Stairwell & Lift Pressurization Calculations
Stairwell & Lift Pressurization Calculations
Stairwell & Lift Pressurization Calculations
SMOKE CONTROL
BY
PRESSURISATION
November 1998
(Third Edition)
PAGE NO:
Summary 4
ACKNOWLEDGEMENTS
The author wishes to acknowledge the assistance he received from Mr Cyril Moss,
KG Smoke Dispersals Ltd and Mr E Gorden Butcher of Fire Check Consultants with
the preparation of this paper.
3
WOODS AIR MOVEMENT LIMITED
SUMMARY
There are basically two main methods for controlling smoke in buildings to
prevent it contaminating escape routes - by Ventilation and by Pressurisation.
Fans for Fire Smoke Venting (Ref 1) examines the motivation behind the
increased use of Powered Ventilators for the exhausting of hot smoke from
fires and determines their requirements and specifications.
4
CHAPTER 1
Fire induced forces create pressure differ- Thomas’ correlation (Ref 3) estimates that a
ences across doors etc, which allow smoke 2.4 MW fire will cause smoke to flow
to flow through any gaps present. through a 0.9 metre wide opening at 3-4 m/
sec. BS5588 Part 4:1978 requires this for
By altering these pressure differences we permanent openings.
can control the movement of smoke.
In practice a velocity of this magnitude is
The two BASIC PRINCIPLES of smoke virtually impossible to achieve in the type of
control were defined by JH KLOTE (Ref 2) buildings using Pressurisation for Smoke
as:- Control, and some compromise is neces-
sary. Doors are considered as only being
a) Airflow can control smoke movement if
opened intermittently and hence VELOCI-
the average VELOCITY is of sufficient
TIES can be reduced.
magnitude.
b) A PRESSURE difference across a bar- Table 1 shows VELOCITIES between 0.75
rier can act to control smoke movement. m/sec and 2.0 m/sec.
Although the second of these principles can BS5588 Part 4:1978 specified up to 0.75 m/
be taken as a special case of the first, when sec during the Escape period.
dealing with them as an engineering prob- BS5588 Part 5:1991 - 2.0 m/sec for Fire
lem it is easier to take the two separately Fighting.
viz:-
b) Number of Open Doors
Large Gaps- Open Door etc - VELOCITY
Variations in this parameter have the great-
Small Gaps - Closed Door etc - PRESSURE est effect on fan size.
These, then are the BASIC PRINCIPLES Again table 1 shows much variation from
which control the design and ultimately the ONE EFFECTIVE DOOR OPEN specified
satisfactory functioning of a PRESSURISA- by BS5588 Part 4 1978 to FOUR EFFEC-
TION SYSTEM for SMOKE CONTROL. TIVE DOORS OPEN required by the CA-
They formed the basis of the British Stand- NADIAN STANDARD - N.B.C.C. 1990.
ard Codes of Practice - BS5588 Parts
4:1978 and 5:1991, and the same elements However the combination of DOOR VE-
can be seen in many of the various national LOCITY and DOORS OPEN likely to pro-
standards listed in TABLE 1. duce the greatest air supply requirement is
that specified by BS5588 Part 5 1991 - 2.0
1.2 SUPPLY AIR PARAMETERS m/sec with TWO EFFECTIVE DOORS
OPEN.
The two parameters which have the great-
est effect on the size of the supply fan are:- 1.3 RECENT DEVELOPMENTS
a) The AIR VELOCITY through the OPEN BS5588 Part 4 - 1978 was revised and re-
DOORS. issued during April 1998
b) The number of EFFECTIVE OPEN The revised Code Practice designated
DOORS BS5588: Part 4: 1998, retains the
5
0.75m/sec air velocity through the open In addition, BS5588: Part 4: 1998 incorpo-
door(s) onto the fire floor during the escape rates the Pressurisation System require-
ments for Fire Fighting specified in
phase, but now demands that up to three
BS5588: Part 5 1991 and it is still this re-
effective doors be regarded as being quirement - 2.0m/sec with up to THREE EF-
OPEN when calculating the supply air quan- FECTIVE DOORS OPEN which produces
tity required. The number of open doors the greatest air supply demand.
varies with the type and usage of the build-
The discussion and calculations in this re-
ing, but in general, this change from 1978 vised paper are now based on the require-
code will increase the quantity of supply air ments of BS5588: Part 4: 1998.
required.
U.S.A. U.B.C. 37 -
1988 No Mention No Mention
6
CHAPTER 2
Why Pressurisation?
