Modbus Manual v1.7
Modbus Manual v1.7
User Manual APM, ITA 30 - 40kVA, EPM, NX, NXC 30 - 40kVA And NXr Series UPS
Contents
Chapter 1 Product Description ............................................................................................................................................ 1
1.1 Introduction ........................................................................................................................................................... 1
1.2 Specifications And Features ................................................................................................................................. 1
1.3 Appearance And Hardware Description................................................................................................................ 1
Chapter 2 Installation .......................................................................................................................................................... 3
2.1 Unpacking Inspection............................................................................................................................................ 3
2.2 Installation Notes .................................................................................................................................................. 3
2.3 Installation Procedures ......................................................................................................................................... 3
2.3.1 Setting Basic Parameters .......................................................................................................................... 3
2.3.2 Plugging In Adapter ................................................................................................................................... 5
2.3.3 Connecting Communication Cable ............................................................................................................ 5
2.3.4 Setting Communication Parameters In Host Software............................................................................... 6
Chapter 3 Protocol Text ...................................................................................................................................................... 7
3.1 Protocol Text Of UL33 UPS .................................................................................................................................. 7
3.2 Protocol Text Of UH31 UPS ............................................................................................................................... 10
3.3 Protocol Text Of UH11 UPS ............................................................................................................................... 12
3.4 Protocol Text Of iTrust 2G UPS .......................................................................................................................... 13
3.5 Protocol Text Of iTrust Adapt 5/10kVA UPSs ..................................................................................................... 15
3.6 Protocol Text Of NXa, NXb, NXe UPSs .............................................................................................................. 16
3.7 Protocol Text Of Hipulse U UPS And FLP .......................................................................................................... 20
3.8 Protocol Text Of iTrust Adapt 16/20kVA UPS ..................................................................................................... 23
3.9 Protocol Text Of APM 150 UPS .......................................................................................................................... 27
3.10 Protocol Text Of NXr / APM300/EPM UPSs ..................................................................................................... 33
3.11 Protocol Text Of APL(NXp) UPS....................................................................................................................... 37
3.12 ITA/NXC 30/40k UPS........................................................................................................................................ 43
3.13 Protocol Text Of APS UPS ............................................................................................................................... 47
3.14 Protocol Text Of GXE 1-10kVA UPS ................................................................................................................ 52
Chapter 4 Troubleshooting................................................................................................................................................ 54
UL33 UPS
UH31 UPS
UH11 UPS
ITrust 2G UPS
NXa UPS
NXb UPS
NXe UPS
Equipment series
ITrust series
NX series
10
FLP120/160/200/300/400 kVA
FLP series
11
NXr UPS
NXr series
12
13
14
APL UPS
15
EPM
16
ITA/NXC 30/40K
17
APS
18
GXE 1-10K
Hipulse U series
User Manual
DIP switch
Communication port
Figure 1-1
Adapter appearance
Hardware description
The printed board of the adapter is available in two sizes: 130mm (L) 60mm (W) 1.6mm (H) and 130mm (L)
63mm (W) 1.6mm (H); additionally, the former has a narrow opening at the plug-in connector. The former is
applicable to NX, NXr series UPS, iTrust Adapt UPS and APM 150 UPS, while the latter is applicable to Hipulse U
series UPS, FLP, and all iTrust series UPS except for iTrust Adapt UPS.
As shown in Figure 1-1, the adapter provides communication port, equipment communication LED, host
communication LED, plug-in connector and DIP switch, which are described in Table 1-2.
Table 1-2
Hardware description
Name
Communication port
Description
Connects to the host computer, supports RS232 and RS485 communication modes
OFF: power off
equipment communication
LED (yellow)
ON: power on, but communication with UPS or FLP not established
Flash slowly (once per 5s): communication with UPS or FLP failed
Flash quickly (about once per 1s): communication with UPS or FLP is normal
Flash: communication with host computer being normal
Plug-in connector
Plug in the SNMP slot of the UPS or FLP, connect to the UPS or FLP
DIP switch
Warning
All external ports of the adapter must connect to SELV circuit. Failure to observe this could cause damage to the adapter.
User Manual
Chapter 2 Installation
Chapter 2 Installation
2.1 Unpacking Inspection
Unpack the adapter, take out the delivery list (see Table 2-1), and check the goods against it. Should there be any
discrepancy, contact the distributor immediately.
Table 2-1
S/N.
Goods
Qty.
Remark
1
2
Adapter
CD
1 pcs
1 pcs
ON
Figure 2-1
DIP switch
The basic parameters of the adapter are set by Bits 1~7 of the DIP switch, Bit 8 is factory reserved. The setting
shown in Figure 2-1 is the factory default.
User Manual
Chapter 2 Installation
Setting physical address
The physical address of the adapter is set by Bits 1~5. The setting range is 1~31, 0 is factory-reserved setting, 1 is
the factory default.
The physical address setting method is shown in Table 2-2:
Table 2-2
Physical address
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Warning
The physical address 0 is factory reserved. You shall not set the physical address to 0; otherwise, the adapter cannot operate
normally.
Setting communication baud rate
The communication baud rate of the adapter is set by Bits 6~7, and can be set to 2400bps, 4800bps, 9600bps, or
19200bps. 9600bps is the factory default.
The communication baud rate setting method is shown in Table 2-3:
Table 2-3
Bit 6
Bit 7
2400
4800
9600
19200
OFF
ON
OFF
ON
OFF
OFF
ON
ON
User Manual
Chapter 2 Installation
Note
The adapter is hot-pluggable. You can install the adapter with shutting down the UPS or FLP.
User the following steps to plug the adapter in the SNMP slot of the UPS or FLP:
1. Remove the SNMP slot cover on the rear panel of the UPS or FLP.
Retain the SNMP slot cover and the screws for use in the future. Refer to the corresponding UPS or FLP user manual
for the location of the SNMP slot.
2. Align the plug-in connector of the adapter with the SNMP slot, plug the adapter into the slot along the grooves on
both sides of the slot, then fix the adapter through the fixing holes on the adapter panel.
More than ten seconds later, you will see the yellow equipment communication LED on the adapter panel flash
quickly, indicating that the adapter has started to operate normally and the communication between the adapter and
the UPS or FLP has been established.
Note
Figure 2-2
Communication port
As shown in the figure, the four terminals on the left are for RS485 communication, while the three ones on the right
are for RS232 communication. The terminals are described in Table 2-4.
Table 2-4
Terminal
T+
TTx
Rx
GND
Description
RS485 communication differential signal+, 2 terminals, shorted internally, used for cascade connection
RS485 communication differential signal -, 2 terminals, shorted internally, used for cascade connection
Transmit terminal of RS232 communication signal
Receive terminal of RS232 communication signal
Signal ground
Tx
Rx
GND
Pin 2
Pin 3
Pin 5
User Manual
Chapter 2 Installation
2. RS485 communication
Where RS485 communication is used, please provide an RS232-to-RS485 converter for yourself, and make the
connection between the adapter and the computer using the method shown in Table 2-6 and Table 2-7. For details of
the communication ports of the RS232-to-RS485 converter, please refer to the user manual of the converter.
Table 2-6
T+
TTable 2-7
Pin 2
Pin 3
Pin 5
Warning
RS232 communication and RS485 communication cannot be used at the same time.
User Manual
Note
1. The adapter provides answer only to the #03 query command. It will not answer the query commands of other function codes.
2. When the adapter answers the #03 query command, it will return invalid data address information, with abnormal code #02, if
the required byte of answer information is bigger than 100.
3. In communication through JBUS/MODBUS(RTU) protocol, the adapter is passive, waiting for the host monitoring software to
query it.
The following sections provide the JBUS/MODBUS (RTU) protocol texts of various UPSs or FLPs.
