Rxyq T PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 57

Air Conditioning

Technical Data
VRV IV heat pump, without continuous heating

EEDEN15-200_1A

RXYQ-T

Outdoor Unit RXYQ-T

TABLE OF CONTENTS
RXYQ-T

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3
4
5
6
7
7

Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Combination table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

13

Capacity Table Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


Integrated Heating Capacity Correction Factor . . . . . . . . . . . . . . . . . . . . .
Capacity Correction Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

13
14

Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

27

Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

28

Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

29

Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

31

Wiring Diagrams - Three Phase

15

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

10

External connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11

Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

12

13

35

Sound Power Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


Sound Pressure Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

37

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

45

Installation Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fixation and Foundation of Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Pipe Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

45

Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

54

VRV Systems RXYQ-T

41

46
47

Outdoor Unit RXYQ-T

Features

t is a mn e Ue h t sr V oy T I oS - d Q Vt Y RuX VDaikin's
OR

solution for comfort & low energy consumption

Covers all thermal needs of a building via a single point of contact:


accurate temperature control, ventilation, hot water, air handling units
and Biddle air curtains

Wide range of indoor units: possibility to combine VRV with stylish


indoor units (Daikin Emura, Nexura, ...)

Incorporates VRV IV standards & technologies: Variable Refrigerant


Temperature, VRV configurator, 7 segment display and full inverter
compressors, 4-side heat exchanger, refrigerant cooled PCB, new
DC fan motor, ...

Fits any building as also indoor installation is possible as a result of


high external static pressure of up to 78.4 Pa. Indoor installation
leads to less piping length, lower installation costs, increased
efficiency and better visual aesthetics

Simplified installation & guaranteed optimal efficiency with automatic


charging & testing

Easy compliance with F-gas regulation thanks to automated


refrigerant containment check

Customize your VRV for best seasonal efficiency & comfort with the
weather dependant Variable Refrigerant Temperature function.
Increased seasonal efficiency with up to 28%. No more cold draft by
supply of high outblow temperatures

Wide piping flexibility: 30m indoor height difference, maximum piping


length: 190m, total piping length: 1,000m

The ability to control each conditioned zone individually keeps VRV


system running costs to an absolute minimum

VRV configurator software for the fastest and most accurate


commissioning, configuration and customisation

Spread your installation cost by phased installation

Outdoor unit display for quick on-site settings and easy read out of
errors together with the indication of service parameters for checking
basic functions.

Keep your system in top condition via our ACNSS service: 24/7
monitoring for maximum efficiency, extended lifetime, immediate
service support thanks to failure prediction and a clear understanding
of operability and usage

Free combination of outdoor units to meet installation space or


efficiency requirements

Available as heating only by irreversible field setting

Inverter

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

Specifications

2-1 Technical Specifications


Capacity range

RXYQ10T

RXYQ12T

RXYQ14T

RXYQ16T

RXYQ18T

RXYQ20T

HP

10

12

14

16

18

20

Cooling capacity

Nom.

kW

28.0 (1) / 28.0


(2)

33.5 (1) / 33.5


(2)

40.0 (1) / 40.0


(2)

45.0 (1) / 45.0


(2)

50.4 (1)

56.0 (1)

Heating capacity

Nom.

kW

28.0 (3) / 28.00 33.5 (3) / 33.50


(4)
(4)

40.0 (3) / 40.0


(4)

45.0 (3) / 45.0


(4)

50.4 (3)

56.0 (3)

Max.

kW

31.5 (3)

37.5 (3)

45.0 (3)

50.0 (3)

56.5 (3)

63.0 (3)

Power input - 50Hz

Capacity control

Cooling

Nom.

kW

7.29 (1) / 6.32


(2)

8.98 (1) / 8.09


(2)

11.0 (1) / 9.88 13.0 (1) / 12.10


(2)
(2)

15.0 (1)

18.5 (1)

Heating

Nom.

kW

6.29 (3) / 5.47


(4)

7.77 (3) / 6.59


(4)

9.52 (3) / 9.30


(4)

11.1 (3) / 9.8


(4)

12.6 (3)

14.5 (3)

Max.

kW

7.38 (3)

9.10 (3)

11.2 (3)

12.8 (3)

14.6 (3)

17.0 (3)

3.36 (1)

3.03 (1)

Method
3.84 (1) / 4.43
(2)

3.73 (1) / 4.14


(2)

3.64 (1) / 4.05


(2)

3.46 (1) / 3.73


(2)

ESEER - Automatic

7.20

6.96

6.83

6.50

6.38

5.67

ESEER - Standard

5.67

5.50

5.31

5.05

4.97

4.42

COP - Max.

4.27 (3)

4.12 (3)

4.02 (3)

3.91 (3)

3.87

3.71

COP - Nom.

4.45 (3) / 5.12


(4)

4.31 (3) / 5.08


(4)

4.20 (3) / 4.30


(4)

4.05 (3) / 4.59


(4)

4.00

3.86

Maximum number of connectable indoor units

64 (5)

Indoor index
connection

Min.

125

150

175

200

225

250

Nom.

250

300

350

400

450

500

325

390

455

520

585

650

Dimensions

Unit

Max.
Height

Packed unit

Packing

mm

Depth

mm

Height

mm

Width

mm

Depth

mm

1,685
930

1,240
765
1,820

1,000

1,310
835

Unit

kg

194

305

314

Packed unit

kg

212

325

334

Material

Carton
kg

2.00

3.00

Material

Wood

Weight
Packing 3

mm

Width

Weight
Packing 2

kg

17.00

18.50

Material

Plastic

Weight

kg

0.50

Casing

Colour

Daikin White

Material

Painted galvanized steel plate

Heat exchanger

Type

Cross fin coil

Fin
Compressor

Treatment

Anti-corrosion treatment

Quantity

Model

Inverter

Type

Hermetically sealed scroll compressor

Crankcase heater
Fan

33

Type

Propeller fan

Quantity

Air flow rate

Cooling Nom.

m/min

External static
pressure

Max.

Pa

175

2
185

223

260

251

261

78

Discharge direction
Fan motor

Inverter controlled

EER

Weight

Vertical

Quantity

Model

Brushless DC motor

Output

750

Sound power level

Cooling

Nom.

dBA

79

81

Sound pressure level

Cooling

Nom.

dBA

58

61

Operation range

Cooling

Min.~Max.

CDB

-5~43

Heating

Min.~Max.

CWB

-20~15.5

VRV Systems RXYQ-T

86
64

88
65

66

Outdoor Unit RXYQ-T

Specifications

2-1 Technical Specifications


Refrigerant

RXYQ10T

RXYQ12T

RXYQ14T

Type
Charge

kg
TCO2eq

6.3

12.5

Refrigerant oil

11.7

11.8

21.7

24.4

24.6

Synthetic (ether) oil


l

Liquid

1.2

1.4

2.4

Type

3.3

Braze connection

OD

mm

9.52

12.7

Type

15.9

Braze connection

OD

mm

22.2

28.6

Heat insulation

Both liquid and gas pipes

Piping length

OU - IU Max.

165 (6)

After
branch

90 (6)

1,000 (6)

Max.

Total piping length

System Actual

Level difference

OU - IU Outdoo m
r unit in
highest
position

90 (6)

Indoor m
unit in
highest
position

90 (6)

IU - IU

Max.

30 (6)

Defrost method

PED

10.4

21.5

Type

Gas

Safety devices

RXYQ20T

2,087.5

Charged volume
Piping connections

RXYQ18T

10.3

13.2

GWP

RXYQ16T

R-410A

Reversed cycle
Item

01

High pressure switch

02

Fan driver overload protector

03

Inverter overload protector

04

PC board fuse

Category

Category II

Standard Accessories : Installation and operation manual;


Standard Accessories : Connection pipes;

2-2 Electrical Specifications


Power supply

RXYQ10T

RXYQ12T

RXYQ14T

Name
Phase

Voltage range
Current

Wiring connections 50Hz

Hz

50

Voltage

380-415

Min.

-10

Max.

Zmax

RXYQ20T

18.0 (7)

20.8 (7)

26.9 (7)

10

Text

10.2 (7)

12.7 (7)

15.4 (7)

Minimum Ssc value

kVa

564

615

917

924

873

970

Minimum circuit amps (MCA)

22.0

24.0

27.0

31.0

35.0

39.0

Maximum fuse amps (MFA)

25

Total overcurrent amps (TOCA)

Full load amps


(FLA)

Total

32

40

24.6
1.3

1.5

1.8

42.7
2.6

Quantity

For connection with


indoor

Quantity

Remark

F1,F2

5G

Both indoor and outdoor unit

VRV Systems RXYQ-T

50

35.4

For power supply

Power supply intake

RXYQ18T

3N~

Frequency

Nominal running
Cooling
current (RLA) - 50Hz
Current - 50Hz

RXYQ16T

Y1

Outdoor Unit RXYQ-T

Specifications

Notes

(1) Nominal cooling capacities are based on: indoor temperature: 27CDB, 19CWB, outdoor temperature: 35CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for
standard efficiency series
(2) Nominal cooling capacities are based on: indoor temperature: 27CDB, 19CWB, outdoor temperature: 35CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for

high efficiency series, Eurovent certified


(3) Nominal heating capacities are based on: indoor temperature: 20CDB, outdoor temperature: 7CDB, 6CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for
standard efficiency series
(4) Nominal heating capacities are based on: indoor temperature: 20CDB, outdoor temperature: 7CDB, 6CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for high
efficiency series, Eurovent certified
(5) Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% \<=
CR \<= 130%)
(6) Refer to refrigerant pipe selection or installation manual
(7) RLA is based on following conditions: indoor temp. 27CDB, 19CWB; outdoor temp. 35CDB
For more details on operation range see TW drawing
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
For more details on standard accessories refer to Installation/operation manual
MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always max. running current.
Select wire size based on the value of MCA. The MCA can be regarded as the maximum running current.
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
TOCA means the total value of each OC set.
FLA means the nominal running current of the fan
In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected
only to a supply with Zsys Zmax, respectively Ssc minimum Ssc value.
European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current
75A.
European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current \>16A and \<=
75A per phase
Short-circuit power
system impedance
Multi combination (22~54HP) data is corresponding with the standard multi combination as mentioned on 3D079534
Sound power level is an absolute value that a sound source generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
Sound values are measured in a semi-anechoic room.
The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality
The AUTOMATIC SEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation functionality ( variable refrigerant
temperature control operation)
Contains fluorinated greenhouse gases
Sound values are theoretical values based on sound results of individual installed units. Possible deviations due to variety of installation patterns are not taken into account.
Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
RXYQ22
T

2-3 Technical Specifications


System

RXYQ26
T

RXYQ28
T

RXYQ32
T

RXYQ12T

RXYQ34
T

RXYQ36
T

RXYQ1
0T

Outdoor unit module 2

RXYQ1 RXYQ1 RXYQ1 RXYQ1 RXYQ1 RXYQ1 RXYQ2 RXYQ1


2T
4T
6T
8T
6T
8T
0T
2T

Capacity range

kW

22

26

28

30

RXYQ1
8T
32

34

61.5 (1) 73.5 (1) 78.5 (1) 83.9 (1) 90.0 (1) 95.4 (1)

VRV Systems RXYQ-T

RXYQ42
T

RXYQ10T

HP

Nom.

RXYQ16T

RXYQ40
T

Outdoor unit module 1

Outdoor unit module 3

Cooling capacity

RXYQ30
T

RXYQ44
T

RXYQ1
2T
RXYQ16T
RXYQ16T

36

40

42

44

101.0
(1)

111.9
(1)

118.0
(1)

123.5
(1)

Outdoor Unit RXYQ-T

Specifications
RXYQ22
T

2-3 Technical Specifications


Heating capacity

Nom.

kW

Max.
Power input - 50Hz

RXYQ26
T

RXYQ28
T

RXYQ32
T

RXYQ34
T

61.5 (2) 73.5 (2) 78.5 (2) 83.9 (2) 90.0 (2) 95.4 (2)

kW

69.0

Cooling

Nom.

kW

16.27
(1)

Heating

Nom.

kW

14.06
(2)

17.29
(2)

18.87
(2)

Max.

kW

16.48

20.30

21.90

EER

RXYQ30
T

82.5

87.5

94.0

100.0

106.5

RXYQ36
T

RXYQ40
T

RXYQ42
T

RXYQ44
T

101.0
(2)

111.9
(2)

118.0
(2)

123.5
(2)

113.0

125.5

131.5

137.5

20.0 (1) 22.0 (1) 24.0 (1) 26.0 (1) 28.0 (1) 31.5 (1) 31.3 (1) 33.3 (1) 35.0 (1)
20.4 (2) 22.2 (2) 23.7 (2) 25.6 (2) 26.7 (2)

3.77 (1) 3.68 (1) 3.57 (1)

23.7

25.6

27.4

29.8

31.1

3.5 (1)

3.46 (1)

3.4 (1)

3.21 (1)

3.6 (1)

28.49
(2)

29.97
(2)

32.98

34.70

3.54 (1)

ESEER - Automatic

7.07

6.89

6.69

6.60

6.50

6.44

6.02

6.74

6.65

6.62

ESEER - Standard

5.58

5.39

5.23

5.17

5.05

5.01

4.68

5.29

5.19

5.17

COP - Max.

4.19

4.06

3.91

3.9

3.79

4.0

3.99

3.96

COP - Nom.

4.37

4.25

4.16

4.1

4.05

4.0

3.95

4.2

4.14

4.12

4.00

Maximum number of connectable indoor units

64

Indoor index
connection

Min.

275

325

350

375

400

425

450

500

525

550

Nom.

550

650

700

750

800

850

900

1,000

1,050

1,100

715

845

910

975

1,040

1,105

1,170

1,300

1,365

1,430

Piping connections

Liquid

OD

mm

15.9

Gas

OD

mm

28.6

Piping length

OU - IU Max.

165

After
branch

90

1,000

Max.

34.9

41.3

Total piping length

System Actual

Level difference

OU - IU Outdoo m
r unit in
highest
position

90

Indoor m
unit in
highest
position

90

IU - IU
PED

Max.

19.1

Max.

30

Category

Category II

Standard Accessories : Installation and operation manual;


Standard Accessories : Connection pipes;

2-4 Technical Specifications

RXYQ46T

System

RXYQ14T

Outdoor unit module 1

RXYQ48T

Outdoor unit module 2

RXYQ52T

RXYQ18T

RXYQ16T

Capacity range

RXYQ54T

RXYQ18T

RXYQ16T

Outdoor unit module 3

RXYQ18T

HP

46

48

50

52

54

Cooling capacity

Nom.

kW

130.0 (1)

135.0 (1)

140.0 (1)

145.8 (1)

151.2 (1)

Heating capacity

Nom.

kW

130.0 (2)

135.0 (2)

140.0 (2)

145.8 (2)

151.2 (2)

Max.

kW

145.0

150.0

156.0

163.0

169.5

Power input - 50Hz

Cooling

Nom.

kW

37.0 (1)

39.0 (1)

40.7 (1)

43.0 (1)

45.0 (1)

Heating

Nom.

kW

31.72 (2)

33.3 (2)

34.6 (2)

36.3 (2)

37.8 (2)

Max.

kW

36.8

38.4

40.0

42.0

43.8

3.51 (1)

3.46 (1)

3.44 (1)

3.4 (1)

3.40 (1)

EER
ESEER - Automatic

6.60

6.50

6.46

6.42

6.38

ESEER - Standard

5.13

5.05

5.02

4.99

4.97

COP - Max.

3.94

3.91

COP - Nom.

4.10

Indoor index
connection

3.90
4.05

Maximum number of connectable indoor units

RXYQ50T

RXYQ16T

4.0
64

Min.

575

600

625

650

675

Nom.

1,150

1,200

1,250

1,300

1,350

Max.

1,495

1,560

1,625

1,690

1,755

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

Specifications

2-4 Technical Specifications


Piping connections

RXYQ46T

Liquid

OD

RXYQ50T

19.1

Gas

OD

mm

41.3

Piping length

OU - IU Max.

165

After
branch

90

1,000

Max.

Total piping length

System Actual

Level difference

OU - IU Outdoo m
r unit in
highest
position

90

Indoor m
unit in
highest
position

90

IU - IU
PED

RXYQ48T

mm

Max.