2.1 OBJECTIVE OF SMOKE CONTROL Major development work on Axial Flow Fans
for the venting of hot fire smoke was carried
The objective of any SMOKE CONTROL out during the 1980’s (Ref 4), which led to
system is to keep the smoke and toxic the publication in 1990 of a test standard
gases out of the escape route long enough BS7346 Part 2 (Ref 5).
to allow the occupants to escape or seek a
safe refuge. In addition an adequate smoke In high rise, multi room buildings, where the
control system will help the fire fighters deal Staircases, Lift Lobbies and Corridors pro-
both with the fire and any residue smoke. vide the escape route, SMOKE
EXTRACTION may only serve to worsen
2.2 SMOKE VENTILATION the situation.
-VE
-VE
-VE
-VE
7
Pressurising Air
2.3 PRESSURISATION
The idea of PRESSURISATION is not new. The first Code of Practice permitting the use
For over 50 years PRESSURISATION sys- of PRESSURISATION as a fire protection
tems have been used to keep rooms free of method was published in Australia in 1957.
dust and harmful contamination, and to pro-
In the U.K. research continued during the
vide sterile condition in operating theatres etc.
1960’s and 1970’s (Ref 6) resulting in the pub-
The use of Pressurisation for SMOKE CON- lication of a Code of Practice - BS5588 Part 4
TROL began to be considered during the in 1978 (Ref 7). This Code of Practice was
1950’s, both in the U.K. and Australia. reviewed and reissued in April 1998 as
BS5588:Part 4:1998(Ref 8)
8
CHAPTER 3
Exhaust Air
(Natural)
Staircase
Accomodation
Pressurising
Air Supply Exhaust Air
(Powered)
Exhaust Air
(Natural)
+ 50 Pa
a) A Supply Air System designed to blow
into the protected spaces a sufficient
quantity of air to maintain the required
pressure level or air velocity.
This will always be fan powered.
b) An Exhaust Air System to enable the
pressurising air to escape from the
unpressurised areas of the building via
the fire floor.
Fire Floor
This can be either a natural or fan powered
method. The fans used would be required
to handle the hot fire smoke and comply
with BS7346 Part 2 (Ref 5).
9
Mode 1 - DECTECTION PHASE - To raise The Fire Fighting (Mode 3), is included in
a pressure differential in the protection the classification. The system require-
space - staircase, corridor etc, by the ment, taken from BS5588:Part 5:1991
required amount (50Pa in the UK) when remain common to all building types.
ALL DOORS ARE CLOSED.
A notable addition in the new code of
Mode 2 - ESCAPE PHASE - To maintain a practice is that CLASS C; E; and D sys-
specified AIR VELOCITY (0.75m/sec) tems have BOTH a VELOCITY and
through the OPEN DOOR(S) onto the fire PRESSURE CRITERION requirement
floor with various other doors open, OR a during the Escape Phase (Mode 2)
PRESSURE DIFFERENCE OF 10+ Pa
with the fire floor door(s) closed and vari- These CLASSES of Pressurisation Sys-
ous other doors open (fig 7-9) tems are detailed in TABLE 2 and their
individual requirements are discussed
Mode 3 - FIRE FIGHTING PHASE - To below.
maintain a specified AIR VELOCITY (2.0
m/sec) through the OPEN DOOR(S) onto
the fire floor with various other doors open.
CLASS "A" SYSTEMS - ESCAPE
PHASE - (MODE 2)
ALL pressurisation systems for SMOKE
CONTROL have a Detection Phase (Mode
1)
10
CLASS "B" SYSTEMS - FIRE FIGHTING
PHASE - MODE 3
11
CLASS 'C' SYSTEMS - ESCAPE PHASE
- (MODE 2)
Staircase Accom.
Open
Staircase Accom.
Fig. (7b) - Pressure Criterion
12
CLASS "D" SYSTEMS -ESCAPE PHASE
- (MODE 2)
Open
Staircase Accom.
Open
Staircase Accom.
Fig. (8b) - Pressure Criterion
13
CLASS "E" SYSTEMS - ESCAPE
PHASE - (MODE 2)
Open
Staircase Accom.
Open
Open
To maintain a pressure difference of
+10Pa across the closed fire door with the
final exit and two other doors (Fig. 9b)
Fire Floor
+ 10 Pa
Open
Staircase Accom.
14
3.3 EXHAUST AIR SYSTEM the size of duct (cross-sectional area) can
cause problems.