Byte
Item
UPS name
UPS firmware release
Manufacturer
Adapter firmware release
Value
"UL33 0200L"
0x010B corresponds to V1.11
"EmersonNetworkPower "
0x010B corresponds to V1.11
Bit 0
Bit 1
Bit 2
Item
UPS alarm flag
Adapter communication failure flag
Not defined
Value
0: Normal; 1: Alarm
0: Normal; 1: Fault
Bit 3
Synchronization/Unsynchronization
Bits 5/4
Mains voltage
Bit 6
Bit 7
Rectifier
Inverter
Bits 9/8
Bits 12~10
Bits 15~13
Not defined
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Mains frequency
Input transformer over-temperature
Output transformer over-temperature
Inverter SCR damaged
Bypass SCR damaged
User operation error
10
2
20
2
1030
1031
Bit
User Manual
0: Normal
1: Unsynchronization
00: Normal
01: Abnormal
10:Undervoltage
0: Normal; 1: Fault
0: Normal; 1: Fault
00: Normal
01: Outside synchronization range
10: Outside protection range
000: Normal
001: No battery
010: Below lower limit (EOD point)
011: Above upper limit (voltage too high)
100: Battery reverse connection
101: Pre-alarm
0: Normal;
1: need replacement
0: Normal; 1: Abnormal
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
1031
1032
1033
1034
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit
Item
Inverter heatsink over-temperature
Rectifier heatsink over-temperature
Inverter fan failure
Rectifier fan fault
Battery contactor fault
Rectifier input contactor abnormal
Auxiliary contactor abnormal
Input fuse blowout
Output fuse blowout
Module output overload
Parallel system overload
Module overload timeout
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bits 15/14
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bits 15~8
User Manual
Value
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Failed
0: Normal; 1: Failed
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Overload
0: Normal; 1: Overload
0: Normal; 1: Overload timeout
0: Normal;
1: Over-current timeout
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
1040
1041
Bit
Item
Bits 2/1/0
Operation mode
Bit 3
Bits 5/4
Boost/float charge
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Turn-on/off
Generator connection
Input breaker state
Manual bypass breaker state
Automatic bypass breaker state
Output breaker state
Generator operation status
Module output inhibited
Parallel system output inhibited
Not defined
Bits 2/1/0
UPS property
Bits 15~3
Not defined
Value
000: Neither Normal nor Battery mode
001: Normal mode
010: Battery mode
011: Bypass mode
100: Source share mode
0: Not under test; 1: Under test
00: Float charge;
01: Boost charge;
10: Not charging
0: Turn-on; 1: Turn-off
0: Connected; 1: Not connected
0: Open; 1: Closed
0: Open; 1: Closed
0: Open; 1: Closed
0: Open; 1: Closed
0: Not in operation;1: In operation
0: Yes; 1: No
0: Yes; 1: No
Byte
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Item
AC input phase voltage A
AC input phase voltage B
AC input phase voltage C
AC output phase voltage A
AC output phase voltage B
AC output phase voltage C
AC output current A
AC output current B
AC output current C
DC input voltage (battery voltage)
Output frequency (3 phases the same)
AC input line voltage AB
AC input line voltage BC
AC input line voltage CA
Phase A input current
Phase B input current
Phase C input current
Input frequency (3 phases the same)
Input power factor (3 phases the same)
Phase A bypass voltage
Phase B bypass voltage
Phase C bypass voltage
Phase A bypass current
Phase B bypass current
Phase C bypass current
Bypass frequency (3 phases the same)
Battery temperature
Phase A output power factor
Phase B output power factor
User Manual
Value
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
1000 corresponds to 100.0A
1000 corresponds to 100.0A
1000 corresponds to 100.0A
1000 corresponds to 100Vdc
5000 corresponds to 50.00Hz
3800 corresponds to 380.0Vac
3800 corresponds to 380.0Vac
3800 corresponds to 380.0Vac
1000 corresponds to 100.0A
1000 corresponds to 100.0A
1000 corresponds to 100.0A
5000 corresponds to 50.00Hz
100 corresponds to 1
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
1000 corresponds to 100.0A
1000 corresponds to 100.0A
1000 corresponds to 100.0A
5000 corresponds to 50.00Hz
1000 corresponds to 100 Celsius degrees
100 corresponds to 1
100 corresponds to 1
10
Byte
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Item
Phase C output power factor
Phase A output active power
Phase B output active power
Phase C output active power
Battery current
Battery autonomy
Phase A output apparent power
Phase B output apparent power
Phase C output apparent power
Phase A output load percentage
Phase B output load percentage
Phase C output load percentage
Ambient temperature
Phase A output peak value
Phase B output peak value
Phase C output peak value
Reserved
Reserved
Reserved
Value
100 corresponds to 1
10000 corresponds to 100.00kW
10000 corresponds to 100.00kW
10000 corresponds to 100.00kW
1000 corresponds to 100.0A
1 corresponds to 1 minute
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
1000 corresponds to 100.0%
1000 corresponds to 100.0%
1000 corresponds to 100.0%
1000 corresponds to 100 Celsius degrees
100 corresponds to 1
100 corresponds to 1
100 corresponds to 1
Byte
Item
UPS name
UPS firmware release
Manufacturer
Adapter firmware release
Value
"UH31 0200L"
0x010B corresponds to V1.11
"EmersonNetworkPower "
0x010B corresponds to V1.11
Bit 0
Bit 1
Bit 2
Bit 3
Item
UPS alarm flag
Adapter communication fault flag
Not defined
Synchronization/Unsynchronization
Value
0: Normal; 1: Alarm
0: Normal; 1: Fault
Bits 5/4
Bits 7/6
Bits 9/8
Bit 10
Bit 11
Rectifier
Inverter
Bits 13/12
Bypass voltage
Bits 15~14
Not defined
10
2
20
2
Bit
1030
User Manual
0: Normal; 1:Unsynchronization
00: Normal
01: Below lower limit (mains failure)
10: Above upper limit
11: Outside specifications
00: Normal
01: Below lower limit (mains failure)
10: Above upper limit
11: Outside specifications
00: Normal
01: Below lower limit (mains failure)
10: Above upper limit
11: Outside specifications
0: Normal; 1: Fault
0: Normal; 1: Fault
00: Normal;
01: Below lower limit ;
10: Outside specifications
1031
Bit
Item
Bit 2/1/0
Bits 5/4/3
Bit 6
Bit 7
Bit 8
Charger fault
Output short circuit
Output overload
Bit 9
Heatsink over-temperature
Bit 10
Mains frequency
Bit 11
Bit 12
Bits 15~13
11
Value
000: Normal
001: Below lower limit (EOD point)
010: Above upper limit (voltage too high)
011: Fault
100: Pre-alarm
000: Normal
001: Below lower limit (EOD point)
010: Above upper limit (voltage too high)
011: Fault
100: Pre-alarm
0: Normal; 1: Fault
0: Normal; 1: Short circuit
0: Normal; 1: Overload
0: Normal;
1: Over-temperature
0: Normal;
1: Outside specifications
0: Normal; 1: Fault
0: Normal; 1: Fault
1040
Bit
Item
Bit 1/0
Operation mode
Bit 2
Bits 4/3
Bits 6/5
Bits 8/7
Turn-on/off
Bits 15~9
Not defined
Value
00: Neither Normal nor Battery mode
01: Normal mode
10: Battery mode
11: Bypass mode
0: Not under test; 1: Under test
00: Float charge;
01: Boost charge;
10: Not charging
00: Float charge;
01: Boost charge;
10: Not charging
00: Turn-on; 01: Turn-off;
10: Is turning off
Byte
2
2
2
2
2
2
2
2
2
2
2
2
2
Item
Phase A input voltage
Phase B input voltage
Phase C input voltage
Bypass voltage
Input frequency
Output voltage
Output current
Output frequency
Battery voltage (+)
Battery voltage (-)
Load percentage
Battery capacity
Internal temperature
Value
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
5000 corresponds to 50.00Hz
2200 corresponds to 220.0Vac
1000 corresponds to 100.0A
5000 corresponds to 50.00Hz
1000 corresponds to 100Vdc
1000 corresponds to 100Vdc
1000 corresponds to 100.0%
1000 corresponds to 100.0%
1000 corresponds to 100 Celsius degrees
User Manual
12
Byte
10
2
20
2
Item
UPS name
UPS firmware release
Manufacturer
Adapter firmware release
Value
"UH11 0100L"
0x010B corresponds to V1.11
"EmersonNetworkPower "
0x010B corresponds to V1.11
Bit
Item
0: Normal; 1: Alarm
Bit 1
0: Normal; 1: Fault
Bit 2
Not defined
Bit 3
Synchronization/Unsynchronization
0: Normal; 1:Unsynchronization
Bits 5/4
Mains voltage
00: Normal
01: Below lower limit (mains failure)
10: Above upper limit
11: Outside specifications
Bit 6
Rectifier
0: Normal; 1: Fault
Bit 7
Inverter
0: Normal; 1: Fault
Bits 9/8
Bypass voltage
00: Normal;
01: Below lower limit;
10: Above upper limit
Bits 12/11/10
000: Normal
001: Below lower limit (EOD point)
010: Above upper limit (voltage too high)
011: Fault;
100: Pre-alarm
Bit 13
Charger fault
0: Normal; 1: Fault
Bit 14
0: Normal; 1: Reversed
Bit 15
Bit 0
Output overload
0: Normal; 1: Overload
Bit 1
Heatsink over-temperature
0: Normal;
1: Over-temperature
Bit 2
Mains frequency
Bits 15~3
Not defined
1030
1031
Value
Bit 0
1040
Bit
Item
Value
Bits 1/0
Operation mode
Bit 2
Bits 4/3
Boost/float charge
Bits 6/5
Turn-on/off
Bits 15~7
Not defined
Byte
1050
1051
1052
1053
Item
Value
AC output current
Battery voltage
User Manual
Byte
1054
Output frequency
Item
Value
1055
Input frequency
1056
Load percentage
1057
Battery capacity
1058
Internal temperature
Byte
Item
Value
1000~1004
10
UPS name
1005
1006~1015
20
Manufacturer
"EmersonNetworkPower "
1019
Bit
Value
0: Normal; 1: Alarm
Bit 1
0: Normal; 1: Fault
Bit 2
Not defined
Mains voltage
00: Normal
01: Below lower limit
10: Above upper limit
11: Fault
Bits 6/5
Bypass voltage
00: Normal
01: Below lower limit
10: Above upper limit
11: Fault
Bit 7
Mains frequency
0: Normal; 1: Abnormal
Bit 8
Bypass frequency
0: Normal; 1: Abnormal
Bit 9
0: Normal; 1: Fault
Battery status
Module 1 status
000: Normal
001: Fault
010: Protection
011: Abnormal
100: Communication interrupt
101: Not known
Bits 4/3
1030
Item
Bit 0
Bits 12/11/10
Bits 15/14/13
User Manual
13
14
Bit
Value
Module 2 status
000: Normal
001: Fault
010: Protection
011: Abnormal
100: Communication interrupt
101: Not known
Module 3 status
000: Normal
001: Fault
010: Protection
011: Abnormal
100: Communication interrupt
101: Not known
Module 4 status
000: Normal
001: Fault
010: Protection
011: Abnormal
100: Communication interrupt
101: Not known
Module 5 status
000: Normal
001: Fault
010: Protection
011: Abnormal
100: Communication interrupt
101: Not known
Bits 14/13/12
Module 6 status
000: Normal
001: Fault
010: Protection
011: Abnormal
100: Communication interrupt
101: Not known
Bit 15
Not defined
Bits 2/1/0
Bits 5/4/3
1031
Item
Bits 8/7/6
Bits 11/10/9
1040
Bit
Item
Value
Bits 1/0
Operation mode
Bit 2
ON or OFF state
0: ON ; 1: OFF
Bit 3
0: Yes; 1: No
Bit 4
0: No; 1: Yes
Bit 5
Redundancy