RXYQ52T

RXYQ54T

3
2

30

Category

Category II

Standard Accessories : Installation and operation manual;


Standard Accessories : Connection pipes;

RXYQ22
T

RXYQ26
T

RXYQ28
T

RXYQ30
T

RXYQ32
T

RXYQ34
T

RXYQ36
T

RXYQ40
T

RXYQ42
T

RXYQ44
T

22.9

28.1

30.7

33.5

36.0

38.8

44.9

43.7

46.2

48.7

2-5 Electrical Specifications


Current
Current - 50Hz

Wiring connections 50Hz

Nominal running
Cooling
current (RLA) - 50Hz
Minimum Ssc value

kVa

1,179

1,532

1,539

1,488

1,848

1,797

1,894

2,052

2,412

2,463

Minimum circuit amps (MCA)

46.0

51.0

55.0

59.0

62.0

66.0

70.0

81.0

84.0

86.0

Maximum fuse amps (MFA)

63

80

For power supply

Quantity

For connection with


indoor

Quantity

Remark

F1,F2

5G

Power supply intake

Both indoor and outdoor unit

2-6 Electrical Specifications


Current
Current - 50Hz

Wiring connections 50Hz

100

RXYQ46T

RXYQ48T

RXYQ50T

RXYQ52T

RXYQ54T

Nominal running
Cooling
current (RLA) - 50Hz

51.4

54.0

56.8

59.6

62.4

Minimum Ssc value

kVa

2,765

2,772

2,721

2,670

2,619

Minimum circuit amps (MCA)

89.0

93.0

97.0

101.0

105.0

Maximum fuse amps (MFA)

100

125

For power supply

Quantity

For connection with


indoor

Quantity

Remark

F1,F2

Power supply intake

5G

Both indoor and outdoor unit

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

Specifications

Notes

(1) Cooling: indoor temp. 27CDB, 19.0CWB; outdoor temp. 35CDB; equivalent piping length: 5m; level difference: 0m
(2) heating: indoor temp. 20CDB; outdoor temp. 7CDB, 6CWB; equivalent refrigerant piping: 5m; level difference: 0m (nominal)

Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% \<= CR
\<= 130%)
For more details on operation range see TW drawing
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
Refer to refrigerant pipe selection or installation manual
For more details on standard accessories refer to Installation/operation manual
RLA is based on following conditions: indoor temp. 27CDB, 19CWB; outdoor temp. 35CDB
MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always max. running current.
Select wire size based on the value of MCA. The MCA can be regarded as the maximum running current.
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
TOCA means the total value of each OC set.
FLA means the nominal running current of the fan
In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected
only to a supply with Zsys Zmax, respectively Ssc minimum Ssc value.
European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current
75A.
European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current \>16A and \<=
75A per phase
Short-circuit power
system impedance
Multi combination (22~54HP) data is corresponding with the standard multi combination as mentioned on 3D079534
Sound power level is an absolute value that a sound source generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
Sound values are measured in a semi-anechoic room.
The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality
The AUTOMATIC SEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation functionality ( variable refrigerant
temperature control operation)
Contains fluorinated greenhouse gases
Sound values are theoretical values based on sound results of individual installed units. Possible deviations due to variety of installation patterns are not taken into account.
Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

3-1

Options
Options

RYYQ-T
RYMQ-T
RXYQ-T
RXYQQ-T
VRV4 Heat Pump Option list
No

I.

Item

RXYQ10-12T
RYYQ10-12T
RXYQQ10-12T

REFNET HEADER

II.

REFNET JOINT

III.
IV.

OUTDOOR MULTI CONNECTION KIT (see note 2)


OUTDOOR MULTI CONNECTION KIT (see note 2)

No
1a
1b
1c
1d
2
3
4
5
6

Item
COOL/HEAT SELECTOR (SWITCH)
COOL/HEAT SELECTOR (PCB)
COOL/HEAT SELECTOR (SWB MOUNTING PLATE)
COOL/HEAT SELECTOR (FIXING BOX)
VRV CONFIGURATOR
HEATER TAPE KIT (see note 6)
HEATER TAPE KIT PCB
DEMAND PCB (see note 7)
DEMAND PCB (MOUNTING PLATE)

1.
2.
3.
4.
5.
6.
7.

RXYQ8T
RYYQ8T
RXYQQ8T

8HP

10HP

12HP

14HP
KRC19-26A
BRP2A81

RXYQ14-18T
RXYQ20T
RYYQ22~54T
RYYQ14-18T
RYYQ20T
RXYQ22~54T
RXYQQ14-18T
RXYQQ20T
RXYQQ22~42T
KHRQ22M29H
KHRQ22M64H
KHRQ22M75H
KHRQ22M20T
KHRQ22M29T9
KHRQ22M64T
KHRQ22M75T
BHFQ22P1007
BHFQ22P1517
16HP

18HP

20HP

KKSA26A560*
KJB111A
EKPCCAB*

EKBPH012T*

EKBPH020T*
EKBPHPCBT*
DTA104A61/62*

KKSB26B1*

NOTES
All options are kits
Only for multi units
Option 1a and 1b are both required to operate the COOL/HEAT SELECTOR function on a VRV4 Heat Pump System
Option 1d is required to mount 1a
1c is only required when combining 1b with 3 on a VRV4 Heat Pump system
To install the HEATER TAPE KIT, a HEATER TAPE KIT PCB is required
To install the DEMAND PCB on the Large casing type, the DEMAND PCB (MOUNTING PLATE) is required

Medium casing type VRV4 Heat Pump: modules 8~12HP


Large casing type VRV4 Heat Pump: modules 14~20HP

3D079531F

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

Combination table

4-1

Combination Table

RYYQ-T
RYMQ-T
RXYQ-T
VRV* DX
indoor

Indoor unit combination pattern

RA DX
indoor

Hydrobox

AHU (3)

VRV* DX indoor

RA DX indoor

Hydrobox

01

AHU (3)

02

0: allowed
x: forbidden
NOTES

1) VRV* DX indoor
- VRV DX indoor can only be allowed with one of the other combinable indoor units.
eg
Allowed: (VRV DX indoor + Hydro) OR (VRV DX indoor + RA DX indoor) OR (VRV DX indoor + AHU)
Not allowed: [VRV DX indoor + (RA DX indoor & (Hydro or AHU))] OR [VRV DX indoor + (Hydro & (RA DX indoor or AHU))]
2) 01
- Connecting only Hydroboxes without a VRV DX indoor unit to a VRV IV Heat Pump unit is not allowed
 
6HHDOVRFRQQHFWLRQUDWLR &5 UHVWULFWLRQV '
 
2QO\+\GURER[FRQQHFWLRQFI'DLNLQ$OWKHUPDVROXWLRQV
 2QO\FRPSDWLEOH+\GURER[LV+;< VHULHV+\GURER[
 
+;+' +\GURER[LVQRWDOORZHG
3) 02:
AHU connection only (combination with VRV DX indoor units is not allowed; max. 30HP = 3 x 250 class EKEXV kit)
;FRQWUROLVSRVVLEOH XSWR[>(.(;9(.(4) ER[@DUHDOORZHGWRRQHRXWGRRUXQLW V\VWHP QR9DULDEOH5HIULJHUDQW7HPSHUDWXUHFRQWUROSRVVLEOH
<FRQWUROLVSRVVLEOH XSWR[>(.(;9(.(4) ER[@DUHDOORZHGWRRQHRXWGRRUXQLW V\VWHP QR9DULDEOH5HIULJHUDQW7HPSHUDWXUHFRQWUROSRVVLEOH




4) &RPELQDWLRQRI$+8ZLWK+\GURER[RU5$';LQGRRUXQLWVLVQRWDOORZHG
5)  )ROORZLQJDUHFRQVLGHUHGDV$+8

(.(;9(.(4 0) $+8FRLO

%LGGOHDLUFXUWDLQV

);04B0)XQLWV
Information
9.0LVFRQVLGHUHGWREHDUHJXODU959';LQGRRUXQLW

3D079543D(1/2)
RYYQ-T
RYMQ-T
RXYQ-T

0:
x:

Indoor/Outdoor combination

RYYQ*
(single CH)

RYYQ*
(multi CH)

RXYQ*
(single n-CH)

RXYQ*
(multi n-CH)

VRV* DX indoor

RA DX indoor

Hydrobox (HXY*)

01

01

AHU (2)

allowed
forbidden
NOTES

1) 01
Upon request through SPN procedure
1) (2) Following are considered as AHU

(.(;9(.(4 0) $+8FRLO

%LGGOHDLUFXUWDLQV

);04B0)XQLWV

3D079543D(2/2)

10

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

4-1

Combination table
Combination Table

RYYQ-T
RYMQ-T
RXYQ-T

VRV4 Heat Pump RA DX indoor unit compatibility list


&RQJXUDWLRQ
:DOOPRXQWHG

Emura

)ORRU&HLOLQJ

Flex

)ORRUVWDQGLQJ

FVXS

Nexura

8QLWW\SH
FTXG25J
FTXG35J
FTXG50J
FTXS20K
FTXS25K
FTXS35K
FTXS42K
FTXS50K
FTXS60G
FTXS71G
CTXS15K
CTXS35K
FLXS25B
FLXS35B
FLXS50B
FLXS60B
FVXS25F
FVXS35F
FVXS50F
FVXG25K
FVXG35K
FVXG50K

NOTES

1. Limitations on use of RA DX indoor units with VRV4 Heat Pump is subject to rules mentioned in 3D079543 and 3D079540.
2. Use VRV DX indoor equivalent in case RA/SA DX Cassette, Ceiling mounted or Duct type is needed.

3D082373

VRV Systems RXYQ-T

11

Outdoor Unit RXYQ-T

4-1

Combination table

Combination Table

RYYQ-T
RYMQ-T
RXYQ-T
RXYQQ-T

VRV4 Heat Pump Standard combination table (multi)

See Note concerning base model type

Multi combination with 3


outdoor units

Multi combination with


2 outdoor units

Heat PUMP

8HP
RXYQ8* / RYYQ8* / RXYQQ8*
RXYQ10* / RYYQ10* / RXYQQ10*
RXYQ12* / RYYQ12* / RXYQQ12*
RXYQ14* / RYYQ14* / RXYQQ14*
RXYQ16* / RYYQ16* / RXYQQ16*
RXYQ18* / RYYQ18* / RXYQQ18*
RXYQ20* / RYYQ20* / RXYQQ20*
RXYQ22* / RYYQ22* / RXYQQ22*
RXYQ24* / RYYQ24* / RXYQQ24*
RXYQ26* / RYYQ26* / RXYQQ26*
RXYQ28* / RYYQ28* / RXYQQ28*
RXYQ30* / RYYQ30* / RXYQQ30*
RXYQ32* / RYYQ32* / RXYQQ32*
RXYQ34* / RYYQ34* / RXYQQ34*
RXYQ36* / RYYQ36* / RXYQQ36*
RXYQ38* / RYYQ38* / RXYQQ38*
RXYQ40* / RYYQ40* / RXYQQ40*
RXYQ42* / RYYQ42* / RXYQQ42*

10HP

12HP

14HP

16HP

18HP

20HP

1
1
1
1
1
1
1
1

1
1
1
1

1
1
1
2
1
1

RXYQ46* / RYYQ46*
RXYQ48* / RYYQ48*
RXYQ50* / RYYQ50*
RXYQ52* / RYYQ52*
RXYQ54* / RYYQ54*

1
1
1

1
1
1
1

2
1

2
3
2
1

1
2
3

NOTES

1)
2)
3)
4)
5)
6)
7)
8)

RYYQ8~20 = single continuous heating model


RYYQ22~54 = multi continuous heating model
RXYQ8~20 = single non-continuous heating model
RXYQ22~54 = multi non-continuous heating model
RXYQQ8~20 = single non-continuous heating replacement model (VRV4-Q)
RXYQQ22~42 = multi non-continuous heating replacement model (VRV4-Q)
Single unit can be chosen: RYYQ* model (continuous heating) and RXYQ* model (non-continuous heating)
Multi combinations non-continuous heating consist out of RXYQ8~20 modules. Eg RXYQ36* = RXYQ16* + RXYQ20*
Multi combinations continuous heating consist out of RYMQ8~20 modules. Eg RYYQ36* = RYMQ16* + RYMQ20*
-> multi modules RYMQ* cannot be used as stand alone units (RYMQ8~20HP)
Multi combinations can never contain RYYQ8~20 models
Multi continuous heating RYYQ* combinations can never contain RXYQ* models
Multi non-continuous heating RXYQ* combinations can never contain RYMQ* models
Multi non-continuous heating replacement models only consist out of RXYQQ8~20 modules. Eg RXYQQ36* = RXYQQ16* + RXYQQ20*
Replacement models can never be combined with other models

3D079534B

12

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

5-1

Capacity tables

Capacity Table Legend

,QRUGHUWRIXOOOPRUH\RXUUHTXLUHPHQWVRQTXLFNDFFHVVRIGDWDLQWKHIRUPDW\RXUHTXLUHZHKDYHGHYHORSHGDWRROWR
FRQVXOWFDSDFLW\WDEOHV

%HORZ\RXFDQQGWKHOLQNWRWKHFDSDFLW\WDEOHGDWDEDVHDQGDQRYHUYLHZRIDOOWKHWRROVZHKDYHWRKHOS\RXVHOHFWWKH
FRUUHFWSURGXFW
 &
 DSDFLW\WDEOHGDWDEDVHOHWV\RXQGEDFNDQGH[SRUWTXLFNO\WKHFDSDFLW\LQIRUPDWLRQ\RXDUHORRNLQJIRUEDVHGXSRQXQLW
PRGHOUHIULJHUDQWWHPSHUDWXUHDQGFRQQHFWLRQUDWLR

KWWSH[WUDQHWGDLNLQHXURSHFRPFDSWDE

 (GDWDDSSJLYHVDFRPSOHWHRYHUYLHZRIWKH'DLNLQSURGXFWVDYDLODEOHLQ\RXUFRXQWU\ZLWKDOOHQJLQHHULQJGDWDDQG
FRPPHUFLDOLQIRLQ\RXURZQODQJXDJH'RZQORDGWKHDSSQRZ

KWWSVLWXQHVDSSOHFRPXVDSSGDLNLQHGDWDLG"PW 

 6HOHFWLRQVRIWZDUHDOORZV\RXWRGRORDGFDOFXODWLRQVHTXLSPHQWVHOHFWLRQVDQGHQHUJ\VLPXODWLRQVIRURXU959'DLNLQ
$OWKHUPDUHIULJHUDWLRQDQGDSSOLHGV\VWHPVSURGXFWV

KWWSH[WUDQHWGDLNLQHXURSHFRPHQVRIWZDUHGRZQORDGVGHIDXOWMVS

VRV Systems RXYQ-T

13

Outdoor Unit RXYQ-T

5-2

Capacity tables

Integrated Heating Capacity Correction Factor

RYYQ-T
RXYQ-T
RXYQQ-T
The heating capacity tables do not take account of the reduction in capacity, when frost has accumulated or while the defrosting operation is in progress.
The capacity values, which take these factors into account, in other words, the integrated heating capacity values, can be calculated as follows:

Formula:
Integrated heating capacity = A
Value given in table of capacity characteristics = B
Integrating correction factor for frost accumulation (kW) = C
A=BxC
Inlet air temperature of heat exchanger
[CDB/CWB]

-7/-7.6

-5/-5.6

-3/-3.7

0/-0.7

3/2.2

5/4.1

7/6

0.84

0.85

0.90

1.00

Integrated correction factor for frost accumulation (C)


0.95

0.93

0.88

NOTES

1. 7KHJXUHVKRZVWKDWWKHLQWHJUDWHGKHDWLQJFDSDFLW\H[SUHVVHVWKHLQWHJUDWHGFDSDFLW\IRUDVLQJOHF\FOH IURPGHIURVWRSHUDWLRQWRGHIURVWRSHUDWLRQ LQWHUPVRUWLPH


2. Note that, when there is an accumulation of snow against the outside surface of the outdoor unit heat exchanger, there will always be a temporary reduction in capacity, although this will of
course vary in degree in accordance with a number of other factors, such as the outdoor temperature (CDB), relative humidity (RH) and the amount of frosting which occurs.
3. Multi combination (22~54HP) data is corresponding with the standard multi combination as mentioned on 3D079534

3D079898

14

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

5-3

Capacity tables

Capacity Correction Factor

RYYQ8T
RXYQ8T
RXYQQ8T
Height Difference between outdoor and farest
Indoor (m)

Correction ratio for heating capacity

Height Difference between outdoor and farest


Indoor (m)

Correction ratio for cooling capacity

Equivalent piping length (m)

Equivalent piping length (m)

3D079897A
NOTES

1.