The EXHAUST AIR system must be de- d) Mechanical, powered extract from the
signed to provide a LOW RESISTANCE unpressurised space. This can be
route for the supply air to leave the building achieved by either:-
via the fire floor. i) Providing the vertical duct Fig 10 with an
exhaust fan selected to both overcome
This can be achieved by one of four methods:- the resistance of the duct work and han-
dle the hot smoke. The size of the duct
a) Via the leakage provided by the window can then be reduced.
cracks on the outside of the building.
ii) By utilising any existing mechanical ex-
In practice this is unrealistic. The area pro- haust system from the unpressurised
vided is unlikely to be sufficient. spaces.
A powered exhaust system from the fire
b) Through automatically opened windows room could provide two incremental advan-
or vents around the perimeter of the tages.
building.
This is a possibility where the area con- 1) The exhaust fan would be selected to
cerned has sufficient outside wall space to overcome any resistance from the exhaust
accommodate the vent area necessary. vent or grill. The residue pressure in the
Operating Mode 2 would require almost 0.5 staircase, when the doors are open, would
m2 of vent area on every floor for each pres- be reduced, and with it the quantity of air
leaving the building via the final exit door -
surised staircase. on systems where this is specified as
OPEN. The result would be a reduced
c) The provision of a vertical duct through quantity of supply air to the system (see
the building with a damper arranged to also paragraph 5.6)
open automatically on the FIRE FLOOR.
See Fig 10.
2) The system can be designed to remove
This method is often the best solution more air than the pressurisation system is
although to ensure a low resistance path
supplying. This would tend to create a
negative pressure, in the fire area, relative
to the rest of the building ensuring that all
Powered Vent airflow through the building is towards the
fire area. Smoke will thereby be prevented
from entering unaffected parts of the build-
Natural Vent ing via unidentified leakage paths.
Mechanical exhaust may be the only way of
dealing with the high volumes of air exhaust
demanded by Class B, D and E System.
Damper 3.4 OPERATING LEVELS
The operating status of a pressurisation
system can be organised at 2 levels.
LEVEL 1
Plant OFF - except in an emergency
(SINGLE STAGE PRESSURE SYSTEM)
LEVEL 2
Plant ON - running continuously at RE-
DUCED capacity - except in an emergency.
Fig 10 - Exhaust System by Vertical Duct (TWO STAGE PRESSURE SYSTEM).
15
3.5 SPACES TO BE PRESSURISED
a) STAIRCASE ONLY
The SMOKE CONTROL system will provide
protection to the vertical part of the escape Accom.
route only. It should only be used when the
STAIRCASE is entered direct from the ac-
commodation or via a simple lobby (i.e. a Stairs
lobby without LIFTS, TOILETS or other pos-
sible air escape routes) Fig 11. Simple Lobby
Stairs
Fig 12 - Staircase With Lift Lobby
Lift
Lift
c) STAIRCASE, LOBBY & CORRIDOR Lobby
Extending the LOBBY pressurisation sys- Corridor
tem into the CORRIDOR using additional
outlets in the corridor Fig 13. Used only
where the construction of the corridor has a
fire resistance of 30 minutes or more. Stairs
Fig 13 - Stairwell With Lift Lobby & Corridor
d) LIFT SHAFT
Generally only used in Fire Fighting
(BS5588 Part 5). The LIFT LOBBY then
effectively becomes a simple lobby as far as
the staircase pressurisation system is con-
cerned. With the lift shaft pressurised there
is no escape path for the air via the lift shaft.
The STAIRCASE and LIFT SHAFT can be
pressurised using a common fan with sepa-
rate ducting.
16
CHAPTER 4
The design of any air movement system in- This established the DESIGN PRESSURE
volves an answer to the question:- levels of 50 Pa for operating MODE 1 - All
Doors Closed - of a system although re-
“How do I establish the AIR VOLUME duced pressures would be acceptable on
required to make this system work?” buildings of lower height.
With a Pressurisation System designed for
SMOKE CONTROL there is an initial ques- 4.3 SUPPLY AIR VOLUME
tion to be answered.
Having established the PRESSURE LEVEL
“What PRESSURE (or VELOCITY) do I required to hold back the smoke, the AIR
need to develop in the escape routes to VOLUME to be supplied to the escape route
hold back the smoke?” to develop this pressure can be calculated.
The answers to both these questions were Again, the formula for doing this comes from
provided as a result of research work by P.J. the work by HOBSON and STEWART.