Bits 15~6
Not defined
Byte
1050
Item
Value
1051
1052
AC output current
1053
Output frequency
1054
1055
Input power
1056
Input frequency
1057
1058
1059
Battery autonomy
1060
Battery voltage
1061
Bypass voltage
User Manual
Byte
1062
Item
Value
Bypass current
1063
Bypass frequency
1064
Load percentage
Byte
Item
Value
1000~1004
10
UPS name
UPS firmware release
1005
Manufacturer
1006~1015
20
"EmersonNetworkPower"
1019
UPS name
1030
Bit
Value
Bit 0
0: Normal; 1: Alarm
Bit 1
0: Normal; 1: Fault
Bit 2
Not defined
Bit 3
Synchronization/Unsynchronization
0: Normal;
1: Unsynchronization
Bits 5/4
Mains status
00: Normal;
01: Abnormal
Bit 6
Rectifier status
0: Normal; 1: Fault
Bit 7
Inverter status
0: Normal; 1: Fault
Bits 9/8
Bypass status
00: Normal
01: Below lower limit
10: Above upper limit
11: Fault
Bits 11/10
1031
Item
Bit 12
Heatsink status
0: Normal; 1: Overtemperature
Bit 13
Fan status
0: Normal; 1: Abnormal
Bits 15/14
00: Normal
01: Abnormal
10: nonsupport
Bit 0
0: Normal; 1: Abnormal
Bit 1
0: Normal; 1: Fault
Bit 2
Bit 3
0: Normal; 1: Fault
Bit 4
0: Normal; 1: Overload
Bit 5
0: Normal; 1: Shortcircuit
Bit 6
Overload time-out
0: Normal; 1: Time-out
Bit 7
0: Normal; 1: Fault
Bit 8
0: Normal; 1: Fault
Bits 10/9
00: Normal
01: Alarm
10: No Parallel System
Bits 12/11
00: Normal
01: Alarm
10: No Parallel System
Bits 14/13
System Overload
00: Normal
01: Alarm
10: No Parallel System
Bit 15
Not defined
User Manual
15
16
1032
Bit
Item
Bits 1/0
EPO
Bits 15~2
Not defined
Value
00: Normal
01: EPO
10: nonsupport
ID
Item
Value
Operation mode
Bits 3/2
Bit 4
Bit 5
0: Enabled
1: Not enabled
Bit 6
Bit 7
Switch-on or switch-off
0: On; 1: Off
Bits 15~8
Not defined
Bits 1/0
1040
Byte
1050
1051
1052
Item
Value
1053
1054
AC output current
1055
Battery voltage
1056
Output frequency
1057
Input frequency
1058
Bypass voltage
1059
Bypass current
1060
1061
1062
1063
Bypass frequency
Byte
10
2
20
2
Item
UPS name
UPS firmware release
Manufacturer
Adapter firmware release
Value
"UH33 0200L"
0x010B corresponds to V1.11
"EmersonNetworkPower "
0x010B corresponds to V1.11
User Manual
Bit 0
Bit 1
Bit 2
Bit
Item
UPS alarm flag
Adapter communication fault flag
Not defined
Value
Bit 3
Synchronization/Unsynchronization
Bit 4
Bit 5
Bit 6
Bit 7
Bits 10/9/8
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
0: Normal; 1: Alarm
0: Normal; 1: Fault
1030
1031
1032
0: Normal
1: Unsynchronization
0: Normal; 1: Abnormal
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal
1: Outside specifications
000: Normal
001: Below lower limit (EOD point)
010: Above upper limit (voltage too high)
011: No battery
100: Pre-alarm
101: Battery reverse connection
0: Normal
1: Outside specifications
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Overcurrent
0: Normal; 1: Overtemperature
0: Normal; 1: Blown out
0: Normal; 1: Failed
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Overtemperature
0: Normal; 1: Overtemperature
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Error
0: Normal; 1: Blown out
0: Normal; 1: Failed
0: Normal; 1: Overload
0: Normal; 1: Overload
0: Normal; 1: Overload timeout
0: Normal; 1: Abnormal
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
User Manual
17
18
1033
1034
Bit
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Item
DC bus overvoltage fault
Parallel cable connection fault
Ambient temperature too high
Rectifier communication fault
Inverter communication fault
Parallel communication fault
Output DC component too big fault
Parallel system battery pre-alarm fault
Input neutral line missing
Inverter contactor fault
Rectifier fault
Bits 12/11
Battery life
Bit 13
Bit 14
Bit 15
EPO
Battery temperature too high
Not defined
Bit 0
BCB status
Bit 2
Bit 3
Bits 15~4
Battery earthing
Equalize charge overtime
Not defined
Value
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
00: Normal
01: Battery needs replacement
10: Life span terminates
0: Normal; 1: Fault
0: Normal; 1: Fault
1040
1041
Bit
Item
Bits 2/1/0
Operation mode
Bit 3
Bits 5/4
Boost/float charge
Bit 6
Turn-on/off
Bit 7
Generator connection
Bit 8
Bit 9
Bit 10
Bit 11
Bits 14/13/12
Bit 15
Not defined
Bit 1/0
Bits 15~2
Not defined
Value
000: Neither Normal nor Battery mode
001: Normal mode
010: Battery mode
011: Bypass mode
100: Source share mode
0: Not under test;1: Under test
00: Float charge;
01: Boost charge
10: Not charging
0: Turn-on; 1: Turn-off
0: Connected
1: Not connected
0: Open; 1: Closed
0: Open;1: Closed
0: Open; 1: Closed
0: Open; 1: Closed
000: Closed
001: Under test
010: Normal
011: Bypass state
100: Maintenance state
Byte
2
2
2
Item
AC input phase voltage A
AC input phase voltage B
AC input phase voltage C
Value
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
User Manual
Byte
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Item
AC output phase voltage A
AC output phase voltage B
AC output phase voltage C
AC output current A
AC output current B
AC output current C
Battery voltage
Output frequency (3 phases the same)
AC input line voltage AB
AC input line voltage BC
AC input line voltage CA
Phase A input current
Phase B input current
Phase C input current
Input frequency (3 phases the same)
Phase A input power factor
Phase B input power factor
Phase C input power factor
Phase A bypass voltage
Phase B bypass voltage
Phase C bypass voltage
Bypass frequency (3 phases the same)
Battery current
Phase A output power factor
Phase B output power factor
Phase C output power factor
Module Phase A output peak value
Module Phase B output peak value
Module Phase C output peak value
Module Phase A output active power
Module Phase B output active power
Module Phase C output active power
Module Phase A output apparent power
Module Phase B output apparent power
Module Phase C output apparent power
Module Phase A output load percentage
Module Phase B output load percentage
Module Phase C output load percentage
Module Phase A output reactive power
Module Phase B output reactive power
Module Phase C output reactive power
System Phase A output active power
System Phase B output active power
System Phase C output active power
System Phase A output apparent power
System Phase B output apparent power
System Phase C output apparent power
System Phase A output reactive power
System Phase B output reactive power
System Phase C output reactive power
Battery autonomy
Battery temperature
Ambient temperature
Battery voltage (-)
Battery current (-)
Value
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
1000 corresponds to 100.0A
1000 corresponds to 100.0A
1000 corresponds to 100.0A
1000 corresponds to 100Vdc
5000 corresponds to 50.00Hz
3800 corresponds to 380.0Vac
3800 corresponds to 380.0Vac
3800 corresponds to 380.0Vac
1000 corresponds to 100.0A
1000 corresponds to 100.0A
1000 corresponds to 100.0A
5000 corresponds to 50.00Hz
100 corresponds to 1
100 corresponds to 1
100 corresponds to 1
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
5000 corresponds to 50.00Hz
1000 corresponds to 100.0A
100 corresponds to 1
100 corresponds to 1
100 corresponds to 1
100 corresponds to 1
100 corresponds to 1
100 corresponds to 1
10000 corresponds to 100.00kW
10000 corresponds to 100.00kW
10000 corresponds to 100.00kW
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
1000 corresponds to 100.0%
1000 corresponds to 100.0%
1000 corresponds to 100.0%
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kW
10000 corresponds to 100.00kW
10000 corresponds to 100.00kW
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
1 corresponds to 1 minute
1000 corresponds to 100 Celsius degrees
1000 corresponds to 100 Celsius degrees
1000 corresponds to 100Vdc
1000 corresponds to 100.0A
User Manual
19
20
Byte
Item
UPS name
UPS firmware release
Manufacturer
Adapter firmware release
Value
"HL33 0200L"
"0100" corresponds to V1.0
"EmersonNetworkPower "
0x1234 corresponds to Ver12.34
Bit
Bit 0
Bit 1
Bit 2
Item
UPS alarm flag
Adapter communication fault flag
Not defined
0: Normal; 1: Alarm
0: Normal; 1: Fault
Bit 3
Synchronization/Unsynchronization
Bit 4
Bit 5
Bit 6
Bit 7
Bits 10/9/8
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Input fuse
Mains phase
REC input Phase
Control power 1
Control power 2
Rectifier
Soft start
Rectifier overtemp.
Input filter fault
Input filter transfer time-out
Filter contactor fault
REC drive cirtuit fault
Rectifier comm. fail
Inverter overtemp.
Fan fault
Inverter STS fail
Bypass STS fail
Operation invalid
Unit over load
System over load
10
2
20
2
1030
1031
Value
0: Normal
1: Unsynchronization
0: Normal; 1: Abnormal
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal
1: Outside specifications
000: Normal
001: Below lower limit (EOD point)
010: Above upper limit (voltage too high)
011: No battery
100: Pre-alarm
101: Battery reverse connection
0: Normal;
1: Outside specifications
0: Normal; 1 Fail:
0: Normal; 1: Reversed
0: Normal; 1: Missing
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Current limit
0: Normal; 1: Fail
0: Normal; 1: Overtemp.
0: Normal; 1: Fault
0: Normal; 1: Time-out
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fail
0: Normal; 1: Overtemp.
0: Normal; 1: Fault
0: Normal; 1: Fail
0: Normal; 1: Fail
0: Normal; 1: Invalid
0: Normal; 1: Over load
0: Normal; 1: Over load
User Manual
1032
1033
1034
Bit
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Item
Unit over load time-out
Byp. abnormal shutdown
Output over voltage
Inverter over current
Bypass phase
Load impact transfer
Transfer time-out
Load sharing fault
DC bus abnormal
System transfer
Parallel board fault
Parallel connect fault
Parallel comm. fail
Bypass over current
Bits 15/14
LBS Active/Fault
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bits 9/8
Battery life
Bit 10
Bit 11
Bit 12
Battery overtemp.
Battery ground fault
Battery fuse fail
Bits 14/13
BCB status
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bits 15~9
Value
0: Normal; 1: Time-out
0: Normal; 1: Shutdown
0: Normal; 1: Over voltage
0: Normal; 1: Over current
0: Normal; 1: Reverse
0: Normal; 1: Transfer
0: Normal; 1: Time-out
0: Normal; 1: Fault
0: Normal; 1: Abnormal
0: Normal; 1: Transfer
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Over current
00: Not Active
01: Active
10: Fault
0: Normal; 1: Overtemp
0: Normal; 1: Overtemp
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Warning
0: Normal; 1: EPO
0: Normal; 1: Overtemp.
00: Normal
01: Battery needs replacement
10: Life span terminates
0: Normal; 1: Overtemp.