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.

2.

With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.

3.

Method of calculating the capacity of the outdoor units


The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%.
Maximum capacity of outdoor units

Capacity of outdoor units from capacity table at the 100% connection ratio

Correction ratio of piping to furthest indoor

Condition: Indoor connection ratio exceeds 100%.


Maximum capacity of outdoor units

4.

5.

Capacity of outdoor units from capacity table at installed connection ratio

Correction ratio of piping to furthest indoor

When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model

Gas

Liquid

8HP

22.2

12.7

When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for deicated indoor connection types.
Diameter of main pipes (standard size)

6.

Model

Gas

Liquid

8HP

19.1

9.5

Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length

Equivalent length of main pipe


+
Equivalent length of branch pipes

Correction factor

Choose the correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size

Size increase

Cooling (gas pipe)

1.0

0.5

Heating (liquid pipe)

1.0

0.5

Example

Main gas pipe size increase


Main Liquid pipe size increase

Equivalent length branch

80 m

40 m

In the above case

(Cooling) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rete of change in cooling capacity when height difference = 0 is thus approximately 0.86
heating capacity when height difference = 0 is thus approximately 1.0

VRV Systems RXYQ-T

15

Outdoor Unit RXYQ-T

5-3

Capacity tables

Capacity Correction Factor

RYYQ10T
RXYQ10T
RXYQQ10T

Height Difference between outdoor and farest


Indoor (m)

Correction ratio for heating capacity

Height Difference between outdoor and farest


Indoor (m)

Correction ratio for cooling capacity

Equivalent piping length (m)

Equivalent piping length (m)

3D079897A
NOTES

1.

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.

2.

With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.

3.

Method of calculating the capacity of the outdoor units


The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%.
Maximum capacity of outdoor units

Capacity of outdoor units from capacity table at the 100% connection ratio

Correction ratio of piping to furthest indoor

Condition: Indoor connection ratio exceeds 100%.


Maximum capacity of outdoor units

4.

5.

6.

Capacity of outdoor units from capacity table at installed connection ratio

Correction ratio of piping to furthest indoor

When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased. For new diameters, see below.
Model

Gas

Liquid

RXYQ10P

25.4*

12.7

*If not available on site, do not increase. If not increased correction factor should be applied to the equivalent length (see note 6).
When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model

Gas

Liquid

10 HP

22.2

9.5

Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length

Equivalent length of main pipe


+
Equivalent length of branch pipes

Correction factor

Choose the correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size

Size increase

Cooling (gas pipe)

1.0

0.5

Heating (liquid pipe)

1.0

0.5

Example

Main gas pipe size increase


Main Liquid pipe size increase

Equivalent length branch

80 m

40 m

In the above case

(Cooling) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rete of change in cooling capacity when height difference = 0 is thus approximately 0.87
heating capacity when height difference = 0 is thus approximately 0.90

16

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

5-3

Capacity tables

Capacity Correction Factor

RYYQ12,14,24,36T
RXYQ12,14,24,36T
RXYQQ12,14,24,36T
Correction ratio for heating capacity
Height Difference between outdoor and farest
Indoor (m)

Height Difference between outdoor and farest


Indoor (m)

Correction ratio for cooling capacity

Equivalent piping length (m)

Equivalent piping length (m)

3D079897A
NOTES

1.

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.

2.

With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.

3.

Method of calculating the capacity of the outdoor units


The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%.
Maximum capacity of outdoor units

Capacity of outdoor units from capacity table at the 100% connection ratio

Correction ratio of piping to furthest indoor

Condition: Indoor connection ratio exceeds 100%.


Maximum capacity of outdoor units

4.

Capacity of outdoor units from capacity table at installed connection ratio

Correction ratio of piping to furthest indoor

When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased. For new diameters, see below.
Model
12 HP
14 HP
24 HP
36 HP

5.

Gas
28.6
28.6
34.9
41.3

Liquid
15.9
15.9
19.1
22.2

When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model
12 HP
14 HP
24 HP
36 HP

6.

Gas
28.6
28.6
34.9
41.3

Liquid
12.7
12.7
15.9
19.1

Equivalent length used in the above figures is based upon the following equivalent length
=
Equivalent piping length
Equivalent length of main pipe
+
Equivalent length of branch pipes

Correction factor

Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size
Size increase
1.0
1.0
0.5

Cooling (gas pipe)


Heating (liquid pipe)
Example

Main gas pipe size increase


Main Liquid pipe size increase

Equivalent length branch

80 m

40 m

In the above case

(Cooling) Overall equivalent length = 80 m x 1.0 + 40 m = 120 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.89
heating capacity when height difference = 0 is thus approximately 1.0

VRV Systems RXYQ-T

17

Outdoor Unit RXYQ-T

5-3

Capacity tables

Capacity Correction Factor

RYYQ16T
RXYQ16T
RXYQQ16T

Correction ratio for heating capacity


Height Difference between outdoor and farest
Indoor (m)

Height Difference between outdoor and farest


Indoor (m)

Correction ratio for cooling capacity

Equivalent piping length (m)

Equivalent piping length (m)

3D079897A
NOTES

1.

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.

2.

With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.

3.

Method of calculating the capacity of the outdoor units


The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%.
Maximum capacity of outdoor units

Capacity of outdoor units from capacity table at the 100% connection ratio

Correction ratio of piping to furthest indoor

Condition: Indoor connection ratio exceeds 100%.


Maximum capacity of outdoor units

4.

5.

Capacity of outdoor units from capacity table at installed connection ratio

Correction ratio of piping to furthest indoor

When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased. For new diameters, see below.
Model
Gas
Liquid
16 HP
31.8*
15.9
*If not available on site, do not increase. If not increased correction factor should be applied to the equivalent length (see note 6).
When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model
16 HP

6.

Gas
28.6

Liquid
12.7

Equivalent length used in the above figures is based upon the following equivalent length
=
Equivalent piping length
Equivalent length of main pipe
+
Equivalent length of branch pipes

Correction factor

Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size
Size increase
1.0
0.5
1.0
0.5

Cooling (gas pipe)


Heating (liquid pipe)
Example

Main gas pipe size increase


Main Liquid pipe size increase

Equivalent length branch

80 m

40 m

In the above case

(Cooling) Overall equivalent length = 80 m x 1.0 + 40 m = 80 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.88
heating capacity when height difference = 0 is thus approximately 0.99

18

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

5-3

Capacity tables

Capacity Correction Factor

RYYQ18,26,28,30,38,40,42,44T
RXYQ18,26,28,30,38,40,42,44T
RXYQQ18,26,28,30,38,40,42T
Correction ratio for heating capacity
Height Difference between outdoor and farest
Indoor (m)

Height Difference between outdoor and farest


Indoor (m)

Correction ratio for cooling capacity

Equivalent piping length (m)

Equivalent piping length (m)

3D079897A
NOTES

1.

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.

2.

With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.

3.

Method of calculating the capacity of the outdoor units


The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%.
Maximum capacity of outdoor units

Capacity of outdoor units from capacity table at the 100% connection ratio

Correction ratio of piping to furthest indoor

Condition: Indoor connection ratio exceeds 100%.


Maximum capacity of outdoor units

4.

5.

Capacity of outdoor units from capacity table at installed connection ratio

Correction ratio of piping to furthest indoor

When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model
Gas
Liquid
18 HP
31.8*
19.1
26~30 HP
38.1*
22.2
38~44 HP
41.3
22.2
*If not available on site, do not increase. If not increased correction factor should be applied to the equivalent length (see note 6).
When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model
18 HP
26~30 HP
38~44 HP

6.

Gas
28.6
34.9
41.3

Liquid
15.9
19.1
19.1

Equivalent length used in the above figures is based upon the following equivalent length
=
Equivalent piping length
Equivalent length of main pipe
+
Equivalent length of branch pipes

Correction factor

Choose the correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size
Size increase
1.0
0.5
1.0
0.5

Cooling (gas pipe)


Heating (liquid pipe)
Example

Main gas pipe size increase


Main Liquid pipe size increase

Equivalent length branch

80 m

40 m

In the above case (for RXYQ38-44) (Cooling) Overall equivalent length = 80 m x 1.0 + 40 m = 120 m
(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in
cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 1.0

VRV Systems RXYQ-T

19

Outdoor Unit RXYQ-T

5-3

Capacity tables

Capacity Correction Factor

RYYQ20,32,34T
RXYQ20,32,34T
RXYQQ20,32,34T

Correction ratio for heating capacity


Height Difference between outdoor and farest
Indoor (m)

Height Difference between outdoor and farest


Indoor (m)

Correction ratio for cooling capacity

Equivalent piping length (m)

Equivalent piping length (m)

3D079897A
NOTES

1.

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.

2.

With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.

3.

Method of calculating the capacity of the outdoor units


The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%.
Maximum capacity of outdoor units

Capacity of outdoor units from capacity table at the 100% connection ratio

Correction ratio of piping to furthest indoor

Condition: Indoor connection ratio exceeds 100%.


Maximum capacity of outdoor units

4.

5.

Capacity of outdoor units from capacity table at installed connection ratio

Correction ratio of piping to furthest indoor

When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model
Gas
Liquid
20 HP
31.8*
19.1
32/34 HP
38.1*
22.2
*If not available on site, do not increase. If not increased correction factor should be applied to the equivalent length (see note 6).
When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model
20 HP
32/34 HP

6.

Gas
28.6
34.9

Liquid
15.9
19.1

Equivalent length used in the above figures is based upon the following equivalent length
=
Equivalent piping length
Equivalent length of main pipe
+
Equivalent length of branch pipes

Correction factor

Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size
Size increase
1.0
0.5
1.0
0.5

Cooling (gas pipe)


Heating (liquid pipe)
Example

Main gas pipe size increase


Main Liquid pipe size increase

Equivalent length branch

80 m

40 m

In the above case

(Cooling) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.88
heating capacity when height difference = 0 is thus approximately 1.0

20

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

5-3

Capacity tables

Capacity Correction Factor

RYYQ22T
RXYQ22T
RXYQQ22T
Correction ratio for heating capacity
Height Difference between outdoor and farest
Indoor (m)

Height Difference between outdoor and farest


Indoor (m)

Correction ratio for cooling capacity

Equivalent piping length (m)

Equivalent piping length (m)

3D079897A
NOTES

1.

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.

2.

With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.

3.

Method of calculating the capacity of the outdoor units


The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%.
Maximum capacity of outdoor units

Capacity of outdoor units from capacity table at the 100% connection ratio

Correction ratio of piping to furthest indoor

Condition: Indoor connection ratio exceeds 100%.


Maximum capacity of outdoor units

4.

Capacity of outdoor units from capacity table at installed connection ratio

Correction ratio of piping to furthest indoor

When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model
Gas
Liquid
22 HP
31.8*
19.1
* If not available on site, do not increase, if not increased, no correction factor should be applied to the equivalent length (see note 6).

5.

When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model
22 HP

6.

Gas
28.6

Liquid
15.9

Equivalent length used in the above figures is based upon the following equivalent length
=
Overal equivalent length
Equivalent length of main pipe
+
Equivalent length of branch pipes

Correction factor

Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size
Size increase
1.0
0.5
1.0
0.5

Cooling (gas pipe)


Heating (liquid pipe)
Example

Main gas pipe size increase


Main Liquid pipe size increase

Equivalent length branch

80 m

40 m

In the above case

(Cooling) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.88
heating capacity when height difference = 0 is thus approximately 1.0

VRV Systems RXYQ-T

21

Outdoor Unit RXYQ-T

5-3

Capacity tables

Capacity Correction Factor

RYYQ46T
RXYQ46T

Correction ratio for heating capacity


Height Difference between outdoor and farest
Indoor (m)

Height Difference between outdoor and farest


Indoor (m)

Correction ratio for cooling capacity

Equivalent piping length (m)

Equivalent piping length (m)

3D079897A
NOTES

1.

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.

2.

With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.

3.

Method of calculating the capacity of the outdoor units


The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%.
Maximum capacity of outdoor units

Capacity of outdoor units from capacity table at the 100% connection ratio

Correction ratio of piping to furthest indoor

Condition: Indoor connection ratio exceeds 100%.


Maximum capacity of outdoor units

4.

Gas
41.3

Correction ratio of piping to furthest indoor

Liquid
22.2

When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model
46 HP

6.

Capacity of outdoor units from capacity table at installed connection ratio

When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model
46 HP

5.

Gas
41.3

Liquid
19.1

Equivalent length used in the above figures is based upon the following equivalent length
=
Equivalent piping length
Equivalent length of main pipe
+
Equivalent length of branch pipes

Correction factor

Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size
Size increase
1.0
1.0
0.5

Cooling (gas pipe)


Heating (liquid pipe)
Example

Main gas pipe size increase


Main Liquid pipe size increase

Equivalent length branch

80 m

40 m

In the above case

(Cooling) Overall equivalent length = 80 m x 1.0 + 40 m = 120 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 1.0

22

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

5-3

Capacity tables

Capacity Correction Factor

RYYQ48T
RXYQ48T
Correction ratio for heating capacity
Height Difference between outdoor and farest
Indoor (m)

Height Difference between outdoor and farest


Indoor (m)

Correction ratio for cooling capacity

Equivalent piping length (m)

Equivalent piping length (m)

3D079897A
NOTES

1.

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.

2.

With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.

3.

Method of calculating the capacity of the outdoor units


The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%.
Maximum capacity of outdoor units

Capacity of outdoor units from capacity table at the 100% connection ratio

Correction ratio of piping to furthest indoor

Condition: Indoor connection ratio exceeds 100%.


Maximum capacity of outdoor units

4.

Gas
41.3

Correction ratio of piping to furthest indoor

Liquid
22.2

When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model
48 HP

6.

Capacity of outdoor units from capacity table at installed connection ratio

When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model
48 HP

5.

Gas
41.3

Liquid
19.1

Equivalent length used in the above figures is based upon the following equivalent length
=
Equivalent piping length
Equivalent length of main pipe
+
Equivalent length of branch pipes

Correction factor

Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size
Size increase
1.0
1.0
0.5

Cooling (gas pipe)


Heating (liquid pipe)
Example

Main gas pipe size increase


Main Liquid pipe size increase

Equivalent length branch

80 m

40 m

In the above case

(Cooling) Overall equivalent length = 80 m x 1.0 + 40 m = 120 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 0.97

VRV Systems RXYQ-T

23

Outdoor Unit RXYQ-T

5-3

Capacity tables

Capacity Correction Factor

RYYQ50T
RXYQ50T

Correction ratio for heating capacity


Height Difference between outdoor and farest
Indoor (m)

Height Difference between outdoor and farest


Indoor (m)

Correction ratio for cooling capacity

Equivalent piping length (m)

Equivalent piping length (m)

3D079897A
NOTES

1.

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.

2.

With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.

3.

Method of calculating the capacity of the outdoor units


The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%.
Maximum capacity of outdoor units

Capacity of outdoor units from capacity table at the 100% connection ratio

Correction ratio of piping to furthest indoor

Condition: Indoor connection ratio exceeds 100%.


Maximum capacity of outdoor units

4.

Gas
41.3

Correction ratio of piping to furthest indoor

Liquid
22.2

When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model
50 HP

6.

Capacity of outdoor units from capacity table at installed connection ratio

When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model
50 HP

5.

Gas
41.3

Liquid
19.1

Equivalent length used in the above figures is based upon the following equivalent length
=
Equivalent piping length
Equivalent length of main pipe
+
Equivalent length of branch pipes

Correction factor

Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size
Size increase
1.0
1.0
0.5

Cooling (gas pipe)


Heating (liquid pipe)
Example

Main gas pipe size increase


Main Liquid pipe size increase

Equivalent length branch

80 m

40 m

In the above case

(Cooling) Overall equivalent length = 80 m x 1.0 + 40 m = 120 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 0.92

24

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

5-3

Capacity tables

Capacity Correction Factor

RYYQ52T
RXYQ52T
Correction ratio for heating capacity
Height Difference between outdoor and farest
Indoor (m)

Height Difference between outdoor and farest


Indoor (m)

Correction ratio for cooling capacity

Equivalent piping length (m)

Equivalent piping length (m)

3D079897A
NOTES

1.

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.

2.

With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.

3.

Method of calculating the capacity of the outdoor units


The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%.
Maximum capacity of outdoor units

Capacity of outdoor units from capacity table at the 100% connection ratio

Correction ratio of piping to furthest indoor

Condition: Indoor connection ratio exceeds 100%.


