Relay Selection Chart1
Relay Selection Chart1
Relay Selection Chart1
Sr. RELAY APPLICATION IEEE/ GEC - ABB Relay ABB Relay Special Features of ABB
No. ANSI Alsthom Type Design Relays/Remarks
CODES (Areva)
Relay Type
1 Auxiliary Relay 30/74 VAA 11 CV2dj / CV2d2j E.M. Heavy duty double break contacts 2/4
SR contacts in CV2dj/CV2d2j
respectively
10 Trip Circuit Supervision 95 VAX 31 TCS Static Pre & Post close supervision
11 AC Inst. O/C or E/F Protection 50/50N CAG 11 RXIG 21 Static Static, sensitive instantaneous version
with combiflex connections &
12 AC Inst. O/C or E/F Protection 50/50N CAG 12 RXIG 21 Static continuously variable setting.
14 Restricted Earth Fault 64 CAG 14 with IRXM with Static Voltage operated relay, self monitoring
Protection Metrosil Metrosil feature.
15 AC Inst. O/C Protection ? CAG 17 IKM2 Static/E.M. RXIG 22 is harmonically desensitised
sensitive inst. O/C relay with
16 AC Inst. O/C Protection ? CAG 37 3 * IKM2 Static/E.M. continuously variable settings in
combiflex connection.
17 High impedance 3 Ph. 87/64 CAG 34 3 *IRXM with Static Voltage operated relay, self monitoring
Differential protection VDR feature.
18 Single pole non directional 51/51N CDG 11 ICM 21np E.M. Linearity in Time Multiplier Setting.
IDMT Protection Temperature compensated measuring
system.
19 Single pole non directional 51/51N/ CDG 21 ICM21p/ E.M.
IDMT with instantaneous 50/50N ICM21kp
Protection
22 2 O/C & Restricted Earth Fault (51+64) CDAG31 NI40 / SPAE E.M. / Current operated relay, self monitoring
Protection 010/011 + VDR Micropro- feature.
cessor based
Sr. RELAY APPLICATION IEEE/ GEC - ABB Relay ABB Relay Special Features of ABB
No. ANSI Alsthom Type Design Relays/Remarks
CODES (Areva)
Relay Type
23 3 O/C & Restricted Earth Fault (51+64) CDAG 51 / SPAJ140C + Micropro- Wide selection of operating characteristic
Protection 53 / 54 VDR cessor based like inverse, Normal inverse, Very
(Needbased) inverse, Extremely inverse, Long time
inverse, RI and DMT, Display of service
and last 5 fault current phase wise. High
set unit for O/C and E/F can be made
inst., delayed or decommissioned. Two
setting banks available. Breaker failure
protection included. Self diagnostic
feature, compact size. Has inbuilt master
trip relay.
24 Definite Time Over Current (50+2) CAUM 39 RXIG21 + Static Static Design, Compact Version in
Protection RXKL1+RXSF1 combiflex connections
25 DC No volt relay 80 VAG11/21 PN8nCH2j / EM / Static 5 heavy duty double break contacts
RXSF1 available in PN8. Flush mounting. RXSF
list available in combiflex connection.
26 Single pole AC inst. U/V or O/V (27/59) VAG21 VHXm22A / Static
Protection VHXm23A Static
27 Single pole AC inst. U/V or O/V (27/59) VAGM22 VHXm22A / Static Static relay having compact design & low
Protection VHXm23A VA burden
Single pole AC Definite Time (27/50 + VAGM22 + VHXm22B / Static
U/V or O/V relay 2) VTT1 VHXm23B
28 Three pole fuse failure relay 97 VAPM31 UVT92m Static Low rated burden (0.5 VA per phase).
Compact design.
29 Neutral desplacement relay 60/64 VDG21 UBX117 Static Static def. Time version, compact design,
3rd & 5th harmonic restraint available.
Continuously variable setting available.
30 Delay on pickup static timer 2 VTT11 SSX90m6c2j Static Upto 6 Nos. heavy duty contacts
available. Flush mounting type.
Protection mounting on metal base.
31 Delay on pickup static timer 2 VTT14 SSX90m6c2j Static Heavy duty, double break contacts.
33 AC instantaneous O/V 59 VTIG12 VHXm23A Static There are 5 heavy duty. Double break
Protection contacts with wide time range availabe in
VHXm range. Similar compact deisgn.
44 Check synchronism relay 25 SKD RASC (w/o test Static/Micro SPAU140C provides continuous or pulse
switch) / processor output. Has 2 N/O and 2 N/C heavy duty
SPAU140C based contacts / Capable of synchronising 2
communicable CB, wider setting range with provision of
external blocking, self diagnostic feature.
SKE SPAU140C
45 Transformer differential relay 87T 3 * MBCH12 RADSB (2 Static 5th harmonic restraint with limit for
winding) (Combiflex) dangerous over excitation. Consistent
operating range. Relay with 5 input also
46 Transformer differential relay 87T 3 * MBCH13 RADSB (3 " available for special applications.
winding)
47 Over fluxing Protection 99 GTT/GTTM UFX132 / Static Combiflex connection & inverse
RATUB characteristics available for better
matching of transformer overfluxing
withstand capacity in RATUB. Only fixed
time delay version available in UFX132.
48 Reverse Power/Low Forward (32 + 2) WCD + PPX111 Static 3 ph. Static available with built-in two
Power Protection relay 2*VTT11 stage time delay. Supplied in 19" rack
with dc/dc convertor and dc circuit test
facility.
49 Rotor E/F Protection 64R CAEM + IWX161+YWX Static Uses bridge balancing technique for
VAEM21 111 measuring. True uniform rotor insulation
failure detection is also available
supplied in 19: rack.
50 Relay Test Kit CFB TURE (With in- - Suitable for testing all voltage / current
built Timer) relays.
51 Capacitor Bank Protection ? SPAJ160C Microprocessor Overload, undercurrent and unbalance
based protection. Self diagnostic feature.
communicable
52 Feeder Protection Terminal SPAC310C Microprocessor Provides Protection, Control &
based Measurement of Feeder.
communicable
53 Motor Feeder Protection 99+ SPAC320C Microprocessor Provides Protection, Control &
Terminal control based Measurement of Motor Feeder.
communicable
54 Combined Over Current and REJ52_ / Microprocessor Overcurrent, earth fault , Phase
Earth Fault Relay REX521 based discontinuity and Circuit Breaker failure
communicable protection.
55 Feeder Protection Terminal REF54_ / Microprocessor ProvidesProtection,Control,
REX521 / based Measurement, Conditon monitoring and
REF610 communicable standared Functons of Medium Voltage
Network.
56 Machine Terminal REM543 Microprocessor ProvidesProtection,Control,
based Measurement and Superision of
communicable Generators / Generator-Transformer
Units and Large MV Synchronous and
Asynchronous Motors.
57 Transformer Protection RET541 / Microprocessor Fast and selective Protection and Control
Terminal SPAD346C based of two and three winding transformer,
communicable Autotransformer, Generator-Transformer
bloks and Shunt reactor.
58 combined Over Voltage and REU523 / Microprocessor Over- Voltage, Under-Voltage, Positive
Undervoltage Relay REU610 / based Phase sequence and Circuit Breaker
SPAU130C communicable Failure Protection and Disturbance
Recorder.
NOTE: ABB has vast range of relays in Electromechanical / Static / Microprocessor (Communicable) based designs. All of them are
not covered in the Selection Chart above. ABB also covers all ranges of EHV protection schemes. For requirements & queries, please