0: Normal; 1: Fault
0: Normal; 1: Fault
00: BCB not connected
01: BCB closed
10: BCB open
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Time-out
0: Normal; 1: Fault
0: Normal; 1: Fault
0: Normal; 1: Fault
User Manual
21
22
1040
1041
Bit
Item
Bits 2/1/0
Operation mode
Bit 3
Battery selftest
Bits 5/4
Boost/float charge
Bit 6
Turn-on/off
Bit 7
Generator connection
Bit 8
Bit 9
Bit 10
Bit 11
Bits 13/12
Bits 15/14
No use
Bits 2/1/0
Bit 3
Filter state
Bit 4
Sleep state
Bit 5
Bits 15~6
No use
Value
000: Neither Normal nor Battery mode
001: Normal mode
010: Battery mode
011: Bypass mode
100: Source share mode
0: Not under test
1: Under test
00: Float charge
01: Boost charge
10: Not charging
0: Turn-on; 1: Turn-off
0: Connected
1: Not connected
0: Open; 1: Closed
0: Open; 1: Closed
0: Open; 1: Closed
0: Open; 1: Closed
00: Normal mode
01: Battery mode
10: Bypass mode
11: No output
000: Closed
001: Under test
010: Normal
011: Bypass state
100: Maintenance state
0: Not Connected
1: connected
0: Not Sleep
1: Sleep
0: normal mode
1: PFC mode
Byte
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Item
AC output phase voltage A
AC output phase voltage B
AC output phase voltage C
AC output current A
AC output current B
AC output current C
Battery voltage
Output frequency (3 phases the same)
AC input line voltage AB
AC input line voltage BC
AC input line voltage CA
Phase A input current
Phase B input current
Phase C input current
Input frequency (3 phases the same)
Total input power factor
Phase A bypass voltage
Phase B bypass voltage
Phase C bypass voltage
Bypass frequency (3 phases the same)
Battery current
Value
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
1000 corresponds to 100.0A
1000 corresponds to 100.0A
1000 corresponds to 100.0A
1000 corresponds to 100Vdc
5000 corresponds to 50.00Hz
3800 corresponds to 380.0Vac
3800 corresponds to 380.0Vac
3800 corresponds to 380.0Vac
1000 corresponds to 100.0A
1000 corresponds to 100.0A
1000 corresponds to 100.0A
5000 corresponds to 50.00Hz
100 corresponds to 1
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
2200 corresponds to 220.0Vac
5000 corresponds to 50.00Hz
1000 corresponds to 100.0A
User Manual
Byte
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Item
Phase A output power factor
Phase B output power factor
Phase C output power factor
Module Phase A output peak value
Module Phase B output peak value
Module Phase C output peak value
Module Phase A output active power
Module Phase B output active power
Module Phase C output active power
Module Phase A output apparent power
Module Phase B output apparent power
Module Phase C output apparent power
Module Phase A output load percentage
Module Phase B output load percentage
Module Phase C output load percentage
Module Phase A output reactive power
ModulePhase B output reactive power
ModulePhase C output reactive power
System Phase A output active power
System Phase B output active power
System Phase C output active power
System Phase A output apparent power
System Phase B output apparent power
System Phase C output apparent power
System Phase A output reactive power
System Phase B output reactive power
System Phase C output reactive power
Battery autonomy
Battery temperature
Ambient temperature
Battery aging ratio
Value
100 corresponds to 1
100 corresponds to 1
100 corresponds to 1
100 corresponds to 1
100 corresponds to 1
100 corresponds to 1
10000 corresponds to 100.00kW
10000 corresponds to 100.00kW
10000 corresponds to 100.00kW
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
1000 corresponds to 100.0%
1000 corresponds to 100.0%
1000 corresponds to 100.0%
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kW
10000 corresponds to 100.00kW
10000 corresponds to 100.00kW
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
10000 corresponds to 100.00kVA
1 corresponds to 1 minute
1000 corresponds to 100 Celsius degrees
1000 corresponds to 100 Celsius degrees
10000 corresponds to 100
1000 ~ 1004
Byte
10
Item
Value
UPS name
HR331500
0x0201 to V2.01
1005
1006 ~ 1015
20
Manufacturer
EmersonNetworkPower
1019
0x0201 to V2.01
User Manual
23
24
Bit
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Item
UPS general alarm flag bit
Modbus card/dry contactor card communication
failure flag bit
Reserved
Inverter synchronous/asynchronous
Mains voltage
Rectifier status
Inverter status
Bypass conditions (voltage or frequency)
1032
0: Normal; 1: Failure
Bits
10/9/8
Battery 1 status
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 7/6
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Fan failure
Environmental temperature over-high
Emergency power off
Bypass thyristor failure
Bypass phase sequence reverse
Bypass over-current failure
Bypass abnormal power off
Bypass switching number limit
Failure of module combining board
Failure of module combining cable
Communication failure of module combining
Auxiliary power 2 power off
Contactor power board 1 failure
0: Synchronous; 1: Asynchronous
0: Synchronous; 1: Asynchronous
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Excessive
000: Normal
001: Below the lower limit (power-off point)
010: Above the upper limit (excessive voltage)
011: No battery
100: Pre-alarm
101: Reverse batteries
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
00: Normal; 01: Keyboard failure
10: Model capacity invalid
0: Normal; 1: Failure
0: Normal; 1: Over-high
0: Normal; 1: Power off
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Abnormal
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
Bit 5
0: Normal; 1: Failure
Bit 6
Bit 8/7
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
0: Normal; 1: Abnormal
00: BCB not accessed; 01: BCB closed
03: BCB disconnected
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Over-current
0: Normal; 1: Over-current
0: Normal; 1: Over-temperature
1030
1031
Value
0: Normal; 1: Alarm
User Manual
1033
1034
Bit
Bit 0
Bit 1
Bit 2
Item
Battery 2 converter over-temperature
Battery 1 charger failure
Battery 2 charger failure
Bit 4/3
Battery 1 life
Bit 6/5
Battery 2 life
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit13
Bit 14
Bit 15
Bit 0
Bit 115
Reserved
Bit 3
1035
1036
Value
0: Normal; 1: Over-temperature
0: Normal; 1: Failure
0: Normal; 1: Failure
00: Normal; 01: Battery to be replaced
10: Battery life ended
00: Normal; 01: Battery to be replaced
10: Battery life ended
0: Normal; 1: Over-high
0: Normal; 1: Over-high
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Excessive
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Failure
0: Normal; 1: Over-current
0: Normal; 1: Broken
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Failure
0: Normal; 1: Error
0: Normal; 1: Broken
0: Normal; 1: Overload
0: Normal; 1: Overload
0: Normal; 1: Overload timeout
0: Normal; 1: Over-voltage
0: Normal; 1: Over-current
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
User Manual
25
26
1040
Bit
Value
00: UPS power supply; 01: Bypass power
supply
10: No power supply
0: In self-check; 1: Not in self-check
00: Floating charge; 01: Average charge
10: Non-charging status
0: Power-off; 1: Power-on
00: Master channel input, rectifier started
01: Battery input, rectifier started
10: Combined input, rectifier started
11: No input from master channel or batteries
0: Generator accessed; 1: Generator not
accessed
0: Disconnected; 1: Closed
Bit 1/0
Bit 2
Battery 1 self-check
Bit 4/3
Bit 5
Bit 7/6
Bit 8
Bit 9
Bit 11
Bit 12
Bit
15/14/13
Bits 2/1/0
Bit 3
Bit 5/4
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
0: Disconnected; 1: Closed
0: Disconnected; 1: Closed
000: Closed
001: Under test
010: Normal
011: Bypass
100: Maintenance
000: No power supply
001: Bypass power supply
010: Mains supply
011: Battery inversion power supply
100: United power supply
101: Output prohibited
0: in self-check; 1: Not in self-check
00: Floating charge; 01: Average charge
10: Non charge
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
Item
Input phase voltage A
Input phase voltage B
Input phase voltage C
Output phase voltage A
Output phase voltage B
Output phase voltage C
Output phase current A
Output phase current B
Output phase current C
DC input voltage (Battery 1 voltage)
Output frequency (consistency in three phases)
Input cable voltage AB
Input cable voltage BC
0.1V
0.1V
0.1V
0.1V
0.1V
0.1V
0.1A
0.1A
0.1A
0.1V
0.01Hz
0.1V
0.1V
Bit 10
1041
Item
0: Disconnected; 1: Closed
Byte
2
2
2
2
2
2
2
2
2
2
2
2
2
Value
User Manual
Byte
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Item
Input cable voltage CA
Input phase current A
Input phase current B
Input phase current C
Input frequency (consistency in three phases
Phase A input power factor
Phase B input power factor
Phase C input power factor
Bypass phase voltage A
Bypass phase voltage B
Bypass phase voltage C
Bypass frequency
Phase A output power factor
Phase B output power factor
Phase C output power factor
Phase A output peak ratio
Phase B output peak ratio
Phase C output peak ratio
Phase A output active power
Phase B output active power
Phase C output active power
Phase A output reactive power
Phase B output reactive power
Phase C output reactive power
Phase A output apparent power
Phase B output apparent power
Phase C output apparent power
Battery backup time
Positive battery voltage
Positive battery current
Negative battery voltage
Negative battery current
Battery aging coefficient
Battery temperature
Environmental temperature
Value
0.1V
0.1A
0.1A
0.1A
0.01Hz
0.01
0.01
0.01
0.1V
0.1V
0.1V
0.01Hz
0.01
0.01
0.01
0.01
0.01
0.01
0.01kW
0.01kW
0.01kW
0.01kVA
00.01kVA
0.01kVA
0.01kVA
0.01kVA
0.01kVA
Minute
0.1V
0.1A
0.1V
0.1A
0.1
0.1C
0.1C
Byte
1000 ~ 1004
10
Item
Value
UPS name
APM 150
1005
0x0210 to V2.10
1006 ~ 1015
20
Manufacturer
EmersonNetworkPower
1016
Reserved
1019
0x0210 to V2.10
1030
Bit
Bit 0
Bit 2
Item
UPS general alarm flag bit
Modbus card/dry contactor card communication
failure flag bit
Reserved
Bit 3
Inverter synchronous/asynchronous
Bit 1
Value
0: Normal; 1: Alarm
0: Normal; 1: Failure
0: Synchronous; 1: Asynchronous
User Manual
27
28
1030
Bit
Bit 4
Bit 5
Bit 6
Bit 7
Item
Mains voltage
Rectifier status
Inverter status
Bypass conditions (voltage or frequency)
Bits
10/9/8
Battery 1 status
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bits 7/6