Maximum capacity of outdoor units

4.

Gas
41.3

Correction ratio of piping to furthest indoor

Liquid
22.2

When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model
52 HP

6.

Capacity of outdoor units from capacity table at installed connection ratio

When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model
52 HP

5.

Gas
41.3

Liquid
19.1

Equivalent length used in the above figures is based upon the following equivalent length
=
Equivalent piping length
Equivalent length of main pipe
+
Equivalent length of branch pipes

Correction factor

Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size
Size increase
1.0
1.0
0.5

Cooling (gas pipe)


Heating (liquid pipe)
Example

Main gas pipe size increase


Main Liquid pipe size increase

Equivalent length branch

80 m

40 m

In the above case

(Cooling) Overall equivalent length = 80 m x 1.0 + 40 m = 120 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m
The rate of change in cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 0.88

VRV Systems RXYQ-T

25

Outdoor Unit RXYQ-T

5-3

Capacity tables

Capacity Correction Factor

RYYQ54T
RXYQ54T

Correction ratio for heating capacity


Height Difference between outdoor and farest
Indoor (m)

Height Difference between outdoor and farest


Indoor (m)

Correction ratio for cooling capacity

Equivalent piping length (m)

Equivalent piping length (m)

3D079897A
NOTES

1.

These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, shown it the above figures.

2.

With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.

3.

Method of calculating the capacity of the outdoor units


The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%.
Maximum capacity of outdoor units

Capacity of outdoor units from capacity table at the 100% connection ratio

Correction ratio of piping to furthest indoor

Condition: Indoor connection ratio exceeds 100%.


Maximum capacity of outdoor units

4.

Capacity of outdoor units from capacity table at installed connection ratio

Correction ratio of piping to furthest indoor

When level difference is 50 m or more (see installation manual and 3D079540 / 3D079543) and equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes
(outdoor unit - branch sections) must be increased.
For new diameters, see below.
Model
54 HP

5.

Gas
41.3

Liquid
22.2

When the pipe length after the first refrigerant branch kit is more than 40 m, pipe size between first and final branch kit must be increased
(only for VRV DX indoor units; details see installation manual).
*Refer to the installation manual for allowed system setups and rules for dedicated indoor connection types.
Diameter of main pipes (standard size)
Model
54 HP

6.

Gas
41.3

Liquid
19.1

Equivalent length used in the above figures is based upon the following equivalent length
=
Equivalent piping length
Equivalent length of main pipe
+
Equivalent length of branch pipes

Correction factor

Choose a correction factor from the following table. When cooling capacity is calculated: gas pipe size When heating capacity is calculated: liquid pipe size
Correction factor
Standard size
Size increase
1.0
1.0
0.5

Cooling (gas pipe)


Heating (liquid pipe)
Example

Main gas pipe size increase


Main Liquid pipe size increase

Equivalent length branch

80 m

40 m

In the above case

(Cooling) Overall equivalent length = 80 m x 1.0 + 40 m = 120 m


(Heating) Overall equivalent length = 80 m x 0.5 + 40 m = 80 m

The rate of change in cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 0.83

26

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

Dimensional drawings

6-1

Dimensional Drawings

RYYQ8-12T
RYMQ8-12T
RXYQ8-12T
RXYQQ8-12T

3LWFKRIIRXQGDWLRQEROWKROHV
766

125
107

66

353
134

112

729
100

3LWFKRIIRXQGDWLRQEROWKROHV

AA

AB

339

160
70

106
AC

'HWDLO$

'HWDLO%

10

4-15x22.5mm2EORQJKROH
)RXQGDWLRQEROWKROH

9LHZ&

1685

11

9
122

179

131

276

259

515

0RGHO
RYYQ8T, RXYQ8T, RXYQQ8T
RYYQ10-12T, RXYQ10-12T, RXYQQ10-12T
RYMQ8T
REMQ5T, RYMQ10-12T, REYQ8-12T

76

76

97
137

DETAIL B

DETAIL A

AC
240
240

107

328

1RWHV

373

1. 'HWDLO$DQGGHWDLO%LQGLFDWHWKHGLPHQVLRQVDIWHUIL[LQJWKHDWWDFKHGSLSLQJ
2. ,WHPV
.QRFNRXWKROH

930

11
10
9
8
7
6
5
4

EUD]LQJFRQQHFWLRQ
EUD]LQJFRQQHFWLRQ
EUD]LQJFRQQHFWLRQ
EUD]LQJFRQQHFWLRQ

/LTXLGSLSH
RYYQ8-10T, RYMQ8-10T, RXYQ8-10T, RXYQ
Q8-10T, REMQ5T, REYQ8-12T
:
RYYQ12T, RYMQ12T, RXYQ12T, RXYQQ12T :

AB
208
208

272

765

3. *DVSLSH
RYYQ8T, RYMQ8T, RXYQ8T, RXYQQ8T
:
RYYQ10T, RYMQ10T, RXYQ10T, RXYQQ10T :
REMQ5T, REYQ8-12T
:
RYYQ12T, RYMQ12T, RXYQ12T, RXYQQ12T :

AA
248
195
248
195

EUD]LQJFRQQHFWLRQ
EUD]LQJFRQQHFWLRQ

(TXDOLVLQJSLSH
RYMQ8-10T :
RYMQ12T :

EUD]LQJFRQQHFWLRQ

+LJKSUHVVXUHORZSUHVVXUHJDVSLSH
REMQ5T, REYQ8-12T :

EUD]LQJFRQQHFWLRQ

3
2
1
No.

EUD]LQJFRQQHFWLRQ

,QVLGHRIWKHVZLWFKER[ 0

*URXQGLQJWHUPLQDO
3LSHURXWLQJKROH ERWWRP
3LSHURXWLQJKROH IURQW

65
27
65
80
65

3RZHUFRUGURXWLQJKROH ERWWRP
3RZHUFRUGURXWLQJKROH IURQW
3RZHUFRUGURXWLQJKROH IURQW
3RZHUFRUGURXWLQJKROH IURQW
3RZHUFRUGURXWLQJKROH VLGH
(TXDOLVLQJSLSHFRQQHFWLRQSRUW
+LJKSUHVVXUHORZSUHVVXUHJDVSLSH

6HHQRWH

*DVSLSHFRQQHFWLRQSRUW

6HHQRWH

/LTXLGSLSHFRQQHFWLRQSRUW

6HHQRWH

3DUWQDPH

5HPDUN

2D079532B

RYYQ14-20T
RYMQ14-20T
RXYQ14-20T
RXYQQ14-20T

3LWFKRIIRXQGDWLRQEROWKROHV
1076

393
134

107

112

125

70

71

100

3LWFKRIIRXQGDWLRQEROWKROHV

192

AB

310

729

106

160

10

AA
4-15x22.5mm - 2EORQJKROH
)RXQGDWLRQEROWKROH

'HWDLO%

'HWDLO$

9LHZ&

1685

11

179

0RGHO
RYMQ14-16T, RXYQQ14-16T, REYQ14-20T
RYMQ18-20T, RXYQQ18-20T

76

76

97

137

DETAIL B

765

DETAIL A

107

373

1. 'HWDLO$DQGGHWDLO%LQGLFDWHWKHGLPHQVLRQVDIWHUIL[LQJWKHDWWDFKHGSLSLQJ
2. ,WHPV
.QRFNRXWKROH
3. *DVSLSH
REYQ14-20T

1240

EUD]LQJFRQQHFWLRQ

RYYQ14-20T, RYMQ14-20T, RXYQ14-20T, RXYQQ14-20T

AB
205
210

272
328

1RWHV

AA
240
240

131

276

259

515

122

EUD]LQJFRQQHFWLRQ

/LTXLGSLSH
RYYQ14-16T, RYMQ14-16T, RXYQ14-16T, RXYQQ14-16T, REYQ14-20T :

EUD]LQJFRQQHFWLRQ

RYYQ18-20T, RYMQ18-20T, RXYQ18-20T, RXYQQ18-20T

EUD]LQJFRQQHFWLRQ

(TXDOLVLQJSLSH
RYMQ14-16T

EUD]LQJFRQQHFWLRQ

RYMQ18-20T

EUD]LQJFRQQHFWLRQ

+LJKSUHVVXUHORZSUHVVXUHJDVSLSH
REYQ14-20T

EUD]LQJFRQQHFWLRQ

11
10
9
8
7
6
5
4
3

*URXQGLQJWHUPLQDO
3LSHURXWLQJKROH IURQW
3RZHUFRUGURXWLQJKROH ERWWRP
3RZHUFRUGURXWLQJKROH IURQW
3RZHUFRUGURXWLQJKROH IURQW
3RZHUFRUGURXWLQJKROH IURQW
3RZHUFRUGURXWLQJKROH VLGH
(TXDOLVLQJSLSHFRQQHFWLRQSRUW

65
27
65
80
65
6HHQRWH

+LJKSUHVVXUHORZSUHVVXUHJDVSLSH

2 *DVSLSHFRQQHFWLRQSRUW
1 /LTXLGSLSHFRQQHFWLRQSRUW
No. 3DUWQDPH

VRV Systems RXYQ-T

,QVLGHRIWKHVZLWFKER[ 0

3LSHURXWLQJKROH ERWWRP

6HHQRWH
6HHQRWH

2D079533B

5HPDUN

27

Outdoor Unit RXYQ-T

7-1

Centre of gravity
Centre of Gravity

RYYQ8-12T
RYMQ8-12T
RXYQ8-12T
RXYQQ8-12T

8QLW

RYYQ8-12T

AA

AB

AC

328

366

565

REMQ5T / REYQ8-12T
RYMQ8-12T
RXYQ8-12T

354

443

565

339

448

565

AC

RXYQQ8-12T

9LHZ$

AA
)RXQGDWLRQEROWKROH

AB
)RXQGDWLRQEROWKROH

766

729

)RXQGDWLRQEROWKROH

)RXQGDWLRQEROWKROH VORW

9LHZ$

3D079582B

RYYQ14-20T
RYMQ14-20T
RXYQ14-20T
RXYQQ14-20T

AC

Unit

9LHZ$

AA
729

AB
1076

)RXQGDWLRQEROWW\SH

)RXQGDWLRQEROWW\SH

)RXQGDWLRQEROWKROH

)RXQGDWLRQEROWKROH VORW
9LHZ$

3D079583B

28

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

8-1

Piping diagrams
Piping Diagrams

RXYQ8-12T

R1T
Service Port

Double tube
Heat exchanger

R4T

R6T

R5T

Heat sink
PCB

Fan
Filter

M1F

Electronic
expansion
valve <(

R7T
Heat exchanger

Electronic
expansion
valve <(

Filter

Pressure
regulating
valve

Four way
valve <6

Low pressure
sensor 613/

High pressure
sensor 613+

Check
valve

OIL
SEPARATOR

Filter

R3T

High pressure
switch 63+

Filter
R21T

Compressor
INV
M1C

Filter

R8T
Only for
10-12HP

Solenoid
valve
<6
Capillary
tube

Accumulator

Solenoid
valve <6

Liquid pipe
Gas pipe
Filter
Charge port

Stop valve
:LWKVHUYLFHSRUWRQRQVLWHSLSLQJVLGHPPDUHFRQQHFWLRQ

3D081913

VRV Systems RXYQ-T

29

Outdoor Unit RXYQ-T

8-1

Piping diagrams

Piping Diagrams

RXYQ14-20T

R1T
Service
Port
Double tube Heat
exchanger

Heat sink
PCB

R6T

R5T

Fan

R4T Filter
Electronic
expansion
valve <(

Fan

M1F

M2F

R7T
Heat exchanger

Pressure
regulating
valve

Filter

Electronic
expansion
valve <(

Four way
valve <6
Low pressure
sensor 613/

High pressure
sensor 613+

Check
valve

HPS
High pressure
switch 63+

OIL
SEPARATOR

OIL
SEPARATOR

Filter

Filter

Check
valve

R3T

Filter

Accumulator

Capillary
tube

M1C

Capillary
tube

Compressor
INV

Filter

Filter
Solenoid
valve
<6

R21T

HPS
High pressure
switch 63+
R22T

Solenoid
valve
<6

Compressor
INV
M2C

R8T
Only for
18-20HP

Solenoid
valve <6

Liquid pipe
Gas pipe
Filter

Capillary
tube

Charge port

Stop valve
:LWKVHUYLFHSRUWRQRQVLWHSLSLQJVLGHPPDUHFRQQHFWLRQ

3D081914

30

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

9-1

Wiring diagrams

Wiring Diagrams - Three Phase

RYYQ8T
RYMQ8T
RXYQ8T
Power supply

9
Seg1

Seg2

On
2II

Seg3

(Note 8)

On
2II

(Note 3)

(Note 9)

TO IN/D UNIT TO OUT/D UNIT

(Note 3)

Selector

/D\RXWRI
0&0)

(Note 4)
(Note 4)

(OFRPSRER[
(OFRPSRER[

indoor
outdoor

Outer Shell

Heat
Cool

Cool
Heat
Fan

7HUPLQDORI
M1C

Cool/heat selector
(optional accessory) (note 3)
(Front side)

A1P
A2P
A3P
A4P
BS1~3
&&
'6'6
E1HC
)8)8
F3U
F101U
F400U
F410U ~ F412U
HAP
K1M
K1R
K3R
K3R
K4R
K6R
K7R

Printed circuit board (main)


3ULQWHGFLUFXLWERDUG QRLVHOWHU
Printed circuit board (inv)
3ULQWHGFLUFXLWERDUG IDQ
3XVKEXWWRQVZLWFK $3  PRGHVHWUHWXUQ
Capacitor (A3P)
Dip switch (A1P)
Crankcase heater
)XVH 7$9  $3
)LHOGIXVH
Fuse (A4P)
Fuse (A2P)
Fuse (A2P)
Pilotlamp (service monitor-green) (A1P)
Magnetic relay (A3P)
Magnetic relay (A3P)
Magnetic relay (A2P)
Magnetic relay (Y3S) (A1P)
Magnetic relay (Y2S) (A1P)
Magnetic relay (Y5S) (A1P)
Magnetic relay (E1HC) (A1P)

K11R
L1R
M1C
M1F
PS
Q1DI
QR1P
R1T
R21T
R3T
R4T
R5T
R6T
R7T
55
R24
R77
R78
S1NPH
S1NPL
S1PH

Magnetic relay (Y1S) (A1P)


Reactor
Motor (compressor)
0RWRU IDQ
6ZLWFKLQJSRZHUVXSSO\ $3$3
Field earth leakage breaker
Phase reversal detect circuit (A1P)
Thermistor (AIR) (A1P)
Thermistor (M1C discharge)
Thermistor (accumulator)
7KHUPLVWRU KHDWH[FOLTSLSH
7KHUPLVWRU VXEFRROOLTSLSH
7KHUPLVWRU KHDWH[FJDVSLSH
7KHUPLVWRU KHDWH[FGHLFHU
Resistor (A3P)
Resistor (current sensor) (A4P)
Resistor (current sensor) (A3P)
Resistor (current limiting) (A3P)
Pressure sensor (high)
Pressure sensor (low)
Pressure switch (disch)

SEG1~SEG3
V1R
;$;$
X3A
X1M
X1M
Y1E
Y2E
Y3E
Y1S
Y2S
Y3S
Y5S
Z1C~Z6C
Z1F

X37A
X66A

(Rear side)

7-segment display (A1P)


Power module (A3P) (A4P)
Connector (M1F)
Connector (check the residual charge)
Terminal block (power supply)
Terminal block (control) (A1P)
(OHFWURQLFH[SDQVLRQYDOYH PDLQ
(OHFWURQLFH[SDQVLRQYDOYH LQMHFWLRQ
(OHFWURQLFH[SDQVLRQYDOYH VWRUDJHYHVVHO  QRWH
Solenoid valve (main)
Solenoid valve (accumulator oil return)
Solenoid valve (OIL1)
Solenoid valve (sub) (note 9)
1RLVHOWHU IHUULWHFRUH
1RLVHOWHU $3  ZLWKVXUJHDEVRUEHU

&RQQHFWRUIRURSWLRQDODFFHVVRULHV
Connector (power adapter)
Connector (remote switching cool/heat selector)

NOTES

1.
2.
3.
4.
5.
6.
7.
8.
9.

This wiring diagram applies only to the outdoor unit.


