ALARM

PUMP ROOM SUBMERSIBLE PUMPS


ON/OFF TRIP STATUS
AUTO-MANUAL-OFF STATUS
CHEMICAL HOLDING TANKS PUMPS
ON/OFF TRIP STATUS
AUTO-MANUAL-OFF STATUS
SUMPIT PUMP ROOM
LOW LEVEL STATUS
HIGH LEVEL STATUS
DIESEL FUEL DAY TANK
LOW LEVEL STATUS
HIGH LEVEL STATUS
DIESEL FUEL STORAGE
LOW LEVEL STATUS
HIGH LEVEL STATUS
DIESEL FUEL TRANSFER PUMPS
ON/OFF TRIP STATUS
AUTO-MANUAL-OFF STATUS
PUMP ROOM SPACE HEATER
ON/OFF TRIP STATUS
AUTO-MANUAL-OFF STATUS
ON-OFF COMMAND
ROOM TEMPERATURE SATUS AND SET POINT
TRANSFORMER
ON/OFF TRIP STATUS ACB
HIGH PRESSURE SF-6
LOW PRESSURE SF-6
HIGH OIL TEMEPRATURE
MV IMCOMMER CIRCUIT BRAKER OPEN/CLOSE STATUS
MV IMCOMMER CIRCUIT BRAKER EARTHING OPEN/CLOSE STATUS
MV OUT-GOING CIRCUIT BRAKER OPEN/CLOSE STATUS
MV OUT-GOING CIRCUIT BRAKER EARTHING OPEN/CLOSE STATUS
MV CIRCUIT BREAKER OPNE CLOSE STATUS
MV CIRCUIT BREAKER EARTHING OPNE CLOSE STATUS
POTABLE WATER PUMPS
ON/OFF TRIP STATUS
AUTO-MANUAL-OFF STATUS
PRESSURE STATUS
DRY RUN ALARM

VFD ON-OFF & FAILURE STATUS


FIRE PUMPS
ON/OFF TRIP STATUS
AUTO-MANUAL-OFF STATUS
PRESSURE STATUS
MAIN BUTTER FLY VALVE STATUS
PHASE FAILURE & COMMON ALARM
JOKEY PUMO
ON/OFF TRIP STATUS
AUTO-MANUAL-OFF STATUS
PRESSURE STATUS
FIRE ALARM CHECK VALVE
PRESSURE SWITVH ALARM
SPRINKLER FLOW SWITCHES
FLOW STATUS
FIRE WATER TANK
LOW LEVEL STATUS
HIGH LEVEL STATUS
UNDERGROUND WATER TANK
LOW LEVEL STATUS
HIGH LEVEL STATUS
UNDERGROUND CHEMICAL HOLDING TANK
LOW LEVEL STATUS
HIGH LEVEL STATUS
CCTV
POWER SUPPLY STATUS
ACCESS CONTROL SYSTEM
POWER SUPPLY STATUS
CLOCK SYSTEM
POWER SUPPLY STATUS
ELECTRICAL PANNEL POWER METER
MODBUS STATUS
UPS
MODBUS STATUS
GENERATOR

MODBUS STATUS
SPLIT AIR-CONDITIONERS
ON/OFF TRIP STATUS
ON-OFF COMMAND
FIRE ALARM PANNEL
FIRE ALRAM STATUS
COMMON FAULT
EXHAUST FANS -A
EF-DC-01-A1, EF-DC-01-A2, DC-02-A, EF-DC-03-A1, EF-DC-03-A2,
EF-01-A, EF-02-A, EF-03-A, EF-04-A.
ON/OFF TRIP STATUS
AUTO-MANUAL-OFF STATUS
ON-OFF COMMAND
FAN AIR FLOW STATUS
EXHAUST FANS-B
EF-DC-01-B1, EF-DC-01-B2, DC-02-B, EF-DC-03-B1, EF-DC-03-B2,
EF-01-B, EF-02-B, EF-03-B, EF-04-B.
ON/OFF TRIP STATUS
AUTO-MANUAL-OFF STATUS
ON-OFF COMMAND
FAN AIR FLOW STATUS
EXHAUST FANS-COMMON
EF-05, EF-06, EF,07
ON/OFF/TRIP STATUS
AUTO-MANUAL-OFF STATUS
ON-OFF COMMAND
DESERT COOLERS-A
DC-01-A, DC-02-A, DC-03-A
SUPPY AIR TEMPERATURE STATUS
FAN CONTROL/MONITORING
FAN AIR FLOW STATUS
FAN RUN STATUS
ON-OFF COMMAND
ON/OFF/TRIP STATUS
AUTO-MANUAL-OFF STATUS
FILTER MONITORING
FILTER STATUS
WATER PUMP CONTROL & STATUS
ON/OFF TRIP STATUS
ON-OFF COMMAND
WATER BLEEDER
ON-OFF COMMAND