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Fan failure
Environmental temperature over-high
Emergency power off
Bypass thyristor failure
Bypass phase sequence reverse
Bypass over-current failure
Bypass abnormal power off
Bypass switching number limit
Failure of module combining board
Failure of module combining cable
Communication failure of module combining
Auxiliary power 2 power off
Contactor power board 1 failure
Value
0: Synchronous; 1: Asynchronous
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Excessive
000: Normal
001: Below the lower limit (power-off point)
010: Above the upper limit (excessive voltage)
011: No battery
100: Pre-alarm
101: Reverse batteries
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
00: Normal
01: Keyboard failure
10: Model capacity invalid
0: Normal; 1: Failure
0: Normal; 1: Over-high
0: Normal; 1: Power off
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Abnormal
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
Bit 5
0: Normal; 1: Failure
Bit 6
Bits 8/7
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bits 4/3
Battery 1 life
Bits 6/5
Battery 2 life
Bit 7
0: Normal; 1: Abnormal
00: BCB not accessed
01: BCB closed
03: BCB disconnected
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Over-current
0: Normal; 1: Over-current
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Failure
0: Normal; 1: Failure
00: Normal
01: Battery to be replaced
10: Battery life ended
00: Normal
01: Battery to be replaced
10: Battery life ended
0: Normal; 1: Over-high
1031
1032
1033
User Manual
1033
1034
Bit
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
1035
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit13
Bit 14
Bit 15
Bit 0
Bit 1
1036
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bits 11
15
Item
Battery 2 temperature over-high
Battery 1 grounding failure
Battery 2 grounding failure
Master channel frequency abnormal
Balance inductor over-temperature
Input inductor over-temperature
Rectifier over-temperature
Balance circuit failure
Balance inductor over-current
Master fuse broken
Auxiliary power 1 power-off
Master channel phase sequence reverse
Rectifier over-current
Software start failure
Inversion inductor over-temperature
Inductor over-temperature
Inversion thyristor failure
User operation error
Output fuse broken
Single unit output overload
Combined system overload
Single unit overload timeout
AC output over-voltage
Inverter over-current
Turning to bypass due to load impact
Failure of current sharing in combined units
Abnormal power-off of bus
Turning to bypass due to request by neighbor
system
DC bus over-voltage failure
Rectifier communication failure
Inverter communication failure
Output DC excess failure
Combined system battery pre-alarm failure
Input zero-lacking failure
Inversion contactor failure
Input contactor failure
Input current abnormal
Output voltage abnormal
Input current excessive
Bypass over-temperature
Thyristor failure in neighboring unit
External input isolated transformer
over-temperature
External input isolated transformer fan failure
Bypass transformer over-temperature
Top-outlet Fan fault
Loss of redundancy
Capacity Exceeded
Functional module 11 failure
Functional module 12 failure
Bypass not available
Equalize charge overtime
Value
0: Normal; 1: Over-high
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Excessive
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Failure
0: Normal; 1: Over-current
0: Normal; 1: Broken
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Failure
0: Normal; 1: Error
0: Normal; 1: Broken
0: Normal; 1: Overload
0: Normal; 1: Overload
0: Normal; 1: Overload timeout
0: Normal; 1: Over-voltage
0: Normal; 1: Over-current
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
Reserved
User Manual
29
30
Bit
Item
Bits 1/0
Bit 2
Battery 1 self-check
Bits 4/3
Bit 5
Bit 7/6
Bit 8
Bit 9
Bit 11
Bit 12
Bits
15/14/13
Bits 2/1/0
Bit 3
Bit 5/4
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
0: Disconnected; 1: Closed
0: Disconnected; 1: Closed
000: Closed
001: Under test
010: Normal
011: Bypass
100: Maintenance
000: No power supply
001: Bypass power supply
010: Mains supply
011: Battery inversion power supply
100: United power supply
101: Output prohibited
0: In self-check; 1: Not in self-check
00: Floating charge
01: Average charge
10: Non charge
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
Bit 0
Bit 1
Bit 2
Bit 3
0: Online; 1: Offline
0: Online; 1: Offline
Bits 415
Reserved
1040
Bit 10
1041
1042
Value
00: UPS power supply
01: Bypass power supply
10: No power supply
0: In self-check; 1: Not in self-check
00: Floating charge
01: Average charge
10: Non-charging status
0: Power-off; 1: Power-on
00: Master channel input, rectifier started
01: Battery input, rectifier started
10: Combined input, rectifier started
11: No input from master channel or batteries
0: Generator accessed
1: Generator not accessed
0: Disconnected; 1: Closed
0: Disconnected; 1: Closed
Byte
2
2
2
2
2
2
Item
Input phase voltage A
Input phase voltage B
Input phase voltage C
Output phase voltage A
Output phase voltage B
Output phase voltage C
Value
0.1V
0.1V
0.1V
0.1V
0.1V
0.1V
User Manual
Byte
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Item
Output phase current A
Output phase current B
Output phase current C
DC input voltage (Battery 1 voltage)
Output frequency (consistency in three phases)
Input cable voltage AB
Input cable voltage BC
Input cable voltage CA
Input phase current A
Input phase current B
Input phase current C
Input frequency (consistency in three phases)
Phase A input power factor
Phase B input power factor
Phase C input power factor
Bypass phase voltage A
Bypass phase voltage B
Bypass phase voltage C
Bypass frequency
Phase A output power factor
Phase B output power factor
Phase C output power factor
Phase A output peak ratio
Phase B output peak ratio
Phase C output peak ratio
Phase A output active power
Phase B output active power
Phase C output active power
Phase A output reactive power
Phase B output reactive power
Phase C output reactive power
Phase A output apparent power
Phase B output apparent power
Phase C output apparent power
Phase A output load percentage
Phase B output load percentage
Phase C output load percentage
Battery backup time
Positive battery voltage
Positive battery current
Negative battery voltage
Negative battery current
Battery aging coefficient
0.1A
0.1A
0.1A
0.1V
0.01Hz
0.1V
0.1V
0.1V
0.1A
0.1A
0.1A
0.01Hz
0.01
0.01
0.01
0.1V
0.1V
0.1V
0.01Hz
0.01
0.01
0.01
0.01
0.01
0.01
0.01kW
0.01kW
0.01kW
0.01kVA
0.01kVA
0.01kVA
0.01kVA
0.01kVA
0.01kVA
0.01
0.01
0.01
Minute
0.1V
0.1A
0.1V
0.1A
0.1
1103
Battery temperature
0.1
1104
Environmental temperature
0.1
Value
User Manual
31
32
Bit
Bit 2/1/0
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
2000
2001+n (0N17)
Item
Reserved
Inside communication status
Input dry contactor 1 status
Input dry contactor 2 status
Input dry contactor 3 status
Input dry contactor 4 status
Collaction board 5 ready status
Collaction board 6 ready status
Collaction board 7 ready status
Collaction board 8 ready status
Collaction board 10 ready status
Collaction board 11 ready status
Collaction board 12 ready status
CRC check status
Branch 3n+1 over-current
Branch 3n+1 ultra-high current threshold
Branch 3n+1 low current threshold
Branch 3n+1 impact over-current
Branch 3n+1 switch abnormal
Branch 3n+2 over-current
Branch 3n+2 ultra-high current threshold
Branch 3n+2 low current threshold
Branch 3n+2 impact over-current
Branch 3n+2 switch abnormal
Branch 3n+3 over-current
Branch 3n+3 ultra-high current threshold
Branch 3n+3 low current threshold
Branch 3n+3 impact over-current
Branch 3n+3 switch abnormal
Value
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
0: Normal; 1: Alarm
Byte
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Item
SPM Branch 1 current
SPM Branch 1 power (kWh)
SPM Branch 1 switch status
SPM Branch 1 active power
SPM Branch 1 apparent power
SPM Branch 1 THDi
SPM Branch 1 rated current
SPM Branch 1 load ratio
SPM Branch 1 power factor
SPM Branch 1 reserved
SPM Branch 1 reserved
SPM Branch 1 reserved
SPM Branch 1 reserved
SPM Branch 1 reserved
SPM Branch 1 reserved
SPM Branch 2 current
SPM Branch 2 power (kWh)
SPM Branch 2 switch status
SPM Branch 2 active power
SPM Branch 2 apparent power
SPM Branch 2 THDi
SPM Branch 2 rated current
SPM Branch 2 load ratio
SPM Branch 2 power factor
SPM Branch 2 reserved
Value
0.1A
0.1kWh
1
0.1kW
0.1kW
0.01
0.1A
0.01
0.01
0.1A
0.1kWh
1
0.1kW
0.1kW
0.01
0.1A
0.01
0.01
User Manual
1923
1924
1925
1926
1927
1928
1929
1930
1931
1932
1933
1934
1935
1936
1937
1999
Byte
2
2
Item
SPM Branch 2 reserved
SPM Branch 2 reserved
SPM Branch 2 reserved
SPM Branch 2 reserved
SPM Branch 2 reserved
Reserved
33
Value
0.1A
0.1kWh
1
0.1kW
0.1kW
0.01
0.1A
0.01
0.01
Byte
1000 ~ 1004
10
Item
Value
UPS name
HR331500
0x0201 to V2.01
1005
1006 ~ 1015
20
Manufacturer
EmersonNetworkPower
1019
0x0201 to V2.01
Bit
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Item
UPS general alarm flag bit
Modbus card/dry contactor card communication
failure flag bit
Reserved
Inverter synchronous/asynchronous
Mains voltage
Rectifier status
Inverter status
Bypass conditions (voltage or frequency)
1030
Bits
10/9/8
Battery 1 status
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Value
0: Normal; 1: Alarm
0: Normal; 1: Failure
0: Synchronous; 1: Asynchronous
0: Synchronous; 1: Asynchronous
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Excessive
000: Normal
001: Below the lower limit (power-off point)
010: Above the upper limit (excessive voltage)
011: No battery
100: Pre-alarm
101: Reverse batteries
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
User Manual
34
1031
1032
1033
Bit
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Item
Functional module 6 failure
Functional module 7 failure
Functional module 8 failure
Functional module 9 failure
Functional module 10 failure
LBS abnormal
Bit 7/6
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Fan failure
Environmental temperature over-high
Emergency power off
Bypass thyristor failure
Bypass phase sequence reverse
Bypass over-current failure
Bypass abnormal power off
