low
Pressure - 2 See Note 1 and Fig. 20 on page refrigerant charge, plugged oil
49. filter, closed oil valve, bad oil
solenoid, compressor oil check
valve stuck, oil line check valve
stuck, plugged oil strainer
T027 Alert Compressor A2 Low Oil Po-Pe < OH Set Point 1. Comp A2 shut down Manual Low Water Temperature, low
Pressure -1 See Note 1 and Fig. 20 on page retrigerant charge, plugged oil
49. filter, closed oil valve, bad oil
solenoid, compressor oil check
valve stuck, oil line check valve
stuck, plugged oil strainer
Compressor A2 Low Olí P0-Ps Oil Set Point 2. Comp A2 shut down Manual Low Water Temperature, low
Pressure - 2 See Note 1 and Fig. 20 on page refrigerant charge, plugged oil
49. filter, closed oil valve, bad oil
solenoid, compressor oil check
valve stuck, olí line check valve
stuck, plugged oil strainer
T028 Alert Compressor B1 Low Oil Po-Pe < Oil Set Point 1. Comp B1 shut down Manual Low Water Temperature, low
Pressure - 1 See Note 1 and Fig. 20 on page refrigerant charge, plugged oil
49. filter, closed oil valve, bad oil
solenoid, compressor oil check
valve stuck, olí line check valve
stuok, plugged oil strainer
Compressor B1 Low Oil Po-Ps < Oil Set Point 2. Comp B1 shut down Manual Low Water Temperature, low
Pressure - 2 See Note 1 and Fig. 20 on page refrigerant charge, plugged olí
49. filter, closed oil valve, bad oil
solenoid, compressor oil check
valve stuck, oil line check valve
stuck, plugged oil strainer
T029 Alert Compressor B2 Low Olí Po-Pe < Oil Set Point 1. Comp B2 shut down Manual Low Water Temperature, low
Pressure -1 See Note 1 and Fig. 20 on page refrigerant charge, plugged oil
49. filter, closed oil valve, bad oil
solenoid, compressor oil check
valve stuck, oil line check valve
stuck, plugged oil strainer
Compressor B2 Low Oil Po-Ps < Oil Set Point 2. Comp B2 shut down Manual Low Water Temperature, Jow
Pressure - 2 See Note 1 and Fig. 20 on page refrigerant charge, plugged oil
49. filter, closed oil valve, bad oil
solenoid, compressor oil check
valve stuck, oil line check valve
stuck, plugged oil strainer
A030 Alarm Compressor A1 Pre- Oil Pump did not build suffi- Compressor cannot Manual Low oil, oil pump failure, olí
Start Oil Pressure cient pressure during pre-lube start. solenoid failure, oil transducer
cycle. failure, check valve failed open,
oil shutoff valve closed.
A031 Alarm Compressor A2 Pre- Oil Pump did not build suffi- Compressor cannot Manual Low oil, oil pump failure, olí
Start Oil Pressure cient pressure during pre-lube start. solenoid failure, oil transducer
cycle. failure, check valve failed open,
oil shutoff valve closed.
A032 Alarm Compressor B1 Pre- Oil Pump did not build sufti- Compressor cannot Manual Low oil, oil pump failure, oil
Start Oil Pressure cient pressure during pre-lube start. solenoid failure, oil transducer
cycle. failure, check valve failed open,
oil shutoff valve closed.
A033 Alarm Compressor B2 Pre- Oil Pump did not build suffl- Compressor cannot Manual Low oil, oil pump failure, oil
Slart Oil Pressure cient pressure during pre-lube start. solenoid failure, oil transducer
cycle. failure, check valve failed open,
oil shutoff valve closed.
ALARM/ALERT ALARM OR DESCRIPTION WHY WAS THIS ALARM ACTION TAKEN BY RESET PROBABLE CAUSE
CODE ALERT GENERATED? CONTROL METHOD
A034 Alarm Comp. A1 Max. Oil Delta (Discharge press - Oil press) > Comp. A1 shut down Manual Plugged oil filter, closed oil valve,
P, check olí Une 100 PSI for more than bad oil solenoid, compressor oil
5 seconds check valve stuck, oil line check
valve stuck, plugged oil strainer
54
Table 32 — Alarm and Alert Codes (cont)
A035 Alarm Comp. A2 Max. Oil Delta (Discharge press - Oil press) > Comp. A2 shut down Manual Plugged oil filter, closed oil valve,
P, check oil line 100 PSI for more than 5 bad oil solenoid, compressor oil
seconds check valve stuck, oil line check
valve stuck, plugged oil strainer
A036 Alarm Comp. B1 Max. Oil (Discharge press - Oil press) > Comp. B1 shut down Manual Plugged oil filter, closed oil valve,
Delta P, check olí line 100 PSI for more than bad oil solenoid, compressor oil
5 seconds check valve stuck, oil line check
valve stuck, plugged oil strainer
A037 Alarm Comp. B2 Max. Oil (Discharge press - Oil press) > Comp. B2 shut down Manual Plugged oil filter, closed oil valve,
Delta P, check oil line 100 PSI for more than 5 bad oil solenoid, compressor oil
seconds check valve stuck, oil line check
valve stuck, plugged oil strainer
A038 Alarm Comp. A1 Failed Oil Ditf. Oil Pressure > 2.5 PSI Comp. A1 not allowed to Manual Faulty oil solenoid valve
Solenoid during period after oil pump start
starts and before oil solenoid
opens
A039 Alarm Comp. A2 Failed Oil Ditf. Oil Pressure > 2.5 PSI Comp. A2 not allowed to Manual Faulty oil solenoid valve
Solenoid during period after oil pump start
starts and before oil solenoid
opens
A040 Alarm Comp. B1 Failed Oil Diff. Oil Pressure > 2.5 PS! Comp. B1 not allowed to Manual Faulty oil solenoid valve
Solenoid during period after oil pump start
starts and before oil solenoid
opens
A041 Alarm Comp. B2 Failed Oil Diff. Oil Pressure > 2.5 PSI Comp. B2 not allowed to Manual Faulty olí solenoid valve
Solenoid during period after oil pump start
starts and before oil solenoid
opens
ALARM/ALERT ALARM DESCRIPTION WHY WAS THIS ALARM ACTION TAKEN BY RESET PROBABLE CAUSE
CODE OR GENERATED? CONTROL METHOD
ALERT
Compressor A1 Failure See additional descriptions below.
T051 Alert - (See below)
Compressor A2 Failure
- (See below)
T052 Alert Compressor B1 Failure
- (See below)
T055 Alert Compressor B2 Failure
- (See below)
T056 Alert
High Pressure Switch HPS Input to CCP module Comp. shut down Manual Loss of condenser air/water flow.
Trip open Operation beyond chiller
capability. Liquid valve not open.
No Motor Current CCP reads less than 10% of Comp. shut down Manual Power supply disconnected,
MTA on all legs for >3.0 blown fuse(s), wiring error, con-
seconds tactor not energized, faulty current
toroid, check toroid wiring.
Current Unbalance CCP measures current Circuit shut down Manual Loose termináis on power wires.
imbalance between phases Alert will be generated if
must be above C.UNB for 25 measured imbalance exceeds set
minutes point.
' Single Phase Current CCP measures current Circuit shut down Manual Blown fuse, wiring error, loose
Loss imbalance between phases termináis
greater than 50% (running
current <50% of MTA) or 30%
(running current > 50% of MTA)
for 1 second.
High Motor Current CCP detects high currenl Comp. shut down Manual Operation beyond chiller capability,
compared to MTA setting ¡mproperly punched configuration
header, blown fuse
Ground Fault Trip CCP detects ground current Comp. shut down Manual Motor winding(s) gone to ground,
(4.0 ± 2.0 amps) wiring error, loose plug connector.
Contactor Failure CCP detects min. 10% of MTA All remaining com- Manual Faulty contactor, contactor
for 10 seconds after shutting off pressors shut down. All welded, wiring error.
compressor contactor. Oil loaders deenergized.
solenoid is energized. Min. load valve of
affected circuit
energized (if equipped)
Current Phase Reversal CCP detects phase reversal Circuit shut down Manual Terminal block power supply leads
from toroid reading or from not in correct phase. Toroid wire
incoming power supply. harness crossed. Check
compressor contactor.
55
Table 32 — Alarm and Alert Codes (cont)
Motor Over CCP detects motor winding Comp. shut down Manual Motor cooling (all) or Economizer
Temperature temperature >245 F (2 comp. circuits) solenoid failure,
low refrigerant charge. Faulty
economizer TXV or poor bulb
connection to motor cooling line.
Open Thermistor CCP detects open circuit in Comp. shut down Manual Wiring error or faulty thermistor*
motor temp thermistor
MTA Header Fault CCP finds error with MTA valué Comp. shut down Manual Header pins on CCP board either
punched out in header. all or none punched out, header
not fully seated in CCP board.
MTA Valué Error MTA valué stored In MBB does Comp. not allowed to Manual Header pin(s) on CCP board not
not agree with MTA header start punched out correctly. See
valué from CCP. Appendix A. Incorrect slze or
voltage entered when MBB was
downloaded.
Shorted Thermistor CCP detects short circuit in Comp. shut down Manual Wiring error or faulty thermistor*
motor temp thermistor
A060 Alarm Cooler Leaving Fluid Thermistor outside range of -40 Automatic Thermistor failure, damaged
Thermistor Failure - 1 to 240° F (-40 to116° C) Chiller shut down Chiller cable/wlre or wiring error.
Cooler Leaving Fluid LWT > EWT + 5o F for 15 Manual Thermistor failure, damaged
Thermistor Failure - 2 minutes cable/wire, wiring error or water
shut down
piping error.
A061 Alarm Cooler Entering Fluid Thermistor outside range of -40 Automatic Thermistor failure, damaged
Uses 0.1xF/% Total
Thermistor Failure to 240° F (-40 to 116° C) Capacity as rise/ton cable/wire or wiring error.
T062 Alert Condenser Leaving Thermistor outside range of -40 None. Chiller continúes Automatic Thermistor failure, damaged
Fluid Thermistor Failure to 240" F (-40 to 116° C) to run. cable/wire or wiring error.
Condenser Entering
T063 Alert Fluid Thermistor Failure Thermistor outside range of -40 None. Chiller continúes Automatic Thermistor failure, damaged
to 240° F (-40 to 116° C) to run. cable/wire or wiring error.
T070 Alert Clr. A Discharge Gas Average of compressor A1 and Circuit A shut down Manual Thermistor failure, damaged
Thermistor Failure A2 (if installed) sensors > 210° cable/wire, wiring error or motor
Ffor 30 seconds. cooling solenoid failure.
ALARM/ ALARMO DESCRIPTION WHY WAS THIS ALARM ACTION TAKEN BY RESET PROBABLE CAUSE
ALERT R ALERT GENERATED? CONTROL METHOD
CODE
T071 Alert Cir. B Dlscharge Gas Average of compressor B1 and Circuit B shut down Manual Thermistor failure, damaged
Thermistor Failure B2 (if installed) sensors > 210° cable/wire, wiring error or motor
F for cooling solenoid failure,
30 secón ds.
T073 Alert Outside Air Tempera- Thermistor outside range of -40 Reset disabied. Runs Automatic Thermistor failure, damaged
ture Thermistor Failure to 240 F (-40 to116C) under normal control/ set cable/wire, wiring error or sensor
points. not installed
T074 Atert Space Temperature Thermistor outside range of -40 Reset disabied. Runs Automatic Thermistor failure, damaged
Thermistor Failure to 240 F (-40 to 116 C) under normal control/ set cable/wire, wiring error or sensor
points. not installed.
T075 Alert Compressor A1 Thermistor outside range of- 40 Comp A1 shut down Automatic Thermistor failure, damaged
Discharge Gas to 240° F (-40 to 116° C) cable/wire, wiring error or motor
Thermistor Failure cooling solenoid failure.
T076 Alert Compressor A2 Thermistor outside range of- 40 Comp A2 shut down Automatic Thermistor failure, damaged
Discharge Gas to 240° F (-40 to 116° C) cable/wire, wiring error or motor
Thermistor Failure cooling solenoid failure.
T077 Alert Compressor B1 Thermistor outside range of - 40 Comp B1 shut down Automatic Thermistor failure, damaged
Discharge Gas to 240° F (-40 to 116° C) cable/wire, wiring error or motor
Thermistor Failure cooling solenoid failure.
T078 Alert Compressor B2 Thermistor outside range of - 40 Comp B2 shut down Automatic Thermistor failure, damaged
Discharge Gas to 240° F (-40 to 116° C) cable/wire, wiring error or motor
Thermistor Failure cooling solenoid failure.
T079 Alert Lead/Lag Leaving Fluid Thermistor outside range of -40 Breaks Dual Chiller link Automatic Thermistor failure, damaged
Temperature Thermistor to 240 F (-40 to 116 C) if set up for Parallel cable/wire, wiring error or sensor
Failure operation. not installed.
T090 Alert Circuit A Discharge Voltage ratio more than 98.9% or Circuit A shut down Automatic Transducer failure, poor con-
Pressure Transducer less than 6%. nection to MBB, or wiring
Failure damage/error.
T091 Alert Circuit B Discharge Voltage ratio more than 98.9% or Circuit B shut down Automatic Transducer failure, poor con-
Pressure Transducer less than 6%. nectlon to MBB, or wiring
Failure damage/error.
T092 Alert Circuit A Suction Voltage ratio more than 99.9% Circuit A shut down Automatic Transducer failure, poor con-
Pressure Transducer or less than 0.5% for 50 nectlon to MBB, or wiring
Failure seconds. damage/error.
T093 Alert Circuit B Suction Voltage ratio more than 99.9% Circuit B shut down Automatic Transducer failure, poor con-
Pressure Transducer or less than 0.5% for 50 nection to MBB, or wiring
Failure seconds. damage/error.
56
Table 32 — Alarm and Alert Codes (cont)
T094 Alert Comp A1 Oil Pressure Voltage ratio more than 98.9% or Comp A1 shut down Automatic Transducer failure, poor con-
Transducer Failure less than 6%. nection to SCB, or wiring
damage/error.
T095 Alert Comp A2 Oil Pressure Voltage ratio more than 98.9% or Comp A2 shut down Automatic Transducer failure, poor con-
Transducer Failure less than 6%. nection to SCB, or wiring
damage/error.
T096 Alert Comp B1 Oil Pressure Voltage ratio more than 98.9% or Comp B1 shut down Automatic Transducer failure, poor con-
Transducer Failure less than 6%. nection to SCB, or wiring
damage/error.
T097 Alert Comp B2 Oil Pressure Voltage ratio more than 98.9% or Comp B2 shut down Automatic Transducer failure, poor con-
Transducer Failure less than 6%. nection to SCB, or wiring
damage/error.
T098 Alert Circuit A Economizer Voltage ratio more than 99.9% Circuit A shut down Automatic Transducer failure, poor con-
Pressure Transducer or less than 0.5% for 50 nectlon to SCB, or wiring
Faiture — 1 seconds. damage/error.
Alerl Circuit A Economizer Economizer pressure is more Circuit A shut down Manual Suction and Economizer pressure
Pressure Transducer than 12 psi (83 kPa) less than connectors/wiring are swapped.
Failure - 2 suction pressure.
T099 Alert Circuit B Economizer Voltage ralio more than 99.9% Circuit B shut down Automatic Transducer failure, poorcon-
Pressure Transducer or less than 0.5% for 50 nection to SCB, or wiring
Failure - 1 seconds, damage/error.
Alert Circuit B Economizer Economizer pressure is more Circuit B shut down Manual Suction and Economizer pressure
Pressure Transducer than 12 psi (83 kPa) less than connectors/wiring are swapped.
Failure - 2 suction pressure.
T110 Alert Circuit A Loss of Discharge pressure reading <10 Circuit A shut down Manual Refrigerant leak or transducer
Charge psig for 30 seconds. failure.
T111 Alert Circuit B Loss of Discharge pressure reading < 10 Circuit B shut down Manual Refrigerant leak or transducer
Charge psig for 30 seconds. failure.
ALARM/ ALARM DESCRIPTION WHY WAS THIS ALARM ACTION TAKEN BY RESET PROBABLE CAUSE
ALERT OR GENERATED? CONTROL METHOD
CODE ALERT
T120 Alert o
Circuit A Low Saturated SST reads 6 F (3.3° C) or more Circuit A shut down Manualf Low refrigerant charge, plugged
Suction Temperature below the brine freeze point for 3 stralner, faulty expansión valve,
minutes or 28° F below brine or low water flow.
freeze point for 2 minutes.
T121 Alert Circuit B Low Saturated SST reads 6o F (3.3° C) or more Circuit B shut down Manualf Low refrigerant charge, plugged
Suction Temperature below the brine freeze point for 3 strainer, faulty expansión valve,
minutes or 28° F below brine or low water flow.
freeze point for 2 minutes.
T122 Atert Circuit A High Saturated After first 90 seconds, SST > 55 Circuit A shut down Manual Faulty expansión valve or
Suction Temperature F (12.8 C) and EXV < 1% for 5 transducer.
minutes.
T123 Alert Circuit B High After first 90 seconds, SST > 55 Circuit B shut down Manual Faulty expansión valve or
Saturated Suction F (12.8 C) and EXV < 1% for 5 transducer.
Temperature minutes.
T124 Alert Circuit A Low Oil Level switch input open. Circuit A shut down after Manual Low oil level, failed switch, wiring
Level/Flow 4th failure in 18 hours. error, failed control module.
T125 Alert Circuit B Low Oil Level switch input open. Circuit B shut down after Manual Low oil level, failed switch, wiring
Level/Flow 4th failure in 18 hours. error, failed control module.
T126 Alert Circuit A High Dis- SCT > MCT SP + 5° F (2.8° C) Circuit A shut down. Automatic" Faulty transducer/high pressure
charge Pressure switch, low/restricted condenser
air/water flowtt
T127 Alert Circuit B High Dis- SCT > MCT SP + 5°F 2.8° C) Circuit B shut down. Automatic** Faulty transducer/high pressure
charge Pressure switch, low/restricted condenser
air/water flowtt
A128 Alarm Circuit A Condenser For water cooled chillers only, if Chiller shut down. Turns Automatic Falléd/bad discharge pressure
Freeze Protection SCT <34 F (1.1 “C) condenser pump On if transducer, refrigerant leak,
(alarm ignored for brine Chiller is Off. configured for water- cooled
chillers) condenser.
A129 Alarm Circuit B Condenser For water cooled chillers only, if Chiller shut down. Turns Automatic Failed/bad discharge pressure
Freeze Protection SCT < 34 F (1.1 ° C) condenser pump On if transducer, refrigerant leak.
(alarm ignored for brine Chiller is Off. configured for water- cooled
chillers) condenser.
T135 Alert Circuit A Failure to With EXV closed, SST did not None Manual Faulty transducer or EXV.
Pump Out drop 10° F (5.6° C) in 6 minutes,
or SST is not 6° F (3.3° C) less
than Brine Freeze, or SST Is not
less than 10 F (-12 C).
57
Table 32 — Alarm and Alert Codes (cont)
T136 Alert Circuit B Failure to With EXV closed, SST did not None Manual Faulty transducer or EXV
Pump Out drop 10° F (5,6° C) in 6 minutes,
or SST is not 6° F (3.3° C) less
than Brine Freeze, or SST is not
less than 10 F (-12 C).
T137 Alert Circuit A Low Dis- Superheat < 5° F (2.8° C) for 10 Circuit A shut down Manual Faulty thermistor, transducer,
charge Superheat minutes. EXV, or Economizer TXV. Motor
cooling solenoid stuck open.
T138 Alert Circuit B Low Dis- Superheat < 5° F (2,8° C) for 10 Circuit B shut down Manual Faulty thermistor, transducer,
charge Superheat minutes. EXV, or Economizer TXV. Motor
cooling solenoid stuck open.
T140 Alert Compressor A1 - High Oil filter pressure drop (FD.A1) None Manual Filter change needed to prevent
Oil Filter Pressure Drop exceeds 25 psig 172 kPa) for machine from shutting down.
water-cooled units or 30 psig
(207 kPa) for air-cooled and split
system units.
T141 Alert Compressor A2 - High Oil filter pressure drop (FD.A2) None Manual Filter change needed to prevent
Oil Filter Pressure Drop exceeds 25 psig (172 kPa) for machine from shutting down.
water-cooled units or 30 psig
(207 kPa) for air-cooled and split
system units.
ALARM/ALERT ALARM DESCRIPTION WHY WAS THIS ALARM ACTION TAKEN BY RESET PROBABLE CAUSE
CODE OR GENERATED? CONTROL METHOD
ALERT
T142 Alert Compressor B1 - High OH filter pressure drop (FD.B1) None Manual Filter change needed to prevent
Oil Filter Pressure Drop exceeds 25 psig (172 kPa) for machine from shutting down.
waler-cooled units or 30 psig
(207 kPa) for air-cooled and
split system units.
T143 Alert Compressor B2 - High Oil filter pressure drop (FD.B2) None Manual Filter change needed to prevent
Oil Filter Pressure Drop exceeds 25 psig (172 kPa) for machine from shutting down.
water-capíed units or 30 psig
(207 kPa) for air-cooled and
split system units.
A150 Alarm Unit is in Emergency CCN command received to Chiller shut down CCN/ Network command
Stop shut unit down Automatic
A151 Alarm lllegal Configuration-x lllegal Configuration has been Chiller cannot start. Manual Configuration error
entered. Correction needed. See Table 33.
A152 Alarm Circuit A&B Off for Alerts. Control has shut down both None Automatic Check individual alarms.
Unit down. circuits due to alerts.
T153 Alert Real Time Clock Hard- Time not advancing on board, Defaults to occupied Automatic Time clock not inltialized or board
ware Failure fail
A154 Alarm Serial EEPROM Hard- Internal failure of the EEPROM. Machine shuts down Manual Replace Main Base Board.
ware Failure
A155 Alarm Serial EEPROM Stor- Internal diagnostic has found Machine shuts down Manual Re-download the software of
age Failure Error an error on critical data. consider replacement of the Main
Base Board.
A156 Alarm Critical Serial EEPROM Internal diagnostic has found Machine shuts down Manual Replace Main Base Board.
Storage Failure Error an error on critical data.
A157 Alarm A/D Hardware Failure A/D converter on the MBB has Machíne shuts down Manual Replace Main Base Board.
failed.
A159 Alarm Loss of Condenser Flow How switch not closed within 1 Chiller shut down. Manual Low condenser water flow, failed
minute after pump is started or condenser pump.
if flow switch opens during
normal operation for > 10 sec.
A172 Alarm Loss of Communlca- tion MBB has lost communication Chiller shut down. Automatic Failed EXV Module, wiring error,
with EXV Module with the EXV Module loose connections, failed
transformer, wrong address.
T173 Alert Loss of Communication MBB has lost communication EMM options are Automatic Failed EMM, wiring error, loose
with Energy Man- with the Energy Management disabled. connections, failed transformer,
agement Module Module when this option is wrong address, wrong configu-
installed. ration.
T174 Alert 4-20 mA Cool Setpoint If configured and input signal to Function disabled. Automatic Faulty signal generator, wiring
Input Failure EMM less than 2 mA or greater Normal set point ussd. error, loss of signal
than 22 mA.
T175 Alert 4-20 mA Heat Setpoint If configured and input signal to Function disabled. Automatic Faulty signal generator, wiring
Input Failure EMM less than 2 mA or greater Normal set point used. error, loss of signal
than 22 mA.
58
Table 32 — Alarm and Alert Codes (cont)
T176 Alert 4-20 mA Reset Input Out If configured and input signal to Reset function dls- Automatic Faulty signal generator, wiring error
of Range EMM less than 2 mA or greater abled. Normal set point loss of signal
than 22 mA. used.
T177 Alert 4-20 mA Demand Limit If configured and input signal to Reset function disabled. Automatic Faulty signal generator, wiring
Input Out of Range EMM less than 2 mA or greater Normal set point used. error, loss of signal
than 22 mA.
A178 Alarm Loss of Communication MBB has lost communication Chiller shut down. Automatic Failed SCB Module, wiring error,
with Screw Chiller with the Screw Chiller Module loose connections, failed
Module transformer, wrong address.
A180 Alarm Loss of Communication MBB has lost communication Chiller shut down. Automatic Failed CCP Module, wiring error,
with Compressor with the Compressor Protection loose connections, failed
Protection Module 1 Module 1 transformer, wrong address.