DESERT COOLER HEATER


ON-OFF STATUS STAGE-1
ON-OFF STATUS STAGE-2
HEATER TRIP STATUS (ALL STAGES)
THERMAL TRIP STATUS (AUTO RESET)
THERMAL TRIP STATUS (MANUAL RESET)
AIR FLOW STATUS
DESERT COOLERS-B
DC-01-B, DC-02-B, DC-03-B
SUPPY AIR TEMPERATURE STATUS
FAN CONTROL/MONITORING
FAN AIR FLOW STATUS
FAN RUN STATUS
ON-OFF COMMAND
ON/OFF/TRIP STATUS
AUTO-MANUAL-OFF STATUS
FILTER MONITORING
FILTER STATUS
WATER PUMP CONTROL & STATUS
ON/OFF TRIP STATUS
ON-OFF COMMAND
WATER BLEEDER
ON-OFF COMMAND
DESERT COOLER HEATER
ON-OFF STATUS STAGE-1
ON-OFF STATUS STAGE-2
HEATER TRIP STATUS (ALL STAGES)
THERMAL TRIP STATUS (AUTO RESET)
THERMAL TRIP STATUS (MANUAL RESET)
AIR FLOW STATUS
VARIABLE AIR VOLUME-A
SUPPLY AIR DAMPER CONTROL AD POSITION
ROOM TEMPERATURE STATUS AND SET POINT
VAV HEATER
ON-OFF COMMAND
ON-OFF STATUS STAGE-1
ON-OFF STATUS STAGE-2
THERMAL TRIP STATUS (AUTO RESET)
THERMAL TRIP STATUS (MANUAL RESET)
AIR FLOW STATUS
VARIABLE AIR VOLUME-B
SUPPLY AIR DAMPER CONTROL AD POSITION
ROOM TEMPERATURE STATUS AND SET POINT
VAV HEATER
ON-OFF COMMAND

ON-OFF STATUS STAGE-1


ON-OFF STATUS STAGE-2
THERMAL TRIP STATUS (AUTO RESET)
THERMAL TRIP STATUS (MANUAL RESET)
AIR FLOW STATUS
NOVEC SYSTEM-A
NOVECT SYSTEM ALARM STATUS
FIRE & SMOKE DAMPER OPEN/CLOSE STATUS (SUPPLY & RETURN)
NOVEC SYSTEM-B
NOVECT SYSTEM ALARM STATUS
FIRE & SMOKE DAMPER OPEN/CLOSE STATUS (SUPPLY & RETURN)
STEAM HUMIDIFIERS-A
ON-OFF COMMAND
ON-OFF AND TRIP STATUS
CAPACITY CONTROL
STEAM HUMIDIFIERS-B
START STOP COMMAND
ON-OFF AND TRIP STATUS
CAPACITY CONTROL

QTY
2

DI

DO

AI

4
4
2
4
4
1
1
1
1
1
1
1
1
1
1
2
2

2
2
1
1
2
4
2
2
2
1
1
1
1
2
2
3
6
6
1
1

AO

2
2
4
4
2
2
4
1
2
2
1
2
2
8
8
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
MODBUS
1
MODBUS
1

MODBUS
8
16
8
2
2
2

9
18
18
9
DPS400

9
18
18
9
DPS400

3
6
6
3

3
3
3
3
3
6
6
3
6
3
3

3
3
3
3
3
3

3
3
3
3
3
6
6
3
6
3
3
3
3
3
3
3
3
38
38
35
38
38
38
38
38
38
38
38
35
38

38
38
38
38
38
3
3
6
3
3
6
4
4
8
4
4
4
8
4

DESCRIPTION
1-C

FIELD
DEVICES

POTABLE WATER PUMPS


ON/OFF TRIP STATUS
AUTO-MANUAL-OFF STATUS
PRESSURE STATUS
DRY RUN ALARM
VFD ON-OFF & FAILURE STATUS

2-C

FIRE PUMPS
ON/OFF TRIP STATUS
AUTO-MANUAL-OFF STATUS
PRESSURE STATUS
MAIN BUTTER FLY VALVE STATUS
PHASE FAILURE & COMMON ALARM