Bypass switching number limit
Failure of module combining board
Failure of module combining cable
Communication failure of module combining
Auxiliary power 2 power off
Contactor power board 1 failure
Contactor power board 2 failure
Redundant fan power failure
Bit 8/7
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 4/3
Battery 1 life
Bit 6/5
Battery 2 life
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Value
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
00: Normal; 01: Keyboard failure
10: Model capacity invalid
0: Normal; 1: Failure
0: Normal; 1: Over-high
0: Normal; 1: Power off
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Abnormal
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Abnormal
00: BCB not accessed; 01: BCB closed
03: BCB disconnected
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Over-current
0: Normal; 1: Over-current
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Failure
0: Normal; 1: Failure
00: Normal; 01: Battery to be replaced
10: Battery life ended
00: Normal; 01: Battery to be replaced
10: Battery life ended
0: Normal; 1: Over-high
0: Normal; 1: Over-high
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Excessive
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Failure
User Manual
1034
Bit
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
1035
1036
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bits
1115
Item
Balance inductor over-current
Master fuse broken
Auxiliary power 1 power-off
Master channel phase sequence reverse
Rectifier over-current
Software start failure
Inversion inductor over-temperature
Inductor over-temperature
Inversion thyristor failure
User operation error
Output fuse broken
Single unit output overload
Combined system overload
Single unit overload timeout
AC output over-voltage
Inverter over-current
Turning to bypass due to load impact
Failure of current sharing in combined units
Abnormal power-off of bus
Turning to bypass due to request by neighbor
system
DC bus over-voltage failure
Rectifier communication failure
Inverter communication failure
Output DC excess failure
Combined system battery pre-alarm failure
Input zero-lacking failure
Inversion contactor failure
Input contactor failure
Input current abnormal
Output voltage abnormal
Input current excessive
Bypass over-temperature
System Bypass STS fail
Input TX Overtemp
Input TX Fan fault
Bp cabinet TX Overtemp
Top-outlet Fan fault
Loss of redundancy
Capacity Exceeded
Functional module 11 failure
Functional module 12 failure
Bypass not available
Equalize charge overtime
Value
0: Normal; 1: Over-current
0: Normal; 1: Broken
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Failure
0: Normal; 1: Error
0: Normal; 1: Broken
0: Normal; 1: Overload
0: Normal; 1: Overload
0: Normal; 1: Overload timeout
0: Normal; 1: Over-voltage
0: Normal; 1: Over-current
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Failure
0: Normal; 1: Failure
Reserved
User Manual
35
36
1040
Bit
1042
Value
00: UPS power supply; 01: Bypass power
supply
10: No power supply
0: In self-check; 1: Not in self-check
00: Floating charge; 01: Average charge
10: Non-charging status
0: Power-off; 1: Power-on
00: Master channel input, rectifier started
01: Battery input, rectifier started
10: Combined input, rectifier started
11: No input from master channel or batteries
0: Generator accessed; 1: Generator not
accessed
0: Disconnected; 1: Closed
Bit 1/0
Bit 2
Battery 1 self-check
Bit 4/3
Bit 5
Bit 7/6
Bit 8
Bit 9
Bit 11
Bit 12
Bit
15/14/13
Bits 2/1/0
Bit 3
Bit 5/4
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
0: Disconnected; 1: Closed
0: Disconnected; 1: Closed
000: Closed
001: Under test
010: Normal
011: Bypass
100: Maintenance
000: No power supply
001: Bypass power supply
010: Mains supply
011: Battery inversion power supply
100: United power supply
101: Output prohibited
0: in self-check; 1: Not in self-check
00: Floating charge; 01: Average charge
10: Non charge
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
Bit 0
Bit 1
Bit 2
Bit 3
0: Online; 1: Offline
0: Online; 1: Offline
Bit 215
Reserved
Bit 10
1041
Item
0: Disconnected; 1: Closed
Byte
2
2
2
2
2
2
2
Item
Input phase voltage A
Input phase voltage B
Input phase voltage C
Output phase voltage A
Output phase voltage B
Output phase voltage C
Output phase current A
Value
0.1V
0.1V
0.1V
0.1V
0.1V
0.1V
0.1A
User Manual
Byte
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Item
Output phase current B
Output phase current C
DC input voltage (Battery 1 voltage)
Output frequency (consistency in three phases)
Input cable voltage AB
Input cable voltage BC
Input cable voltage CA
Input phase current A
Input phase current B
Input phase current C
Input frequency (consistency in three phases
Phase A input power factor
Phase B input power factor
Phase C input power factor
Bypass phase voltage A
Bypass phase voltage B
Bypass phase voltage C
Bypass frequency
Phase A output power factor
Phase B output power factor
Phase C output power factor
Phase A output peak ratio
Phase B output peak ratio
Phase C output peak ratio
Phase A output active power
Phase B output active power
Phase C output active power
Phase A output reactive power
Phase B output reactive power
Phase C output reactive power
Phase A output apparent power
Phase B output apparent power
Phase C output apparent power
Battery backup time
Positive battery voltage
Positive battery current
Negative battery voltage
Negative battery current
Battery aging coefficient
Battery temperature
Environmental temperature
Value
0.1A
0.1A
0.1V
0.01Hz
0.1V
0.1V
0.1V
0.1A
0.1A
0.1A
0.01Hz
0.01
0.01
0.01
0.1V
0.1V
0.1V
0.01Hz
0.01
0.01
0.01
0.01
0.01
0.01
0.01kW
0.01kW
0.01kW
0.01kVA
00.01kVA
0.01kVA
0.01kVA
0.01kVA
0.01kVA
Minute
0.1V
0.1A
0.1V
0.1A
0.1
0.1C
0.1C
1000 ~ 1004
Byte
10
Item
Value
UPS name
MR33 0300
0x0201 to V2.01
1005
1006 ~ 1015
20
Manufacturer
EmersonNetworkPower
1019
0x0201 to V2.01
User Manual
37
38
Bit
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Item
UPS general alarm flag bit
Modbus card/dry contactor card communication
failure flag bit
Reserved
Inverter synchronous/asynchronous
Mains voltage
Rectifier status
Inverter status
Bypass conditions (voltage or frequency)
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
0: Normal; 1: Failure
Bit 6
Bit 8/7
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
0: Normal; 1: Abnormal
00: BCB not accessed; 01: BCB closed
03: BCB disconnected
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Over-current
0: Normal; 1: Over-current
0: Normal; 1: Over-temperature
Bits
10/9/8
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 7/6
1032
0: Normal; 1: Failure
0: Synchronous; 1: Asynchronous
0: Normal; 1: Abnormal
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Abnormal
000: Normal
001: Below the lower limit (power-off point)
010: Above the upper limit (excessive
voltage)( Reserved)
011: No battery
100: Pre-alarm
101: Reverse batteries
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Abnormal
00: Normal; 01: Keyboard failure
10: Model capacity invalid
0: Normal; 1: Abnormal
0: Normal; 1: Over-high
0: Normal; 1: Power off
0: Normal; 1: Failure
0: Normal; 1: Phase sequence reverse
0: Normal; 1: Over-current
0: Normal; 1: Abnormal Power off
0: Normal; 1: Limit
0: Normal; 1: Failure
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Limit
1030
1031
Value
0: Normal; 1: Alarm
Battery status
User Manual
1033
1034
Bit
Bit 0
Bit 1
Bit 2
Item
Battery 2 converter over-temperature(Reserved)
Battery charger failure
Battery 2 charger failure (Reserved)
Bit 4/3
Battery to be replaced
Bit 6/5
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
1035
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit13
Bit 14
Bit 15
Value
0: Normal; 1: Over-temperature
0: Normal; 1: Failure
0: Normal; 1: Failure
00: Normal; 01: Battery to be replaced
10: Battery life ended
00: Normal; 01: Battery to be replaced
10: Battery life ended
0: Normal; 1: Over-high
0: Normal; 1: Over-high
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Abnormal
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Failure
0: Normal; 1: Over-current
0: Normal; 1: Broken
0: Normal; 1: Power off
0: Normal; 1: Phase sequence reverse
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Failure
0: Normal; 1: Error
0: Normal; 1: Broken
0: Normal; 1: Overload
0: Normal; 1: Overload
0: Normal; 1: Overload timeout
0: Normal; 1: Over-voltage
0: Normal; 1: Over-current
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
User Manual
39
40
Bit
Bit 0
Bit 1
Bit 2
1036
1037
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bits 4~15
Item
Thyristor failure in neighboring unit
External input isolated transformer
over-temperature(Reserved)
External input isolated transformer fan
failure(Reserved)
Bypass transformer over-temperature(Reserved)
IGBT drv. cable fault
SCR fan abnormal
Charger fan abnormal
SubBlock1 fan abnormal
SubBlock2 fan abnormal
SubBlock3 fan abnormal
Auxpower fan abnormal
Rec. ind. fan abnormal
Inv. conta. power fail
SubBlock1 over-current
SubBlock2 over-current
SubBlock3 over-current
Para.connect. abnormal
Byp.fan power abnormal
Byp. drv. cable fault
SubBlock1 overtemp
SubBlock2 overtemp
SubBlock3 overtemp
SCR overtemp
Charger overtemp
Batt. port short
Byp.aux.pwr.fan abnor
Inv aux.conta.1 abnor
Inv aux.conta.2 abnor
Battery room alarm
BCB status abnormal
Byp. neutral lost
Bypass in charge
BCB1 status abnormal
BCB2 status abnormal
BCB3 status abnormal
BCB4 status abnormal
Reserved
Value
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Over-temperature
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Failure
0: Normal; 1: Over-current
0: Normal; 1: Over-current
0: Normal; 1: Over-current
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Failure
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Failure
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Failure
0: No charge;1: In charge
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
User Manual
41
1040
Bit
Bit 1/0
Bit 2
Battery self-check
Bit 4/3
Bit 5
Bit 7/6
Bit 8
Bit 9
Bit 11
Bit 12
Bit
15/14/13
Bits 2/1/0
Bit 3
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 1/0
BCB Status
Bit 3/2
BCB 1 Status
Bit 5/4
BCB 2 Status
Bit 7/6