HOGZLULQJ
WHUPLQDOEORFN
FRQQHFWRU WHUPLQDO
: Protective earth (SREW)
:KHQXVLQJWKHRSWLRQDODGDSWHUUHIHUWRWKHLQVWDOODWLRQPDQXDORIWKHRSWLRQDODGDSWHU
)RUFRQQHFWLRQZLULQJWRLQGRRURXWGRRUWUDQVPLVVLRQ))RXWGRRURXWGRRUWUDQVPLVVLRQ))UHIHUWRWKHLQVWDOODWLRQPDQXDO
How to use BSaVZLWFK5HIHUWRVHUYLFHSUHFDXWLRQODEHORQHOFRPSRER[FRYHU
:KHQRSHUDWLQJGRQWVKRUWFLUFXLWWKHSURWHFWLRQGHYLFH S1PH)
&RORUVEONEODFNUHGUHGEOXEOXHZKWZKLWHJUQJUHHQ
2QO\IRURYYQ model.
2QO\IRURYYQ/RYMQ model.

VRV Systems RXYQ-T

2D083677

31

Outdoor Unit RXYQ-T

9-1

Wiring diagrams

Wiring Diagrams - Three Phase

RYYQ10-12T
RYMQ10-12T
RXYQ10-12T
Power supply

9
Seg1

Seg2

On
2II

Seg3

(Note 8)

On
2II

(Note 3)

(Note 9)

TO IN/D UNIT TO OUT/D UNIT

(Note 3)

Selector

/D\RXWRI
0&0)

(Note 4)
(Note 4)

(OFRPSRER[

indoor

(OFRPSRER[

outdoor

Outer Shell

Heat
Cool

Cool
Heat
Fan

7HUPLQDORI
M1C

Cool/heat selector
(optional accessory) (note 3)
(Front side)

A1P
A2P
A3P
A4P
BS1~3
&&
'6'6
E1HC
)8)8
F101U
F3U
F410U ~ F412U
F601U
HAP
K1M
K1R
K3R
K3R
K4R
K6R
K7R

Printed circuit board (main)


3ULQWHGFLUFXLWERDUG QRLVHOWHU
Printed circuit board (inv)
3ULQWHGFLUFXLWERDUG IDQ
3XVKEXWWRQVZLWFK $3  PRGHVHWUHWXUQ
Capacitor (A3P)
Dip switch (A1P)
Crankcase heater
)XVH 7$9  $3
Fuse (A4P)
)LHOGIXVH
Fuse (A2P)
Fuse (A3P)
Pilotlamp (service monitor-green) (A1P)
Magnetic contactor (A3P)
Magnetic relay (A3P)
Magnetic relay (A3P)
Magnetic relay (Y3S) (A1P)
Magnetic relay (Y2S) (A1P)
Magnetic relay (Y5S) (A1P)
Magnetic relay (E1HC) (A1P)

K11R
/5/5
M1C
M1F
PS
Q1DI
QR1P
R1T
R21T
R3T
R4T
R5T
R6T
R7T
R8T
R1
R24
R313
55
S1NPH
S1NPL

Magnetic relay (Y1S) (A1P)


Reactor
Motor (compressor)
0RWRU IDQ
6ZLWFKLQJSRZHUVXSSO\ $3$3
Field earth leakage breaker
Phase reversal detect circuit (A1P)
Thermistor (AIR) (A1P)
Thermistor (M1C discharge)
Thermistor (accumulator)
7KHUPLVWRU KHDWH[FOLTSLSH
7KHUPLVWRU VXEFRROOLTSLSH
7KHUPLVWRU KHDWH[FJDVSLSH
7KHUPLVWRU KHDWH[FGHLFHU
Thermistor (M1C body)
Resistor (current limiting) (A3P)
Resistor (current sensor) (A4P)
Resistor (current sensor) (A3P)
Resistor (A3P)
Pressure sensor (high)
Pressure sensor (low)

S1PH
SEG1~SEG3
V1R
V2R
;$;$
X3a
X1M
X1M
Y1E
Y2E
Y3E
Y1S
Y2S
Y3S
Y5S
Z1C~Z6C
Z1F
X37A
X66A

(Rear side)

Pressure switch (disch)


7-segment display (A1P)
Power module (A3P) (A4P)
Power module (A3P)
Connector (M1F)
Connector (check the residual charge)
Terminal block (power supply)
Terminal block (control) (A1P)
(OHFWURQLFH[SDQVLRQYDOYH PDLQ
(OHFWURQLFH[SDQVLRQYDOYH LQMHFWLRQ
(OHFWURQLFH[SDQVLRQYDOYH VWRUDJHYHVVHO  QRWH
Solenoid valve (main)
Solenoid valve (accumulator oil return)
Solenoid valve (OIL1)
Solenoid valve (sub) (note 9)
1RLVHOWHU IHUULWHFRUH
1RLVHOWHU $3  ZLWKVXUJHDEVRUEHU
&RQQHFWRUIRURSWLRQDODFFHVVRULHV
Connector (power adapter)
Connector (remote switching cool/heat selector)

NOTES

1.
2.
3.
4.
5.
6.
7.
8.
9.

32

This wiring diagram applies only to the outdoor unit.


HOGZLULQJ
WHUPLQDOEORFN
FRQQHFWRU WHUPLQDO
: Protective earth (SREW)
:KHQXVLQJWKHRSWLRQDODGDSWHUUHIHUWRWKHLQVWDOODWLRQPDQXDORIWKHRSWLRQDODGDSWHU
)RUFRQQHFWLRQZLULQJWRLQGRRURXWGRRUWUDQVPLVVLRQ))RXWGRRURXWGRRUWUDQVPLVVLRQ))UHIHUWRWKHLQVWDOODWLRQPDQXDO
How to use BSaVZLWFK5HIHUWRVHUYLFHSUHFDXWLRQODEHORQHOFRPSRER[FRYHU
:KHQRSHUDWLQJGRQWVKRUWFLUFXLWWKHSURWHFWLRQGHYLFH S1PH)
&RORUVEONEODFNUHGUHGEOXEOXHZKWZKLWHJUQJUHHQ
2QO\IRURYYQ model.
2QO\IRURYYQ/RYMQ model.

VRV Systems RXYQ-T

2D083678

Outdoor Unit RXYQ-T

9-1

Wiring diagrams

Wiring Diagrams - Three Phase

RYYQ14-16T
RYMQ14-16T
RXYQ14-16T
Power supply

Seg1

Seg2

On
2II

Seg3

(Note 7)

On
2II

(Note 8)
(Note 3)
TO IN/D UNIT TO IN/D UNIT
(Note 3)
selector

/D\RXWRI
0&0&0)0)

Heat
Cool

Cool
Heat
Fan

(Note 4)
(Note 4)

(OFRPSRER[

indoor
Cool/heat selector (optional accessory) (note 3)

outdoor
Outer Shell

7HUPLQDORI
0&0&

(OFRPSRER[

&RORUV EONEODFNUHGUHGEOXEOXH
ZKWZKLWHJUQJUHHQ

LVFRQQHFWRUFRORUIRUFRPSRQHQW

LVGLVFULPLQDWLRQFRORUIRU
component lead wire

A1P
$3$3
$3$3
$3$3
BS1~3
&&
'6'6
(+&(+&
)8)8
F101U
F3U
F400U
F410U ~ F412U
HAP
K1M
K1R
K3R
K3R
K4R
K5R
K6R
K7R

Printed circuit board (main)


3ULQWHGFLUFXLWERDUG QRLVHOWHU
Printed circuit board (inv)
3ULQWHGFLUFXLWERDUG IDQ
3XVKEXWWRQVZLWFK $3  PRGHVHWUHWXUQ
&DSDFLWRU $3  $3
Dip switch (A1P)
Crankcase heater
)XVH 7$9  $3
)XVH $3$3
)LHOGIXVH
)XVH $3$3
)XVH $3$3
Pilotlamp (service monitor-green) (A1P)
0DJQHWLFFRQWDFWRU $3$3
0DJQHWLFUHOD\ $3$3
0DJQHWLFUHOD\ $3$3
Magnetic relay (Y4S) (A1P)
Magnetic relay (Y2S) (A1P)
Magnetic relay (Y3S) (A1P)
Magnetic relay (Y5S) (A1P)
Magnetic relay (E1HC) (A1P)

K8R
K11R
/5/5
0&0&
0)0)
PS
Q1DI
QR1P
55
R24
R77
R78
R1T
5757
R3T
R4T
R5T
R6T
R7T
S1NPH
S1NPL
63+63+

Magnetic relay (E2HC) (A1P)


Magnetic relay (Y1S) (A1P)
Reactor
Motor (compressor)
0RWRU IDQ
6ZLWFKLQJSRZHUVXSSO\ $3$3$3
Field earth leakage breaker
Phase reversal detect circuit (A1P)
5HVLVWRU $3$3
5HVLVWRU FXUUHQWVHQVRU  $3$3
5HVLVWRU FXUUHQWVHQVRU  $3$3
5HVLVWRU FXUUHQWOLPLWLQJ  $3$3
Thermistor (AIR) (A1P)
7KHUPLVWRU 0&0&GLVFKDUJH 
Thermistor (accumulator)
7KHUPLVWRU KHDWH[FOLTSLSH
7KHUPLVWRU VXEFRROOLTSLSH
7KHUPLVWRU KHDWH[FJDVSLSH
7KHUPLVWRU KHDWH[FGHLFHU
Pressure sensor (high)
Pressure sensor (low)
Pressure switch (disch)

SEG1~SEG3
V1R
V1R
X1A~4A
X5A~X6A
X1M
X1M
Y1E
Y2E
Y3E
Y1S
Y2S
Y3S
Y4S
Y5S
Z1C~Z7C
Z1F

X37A
X66A

7-segment display (A1P)


3RZHUPRGXOH $3$3
3RZHUPRGXOH $3$3
&RQQHFWRU 0)0)
Connector (check the residual charge)
Terminal block (power supply)
Terminal block (control) (A1P)
(OHFWURQLFH[SDQVLRQYDOYH PDLQ
(OHFWURQLFH[SDQVLRQYDOYH LQMHFWLRQ
(OHFWURQLFH[SDQVLRQYDOYH VWRUDJHYHVVHO  QRWH
Solenoid valve (main)
Solenoid valve (accumulator oil return)
Solenoid valve (OIL1)
Solenoid valve (OIL2)
Solenoid valve (sub) (note 8)
1RLVHOWHU IHUULWHFRUH
1RLVHOWHU $3$3  ZLWKVXUJHDEVRUEHU
&RQQHFWRUIRURSWLRQDODFFHVVRULHV
Connector (power adapter)
Connector (remote switching cool/heat selector)

NOTES

1.
2.
3.
4.
5.
6.
7.
8.

This wiring diagram applies only to the outdoor unit.


HOGZLULQJ
WHUPLQDOEORFN
FRQQHFWRU WHUPLQDO
: Protective earth (SREW)
:KHQXVLQJWKHRSWLRQDODGDSWHUUHIHUWRWKHLQVWDOODWLRQPDQXDORIWKHRSWLRQDODGDSWHU
)RUFRQQHFWLRQZLULQJWRLQGRRURXWGRRUWUDQVPLVVLRQ))RXWGRRURXWGRRUWUDQVPLVVLRQ))UHIHUWRWKHLQVWDOODWLRQPDQXDO
How to use BSaVZLWFK5HIHUWRVHUYLFHSUHFDXWLRQODEHORQHOFRPSRER[FRYHU
:KHQRSHUDWLQJGRQWVKRUWFLUFXLWWKHSURWHFWLRQGHYLFH 63+63+)
2QO\IRURYYQ model.
2QO\IRURYYQ/RYMQ model.

2D083679

VRV Systems RXYQ-T

33

Outdoor Unit RXYQ-T

9-1

Wiring diagrams

Wiring Diagrams - Three Phase

RYYQ18-20T
RYMQ18-20T
RXYQ18-20T
Power supply

Seg1

Seg2

On
2II

(Note 7)

Seg3

On
2II

(Note 8)
(Note 3)
TO IN/D UNIT TO IN/D UNIT
(Note 3)
selector

/D\RXWRI
0&0&0)0)

Heat
Cool

Cool
Heat
Fan

(Note 4)
(Note 4)

(OFRPSRER[

indoor
Cool/heat selector (optional accessory) (note 3)

(OFRPSRER[

&RORUV EONEODFNUHGUHGEOXEOXH
ZKWZKLWHJUQJUHHQ

LVFRQQHFWRUFRORUIRUFRPSRQHQW

LVGLVFULPLQDWLRQFRORUIRU
component lead wire

A1P
$3$3
$3$3
$3$3
BS1~3
&&
&&
'6'6
(+&(+&
)8)8
F3U
F101U
F400U
F410U ~ F412U
F601U
HAP
K1M
K1R
K3R
K3R
K4R
K5R
K6R
K7R
K8R

Printed circuit board (main)


3ULQWHGFLUFXLWERDUG QRLVHOWHU
Printed circuit board (inv)
3ULQWHGFLUFXLWERDUG IDQ
3XVKEXWWRQVZLWFK $3  PRGHVHWUHWXUQ
Capacitor (A3P)
Capacitor (A6P)
Dip switch (A1P)
Crankcase heater
)XVH 7$9  $3
)LHOGIXVH
)XVH $3$3 
Fuse (A2P)
)XVH $3$3
Fuse (A6P)
Pilotlamp (service monitor-green) (A1P)
0DJQHWLFFRQWDFWRU $3$3
0DJQHWLFUHOD\ $3$3
0DJQHWLFUHOD\ $3$3
Magnetic relay (Y4S) (A1P)
Magnetic relay (Y2S) (A1P)
Magnetic relay (Y3S) (A1P)
Magnetic relay (Y5S) (A1P)
Magnetic relay (E1HC) (A1P)
Magnetic relay (E2HC) (A1P)

K11R
L1R ~ L3R
0&0&
0)0)
PS
Q1DI
QR1P
R1
55
R24
R77
R78
R313
55
R1T
5757
R3T
R4T
R5T
R6T
R7T
R8T
S1NPH
S1NPL
63+63+

Magnetic relay (Y1S) (A1P)


Reactor
Motor (compressor)
0RWRU IDQ
6ZLWFKLQJSRZHUVXSSO\ $3$3$3
Field earth leakage breaker
Phase reversal detect circuit (A1P)
Resistor (current limiting) (A6P)
Resistor (A3P)
5HVLVWRU FXUUHQWVHQVRU  $3$3
Resistor (current sensor) (A3P)
Resistor (current limiting) (A3P)
Resistor (current censor) (A6P)
Resistor (A6P)
Thermistor (AIR) (A1P)
7KHUPLVWRU 0&0&GLVFKDUJH 
Thermistor (accumulator)
7KHUPLVWRU KHDWH[FOLTSLSH
7KHUPLVWRU VXEFRROOLTSLSH
7KHUPLVWRU KHDWH[FJDVSLSH
7KHUPLVWRU KHDWH[FGHLFHU
7KHUPLVWRU 0&ERG\
Pressure sensor (high)
Pressure sensor (low)
Pressure switch (disch)

outdoor
Outer Shell

7HUPLQDORI
0&0&

SEG1~SEG3
V1R
V1R
V2R
X1A~4A
X5A~X6A
X1M
X1M
Y1E
Y2E
Y3E
Y1S
Y2S
Y3S
Y4S
Y5S
Z1C~Z7C
Z1F

X37A
X66A

7-segment display (A1P)


3RZHUPRGXOH $3$3
3RZHUPRGXOH $3$3
Power module (A6P)
&RQQHFWRU 0)0)
Connector (check the residual charge)
Terminal block (power supply)
Terminal block (control) (A1P)
(OHFWURQLFH[SDQVLRQYDOYH PDLQ
(OHFWURQLFH[SDQVLRQYDOYH LQMHFWLRQ
(OHFWURQLFH[SDQVLRQYDOYH VWRUDJHYHVVHO  QRWH
Solenoid valve (main)
Solenoid valve (accumulator oil return)
Solenoid valve (OIL1)
Solenoid valve (OIL2)
Solenoid valve (sub) (note 8)
1RLVHOWHU IHUULWHFRUH
1RLVHOWHU $3$3  ZLWKVXUJHDEVRUEHU

&RQQHFWRUIRURSWLRQDODFFHVVRULHV
Connector (power adapter)
Connector (remote switching cool/heat selector)

NOTES

1.
2.
3.
4.
5.
6.
7.
8.

This wiring diagram applies only to the outdoor unit.