Hobson and L. J Stewart in the U.K. during 1
n
the 1960’s and 1970’s (Ref 6). This work Q = 0.83 AEP
led directly to the publication of the U.K. Q = The volume of air required (m3/sec)
code of Practice for Pressurisation Systems AE = Leakage area from the space (m2)
- BS5588 Part 4 in 1978 (Ref 7), now super- P = Pressure differential (Pa)
seded by the current code of practice in n = Leakage factor
BS5588 Part 4:1998 (Ref 8).
For large leakage areas - Doors etc - n = 2
4.2 PRESSURE LEVELS For small leakage areas - Window cracks -
n = 1.6
Stewart and Hobson studied the factors
which can cause smoke to spread around a For the purpose of a Pressurisation System
building. As a result they were able to sug- designed to hold the smoke behind doors
gest guidelines for a Pressurisation System the formula becomes,
1
designed for SMOKE CONTROL. TABLE 3 Q = 0.83 AEP 2
details these guidelines.
5 8.5 8.0 25
25 8.5 10.5 25
50 8.5 13.0 50
100 8.5 19.5 50
150 8.5 29.5 50
Table 3 - Design Pressures
17
4.4 DOOR LEAKAGE AREA
The effective door leakage areas can be estimated by using the values given in TABLE
4 (Ref 7). These values only apply to the door types and sizes shown.
For single openings, one door, AE = nett free area of the opening.
For several openings, or doors, situated in PARALLEL around a pressurised space Fig 11.
AE = A1 + A2 + A3 + A4 ...
Lift Lift
A4 A3
Accomodation
Accomodation
A2 Lift A1
Lobby
+VE
Stairs +VE
For two doors in series more typical of a pressurisation system this simplifies to
Stairs
+VE A1 A2 A3
Although we can estimate the effective area Fig. 7 to 9 inclusive detail this later require-
for an escape route in this way, there are al- ment.
ways, in any building, other ‘leaks we are
not aware of’.
This pressure criterion is likely to produce
To accommodate these, the air supply vol- the highest demand for supply air on Class
ume calculated should be increased by at C systems, and occasonially on Class E & F
least 50%, stipulated by the CODE OF systems using power exhaust from the Fire
PRACTICE. Floor.
19
4.6 REQUIREMENTS OF A
PRESSURISATION SYSTEM
b) A Pressurisation System designed to Here then are the simple tools which allow
protect an escape route which is to be us to establish the AIR SUPPLY and EX-
used both for MEANS OF ESCAPE HAUST requirements of a PRESSURISA-
and FIRE FIGHTING is required to TION SYSTEM for SMOKE CONTROL.
achieve a VELOCITY of 2 m/sec They will apply to any combination of
through the open door on the fire floor PRESSURE or DOOR VELOCITIES
under the conditions illustrated by Fig SPECIFIED IN THE VARIOUS NATIONAL
6, in addition to the requirements Codes of Practice.
specified in (a) above.
20
CHAPTER 5
Fan Selections
5.1 WORKED EXAMPLE
The best method for establishing the re- a) The addition of 50% to the calculated air-
quirements of SUPPLY FANS for pressuri- flows at MODE 1.
sation systems is to select the fans for a b) Assuming that, when the door(s) as
typical pressurised staircase. specified, are open (MODE 2 AND
The example chosen is perhaps the sim- MODE 3), the pressure of 50 Pa is main-
plest form of a Pressurised Staircase for tained in the staircase and lift lobbies.
Smoke Control, and as such may be unreal. However, buildings in general, and stair-
However, using a simple example, it is cases in particular are notoriously ‘leaky’.
easier to determine and highlight the fan Equally, incorrect and ill-fitting doors would
requirements. increase the airflow demands. Over sizing
Example: A Staircase, Fig 16 serves 6 the supply fan at the design stage can prove
floors. There is a double door to outside beneficial during commissioning.
at ground level and single doors into the This highlights one of the requirements
accommodation on each floor. of a supply air fan - that it’s air volume
output be easily adjustable on site. Axial
5.2 CALCULATION PROCEDURE flow fans with variable geometry
impellers meet this requirement.