BCB 3 Status
Bit 9/8
BCB 4 Status
Bit 10
Bit 11
Bit 12
Bit 13
Bit 10
Bit 5/4
1041
1042
Item
Value
00: UPS power supply; 01: Bypass power
supply
10: No power supply
0: In self-check; 1: Not in self-check
00: Floating charge; 01: Average charge
10: Non-charging status
0: Power-off; 1: Power-on
00: Master channel input, rectifier started
01: Battery input, rectifier started
10: Combined input, rectifier started(Reserved)
11: No input from master channel or batteries
0: Generator accessed; 1: Generator not
accessed
0: Disconnected; 1: Closed
0: Disconnected; 1: Closed
0: Disconnected; 1: Closed
0: Disconnected; 1: Closed
000: Closed
001: Under test
010: Normal
011: Bypass
100: Maintenance
000: No power supply
001: Bypass power supply
010: Mains supply
011: Battery inversion power supply
100: United power supply
101: Output prohibited
0: in self-check; 1: Not in self-check
00: Floating charge; 01: Average charge
10: Non charge
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
00: BCB not connected; 01: BCB open; 10:
BCB close
00: BCB not connected; 01: BCB open; 10:
BCB close
00: BCB not connected; 01: BCB open; 10:
BCB close
00: BCB not connected; 01: BCB open; 10:
BCB close
00: BCB not connected; 01: BCB open; 10:
BCB close
0 :Close; 1: Open
0 :Close; 1: Open
0 :Close; 1: Open
0 :Close; 1: Open
User Manual
42
Byte
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Item
Input phase voltage A
Input phase voltage B
Input phase voltage C
Output phase voltage A
Output phase voltage B
Output phase voltage C
Output phase current A
Output phase current B
Output phase current C
DC input voltage (Battery 1 voltage)
Output frequency (consistency in three phases)
DC input voltage (Battery 2 voltage)(Reserved)
Input cable voltage AB
Input cable voltage BC
Input cable voltage CA
Input phase current A
Input phase current B
Input phase current C
Input frequency (consistency in three phases)
Phase A input power factor
Phase B input power factor
Phase C input power factor
Bypass phase voltage A
Bypass phase voltage B
Bypass phase voltage C
Bypass frequency
Input capacitance current A
Input capacitance current B
Input capacitance current C
Output capacitance current A
Output capacitance current B
Output capacitance current C
Phase A output power factor
Phase B output power factor
Phase C output power factor
Phase A output peak ratio
Phase B output peak ratio
Phase C output peak ratio
Phase A output active power
Phase B output active power
Phase C output active power
Phase A output reactive power
Phase B output reactive power
Phase C output reactive power
Phase A output apparent power
Phase B output apparent power
Phase C output apparent power
Phase A output load level
Phase B output load level
Phase C output load level
Battery backup time
Positive battery voltage
Positive battery current
Negative battery voltage
Negative battery current
Battery aging coefficient
Battery temperature
Value
0.1V
0.1V
0.1V
0.1V
0.1V
0.1V
0.1A
0.1A
0.1A
0.1V
0.01Hz
0.1V
0.1V
0.1V
0.1V
0.1A
0.1A
0.1A
0.01Hz
0.01
0.01
0.01
0.1V
0.1V
0.1V
0.01Hz
0.1A
0.1A
0.1A
0.1A
0.1A
0.1A
0.01
0.01
0.01
0.01
0.01
0.01
0.01kW
0.01kW
0.01kW
0.01kVA
00.01kVA
0.01kVA
0.01kVA
0.01kVA
0.01kVA
0.01
0.01
0.01
Minute
0.1V
0.1A
0.1V
0.1A
0.1
0.1C
User Manual
Byte
2
2
Item
Environmental temperature
Unit environmental temperature
Value
0.1C
0.1C
Byte
1000 ~ 1004
10
Item
Value
UPS name
XC33 0300
0x0201 to V2.01
1005
1006 ~ 1015
20
Manufacturer
EmersonNetworkPower
1019
0x0201 to V2.01
Bit
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 8/7
Item
UPS general alarm flag bit
Modbus card/dry contactor card communication
failure flag bit
Reserved
Inverter synchronous/asynchronous
Mains voltage
Rectifier status
Inverter status
Bypass conditions (voltage or frequency)
1030
Bits
11/10/9
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 7/6
1031
Bit 9/8
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Battery status
Value
0: Normal; 1: Alarm
0: Normal; 1: Failure
0: Synchronous; 1: Asynchronous
0: Normal; 1: Abnormal
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Abnormal
000: Normal
001: Below the lower limit (power-off point)
010: Above the upper limit (excessive
voltage)( Reserved)
011: No battery
100: Pre-alarm
101: Reverse batteries
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 01: Active; 10:Abnormal
00: Normal; 01: Keyboard failure
10: Model capacity invalid
0: Normal; 1: Abnormal
0: Normal; 1: Over-high
0: Normal; 1: Power off
0: Normal; 1: Failure
0: Normal; 1: Phase sequence reverse
0: Normal; 1: Over-current
User Manual
43
44
1032
1033
1034
Bit
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 10/9
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 6/5
Item
Bypass abnormal power off
Bypass switching number limit
Failure of module combining board(Reserved)
Abnormal of module combining cable(Reserved)
Communication abnormal of module combining
Auxiliary power 2 power off(Reserved)
Contactor power board 1 failure(Reserved)
Contactor power board 2 failure(Reserved)
Redundant fan power failure(Reserved)
BCB status
Battery contactor failure(Reserved)
Battery 2 contactor failure(Reserved)
Battery converter failure
Battery 2 converter failure(Reserved)
Battery converter over-current(Reserved)
Battery 2 converter over-current(Reserved)
Battery converter over-temperature(Reserved)
Battery 2 converter over-temperature(Reserved)
Battery charger failure
Battery 2 charger failure(Reserved)
Battery to be maintenance
Bit 8/7
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Value
0: Normal; 1: Abnormal Power off
0: Normal; 1: Limit
0: Normal; 1: Failure
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Over-current
0: Normal; 1: Over-current
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Failure
0: Normal; 1: Failure
00: Normal; 01: Battery to be maintenance
00: Normal; 01: Battery to be replaced
10: Battery life ended
0: Normal; 1: Over-high
0: Normal; 1: Over-high
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Abnormal
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Failure
0: Normal; 1: Over-current
0: Normal; 1: Broken
0: Normal; 1: Power off
0: Normal; 1: Phase sequence reverse
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Over-temperature
0: Normal; 1: Over-temperature
0: Normal; 1: Failure
0: Normal; 1: Error
0: Normal; 1: Broken
0: Normal; 1: Overload
0: Normal; 1: Overload
0: Normal; 1: Overload timeout
User Manual
Bit
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
1035
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit15
Bit 0
Bit 1
Bit 2
Bit 3
1036
Bit 4
Bit 5
Bit 6
Bits 15-7
Item
AC output over-voltage(Reserved)
Inverter over-current(Reserved)
Turning to bypass due to load impact
Failure of current sharing in combined units
Abnormal power-off of bus
Turning to bypass due to request by neighbor
system
DC bus over-voltage failure
Rectifier communication failure(Reserved)
Communication failure
Output DC excess failure(Reserved)
battery pre-alarm failure(Reserved)
Input zero-lacking failure
Inversion contactor failure(Reserved)
Input contactor failure(Reserved)
Input current abnormal
Output voltage abnormal
Input current excessive
Bypass over-temperature(Reserved)
Thyristor failure in neighboring unit
External input isolated transformer
over-temperature(Reserved)
External input isolated transformer fan
failure(Reserved)
Input Feedback
Discharge current limit
Reserved
45
Value
0: Normal; 1: Over-voltage
0: Normal; 1: Over-current
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Failure
0: Normal; 1: Over-temperature
0: Normal; 1: Failure
0: Normal; 1: Failure
1040
Bit
Item
Bit 1/0
Bit 2
Battery self-check
Bit 4/3
Bit 5
Bit 7/6
Bit 8
Bit 9
Bit 11
Bit 12
Bit
15/14/13
Bit 10
Value
00: UPS power supply; 01: Bypass power
supply
10: No power supply
0: In self-check; 1: Not in self-check
00: Floating charge; 01: Average charge
10: Non-charging status
0: Power-off; 1: Power-on
00: Master channel input, rectifier started
01: Battery input, rectifier started
10: Combined input, rectifier started(Reserved)
11: No input from master channel or batteries
0: Generator accessed; 1: Generator not
accessed
0: Disconnected; 1: Closed
0: Disconnected; 1: Closed
0: Disconnected; 1: Closed
0: Disconnected; 1: Closed
000: Closed
001: Under test
010: Normal
011: Bypass
100: Maintenance
User Manual
46
Bit
Bits 2/1/0
Bit 3
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Value
000: No power supply
001: Bypass power supply
010: Mains supply
011: Battery inversion power supply
100: United power supply
101: Output prohibited
0: in self-check; 1: Not in self-check
00: Floating charge; 01: Average charge
10: Non charge
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
0: Online; 1: Offline
Bit 0
Bit 2/1
BCB Status
Bit3 15-3
Reserved
Bit 5/4
1041
1042
Item
Byte
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Item
Input phase voltage A
Input phase voltage B
Input phase voltage C
Output phase voltage A
Output phase voltage B
Output phase voltage C
Output phase current A
Output phase current B
Output phase current C
DC input voltage (Battery 1 voltage)
Output frequency (consistency in three phases)
Reserved
Reserved
Reserved
Reserved
Input cable voltage AB
Input cable voltage BC
Input cable voltage CA
Input phase current A
Input phase current B
Input phase current C
Input frequency (consistency in three phases)
Phase A input power factor
Phase B input power factor
Phase C input power factor
Bypass phase voltage A
Bypass phase voltage B
Bypass phase voltage C
Bypass frequency
Phase A output power factor
Phase B output power factor
Phase C output power factor
Value
0.1V
0.1V
0.1V
0.1V
0.1V
0.1V
0.1A
0.1A
0.1A
0.1V
0.01Hz
0.1V
0.1V
0.1V
0.1A
0.1A
0.1A
0.01Hz
0.01
0.01
0.01
0.1V
0.1V
0.1V
0.01Hz
0.01
0.01
0.01
User Manual
Byte
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Item
Phase A output peak ratio
Phase B output peak ratio
Phase C output peak ratio
Phase A output active power
Phase B output active power
Phase C output active power
Phase A output reactive power
Phase B output reactive power
Phase C output reactive power
Phase A output apparent power
Phase B output apparent power
Phase C output apparent power
Phase A output load level
Phase B output load level