HOGZLULQJ
WHUPLQDOEORFN
FRQQHFWRU WHUPLQDO
: Protective earth (SREW)
:KHQXVLQJWKHRSWLRQDODGDSWHUUHIHUWRWKHLQVWDOODWLRQPDQXDORIWKHRSWLRQDODGDSWHU
)RUFRQQHFWLRQZLULQJWRLQGRRURXWGRRUWUDQVPLVVLRQ))RXWGRRURXWGRRUWUDQVPLVVLRQ))UHIHUWRWKHLQVWDOODWLRQPDQXDO
How to use BSaVZLWFK5HIHUWRVHUYLFHSUHFDXWLRQODEHORQHOFRPSRER[FRYHU
:KHQRSHUDWLQJGRQWVKRUWFLUFXLWWKHSURWHFWLRQGHYLFH 63+63+)
2QO\IRURYYQ model.
2QO\IRURYYQ/RYMQ model.

2D083680

34

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

10

External connection diagrams

10 - 1 External Connection Diagrams


RYYQ8-20T
RXYQ8-20T
RXYQQ8-20T

Power Supply

Main Switch

10

Outdoor units

Switch
Fuse

Power Supply

Main Switch

2 Wires cable
(Transmission line)
2 Wires cable

2 Wires cable

2 Wires cable

(Transmission line)

(Transmission line)

(Transmission line)

(Power line)

Switch

Switch

Fuse
2 Wires cable

Switch

Fuse
2 Wires cable

(Power line)

Switch

Fuse

Fuse

2 Wires cable
(Power line)

(Power line)

2 Wires cable
(Power line)

Indoor units

3D079576

NOTES

1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

All wiring, components and materials to be procured on the site must comply with the applicable local and national codes.
Use copper conductors only.
As for details, see wiring diagram.
Install circuit breaker for safety.
$OOHOGZLULQJDQGFRPSRQHQWVPXVWEHSURYLGHGE\OLFHQVHGHOHFWULFLDQ
Unit shall be grounded in compliance with the applicable local and national codes.
:LULQJVKRZQDUHJHQHUDOSRLQWVRIFRQQHFWLRQJXLGHVRQO\DQGDUHQRWLQWHQGHGIRURUWRLQFOXGHDOOGHWDLOVIRUDVSHFLFLQVWDOODWLRQ
Be sure to install the switch and the fuse to the power line of each equipement.
Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equipment utilizing the multiple power sources.
,IWKHUHH[LVWVWKHSRVVLELOLW\RIUHYHUVHGSKDVHORVHSKDVHPRPHQWDU\EODFNRXWRUWKHSRZHUJRHVRQDQGRIIZKLOHWKHSURGXFWLVRSHUDWLQJDWWDFKDUHYHUVHGSKDVHSURWHFWLRQFLUFXLWORFDOO\
5XQQLQJWKHSURGXFWLQUHYHUVHGSKDVHPD\EUHDNWKHFRPSUHVVRUDQGRWKHUSDUWV
11. Must install earth leakage circuit breaker.

RYYQ22-36T
RXYQ22-36T
RXYQQ22-36T
Power Supply

Power Supply

< When the power source is supplied to each outdoor unit individually. >

Outdoor units

Main
Switch

< When the power source is connected in series between the units. >

Outdoor units

Main
Switch

2 Wires cable
(Transmission line)

2 Wires cable
(Transmission line)

Power Supply

Power Supply

Main
Switch

Main
Switch

2 Wires cable
(Transmission line)
2 Wires cable
(Power line)

Switch
Fuse

2 Wires cable
(Transmission line)
2 Wires cable
(Transmission line)

2 Wires cable
(Transmission line)

Switch
Fuse

Switch
Fuse

2 Wires cable
(Transmission line)

Switch
Fuse

2 Wires cable
(Power line)

2 Wires cable
(Transmission line)

Switch

Switch

Fuse

Fuse

2 Wires cable
(Transmission line)

Switch
Fuse

2 Wires cable
(Transmission line)

Switch
Fuse

2 Wires cable
(Power line)
2 Wires cable
(Power line)

2 Wires cable
(Power line)

2 Wires cable
(Power line)

Indoor units

2 Wires cable
(Power line)

2 Wires cable
(Power line)

2 Wires cable
(Power line)

Indoor units

2 Wires cable
(Power line)

3D079577

NOTES

1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.

All wiring, components and materials to be procured on the site must comply with the applicable local and national codes.
Use copper conductors only.
As for details, see wiring diagram.
Install circuit breaker for safety.
$OOHOGZLULQJDQGFRPSRQHQWVPXVWEHSURYLGHGE\OLFHQVHGHOHFWULFLDQ
Unit shall be grounded in compliance with the applicable local and national codes.
:LULQJVKRZQDUHJHQHUDOSRLQWVRIFRQQHFWLRQJXLGHVRQO\DQGDUHQRWLQWHQGHGIRURUWRLQFOXGHDOOGHWDLOVIRUDVSHFLFLQVWDOODWLRQ
Be sure to install the switch and the fuse to the power line of each equipement.
Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equipment utilizing the multiple power sources.
the capacity of UNIT1 must be larger than UNIT2 when the power source is connected in series between the units.
,IWKHUHH[LVWVWKHSRVVLELOLW\RIUHYHUVHGSKDVHORVHSKDVHPRPHQWDU\EODFNRXWRUWKHSRZHUJRHVRQDQGRIIZKLOHWKHSURGXFWLVRSHUDWLQJDWWDFKDUHYHUVHGSKDVHSURWHFWLRQFLUFXLWORFDOO\
5XQQLQJWKHSURGXFWLQUHYHUVHGSKDVHPD\EUHDNWKHFRPSUHVVRUDQGRWKHUSDUWV
12. Must install earth leakage circuit breaker.

VRV Systems RXYQ-T

35

Outdoor Unit RXYQ-T

10

External connection diagrams

10 - 1 External Connection Diagrams

<When the power source is supplied to each outdoor unit individually>

RYYQ38-54T
RXYQ38-54T
RXYQQ38-42T

<When the power sourse is connected in series between the units>

OUTDOOR UNITS

Power supply

Main
switch

OUTDOOR UNITS

Power supply
Main
switch

10

2 wires cable
2 wires cable
(Transmission line) (Transmission line)
(UNIT 2)
(UNIT 3)

(UNIT 1)
Switch

Switch
Fuse

Fuse

(UNIT 1)

Switch
Fuse

2 wires cable
2 wires cable
(Transmission line) (Transmission line)
(UNIT 2)
(UNIT 3)

Switch
Power supply

Power supply
Main
switch

Main
switch

2 wires cable
(Transmission line)

2 wires cable
(Power line) Switch
Fuse
2 wires cable
(Power line)

2 wires cable
(Transmission line)
2 wires cable
(Transmission line)

2 wires cable
(Transmission line)

2 wires cable
(Transmission line)

Switch
Fuse

Switch
Fuse

Switch
Fuse

2 wires cable
(Power line)

2 wires cable
(Power line)

2 wires cable
(Power line)

INDOOR UNITS

2 wires cable
(Power line)
Switch
Fuse
2 wires cable
(Power line)

2 wires cable
(Transmission line)

2 wires cable
(Transmission line)

Switch
Fuse
2 wires cable
(Power line)

2 wires cable
(Transmission line)

Switch
Fuse

Switch
Fuse

2 wires cable
(Power line)

2 wires cable
(Power line)

INDOOR UNITS

3D079578
NOTES

1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.

All wiring, components and materials to be produced on the site must comply with the applicable local and national codes.
Use copper conductors only.
As for details, see wiring diagram.
Install circuit breaker for safety.
$OOHOGZLULQJDQGFRPSRQHQWVPXVWEHSURYLGHGE\OLFHQVHGHOHFWULFLDQ
Unit shall be grounded in compliance with the applicable local and national codes.
:LULQJVKRZQDUHJHQHUDOSRLQWVRIFRQQHFWLRQJXLGHVRQO\DQGDUHQRWLQWHQGHGIRURUWRLQFOXGHDOOGHWDLOVIRUDVSHFLFLQVWDOODWLRQ
Be sure to install the switch and the fuse to the power line of each equipement.
Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equipment utilizing the multiple power sources.
The capacity of UNIT1 must be larger than UNIT2 when the power source is connected in series between the units.
If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
12. Must install earth leakage circuit breaker.

36

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

11

Sound data

11 - 1 Sound Power Spectrum

^

ZzzYd
ZzDYd
ZyzYd
ZyzYYd

90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10

90

11

NR90

80

NR85
NR80
NR75

70

NR70

60

NR65
NR60

50

NR55
NR50

40

NR45
NR40

30

NR35
NR30

NR5

63

125

20

NR25

NR0

250

NR15

NR10

500

NR20

10
1000

2000

4000

8000

dBA

K,

E
/
Zt
D/^K
 



^

ZzzYd
ZzDYd
ZyzYd
ZyzYYd

90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10

90
NR90

80

NR85
NR80
NR75

70

NR70

60

NR65
NR60

50

NR55
NR50

40

NR45
NR40

30

NR35
NR30

NR5

63

125

20

NR25

NR0

250

NR10

500

NR15

1000

NR20

10
2000

4000

8000

dBA

K,

E
/
Zt
D/^K
 



VRV Systems RXYQ-T

37

Outdoor Unit RXYQ-T

11

Sound data

11 - 1 Sound Power Spectrum

ZzzYd
ZzDYd
ZyzYd
ZyzYYd

^

11

90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10

90
NR90

80

NR85
NR80
NR75

70

NR70

60

NR65
NR60

50

NR55
NR50

40

NR45
NR40

30

NR35
NR30

NR5

63

125

20

NR25

NR0

250

NR10

500

NR15

NR20

10

1000

2000

4000

8000

dBA

K,

E
/
Zt
D/^K




^

ZzzYd
ZzDYd
ZyzYd
ZyzYYd

90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10

90
NR90

80

NR85
NR80

70

NR75
NR70

60

NR65
NR60

50

NR55
NR50

40

NR45
NR40

30

NR35
NR30

NR5

63

125

20

NR25

NR0

250

NR10

500

NR15

1000

NR20

10
2000

4000

8000

dBA

K,

E
/
Zt
D/^K




38

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

11

Sound data

11 - 1 Sound Power Spectrum

^

ZzzYd
ZzDYd
ZyzYd
ZyzYYd

90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10

90
NR90

80

NR85
NR80
NR75

11

70

NR70

60

NR65
NR60

50

NR55
NR50

40

NR45
NR40

30

NR35
NR30

NR5

63

125

20

NR25

NR0

250

NR15

NR10

500

NR20

10

1000

2000

4000

8000

dBA

K,

E
/
Zt
D/^K
 



^

ZzzYd
ZzDYd
ZyzYd
ZyzYYd

90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10

90
NR90

80

NR85
NR80
NR75

70

NR70

60

NR65
NR60

50

NR55
NR50

40

NR45
NR40

30

NR35
NR30

NR5

63

125

20

NR25

NR0

250

NR10

500

NR15

1000

NR20

10
2000

4000

8000

dBA

K,

E
/
Zt
D/^K
 



VRV Systems RXYQ-T

39

Outdoor Unit RXYQ-T

11

Sound data

11 - 1 Sound Power Spectrum

ZzzYd
ZzDYd
ZyzYd
ZyzYYd

^

11

90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10

90
NR90

80

NR85
NR80
NR75

70

NR70

60

NR65
NR60

50

NR55
NR50

40

NR45
NR40

30

NR35
NR30

NR5

63

125

20

NR25

NR0

250

NR10

500

NR15

1000

NR20

10
2000

4000

8000

dBA

K,

E
/
Zt
D/^K
 



40

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

11

Sound data

11 - 2 Sound Pressure Spectrum

3
ZzzYd
ZzDYd
ZyzYd
ZyzYYd

70
65

11

NR70

60

60

NR65

D

55

NR60

50

50
&

NR55

45

NR50
40

40
NR45
35
NR40

30

30
NR35
25
NR30
20

20

NR25
NR20

15
NR0

NR5

NR15

NR10

10

10
63

125

250

500

1000

2000

4000

8000

dBA

K,

E


/
ZW




ZzzYd
ZzDYd
ZyzYd
ZyzYYd

70

70

NR75

65

NR70

60

60

NR65

55

NR60
D

50

NR55

45

NR50

40

40
NR45

&

50

^

^

70

NR75

35
NR40
30

30
NR35
25
NR30
20

20
NR25
NR20

15
NR0

NR5

NR10

NR15
10

10
62,5

125

250

500

1000

2000

4000

8000

dBA

K,

E


/
ZW




VRV Systems RXYQ-T

41

Outdoor Unit RXYQ-T

11

Sound data

11 - 2 Sound Pressure Spectrum

ZzzYd
ZzDYd
ZyzYd
ZyzYYd

70
65

NR70

60

D

55

NR60

50

^

60

NR65

50

NR55

45

&

11

70

NR75

NR50

40

40
NR45

35
NR40
30

30
NR35

25
NR30
20

20

NR25
NR20

15
NR0

NR5

NR15

NR10

10

10
63

125

250

500

1000

2000

4000

8000

dBA

K,

E


/
ZW




ZzzYd
ZzDYd
ZyzYd
ZyzYYd

70
65

NR70

60

60

NR65

D

55

NR60

50

50

NR55

45

&

^

70

NR75

NR50
40

40
NR45
35
NR40

30

30
NR35
25
NR30
20

20

NR25
NR20

15
NR0

NR5

NR10

NR15
10

10
63

125

250

500

1000

2000

4000

8000

dBA

K,

E


/
ZW




42

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

11

Sound data

11 - 2 Sound Pressure Spectrum

ZzzYd
ZzDYd
ZyzYd
ZyzYYd

70
65

11

NR70

60

60

NR65

D

55

NR60

50

50
&

NR55

45
^

70

NR75

NR50
40

40
NR45
35
NR40

30

30
NR35
25
NR30
20

20

NR25
NR20

15
NR0

NR5

NR15

NR10

10

10
63

125

250

500

1000

2000

4000

8000

dBA

K,

E


/
ZW




ZzzYd
ZzDYd
ZyzYd
ZyzYYd

70
65

NR70

60

60

NR65

D

55

NR60

50

50

NR55

45

&

^

70

NR75

NR50
40

40
NR45
35
NR40

30

30
NR35
25
NR30
20

20

NR25
NR20

15
NR0

NR5

NR15

NR10

10

10
63

125

250

500

1000

2000

4000

8000

dBA

K,

E


/
ZW




VRV Systems RXYQ-T

43

Outdoor Unit RXYQ-T

11

Sound data

11 - 2 Sound Pressure Spectrum

ZzzYd
ZzDYd
ZyzYd
ZyzYYd

70
65

NR70

60

D

55

NR60

50

^

60

NR65

50

NR55

45

&

11

70

NR75

NR50
40

40
NR45
35
NR40

30

30
NR35
25
NR30
20

20

NR25
NR20

15
NR0

NR5

NR10

NR15
10

10
63

125

250

500

1000

2000

4000

8000

dBA

K,

E


/
ZW




44

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

12

Installation

12 - 1 Installation Method

RYYQ-T
RYMQ-T
RXYQ-T
RXYQQ-T

For single unit installation


(Pattern 1)

For installation in rows


(Pattern 1)

300 or more

10 or more

(Pattern 1)
300 or more

10 or
more

(FRONT)
500 or more

(Pattern 2)

10 or
more

20 or more

300 or more

(FRONT)
500 or more

20 or more

10 or more 10 or more

300 or more

(FRONT)
600 or more

20 or more

(FRONT)
500 or more

20 or more

10 or more
10 or more

(FRONT)
500 or more

(FRONT)

20 or more

10 or more 10 or more

500 or more

10 or more

20 or more
900 or more

(Pattern 2)
100 or more

50 or more

12

For centralized group layout

(FRONT)
500 or more

100 or more

50 or
more 50 or more

(Pattern 3)
300 or more

(FRONT)
200 or more

10 or more

10 or more
10 or more

300 or more
20 or more

10 or more

10 or more

20 or more
(FRONT)

500 or more

10 or more

(Pattern 2)
100 or more

(FRONT)
500 or more

100 or more

50 or more
100 or
more

(Pattern 3)

Wall height unrestricted

Wall height
unrestricted

50 or more

300 or more

400 or more
200 or more

50 or more
(FRONT)

400 or more

(FRONT)
500 or more

(FRONT)
500 or more

100 or more

100 or more

100 or
more
50 or
more 50 or more
100 or
more
50 or more
50 or more

(FRONT)