A181 Alarm Loss of Communication MBB has lost communication Chiller shut down. Automatic Failed CCP Module, wiring error,
with Compressor with the Compressor Protection loose connections, failed
Protection Module 2 Module 2 transformer, wrong address.
59
Table 32 — Alarm and Alert Codes (cont)
ALARM/ALERT ALARM DESCRIPTION WHY WAS THIS ALARM ACTION TAKEN BY RESET PROBABLE CAUSE
CODE OR ALERT GENERATED? CONTROL METHOD
T182 Alert Compressor Protec- tion The ComfortLink™ Compres- Affected compressors are Manual on Elimínate EMI sources around the
Module 1 Interna! sor Protection Module has shut down. CCP and module, consider replace- ment of
Diagnostlc generated an Infernal diagnostic MBB the CCP module if alerts continué.
alert.
T183 Alert Compressor Protec- tion The ComfortLmk Compres- sor Affected compressors are Manual on Elimínate EMI sources around the
Module 2 Infernal Protection Module has generated shut down. CCP and module, consider replace- ment of
Diagnostic an internal diagnostic alert. MBB the CCP module if alerts continué.
T184 Alarm Compressor Protec- tion CCP has experienced too many Chiller shut down Manual Loose connections, frequent
Module 1 power cycles*** power interruptions.
T185 Alarm Compressor Protec- tion CCP has experienced too many Chiller shut down Manual Loose connections, frequent
Module 2 power cycles*** power interruptions.
A200 Alarm Cooler Pump Inter- lock Interlock did not cióse within 5 Chiller shut down. Pump Manual Failure of cooler pump, cooler
Failed at Start-Up minutes after chiller was enabled turned off. pump Interlock, or flow switch
A201 Alarm' Cooler Pump Inter- lock Interlock opened for at least 10 Chiller shut down. Pump Manual Failure of cooler pump, cooler
Opened Unexpectedly seconds during operation and turned off. pump interlock, or flow switch
does not cióse within
A202 Alarm Cooler Pump Inter- lock Interlock closed when pump Cooler pump remains off. Manual Failure of cooler pump relay or
Closed When Pump relay is off Unit preventedfrom interlock, welded contacts. Cooler
OFF starting. pump enabled but mot controlling
pump
T203 Alert Loss of Communica- The master chiller (when con- Master chiller runs as a Automatic Failed Slave MBB Module, wiring
tion with the Slave figured) has lost communica- stand-alone chiller. error, loose connections, wrong
Chiller tion with the slave chiller for 3 address, loss of control power on
minutes. slave chiller.
T204 Alert Loss of Communica- The slave chiller (when con- Slave chiller runs as a Automatic Failed Master MBB Module, wiring
tion with the Master figured) has lost communica- stand-alone chiller. error, loose connections, wrong
Chiller tion with the master chiller for 3 address, loss of control power on
minutes. master chiller.
T205 Alert Master and Slave Chiller The master chiller (when con- Dual chiller control dis- Automatic Master and Slave chiller must
with Same Address figured) has determlned that its abied. have different addresses.
address ¡s the same as the slave
address.
T206 Alert High Leaving Chilled LCW read > LCW Delta Alarm None. Automatic Building load greaterthan unit
Water Temperature limit and total capacity Is 100% capacity, low water/brine flow, or
and current LCW > LCW reading compressor fault. Check for other
1 minute ago alarms or alerts.
A207 Alarm Cooler Freeze Protec- Cooler EWT or LWT less than Chiller shut down. Leave Automaticf Faulty thermistor, low water flow
tion freeze point. Freeze point is the Cooler pump on. Turn
brine freeze setpoint +2 F (1.1 Cooler pump on if Chiller
C). is off.
T210 Alert Winterization SCT<32 F in either circuit None Manual Winterization must be per- formed
Required to avoid cooler freeze- up. After
winterization has been completed,
configure W.DNE Winterization
Performed (Con- figuration Mode,
Sub-mode SERV) to YES to reset
alert.
T950 Alert Loss of Communica- No Communications have been WSM forces removed. Automatic Failed module, wiring error, failed
tion with WSM received by the MBB within 5 Runs under own control. transformer, loose con- nection
minutes of transmission. plug, wrong address
A951 Alarm Loss of Communica- No Communications have been CSM forces removed. Automatic Wiring faulty or module failure
tion with Chillervisor received by the MBB within 5 Runs under own control.
System Manager minutes of last transmission.
(CSM)
T998 Alert Loss of Refrigerant Between 40 and 90 seconds of Circuit A compressor is Manual Refrigerant restriction such as
Flow in Circuit A. runtime, SST is less than 0° F (- shut down. closed suction Service valve,
18 C) and the rate of change is closed liquid line Service valve,
negative (in 5 sec- ond faulty liquid line solenoid valve,
increments). faulty EXV/Economizer operation,
plugged refrigerant strainer, closed
discharge line valve.
T999 Alert Loss of Refrigerant Between 40 and 90 seconds of Circuit B compressor is Manual Refrigerant restriction such as
Flow in Circuit B. runtime, if SST is less than 0° F shut down. closed suction Service valve,
(-18 C) and the rate of change is closed liquid line Service valve,
negative (in 5 sec- ond faulty liquid line solenoid valve,
increments). faulty EXV/Economizer operation,
plugged refrigeran! strainer, closed
discharge line valve.
60
LEGEND AND NOTES FOR TABLE
Oil Set Point 1 is
defined as:
A/D — Analog to Digital Converter
a.If Ps < 35, then Oil Set
CCN — Carrier Comfort NetworkPoint 1 = 1 0 psig.
CCP — ComfortLink™ Compressor
b.If Ps > 35 Protection
and < 51, then
EMI — Electromagnetic Interference
Oil Set Point 1 =12.5
EMM — Energy Management Module psig.
EWT — Entering Water Temperature
c. If Ps > 51, then Oil Set
EXV — Electronic Expansión Valve Point 1 = 1 5 psig.
HPS — High-Pressure Switch
LCW — Leaving Chilled Water Oil Set Point 2 (see
LWT — Leaving Water Temperature Fig. 20) is defined
MBB — Main Base Board as:
MCT SP — Máximum Condensing a.If (P d - Ps) < 125,
Temperature then
Set Point
MTA — Compressor Must Trip Amps Oil Set Point 2
SCB — Screw Compressor Board ='0.235 x (Pd - Ps )+
SCT 0.588
— Saturated Condensing Temperature
SST — Saturated Suction b.If (Pd - Ps) > 125 and <
Temperature
TXV — Thermostatic Expansión 165, Valve then Oil Set
WSM — Water-System Manager Point 2 = 2.0 x ( P d -
P s ) - 220.0
c. If (Pd - Ps) > 165 then Oil
'Compressors are Set Point 2 = 0.6364
equipped with 2 x (Pd - Ps) + 5.0
motor winding 2.(P0 - Pe) is the Oil
temperature pressure differential
thermistors. Verify displayed as items
first that the problem DO.A1 and DO.A2
is not a wiring error (Pressures mode
before using backup under sub-mode
thermistor. PRC.A) for Circuit A
IManual reset after 1 and DO.B1 and
hour from DO.B2 (Pressures
occurrence. mode under sub-
"Reset automatic first mode PRC.B) for
time, manual if Circuit B.
repeated on the 3.Alert criteria is based on
same date. tfNote operating time.
that the high- a.On time less than 5
pressure switch seconds oil pressure
should trip before this is ignored.
alert is generated. b.On time between 5 and
Check HPS 120 seconds, the
operation if this alert alert will be gener-
is generated. ated if the following
•"Máximum 5 power condition is true for
losses at CCP in one 3 consecutive read-
hour. ings:
NOTES: (P0 - Pe) < [15
1.Low Oil Pressure Alert psig/120 sec.] x
Criteria and Set [Compressor Run
Points Time in sec.]
Where: Pd = c. On time greater Ihan
Discharge Pressure, 120 seconds Ihe
P? = Suction alarm will be
Pressure. generated if one of
P0 = Oil Pressure the following
and Pe = condilions is true:
Economizer (P0 - Pe) < Oil Set
Pressure Point 1 for 15
Two oil set points seconds.
are used by the (P0 - Ps) < Oil Set
control for the Low Point 2 for 15
Oil Pressure seconds.
alert trip.
18
0
16
0
140
tn
Q.
CM" 120
O £
100
LU
§ 80
O)
05
LU
£ 60 O
40
2
0
0
0 10 20 30 40 50 60 70 00 90 100 110 120 125 130 140 150 160 165 170 100 190 200 210 220 230 240
(DISCHARGE-SUCTION) PRESSURE, PSI
Fig. 20 — Oil Pressure Set Point 2
Calculation
63
hold |^j undl 100% is Observe the operation of the
lead screw and sleeve. The motor should be
tuming the lead screw and sleeve
counterclockwise, raising the sleeve closer to
the motor. Lead screw movement should be
smooth and uniform from fully closed to fully
open position. Press ENTEB , use Q to select 0%
and press ENTEB again to check open to closed
operation. If the valve is properly connected to
the processor and receiving correct signáis, yet
does not operate as described above, the sealed
motor portion of the valve should be replaced.
PL-EXVB
YEL
J7
GR Y
REO
O EXV-A
GRr
RED
64
BRAZED-PLATE ECONOMIZERS — Brazed-plate NOTE (non-economized units only): Frosting of
econo- mizers are factory-installed in each circuit on valve is normal during compressor test steps and at
30GXN,R108, 118-350 and 30HXA,C161-271 initial start-up. Frost should dissipate after 5 to 10
models. A TXV is included to meter the flow of minutes operation in a system that is operating
refrigerant to the economizer port of the properly. If valve is to be replaced, wrap valve with
compressor. Flow íhrough the TXV is enabled only a wet cloth to prevent excessive heat from
when the circuit is fully loaded for 30GXN.R models. damaging intemal components.
The TXV bulb is secured to the side of the Fig. 22 — Brazed-Plate Economizer
economizer outlet tube. See Fig. 22 for typical
piping arrangement.
Brazed-plate heat exchangers cannot be repaired
if they de- velop a leak. If a refrigerant leak is
detected, the heat exchanger must be replaced. To
replace a brazed-plate heat exchanger the following
steps must be perfonned:
1. Using proper techniques, move the refrigerant
remaining in the circuit to the high side and
cióse the discharge and liquid line ball valves.
Reclaim any refrigerant remaining in the low
side.
2. Un-solder the refngerant-in and refrigerant-out
connections.
3. Remove the four 8mm (V4-2O on 30HX units)
nuts holding the heat exchanger to the
brackets. Save the nuts and hardware.
4. Check that the replacement heat exchanger is
the same as the original heat exchanger.
5. Insulate the new heat exchanger to match the
original and attach to the mounting brackets
with the hardware removed in Step 3.
6. Carefiilly braze the refrigerant lines to the
connections on the heat exchanger. Lines
should be soldered using silver as the soldering
material with a mínimum of 45% silver. Keep
the temperature below 1472 F (800 C) under
normal soldering conditions (no vacuum) to
prevent the copper solder of the brazed píate
heat exchanger from changing its structure.
Failure to do so can result in Ínter- nal or
extemal leakage at the connections which
cannot be repaired.
7. Braze equalizer line in place if removed. Attach
economizer and motor cooling solenoid coils to
their bodies if removed.
8. Dehydrate and recharge the circuit. Check for
leaks. NOTE: The brazed-plate heat economizers
are not serviceable.
If operating problems persist after economizer ITEM ft-lb n-m
replacement, they may be due to a bad liquid level Sighi Glass 15-25 20-34
sensor, suction pressure transducer. discharge gas
Seal Cap 18-22 24-30
thermistor or intermiltent connections between the
processor board termináis and EXV plug. Recheck Fig. 23 — Typical 30GXN,GXR,HX EXV
all wiring connections and voltage signáis.
SERVICE
Other possibie causes of improper refrigerant flow
control could be restrictions in the liquid line. Servicing Coolers and Condensers — When cool-
Check for plugged strainer(s) or restricted metering er heads and partition plates are removed, tube
slots in the EXV (see Fig. 23). Formation of ice or sheets are exposed showing the ends of tubes. The
frost on lower body of electronic expansión valve is 30GXN,GXR,HX units use a flooded cooler design.
one symptom of restricted metering slots. However, Water flows inside the tubes. TUBEPLUGGING — A
frost or ice formation is normally expected when leaky tube in one circuit can be plugged uhtil
leaving fluid temperature from the cooler is below retubing can be done. The number of tubes
40 F (4.4 C). Clean or re- place valve if necessary. plugged determines how soon the cooler must be
retubed. All tubes in the 30GXN,R and 30HX
coolers and 30HX condensers can be removed.
Loss of unit capacity and efficiency as well as
increased pump power will result from plugging
tubes. Failed tubes should be replaced as soon as
possible. Up to 10% of the total number of tubes
can be plugged before retubing is necessary. Figure
24 shows an Elliott tube plug and a cross- sectional
view of a plug in place. The same components for
plugging and rolling tubes can be used for all
65
ECONOMIZER TXV
BRAZED
PLATE
ECONOMIZER
coolers and 30HXC condensers. See Table 34. If Tube sheet hole diameter: 0.756 19.20
Tube OD 0.750 19.05
tube failure is in both circuits, using tube plugs will Tube ID after rolling: 0.650 16.51
not correct problem. Contact your Carrier (includes expansión to to
representative for assistance. due to clearance) 0.667 16.94
A CAUTION
Use extreme care when installing plugs to
prevent damage to the tube sheet section
between the holes. PIN AND RING INSTALLED Fig.
NOTE: Tubes replaced along heat exchanger head partitions must be flush with tube sheet.
66
0 0 'X,
/L±J 0\
/0 0^
10 0y
\m □/
V 3 0^
CONDEN the
SERS entering
(30HX and
Only) — leaving
Since this condense
water r water
circuit is thermisto
usually an rs (if
open-type instalied)
system, for signs
the tubes of
may be corrosion
subject to or scale.
contamin Replace
ation and the
scale. sensor if
Clean the corroded
condense or remove
r tubes any scale
with a if found.
rotary Higher
tube íhan
cleaning normal
system at condense
regular r
intervals, pressures
and more , together
often if with in-
the water ability to
is reach full
contamin refrigerat
ated. ion load,
Inspect usually
indícate scratchin
dirty g the tube
tubes or wall.
air in the Contact
machine. your
If the Carrier
refrigerat represent
ion log ative to
indicates obtain
a rise these
above brushes.
normal Do not
condense use wire
r brushes.
pressures
, check A
the CAUTIO
condense
r
N
refrigeran Hard
t scale
temperat may
ure requir
against e
the chemi
leaving cal
condense treat
r water ment
temperat for its
ure. If preve
this n- tion
reading is or
more remov
than what al.
the Consu
design lt a
difference water
is treat
supposed ment
to be, specia
then the list for
condense prope
r tubes r
may be treat
dirty, or ment
water proce
flow may dures.
be
incorrect.
Due to
the
pressure
in the R-
I34a
system,
air
usually
will not
emer the
machine;
the
refrigeran
t will leak
out.
During
the tube
cleaning
process,
use
brushes
specially
designed
to avoid
scraping
and
Water treated
Treatmen water.
t —
Untreated Condens
orimprop er Coils
erly (30GXN,
treated R only)
water COIL
may CLEANI
result in NG —
corrosion, For
scaling, standard
erosión, aluminu
or algae. m,
The ser- copper
vices of a and pre-
qualifíed coated
water aluminu
treatment m fin
specialist coils,
should be clean the
ob- tained coils
to with a
develop vacuum
and cleaner,
monitor a fresh
treatment water,
program. compres
A sed air,
CAUTIO or a
N bristle
Water brush
must be (not
within wire).
design Units
flow instalied
limits, in
clean corrosive
and environ
treated ments
to should
ensure have coil
proper cleaning
machine as part
performa of a
nce and planned
reduce mainten
the ance
potemial schedule
of tubing . In this
damage type of
due to applicati
corrosio on, all
n, accumul
scaling, ations of
erosión, dirt
and should
algae. be
Carrier cleaned
assumes off the
no coil.
responsi
bility for A
chiller or CAUTIO
condens N
er Do not
damage use high-
resulting pressure
from water or
untreate air to
d or clean
improper coils —
ly fin
damage
may
result.
CLEANI
NG E-
COATED
COILS —
Follow
the
outlined
pro-
cedure
below
for
proper
care,
cleaning
and
mainten
ance of
E-coated
aluminu
m or
copper
fin coils:
Coil
Mainten
ance and
Cleaning
Recomm
endation
s — Rou-
tine
cleaning
of coil
surfaces
is
essential
to
maintain
proper
operatio
n of the
unit.
Eliminati
on of
contamin
ation
and
removal
of
harmful
resitlues
will
greatly
increase
the lile
of the
coil and
extend
the life
of the
unit.
Remove Periodic
Surface Clean
Loaded Water
Fibers — Rinse — A
Surface periodic
loaded clean
fibers or water
dirt rinse is
should be very
removed beneficial
with a for coils
vacuum that are
cleaner. If applied in
a vacuum Coastal or
cleaner is industrial
not environm
available, ents.
a soft However,
brush it is very
may be important
used. In that the
either water
case, the rinse is
tool made with
should be very low
applied in velocity
the water
direction stream to
of the avoid
fins. Coil damaging
surfaces the fin
can be edges.
easily Monthly
damaged cleaning
(fin edges as
bent over) descríbed
if the tool below is
is applied recomme
across the nded.
fins. Routine
NOTE: Cleaning
Use of a of Coil
water Surfaces
stream, —
such as a Monthly
garden cleaning
hose, with
against a Environm
surface entally
loaded Sound
coil will Coil
drive the Cleaner is
fibers and essential
dirt into to extend
the coil. the life of
This will coils. It is
make recomme
nded that
cleaning
all coils,
efforts
including
more
standard
difficult. aluminum
Surface , pre-
loaded coated,
fibers copper/co
must be pper or E-
completel coated
y removed coils are
prior to cleaned
using low with the
velocity Environm
clean entally
water Sound
rinse. Coil
Cleaner
as Environm
descríbed' entally
below. Sound
Coil Coil
cleaning Cleaner
Applicatio
should be n
part of Equipmen
the units t
regularly • 2V2
scheduled Gallón
maintena Garden
nce Sprayer
procedure •
s to
W
ensure
long life at
of the er
coil. Ri
Failure to n
clean the s
coils may e
result in w
reduced it
durability h
in the L
environm o
ent. w
Environ V
mentally el
Sound o
Coil ci
Cleaner is ty
non- S
flammabl
p
e,
hypoaller ra
genic, y
non- N
bacterial, o
USDA zz
accepted le
biodegrad E
able and n
100% vi
ecological ro
ly safe n
agent that m
will not e
harm the nt
coil or al
surroundi ly
ng S
componen
o
ts such as
u
electrical
wiring, n
painted d
metal C
surfaces oi
or l
insulation. Cl
Use of e
non- a
recomme n
nded coil er
cleaners A
is strongly p
discourag pl
ed since ic
coil and at
unit io
durability n
could be
In
affected.
st
r p
u r
c- o-
ti te
o ct
n io
s n
— s
Al u
th c
o h
u a
g s
h s
E af
n et
vi y
ro gl
n a
m ss
e e
nt s
al is
ly re
S c
o o
u m
n m
d e
C n
oi d
l e
Cl d
e d
a u
n ri
er n
is g
h m
ar ix
m in
le g
ss a
to n
h d
u a
m p
a pl
n ic
s, at
a io
ni n.
m 1. Remo
al ve all
s, surfa
a ce
n loade
d d
m fibers
ar and
dirt
in
with
e
a
lif vacu
e, um
p clean
ro er as
p descr
er íbed
e abov
y e.
e
2. Thor y
oughl apply
y wet Envir
finne onme
d ntally
surfa Soun
ces d Coil
with Clean
clean er
water soluti
and a on to
low all
veloci coil
ty surfa
garde ces
n inclu
hose ding
finne
being
d
caref
area,
ul not
tube
to sheet
bend s and
fins. coil
3. Mix head
Envir ers.
onme 5. Hold
ntally garde
Soun n
d Coil spray
Clean er
er in nozzl
a 2V2 e
galló cióse
n to
garde finne
n d
spray areas
er and
accor apply
ding clean
to the er
instr with
uctio a
ns vertic
inclu al,
ded up-
with and-
the down
Enzy motio
me n.
Clean Avoid Fig. 26 — Condenser Fan Position (Standard Fan)
er. spray
The ing in
optim horiz
um ontal
soluti patte
on m to
temp mini
er- mize
ature poten
is tial
100 for
F. fin
NOTE: DO dama
NOT USE ge. 2.15 INCHES (54.6 mm) ABOVE FAN DECK SURFACE
water in 6. Ensu
excess of re Fig. 27 — Condenser Fan Position (High-
130 F as the clean Static Fan)
enzy- matic er
activity will thoro
be ughly
destroyed. penet
4. Thor rales
oughl deep
into clea
finne n
d wate
areas r
. usin
Interi g
or dow
and nwa
exteri rd
or rinsi
finne ng
d moti
areas on
must of
be wate
thoro r
ughly spra
clean y
ed. nozz
Finne le.
d Prot
surfa ect
ces fins
shoul from
d dam
remai age
n wet from
with the
clean spra
ing y
soluti nozz
on le.
for
10 A
minut CAUTIO
es.
Ensu
N
re Harsh
surfa Chemic
ces al and
are Acid
not Cleaner
allow s —
ed to Harsh
dry chemic
befor al,
e househ
rinsin old
g. bleach
Reap or acid
ply cleaner
clean s
er as should
need not be
ed to used to
ensur clean
e 10- outdoor
minut or
e indoors
satur coils of
ation any
is kind.
achie These
ved. cleaner
7. Thor s can
oug be very
hly difficult
rins to rinse
e all out of
surf the coil
aces and can
with acceler-
low ate
velo corrosi
city on at
the Condens
fin/tube er Fans
interfac (30GXN,
e where R Only)
dissimil — Each
ar fan is
materia supporte
ls are in d by a
contact. formed
If there wire
is dirt mount
below bolted to
the a fan
surface deck and
of the covered
coil, with a
use the wire
Environ guard.
mentall The
y Sound exposed
Coil end of
Cleaner the fan
as motor
describ shaft is
ed protected
above. from
High weather
Velocity by
Water grease. If
or the fan
Compre motor
ssed Air must be
— High removed
velocity for
water Service
from a or
pressur replacem
e ent, be
washer, sure to
garden regrease
hose or fan shaft
compre and
ssed air reinstall
should fan cover,
never retaining
be used clips, and
to clean fan
a coil. guard.
The For
forcé of proper
the performa
water nce, the
or air fans
jet will should be
bend positione
the fin d as
edges shown in
and Fig. 26 or
increas 27.
e Tighten
airside setscrew
pressur s to 14 ±
e drop. 1 ft-lb
Reduce (18+1.3
d unit N-m).
perform Check
ance or for
nuisanc proper
e unit rotation
shutdo of the
wn may fan(s)
occur. once
reinstalle
d
(clockwis
e for high
static
and
countercl
ockwise
for
standard
viewed
from
above). If
necessar
y to
reverse,
switch
leads at
contactor
(s) in
control
box.
Refrigera dama
nt ge is
Charging/ consid
Adding ered
Charge abuse
IMPO and
RTAN may
T: void
These the
units Carrie
are r
desig warra
ned nty.
for
use
with A
R- CAUTIO
134a N
only. DO
DO NOT
NOT OVER
USE CHAR
ANY GE
OTHE syste
R m.
REFRI Overc
G- hargin
ERAN g
T in result
these s in
units higher
withou discha
t first rge
Consul press
ting ure
your with
Carrie higher
r coolin
repres g fluid
entativ consu
e. mptio
n,
possib
A le
CAUTIO compr
N essor
When dama
addin ge
g or and
remov higher
ing power
consu
charg
mptio
e,
n.
circuí
ate Indication
water of low
throu charge on
gh the a system:
conde NOTE: To
nser check for
(30HX low
C) refrigeran
and t charge
cooler on a
30HXC
at all
unit,
times
several
to
factors
preve must be
nt considere
freezi d. A
ng. flashing
Freezi liquid line
ng
sight B’
glass depe
(located ndin
in tlie g on
EXV the
body) is circu
not it
necessaril unde
y an r
indication inves
of -
inadequat tigati
e charge. on.