A complete and detailed calculation proce-
dure, with worked examples, is outlined in 5.3 EXHAUST AIR FANS
BS5588 Part 4:1998. Designers should fol-
low this approach when seeking approval The sizing of any EXHAUST AIR FANS will
for their schemes. also be determined from the system calcula-
tion procedure. These fans must be capable
With the possible exceptions outlined in of handling hot air smoke and comply with
paragraph 4.5(a) the size of the supply fan BS7346 - Part 2 (Ref 2) or similar testing
for pressurisation system is determined by standard.
the velocity through the open door (s) -
MODE 2 or MODE 3. The airflow
requirments of MODE 1 and are then BS5588 - Part 4: 1998 recommends that
achieved by either:- exhust air fans be capable of surviving
a) Wasting the excess air to atmosphere or 600°C for 2 hours in unsprinklered buildings
300°C for 2 hours in sprinklered buildings.
b) Reducing the volume flow of the fan.
21
5.4 PRESSURISED STAIRCASE ONLY a) To calculate pressure required in
stairwell to exhaust 1.2 m3/sec to atmos-
MODE 1 (B5588 Part 4 - 1998) phere via fire floor (see fig 17).
ALL SYSTEMS ALL DOORS CLOSED
Area of single leaf door = 2.0 x 0.8 = 1.6 m2
Area of exhaust vent = 1.2/2.5 = 0.48 m2
Double Exhaust
Doors Vent
Accomodation
--1/2 --11/2/2
Stairs AE = 1 + 1 = 1 + 1
6 Floors
A12 A22 1.62 0.482
Fig 16- Plan of Staircase
= 0.46 m2
A = 1 x double door at 0.03 = 0.03 m2
6 x single doors at 0.01 = 0.06 m2 2 2
P1 = Q = 1.2
0.09 m2 0.83 x AE 0.83 x 0.46
1/
Q = 0.83AEP 2
= 0.83 x 0.09 x 50 /2
1
= 0.53m3/sec = 10.01 Pa
Increase by 50% + 0.26 m3/sec This is more than covered by 50 Pa assumed.
0.79 m3/sec b) To calculate area of Pressure Relief.
Say 0.80 m3/sec
MODE 2 (BS5588 Part 4 - 1998) Quantity of air to be wasted = (2.0 - 0.8)
CLASS A SYSTEMS ESCAPE = 1.2m3/sec
P0
MODE 2 CLASS E SYSTEM ESCAPE
PRESSURE CRITERION
Door
Closed Open
22
a) To calucluate the airflow through a) To calculate airflow through open fire
open door to outside with 10Pa floor door.
pressure in stairwell.
A = Area of single leaf door
1/
Q = 0.83 AE P 2 = 2.0 x 0.8 m = 1.6 m2
V = Velocity through door = 0.75 m/sec
= 0.83 x 1.6 x 10 = 4.20 m3/sec Q = A x V = 1.6 x 0.75 = 1.20m3/sec
b) To calculate airflow through open
b) To calculate pressure required in
accommodation door with 10Pa pres- stairwell to exhaust 1.2 m3/sec to atmos-
sure in stairwell an assumed and phere via fire floor. (Fig 18)
0.22m2 area of leakage from each floor.
Area of single leaf door = 1.6 m2
(see Fig 17 and note below).
Area of exhaust vent from fire floor = 0.48 m2
-1/2 -1/2
AE = 1 + 1 = 1 + 1
2 2
-1/2 -1/2
A 1
2
A2
2
1.6 0.22 AE = 1 + 1 = 1 + 1
A12 A22 1.62 0.482
= 0.217 m2 = 0.458 m2
1
Q = 0.83 AE P /2 2 2
1/
2 P1 = Q = 1.2
= 0.83 x 0.217 x 10 0.83 x AE 0.83 x 0.458
= 0.57 m3/sec
= 10.01 Pa
Note: The accommodation on each floor is assumed to (Say 10 Pa)
be an open plan office - 900 m2 in area x 3m high. From
Table D3 in BS5588 - Part - 1998, using average c) To calculate airflow through open
leakage via the floors and loose leakage walls, the door to outside with 10Pa Pressure in
leakage area from the accommodation on one floor
would be 0.22m2.
stairwell.
1/
c) To calculate airflow required to Q = 0.83 AE P 2 1/2
= 0.83 x 1.6 x 10 = 4.20 m3/sec
maintain the Pressure Criterion.