Phase C output load level
Battery backup time
Positive battery voltage
Positive battery current
Negative battery voltage
Negative battery current
Battery aging coefficient
Battery temperature
Environmental temperature
Value
0.01
0.01
0.01
0.01kW
0.01kW
0.01kW
0.01kVA
00.01kVA
0.01kVA
0.01kVA
0.01kVA
0.01kVA
0.01
0.01
0.01
Minute
0.1V
0.1A
0.1V
0.1A
0.1
0.1C
0.1C
Byte
1000 ~ 1004
10
Item
Value
UPS name
EgPA1R002002
1005
0x0201 to V2.01
1006 ~ 1015
20
Manufacturer
EmersonNetworkPower
1019
0x0201 to V2.01
Byte
Bit 0
Bit 1
Bit 2
Bit 3
1030
Bit 4
Bit 5
Bit 6
Bit 7
Bits 10/9/8
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Item
UPS general alarm flag bit
Modbus card/dry contactor card
communication failure flag bit
Reserved
Inverter
synchronous/asynchronous(nonsupport)
Mains voltage(nonsupport)
Rectifier status(nonsupport)
Inverter status(nonsupport)
Bypass conditions (voltage or frequency)
(nonsupport)
Battery voltage abnormal nonsupport)
Input phase A not qualified
Input phase B not qualified
Input phase C not qualified
PM fan failure
PM lock lever in remove position
Value
0: Normal; 1: Alarm
0: Normal; 1: Failure
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
User Manual
47
48
1031
1032
1033
Byte
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bits 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bits 10
Bit 11
Bit 12
Bit 13
Bits 14
Bit 15
Item
PM fault
PM short circuit
PM warning
Insufficient capacity to start
PM over load
PM over temperature warning
PM over temperature shutdown
Output off- Overload,bypass abn
Short circuit shutdown
Bypass monitor board fault
Guaranteed shutdown
transformer over temp shutdown
EOD shutdown
transformer over temperature
Output off,voltage is not zero
Reserved
Bypass control board alarm
Frame fan fault
Bypass abnormal
Transformer fan fault
Battery module voltage low
Bp ctr locker in remove position
Bp monitor board fault
Shutdown on manual bypass
Output off- bypass unavailable
Bp mnt locker in remove position
CM power source is not qualified
CM alarm
CM locker in remove position
CM fan fault
CM over temperature
Reserved
CM fault
CM over temperature and shutdown
No matching battery module
Load exceeds BM capacity
Battery cabinet not connected
Battery module alarm
BM locker in Remove position
Battery module over temperature
Low battery warning
Battery test failure
Low battery for battery test
Battery temperature imbalance
BM over temperature and shutdown
Battery module fault
Starting battery test
Stoped battery test
Value
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
User Manual
1034
1035
1036
Byte
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bits 4-15
Item
BM use exceed 5 years of age
Output pending
All PMs are not ready
Communication output off
UPS is operating on battery
Battery-to-utility transition
UPS's load power is on
Load off from user interface
Operating on Inverter
On manual bypass
Time to check the fan filters
Acknowledged filter reminder
Acknowledged batt test results
Load off due to shutdown on batt
Output must be off
Power module redundancy alarm
Output exceeds max load setting
System alarm
EPO shutdown
Overload cleared
NO battery module are ready
L1 L2 reversed
Battery reversed
Input fuse disconnection
L1 L2 input current imbalance
Frame fault
Ext batt over temperature
No external batt
Load exceeds Ext batt capacity
Ext batt high voltage
Ext batt low voltage
Ext batt mode BM exit
Rear rocker switch turned off
Input neutral is not connected
Bypass jumper error
Operating on Bypass
Reserved
Value
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
0: Normal; 1: Abnormal
User Manual
49
50
1040
Byte
Bit 3/2
Bits 6/5/4
Battery status
Bit7
Bits 8-15
CM status
Reserved
Bit 8
Bit 9
Bit 11
Bit 12
1046
Value
00: UPS power supply;
01: Bypass power supply
10: No power supply
Bits 1/0
Bit 10
1045
Item
Bits 15/14/13
Bits 1
Bit 2
Bits3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8-15
Bit 0
Bit 1
Bit 2
Bit 3
Bits 415
Reserved
Byte
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Item
Value
L-N voltage A
L-N voltage B
L-N voltage C
L-N voltage A
L-N voltage B
L-N voltage C
L-N current A
L-N current B
L-N current C
Battery voltage
Output frequency
Reserved
Reserved
Reserved
Input frequency
Input power factor A
Input power factor B
0.01 Volt
0.01 Volt
0.01 Volt
0.01 Volt
0.01 Volt
0.01 Volt
0.01 Ampere
0.01 Ampere
0.01 Ampere
0.01 Volt
0.01 Hz
0.01Hz
0.01
0.01
User Manual
Byte
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Item
Input power factor C
L-N current A
L-N current B
L-N current C
Reserved
Bypass voltage A
Bypass voltage B
Bypass frequency A
Bypass frequency B
Reserved
Battery string count
Remain time
Battery capacity
Battery temperature
Discharge count
Discharge hour
Reserved
External battery cabinet count
Fault BM count
Alarm BM count
CM installed count
Fault CM count
Alarm CM count
Reserved
Reserved
Output power factor A
Output power factor B
System Output apparent power A
System Output apparent power B
Output real power A
Output real power B
Load rate A
Load rate B
PM online count
Alarm PM count
Fault PM count
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
dry contactor card analog 1
dry contactor card analog 2
dry contactor card analog 3
dry contactor card analog 4
dry contactor card analog 5
dry contactor card analog 6
dry contactor card analog 7
dry contactor card analog 8
User Manual
Value
0.01
0.01
0.01
0.01
0.1 Volt
0.1 Volt
0.01 Hz
0.01 Hz
Minute
1%
0.1
0.1Hour
0.01
0.01
0.001KVA
0.001 KVA
0.001KW
0.001KW
0.1
0.1
51
52
Byte
1000~1004
10
1005
1006~1015
1019
2
20
2
Item
UPS name
UPS firmware release
Manufacturer
Adapter firmware release
UPS name
Value
1030
1031
1032
Bit
Item
Value
Bit 0
0: Normal; 1: Alarm
Bit 1
0: Normal; 1: Fault
Bit 2
Not defined
Bit 3
Synchronization/Unsynchronization
0: Normal;
1: Unsynchronization
Bits 5/4
Mains status
00: Normal;
01: Abnormal
Bit 6
Rectifier status
0: Normal; 1: Fault
Bit 7
Inverter status
0: Normal; 1: Fault
Bits 9/8
Bypass status
Bits 11/10
00: Normal
01: Below lower limit
10: Above upper limit
11: Fault
Bit 12
Heatsink status
Bit 13
Fan status
0: Normal; 1: Abnormal
Bits 15/14
00: Normal
01: Abnormal
10: nonsupport
Bit 0
0: Normal; 1: Abnormal
Bit 1
0: Normal; 1: Fault
Bit 2
Bit 3
0: Normal; 1: Fault
Bit 4
0: Normal; 1: Overload
Bit 5
Bit 6
Overload time-out
0: Normal; 1: Time-out
Bit 7
0: Normal; 1: Fault
Bit 8
0: Normal; 1: Fault
Bits 10/9
00: Normal
01: Alarm
10: No Parallel System
Bits 12/11
00: Normal
01: Alarm
10: No Parallel System
Bits 14/13
System Overload
00: Normal
01: Alarm
10: No Parallel System
Bit 15
Not defined
Bits 1/0
EPO
Bit 2
No Battery
0: Normal; 1: Alarm
Bit 3
Battery Reversed
0: Normal; 1: Alarm
Bits 15~4
Not defined
00: Normal
01: EPO
10: nonsupport
User Manual
Bit
Item
Value
Operation mode
Bits 3/2
Bit 4
Bit 5
0: Enabled
1: Not enabled
Bit 6
Bit 7
Switch-on or switch-off
0: On; 1: Off
Bits 15~8
Not defined
Bits 1/0
1040
Byte
1050
1051
1052
Item
Value
1053
1054
AC output current
1055
Battery voltage
1056
Output frequency
1057
Input frequency
1058
Bypass voltage
1059
Bypass current
1060
1061
1062
1063
Bypass frequency
1064
Battery autonomy
1 corresponds to 1 Minute
User Manual
53
54
Chapter 4 Troubleshooting
Chapter 4 Troubleshooting
1. After plugging the adapter in the SNMP slot of the UPS or FLP, the yellow LED (equipment communication LED) of
the adapter does not illuminate.
Cause analysis and solution: the UPS or FLP is off or has no mains input. Please turn on the UPS or FLP; if the UPS
or FLP cannot be turned on, please connect the mains input to the UPS or FLP and try again.
2. After the adapter is installed, the yellow LED (equipment communication LED) of the adapter illuminates, and the
host monitoring software cannot monitor the UPS or FLP normally.
Cause analysis and solution: the UPS or FLP is on, but the communication between the adapter and the UPS or FLP
has not been established. Please pull out the adapter, check for the presence and proper insertion of the chip on the
PCB. If the check proves satisfactory, the adapter must be damaged, please contact the customer service center of
Emerson.
3. After the adapter is installed, the yellow LED (equipment communication LED) of the adapter flashes about once
per 5s, and the host monitoring software cannot monitor the UPS or FLP normally.
Cause analysis and solution: the yellow LED flashing once per 5s indicates the adapter cannot detect the UPS or
FLP or recognize the UPS or FLP type. Please check if the adapter matches the UPS or FLP type according to the
hardware description in section 1.3. The adapter can recognize the UPS or FLP type. After it recognizes the UPS or
FLP, the yellow LED will flash quickly, about once per 1s.
4. The yellow LED (equipment communication LED) flashes quickly, the green LED (host communication LED) is off.
Cause analysis and solution: the adapter is not properly connected to the host computer. Please properly connect the
adapter to the host computer following the instructions provided in section 2.3.3.
5. The yellow LED (equipment communication LED) flashes quickly, the green LED (host communication LED)
flashes too, but the host monitoring software cannot monitor the UPS or FLP normally.
Cause analysis and solution: the yellow LED flashing quickly indicates the communication between the adapter and
the UPS or FLP is normal; if the green LED flashes but the host monitoring software cannot detect the UPS or FLP
data, please check that: 1) the communication cable is properly connected between the adapter and the host
computer; 2) the adapters physical address and communication baud rate settings are the same as those set in the
host monitoring software; 3) the adapters physical address setting does not conflict with that of any other monitored
equipment (applicable only in RS485 cascade connection).
User Manual
While every precaution has been taken to ensure the accuracy and completeness of this
literature, Emerson Network Power assumes no responsibility and disclaims all liability for
damages resulting from use of this information or for any errors or omissions.
All rights reserved throughout the world.
Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners
31011134-V1.7
www.EmersonNetworkPower.com