There are The
many circu
system it is
condition fully
s where a loade
flashing d if
sight its
glass comp
occurs resso
under r and
normal loade
operation. r
The EXV relay
metering s all
device is show
designed ‘On’.
to work 2. It
properly may
under be
these nece
condition ssary
s. to
1. Make use
sure the
that Servi
the ce
circu Test
it is featu
runni re to
ng at forcé
a the
full- circu
load it
cond into
ition. a
To full-
chec load
k condi
whet tion.
her If
circu this
it A is the
is case,
fully see
loade the
d, instr
enter uctio
the ns
Outp for
uts using
mode the
from Servi
the ce
Navi Test
gator featu
and re in
then Table
sub- 13 of
mode this
‘CIR. manu
A’ or al.
‘CIR.
3. With 161-
ihe 271
circu mode
it ls.
runni 4. At
ng at this
full condi
load, tion,
verif obser
y ve
that the
the refri
coole gera
r nt in
leavi the
ng liqui
fluid d line
temp sight
eratu glass
re is . If
in there
the is a
rang clear
e of sight
38 to glass
46 F , and
(3.3 no
to signs
7.8 of
C). flashi
Chec ng,
k then
temp the
eratu circu
re it is
drop adeq
acros uatel
s y
liqui char
d line ged.
strai Skip
ner/d the
rier. rema
Máxi ining
mum steps
allow .
able 5. If the
temp refri
eratu gera
re nt
drop appe
is 3o ars
F to be
(1.7° flashi
C). ng,
Strai the
ner circu
is it is
clean prob
able ably
if low
nece on
ssary char
and ge.
conta Verif
ins 1 y this
stand by
ard chec
drier king
core the
on all EXV
30GX Perce
and nt
30HX Open
A,C . This
Infor char
mati ge
on is for
locat 30HX
ed C
unde units.
r the To add
sub* charge to
mode the
‘CIR. 30HXC
A’ or systems:
'CIR. 1. Make
sure
B'
(Out that
the
puts
mode unit
is
) and
is runni
ng at
show
n as fiall
load,
items
‘EXV. and
that
A’
and the
coole
‘EXV.
B’ r
leavi
Scrol
l ng
fluid
throu
gh temp
eratu
the
Navi re is
in
gator
until the
rang
the
desir e of
42 to
ed
item 46 F
(5.6
is
locat to
7.8
ed.
6. If the
C).
2. At
EXV
Perce these
opera
nt
Open ting
condi
is
great tions,
check
er
than the
liquid
60%,
and line
sight
the
liqui glass.
If
d line
sight there
is a
glass
is clear
sight
flashi
ng, glass,
then
then
the the
unit
circu
it is has
suffic
low
on ient
charg
char
ge. e. If
the
Follo
w the sight
glass
proc
edur is
flashi
e for
addin ng,
then
g
check m of
the the
EXV coole
Perce r.
nt This
Open fittin
. íí g is
this locat
is ed
great betw
er een
than the
60%, Elect
then ronic
begin Expa
addin nsión
g Valve
charg (EXV)
e. and
NOT the
E: A coole
flashi r.
ng 4. Obse
liquid rve
line the
sight EXV
glass Perce
at nt
opera Open
ting valué
condi . The
tions EXV
other shoul
than d
those begin
menti closin
g as
oned
charg
abov
e is
e is
being
not adde
nece d.
s- Allow
sarily the
an unit
indic to
ation stabil
of ize. If
low the
refrig EXV
erant Perce
charg nt
e. Open
3. Add 5 remai
Ib ns
(2.3 abov
kg) of e
liquid 60%,
charg and
e into the
the sight
coole glass
r conti
using núes
the flashi
fittin ng,
g add
locat an
ed on additi
the onal
tube 5 Ib
enter (2.3
ing kg) of
the liquid
botto
charg clear
e. sight
5. Allow glass.
the This
unit shoul
to d be
stabil done
ize, slowl
and y to
again avoid
check overc
the hargi
EXV ng
Perce the
nt unit.
Open 7. Verify
. adeq
Conti uate
nué charg
addin e by
g 5 Ib conti
(2.3 nuing
kg) at to
a run
time at full
of load
liquid with
refrig 42 to
erant 46 F
charg (5.6
e, ío 7.8
and C)
allow coole
the r
unit leavi
to ng
stabil fluid
ize temp
befor er-
e ature
check .
ing Chec
the k that
EXV the
positi refrig
on. erant
6. When is not
the flashi
EXV ng in
Perce the
nt liquid
Open -line
is in sight
the glass.
range The
of 40 EXV
to Perce
60%, nt
check Open
the shoul
liquid d be
line betw
sight een
glass. 40
Slowl and
y add 60%.
enou To add
gh charge tó
additi the 30GX
onal and
liquid 30HXA
systems:
charg
1. Make
e to sure
ensur
that
e a
the resso
circui r and
t is loade
runni r
ng at relay
a full s all
load show
cond ‘On’.
ition 2. It
and may
all be
cond neces
enser sary
fans to
are use
energ the
ized Servi
and ce
runni Test
ng on featu
the re to
keyp forcé
ad, at the
the circui
appro t into
priat a full-
e line load
on condi
the tion.
displ If this
ay. To is the
check case,
whet see
her the
circui instr
t A is uctio
fully ns for
loade using
d, the
enter Seivi
the ce
Outp Test
uts featu
mode re in
from Table
the 13 of
Navi this
gator manu
and al.
then 3. With
sub- the
mode circui
‘CIR. t
A’ or runni
‘CIR. ng at
B’ full-
depe load,
nding verify
on that
the the
circui coole
t r
unde leavi
r ng
inves fluid
tigati temp
on. eratu
The re is
circui in the
t is range
fully of 38
loade to 48
d if F
its (5.6
comp
to7.8 for
C). 30HX
4. For A
30HX units.
A For
chille 30GX
rs, N.R
raise units,
the meas
comp ure
resso the
r liquid
disch temp
arge eratu
to re
appro after
ximat the
ely tee
125 F wher
(51.7 e all
C) liquid
satur lines
ated have
cond joine
ensin d
g (see
tem- Fig.
perat 28
ure and
(185 29).
psig The
[1276 liquid
kPaJ). temp
For eratu
30GX re
N,R shoul
chille d be
rs, appro
raise ximat
the ely
comp 107 F
resso (41.7
r C) for
disch optim
arge um
to charg
appro e. If
ximat the
ely temp
130 F eratu
(54.4 re is
C) great
satur er
ated than
cond 107 F
ensin (4! .7
g C)
temp and
eratu the
re sight
(198 glass
psig is
[1366 flashi
kPa]). ng,
Meas the
ure circui
the t is
liquid unde
temp rchar
eratu ged.
re 5. Add 5
enter Ib
ing (2.3
the kg) of
EXV liquid
charg y add
e into charg
the e as
coole the
r sight
using glass
the begin
fittin s to
g clear
locat to
ed on avoid
the overc
tube hargi
enter ng.
ing
the
botto
m of
the
coole
r.
This
fittin
g is
locat
ed
betw
een
the
Elect
ronic
Expa
nsión
Valve
(EXV)
and
the
coole
r.
6. Allow
the
syste
m to
stabil
ize
and
then
reche
ck
the
liquid
temp
eratu
re.
Repe
at
Step
5 as
need
ed
allow
ing
the
syste
m to
stabil
ize
betw
een
each
charg
e
additi
on.
Slowl
(CIRCUIT B) ■ (CIRCUIT A)
Fig. 29 — This oil is
Saturated available
Liquid in the
Temperatu following
re quantitie
Measurem s from
ent your
(30GXN,R1 local
53,163- Carrier
350) represen
tative
(see
Oil Table
Charging 36).
/Low Oil
Rechargi Table 36 —
ng Available
OIL Oii
SPECIFI Quantities
CATION and Part
— If oil is Numbers
added, it TOTALINE PART NUMBER RCDPART
NUMBER
must
P903-1225 —
meet the
P903-1201 PP23BZ104-001
following
P903-1205 PP23BZ104-005
Carrier
specifica Additio
tions: n of
oil
• Castro char
l ge to
30H
Icematic X,GX
® SW- N,GX
220 R
• Oil syste
type........................ ms:
Inhibited 1. If
polyolest the
er-based 30H
synthetic X,G
compress XN,
or GXR
lubricant unit
for use in shut
screw s off
compress repe
ors. ated
• ISO ly on
Viscosity Low
Grade Oil
220 Leve
l e if
(Aler the
t unit
num does
ber not
124 nor
or mall
125) y
, run
this at
may full
be load.
an 3. Afte
indic r
atio runn
n of ing
inad the
equa unit
te for
oil U/2
char hour
ge. s,
It allo
coul w
d the
also unit
mea to
n rest
simp art
ly and
that run
oil is nor
in mall
the y. If
proc the
ess Low
of Oil
bein Leve
g l
recl alar
aime ms
d pers
from ist,
the cont
low- inué
side follo
of wing
the this
syst proc
em. edur
2. Begi e.
n by 4. Ciós
runn e
ing the
the liqui
unit d
at line
full Serv
load ice
for valv
1V2 e,
hour and
s. plac
Use e a
the pres
Man sure
ual gage
Cont on
rol top
feat of
ure the
of cool
the er.
soft Ena
war ble
the its
Serv nor
ice mal
Test pre-
feat lube
ure pum
usin p
g routi
the ne.
Navi If
gato ther
r e is
and an
tum insuf
the fi-
EOR cien
swit t
ch level
to of
Ena oil
ble. in
Star the
t the oil
desi sepa
Solenoi
d 1
Orange
wire, 1
Brown
wire*
High-
Pressur
e
Switch
2 Red
wires
*One lead
from the
motor
cooling
anú oil
solenoids
are con-
nected
together
with a
single
brown
wire.
A CAUTION
Compressor oil is
pressurized. Use proper
safety precautions when
relieving pressure.
Fully from seat (cióse) the LOADER
SOLENOI
angle valve on the filter and D NO. 2
OIL
the ball valve at the SOLENOID
compressor. Connect a LOADER
SOLENOI
charging lióse to the oil D NO. 1
pressure bleed port and OIL
FILTER
drain the oil trapped SERVICE
hetween service valves. A PORT
oil seáis
NOTE: Lócate strap from center of gravity lifting ring and support motor casing
to provide 3-point level rigging.
Fig. 31 — Compressor Lifting Diagrams
are no-
made mizer
using line
O-rings. flange
Use to the
care compr
when essor.
removin 9. Remo
g bolts ve the
and four
disconn M14
ecting bolts
flanges. securi
The O- ng the
rings discha
must rge
NOT be line
re-used. flange
New O- to the
rings compr
are essor.
provide Two
d with of the
the bolts
replace also
ment secur
compre e the
ssor. mount
The 06N ing
screw brack
compress et for
ors weigh the
approxim extern
ateJy 920 a] oil
Ib (417 filter.
kg). Be Suppo
sure rt the
that an oil
appropr line to
iate preve
lifting nt
cart or dama
hoist is ge to
used to the
avoid line
injury. while
See Fig. the
31 for compr
lifting essor
location is
s and being
center chang
of ed.
gravity For
dimensi 30GX
ons. units,
Make place
sure tempo
compre rary
ssor is prote
properl ction
y rigged over
before coils
unboltin to
g. preve
nt fin
8. Remo and
ve the tube
2 dama
bolts ge.
securi 10.Move
ng the lifting
motor appar
coolin atus
g/eco into
place n
and flange
attach of the
to the cooler
2 lift- . The
ing com-
rings press
on the or is
compr held
essor. in
Apply place
minim using
al four
tensió M14 x
n to 2
hold studs
the throu
compr gh the
essor suctio
while n
the nozzle
remai of the
ning cooler
bolts . The
are studs
remov have
ed. an E-
11.Remo 12
ve the extem
3
/g-in. al
holdd Torx
own drive
bolt head.
securi If
ng the possib
foot at le,
the remov
discha e
rge studs;
end of if
the studs
compr hit
essor the
to the cooler
mount insula
ing tion,
brack leave
et on them
the in
cooler place
. A —
foot they
brack will
et will not
be interf
mount ere
ed to with
the compr
replac essor
ement remov
compr al
essor. orinst
12.Remo allatio
ve the n.
4 Save
lockw all the
asher hardw
s and are as
nuts it will
securi be
ng the neede
compr d to
essor install
to the the
suctio replac
ement are
compr free
essor. and
out of
L the
I
F
way,
T remov
I e
N comp
G ressor
from
L cooler
U .
G Apply
S
a
B light
O film
T of O-
H ring
greas
O e to
U new
T O-
S
I ring
D and
E place
back
E into
D groov
G e in
E moun
S ting
E flange
Q of
U comp
I ressor
D . If
I the
S new
T comp
A ressor
N
T is the
A1/A2
F (30H
R X
O units)
M , A2
(30GX
G N,R20
E
4-268
A
R units)
or B2
C (30GX
O N,R28
V 1-350
E units)
R comp
ressor
E
N
,
D remov
e the
COMPRE comp
SSOR
LIFTING ressor
MECHANI juncti
SM on
13. After box
check and
ing to rotate
ensur it 180
e all degre
lines, es.
wires, Tight
condu en
its, screw
etc. s to
6.8 to of
9.5 N- 81.4
m (5 to
to 7 135.6
ft-lb). N-m
The (60 to
Al 100
and ft-lb).
A2 Do
comp NOT
ressor overti
s are ghten
on as
the dama
right ge
side may
of the result
unit to O-
when ring.
facing Instal
the l and
unit tighte
contr n
ol holdd
box. own
14. Remo bolt
ve in
suctio moun
n ting
cover foot.
píate 15. Remo
and ve
bolts motor
from coolin
new g/eco
comp nomiz
res- er
sor and
and disch
set arge
comp line
ressor cover
on plates
unit from
flange new
. comp
Threa ressor
d the .
studs 16. Apply
all a
the light
way film
back of O-
into ring
the greas
comp e to
ressor motor
. coolin
Instal g/
l the econo
4 lock mizer
wash- and
ers disch
and arge
nuts line
finger O-
-tight. rings,
Tight place
en back
bolts into
in a groov
Crossing es
patter and
n to a install
range flange
bolts. ferrul
Tight e
en seats
disch again
arge st
line fitting
bolts .
in a Threa
Cro d
ssi packi
ng ng
patte nut
m to a onto
range fitting
of and
81.4 tighte
to n
135.6 finger
N-m tight.
(60 to Use a
100 backu
ft-lb). p
Tight wrenc
en h to
motor finish
coolin tighte
g/eco ning
nomiz the
er nut.
bolts Do
to a not
range overti
of ghten
81.4 .
to 18. Reinst
108.5 all
N-m the
(60 to loade
80 ft- r and
lb). oil
Do solen
NOT oids,
overti high-
ghten press
as ure
dama switc
ge h, and
may oil
result press
to O- ure
rings. trans
17. Recon ducer.
nect Make
the sure
oil the
filter loade
to the r
shutof solen
f oids
valve are
and install
oil ed on
line the
to the corre
comp ct
ressor numb
. er
Instal loader
l oil .
line 19. Recon
straig nect
ht condu
into its
fitting back
until into
comp Temp
ressor oraril
juncti y wire
on the
box. rever
Recon se
nect rotati
all on
wirin low
g that press
was ure
remov switc
ed in h in
Steps series
4, 5, with
and 7. the
Temp comp
oraril ressor
y ’s
install high
the press
rever ure
se switc
rotati h as
on show
low n in
press Fig.
ure 32.
switc 20. Leak
h that check
is comp
suppli ressor
ed and
with refrig
the erant
replac lines
ement with
comp nitro-
ressor gen.
. Repai
Conn r any
ect leaks
the found
switc .
h to Remo
the ve
secon nitrog
d en
high from
press syste
ure m.
port Evacú
using ate
a comp
stand ressor
ard and
V^in. refrig
Servi erant
ce lines.
hose. Refer
The to the
switc Refrig
h will erant
not Charg
reset ing/A
until dding
10 psi Charg
g of e and
press Oil
ure is Charg
prese ing/L
nt on ow
the Oil
switc Recha
h. rging
sectio turn
ns on the
pages TEST
55 sub-
and mode
56 for ‘On’.
recha Unde
rging r the
proce OUTS
dures. sub-
21. Open mode,
all test
shutof each
f comp
valves ressor
and ’s oil
leak and
check motor
the coolin
circui g
t and solen
all oids
fitting (items
s and ‘MC.A
joints. 1’,
Repai ‘OS.A
r any 1’,
leaks etc.).
found Next,
. lócate
22. Reset and
the test
revers each
e loade
rotati r
on
low solen
press oid
ure under
switch the
. COM
23. Resto P sub-
re mode
main (items
and ‘LD.A
contr 1’,
ol etc.).
power It is
to the impor
machi tant
ne. that
Put the
the loade
Enabl rs are
e/Off/ locate
Remo d
te prope
Conta rly
ct (loade
switc r 1 on
h in right
the hand
Enabl side
e when
posi- viewe
tion. d
Using from
the side
Navig oppos
ator ite
under contr
the ol box
Servi on
ce 30HX
Test A,HX
mode, C
units,
on
left
hand
side
when
reach
ing
over
comp
ressor
to far
side
on
30GX
N,R
units)
.
-» -------------- Once
«—
the
HPS
comp
LE
G resso
E r has
N
D succe
HPS — High-
Pressure ss-
Switch fully
RRS —
Reverse start
Rotation
Switch ed,
(HK01C
B002) energ
Fig. ize
32 — both
Rever loade
se
Rotati rs
on one
Switc at a
h
Wirin time.
g Let
the
24. Lócat circui
e the t
appr stabil
opria ize
te with
comp both
resso loade
r rs
item energ
(‘CC. ized.
A1’, Refer
etc.) to
unde the
r the Refri
COM geran
P t
sub- Cbar
mode ging/
and Addi
start ng
the Char
comp ge
resso and
r. Oil
Press Char
| ging/
E«TE Low
H| I Oil
follo Rech
wed argin
by |¿] g
to secti
chan ons
ge of
the this
valué docu
to ment
On, for
and recha
then rging
again proce
. dures
and procedur
perfo e
provides
rman the
ce minimimi
criter steps to
ia. be Utken
25. Once before
prope restartin
r g the
rotati circuit.
on 1. Remo
has ve
been the
verifi oil
ed, from
disco the
nnect oil
and separ
lock ator.
out This
the can
powe be
r to fácil
the i-
chille tated
r. The by
rever conn
se ectin
rotati g a
on lióse
low to
press the
ure port
switc locat
h can ed on
now the
be servi
remo ce
ved valve
from enter
the ing
comp the
res- exle
sor mal
and oil
high filter.
press Run
ure ihe
switc hose
h to a
circui conta
t. iner(s
BURNO ) tiiai
UT can
CLEAN- hokl
UP up to
PROCED 5 to 6
URE — If gailo
a screw ns
com- (19
prcssor to 20
motor L) of
bums out oil.
on a Press
30GX,HX tirize
chiller, a the
simple circui
cleanup t to
should forcé
be out
performe most
d. The of the
following oil in
the
separ Chan
ator. geout
To Sequ
remo ence
ve proce
the dure
remai on
ning page
oil, 57.
the 3. Once
pre- the
lube comp
pump resso
can r is
be remo
run ved
in the acces
Servi s the
ce oil
Test catch
mode pan
from throu
the gh
Navi the
gator. eooie
Enabl r-
e the comp
desir resso
ed r
pump moun
(eithe ting
r flang
item e.
‘OL.P. Clean
A’ or out
'OL.P. any
B' in debri
the s
OUT whic
S h
sub- may
mode have
). To collec
pre- ted in
vent the
wear oil
to catch
the pan.
pump 4. Instal
comp l a
onent new
s, do comp
not ressor
.
allow
the 5. To
pre- dilute
lube and
pump remo
to ve
opera any
te resid
“dry.” ual
2. Remo oil
ve left
the in the
failed separ
comp ator,
resso pump
r appr
follo oxim
wing ately
the V2
Com galló
press n (2
or L) of
comp bumo
resso ut
r oil (activ
into ated
the carbó
oil n)
separ core
ator may
using be
the used,
Schr but
ader shoul
port d be
locat repla
ed on ced
top of with
the a
separ stand
ator ard
(30G filter
XN,R drier
) or core
on durin
the g the
disch next
arge filter
line repla
(30H ceme
XA,H nt.
XC) 8. Meas
and ure
remo in the
ve amou
using nt of
the Castr
pre- ol SW
lube 220
pump Polyo
descr lester
ibed oil as
in speci
Step fied
1. on
6. Disco the
nnect name
the plate
hose of the
from chille
the r.
exte 9. Leak
mal chec
oil k,
filter evac
servi úate
ce and
valve recha
. rge
7. Instal the
l a mach
new ine
filter as
drier descr
core ibed
and in
comp this
resso manu
r al
exter with
nal the
oil amou
filter. nt of
If R-
desir 134a
ed, a state
d on system is
the measured
chille in parts
r per
name million
plate. (ppm),
10. Perfo changes
rm of color of
perio indicator
dic are:
acid Green
chec —
ks on moistur
the e is
circui below
t and 80
chan ppm;
ge Yel
the lo
filter w-
drier gr
core ee
in the n
liquid (cb
line art
as reu
neces se)
sary. —
Use 80
the to
Cairi 22
er 5
Stan pp
dard m
Servi (ca
ce uti
Tech on)
nique ;
s Yel
Manu lo
al as w
a (w
sourc et)
e of —
refer ab
ence. ove
Moisture- 22
Liquid 5
Indicator pp
— Clear m.
flow of
liquid Change
refrigera filter
drier at
nt the first
indicates sign of
sufficient moistur
charge in e in the
the system.
system.
Note, IMPOR
however, TANT:
that Unit
bubbles must in
in ihe operati
siglit on for
glass do at least
not 12 ho
riecessari urs
ly indí- befor
cate e
insufficie moist
nt ure
charge. indic
Moisture ator
in the can
give drier core
an in each
accu strainer.
rate See Fig.
readi 33.
ng. Liquid
With Line
the Service
unit Valve —
runni This valve
ng, is located
the ahead of
indic the filter
ating drier and
elem provides
ent a '/¿i-in.
must Schrader
be in connec-
conta tion
ct (30GXN,R
with only) for
liqui field
d charging.
refri In
gera combinati
nt to on with
give compress
true or
readi discharge
ng. service
valve,
Filter each
Drier — circuit
Whenever can be
moisture- pumped
liquid down into
indicator the high
shows sitie for
presence servicing.
of
moisture, Thermist
replace ors — To
filter aid in
drier verifying
core. thermisto
Refer to r perfor-
Carrier mance,
Standard resistanc
s Service es at
Techniqu various
e Manual, temperat
Chapter ures are
1, listed for
Refrigera all
nts, for thermisto
details on rs (except
servicing motor
filter thermisto
driers. rs) in
Cleanable Tables
strainers 38A-39B.
have been See Table
instalied 40 for
in each motor
circuit’s thermisto
liquid line r valúes.
to aid in LOCATIO
removal N—
of system General
contamin location
ants and
of
debris.Th
ere is one thermisto
industry r sensors
standard and
terminal te
connectio connector
ns in the from the
Main
control
Base
box are Board
listed in (MBB) or
Table 3. Screw
THERMIS Compress
TOR or Board
REPLACE (SCB).
MENT Thermisto
rs TI and
T2 are
¿k connecte
CAUTIO d lo MBB-
N J8 and
All thermisto
thermis rs T3
tors are through
instalie T6 are
d in connecte
wells d to EXV-
and J5. These
will six
slide thermisto
out of rs use
the insula-
wells tion
easily. displacem
The ent
wells connector
are s. New
under thermisto
refriger rs should
ant be spliced
pressur to
e existing
(cooler wiring
EWT cióse to
and the
LWT connector
are un less
under new
watersi connector
de s are
pressur required.
e) and A special
do not AMP
need to crimping
be tool, pait
remove 110.
d to 58580-1,
replace is needed
a faulty if new
thermis connector
tor. s are
used.
To Remove
Replace thermisto
Thermisto r cable
rs TI. T2. from
T3. T4. hamess.
T5. or T6 Remove
(Emer- and
¡11a. discard
Leaving original
Water: thermisto
Discharge r from
Gas well.
Temperat Insert
ura — new
Dis- thermisto
conncct r in well
appropria body to
its full
depth.
Add a
small
amount of
(herma!
conductiv
e grease
to
thermisto
r probe
and well.
Thermisto
rs are
friction-fit
thermisto
rs and
will slip
back into
well
located at
the cooler
head (TI,
T2) or at
the top of
each
compress
or
discharge
line (T3
through
T6).