3-C

JOCKEY PUMP
ON/OFF TRIP STATUS
AUTO-MANUAL-OFF STATUS
PRESSURE STATUS

4-C

UNDERGROUND WATER TANK


LOW LEVEL STATUS
HIGH LEVEL STATUS

5-C

LS-TM
LS-TM

SUMP PIT SUBMERSIBLE PUMPS


ON/OFF TRIP STATUS
AUTO-MANUAL-OFF STATUS

6-C

SUMP PIT PUMP ROOM


LOW LEVEL STATUS
HIGH LEVEL STATUS

7-C

LS-TM
LS-TM

HOLDING TANK PUMPS


ON/OFF TRIP STATUS
AUTO-MANUAL-OFF STATUS

8-C

HOLDING TANK
LOW LEVEL STATUS
HIGH LEVEL STATUS

9-C

DIESEL FUEL TRANSFER PUMPS


ON/OFF TRIP STATUS
AUTO-MANUAL-OFF STATUS

LS-TM
LS-TM

DESCRIPTION

FIELD
DEVICES

10-C DIESEL FUEL DAY TANK


LOW LEVEL STATUS
HIGH LEVEL STATUS
11-C DIESEL FUEL STORAGE
LOW LEVEL STATUS
HIGH LEVEL STATUS
12-C PUMP ROOM SPACE HEATER
ON/OFF TRIP STATUS
AUTO-MANUAL-OFF STATUS
ON-OFF COMMAND
ROOM TEMPERATURE SATUS AND SET POINT
13-C TRANSFORMER
ON/OFF TRIP STATUS ACB
HIGH PRESSURE SF-6
LOW PRESSURE SF-6
HIGH OIL TEMPERATURE
MV INCOMER CIRCUIT BREAKER OPEN/CLOSE STATUS
MV INCOMER CIRCUIT BREAKER EARTHLING OPEN/CLOSE STATUS
MV OUT-GOING CIRCUIT BREAKER OPEN/CLOSE STATUS
MV OUT-GOING CIRCUIT BREAKER EARTHLING OPEN/CLOSE STATUS
MV CIRCUIT BREAKER OPEN CLOSE STATUS
MV CIRCUIT BREAKER EARTHLING OPEN CLOSE STATUS
14-C CCTV
POWER SUPPLY STATUS
15-C ACCESS CONTROL SYSTEM
POWER SUPPLY STATUS
16-C CLOCK SYSTEM
POWER SUPPLY STATUS
17-C UPS
MODBUS STATUS
18-C GENERATOR
MODBUS STATUS

LS-TM
LS-TM

DESCRIPTION

FIELD
DEVICES

19-C EXHAUST FANS-COMMON


EF-05, EF-06, EF,07
ON/OFF/TRIP STATUS
AUTO-MANUAL-OFF STATUS
ON-OFF COMMAND
AIR FLOW STATUS
20-C SPLIT AIR-CONDITIONERS
ON/OFF TRIP STATUS
ON-OFF COMMAND

DPS-400

DEVICES
QTYS

EQUIP. QTY

DI

DO

AI

3
6
6
1
1
2
2
4
4
2
2
4
1
2
2
1
1
2
1

2
1
2
4
4
1

1
1

1
1
2
4
4
1

1
1

1
1
1
2
2

AO

DEVICES
QTYS

EQUIP. QTY

DI

DO

AI

1
1
1
1
1
1

1
1

2
2
1
1
2
4
2
2
2
1
1
1
1
2
2
1
1
1
1
1
1
1
MODBUS
1
MODBUS

AO

DEVICES
QTYS

EQUIP. QTY

DI

DO

3
6
6
3
3
2
4
2

AI

AO

DESCRIPTION
1-B

FIELD
DEVICES

FIRE ALARM CHECK VALVE


PRESSURE SWITCH ALARM

2-B

SPRINKLER FLOW SWITCHES


FLOW STATUS

3-B

ELECTRICAL PANEL POWER METER (MDP)


MODBUS STATUS

4-B

SPLIT AIR-CONDITIONERS
ON/OFF TRIP STATUS
ON-OFF COMMAND

5-B

FIRE ALARM PANEL


FIRE ALARM STATUS
COMMON FAULT

6-B

7-B

8-B

EXHAUST FANS-(B) PART-1


EF-01-B, EF-02-B, EF-03-B, EF-04-B.
ON/OFF TRIP STATUS
AUTO-MANUAL-OFF SELECTOR SWITCH STATUS
ON-OFF COMMAND
FAN AIR FLOW STATUS