(FRONT)
500 or more

100 or more

50 or more
50 or more

500 or more

50 or more

100 or more
600 or more

300 or more
100 or more

50 or more 50 or more

100 or more

(FRONT)
500 or more

50 or more

<Suction side>

<Front>

<Unit = mm>

NOTES

1. Heights of walls in case of patterns 1 and 2:


Front: 1500mm
Suction side: 500mm
Side: Height unrestricted
Installation space as shown on this drawing is based on the cooling operation at 35 degrees outdoor air temperature.
When the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability of much generation load of heat in all outdoor unit, take the suction side space more
broadly than the space as shown on this drawing.
2. ,IWKHDERYHZDOOKHLJKWVDUHH[FHHGHGWKHQKDQGKVKRXOGEHDGGHGWRWKHIURQWDQGVXFWLRQVLGHVHUYLFHVSDFHVUHVSHFWLYHO\DVVKRZQLQWKHJXUHRQWKHULJKW
3. :KHQLQVWDOOLQJWKHXQLWVPRVWDSSURSULDWHSDWWHUQVKRXOGEHVHOHFWHGIURPWKRVHVKRZQDERYHLQRUGHUWRREWDLQWKHEHVWWLQWKH
space available. Always keep in mind the need to leave enough space for a person to pass between units and wall and also for the air to circulate freely.
(If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits).
4. 7KHXQLWVVKRXOGEHLQVWDOOHGWROHDYHVXIFLHQWVSDFHDWWKHIURQWIRUWKHRQVLWHUHIULJHUDQWSLSLQJZRUNWREHFDUULHGRXWFRPIRUWDEO\

3D079542

VRV Systems RXYQ-T

45

Outdoor Unit RXYQ-T

12

Installation

12 - 2 Fixation and Foundation of Units

RYYQ-T
RYMQ-T
RXYQ-T
RXYQQ-T
)RXQGDWLRQEROWW\SH-$
6L]H0
KROHVIRUDQFKRUEROWV

1XW

12

6SULQJZDVKHU

WKUHDGULGJHVRUPRUH

80

729

929

)UDPH

1 0

80

80

100

)RXQGDWLRQEROWIL[LQJPHWKRG

'UDLQGLWFK
6PRRWKGRZQJUDGHRIDERXW

AC

AA
'UDLQGLWFK

AB

6PRRWKGRZQJUDGHRIDERXW

<GLWFK

AD

AA

AD

AA

)RUPXOWLXQLWLQVWDOODWLRQ
0RGHO
:KHQEXLOGLQJDIRXQGDWLRQRQWKHJURXQG

:KHQEXLOGLQJDIRXQGDWLRQRQDFRQFUHWHIORRU
'UDLQGLWFK

100

50
50

<GLWFK

50

<GLWFK

Floor

&URVVVHFWLRQ;;

RYYQ8-12T
RYMQ8-12T
RXYQ8-12T
RXYQQ8-12T
REMQ5T / REYQ8-12T
RYYQ14-20T
RYMQ14-20T
RXYQ14-20T
RXYQQ14-20T
REYQ14-20T

AA

AB

766

992

1076

RXYCQ8

497

697

3URYLGHDGUDLQGLWFKDURXQGWKHIRXQGDWLRQWRGUDLQZDWHUIURPWKHLQVWDOODWLRQDUHD

RXYCQ10-14

792

992

2.

7KHVXUIDFHKDVWREHILQLVKHGZLWKPRUWDU7KHFRUQHUHGJHVKDYHWREHFKDPIHUHG

RXYCQ16-20

1102

1302

3.

%XLOGWKHIRXQGDWLRQRQDFRQFUHWHIORRURULIQRWSRVVLEOHPDNHVXUHWKHIRXQGDWLRQVXUIDFHKDVDURXJKILQLVK

4.

8VHDFHPHQWVDQGJUDYHOUDWLRRIIRUWKHFRQFUHWHDQGDGLDPHWHURIPPIRUWKHUHLQIRUFHPHQWEDUV DSSUR[LPDWHO\PPLQWHUYDOV 

5.

:KHQLQVWDOOLQJWKHHTXLSPHQWRQDURRIPDNHVXUHWRFKHFNWKHVWUHQJWKRIWKHIORRUDQGWDNHDGHTXDWHZDWHUSURRILQJPHDVXUHV

AD

113

185

100

160

1302

1.

1RWHV

AC

3D079547D

46

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

12

Installation

12 - 3 Refrigerant Pipe Selection

RYYQ-T
RXYQ-T
RYMQ-T

1.
1.1.

Refrigerant pipe size and allowable


pipe length

1.3.1.

Choose from the following table in accordance with the outdoor unit
total capacity type, connected downstream.

General information

Outdoor unit capacity


type (HP)

NOTICE
The refrigerant R410A requires strict cautions for keeping the
system clean, dry and tight.

Clean and dry: foreign materials (including mineral oils or


moisture) should be prevented from getting mixed into the
system.

Tight: R410A does not contain any chlorine, does not destroy
the ozone layer, and does not reduce earth's protection
against harmful ultraviolet radiation. R410A can contribute
slightly to the greenhouse effect if it is released. Therefore we
should take special attention to check the tightness of the
installation.

19.1

10

22.2

12~16

Piping and other pressure containing parts shall comply with the
applicable legislation and shall be suitable for refrigerant. Use
phosphoric acid deoxidised seamless copper for refrigerant.

34.9

26~34
36~54

1.3.

19.1

41.3

Piping between refrigerant branch kits: D

Indoor unit capacity


index

Piping outer diameter size (mm)


Gas pipe

150x<200

19.1

Installation shall be done by a licensed installer, the choice of


materials and installation shall conform completely with the
applicable national and international codes.

200x<290

22.2

In Europe, EN 378 is the applicable standard that shall be used.

420x<640

Foreign materials inside pipes (including oils for fabrication) must be 30


mg/10 m.
Temper grade: use piping with temper grade in function of the pipe
diameter as listed in table below.
Temper grade of piping material

15.9

O (annealed)

19.1

1/2H (half hard)

290x<420

Determine the proper size referring to following tables and reference figure
(only for indication).

9.5

12.7

28.6

15.9

640x<920

34.9

19.1

>920

41.3

19.1

Example:
Downstream capacity for E=capacity index of unit 1
Downstream capacity for D=capacity index of unit 1+capacity index
of unit 2
1.3.3.

Selection of piping size

Liquid pipe

15.9

NOTICE

Pipe (mm)

12.7
15.9

24

<150

9.5

Choose from the following table in accordance with the indoor unit
total capacity type, connected downstream. Do not let the
connection piping exceed the refrigerant piping size chosen by the
general system model name.

Selection of piping material


NOTICE

Liquid pipe

28.6

18~22

Piping between refrigerant branch kit and BP unit: F

Pipe size for direct connection on BP unit must be based on the total
capacity of the connected indoor units (only in case RA DX indoor
units are connected).
Total capacity index of connected
indoor units

Gas pipe
(mm)

Liquid pipe
(mm)

12.7

6.4

20-62

a
D

B
C y

63-149

15.9

150-208

19.1

9.5

Example:
Downstream capacity for F=capacity index of unit 4+capacity index
of unit 5

12

Piping outer diameter size (mm)


Gas pipe

1.3.2.

1.2.

Piping between outdoor unit and (first) refrigerant


branch kit: A, B, C

1.3.4.

Piping between BP unit and RA DX indoor unit: G

Only in case RA DX indoor units are connected.

E
1

Indoor unit capacity index

2
1,2
3
4,5
a,b
x,y

20, 25, 30

VRV DX indoor unit


BP box
RA DX indoor unit
Indoor branch kit
Outdoor multi connection kit

50
60
71

Gas pipe (mm)


9.5

Liquid pipe (mm)


6.4

12.7
15.9

9.5

4P329765-1C (1/5)

VRV Systems RXYQ-T

47

Outdoor Unit RXYQ-T

12

Installation

12 - 3 Refrigerant Pipe Selection


RYYQ-T
RXYQ-T
RYMQ-T
1.3.5.

12

Piping between refrigerant branch kit and indoor unit: E

1.4.

Pipe size for direct connection to indoor unit must be the same as the
connection size of the indoor unit (in case indoor unit is VRV DX indoor or
Hydrobox).
Piping outer diameter size
(mm)
Gas pipe

Liquid pipe

15, 20, 25, 32, 40, 50

Indoor unit capacity index

12.7

6.4

63, 80, 100, 125

15.9

200

19.1

250

22.2

9.5

For piping example, refer to "9.3. Selection of piping size".

When using refnet joints at the first branch counted from the outdoor unit
side, choose from the following table in accordance with the capacity of
the outdoor unit (example: refnet joint a).
Outdoor unit capacity type (HP)

1
2
3
4
5

KHRQ22M29T9

12-22

KHRQ22M64T

24-54

KHRQ22M75T

For refnets joints other than the first branch (example refnet joint b),
select the proper branch kit model based on the total capacity index of all
indoor units connected after the refrigerant branch.
Indoor unit capacity index

KHRQ22M20T

200x<290

KHRQ22M29T9

290x<640

KHRQ22M64T

640

KHRQ22M75T

Concerning refnet headers, choose from the following table in


accordance with the total capacity of all the indoor units connected below
the refnet header.
Indoor unit capacity index

<200
Size up
HP Class

Gas side (mm)

19.1 22.2

10

22.2 25.4(a)

Liquid size (mm)


9.5 12.7

28.6(b)

12+14

2 pipes

<200

Outdoor unit
Main pipes
Increase
First refrigerant branch kit
Indoor unit

2 pipes

8-10

When the equivalent pipe length between outdoor and indoor units is 90
m or more, the size of the main pipes (both gas side and liquid side) must
be increased. Depending on the length of the piping, the capacity may
drop, but even in such a case it is possible to increase the size of the
main pipes.

Selection of refrigerant branch kits

Refrigerant refnets

2 pipes
KHRQ22M29H

200x<290

KHRQ22M29H

290x<640

KHRQ22M64H(a)

640

KHRQ22M75H

(a) If the pipe size above the refnet header is 34.9 or more, KHRQ22M75H is
required.

12.7 15.9

16

28.6 31.8(a)

18~22

28.6 31.8(a)

15.9 19.1

INFORMATION

34.9(b)

15.9 19.1

Maximum 8 branches can be connected to a header.

24
26~34

34.9 38.1(a)

36~54

41.3(b)

19.1 22.2

(a) If size is NOT available, increase is NOT allowed.


(b) Increase is NOT allowed.

Number of outdoor units

Branch kit name

BHFQ22P1007

BHFQ22P1517

The pipe thickness of the refrigerant piping shall comply with the
applicable legislation. The minimal pipe thickness for R410A piping must
be in accordance with the table below.
Pipe (mm)

Minimal thickness t (mm)

6.4
9.5

0.80

12.7
15.9
19.1
22.2

The RYYQ22~54 models, consisting of two or three RYMQ modules,


require a 3-pipe system. There is an additional equalizing pipe for
such modules (in addition to the conventional gas and liquid piping).
This equalizing pipe does not exist for RYYQ8~20 or RYXQ8~54
units.

0.99
0.80

28.6

0.99

34.9

1.21

41.3

1.43

The equalizing pipe connections for the different RYMQ modules are
mentioned in below table.
RYMQ
8

In case the required pipe sizes (inch sizes) are not available, it is also
allowed to use other diameters (mm sizes), taken the following into
account:

Select the pipe size nearest to the required size.


Use the suitable adapters for the change-over from inch
to mm pipes (field supply).
In this case, the additional refrigerant calculation has to be
adjusted as mentioned in "14. Charging refrigerant".

Equalizing pipe (mm)


19.1

10
12

How to choose an outdoor multi connection piping kit (needed if the


outdoor unit capacity type is 22 HP or more). Choose from the following
table in accordance with the number of outdoor units.

14

22.2

16
18
20

28.6

4P329765-1C (2/5)

48

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

12

Installation

12 - 3 Refrigerant Pipe Selection

RYYQ-T
RXYQ-T
RYMQ-T

1.5.

Deciding the equalizing pipe diameter:

In case of 3 multi units: the connection diameter of outdoor to


T-joint has to be kept.

In case of 2 multi units: the connection pipe has to have the


largest diameter.

System piping (length) limitations

1.5.1.

Piping length restrictions

Make sure to perform the piping installation within the range of the
maximum allowable pipe length, allowable level difference and
allowable length after branching as indicated below. Three patterns
will be discussed, including VRV DX indoor units combined with
Hydrobox units or RA DX indoor units.

There is never a connection of the equalizing pipe with the indoor


units.
Example (free multi combination): RYMQ8+RYMQ12+RYMQ18.
Largest connection is 28.6 (RYMQ18); 22.2 (RYMQ12) and
19.1 (RYMQ8). In figure below only equalizing pipe is shown.

12

Definitions
Actual piping length: pipe length between outdoor(1) and indoor
units.
Equivalent piping length(2): pipe length between outdoor(1) and
indoor units.
Total piping length: total piping length from the outdoor(1) to all indoor units.
Difference in height between outdoor and indoor units: H1.

22.2 mm

28.6 mm

Difference in height between indoor and indoor units: H2.

19.1 mm

Difference in height between outdoor and outdoor units: H3.


Difference in height between outdoor and BP unit: H4.

INFORMATION

Difference in height between BP unit and BP unit: H5.

Reducers or T-joints are field supplied.

Difference in height between BP unit and RA DX indoor unit: H6.

NOTICE
Refrigerant branch kits can only be used with R410A.

INFORMATION
Equalizing pipe for RYMQ has to be connected between
the outdoor modules of multi continuous heating models:
RYYQ22~54 consisting of 2 or 3 RYMQ8~20 modules. The
equalizing pipe should never have a connection to any
indoor unit.

1.5.2.

(1)

If the system capacity is >20HP, re-read "the first outdoor branch as seen
from the indoor unit".
Assume equivalent piping length of refnet joint=0.5 m and refnet
header=1 m (for calculation purposes of equivalent piping length, not for
refrigerant charge calculations).

(2)

System only containing VRV DX indoor units

System setup
Branch with refnet joint and refnet
header

Branch with refnet joint

Branch with refnet header

Single outdoor
i

a
b

a
A

e
D

f
F

7
H2

d
1

e
2

H1 H1

f
3

k
7

H2

H1
b

c
1

e
3

Example 1.2

Example 1.1

f
4

h
7
H2

i
8

Example 1.3

Multi outdoor

Refnet joint

r
u

c
B

d
C

r
u

Refnet header

H3

H3

Indoor unit

e
D

f
E

g
F

Example 2.1

p
8

Outdoor multi
connection
piping kit

H1
G

H3

d
1

e
2

f
3

g
5

h
6

H2

r
u

H1
k
b

c
1

d
2

H1
e

f
4

g
6

7
8

4P329765-1C (3/5)

VRV Systems RXYQ-T

49

Outdoor Unit RXYQ-T

12

Installation

12 - 3 Refrigerant Pipe Selection


RYYQ-T
RXYQ-T
RYMQ-T
Example 3: with standard multi layout

12
r

u
Maximum allowable length

Between outdoor and indoor units (standard multi/free multi combinations)

Actual piping length

165 m/135 m

Example 1.1
unit 8: a+b+c+d+e+f+g+p165 m

Example 1.2
unit 6: a+b+h165 m
unit 8: a+i+k165 m

Example 1.3
unit 8: a+i165 m

Example 2.1
unit 8: a+b+c+d+e+f+g+p135 m
Equivalent length(2)

190 m/160 m

Total piping length

1000 m/500 m

Example 1.1
a+b+c+d+e+f+g+h+i+j+k+l+m+n+p1000 m

Example 2.1
a+b+c+d+e+f+g+h+i+j+k+l+m+n+p500 m

Between outdoor branch and outdoor unit (only in case >20 HP)

Actual piping length

10 m

Example 3
r, s, t10 m; u5 m

Equivalent length

13 m

Maximum allowable height difference


H1

50 m (40 m)(a) (if outdoor is located below indoor units)

H2

30 m

H3

5 m
(a) Conditional extension up till 90 m is possible without additional option kit:
In case the outdoor location is higher than indoor: extension is possible up till
90 m and following 2 conditions must be fulfilled:
Liquid piping size up (see table "Size up").
Dedicated setting on outdoor unit is required (see "[2-49]").
In case the outdoor location is lower than indoor: extension is possible up till 90 m
and following 6 conditions must be fulfilled:
40~60 m: minimum connection ratio connected: 80%.
60~65 m: minimum connection ratio connected: 90%.
65~80 m: minimum connection ratio connected: 100%.
80~90 m: minimum connection ratio connected: 110%.
Liquid piping size up (see table "Size up").
Dedicated setting on outdoor unit is required (see "[2-35]").

a.