Secure
thermisto
r to well
body with
a wire tie
to
prevent
thermisto
r from
working
its way
out of the
well. See
Fig. 34.
To Service there is a
Compress trae short
or Motor or open
Thermisto circuit at
rs ■— these
Two ther- termináis.
mistors If one of
are the
factory thermisto
installed rs fails,
in each disconnec
compress t and
or. relocate
Connectio the wire
ns for the on one of
thermisto the S
rs are termináis
located in to the
the other S
compress terminal
or (SI to S2
junction or S2 to
box. SI). The
There are thermisto
3 rs are not
termináis serviceabl
for the ein the
thermisto field. If
rs: SI, S2, both of
and C. the
Motor compress
temperatu or motor
re is thermisto
measured rs fail,
by leads compress
connected or
to one of replacem
the S ter- ent is
mináis required.
and the C See Table
terminal. 40 for
If a motor
compress thermisto
or motor r
thermisto temperatu
r failure re and
occurs, resistance
verify that valúes.
STRAINER
SCREENS
Fi
g-
33
—
Fil
ter
Dri
er
THERMISTOR JACKETED CABLE SENSOR TUBE BEND SLIGHTLY BEFORE WELL THERMISTOR WELL
L L /
INSERTION
JL
h 4 in T_ ■ 3/16 in,
Fig. 34 — Thermistor
Replacement (T1 through T6)
Table 38A — 5K Thermistor Temperature (°F) vs Resistance/Voltage
TEM VOLTAG RESISTANCE 59 1.982 7,686 146 0.485 1,118
P E (Ohms) 60 1.956 7,665 147 0.477 1,095
(F) DROP 61 1.930 7,468 148 0.469 1,072
62 1.905 7,277 149 0.461 1,050
-25 3.699 98,010
63 1.879 7,091 150 0.453 1,029
-24 3.689 94,707 151 0.445 1,007
-23 3.679 91,522 64 1.854 6,911
65 1.829 6,735 152 0.438 986
-22 3.668 88,449 153 0.430 965
-21 3.658 85,486 66 1.804 6,564
67 1.779 6,399 154 0.423 945
-20 3.647 82,627 155 0.416 925
68 1.754 6,238
-19 3.636 79,871 156 0.408 906
-18 3.624 77,212 69 1.729 6,081
70 1.705 5,929 157 0.402 887
-17 3.613 74,648 158 0.395 868
71 1.681 5,781
-16 3.601 72,175 159 0.388 850
-15 3.588 69,790 72 1.656 5,637
73 1.632 5,497 160 0.381 832
-14 3.576 67,490 161 0.375 815
-13 3.563 65,272 74 1.609 5,361
75 1.585 5,229 162 0.369 798
-12 3.550 63,133 163 0.362 782
-11 3.536 61,070 76 1.562 5,101
77 1.538 4,976 164 0.356 765
-10 3.523 59,081 165 0.350 750
78 1.516 4,855
-9 3.509 57,162 166 0.344 734
-8 3.494 55,311 79 1.493 4,737
80 1.470 4,622 167 0.339 719
-7 3.460 53,526 168 0.333 705
81 1.448 4,511
-6 3.465 51,804 169 0.327 690
-5 3.450 50,143 82 1.426 4,403
83 1.404 4,298 170 0.322 677
' -4 3.434 48,541 171 0.317 663
S4 1.382 4,196
-3 3.418 46,996 172 0.311 650
85 1.361 4,096
-2 3.402 45,505 173 0.306 638
-1 3.386 44,066 86 1.340 4,000
87 1.319 3,906 174 0.301 626
0 3.369 42,679 175 0.296 614
88 1.298 3,814
1 3.352 41,339 176 0.291 602
89 1.278 3,726
2 3.335 40,047 177 0.286 591
90 1.257 3,640
3 3.317 38,800 178 0.282 581
91 1.237 3,556
4 3.299 37,596 179 0.277 570
92 1.217 3,474
5 3.281 36,435 180 0.272 561
93 1.198 3,395
6 3.262 35,313 181 0.268 551
94 1.179 3,318
7 3.243 34,231 182 0.264 542
95 1.160 3,243
8 3.224 33,185 183 0.259 533
96 1.141 3,170
9 3.205 32,176 184 0.255 524
97 1.122 3,099
10 3.185 31,202 185 0.251 516
98 1.104 3,031
11 3.165 30,260 186 0.247 508
99 1.086 2,964
12 3.145 29,351 187 0.243 501
100 1.068 2,898
13 3.124 26,473 188 0.239 494
101 1.051 2,835
14 3.103 27,624 189 0.235 487
102 1.033 2,773
15 3.082 26,804 190 0.231 480
103 1.016 2,713
16 3.060 26,011 191 0.228 473
104 0.999 2,655
17 3.038 25,245 192 0.224 467
105 0.983 2,597
18 3.016 24,505 193 0.220 461
106 0.966 2,542
19 2.994 23,789 194 0.217 456
107 0.950 2,488
20 2.972 23,096 195 0.213 450
108 0.934 2,436
21 2.949 22,427 196 0.210 445
109 0.918 2,385
22 2.926 21,779 197 0.206 439
110 0.903 2,335
23 2.903 21,153 198 0.203 434
111 0.888 2,286
24 2.879 20,547 199 0.200 429
112 0.873 2,239
25 2.856 19,960 200 0.197 424
113 0.858 2,192
26 2.832 19,393 201 0.194 419
114 0.843 2,147
27 2.808 18,843 202 0.191 415
115 0.829 2,103
28 2.784 18,311 203 0.188 410
116 0.815 2,060
29 2.759 17,796 204 0.185 405
117 0.801 2,018
30 2.735 17,297 205 0.182 401
118 0.787 1,977
31 2.710 16,814 206 0.179 396
119 0.774 1,937
32 2.685 16,346 207 0.176 391
120 0.761 1,898
33 2.660 15,892 208 0.173 386
121 0.748 1,860
34 2.634 15,453 209 0.171 382
122 0.735 1,822
35 2.609 15,027 210 0.168 377
123 0.723 1,786
36 2.583 14,614 211 0.165 372
124 0.710 1,750
37 2.558 14,214 212 0.163 367
125 0.698 1,715
38 2.532 13,826 213 0.160 361
126 0.686 1,680
39 2.506 13,449 214 0.158 356
127 0.674 1,647
40 2.480 13,084 215 0.155 350
128 0.663 1,614
41 2.454 12,730 216 0.153 344
129 0.651 1,582
42 2.428 12,387 217 0.151 338
130 0.640 1,550
43 2.402 12,053 218 0.148 332
131 0.629 1,519
44 2.376 11,730 219 0.146 325
132 0.618 1,489
45 2.349 11,416 220 0.144 318
133 0.608 1,459
46 2.323 11,112 221 0.142 311
134 0.597 1,430
47 2.296 10,816 222 0.140 304
135 0.587 1,401
48 2.270 10,529 223 0.138 297
136 0.577 1,373
49 2.244 10,250 224 0.135 289
137 0.567 1,345
50 2.217 9,979 225 0.133 282
138 0.557 1,318
51 2.191 9,717
139 0.548 1,291 TEMP VOLTAGE RESISTANCE
52 2.165 9,461
140 0.538 1,265 (C) DROP (Ohms)
53 2.138 9,213
141 0.529 1,240 (V)
54 2.112 8,973
142 0.520 1,214
55 2.086 8,739 -32 3.705 100,260
56 2.060 8,511 TEM VOLTAGE RESISTANCE -31 3.687 94,165
57 2.034 8,291 P DROP (Ohms)
(F) (V) -30 3.668 88,480
58 2.008 8,076
-29 3.649 83,170
TEM VOLTAGE RESISTANCE 143 0.511 1,190 -26 3.629 78,125
P DROP (Ohms) 144 0.502 1,165 -27 3.608 73,580
(F) (V) 145 0.494 1,141 -26 3.586 69,250
11
8
Table 38A — 5K Thermistor Temperature (°F) vs Resistance/Voltage
-25 3.563 65,205 18 1.844 6,840 62 0.506 1,158
-24 3.539 61,420 19 1.799 6,536 63 0.490 1,118
-23 3.514 57,875 20 1.754 6,246 64 0.475 1,079
-22 3.489 54,555 21 1.710 5,971 65 0.461 1,041
-21 3.462 51,450 22 1.666 5,710 66 0.4.47 1,006
-20 3.434 48,536 23 1.623 5,461 67 0.433 971
-19 3.406 45,807 24 1.580 5,225 68 0.420 938
-18 3.376 43,247 25 1.538 5,000 69 0.407 906
-17 3.345 40,845 26 1.497 4,786 70 0.395 876
-16 3.313 38,592 27 1.457 4,583 71 0.383 836
-15 3.281 38,476 28 1.417 4,389 72 0.371 805
-14 3.247 34,489 29 1.378 4,204 73 0.360 775
-13 3.212 32,621 30 1.340 4,028 74 0.349 747
-12 3.177 30,866 31 1.302 3,861 75 0.339 719
-11 3.140 29,216 32 1.265 3,701 76 0.329 693
-10 3.103 27,633 33 1.229 3,549 77 0.319 669
-9 3.065 26,202 34 1.194 3,404 78 0.309 645
-8 3.025 24,827 35 1.160 3,266 79 0.300 623
-7 2.985 23,532 36 1.126 3,134 80 0.291 602
-6 2.945 22,313 37 1.093 3,008 81 0.283 583
-5 2.903 21,163 38 1.061 2,888 82 0.274 564
-4 2.860 20,079 39 1.030 2,773 83 0.266 547
-3 2.817 19,058 40 0.999 2,663 84 0.258 531
-2 2.774 18,094 41 0.969 2,559 85 0.251 516
-1 2.730 17,184 42 0.940 2,459 86 0.244 502
0 2.685 16,325 43 0.912 2,363 87 0.237 489
1 2.639 15,515 44 0.885 2,272 88 0.230 477
2 2.593 14,749 45 0.850 2,184 89 0.223 466
3 2.547 14,026 46 0.832 2,101 90 0.217 456
4 2.500 13,342 47 0.807 2,021 91 0.211 446
5 2.454 12,696 48 0.782 1,944 92 0.204 436
6 2.407 12,085 49 0.758 1,871 93 0.199 427
7 2.360 11,506 50 0.735 1,801 94 0.193 419
8 2.312 10,959 51 0.713 1,734 95 0.188 410
9 2.265 10,441 52 0.691 1,670 96 0.182 402
10 2.217 9,949 53 0.669 1,609 97 0.177 393
11 2.170 9,485 54 0.649 1,550 98 0.172 385
12 2.123 9,044 55 0.629 1,493 99 0.168 376
13 2.076 8,627 56 0.610 1,439 100 0.163 367
14 2.029 8,231 57 0.591 1,387 101 0.158 357
5B 0.573 1,337 102 0.154 346
TEM VOLTAGE RESISTANCE 59 0.555 1,290
P DROP (Ohms) 103 0.150 335
(C) 60 0.538 1,244 104 0.146 324
(V) 61 0.522 1,200 105 0.142 312
15 1.982 7,855 106 0.138 299
TEM VOLTAGE RESISTANCE
16 1.935 7,499 P DROP (Ohms) 107 0.134 285
17 1.889 7,161 (C) (V)
1
1
9
Table 39A — 10K Thermistor Temperatures (°F) vs Resistance/Voltage Drop
(For Thermistor T10)
TEMP VOLTAGE RESISTANCE TEMP VOLTAGE RESISTANCE TEMP VOLTAGE RESISTANCE
(F) DROP (V) (Ohms) (F) DROP (V) (Ohms) (F) DROP <V) {Ohms)
-25 4 758 196,453 61 2.994 14,925 147 0.890 2,166
-24 4.750 189,692 62 2.963 14,549 148 0.876 2,124
-23 4.741 183,300 63 2.932 14,180 149 0.862 2,083
-22 4.733 177,000 64 2.901 13,824 150 0.848 2,043
-21 4.724 171,079 65 2.870 13,478 151 0.835 2,003
-20 4.715 165,238 66 2.839 13,139 152 0.821 1,966
-19 4.705 159,717 67 2.808 12,814 153 0.808 1,928
-18 4.696 154,344 68 2.777 12,493 154 0.795 1,891
-17 4.686 149,194 69 2.746 12,187 155 0.782 1,855
-16 4.676 144,250 70 2.715 11,884 156 0.770 1,820
-15 4.665 139,443 71 2 684 11,593 157 0.758 1,786
-14 4.655 134,891 72 2 653 11,308 158 0.745 1,752
-13 4.644 130,402 73 2.622 11,031 159 0.733 1,719
-12 4.633 126,183 74 2.592 10,764 160 0.722 1,687
-11 4.621 122,018 75 2.561 10,501 161 0.710 1,656
-10 4.609 118,076 76 2.530 10,249 162 0.699 1,625
-9 4.597 114,236 77 2.500 10,000 163 0.687 1,594
-8 4.585 110,549 78 2.470 9,762 164 0.676 1,565
-7 4.572 107,006 79 2.439 9,526 165 0.666 1,536
-6 4.560 103,558 80 2.409 9,300 166 0.655 1,508
-5 4.546 100,287 81 2.379 9,078 167 0.645 1,480
-4 4.533 97,060 82 2.349 8,862 168 0.634 1,453
‘-3 4.519 94,020 83 2.319 8,653 169 0.624 1,426
-2 4.505 91,019 84 2.290 8,448 170 0.614 1,400
-1 4.490 88,171 85 2.260 8,251 171 0.604 1,375
0 4 476 85,396 86 2.231 8,056 172 0.595 1,350
1 4.461 82,729 87 2 202 7,869 173 0.585 1,326
2 4.445 80,162 88 2.173 7,685 174 0.576 1,302
3 4.429 77,662 89 2.144 7,507 175 0.567 1,278
4 4.413 75,286 90 2.115 7,333 176 0.558 1,255
5 4.397 72,940 91 2.087 7,165 177 0.549 1,233
6 4.380 70,727 92 2.059 6,999 178 0.540 1,211
7 4.363 68,542 93 2.030 6,838 179 0.532 1,190
8 4.346 66,465 94 2.003 6,683 180 0.523 1,169
9 4.328 64,439 95 1.975 6,530 181 0.515 1,148
10 4.310 62,491 96 1.948 6,383 182 0.507 1,128
11 4.292 60,612 97 1.921 6,238 183 0.499 1,108
12 4.273 58,781 98 1.894 6,098 184 0.491 1,089
13 4,254 57,039 99 1.867 5,961 185 0.483 1,070
14 4.235 55,319 100 1.841 5,827 186 0.476 1,052
15 4.215 53,693 101 1.815 5,698 187 0.468 1,033
16 4.195 52,086 102 1.789 5,571 188 0.461 1,016
17 4.174 50,557 103 1 763 5,449 189 0.454 998
18 4.153 49,065 104 1.738 5,327 190 0.447 981
19 4.132 47,627 105 1.713 5,210 191 0.440 964
20 4.111 46,240 106 1.688 5,095 192 0.433 947
21 4.089 44,888 107 1.663 4,984 193 0.426 931
22 4.067 43,598 108 1.639 4,876 194 0.419 915
23 4.044 42,324 109 1.615 4,769 195 0.413 900
24 4.021 41,118 110 1.591 4,666 196 0.407 885
25 3.998 39,926 111 1.567 4,564 197 0.400 870
26 3.975 38,790 112 1.544 4,467 198 0.394 855
27 3.951 37,681 113 1.521 4,370 199 0.388 841
28 3.927 36,610 114 1 498 4,277 200 0.382 827
29 3.903 35,577 115 1.475 4.185 201 0.376 814
30 3.878 34,569 116 1.453 4,096 202 0.370 800
31 3.853 33,606 117 1.431 4,008 203 0.365 787
32 3.828 32,654 118 1.409 3,923 204 0.359 774
33 3.802 31,752 119 1.387 3,840 205 0.354 762
34 3.776 30,860 120 1.366 3,759 206 0.349 749
35 3.750 30,009 121 1.345 3,681 207 0.343 737
36 3.723 29,177 122 1.324 3,603 208 0.338 725
37 3.697 28,373 123 1.304 3,529 209 0.333 714
38 3.670 27,597 124 1.284 3,455 210 0.328 702
39 3.654 26,838 125 1.264 3,383 211 0.323 691
40 3.615 26,113 126 1.244 3,313 212 0.318 680
41 3.587 25,396 127 1.225 3,244 213 0.314 670
42 3.559 24,715 128 1.206 3,178 214 0.309 659
43 3.531 24,042 129 1.187 3,112 215 0.305 649
44 3.503 23,399 130 1.168 3,049 216 0.300 639
45 3.474 22.770 131 1.150 2,986 217 0.296 629
46 3.445 22,161 132 1.132 2,926 218 0.292 620
47 3.416 21,573 133 1.114 2,866 219 0.288 610
48 3.387 20,998 134 1.096 2,809 220 0.284 601
49 3.357 20,447 135 1.079 2,752 221 0.279 592
50 3.328 19,903 136 1.062 2,697 222 0.275 583
51 3 298 19,386 137 1.045 2,643 223 0.272 574
52 3.268 18,874 138 1.028 2,590 224 0.268 566
53 3.238 18,384 139 1.012 2,539 225 0.264 557
54 3.208 17,904 140 0.996 2,488
55 3.178 17,441 141 0.980 2,439
56 3.147 16,991 142 0 965 2,391
57 3.117 16,552 143 0.949 2,343
58 3.086 16,131 144 0.934 2,297
59 3.056 15,714 145 0.919 2,253
60 3.025 15.317 146 0.905 2,209
TEMP VOLTAGE RESISTANCE TEMP VOLTAGE RESISTANCE TEMP VOLTAGE RESISTANCE
(C) DROP (V) (Ohms) (C) DROP (V) (Ohms) (C) DROP (V) (Ohms)
12
0
Table 39A — 10K Thermistor Temperatures (°F) vs Resistance/Voltage Drop
(For Thermistor T10)
-32 4.762 200,510 15 3.056 15,714 62 0.940 2,315
-31 4.748 188,340 16 3.000 15,000 63 0.913 2,235
-30 4.733 177,000 17 2.944 14,323 64 0.887 2,157
-29 4.716 166,342 18 2.889 13,681 65 0.862 2,083
-28 4.700 156,404 19 2.833 13,071 66 0.837 2,011
-27 4.682 147,134 20 2.777 12,493 67 0.813 1,943
-26 4.663 138,482 21 2.721 11,942 68 0.790 1,876
-25 4.644 130,402 22 2.666 11,418 69 0.767 1,813
-24 4.624 122,807 23 2.610 10,921 70 0.745 1,752
-23 4.602 115,710 24 2.555 10,449 71 0.724 1,693
-22 4.580 109,075 25 2.500 10,000 72 0.703 •1,637
-21 4.557 102,868 26 2.445 9,571 73 0.683 1,582
-20 4.533 97,060 27 2.391 9,164 74 0.663 1,530
-19 4.508 91,588 28 2.337 8,776 75 0.645 1,480
-18 4.482 86,463 29 2.284 8,407 76 0.626 1,431
-17 4.455 81,662 30 2.231 8,056 77 0.608 1,385
-16 4.426 77,162 31 2.178 7,720 78 0.591 1,340
-15 4.397 72,940 32 2.127 7,401 79 0.574 1,297
-14 4.367 68,957 33 2.075 7,096 80 0.558 1,255
-13 4.335 65,219 34 2.025 6,806 81 0.542 1,215
-12 4.303 61,711 35 1.975 6,530 82 0.527 1,177
-11 4.269 58,415 36 1.926 6,266 83 0.512 1,140
-10 4.235 55,319 37 1.878 6,014 84 0.497 1,104
-9 4.199 52,392 38 1.830 5,774 85 0.483 1,070
-8 4.162 49,640 39 1.784 5,546 86 0.470 1,037
-7 4.124 47,052 40 1.738 5,327 87 0.457 1,005
-6 4.085 44,617 41 1.692 5,117 88 0.444 974
-5 4.044 42,324 42 1.648 4,918 89 0.431 944
-4 4.003 40,153 43 1.605 4,727 90 0.419 915
-3 3.961 38,109 44 1.562 4,544 91 0.408 889
-2 3.917 36,1 B2 45 1.521 4,370 92 0.396 861
-1 3.873 34,367 46 1.480 4,203 93 0.386 836
0 3.828 32,654 47 1.439 4,042 94 0.375 811
1 3.781 31,030 48 1.400 3,889 95 0.365 787
2 3.734 29,498 49 1.362 3,743 96 0.355 764
3 3.686 28,052 50 1.324 3,603 97 0.345 742
4 3.637 26,686 51 1.288 3,469 98 0.336 721
5 3.587 25,396 52 1.252 3,340 99 0.327 700
6 3,537 24,171 53 1.217 3,217 100 0.318 680
7 3.485 23,013 54 1.183 3,099 101 0.310 661
8 3,433 21,918 55 1.150 2,986 102 0.302 643
9 3.381 20,883 56 1.117 2,878 103 0.294 626
10 3.328 19,903 57 1.086 2,774 104 0.287 609
11 3.274 18,972 58 1.055 2,675 105 0.279 592
12 3.220 18,090 59 1.025 2,579 106 0.272 576
13 3.165 17,255 60 0.996 2,488 107 0.265 561
14 3.111 16,474 61 0.968 2,400
12
1
Pressure Transducers — Discrete high and low pres- seconds. When some flow is detected but not
sure transducers are used for pressure sensing on enough for machine operation, a red LED at the far
all 30GXN,GXR,HX chillers. The discharge and oil left will be illuminated. With increasing flow,
pressure transducers are high pressure successive red LEDs ¡Ilumínate. When the switch
transducers, and the suction and economizer determines flow is present, the amber LED illumi-
pressure transducers are low pressure transducers nates indicating the output has closed. This is not an
(whíte dot). No pressure transducer calibration is indica- tion of mínimum flow. Increasing flow above the
required. The transducers operate on a 5 vdc amber LED output indication illuminates the first
supply, which is generated by the Main Base Board green LED. Each successive green LED indicates
(MBB) for suction and discharge pressure greater flow. The switch closure does not indícate
transducers and by the Screw Compressor Board mínimum flow for the machine. With one green
(SCB) for the oil and economizer pressure LED lit, minor fluctuations in water flow may cause
transducers. See unit wiring labels for specifíc nuisance alarms. Additional green LEDs indícate
MBB and SCB pressure transducer power and higher flow rates, and can avoid the nuisance
signal connections. Refer to Fig. 35A- 35C for alarms. Refer to Fig.'37.
pressure transducer locations. 1. Check to confirm that all strainers are clean,
TROUBLESHOOTING — If transducer is suspected valves are open and pumps are running. For
of being faulty, first check supply voltage to the case of VFD controlled pumps, ensure that
transducer. Supply voltage should be 5 vdc ± .2 v. the mínimum speed setting has not been
If supply voltage is correct, compare pressure changed.
reading displayed on keypad and display module 2. Measure the pressure drop across the cooler
against pressure shown on a calibrated pressure and using Appendix E on pages 95-100,
gage. If the 2 pressure readings are not reasonably calcúlate the cooler flow and compare this to
cióse, replace pressure transducer. Low pressure the system requirements.
transducers suction and economizer pressures 3. If the measured flow rate through the cooler
should be within ± 2 psig. Discharge and oil agrees with the system requirements. At least
pressures should be within ± 5 psig. 2 green LEDs should be lit.
FLOW SENSOR -— Figure 36 shows a typical view 4. If the contacts do not cióse while two green
of the flow sensor as attached to a victaulic nozzle. LEDs are lit, verify operation of the flow
It also shows the connector pin orientation of the switch relay. Without chang- ing fluid flow
sensor. If nuisance trips of the sensor are through the cooler, check for power at the flow
occurring, follow the steps below to correct the switch relay (FSR) coil. if power is not present,
situation: check continuity of flow sensor cable. If the
When power is supplied to the device, a warm- sensor cable is not shorted or open when
up period is initiated. During this period, the right- correct flow has been confirmed and the green
most green LED is lit and turned off as each LED sensor LEDs are lit, the sensor has failed and
to the left is successively lit until the left-most red must be replaced.
LED is lit. The warm-up period may take up to 30
E
OPT-At PT OPT-
B1.