DPS400

EXHAUST FANS-(B) PART-2


EF-DC-01-B1, EF-DC-01-B2, DC-02-B, EF-DC-03-B1, EF-DC-03-B2,
ON/OFF TRIP STATUS
AUTO-MANUAL-OFF SELECTOR SWITCH STATUS
ON-OFF COMMAND
FAN AIR FLOW STATUS

DPS400

DESERT COOLERS
DC-01-B, DC-02-B, DC-03-B
SUPPLY AIR TEMPERATURE STATUS

LF-20

FAN AIR FLOW STATUS


FAN RUN STATUS
ON-OFF COMMAND
ON/OFF/TRIP STATUS
AUTO-MANUAL-OFF SELECTOR SWITCH STATUS

DPS400

FILTER STATUS

DPS400

FAN CONTROL/MONITORING

FILTER MONITORING

DESCRIPTION

FIELD
DEVICES

WATER PUMP CONTROL & STATUS


ON/OFF TRIP STATUS
ON-OFF COMMAND
WATER BLEEDER
ON-OFF COMMAND
DESERT COOLER HEATER
ON-OFF STATUS STAGE-1
ON-OFF STATUS STAGE-2
HEATER TRIP STATUS (ALL STAGES)
THERMAL TRIP STATUS (AUTO RESET)
THERMAL TRIP STATUS (MANUAL RESET)
AIR FLOW STATUS
9-B

VARIABLE AIR VOLUME


SUPPLY AIR DAMPER CONTROL AND POSITION
ROOM TEMPERATURE STATUS AND SET POINT

PVBB4022AS
TR71/U

VAV HEATER
ON-OFF COMMAND
ON-OFF STATUS STAGE-1
ON-OFF STATUS STAGE-2
THERMAL TRIP STATUS (AUTO RESET)
THERMAL TRIP STATUS (MANUAL RESET)
AIR FLOW STATUS
10-B NOVEC SYSTEM
NOVEC SYSTEM ALARM STATUS
FIRE & SMOKE DAMPER OPEN/CLOSE STATUS (SUPPLY & RETURN)
11-B PACKAGE AIR-CONDITIONING UNITS
PACU-2, PACU-4, PACU-6, PACU-8
ON-OFF-TRIP STATUS
ON-OFF COMMAND
TEMPERATURE CONTROLS AND STATUS
OUTSIDE AIR TEMPERATURE AND HUMIDITY STATUS
SUPPLY AIR TEMPERATURE A, HUMIDITY STATUS & SETTING
RETURN AIR TEMPERATURE AND HUMIDITY STATUS
MIXED AIR TEMPERATURE AND HUMIDITY STATUS
SUPPLY FAN CONTROL AND MONITOR
FAN AIR FLOW STATUS
ON/OFF/TRIP STATUS
FILTER MONITOR
PRE-FILTER STATUS

S10010

DESCRIPTION
BAG-FILTER STATUS
HEATER CONTROL AND MONITORING
ON/OFF/TRIP STATUS
STAGE STATUS
DAMPER CONTROLS
FREAH AIR DAMPER POSITION
RETURN AIR DAMPER POSITION
EXHAUST AIR DAMPER POSITION
SMOKE DETECTOR
SUPPLY AIR SMOKE DETECTOR STATUS
12-B STEAM HUMIDIFIERS
START STOP COMMAND
ON-OFF AND TRIP STATUS
CAPACITY CONTROL

FIELD
DEVICES

DEVICES
QTYS

EQUIP. QTY

DI

DO

AI

1
1
4
4
1
MODBUS
3
6
3
1
1
1

4
8
8
4
4

5
10
10
5
5

3
3

3
3
3
6
6

AO

DEVICES
QTYS

EQUIP. QTY

DI

DO

AI

AO

6
3
3
3
3
3
3
3
3
38
38
35

38
35
38
38
38
38
38
38
3
3
6

6
4

8
4
4
4
4
4
4
8
4

DEVICES
QTYS

EQUIP. QTY

DI

DO

AI

AO

4
8
4
4
4
4
4
4
4
8
4

DESCRIPTION
1-A

FIELD
DEVICES

FIRE ALARM CHECK VALVE


PRESSURE SWITCH ALARM

2-A

SPRINKLER FLOW SWITCHES


FLOW STATUS

3-A

ELECTRICAL PANEL POWER METER-(MDP)