The piping length between all indoor to the nearest branch kit is
40 m.
Example: h, I, j p40 m

b.

It is necessary to increase the pipe size of the gas and liquid


piping if the pipe length between the first and the final branch kit
is over 40 m.
If the increased pipe size is larger than the pipe size of the main
pipe, then the pipe size of the main pipe has to be increased as
well.
Increase the pipe size as follows:
9.5 12.7; 12.7 15.9; 15.9 19.1; 19.1 22.2; 22.2
25.4(1); 28.6 31.8(3); 34.9 38.1(3)
Example: unit 8: b+c+d+e+f+g+p90 m and b+c+d+e+f+g
>40 m; increase the pipe size of b, c, d, e, f, g.

Maximum allowable length after branch


The pipe length from the first refrigerant branch kit to the indoor unit
40 m.
Example 1.1: unit 8: b+c+d+e+f+g+p40 m
Example 1.2: unit 6: b+h40 m, unit 8: i+k40 m
Example 1.3: unit 8: i40 m
However, extension is possible if all below conditions are met. In this
case limitation can be extended up to 90 m.

1
b

c
B

d
C

e
D

f
E

g
F

p H1

7
H2

1 Outdoor units
2 Refnet joints (A~G)
3 Indoor unit (1~8)
(1)

If available on the site. Otherwise it cannot be increased.

4P329765-1C (4/5)

50

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

12

Installation

12 - 3 Refrigerant Pipe Selection

RYYQ-T
RXYQ-T
RYMQ-T
c.

d.

When the piping size is increased (step b), the piping length has to be
counted as double (except for the main pipe and the pipes that are not
increased in pipe size).

Example 2: unit 6: b+h40 m, unit 8: i+k40 m

The total piping length has to be within limitations (see table


above).
Example:
a+b*2+c*2+d*2+e*2+f*2+g*2+h+i+j+k+l+m+n+p1000 m
(500 m).

1.5.4.

Example 3: unit 8: i40 m, unit 2: c40 m

12

System containing VRV DX indoor units and RA DX


indoor units

System setup

The piping length difference between the nearest indoor from first branch
to the outdoor unit and farthest indoor to the outdoor unit is 40 m.

Example: The farthest indoor unit 8. The nearest indoor unit 1


(a+b+c+d+e+f+g+p)(a+h)40 m.
1.5.3.

System containing VRV DX indoor units and Hydrobox

H4
e
BP1

System setup
Example 1: Branch with refnet joint.

H5

H1

h
1

a
A

c
B

d
C

e
D

d
1

f
3

k
7

H2

Example 3: Branch with refnet header

c
2

e
3

f
4

g
6

Between outdoor unit and indoor unit.


100 m

Example:
a+b+g+l100 m

Equivalent length(a)

120 m

Total piping length

250 m

Example:
a+b+d+g+l+k+c+e+f+h+i+j250 m

(a) Assume equivalent piping length of refnet joint=0.5 m and refnet header=1 m (for
calculation purposes).

h
7
H2

i
8

Between BP unit and indoor unit.


Indoor unit capacity index

1~7 VRV DX indoor units


8 Hydrobox unit (HXY*)

Maximum allowable length


Between outdoor and indoor units.
Actual piping length

135 m

Example 1:
a+b+c+d+e+f+g+p135 m
a+b+c+d+k135 m

Remark:

Example 2:
a+i+k135 m
a+b+e135 m

Example: a>5 m

Example 3:
a+i135 m
a+d135 m
Equivalent length(a)
Total piping length

160 m
300 m

Actual piping length

H1
1

H6

Header

H2

Maximum allowable length


j

e
2

BP box
1~5 RA DX indoor units
6,7 VRV DX indoor units

b
c

7
H2

7
BP2

H1

Example 2: Branch with refnet joint and refnet header.

H1

g
6

4
G

f
E

Pipe length

<60

2~15 m

60

2~12 m

71

2~8 m

Minimum allowable length between outdoor unit and first refrigerant branch
kit>5 m (the refrigerant noise from the outdoor unit can be transmitted).

Maximum allowable height difference


H1

50 m (40 m) (if outdoor is located below indoor units)

H2

15 m

Example 3:
a+b+c+d+e+f+g+h+i300 m

H4

40 m

H5

15 m

H6

5 m

(a) Assume equivalent piping length of refnet joint=0.5 m and refnet header=1 m (for
calculation purposes).

Maximum allowable height difference (on Hydrobox indoor unit)


H1

50 m (40 m) (if outdoor is located below indoor units)

H2

15 m

Maximum allowable length after branch


The pipe length from the first refrigerant branch kit to the indoor unit 40 m.
Example 1: unit 8: b+c+d+e+f+g+p40 m

Maximum allowable length after branch


The pipe length from the first refrigerant branch kit to the indoor unit 50 m.
Example: b+g+l50 m
If the piping length between the first branch and BP unit or VRV DX indoor unit
is over 20 m, it is necessary to increase the gas and liquid piping size between
the first branch and BP unit or VRV DX indoor unit. If the piping diameter of the
sized up piping exceeds the diameter of the piping before the first branch kit,
than the latter also requires a liquid piping and gas piping size up.

4P329765-1C (5/5)

VRV Systems RXYQ-T

51

Outdoor Unit RXYQ-T

12

Installation

12 - 3 Refrigerant Pipe Selection


RYYQ-T
RYMQ-T
RXYQ-T

VRV4 Heat Pump Field Piping Restrictions (1/3)


Maximum piping length

12

Reference drawing see


page 2/3
Standard
only VRV DX indoor connected
Standard multi combination
Free multi combination
(=all, except standard multi combination)
Hydrobox connection
RA connection
AHU connection

1.





2.
3.






4.
5.
6.
7.

Pair
Multi (6)
Mix (7)

Maximum height difference


Indoor to outdoor (3)
+ RXWGRRUDERYH
Indoor to indoor (H2)
LQGRRU LQGRRUDERYH
outdoor)

Longest pipe
(A+[B,G,E,J])
Actual / (Equivalent)

$IWHUUVWEUDQFK
(B,G,E,J) Actual

$IWHUUVWEUDQFKIRU
outdoor multi (D)
Actual / (Equivalent)

165/(190)m

40m (1)

10/(13)m

50/(40)m (3)

135/(160)m

40m (1)

10/(13)m

50/(40)m (3)

30m

5m

500m

135/(160)m
100/(120)m
50/(55)m (4)
165/(190)m
165/(190)m

40m
50m (2)
40m
40m

10/(13)m
10/13m
10/13m

50/(40)m
50/(40)m
40/(40)m
40/(40)m
40/(40)m

15m
15m
15m
15m

5m
5m
5m

300-500m (5)
250m
1000m
1000m

30m

Outdoor to outdoor
(H3)

5m

NOTES
)RUVWDQGDUGPXOWLFRPELQDWLRQVVHH'
([WHQVLRQLVSRVVLEOHLIDOOEHORZFRQGLWLRQVDUHPHW OLPLWDWLRQFDQEHH[WHQGHGXSWRP
D7KHSLSLQJOHQJWKEHWZHHQDOOLQGRRUWRWKHQHDUHVWEUDQFKNLWLVP
E,WLVQHFHVVDU\WRLQFUHDVHWKHSLSHVL]HRIWKHJDVDQGOLTXLGSLSLQJLIWKHSLSHOHQJWKEHWZHHQWKHUVWDQGWKHQDOEUDQFKNLWLVRYHUP
,IWKHLQFUHDVHGSLSHVL]HLVODUJHUWKDQWKHSLSHVL]HRIWKHPDLQSLSHWKHQWKHSLSHVL]HRIWKHPDLQSLSHKDVWREHLQFUHDVHGDVZHOO
F:KHQWKHSLSLQJVL]HLVLQFUHDVHG E WKHSLSLQJOHQJWKKDVWREHFRXQWHGDVGRXEOH7KHWRWDOSLSLQJOHQJWKKDVWREHZLWKLQOLPLWDLWRQV VHHWDEOHDERYH 
G7KHSLSLQJOHQJWKGLIIHUHQFHEHWZHHQWKHQHDUHVWLQGRRUIURPUVWEUDQFKWRWKHRXWGRRUXQLWDQGIDUWKHVWLQGRRUWRWKHRXWGRRUXQLWLVP
,IWKHSLSLQJOHQJWKEHWZHHQUVWEUDQFKDQG%3ER[RU959LQGRRULVRYHUPLWVQHFHVVDU\WRLQFUHDVHWKHJDVDQGOLTXLGSLSLQJVL]HEHWZHHQUVWEUDQFKDQG%3ER[RU959LQGRRU
([WHQVLRQXSWLOOPLVSRVVLEOHZLWKRXWDGGLWLRQDORSWLRQNLW
-!LQFDVHWKHRXWGRRUORWDWLRQLVKLJKHUWKDQLQGRRUH[WHQVLRQLVSRVVLEOHXSWLOOPXQGHUIROORZLQJFRQGLWLRQV

/LTXLGSLSLQJVL]HXS GHWDLOVLQLQVWDOODWLRQPDQXDO
- Dedicated setting on outdoor unit is required (details in installation manual)
-!LQFDVHWKHRXWGRRUORFDWLRQLVORZHUWKDQLQGRRUH[WHQVLRQLVSRVVLEOHXSWLOOPXQGHUIROORZLQJFRQGLWLRQV

aPPLQLPXPFRQQHFWLRQUDWLRFRQQHFWHG

aPPLQLPXPFRQQHFWLRQUDWLRFRQQHFWHG

aPPLQLPXPFRQQHFWLRQUDWLRFRQQHFWHG

aPPLQLPXPFRQQHFWLRQUDWLRFRQQHFWHG
+

/LTXLGSLSLQJVL]HXS GHWDLOVLQLQVWDOODWLRQPDQXDO
- Dedicated setting on outdoor unit is required (details in installation manual)
7KHDOORZDEOHPLQLPXPOHQJWKLVP
In case of multi connection
8VLQJVHYHUO$+8 (.(;9(.(4NLWV
0L[RI$+8DQG959';LQGRRU

Total Piping Length

1000m

3D079540D

RYYQ-T
RYMQ-T
RXYQ-T

VRV4 Heat Pump Field Piping Restrictions (2/3)


Outdoor

VRV indoor

Hyrdobox
Hydrobox

VRV indoor

NOTES
1. Schematic indication: illustrations may vary from real unit outlook.
2. Displayed system is only to illustrate piping length limitations! Combination of displayed indoor unit types is not allowed. See 3D079543 for allowed combinations.
Allowable piping length

RA connection
AHU connection

Pair
Multi (1)
Mix (2)

BP to RA
(F)
2~15m
-

EXV to AHU
(K)
P
P
P

Max. height difference


BP to RA
(H4)
5m
-

EXV to AHU
(H5)
5m
5m
5m

NOTES
1. Using several AHU (EKEXV + EKEQ - kits)
2. Mix of AHU and VRV DX indoor

3D079540D

52

VRV Systems RXYQ-T

Outdoor Unit RXYQ-T

12

Installation

12 - 3 Refrigerant Pipe Selection

RYYQ-T
RYMQ-T
RXYQ-T

VRV4 Heat Pump Field Piping Restrictions (3/3)


Total

System pattern
Allowed connection ratio (CR)
*Other combinations are N.A.
Only VRV DX indoor
VRV DX indoor + RA DX indoor
Only RA DX indoor
VRV DX indoor + LT hydrobox
VRV DX indoor + AHU (mix)
Only AHU (pair AHU + multi AHU) (4)

1.
2.
3.
4.

capacity
50~130%
80~130%
80~130%
50~130%
50~110% (3)
90~110% (3)

Indoor unit quantity (VRV,


RA, AHU, Hydrobox)
(excl. BP box and EXV kits
Max. 64
Max. 32 (1)
Max. 32 (1)
Max. 32
Max. 64 (2)
Max. 64 (2)

Allowable capacity
VRV DX indoor

RA DX indoor

Hydrobox

AHU

50~130%
0~130%
50~130%
50~110%
-

0~130%
80~130%
-

0~80%
-

0~110%
90~110%

12

NOTES
There is no restriction for the number of connectable BP boxes
When using AHU connection: see EKEXV kit as an indoor unit for counting the total number of indoor units
Restrictions by air handling unit capacity
Pair AHU = system with 1 AHU connected to one outdoor unit / Multi AHU = system with several AHU connected to 1 outdoor unit system

SPECIAL INFORMATION REGARDING VENTILATION APPLICATIONS


I. FXMQ_MF model is considered as an AHU, following AHU limitations and respecting additional limitations:

0D[LPXP);04B0)FRQQHFWLRQUDWLR &5 ZKHQFRPELQHGZLWK959';LQGRRUXQLWV&5

0D[LPXP);04B0)FRQQHFWLRQUDWLR &5 ZKHQRQO\$+8LVXVHG&5

RSHUDWLRQUDQJHLQIRUPDWLRQVHHVSHFLFDWLRQVRI);04B0)XQLW
II. Biddle aircurtain is considered as an AHU, following AHU limitations

RSHUDWLRQUDQJHLQIRUPDWLRQVHHVSHFLFDWLRQVRI%LGGOHXQLW
III. (EKEXV + EKEQ) combined with AHU is considered as an AHU, following AHU limitations

RSHUDWLRQUDQJHLQIRUPDWLRQVHHVSHFLFDWLRQVRI(.(;9(.(4XQLW
IV. VKM is considered to be a regular VRV DX indoor unit

RSHUDWLRQUDQJHLQIRUPDWLRQVHHVSHFLFDWLRQVRI9.0XQLW
V. VAM does not have limitations on connection as there is no refrigerant connection with the outdoor unit (only communication F1/F2; so counting in # indoor units)

3D079540D

VRV Systems RXYQ-T

53

Outdoor Unit RXYQ-T

13

Operation range

13 - 1 Operation Range
RYYQ-T
RYMQ-T
RXYQ-T
RXYQQ-T

+HDWLQJ

&RROLQJ

,QGRRUWHPSHUDWXUH &:%

2SHUDWLRQUDQJH

5DQJHIRUSXOOGRZQRSHUDWLRQ

2XWGRRUWHPSHUDWXUH &:%

5DQJHIRUSXOOGRZQRSHUDWLRQ

2SHUDWLRQUDQJH

2XWGRRUWHPSHUDWXUH &'%

13

,QGRRUWHPSHUDWXUH &'%

NOTES

1. 7KHVHJXUHVDVVXPHWKHIROORZLQJRSHUDWLRQFRQGLWLRQV
,QGRRUDQGRXWGRRUXQLWV
(TXLYDOHQWSLSHOHQJWKP
/HYHOGLIIHUHQFHP
2. 'HSHQGLQJRQRSHUDWLRQDQGLQVWDOODWLRQFRQGLWLRQVWKHLQGRRUXQLWFDQFKDQJHRYHUWRIUHH]HXSRSHUDWLRQ LQGRRUGHLFLQJ 
3. 7RUHGXFHWKHIUHH]HXSRSHUDWLRQ LQGRRUGHLFLQJ IUHTXHQF\LWLVUHFRPPHQGHGWRLQVWDOOWKHRXWGRRUXQLWLQDORFDWLRQQRWH[SRVHGWRZLQG
4. 2SHUDWLRQUDQJHLVYDOLGLQFDVHGLUHFWH[SDQVLRQLQGRRUXQLWVDUHXVHG,QFDVHVSHFLDOLQGRRUXQLWVDUHXVHG HJ+\GURER[ UHIHUWRWHFKQLFDOVSHFV
RIGHGLFDGHGXQLW

54

VRV Systems RXYQ-T

3D079544

The present leaflet is drawn up by way of information only and does not
constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V.
has compiled the content of this leaflet to the best of its knowledge. No
express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products
and services presented therein. Specifications are subject to change
without prior notice. Daikin Europe N.V. explicitly rejects any liability for
any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V.

BARCODE

Daikin products are distributed by:

Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende

EEDEN15-200_1A 03/15 Copyright Daikin


The present publication supersedes EEDEN14-200_1

Daikin Europe N.V. participates in the Eurovent Certification programme for Liquid
Chilling Packages (LCP), Air handling units
(AHU), Fan coil units (FCU) and variable refrigerant flow systems (VRF) Check ongoing
validity
of
certificate
online:
www.eurovent-certification.com or using:
www.certiflash.com

You might also like