-A EPT-B
SPT-
B
DPT-A DPT-B
Fig. 35A — 30HX Pressure Transducer Locations (2-Compressor Unit)
12
2
DPT — Discharge Pressure Transducer EPT
— Economizer Pressure Transducer EXV —
Electronic Expansión Valve OPT — Oil
Pressure Transducer
SPT — Suction Pressure Transducer
OPT-A OPT-B
12
3
FLOW SWITCH LOCATION STANDARD 2-
PASS (UNIT SIZES 118,128, 138-178, 204-
350)1
FLOW SWITCH
LOCATION STANDARD 3-PASS
(UNIT SIZES 080-119, 125, 135)*
RED AMBER
ir
GREEN
□□□□□□□□□□□ JL
FLOW BELOW OUTPUT
FLOW
SET POINT ENERGIZED
ABOVE
SETPOINT
COMPRESSOR CYCLES Loss of charge Repair leak and recharge, Replace transducer.
OFF ON LOW SATURATED SUCTION Bad transducer Add refrigerant. Repair/replace as needed. Re
TEMPERATURE Low refrigerant charge
Failed expansión device
Partially plugged or plugged strainer
COMPRESSOR SHUTS DOWN ON HIGH High-pressure switch erratic in action Compressor discharge Repiace switch.
PRESSURE CONTROL valve partially closed Condenser fanjs) not operating (air Open valve or replace if detective.
cooled units) Condenser coil plugged or dirly (air cooled units) Check wiring. Repair or replace motor(s) if dete
Condenser water valve not operating (water cooled units)
Circuit overcharged Check wiring. Repair or replace valve if detecti
UNIT OPERATES LONG OR Low refrigerant charge Control contacts fused Partially Add refrigerant,
CONTINUOUSLY plugged or plugged strainer Detective insulation Replace control.
Service load exceeding design capacity Inefficient Clean or replace,
compressor Replace or repair,
Evalúate load requirements.
Check loader solenoid valves. Replace if neces
SYSTEM NOISES Pipíng vibration Expansión valve hissing Supportpiping as required.
Compressor noisy Add refrigerant
Check tor plugged liquid line strainer.
Replace compressor (worn bearings).
Check for loose compressor bolts securing
COMPRESSOR LOSES OIL Leak in system Mechanical damage to rotors Find and repair leak. Replace compressor.
HOT LIQUID LINE Shortaqe of refrigerant due to leak Repair leak and recharge.
FROSTED LIQUID LINE Shutoff valve partially closed or restricted Open valve or remove restriction.
COMPRESSOR LOADERS NOT Burned out coil Replace coil. Replace valve. Rewire correclly.
WORKING PROPERLY Detective loader solenoid valve Miswired solenoid
Carrier bus in a
Comfort ilaisy
Network chain
(CCN) arrange
Interface ment.
— The
The positive
30GX,HX pin of
chiller each
units can system
be detnent
connected commu
to the CCN nication
if desired. connect
The or must
communic be
ation bus wired
wiring is a to the
shielded, positive
3- pins of
conductor each
cable with system
drain wire element
and is . Wiring
supplied connec-
and tions
instalied in for
ihe field. CCN
The can be
system mude
elements at
are termina
connected l block
to the TB3.
commu- There
nication are four
termináis Teflon
(including with a
shield) mínimu
located at m
TB3 operati
forperman ng
ent CCN temper
connection ature
. For range
temporary of -20 C
CCN to 60 C
connection is
to the require
chiller, d. Wire
there is manufa
also an RJ- cturad
11 (6 by
position, 6 Alpha
conductor) (2413
connector. or
The 5463),
connector Americ
is for field an
connection (A2250
of a laptop 3),
Computer Belden
running (8772),
Service or
Tool or Columb
ComfortVI ia
EW™ (02525)
software meets
programs. the
Consult above
CCN mentioned
Contractor require
's Manual ments.
for further It is
informatio importa
n. NOTE: nt
Conductor when
s and connect
drain wire ing to a
must be 20 CCN
AWG commu
(American nication
Wire bus
Gage) that a
mínimum color
stranded, coding
tinned scheme
copper. be used
Individual for the
conductors entire
must be networ
insulated k to
with PVC, simplify
PVC/nylon, the
vinyl, installa
Teflon, or tion, It
polyethyle is
ne. An recom
aluminum/ mended
polyesler that red
100% foil be used
shield and for the
an outer signal
jacket of positive
PVC, , black
PVC/nylon, for the
chrome signal
vinyl, or negativ
e, and bus can
while for cause
the signal problems
ground. with all
Use a system
similar elements
scheme for on the
cables bus.
contain-
ing Repiacing
different Detective
colored Modules — The
wires. ComfortUnk™
) replacement
At each system modules are
element, the shown in Table
shields of its 43. The unit
communication model and
bus cables must be serial numbers
tied together. If are printed on
the communication the unil
bus is emirely nameplate
within one located on an
building, the exterior comer
resulting post (30GX) or
continuous shield the comer of
musí be connected the control box
lo a ground at one (30HX). The
point only. If the basic software
communication and unit
bus cable exits configuration
from one building data is factory
and enters instalied by
another, the Carrier in the
shields must be replacement
connected to module.
grounds at the Therefore,
lightning when ordering
suppressor in each any
building where the replacement
cable enters or module, specify
exits the building the replace-
(one point per ment part
building only). number
(located on
IMPORTANT: each module
A shorted front or back),
CCN bus full unit model
cable will number and
prevent some serial number.
routines from The
running and replacement
may prevent modules will be
the unit from downloaded
starting. If with the basic
abnormal software. If the
conditions Main Base
occur, Board (MBB)
disconnect has been
the CCN bus. replaced, verify
If conditions that all
return to configuration
normal, check data is correct.
the CCN Follow the
connections Configuration
and cable. mode table and
Run new verify that all
cable if items under
necessary. sub-modes
A short in one UNIT, OPT1
section of the and OPT2 are
correct. Any
additional field RSET,SLCT)
instalied should also be
accessories or verified.
options (sub-mode
MODULE REPLACEMENT tion drain
PART NUMBER wire (CCP
(With Software)
modules
Main Base Board (MBB) 30GX506748
only). Save
the screws.
Expansión Valve Board (EXV) 30HX515217
2. Remove the
defective
Screw Compressor Board (SCB) 30HX501316
module by
Navigator Display HK50AA033
removing its
mounting
Energy Management Module (EMM) 30HX515218 screws with
a Phillips
Comfor/LInk™ Compressor HN67LM103
Protection Boards
screwdriver,
(CCP1.CCP2) and
removing
Refer to the the module
Start-Up from the
Checklist for control box.
30GXN,GXR,HX Save the
Liquid Chillers screws later
(completed at use. For
time of original Navigator
start-up) found replacement
in the job folder. , remove the
This screw
information is securing the
needed later in cable clamp
this procedure. near TB3.
If the checklist 3. Verify that
does not exist, the instance
fill out the jumper
current (MBB) or
information in address
the switches (all
Configuration other
mode on a new modules)
checklist. Tailor exactly
the various match the
options and settings of
configurations the
as needed for defective
this particular module.
installation. 4. Package the
defective
module in
A CAUTION the cartón
Electrical shock of the new
can cause module for
personal injury. retum to
Disconnect all Carrier.
electrical power
before servicing. 5. Mount the
new module
1. Check that in the unit’s
all power to control box
unit is off. using a
Carefully Phillips
disconnect screwdriver
all wires and the
from the screws
defective saved in
module by Step 2.
unplugging 6. Reinstall all
its module
connectors. connectors
Remove the and
screw communicat
securing the ion drain
communica- wire (CCP
modules after draining.
only). For To prevent
Navigator freeze-up
replace- damage to the
ment, make cooler tubes
sure the perform the
plug is following
installed at procedure.
TB3 in the 1. If cooler
LEN heaters
connector. have been
7. Carefully installed,
check all deenergize
wiring the heaters
connections to prevent
before damage and
restoring possible
power. safety
8. Verify the hazards
Enable/Off/ when
Remote draining, or
Contact when there
switch is in is no liquid
the OFF in the
position. system.
9. Restore Remove
control Fuse 1 to
power. deenergize
Verify that the heaters.
all module Drain the
red LEDs fluid from
blink in the system.
unisón. 2. Isolate the
Verify that cooler from
all green the rest of
LEDs are the system
blinking and with water
that the shut off
Navigator is valves.
communicat 3. Completely fill
ing the cooler
correctly. with an
10.Verify all appropriate
configuratio amount of
n inhibited
information, ethylene
settings, glycol
setpoints solution (or
and other
schedules. suitable
Retum the corrosion-
Enable/Off/ inhibitive
Remote antifreeze)
Contact for 15° F
switch to (8.3° C)
normal below the
operation expected low
position. ambient
conditions (5
Winter Shutdown gallón [19 L]
Preparation — At minimum).
the end of 4. Leave the
each cooling cooler filled
season the fluid with the
should be antifreeze
drained from solution for
the system. the winter, or
However, due to drain if
the cooler desired. Be
circuiting, some sure to
fluid will remain deenergize
in the cooler heaters (if
installed) as • Coil
explained in
cleaning
Step 1 to
prevent with
damage. Use Carrier
an approved approved
method of
disposal coil
when cleaner.
removing the EVERY 3
antifreeze
MONTHS
solution.
5. Update item All machines:
W.DNE • Check all
Winterizatio refrigerant
n Performed joints and
(Configu- valves for
ration Mode, refrigerant
Sub-mode leaks, repair
SERV) to as necessary.
YES. • Check
Winterization moisture
is complete. indicating
Maintenance sight glass
RECOMMENDE for possible
D refrigerant
MAINTENANCE loss and
SCHEDULE — presence of
The following are moisture.
only • Check oil filter
recommended pressure
guidelines. Job drops,
site conditions replace as
may díctate that necessary.
maintenance • Check chilled
schedules be water flow
performed more switch
frequently than operation.
listed here. 30GX machines:
ROUTINE (as • Check
conditions condenser
dictate) coils for
30GX machines debris, clean
with E-coat as necessary.
condenser • Check
coils:
• Check condenser
condenser fan operation.
coils for YEARLY:
debris, clean
All machines:
as necessary
• Periodic • Check all
clean water electrical
rinse, connections.
especially in Tighten as
Coastal and necessary.
industrial • Check
applications. accuracy of
all
MONTHLY transducers
30GX machines for each
with E-coat circuit,
replace as
Condenser necessary.
Coils: • Check
• Check accuracy of
thermistors,
condenser replace if
coils for greater than
debris, clean ± 2o F (1.2°
C) variance
as necessary
from
calibrated • Check all
thermometer. refrigerant
• Obtain and strainers and
test an oil filter driers
sample,
change as pressure
necessary. drops,
• Clean cooler replace/clean
tubes if as necessary
appropriate. • Check chilled
• Check to be water
sure that the strainers,
proper clean as
concentration necessary
30GX machines:
antifreeze is • Check cooler
present in the heater
chilled water operation
loop. • Check
• Check to be condenser
sure that the fan blades to
proper insure they
amount of are securely
inhibitor is fastened to
present in the motor
the chilled shaft and
water loop. their
condition.
30HXC machines:
• Check Condenser Water Regulating Valve
operation, if equipped.
• Clean condenser tubes if appropriate.
• Check condenser water strainers, clean as
necessary
PRE-START-UP PROCEDURE
TMPORTANT: Before beginning Pre-Start-Up or
Start- Up, complete the Start-Up Checklist for
the 30GX.HX Liquid Chillers on pages CL-I to could
CL-10. This Checklist assures proper stail-up of Fig. 38 — Suction Valve Detail
be the
the chiller, and provides a record of unit result
condition, applicalion requirements, system of a
information and operation at initial start-up. refrigerant leak in the cooler.
The checklist should be removed from the 6. Open the oil shutoff valves located by the oil
manual and kept with the job file for future pre-filter, and the ball valve to each compressor.
reference. 7. Check the tightness of all electrical
connections. Check incoming power supply for
IMPORTANT: DO NOT ATTEMPT TO START
proper nameplate voltage.
THE CHILLER UNTIL THE FOLLOWING JAM NUT BRASS CAP
CHECKS HAVE BEEN COMPLETED.
A CAUTION
DO NOT make any changes to the factory-
installed compressor power wiring in the
control box or at the compres- sor junciion box.
Doing so will cause permanenl damage to the
compressor and will require compressor
replacement. Proper phasing has already been
checked at the lactory.
System Check
1. Check all auxiliary components such as Ihe
Caution: loosen stem locknut
chilled fluid circulating pump, air-handling (L.H. thread) before opening
equipment, or other equipment to which the
chiller supplies liquid. Consult the Fig. 39 — Suction Valve Handle Oetails
manufacturéis instructions. If the unit has field-
installed accessories, be sure all are properly 8. Check to ensure the unit is level per the
installed and wired correctly. Refer to the unit installation instructions.
9. Check all field configuration data and set points.
wiring diagrams. 10.Enter correct date, time, and operating
2. Check the cooler flow switch for proper schedule(s).
operation (item ‘FLOW’, Inputs mode under 11.Verify operation of solenoids, pumps, valves,
sub-mode GEN.I). Ensure sensor contacts cióse compressors, fans, etc. as listed in the Start-Up
when the pump is on and open when the pump Checklist.
is tumed off. A flow switch is factory installed 12.Open condenser water valves. Check condenser
on all models with two or more pass coolers. water pump for proper operation (30HXC).
For single pass cooler models, the flow switch
is factory supplied for field installation with START-UP AND OPERATION
factory-supplied victaulic nozzles.
3. Open the discharge and liquid valves in each Actual Start-Up — Actual start-up should be done
circuit. Both shutoff valves are in-line ball type only under supervisión of a qualified
and are open when stem is parallel with the refrigeration mechanic and qualified Carrier
refrigerant flow. Comfort Network personnel.
4. If factory-installed suction service valves are 1. Set leaving fluid temperature. No cooling range
installed, open the suction service valves in adjust- ment is necessary.
each circuit. Service valve is located below the 2. Start chilled fluid pump and condenser pump
compressor in the cooler suction connection (30HXC) if not controlled by unit.
flange. To operate the valve, first remove the 3. Switch Enable/Off/Remote Contact switch lo
cap. Use a back-up wrench on the packing Enable or Remóte Contact.
gland to prevent loosening while removing cap. 4. Provided there is a load on the chiller, allow the
Loosen the jam nut. Rotating the valve handle machine to operate and confirm that everything
clockwise will cióse valve and counterclockwise is functioning properly. Verify that the leaving
will open valve. When closing the valve, the fluid temperature agrees with the cooling set
linkage ann must swing past center of the point (1 or 2), or if reset is being used, the
actuator shaft cam to seat and prevent modified set point. Chiller is controlling to the
accidental opening of the valve. Tighten the jam Control Point (item ‘CTPT’) displayed on the
nut. See Fig. 38 and 39. Navigator.
5. Before filling the system with fluid following a Operating Sequence — The chiller is started by
winter shutdown, check the chilled water loop switching the Enable/Off/Remote Contact switch to
for pressure. Higher than atmospheric pressure
13
6
either Enable or Remóte Contact position. If cooler solenoid is opened and the control reads the oil
pump control is enabled, the cooler pump is started. pressure from the transducer and determines if
If condenser pump control (30HXC) is enabled, the sufficient pressure has been built up. If there is not
condenser pump is started. On a command for sufficient pressure, an alarm is generated after the
cooling, the oil pump is tumed on to start the pre- second attempt and the compressor is not started.
lubrication process. After 20 seconds, the oil
Upon building pressure, the compressor is compressor is started in a Wye configuration. This
allowed to start (after 15 seconds). For across-the- method reduces the locked rotor current
line (XL) start chillers, the compressor starts and requirements by approximately 60% while
comes up to full speed within 1 to 3 seconds. For maintaining enough torque to bring the compressor
Wye-Delta start chillers, contactors 1M and S up to full speed.
(starter contactor assembly) are closed and the
FIELD WIRING
Field wiring is shown in Fig. 40-54
LEGEND FOR FIG. 40-54
Alarm I NEC FUSED DÍSCOÑNECT-!
ALM
CFR
Condenser Fan Relay ----1----1 I----------
Chiller Water Pump Condenser Flow
CMP I
Switch Condenser Pump
CNFS
Interlock Condenser Pump Relay
CNPI 115 V CONTROL CIRCUITS USE
Chilled Water Pump Energy 30 AMP MAXIMUM FROM
CNP-R I
Management Module Entering SEPARATE POWER SUPPLY
CWP
Water Thermistor Factory-
EMM
lnstalled Option Flow Switch
EWT I
Relay Fuse
FIOP FIELD CONTROL POWER SUPPLY
Ground Fault Interrupter Convenience Outlet
FSR
Ground I II I
FU
Liquid Line Solenoid Valve 230 V CONTROL CIRCUITS USE
GFI-CO I I I
Leaving Water Thermistor Main 15 AMP MAXIMUM FROM
GND
Base Board Mínimum Load Valve -1--------f- SEPARATE POWER SUPPLY
LLSV
National Electrical Code Outdoor- 6
LWT
MBB
Air Thermistor Screw
Compressor Board Space
[2 Q]
MLV
Temperature Sensor Switch
NEC '
Terminal Block
OAT GND TB4
Field-Wired
SCB
Factory Wired
SPT Fig. 40 — Power Supply Wiring
SW
TB
8LK-
TB5
M A X L O A D- 7 5 VA S E A L E D 3 6 0 VA I N R U S H
Fig. 41 — Remóte Alarm Relay Accessory Wiring; All Models, 115 or 230 V*
M A X L OA D - 7 5 VA S EA L ED
TB5
3 6 0 VA I N RU S H
—QH--
V i 0
-
--03 TB5
Fig. 42 — Chilled Water Pump Relay Wiring; All Models, 115 or 230 V*
I”F IOP/ACCESSORY GF I
-C0 ! LOAD
_Q=.GRN-
B L K 15
YEL—i
TB < AM PS
BRASS SCREWC— LLI a— -1 S I LVER SCREW
inn) i
-rn- - B l U - -d l F U I I P
BLK
- ------ -B LK------------------| | ■ —m TB4
WH
(5 AMP MAX ) LINE J_. I
■X
T
13
Fig. 43 — Optional Ground Fault Interrupter; Convenience Outlet Accessory Wiring
7
-J
13
8
MAIN BASE BOARD
(fHT-HI TB4
Fig. 44A —
BASE BOARD
------1,
J1QA -O-»
I,
-GH> MINIMUM LOAD fI0P/ACCESS0RY . MLV-A
Tflí
«it 11 TBS
-tu----------------W K T—CE ] TB 4
W, MLV-B *jT
UOHÍÍ (mui
r
------------------
=©=
------------------
1
| MAX IOAO-7SVA StAlCO
|
| 360VA
INRUSH
|
i
____________
¡53
____________
i
m )\ MBB
USV» J10
A
IIKAWm
[
lN T6,
—-Gjé—--------------------------------------------------------------------
—^ C D — í f l S
I,,
(30HXC OHLTJ
* VAX IOAO 7JVA
StALCO ---
T0 j 360VA IMRUSK
(BÍ
—í
K-
Ov1
/
—
—
í* o
”
— '
—
-----
-----
0^0
-----
—
—
—*
—
7C
Q
*hi
—
{jj
ÉI
ÍH
S
^ (J6HXA
ONLÍ)
|
[ MAX IOAO-75VA
SEALEO |
360VA INRUSH
I
-----------------
gg
-----------------
1
ILSV8 IH*A ONU»
F¡g. 45 — Condenser
Pump Relay Wiring;
30HXC and Remóte
Condenser Fan/Liquid
Line Solenoid Valve
Wiring; 30HXA 115 or 230
V*
-REMOVE
JUMPER MBB
T65 WHEN
-TT O USING
\ PUMP
\/ R INTERLO
N N --
---II-
f
CK IBS !8S
OR CWP •o « ^ —-----4|- - -[Tg—,
|—COJ MBB
N FSR ORN —<«- — HNOTC T I-----------1RED —«-©
st0 on-orr S U I T C K
<LHK2)---------------------------- ORN
<To) S E U O i* j*<
1 H
{OltlK fl
o-o— J7
- O K N “#(D l
-REO —«-©
orr ov's—flEí-
Fig. 46 — Chilled Water CMASie ?B
Interlock and Flow Switch i—>
Input Wiring
6
CNPi rs2 <KD ■
FIELO SCB
-- -
r “It -LU ■ i
5
<HD SUPPLI
ED I I
DEVIC
¡ -------ORA -^Of<D E FOR
¡ CNFS T82 | |
-<►£-—-TO-------------------------- --------GRAAKD
30HXA
C
? IRCUIT
<«D B. .
HEAD
»- PRESS
URE *
CONDENSE# EW1 ACCESSORY
Fig. 47 — Remóte On/Off Switch
1-—T Input
<DWiring
4-?0
> Uf l <
rn/
NOIC) VAlVE
T-—
COMÍ ; HEAD
ROI I PRESS
URE
J ni.ni/ rntJOUIIL
8 ■
CON
TROL
WO mA
NOTE:
Install a 500
Q resistor
across
output
termináis to
FIELD convert
SUPP
LIED output
■ signal to 2-
VALV 10 vdc.