MODBUS STATUS

4-A

SPLIT AIR-CONDITIONERS
ON/OFF TRIP STATUS
ON-OFF COMMAND

5-A

FIRE ALARM PANEL


FIRE ALRAM STATUS
COMMON FAULT

6-A

7-A

8-A

EXHAUST FANS. PART-1


EF-01-A, EF-02-A, EF-03-A, EF-04-A.
ON/OFF TRIP STATUS
AUTO-MANUAL-OFF SELECTOR SWITCH STATUS
ON-OFF COMMAND
FAN AIR FLOW STATUS

DPS400

EXHAUST FANS. PART-2


(DELETED FROM ROW)
EF-DC-01-A1, EF-DC-01-A2, DC-02-A, EF-DC-03-A1, EF-DC-03-A2.
ON/OFF TRIP STATUS
AUTO-MANUAL-OFF SELECTOR SWITCH STATUS
ON-OFF COMMAND
FAN AIR FLOW STATUS

DPS400

DESERT COOLERS.
DC-01-A, DC-02-A, DC-03-A

(DELETED FROM ROW)


SUPPLY AIR TEMPERATURE STATUS

LF-20

FAN AIR FLOW STATUS


FAN RUN STATUS
ON-OFF COMMAND
ON/OFF/TRIP STATUS
AUTO-MANUAL-OFF SELECTOR SWITCH STATUS

DPS400

FILTER STATUS

DPS400

FAN CONTROL/MONITORING

FILTER MONITORING

DESCRIPTION

FIELD
DEVICES

WATER PUMP CONTROL & STATUS


ON/OFF TRIP STATUS
ON-OFF COMMAND
WATER BLEEDER
ON-OFF COMMAND
DESERT COOLER HEATER
ON-OFF STATUS STAGE-1
ON-OFF STATUS STAGE-2
HEATER TRIP STATUS (ALL STAGES)
THERMAL TRIP STATUS (AUTO RESET)
THERMAL TRIP STATUS (MANUAL RESET)
AIR FLOW STATUS
9-A

VARIABLE AIR VOLUME


SUPPLY AIR DAMPER CONTROL AD POSITION
ROOM TEMPERATURE STATUS AND SET POINT

PVBB4022AS
TR71/U

VAV HEATER
ON-OFF COMMAND
ON-OFF STATUS STAGE-1
ON-OFF STATUS STAGE-2
THERMAL TRIP STATUS (AUTO RESET)
THERMAL TRIP STATUS (MANUAL RESET)
AIR FLOW STATUS
10-A NOVEC SYSTEM
NOVEC SYSTEM ALARM STATUS
FIRE & SMOKE DAMPER OPEN/CLOSE STATUS (SUPPLY & RETURN)
11-A PACKAGE AIR-CONDITIONING UNITS
PACU-1, PACU-3, PACU-5, PACU-7
ON-OFF-TRIP STATUS
ON-OFF COMMAND
TEMPERATURE CONTROLS AND STATUS
OUTSIDE AIR TEMPERATURE AND HUMIDITY STATUS
SUPPLY AIR TEMPERATURE A, HUMIDITY STATUS & SETTING
RETURN AIR TEMPERATURE AND HUMIDITY STATUS
MIXED AIR TEMPERATURE AND HUMIDITY STATUS
SUPPLY FAN CONTROL AND MONITOR
FAN AIR FLOW STATUS
ON/OFF/TRIP STATUS
FILTER MONITOR
PRE-FILTER STATUS
BAG-FILTER STATUS

S10010

DESCRIPTION
HEATER CONTROL AND MONITORING
ON/OFF/TRIP STATUS
STAGE STATUS
DAMPER CONTROLS
FREAH AIR DAMPER POSITION
RETURN AIR DAMPER POSITION
EXHAUST AIR DAMPER POSITION
SMOKE DETECTOR
SUPPLY AIR SMOKE DETECTOR STATUS
12-A STEAM HUMIDIFIERS
ON-OFF COMMAND
ON-OFF AND TRIP STATUS
CAPACITY CONTROL

FIELD
DEVICES

DEVICES
QTYS

EQUIP. QTY

DI

DO

AI

1
1
4
4
1
MODBUS
3
6
3
1
1
1

4
8
8
4
4

5
10
10
5
5

3
3

3
3
3
6
6

AO

DEVICES
QTYS

EQUIP. QTY

DI

DO

AI

AO

6
3
3
3
3
3
3
3
3
38
38
35

38
35
38
38
38
38
38
38
3
3
6

6
4

8
4
4
4
4
4
4
8
4
4

DEVICES
QTYS

EQUIP. QTY

DI

DO

AI

AO

8
4
4
4
4
4
4
4
8
4