E FOR
30HX Fig. 52
C
¡ CON — Field-
DENS Supplied
ER
FLUI Head
D OR
DEVI Pressure
CE Device
FOR I
30HX Wiring;
A 30HX
CIRC
UIT A Units
SERVICE OPTION
Fig. 48 — Condenser Flow Switch Interlock and
Entering/Leaving Water Thermistor Wiring; 30HXC Units
MBB Í
SERVICE
0E»>~vio BRN-Kf® PORT
VI0-i-<^<T)
©
(1»>=- BRN MODULAR
JACK
<Z»}¿-6NO
BtK——^(5)
--GJ
TB
-ORA —<f<D
MBB J4 G>#-BU WBT-j-<«<D
5 l-RED-Kf®
DUAL SETPOINT
—o—&-—m-
TB5 -5RA —«-(D J7 G)-»1- RED-
1
i
L
Fig. 49 — Remóte Dual
Setpoint Wiring; All Units
Field
Fig. 50 Supplied
—
Outdoor-
Air
Thermist
or (5KQ
at 77 F
[25 C])
and
Space
Tempera
ture
Sensor
(10KQ at
77 F [25
C]) All
Units,
ment
NOTE: Use
signal Module
converter for Option
input types
other than 4- or
20 mA. Accesso
Fig. 54 — ry
Energy Wiring;
Manage All Units
Fig. 51 — Motormaster®
Option; 30GXN,R Units
APPENDIX A
30GXN,R (High Ambient Data [Position 10 in model no. equal to ‘A’, ‘F’, ‘T, or ‘V’], All Models)
ComforLink™ Compressor Protection Module Configuration Header Punch-Outs and Must Trip Arpps
UNIT VOLTS-Hz PUNCHOU PUNCHOUTS PUNCHOU PUNCHOUTS COMP A1 COMP A2 MUST COMP B1 COMP B2 MUST
30GXN,R TS FOR FOR COMP A2 TS FOR FOR COMP B2 MUST TRIP TRIP AMPS MUST TRIP TRIP AMPS
COMP A1 COMP B1 AMPS SETTING SETTING AMPS SETTING SETTING
UNIT VOLTS-Hz PUNCHOU PUNCHOUTS PUNCHOU PUNCHOUTS COMPA1 MUST COMPA2 MUST COMP B1 COMP B2 MUST
30GXN,R TS FOR FOR COMP A2 TS FOR FOR COMP B2 TRIP AMPS TRIP AMPS MUST TRIP TRIP AMPS
COMP A1 COMP B1 SETTING SETTING AMPS SETTING SETTING
125 575-60 1,2,5,7,8 — 1.2.3.7 — 154 — 108 —
380-60 1,3,7,8 — 1,2,6,7 — 234 — 164 —
UNIT VOLTS-HZ PUNCHOU PUNCHOUT PUNCHOU PUNCHOU COMP A1 COMPA2 MUST COMP B1 COMP B2 MUST
30GXN,R TS FOR S FOR TS FOR TS FOR MUST TRIP TRIP AMPS MUST TRIP TRIP AMPS
COMP A1 COMP A2 COMP B1 COMP B2 AMPS SETTING AMPS SETTING
SETTING SETTING
261 575-60 1,3,4,5,7 1.2,3,7 1.3,4,5,7 1,2,3,7 188 100 188 108
380-60 1.5,8 1.2,6.7 1.5,8 1.2,6,7 286 164 286 164
460-60 1,3,7 1,2,4,6,B 1.3,7 1,2,4,6,8 236 134 236 134
14
5
APPENDIX A (cont)
30GXN,R (High Ambient Data [Position 10 in model no. equal to ‘A’, ‘F’, T’, or ‘V’], All Models)
ComfortLink™ Compressor1.6.8
380/415-50 Protection Module
1,2,6,8 Configuration
1,6,8 Header Punch-Outs
1.2,6,8 294 and Must
166 Trip Amps294 166
301 575-60 1.3,4,5,7 1,2.4.5 1.3.4,5,7 1,2,4,5 188 128 188 128
380-60 1.5.8 1.3,4,6,7,8 1,5,8 1.3,4,6,7,8 286 194 286 194
460-60 1.3,7 1,2.5 1.3,7 1.2.5 236 160 236 160
380/415-50 1.6.8 1 *3.4,7,8 1,6,8 1,3,4,7,8 294 202 294 202
325 575-60 1.3,4,5.7 1,2,5,7.8 1.3,4,5.7 1.2,5,7,8 188 154 188 154
380-60 1.5,8 1.3,7.8 1.5,0 1.3.7.8 286 234 286 234
460-60 1,3,7 1.3,4,6,7,8 1.3,7 1,3,4,6,7,8 236 194 236 194
380/415-50 1.6,8 1.3 1,6,8 1,3 294 240 294 240
350 575-60 1,3.4t5t7 1.3,4,5,7 1,3,4,5,7 1.3,4.5,7 188 188 188 188
380-60 1.5,8 1,5,8 1.5,8 1,5,8 286 286 286 286
460-60 1.3.7 1,3,7 1.3,7 1.3.7 236 236 236 236
380/415-50 1,6.8 1,6,8 1,6,8 1,6,8 294 294 294 294
UNIT VOLTS-Hz PUNCHOUT PUNCHOUTS PUNCHOUT PUNCHOUTS COMP A1 COMP A2 COMP B1 COMP B2 MUST
30GXN,R S FOR COMP A2 S FOR FOR COMP B2 MUST TRIP MUST TRIP MUST TRIP TRIP AMPS
FORCOMP COMP B1 AMPS AMPS AMPS SETTING
A1 SETTING SETTING SETTING
000 575-60 1.2,3,5.6 — 1,2,3,4,7,8 — 88 — 74 —
380-60 1.2,4,6.8 — 1.2,3 — 134 — 112 —
230-60 1.3,5,7 — 1,3.4,5,6 — 220 — 184 —
208/230-60 1,4.5,6.7 — 1,3,4,7 — 244 — 204 —
460-60 1,2,3,8 — 1,2,3,5,7 — 110 — 92 —
230-50 1,3.8 — 1.3.4.6 — 238 — 200 —
380/415-50 1.2.4 — 1.2,4,5,6 — 144 — 120 —
083 575-60 1.2.3,4,7.8 — 1,2,3,4,6,7.8 — 74 — 66 —
380-60 1.2.4,5,6,7,8 — 1.2,3,6,8 — 114 — 102 —
230-60 1,3,4.5.7 — 1,2,6 — 188 — 168 —
208/230-60 1,3,4 — 1.3.4.57.8 — 208 — 186 —
460-60 1.2.3.5.8 — 1,2.3,5,67 — 94 — 84 —
230-50 1.3.4,8 — 1,2,7 — 206 — 172 —
380/415-50 1,2,4,5,8 — 1.2.3,6 — 126 — 104 —
090 575-60 1.2.3 — 1,2,3,47.8 — 112 — 74 —
380-60 1,2.6 — 1.2.3 — 168 — 112 —
230-60 1.5,6,7 — 1,3,4,5.6 — 276 — 184 —
208/230-60 2.3.4.5,6.7,8 — 1.3,47 — 306 — 204 —
460-60 1.2.4,7,8 — 1.2.3,5.7 — 138 — 92 —
230-50 1,6,8 — 1.3.4.6 — 294 — 200 —
380/415-50 1.3.4,5,6.7,8 — 1.2,4,5,6 178 — 120 —
093 575-60 1.2.3,5 — 1,2,3,4.67,8 — 96 — 66 —
380-60 1.2,4 — 1,2,3.6,8 — 144 — 102 —
230-60 1,3 — 1,2,6 — 240 — 168 —
208/230-60 1,4,7.a 1,3,4.57.8 — 266 — 186 —
460-60 1,2,4,5,6 — 1.2.3.5.67 — 120 — 84 —
230-50 1.4,5,6 — 1.2,7 — 248 — 172 —
380/415-50 1.2,5,6,8 — 1.2.3.6 — 150 — 104 —
106 575-60 1,2,4,7,8 — 1.2.3.47.8 — 138 — 74 —
380-60 1.3.5,6,7,8 — 1,2,3 — 210 — 112 —
230-60 2,3,5.6 — 1.3,'4,5,6 — 344 — 184 —
200/230-60 2,4,5,8 — 1.3.4,7 — 382 — 204 —
460-60 1,2,7 — 1,2,3.57 — 172 — 92 —
230-50 2,3 — 1,3,4,6 — 360 — 200 —
380/415-50 1,3.5,8 — 1,2.4,5.6 — 222 — 120 —
108 575-60 1,2,4.5,6,8 — 1.2,3,4 — 118 — 80 —
380-60 1,3,4,5.6,7,8 — 1,2,4,5,6 — 178 — 120 —
230-60 2.3,4,5.7 — 1.3.4.6 — 316 — 200 —
208/230-60 2,3,4,6,8 — 1.3,5,0 326 — 222 —
460-60 1.2.5,6.7,8 — 1.2,3,67 — 146 — 100 —
230-50 2,3,4,5,7 — 1.3.4 — 316 — 208 —
380/41 5-50 1,3,4,5,7,8 1.2.4.5,8 — 186 — 126 —
114 575-60 1.2.4,7.8 — 1,2,3.5,6 — 138 — 88 —
380-60 1,3,5,6,7,8 — 1.2.4.6,8 — 210 — 134 —
230-60 2,3,5,6 — 1.3,5,7 — 344 — 220 —
208/230-60 2,4.5,8 — 1,4,5.6,7 — 382 — 244 —
460-60 1,2.7 — 1.2.3.0 — 172 — 110 —
118 575-60 1,2,4,5,6,8 — 1.2,3,5.8 — 118 — 94 —
380-60 1.3.4.5.6.7.8 — 1.2,4,0 — 178 — 142 —
230-60 2.3.4.5.7 — 1,3,7 — 316 — 236 —
208/230-60 2,3,4,6,8 — 1,4.6.7 — 326 — 260 —
460-60 1.2,5,6,7.8 — 1,2,4,5,6,8 — 146 — 118 —
14
6
APPENDIX A (cont)
30GXN,R (Reduced Ambient Data [Position 10 in model no. equal to ‘E’, ‘S’, or ‘U’], Limited Models Only)
ComfortLink™ Compressor Protection Module Configuration Header Punch-Outs and Must Trip Amps
230-50 2.3.4,5,7 — 1.4,57.8 — 316 — 250 —
380/415-50 1,3,4,5,7,8 — 1.2.5.6 — 186 — 152 —
125 575-60 1.2,5.7,8 — 1,2.37.8 — 154 — 106 —
380-60 1,3,7.8 — 1,2.67,8 — 234 — 162 —
230-60 2,4,67 — 1,4,6 — 388 — 264 —
208/230-60 2,7 — 1,6,8 — 428 — 294 —
460-60 1.3.4,6.7.8 — 1.2.4.67 — 194 — 132 —
230-50 2,4,8 — 1.4 — 398 — 272 —
380/415-50 1,3 — 1.2.67 — 240 — 164 —
14
7
APPENDIX A (cont)
30GXN,R (Reduced Ambient Data [Position 10 in model no. equal to ‘E’, ‘S’, or ‘U’], Limited Models Only)
ComfortLink™ Compressor Protection Module Configuration Header Punch-Outs and Must Trip Amps
UNIT VOLTS-Hz PUNCHOU PUNCHOUTS FOR PUNCHOUT PUNCHOUTS COMP A1 COMPA2 MUST COMP B1 COMP B2 MUST
30GXN,R TS FOR COMP A2 S FOR FOR COMP B2 MUST TRIP TRIP AMPS MUST TRIP TRIP AMPS
COMP A1 COMP B1 AMPS SETTING AMPS SETTING
SETTING SETTING
128 575-60 1,2.4.6 — 1.2,3,5.8 — 136 — 94 —
380-60 1,3,4/7 — 1,2,4,8 — 204 — 142 —
230-60 2,3,5.6.7.8 — 1,3,7 — 338 — 236 —
200/230-60 2,4.5,6.a — 1,4,6,7 — 374 — 260 —
460-60 1,2.7.8 — 1.2,4,5,6,8 — 170 — 118 —
230-50 2,3.6,7,8 — 1,4,5,7,8 — 354 — 250 —
380/415-50 1,3,5.6,8 — 1,2.5.6 — 214 — 152 —
136, 283B, 303B, 575-60 1.2,4,6 — 1.2,4.5,6,8 — 136 — 118 —
373B 380-60 1,3,4,'7 — 1,3,4,5,6.7,8 — 204 — 178 —
230-60 2,3,5,6,7,8 — 2,3.4,5.7 — 338 — 316 —
208/230-60 2,4.5,6,8 — 2,3,4,6,8 — 374 — 326 —
460-60 1,2,7.8 — 1.2,5,6,7.8 170 — 146 —
230-50 2,3.6.7,8 — 2,3,4.5,7 — 354 — 316 —
380/415-50 1,3.5,6.8 — 1.3,4.5.7,8 — 214 — 186 —
153, 283A, 328B, 575-60 1,2,7.8 — 1.2,4.5.6.8 — 170 — 118 —
393B, 418B 380-60 1,4.6.7.8 — 1,3,4,5,6,7,8 — 258 — 178 —
230-60 2,7 — 2,3,4,5,7 — 428 — 316 —
208/230-60 3,5,6 — 2,3,4,6,8 — 472 — 326 —
460-60 1,3,5.6.8 — 1,2.5.6,7.8 — 214 — 146 —
230-50 3,4,5,6 — 2,3,4,5.7 — 440 — 316 —
380/415-50 1,4,7,8 — 1,3.4,5,7,8 — 266 — 186 —
163, 303A 575-60 1.2,7-8 — 1.2.4,6 — 170 — 136 —
380-60 1,4,6.7,8 — 1,3.4.7 — 258 — 204 —
230-60 2.7 — 2,3,5,6,7,8 — 428 — 338 —
208/230-60 3,5,6 — 2,4,5,6,8 — 472 — 374 —
460-60 1,3,5,6,8 — 1.2.7.8 — 214 — 170 —
230-50 3,4,5.6 — 2.3,6,7,8 — 440 — 354 —
380/415-50 1,4,7,8 — 1.3,5,6,8 — 266 — 214 —
178, 328A, 353A/B 575-60 1,2,7.8 — 1,2,7,8 — 170 — 170 —
380-60 1.4.6.7.0 — 1,4.6.7,8 — 258 — 258 —
230-60 2,7 — 2,7 — 428 — 420 —
208/230-60 3,5,6 — 3,5.6 — 472 — 472 —
460-60 1.3.5,6,0 — 1,3.5,6,8 — 214 — 214 —
230-50 3.4,5,6 — 3,4,5,6 — 440 — 440 —
300/415-50 1,4,7,8 — 1,4.7.8 — 266 — 266 —
208 575-60 1.2.4.6 1.2,4.6 1,2,4.5,6.8 — 136 136 118 —
380-60 1.3.4.7 1,3,4.7 1,3.4,5,6,7,8 — 204 204 178 —
230-60 2.3.5.6.7.8 2.3.5.6.7.8 2.3.4.5.7 — 338 338 316 —
208/230-60 2.4,5.6.8 2.4,5,6,8 2,3,4,6.8 — 374 374 326 —
460-60 1,2,7.0 1.2,7.a 1,2,5.6.7.8 — 170 170 146 —
230-50 2,3,6,7,0 2.3.6.7.8 2.3.4.5,7 — 354 354 316 —
380/415-50 1,3.5.6.8 1,3.5,6,8 1.3,4.5,7,8 — 214 214 186 —
228, 453A/B, 478B 575-60 1,2,7,8 1.2,4.6 1,2.4,5.6,8 — 170 136 118 —
380-60 1,4,6,7.0 1,3,4.7 1,3.4.5.6.7,0 — 258 204 178 —
230-60 2,7 2,3,5.6,7,8 2,3,4,5,7 — 428 338 316 —
208/230-60 3,5,6 2,4.5.6,8 2,3,4,6,8 — 472 374 326 —
460-60 1,3,5,6,8 1.2,7,8 1.2,5.6,7,8 — 214 170 146 —
230-50 3.4,5,6 2,3,6,7,8 2,3,4,5.7 — 440 354 316 —
380/415-50 1,4,7,8 1,3,5,6,8 1,3,4,5,7,8 — 266 214 186
253, 373A,393A, 575-60 1,2,7,8 1,2.7.8 1,2,4,6 — 170 170 136 —
478A,503A/B 380-60 1,4,6,7.8 1,4,6.7,8 1,3,4,7 — 258 258 204 —
230-60 2,7 2.7 2,3,5,6,7,8 — 428 428 338 —
208/230-60 3,5,6 3,5.6 2,4,5.6,8 — 472 472 374 —
460-60 1,3,5,6,8 1,3,5,6,8 1.2.7.8 — 214 214 170 —
230-50 3,4,5.6 3,4.5.6 2.3,6,7,8 — 440 440 354 —
380/415-50 1.4.7,0 1,4,7,8 1,3,5,6,8 — 266 266 214 —
268, 418A, 528A/B 575-60 1,2,7,8 1.2,7.8 1.2,7,8 — 170 170 170 —
380-60 1.4,6.7,8 1,4,6,7,8 1,4,6.7.8 — 258 258 258 —
230-60 2,7 2,7 2,7 — 428 428 428 —
14
8
APPENDIX E (cont)
30HXC Models
ComforLmk™ Compressor Protection Module Configuration Header Punch-Outs and Must Trip Amps
UNIT VOLTS-Hz PUNCHOUTS PUNCHOUTS FOR PUNCHOUTS COMP A1 MUST COMP A2 MUST TRIP COMP B1 MUST TRIP
30HXC FOR COMP A1 COMP A2 FOR COMP B1 TRIP AMPS SETTING AMPS SETTING AMPS SETTING
14
9
APPENDIX E (cont)
15
0
APPENDIX E (cont)
30HXC Models
ComfortLink™ Compressor Protection Module Configuration Header Punch-Outs and Must Trip Amps
UNIT VOLTS-Hz PUNCHOUTS PUNCHOUTS FOR PUNCHOUTS COMP A1 MUST TRIP COMP A2 MUST TRIP COMP B1 MUST TRIP
30HXC FOR COMP COMP A2 FOR COMP AMPS SETTING AMPS SETTING AMPS SETTING
A1 B1
30HXA Models
Comforíünk™ Compressor Protection Module Configuration Header Punch-Outs and Must Trip Amps
UNIT VOLTS-Hz PUNCHOUTS PUNCHOUTS FOR PUNCHOUTS COMP A1 MUST TRIP COMP A2 MUST TRIP COMP B1 MUST TRIP
30HXA FOR COMP COMP A2 FOR COMP AMPS SETTING AMPS SETTING AMPS SETTING
A1 B1
15
1
APPENDIX E (cont)
30HXA Models
ComfortLink™ Compressor Protection Module Configuration Header Punch-Outs and Must Trip Amps
UNIT VOLTS-Hz PUNCHOUTS PUNCHOUTS FOR PUNCHOUTS COMP A1 MUST TRIP COMP A2 MUST TRIP COMP B1 MUST TRIP
30HXA FOR COMP COMP A2 FOR COMP AMPS SETTING AMPS SETTING AMP SETTING
A1 B1
15
2
APPENDIX E (cont)
15
3
APPENDIX B
Capacity Loading Sequence Example — The fol- chiller. Each compressor has 2 loaders. There is no
lowing tables show the loading sequence for a difference in operation between "Staged” and
30HX186 (50/50 split) and a 30HX161 (59/41 split) “Equal” circuit loading on 2 compressor chillers.
1
5
4
The following tables show the loading sequence for 30HX206 have two loaders and the chillers are configured for
equal circuit
(57/43 split) and 30HX271 (67/33 split) chillers. All compressors loading. See Note 2.
STANDARD LOADING SEQUENCE (CIRCUIT A LEAD CIRCUIT, 3-COMPRESSOR UMIT)
STAGE COMP LOADER LOADER COMP COMP LOADER LOADER % TOTAL % TOTAL
A1 A1 A2 A2 B1 B1 B2 CAPACITY (57/43 CAPACITY (67/33
Split) Split)
0 0 0 0 0 0 0 0 0.0 0.0
1 1 0 0 0 0 0 0 14.3 13.3
2 1 1 0 0 0 0 0 25.0 23.3
3 1 1 1 0 0 0 0 35.7 33.3
4 1 1 0 0 1 1 0 55.2 46.7
5 1 1 0 0 1 1 1 68.2 56.7
6 1 1 1 0 1 1 1 78.9 66.7
7 1 1 0 1 1 1 1 83.0 80.0
8 1 1 1 1 1 1 1 100.0 100.0
LEGEND
1 — Off
2 — On
NOTES:
1. Stages 3A and 7A are not used by the algorithm when increasing stages. Stages 3 and 7 are not
used when decreasing stages.
2. The loading sequence for 30GXN.R204-264 units is the same as those shown for the 30HX206.271
above.
J
APPENDIX B (cont)
The following tables show the loading sequence for staged circuit loading. Loaders Al on compressors Al and A2
30HX206 (57/43 split) and 30HX271 (67/33 split) chillers. All are energized in parallel. The same is true for Loaders
A2 on
compressors have two loaders and the chiller is configured for both compressors Al and A2. See Note 3.
LEGEND
1 — Off
2 — On
NOTES:
1. Stage 3A Is not used by ihe algorithm when increasing stages. Stage 3 is not used by the algorithm when
decreasmg slages.
2. The % Total Capacities above are calculated based on compressor nominal tons. For the case ol the 57/43
split above, the 30HX uses compressors with flow rates of 209, 123, and 250 cfm (from compressor model
numbers 06N_209, 06N_123. and 06N_250), which represen! nominal tons of 66, 39, and 80 (respectively)
at 60 Hz. A factor of 40% is used when no loaders are energized. and a factor of 70% is used when Loader
1 is energized. The capaciiy shown for Slage 4 above is calculated as follows:
% Total Capacity=[(0.70 x 66 + 0.70 x 39 + 0.0 x 80)/(66 + 39 + 80)] x 100% = 39.7%
3. The loading sequence for 30GXN,R204-264 units is the same as those shown for the 30HX206, 271 above.
The following tables show the loading sequence for a 30GXN,R350
chiller. Each compressor has 2 loaders and the chiller is configured for
equal circuit loading. See Note 2.
STANDARD LOADING SEQUENCE (CIRCUIT A LEAD CIRCUIT, 4-COMPRESSOR UNIT)
STAGE COMP LOADER LOADER COMP COMP LOADER LOADER COMP % TOTAL
A1 A1 A2 A2 B1 B1 B2 B2 CAPACITY (50/50 Spiit)
0 0 0 0 0 0 0 0 0 0.0
15
6
APPENDIX B (cont)
1 1 0 0 0 0 0 0 0 10.0
2 1 1 0 0 0 0 0 0 18.0
3 1 1 1 0 0 0 0 0 25.0
4 1 1 0 0 1 1 0 0 35.0
5 1 1 1 0 1 1 0 0 43.0
6 1 1 1 0 1 1 1 0 50.0
7 1 1 0 1 1 1 1 0 60.0
8 1 1 0 1 1 1 0 1 70.0
9 1 1 1 1 1 1 0 1 85.0
10 1 1 1 1 1 1 1 1 100.0
0 0 0 0 0 0 0 0 0 0.0
1 1 0 0 0 0 0 0 0 10.0
2 1 1 0 0 0 0 0 0 18.0
3 1 1 1 0 0 0 0 0 25.0
3A 1 0 0 0 1 0 0 0 20.0
4 1 0 0 0 1 1 0 0 28.0
5 1 1 0 0 1 1 0 0 35.0
6 1 1 1 0 1 1 0 0 43.0
7 1 1 1 0 1 1 1 0 50.0
7A 1 0 0 1 1 1 1 0 45.0
8 1 1 0 1 1 1 1 0 60.0
9 1 1 0 1 1 1 0 1 70.0
10 1 1 1 1 1 1 0 1 85.0
11 1 1 1 1 1 1 1 1 100.0
LEGEND
1 — Off
2 — On
NOTES:
1. Stages 3A and 7A are not used by the algorithm when increasing stages. Stages 3 and 7 are not used
by the algorithm when decreasing stages.
2. The loading sequence for 30GXN.R281-325 units is the same as those shown for the 30GXN.R350
above.
APPENDIX E (cont)
0 0 0 0 0 0 0 0 0 0.0
1 1 0 0 0 0 0 0 0 10.0
2 1 1 0 0 0 0 0 0 18.0
3 1 1 1 0 0 0 0 0 25.0
4 1 1 0 1 0 0 0 0 35.0
5 1 1 1 1 0 0 0 0 50.0
6 1 1 1 1 1 1 0 0 68.0
7 1 1 1 1 1 1 1 0 75.0
8 1 1 1 1 1 1 0 1 85.0
9 1 1 1 1 1 1 1 1 100.0
0 0 0 0 0 0 0 0 0 0.0
1 1 0 0 0 0 0 0 0 10.0
2 1 1 0 0 0 0 0 0 18.0
3 1 1 1 0 0 0 0 0 25.0
3A 1 0 1 0 0 0 0 20.0
4 1 1 0 1 0 0 0 0 35.0
5 1 1 1 1 0 0 0 0 50.0
6 1 1 1 1 1 0 0 0 60.0
7 1 1 1 1 1 1 0 0 68.0
8 1 1 1 1 1 1 1 0 75.0
8A 1 1 1 1 1 0 0 1 70.0
9 1 1 1 1 1 1 0 1 85.0
10 1 1 1 1 1 1 1 1 100.0
LEGEND
1 — Off
2 — On
NOTES:
1. Stages 3A and BA are not used by the algorithm when increasing siages. Stages 3 and 8
are not used by the algorithm when decreasing stages.
2. The loading sequence (or 30GXN.R281-325 unils is the same as Ihose shown for the
30GXN.R350 above.
15
8
APPENDIX C (cont)
Available Accessories (cont)
Available Accessories
J
1
5
9
APPENDIX C
ACCESSORY UNITS DESCRIPTION OF ACCESSORY COMMENTS
PARTNUMBER
30HX-900—035 30GXN.R080,083,090,093, 30HX076-096 (STD) Insulation Kit (14", 3-Pass Cooler, no Tubesheets and heads
30HX116-146 (+1P) Economizer)
30HX-900—036 30GXN,R106,114 (STD) 30HX106 (STD) Insulation Kit (16", 3-Pass Cooler, no Tubesheets and heads
Economizer)
30HX-900—037 30GXN.R080,083,090,093, 30HX076-096 (-1P), 30HX116- Insulation Kit (14", 2-Pass Cooler, no Tubesheets and heads
146 (STD) Economizer)
30HX-900—038 30GXN,R108,125,135 (-1P), Insulation Kit (16", 2-Pass Cooler, with Tubesheets and heads
30GXN.R160,163,174,178.30HX161 -186 (STD) Economizer)
30HX-900—039 30GXN,R204-268 (STD), 30HX206-271 (STD) Insulation Kit (18", 2-Pass Cooler, with Tubesheets and heads
Economizer)
30HX-900—040 30GXN,R106,114 (-1P), 30HX106 (-1P) Insulation Kit (16", 2-Pass Cooler, no Tubesheets and heads
Economizer)
30HX-900—001 30HX116-271 Sound Enclosure Panels
30HX-900—011 30HX076-106 Sound Enclosure Panels
30HX-900—004 30HX076-146 Victaulic Condenser Connections (18 ¡n.)
30HX-900—005 30HX161-186 Victaulic Condenser Connections (20 in.)
30HX-900—015 30HX206-271 Victaulic Condenser Connections (22 in.)
30HX-900—032 30GXN.R and 30HX All Energy Management Module
30HX-900—033 30HX (230 V, 460 V) Conlrol Transformer
30HX-900—034 30HX (575 V) Control Transformer
30GX-900—050 30GXN.R (230 V, 460 V) Control Transformer (080-178*)
30GX-900—051 30GXN,R (575 V) Control Transformer (080-178")
30GX-900—052 30GXN,R (208 V) Control Transformer (080-178’)
30GX-900—055 30GXN.R (230 V, 460 V) Control Transformer (204-350")
30GX-900—056 30GXN.R (575 V) Conlrol Transformer (204-350")
30GX-900—057 30GXN.R (208 V) Conlrol Transformer (204-350")
30GX-900—058 30GXN.R220-528 Dúplex Dúplex Trim Kit
30GX-900—071 30GXN.R080-150, 160" Motormaster® V Control (575 V) Single controller
30GX-900—072 30GXN.R080-150, 160" Motormaster V Control (208/230 V) Single controller
30GX-900—073 30GXN.R080-150,160" Motormasler V Control (380/460 V) Single controller
30GX-900—074 30GXN.R153,163-350" Motormaster V Control (575 V) Two controllers
30GX-900—075 30GXN.R153,163-350* Motormaster V Control (208/230 V) Two controllers
30GX-900—076 30GXN.R153,163-350" Motormaster V Control (380/460 V) Two controllers
CEPL130322-02 30GXN.R and 30HX All Chillervisor System Manager III
CPNLDLK-01 30GXN.R and 30HX All DataLink Control Panel
CPNLDPT-01 30GXN.R and 30HX All DataPort Control Panel
CRLIDASY001A00 30GXN.R and 30HX All Remóle Enhanced Display
30GT-911—049 30GXN.R and 30HX All GFI Convenience Outlet (60 Hz only)
30GT-911—057 30GXN.R All Unit Control Oisplay Window
30GT-911—063 30GXN.R All Remóte Service Pon
16
0
APPENDIX D
Building Interface — The 30GXN,GXR,HX chiller can DataLINK device is an interface device that allows
be interfaced with multi-vendor control systems other HVAC control systems to read and change
through 3 levels of inter-operability using BacLink, (“read/write”) valúes in system elements connected
DataPort™, or DataLINK™ devices. BacLink to a CCN bus. Both DataPort and DataLINK devices
functions as a gateway between a CCN and a request data from a specified CCN system element
BACnet system to facilítate the passing of data from and transíate this data into ASCII characters off
the CCN to BACnet. The Carrier DataPort is an network. Information from the 30GXN,GXR,HX
interface device that allows other HVAC control chiller control to support interface are listed in the
systems to “read only” valúes in system elements following tables.
connected to a CCN communication bus. The
Carrier
Object Definitions
30GXN/GXR/HXA/HXC Series 6 with Software Versión 1.1 and later
CCN Table Descrlption Status Units Point DataPort DataLink BACIink
Ñame
GENERAL PARAMETERS
Control Mode 0 = Service Test STAT RO RO RO
1 = OFF Local
2 = OFF CCN
3 = OFF Clock
4 = OFF Emergency
5 = ON Local
6 = ON CCN
7 = ON Clock
Occupied No/Yes OCC RO RO RO
1 CCN Chiller Start/Stop CHIL S S RO RW RW
H AUINI
IINIT
1 Alarm State Normal/Alert/Alarm ALM RO RO RO
Active Demand Limit Oto 100 O/ DEM LIM RO RW RW
Override Modes In Effect No/Yes /o MODE RO RO NA
Percent Total Capacity Oto 100 o/. CAP T RO RO RO
Active Setpoint -20 to 70 (-28.8 to 21.1) /o SP RO RO NA
Control Point -20 to 70 (-28.8 to 21.1) otr (op\
or ¡on\ CTRL PNT RO RW RW
Entering Fluid Temp snnn.n h ( U) EWT RO RO RO
Leaving Fluid Temp snnn.n r [ o; LWT RO RO RO
Emergency Stop Enable/Emstop r { o; EMSTOP RO RW RW
Minutes Left for Start 00:00 to 15:00 ... MIN LEFT RO RO NA
Heat/Cool Select Heat/Cool Minutes HEATCOOL RO RW RW
CIRC. A DISCRETE OUTPUTS
Compressor A1 Relay Off/On K A1 RLY RO RO RO
Compressor A2 Relay Off/On K A2 RLY RO RO RO
Loader A1 Relay Off/On LOADR A1 RO RO NA
Loader A2 Relay Off/On LOADR A2 RO RO NA
Minimum Load Valve Off/On MLV RO RO NA
Olí Heater Off/On OILA HTR RO RO NA
Motor Cooling A1 Solenoid Off/On MTRCL A1 RO RO NA
CIRCADIO Motor Cooling A2 Solenoid Off/On MTRCL A2 RO RO NA
Oil Pump Off/On OILPMP A RO RO NA
Oil Solenoid A1 Off/On OILSL A1 RO RO NA
Oil Solenoid A2 Off/On OILSL_A2 RO RO NA
CIRC. A DISCRETE INPUTS
Compressor A1 Feedback Off/On K A1 FBK RO RO NA
Compressor A2 Feedback Off/On K A2 FBK RO RO NA
Oil Level Switch Close/Open OlLA.SW RO RO NA
CIRCUIT A ANALOG VALUES
Percent Total Capacity Oto 100 % CAPA T RO RO RO
Percent Available Cap. Oto 100 % CAPA A RO RO RO
Circuit Running Current 0 to 1200 Amps A CURR RO RO NA
Discharge Pressure nnn.n PSIG (KPA) DP A RO RO RO
Suction Pressure nnn.n PSIG (KPA) SP A RO RO RO
Economizer Pressure nnn.n PSIG (KPA) ECNP A RO RO NA
Discharge Superheat Temp snnn.n °F (“O SH A RO RO RO
Discharge Gas Temp nnn.n °F (°C) DISTMP A RO RO NA
Discharge Gas Temp - A1 nnn.n °F (“C) DISTMPA1 RO RO
Discharge Gas Temp - A2 nnn.n °F (°C) DISTMPA2 RO RO
Saturated Condensing Tmp snnn.n °F (°C) TMP SCTA RO RO RO
Saturated Suction Temp snnn.n °F (°C) TMP SSTA RO RO RO
EXV% Open 0 to 100 % EXV A RO RO NA
CIRCA.AN Variable Head Press Pct. Oto 100 % VHPA RO RO NA
COMP A1 ANALOG VALUES
A1 Oil Pressure Diff. nnn.n PSIG (KPA) DOP A1 RO RO NA
A1 Oil Pressure nnn.n PSIG (KPA) OP Á1 RO RO NA
A1 Motor Temperature nnn.n °F (°C) TMTR A1 RO RO NA
Comp A1 Running Current 0 to 600 Amps A1 CURR RO RO NA
Comp A1 % Must Trip Amps Oto 100 %- A1_MTA RO RO NA
COMP A2 ANALOG VALUES
A2 Oil Pressure Diff. nnn.n PSIG (KPA) DOP A2 RO RO NA
A2 Oil Pressure nnn.n PSIG (KPA) OP A2 RO RO NA
16
1
APPENDIX D (cont)
A2 Motor Temperature Object
nnn.nDefinitions (cont) °F (°C) TMTR A2 RO RO NA
Comp A2 Running Current 0 to 600 Amps A2 CURR RO RO NA
Comp A2 % Must Trip Amps Oto 100 ©/ A2 MTA RO RO NA
/o
CCN Table Ñame Description Status Units Point DataPort DataLink BACIink
1
6
2
APPENDIX D (cont)
CCN Table Description Object Definitions
Status (cont) Units Point DataPort DataLink BACIink
Ñame
PUMPS
Cooler Pump Relay Off/On COOL PMP RO RO RO
Condenser Pump Relay Off/On COND_PMP RO RO RO
MISCELLANEOUS
Dual Setpoint Switch Off/On DUAL IN RO RO NA
Cooler Flow Switch Off/On COOLFLOW RO RO NA
Condenser Flow Switch Off/On CONDFLOW RO RO NA
OPTIONS Ice Done No/Yes ICE RO RO NA
(cont) Cooler Heater Off/On COOL HTR RO RO NA
4-20 mA Cooling Setpoint nn.n mA CSP IÑ RO RO NA
4-20 mA Heating Setpoint nn.n mA HSP IN RO RO NA
Liq. Line Solenoid Valve Open/Close LLSV RO RO NA
Dual Chiller Size nnn Tons SIZE DPX RO RO NA
Dual Chiller Pct Total Cap 0-100 % CAPf DPX RO RO NA
Dual Chiller Tons Avail nnn Tons SIZEADPX RO RO NA
Dual Chiller Pct Avail Cap 0-100 % CAPA_DPX RO RO NA
COOLING
Cooling Setpoint 1 -20 to 70 (-28.8 to 21.1) °F (°C) CSP1 NA RW RW
Cooling Setpoint 2 -20 to 70 (-28.8 to 21.1) °F (°C) CSP2 NA RW NA
ICE Setpoint -20 to 32 (-28.8 to 0.0) °F (°C) CSP3 NA RW NA
HEATING
Heating Setpoint 1 80 to 140 (26.7 to 60.0) °F (°C) HSP1 NA RW RW
Heating Setpoint 2 80to 140 (26.7 to 60.0) °F (°C) HSP2 NA RW NA
SETPOINT RAMP LOADING
Cooling Ramp Loading 0.2 to 2.0 (0.1 to 1.1) CRAMP NA RW NA
Heating Ramp Loading 0.2 to 2.0 (0.1 to 1.1) HRAMP NA RW NA
HEAD PRESSURE
Head Pressure Setpoint A 80 to 140 (26.7 to 60.0) °F (°C) HSP A NA RW NA
Head Pressure Setpoint B 80 to 140 (26.7 to 60.0) °F (°C) HSPlB NA RW NA
Approach Setpoint 0.1 to 20.0 °F (°C) APRCH.SP NA RW NA
L
EGEND
°C —
Degrees
Celsius °F
—
Degrees
Fahrenheit
NA — Not
Available
RO —
Read Only
RW —
Read/Writ
e
16
3
APPENDIX D (cont)
'Circuit A Condenser Fan
Object Definitions (cont)
Output (30HXA only). tCircuit B
Condenser Fan Output (30HXA
only).
1
6
4
APPENDIX E
The following charts list pressure drops for coolers and condensers.
£
Unit Size Range
COOLER 30HX
PRESSURE
DROP — SI
1
6
5
CONDENSER FLOW RATE (GPM)
100
0
98
P
R
E
S
S
U
R
E
D
R
O
P
(ft
LEGEND
Electronic Expansión Valve Suction
Pressure Transducer Discharge
Pressure Transducer Economizer
Pressure Transducer Oil Pressure
Transducer High Pressure Switch
Discharge Gas Thermistor Entering
Water Thermistor Leaving Water
Thermistor
Refrigerant Access Fitting
High Flow Schrader Valve
Backseating Service Valve
with Refrigerant Port
Fusible Plug Device Connection
Sighlgla
Sightgla ss
ss Dry Eya
Dry Eye
Typical System Components, 30GXN,GXR080-106,114, Without Economizer
Condenser Fans Condenser Fans LEGEND
Electronic Expansión Valve
Suction Service Valve
— Thermostatic Expansión
Valve
Suction Pressure Transducer
Discharge Pressure Transducer
— Economizer Pressure
Transducer
Oil Pressure Transducer
Liquid Line High Pressure Switch
Service Discharge Gas Thermistor
Valve Entering Water Thermistor
Leaving Water Thermistor
Strainer/
Filter
Refrigerant Access Fitting
Drier High Flow Schrader Valve
— Backseating Service Valve with
Refrigerant Port
Fusible Plug
Device Connection APP
END
IX F
(con
10 t)
O Economizer
T X V.
Sightgla
Sightgla ss
ss Dry Eye
Dry Eye
Typical System Components, 30GXN,GXR108,125-178, With Economizer
LEGEND
— Electronic Expansión Valve
Condenser Fans Condenser Fans — Suction Service Valve
— Thermostatic
Expansión Valve
— Suction Pressure Transducer
— Discharge Pressure Transducer
— Economizer Pressure
Transducer
— Oil Pressure Transducer
— High Pressure Switch
— Discharge Gas Thermistor
Liquid Line — Entering Water Thermistor
Service — Leaving Water Thermistor
Valve — Refrigerant Access Fitting
— High Flow Schrader Valve
— Backseating Service
Valve with Refrigerant
Port
— Fusible Plug
— Device Connection AP
PE
ND
IX
1
Mínimum Load Control F
Solenoid (Option) (co
Mínimum Load nt)
Control Valve
(Option)
Cooler
Heater
(Option)
Condenser Fans Condenser Fans LEGEND
Electronic Expansión Valve
Suction Service Valve
— Thermostatic Expansión
Valve
Suction Pressure Transducer
Discharge Pressure Transducer
— Economizer Pressure
Transducer
Oil Pressure Transducer
High Pressure Switch
Discharge Gas Thermistor
Entering Water Thermistor
Leaving Water Thermistor
Refrigerant Access Fitting
High Flow Schrader Valve
— Backseating Service Valve with
Refrigerant Port
Fusible Plug
Device Connection APP
END
IX F
(con
t)
/„ Econo. Serv.
11 Valve (SSV
Option)
Flow Swilch
^ Sighlglass
Dry Eye
LEGEND Electronic
Expansión Valve Suction Service
Valve Suction Pressure Transducer
Discharge Pressure Transducer
Economizer Pressure Transducer
Oil Pressure Transducer High
Pressure Switch Discharge
Gas Thermistor Entering
Chilled Water Thermistor
Leaving Chilled Water
Thermistor Entering
Condenser Water Thermistor
(Option) Leaving Condenser
Water Thermistor (Option)
Straine
r
Siqhtqla
ss Dry
Eye APP
— Refrigerant Access Fitting
END
High Flow Schrader Valve IX F
Backseating Service Valve (con
with Refrigerant Port t)
Fusible Plug Device
Connection
Sighigla
Sightglas
s Dry ss
Eye Dry Eye
Typical System Components, 30HXC076-146, Without Economizer
EXV — Electronic Expansión Valve
SSV — Suction Service Valve
TXV — Thermostatlc Expansión Valve
Suction Pressure Transducer
Discharge Pressure
Transducer Economizer
Pressure Transducer
Oil Pressure Transducer High
Pressure Switch Discharge
Gas Thermistor Entering
Chilled Water Thermistor
Leaving Chilled Water
Thermistor Entering
Condenser Water Thermistor
(Option) Leaving Condenser
Water Thermistor (Option)
Refrigerant Access Fitting
Liquid Line Solenoid
Valve (Brine Option) High Flow Schrader Valve
Backseating Service Valve
with Refrigerant Port
Fusible Plug Device
Connection
APP
END
IX F
(con
t)
o
o
v
EXV — Electronic Expansión Valve
SSV — Suction Service Valve
TXV — Thermostatic Expansión
Valve
1 — Suction Pressure Transducer
2 — Discharge Pressure Transducer
3 — Economizer Pressure Transducer
4 — Oil Pressure Transducer
5 — High Pressure Switch
6 — Discharge Gas Thermistor
7 — Entering Chilled Water
Thermistor
8 — Leaving Chilled Water
Thermistor
9 — Entering Condenser
Water Thermistor (Option)
10 — Leaving Condenser
Water Thermistor (Option)
í — Refrigerant Access Fitting
Economizer
Relief Valve
3
© A
4 Q c1 b
Suction Service Valve (Option) Suction Service Valve (Oplion)
©
EXV
t
Y y
Ftow
Switch
/ice Valve
Service
(SSVVOi
Oplion)
{S}
Typical System Components, 30HXC206-271 Circuit A, With Economizer
LEGEND
EXV - Electronic Expansión Valve
SSV - Suction Service Valve
TXV - Thermostatic Expansión Valve
Suction Pressure Transducer
1 Discharge Pressure Transducer
2 Economizer Pressure Transducer Oil
3 Pressure Transducer High Pressure
4 Switch Discharge Gas Thermistor
5 Entering Chilled Water Thermistor
6 Leaving Chilled Water Thermistor
7 Refrigerant Access Fitting
8 High Flow Schrader Valve
Backseating Service Valve with
5 Refrigerant Port
Fusible Plug Device Connection
¥
R]
Y
I APP
END
IX F
(con
t)
Motor Cooling i
Solenoid Valve
Economizer Solenoid
Service
Valve (SSV
Option)
Sightglass
Dry Eye
EXV O Flow
Switch
I1
3
EXV - Electronic Expansión Valve Suction
To Condenser ssv - Service Valve Thermostatic
TXV - Expansión Valve
Suction Pressure Transducer
1 Discharge Pressure Transducer
Strainer/
Filter Drier 2 Economizer Pressure Transducer
3
Oil Pressure Transducer High
4 Pressure Switch Discharge Gas
5 Thermistor Entering Water
6 Thermistor Leaving Water
7 Thermistor
8
Refrigerant Access Fitting
5
High Flow Schrader Valve
Backseating Service Valve
í with Refrigerant Port
R] Fusible Plug Device Connection
APP
Y END
IX F
(con
112 t)
Flow Switch
Sightgla
ss Dry
Eye
DESCRIPTION STATUS UNITS POINT FORCIBLE
Control Mocíe 1 = Service Tesl STAT N
2 = Off - Local
3 = Off - CCN
4 = Off - Clock
5 = Off Emergency
6 = On - Local
7 = On-CCN
8 = On - Clock
Occupied Yes/No OCC N
CCN Chiller Slart/Slop CHIL.S.S •Y
Alarm State 1 = Normal ALM N
2 = Alarm 2= Alert
1
1
9
APPENDIX G (cont)
Condenser Entering Fluid ALARMDEF:
snnn.n Alarm Configuration
»c COND_EWT N
Condenser Leaving Fluid snnn.n ac COND..LWT N
Lead/Lag Leaving Fluid snnn.n *F DUAL^LWT N
TEMPEHATURE RESET
4 - 20 ma Reset Signal nn.n ma RST„MA N
Outdoor Air Temperature snnn.n ■F OAT Y
Space Temperature snnn.n °F SPT Y
DEMAND LIMIT
4 - 20 ma Demand Signal nn.n ma LMT.MA N
Demand Limit Switch 1 On/OH DMD.SWt N
Demand Limit Switch 2 On/Oft DMD.SW2 N
CCN Loadshed Signal 1 = Normal DL_STAT N
2 = Rsdline
3 - Loádshed
PUMPS
Cooler Pump Relay On/OII COOL_PMP N
Condenser Pump Relay On/OK COND_PMP N
MISCELLANEOUS
Dual Setpoint Switch On/OII DUAL_IN N
Cooler Flow Switch On/OII COOLFLOW N
Condenser Flow Switch On/Ofl CONDFLOW N
Ice Done Yes/No ÍCE N
Cooler Heater On/Ofl COOL .HTR N
4-20 ma Cooling Setpoint nn.n ma CSPJN N
4-20 ma Heating Setpoint nn.n ma HSPJN N
Liq. Line Solenoid Valve Open/Ciosa LLSV N
120
APPENDIX G (cont)
Month 1 toOPTIONS:
12 Status Display
4 STARTM
Week 1 tos 1 STARTW
Day 1 to 7 7 STARTD
Minutes to Add Oto 99 60 min MINADD
Dayllght Savings Stop
Month 1 to 12 10 STOPM
Week 1 to 5 5 STOPW
Day 1 to 7 7 STOPD
Minutes to Subtract Oto 99 60 min MINSUB
12
1
APPENDIX G (cont)
EXV_CONF: Configuration
DESCRIPTION STATUS DEFAULT UNITS POINT
EXVA Stepper Type 0=1500 Step 1 EXVATYPE
1=15000 Step
EXVA Steps In Range Type 0=1500 Type 15000 STEPS EXVARANG
1=15000
EXVA Steps Per Second Type 0=30 Type 300 EXVARATE
1=300
EXVA Fail Position In % 0 % EXVAPOSF
EXVA Mínimum Steps 0 STEPS EXVAMINS '
EXVA Máximum Steps Type 0=1500 Type 15000 STEPS EXVAMAXS
1=15000
EXVA Overrun Steps Type 0=100 Type 1000 STEPS EXVAOVRS
1=1000
EXVB Stepper Type 0=1500 Step 1 EXVBTYPE
1=15000 Step
EXVB Steps in Range Type 0=1500 Type 15000 STEPS EXVBRANG
1=15000
EXVB Steps Per Second Type 0=30 Type 300 EXVBRATE
1=300
EXVB Fail Position ¡n % 0 % EXVBPOSF
EXVB Minimum Steps 0 STEPS EXVBMINS
EXVB Máximum Steps Type 0=1500 Type 15000 STEPS EXVBMAXS
1=15000
EXVB Overrun Steps Type 0=100 Type 1000 STEPS EXVBOVRS
1=1000
122
APPENDIX G (cont)
DESCRIPTION RESETCON: Options
STATUS Configuration DEFAULT POINT
Cooler Fluid 1 = Water 1 FLUIDTYP
2 = Med, Brine
3 - Low Brine
Min. Load Valve Select No/Yes No MLV FLG
Head Press. Control Type 1 = None 0 HEAD.TYP
2 = Air Cooled
3 = Water Cooled
4 = Common Condenser
5 = Independent Condenser
Var Head Pressure Select 1 = None 0 VHPTYPE
2 = 4-20 mA
3 = 0-20 mA
4 = 20-0 mA
Pressure Transducers No/Yes Yes PRESS_TY
Cooler Pump Control Off/On Off CPC
Condenser Pump Interlock Off/On Off CND.LOCK
Condenser Pump Control 1 = Not Controlled 0 CNPC
2 = On when STATE is On
3 = On when compressors are On
Condenser Fluid Sensors No/Yes No CD_TEMP
EMM Module Installed No/Yes No EMM.BRD
123
APPENDIX G (cont)
Return — Full Reset Temp OPTIONS1: Oto
Options
10 Configuration 0 A
F CRTN_FUL
Return — Degrees Reset -30 to +30 0 AF CRTN_DEG
HEATING RESET
Heating Reset Type 1 = No Reset 0 HRST_TYP
2 = 4 to 20 mA Input
3 = External Temp — OAT 3=
Return Fluid
4 = External Temp — SPT
4-20 MA RESET
4-20 — Degrees Reset -30 to +30 0 H420.DEG
REMOTE RESET
Remóte — No Reset Temp Oto 125 50 dF HREM_NO
Remóte — Full Reset Temp Oto 125 80 dF HREM.FUL
Remóte — Degrees Reset —30 to +30 0 Ap HREM.DEG
RETURN TEMPERATURE RESET
Return — No Reset Temp Oto 10 10 AF HRTN_NO
A
Return — Full Reset Temp Oto 30 0 F HRTN FUL
A
Return — Degrees Reset -30 to +30 0 F HRTNJ3EG
DEMAND LIMIT
Demand Limit Select 1 = None 0 DMD_CTRL
2 = External Switch Input
3 = 4 to 20 mA Input 3=
Loadshed
Demand Limit at 20 mA Oto 100 100 % DMT20MA
Loadshed Group Number Oto 99 0 SHED_NUM
Loadshed Demand Delta Oto 60 0 % SHEDJ3EL
Máximum Loadshed Time Oto 120 60 min SHED„TIM
Demand Limit Switch 1 Oto 100 80 % DLSWSP1
Demand Limit Switch 2 Oto 100 50 % DLSWSP2
LEAD/LAG
Lead/Lag Chiller Enable Dlsable/Enable Dísable LL_ENA
Master/Slave Select Slave/Mastor Master MS_SEL
Slave Address 0 to 239 2 SLV_ADDR
Lead/Lag Balance Select 1 = Master Leads 0 LL.BAL
2 = Slave Leads
3 = Automatic
Lead/Lag Balance Delta 40 to 400 168 hours LL_BAL_D
Log Start Delay Oto 30 5 min LL.DELAY
Parallel Configuration Yes/No No PARALLEL
124
APPENDIX G (cont)
SETPOINT: Configuration
DESCRIPTION STATUS DEFAULT UNITS POINT
COOLING
Cool Setpoint 1 -20 to 70 44.0 •F CSP1
Cool Setpoint 2 -20 to 70 44.0 *F CSP2
Ice Setpoint -20 to 32 32.0 *F CSP3
HEATING
Heat Setpoint 1 80 to 140 100.0 *F HSP1
Heat Setpoint 2 80 to 140 100.0 •F HSP2
RAMP LOADING
Cooling Ramp Loading 0.2 to 2.0 1.0 CRAMP
Heating Ramp Loading 0.2 to 2.0 1.0 HRAMP
HEAD PRESSURE
Head Pressure Setpoint A 80 to 140 113 "F HSP_A
Head Pressure Setpoint B 80 to 140 113 «F HSP_B
SERVICE: Configuration
DESCRIPTION STATUS DEFAULT UNITS POINT
PID GAINS
Head Pressure P Gain -20.0 to +20.0 1.0 HD_PGAIN
Head Pressure 1 Gain -20.0 to +20.0 0.1 HDJGAIN
Head Pressure D Gain -20.0 to +20.0 0.0 HD_DGAIN
Water Valve Mínimum Pos. 0 to 100 20 % HDJVIIN
MISCELLANEOUS
Motor Temp Setpoint 120.0 to 240.0 200.0 °F MTR_T_SP
Brine Freeze Point -20.0 to 34.0 34.0 °F BRN.FRZ
COMPRESSOR ENABLE
Enable Compressor A1 Enable/Dsable Enable ENABLEA1
Enable Compressor A2 Enable/Dsable Enable ENABLEA2
Enable Compressor B1 Enable/Dsable Enable ENABLEB1
Enable Compressor B2 Enable/Dsable Enable ENABLEB2
12
1
DESCRIPTION STATUS UNITS POINT
Dual Chiller Link Good? Yes/No DCJJNK
Master Chiller Role STAND ALONE. Lead Chiller, Lag Chiller MC.ROLE
Slave Chiller Role STAND ALONE, Lead Chiller, Lag Chiller SC^ROLE
Lead Chiller Ctrl Point snnn.n dF LEAD.CP
Lag Chiller Ctrl Point snnn.n dF LAG_CP
Control Point snnn.n dF CTRL PNT
Cool Entering Fluid-Slave snnn.n dF COOLEWTS
Cool Leaving Fluid-Slave snnn.n dF COOLLWTS
Cooler Entering Fluid snnn.n dF COOL„EWT
Cooler Leaving Fluid snnn.n dF COOL_LWT
Lead/Lag Leaving Fluid snnn.n dF DUAL_LWT
Percent Avail.Capacity 0-100 % CAP_A
Percent Avail.Cap.Slave 0-100 % CAP_A_S
Lag Start Delay Time hh:mm LAGDELAY
Load/Unload Factor snnn.n SMZ
Load/Unload Factor-Slave _ snnn.n SMZSLAVE
Lead SMZ Clear Commanded Yes/No LEADSMZC
Lag- SMZ Clear Commanded Yes/No LAG _SMZC
Lag Commanded Off? Yes/No LAG_OFF
Dual Chill Lead CapLImit 0-100 % DCLDCAPL
Dual Chill Laq CapLimit 0-100 % DCLGCAPL
J
DESCRIPTION STATUS UNITS POINT
A1 Oil Pressure snnn.n PSIG OP_A1
A2 Oil Pressure snnn.n PSIG OP_A2
B1 Oil Pressure snnn.n PStG OPJ31
B2 Oil Pressure snnn.n PSIG OP_B2
125
DESCRIPTION STATUS POINT
Winterizatlon Performed No WINTDONE
Dale Winterlzed 00/00/00 00:00 WMSG00
Date Winterlzed 00/00/00 00:00 WMSG01
Date Winterlzed 00/00/00 00:00 WMSG02
Date Winterlzed 00/00/00 00:00 WMSG03
Date Winterlzed 00/00/00 00:00 WMSG04
Date Wlnterize Alerted 00/00/00 00:00 WALRT00
Date Wlnterize Alerted 00/00/00 00:00 WALRT01
Date Wlnterize Alerted 00/00/00 00:00 WALRT02
Date Wlnterize Alerted 00/00/00 00:00 WALRT03
Date Wlnterize Alerted 00/00/00 00:00 WALRT04
Date Wlnter Configured 00/00/00 00:00 WCONFOO
Date Wlnter Unconfigured 00/00/00 00:00 WUCONFOO
Date Wlnter Configured 00/00/00 00:00 WCONFOI
Date Wlnter Unconfigured 00/00/00 00:00 WUCONFOI
Date Wlnter Configured 00/00/00 00:00 WCONF02
Date Wlnter Unconfigured 00/00/00 00:00 WUCQNF02
)
APPENDIX H
30GXN,R Dúplex Combinations
SIZE MODULE A MODULE B
283 153 138
303 163 138
328 178 153
353 178 178
370 225 150
373 253 138
390 264 135
393 253 153
415 264 160
418 268 153
450 225 225
453 228 228
475 249 225
478 253 228
500 249 249
503 253 253
525 264 264
528 268 268
127
APPENDIX I: MOTORMASTER® V OPERATION INSTRUCTION
I
that it can be changed by using
the up and down buttons.
Use Q and [▼) to change
setting.
Press Mode to store new setting.
Pressing the Mode will store the
new setting and also exit the
PROGRAM mode. To change
another parameter, press the
Mode key again to re-enter the
PROGRAM mode (the param-
eter menú will be accessed at
the parameter that was last
viewed or changed before
exiting). If the Mode key is
pressed within two minutes of
exiting the PROGRAM mode,
the password is not required
access the parameters. After
two minutes, the password
must be entered in order to
access the parameters again.
To change password: first enter
the current password then
change parameter P44 to the
desired password.
To reset factory defauits: change
P48 to one of the 4 operating
modes (5-8) and then cycle
power.
Table 2 shows all program
parameters for each of the 4
operating modes.
EPM chip:
This drive uses a removable
EPM chip to store program
parameters. It should not be
removed with power applied to
the VFD.
PARAMETER APPENDIX
DESCRIPTION I (cont) OPERATING MODES
NUMBER Group 5 Group 6 Group 7 Group 8
Table 2: Program Parameters for the 4 Operating Modes:
P01 Line Voltage: 01 = low line. 02 = high line 01 02 01 02
P02 Carrier Freq: 01=4 kHz, 02 = 6 kHz, 03 = 8 kHz 01 01 01 01
P03 Startup mode: fiying restarl 06 06 06 06
P04 Stop mode: coast to stop 01 01 01 01
P05 Standard Speed source: 04 = 4-20 ma, 05 = R22, 06 = R134a 04 04 04 04
P06 TB-14 output: 01 = none 01 01 01 01
P08 TB-30 output: 01 = none 01 01 01 01
P09 TB-31 output: 01 = none 01 01 01 01
P10 TB-13A function sel: 01 = none 01 01 01 01
P11 TB-13B function sel: 01 = none 01 01 01 01
P12 TB-13C function sel: 01 = none 01 01 01 01
P13 TB-15 output: 01 = none 01 01 01 01
P14 Control: 01 = Terminal strip 01 01 01 01
P15 Serial link: 02 = enabled 9600,8,N,2 w/timer 02 02 02 02
P16 Units editing: 02 = whole units 02 02 02 02
P17 Rotation: 01 = torward only, 03 = reverse only 01 01 01 01
P19 Acceleration time: 10 sec 10 10 10 10
P20 □eceleration time: 10 sec 10 10 10 10
P21 De brake time: 0 0 0 0 0
P22 DC BRAKE VOLTAGE 0% 0 0 0 0
P23 Min freq = 8 hz - 100 - 160 rpm 8 8 8 8
P24 Max freq 60 60 50 50
P25 Current limit: 125 125 110 110
P26 Motor overload: 100 100 100 100 100
P27 Base freq: 60 or 50 Hz 60 60 50 50
P28 Fixed boost: 0.5 % at low frequencies 0.5 0.5 0.5 0.5
P29 Accel boost: 0% 0 0 0 0
P30 Sllp compensation: 0% 0 0 0 0
P31 Preset spd #1: 0 57 57 47 47
P32 Preset spd #2: 0 0 0 0 0
P33 Preset spd #3: 0 0 0 0 0
P34 Preset spd 4 default - R22 setpoint, TB12-2 open 18.0 18,0 18.0 18.0
P35 Preset spd 5 default - R134a setpoint, TB12-2 closed 12.6 12.6 12.6 12.6
P36 Preset spd 6 default 0 0 0 0
P37 Preset spd 7 default 0 0 0 0
P38 Sfcip bandwidth 0 0 0 0
P39 Speed scaling 0 0 0 0
P40 Frequency scaling 50 or 60 Hz 60 60 50 50
P41 Load scaling: default [not used so NA) 200 200 200 200
P42 Accel/decel #2: default (not used so NA) 60 60 60 60
P43 Serial address 1 1 1 1
P44 Password:111 111 111 111 111
P45 Speed at min signal: 8 Hz used when PID disabled and 4-20ma Input 8 8 8 8
P46 Speed at max feedback: 60 or 50 Hz. Used when PID disabled and 4-20ma input 60 60 50 50
P47 Clear history? 01 = maintain, (set to 00 to clear) 01 01 01 01
P4S Program selectlon: Mode 1-12 05 06 07 08
P61 Pl Mode: 05 = reverse. 0-5V, 01 = no PID 01 01 01 01
P62 Min feedback = 0 (0V *10) 0 0 0 0
P63 Max feedback = 50 (5V * 10) 50 50 50 50
P64 Proportional gain = 4% 4 A 4 4
P65 Integral gain = .2 .2 ,2 .2 .2
P66 Pl accel/decel (setpoint change filter) = 5 5 5 5 5
P67 Min alarm 0 0 0 0
P68 Max alarm 0 0 0 0
4 ma 0% 20% 8Hz
12 ma 50% 60% 26Hz
20 ma 100% 100% 60Hz
The MMV also provides real unsuccessful, the drive will trip
time monitoring of key inputs into
and outputs. The collective FAULT LOCKOUT (LC), which
group is displayed through requires a manual reset. See
para-meters 50-56 and all Tables 4 and 5.
valúes are read only. To disable external control mode (5-8)
• P50 FAULT HISTORY — Last 8 and enter manual speed control mode:
faults
• P51: SOFTWARE versión Change P05 to ‘01-key pad’
• P52: DC BUS VOLTAGE — in
percent of nominal. Usually Push Q and [▼] arrow key to set
rated input voltage x 1.4. manual speed.
• P53: MOTOR VOLTAGE — in
percent of rated output To provide manual start/stop control:
voltage Remove start command jumper
• P54: LOAD — in percent of and install a switch between
drives rated output current the appropriate start termináis.
rating Loss of CCN Communications:
CCN Communications with extemal
• P55: VDC INPUT — in
control systems can be affected
percent of máximum input: by high frequency electrical
50 will indicate full scale noise generated by
which is 5 v Motormaster V control. Ensure
• P56: 4-20 mA INPUT — in unit is well grounded to elimínate
percent of máximum input: ground currents along
20% = 4 mA, 100% = 20 mA communication lines.
Fault codes: If Communications are lost only
The drive is programmed to while Motormaster V control is
automatically restart after a in operaüon, order a signal
fault and will attempt to restart isolator/repeater (CEAS420876-
three times after a fault (the 2) and power supplies
drive will not restart after CF, (CEAS221045-01, 2 required)
cF, GF, Fl, F2-F9, or Fo faults). for the CCN communication
If all three restart attempts are line.
GF Data Fault: User data and OEM dofaults m the EPM are Restore factory defaults by toggling P48 to another mode.
corrupted. Then set P48 to desired mode to restore all defaults for that mode.
See configuration section (Step 2). If that does not work, replace EPM,
HF High DC Bus Voltage Fault: Line voltage is too high; Deceleration Check line voltage — set P01 appropriately
rate is too fast; Overhauling load.
JF Serial Fault: The watchdog timer has timed out, indicating that the Check serial connection (Computer)
serial link has been lost. Check settings for P15
Check settings in communication software to match P15
LF Low DC Bus Voltage Fault: Line voltage ¡s too low. Check line voltage — set P01 appropriately
OF Output Transistor Fault: Phase to phase or phase to ground short Reduce boost or increase acceleration valúes. If unsuccessful, replace drive.
circuit on the output; Failed output transistor; Boost seltings are
too high; Acceleration rate is too fast.
PF Current Overload Fault: VFD is undersized for the applica- tion; Check line voltage — set P01 appropriately
Mechanical problem with the driven equipment. Check for dirty coils
Check for motor bearing failure
SF Single-phase Fault: Single-phase input power has been applied Check input power phasíng
to a three-phase drive.
F1 EPM Fault: The EPM is missing ordamaged.
F2-F9, Fo Internal Faults: The control board has sensed a problom. Consult factory.
Drive display = '—1 even Start contact is not closed. Check auxiliary contact for proper operation and configuration. See configuration
though drive should be running section (Step 5).
Drive display = 8.0 Hz even Control signal is at 4 mA Saturated condensing temperature is below setpoint
though tan should be running in ComfortLink Controls.
íaster
VFD flashes 57 (or 47) and Speed signal lost. Drive will operate at 57 (or 47) Hz untll reset or In stand-alone mode: In external control mode (30GXN,R) check wiring from unit
LCS loss of start command, Resetting requires cycling start command Controls J8 for 4-20 mA signal. Drive runs at 57 Hz in modes 5.6 and 47 Hz in
(or power). modes 7.8.
VFD flashes “LCS and ” Start contact is not closed. Check auxiliary contact for proper operation and configuration. See configuration
section (Step 5).
LC Fault lockout — 3 or more unsuccessful starts View PSD: Fault History to determine.
o
z
-J
<
c
c
L
U
s
s
c
c
tu
X
O) o
o
c
u
D
o
o
c
(
0
c
d
)
c
'
5
£
O £
■o
’5
C r
□ ü^?
5
0)
üs6:
i-
O o
co z
w -J
0> LU
'Z Q
a> o
0) s
o CC
LU
xcoo
{©Sí
w
cr
1
LU
CC
C
o
p
yr
ig
ht
2
0
0
4
APPENDIX J
C
ar
ri
er
C
or
p
or
at
io
n
M
a
n
uf
ac
tu
re
r
re
se
rv
es
th
e
ri
g
ht
to
di
sc
o
nti
n
u
é,
or
ch
a
n
g
e
at
a
ny
ti
m
e,
sp
ec
ifi
ca
tio
ns
or
d
es
ig
ns
wi
th
o
ut
n
otl
ce
a
n
d
wi
th
o
ut
ín
cu
rri
n
g
o
bli
g
ati
o
ns
.
00052 Printed in U.S.A. Form 30G.H-9T Pg 130 1-04 Replaces: New
START-UP CHECKLIST FOR 30GX,HX LIQUID CHILLER
Project Information
Job Ñame________________
City __________________
Installing Contractor
Sales Office
_____________________
Start-up Performed By
Design Information
Capacity EWT LWT Fluid Type Flow Rate P.D. Ambient
Cooler
Condenser
Equipment
Compressors
Serial
A1) Model ._______
Serial
A2) Model ________
Serial
B1) Model _______
Serial
B2) Model _______
Circuit A Circuit B
Book 2
PC 903 Catalog No. 533-00052 Printed in U.S.A. Form 3QG.H-9T Replaces:
Pg New
1-04
CL-1
Tab 5c
II. Preliminary Equipment Check (to be completed by installing contractor)
Description _____________________________
_________
________________________________________
4. Electrical power wiring is instalied properly. (Branch circuit fused or HACR breaker) □ Yes □ No
6. Electrical circuit protection has been sized and instalied properly. □ Yes □ No
9. All cables and thermistors have been inspected for crossed wires. □ Yes □ No
7. Water loop volume greater than 3 gal/ton for air conditioning or 6 gal/ton for process cooling □ Yes □ No
and low ambient operation.
7. Condenser water flow switch installed. (Required for 30HXC Brine.) □ Yes □ No
9. Condenser water control valve installed. (Separate control power required.) □ Yes □ No
2. Equalizer line is installed from motor cooling line to back-pressure valve. □ Yes □ No
6. Refrigerant piping and condenser have been leak checked and evacuated. □ Yes □ No
Unit Start-Up
6. Leak check unit. Lócate, repair and report any refrigerant leaks. □ Yes □ No
(DO NOT start chiller if voltage imbalance is greater than 2%. Contact local Utility for
assistance.)
9. □ No
Verify cooler flow rate (máximum and minimum) □ Yes Pressure enterina cooler psia (kpa)
Pressure leavina cooler psia (kpa)
Cooler pressure drop psia (kpa)
Psio x 2.31 ft/psi = ft of water Kpa x 0.334 m/psi = m of water
Máximum cooler flow rate apm (l/s) (See Cooler Pressure DroD Curve) Minimum cooler flow rate apm (l/s) (See
Cooler Pressure Drop Curve)
CL-3
III. Unit Start-Up (cont)
9. Verify condenser flow rate. □ Yes □ No
Pressure entering condenser __________________psig (kpa)
Pressure leaving condenser __________________ psig (kpa)
Condenser pressure drop ____________________psig (kpa)
Psig x 2.31 ft/psi = _____ ft of water
Kpa x 0.334 m/psi = _________ m of water
Condenser flow rate _________gpm (l/s) (See Condenser Pressure Drop Curve)
Oil Charge
Additional charge required ____________
Comments:
Signatures:
Date________________ Date__________________
Record Software Versions
MODE — RUN STATUS
SUB-MODE ITEM DISPLAY ITEM
EXPANSION
VERS MBB CESR131344-_________
EXV CESR131172-__________
EMM CESR131174-__________
CP1 100233-1 R3-„„-„
CP2 100233-1 R3-__
SCB CESR131226-_________
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
NAVl CESR131227-_ __
CL-6
SUB-MODE ITEM DISPLAY ITEM EXPANSION ENTRY
OPT2 CTRL X CONTROL METHOD
CCNA XXX CCN ADDRESS
CCNB XXX CCN BUS NUMBER
BAUD X CCN BAUD RATE
LOAD X LOADING SEQUENCE SELECT
LLCS X LEAD/LAG SEQUENCE SELECT
CP.SQ X COMPRESSOR SEQUENCE
LCWT XX.X HIGH LCW ALERT LIMIT
DEL.Y XX MINUTES OFF TIME
CLS.C ENBUDSBL CLOSE CONTROL SELECT
ICE.M ENBUDSBL ICE MODE ENABLE
C.UNB XX% CURRENT UNBALANCE SETPOINT
NO.FL ENBUDSBL NO REFRIGERANT FLOW ALRM ENABLE
W.MSG ENBUDSBL WINTERIZE ALERT CONFIG
ALR.C X ALARM RELAY USAGE
RSET CRST X COOLING RESET TYPE
CRT1 XXX.X NO COOL RESETTEMP
CRT2 XXX.X FULLCOOLRESETTEMP
DGRC XX.X DEGREES COOL RESET
HRST X HEATING RESET TYPE
HRT1 XXX.X NO HEAT RESETTEMP
HRT2 XXX.X FULL HEAT RESET TEMP
DGRH XX.X DEGREES HEAT RESET
DMDC X DEMAND LIMIT SELECT
DM20 xxx% DEMAND LIMIT AT 20 MA
SHNM XXX LOADSHED GROUP NUMBER
SHDL XXX% LOADSHED DEMAND DELTA
SHTM XXX MAXIMUM LOADSHED TIME
DLS1 XXX% DEMAND LIMIT SWITCH 1
DLS2 XXX% DEMAND LIMIT SWITCH 2
LLEN ENBUDSBL LEAD/LAG CHILLER ENABLE
MSSL SLVE/MAST MASTER/SLAVE SELECT
SLVA XXX SLAVE ADDRESS
LLBL X LEAD/LAG BALANCE SELECT
LLBD XXX LEAD/LAG BALANCE DELTA
LLDY XXX LAG START DELAY
PARA YES/NO PARALLEL CONFIGURATION
SLCT CLSP X COOLING SETPOINT SELECT
HTSP X HEATING SETPOINT SELECT
RL.S ENBUDSBL RAMP LOAD SELECT
CRMP x.x COOLING RAMP LOADING
HRMP x.x HEATING RAMP LOADING
HCSW COOUHEAT HEAT COOL SELECT
Z.GN x.x DEADBAND MULTIPLIER
BRN.L YES/NO HXC BRINE CONFIG LOCK
SUB-MODE ITEM DISPLAY ITEM EXPANSION ENTRY
SERV H.PGN XX.X HEAD PRESSURE P GAIN
H.IGN XX.X HEAD PRESSURE I GAIN
H.DGN XX.X HEAD PRESSURE D GAIN
H.MIN XXX.X WATER VALVE MINIMUM POS
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
MODE — SETPOINT
SUB-MODE ITEM DISPLAY ITEM EXPANSION ENTRY
COOL CSP.1 XXX.X COOLING SETPOINT 1
CSP.2 XXX.X COOLING SETPOINT 2
CSP.3 XXX.X ICE SETPOINT
HEAT HSP.1 XXX.X HEATING SETPOINT 1
HSP.2 XXX.X HEATING SETPOINT 2
HEAD HD.P.A XXX.X HEAD PRESSURE SETPOINT A
HD.P.B XXX.X HEAD PRESSURE SETPOINT B
Component Test — Complete the following tests to make sure all peripheral components are operational before the compressors are started.
MODE-SERVICE TEST
To Enable Service Test Mode, move Enable/Off/Remote Contact Switch to OFF. Configure TEST to ON. Move Switch to ENABLE.
SUB-MODE ITEM DISPLAY ITEM EXPANSION ENTRY
TEST ON/OFF SERVICE TEST MODE COMPLETE
OUTS EXV.A xxx % EXV % OPEN
VH.PA xxx % VAR HEAD PRESS %
OLP.A ON/OFF OIL PUMP ■
MC.A1 ON/OFF MOTOR COOLING SOLENOID A1
MC.A2 ON/OFF MOTOR COOLING SOLENOID A2
OS.A1 ON/OFF OIL SOLENOID A1
OS.A2 ON/OFF OIL SOLENOID A2
EXV.B xxx % EXV % OPEN
VH.PB xxx % VAR HEAD PRESS %
OL.P.B ON/OFF OIL PUMP
MC.B1 ON/OFF MOTOR COOLING SOLENOID B1
MC.B2 ON/OFF MOTOR COOLING SOLENOID B2
OS.B1 ON/OFF OIL SOLENOID B1
OS.B2 ON/OFF OIL SOLENOID B2
FAN1 ON/OFF FAN 1 RELAY
FAN2 ON/OFF FAN 2 RELAY
FAN3 ON/OFF FAN 3 RELAY
FAN4 ON/OFF FAN 4 RELAY
CLR.P ON/OFF COOLER PUMP RELAY
CLR.H ON/OFF COOLER HEATER
CND.P ON/OFF CONDENSER PUMP RELAY
RMT.A ON/OFF REMOTE AU\RM RELAY
COMP CC.A1 ON/OFF COMPRESSOR A1 RELAY
CC.A2 ON/OFF COMPRESSOR A2 RELAY
LD.A1 ON/OFF LOADER A1 RELAY
LD.A2 ON/OFF LOADER A2 RELAY
MLV ON/OFF MINIMUM LOAD VALVE
OL.H.A ON/OFF OIL HEATER
CC.B1 ON/OFF COMPRESSOR B1 RELAY
CC.B2 ON/OFF COMPRESSOR B2 RELAY
LD.B1 ON/OFF LOADER B1 RELAY
LD.B2 ON/OFF LOADER B2 RELAY
OL.H.B ON/OFF OIL HEATER
CL-9
ALL UNITS:
Record the following Information from the Pressures and Temperatures Modes when machine is In a stable operation condition.
CIRCUIT A CIRCUIT B
SATURATED CONDENSING TEMP _______________________ __________________
SATURATED SUCTION TEMP ._________________
DISCHARGE SUPERHEAT TEMP (Comp 1/Comp 2) ___________________________________
MOTOR TEMPERATURE (Comp 1/Comp 2) __________________________
DISCHARGE PRESSURE _________ __________________
SUCTION PRESSURE ._________________________
ECONOMIZER PRESSURE ________________________________________________
OIL PRESSURE (Comp 1/Comp 2)
OIL PRESSURE DIFF. (Comp 1/Comp 2)____________________________________________________________________
OIL FILTER DIFF. (Comp 1/Comp 2)
CALCULATED OIL PRESS (Comp 1/Comp 2)
L1 L2 L3
Compressor A1_______________________
Compressor A2
Compressor B1 ____
Compressor B2______________________
L1
Fan Motor 1 __
Fan Motor 2
Fan Motor 3 ____
Fan Motor 4 ____
Fan Motor 5 ____
Fan Motor 6
Fan Motor 7 ____
Fan Motor 8 ____
Fan Motor 9
Fan Motor 10 ____
Fan Motor 11
Fan Motor 12 ____
Fan Motor 13
Fan Motor 14 __
Fan Motor 15 Fan Motor
16
CL-
10
I