Through open exit door = 4.20 m2/sec d) Airflow through open accommodation
door with 10Pa pressure in stairwell -
Through (2 off) open (from PRESSURE CRITERION as above)
accommodation doors = 1.14 m3/sec = 0.57 m3/sec
Add MODE 1 = 0.80 m3/sec
e) To calculate airflow required to main-
6.14 m3/sec tain the VELOCITY CRITERION
2. VELOCITY CRITERION
Through open fire floor door = 1.20m3/sec
Through open exit door = 4.20m3/sec
Through open accommodation door
= 0.57m3/sec
Open Add MODE1 = 0.80m/sec
= 6.77m3/sec
Exit vent
A= Q
V = 0.75 m/sec 2.5 Note Velocity Criterion dominates
P0 P1
f) To calculate area of Pressure Relief
P0 Quantity of air to be wasted
= (6.767-0.800) = 5.97m3/sec
Area of Pressure Relief
= Q = 5.97
Door 1/ 1/
Open 0.83 x (P) 2
0.83 x (50) 2
= 1.02m2
Staircase Accomodation
Fig 19
23
MODE 3 - CLASS B SYSTEMS - FIRE c) To calculate volume air required to
FIGHTING maintain 2.0 m/sec through open door
(BS5588 Part: 4 - 1998) on fire floor.
24
5.6 POWERED EXHAUST
Curves Pa-1, Pa-2 and Pa-3, also shown
The air duty requirements detailed at Para- on the FAN CHARTS, are the system
graph 5.5 are calculated with the pressuris- resistance curves for MODES 1, 2 and 3
ing airflow exhausting from the fire floor respectively.
through a natural vent. This results in an 5.7.1 Pressurised Staircase - Escape Only
increased airflow through the open fire door
to outside. CHART 1 illustrates a fan engineering solu-
tion to this problem viz:-
Fan powered exhaust would eliminate the a) The supply air fan size is determined by
need for this increase in the supply fan duty. the air duty requirements of MODE 2 (2.0
The exhaust air fan could be selected to m3/sec). Fan selected is Woods JM Aerofoil
produce zero pressure on the fire floor. - 40 JM/16/2/28. At 2.0 m3/sec this fan will
Hence, for the example shown, the supply develop a pressure of 250 Pa, leaving 200
air fan would be sized to deliver 7.2 m3/sec Pa available to overcome the resistance of
for MODE 3 (reduced from 9.14 m3/sec). the air system.
The exhaust air fan would need to handle b) Without a PRESSURE RELIEF
3.2 m3/sec. DAMPER, the fan selected would develop
about 360 Pa, (Point A) in the staircase with
The amount of air to be wasted via the pres-
all doors closed (MODE 1). This is well
sure relief damper would fall to 6.4 m3/sec,
above the 60 Pa allowable and would be
thereby reducing the size of the PRES-
unacceptable.
SURE RELIEF DAMPER from 1.43 m2 to
1.09 m2. c) The calculations show that to maintain 50
Pa maximum, 1.2 m3/sec of the supply air
5.7 SUPPLY FAN UNIT SELECTIONS has to be wasted through a pressure relief
(Natural Exhaust) damper 0.204 m2 in area (Dimension X).
However to allow for the change in the fan
These take the form of fan performance
working point, (Point B), when all doors are
charts onto which the calculated airflow re-
closed the air wasted will increase to 2.25
quirements have been plotted.
m3/sec requiring a damper 0.256 m2 in area
(Dimension X + Y).
600 Woods JM Aerofoil
40JM/16/2/28
500
Pa - 1
400
Static Pressure (Pa)
Point A
Pa - 2
Chart 1 300
MODE 2 - CLASS A
200
100 Point B
MODE 1
50 50
X Y
0 1 2 3
Volume Flow (m3/sec)
25
This excess becomes of increased impor- d) To achieve a reduction in the area of the
tance on system with high resistance Pressure Relief Damper the FAN SPEED
ductwork systems, and demonstrates the could be reduced to 695 rpm providing more
need for supply fan to have steep VOL- than sufficient airflow to meet the Dectection
UME/PRESSURE performance charac- Phase (Mode 1) requirement.
teristics (Axial Flow Fans in preference
As Chart 2 shows, at this lower speed the
to Centrifugal).
fan will develop a much reduced pressure,
and there could be situations when this
5.7.2 Pressurised Staircase - would be insufficient to meet the require-
Fire fighting & Escape ments of the system.
500
Pa - 1
14
400
40
Static Pressure (Pa)
Pa - 3
Chart 2 rpm
MODE 2
300 (CLASS E) MODE 3
(CLASS B)
200
69
5
rp
100 MODE 2
m
MODE 1 (CLASS A)
50 50
X Y
0 1 2 3 4 5 6 7 8 9 10 11 12
Volume Flow (m3/sec)
a) The supply air fan size is determined by This highlights a possible danger of us-
the air duty requirements of MODE 3 ing speed control as a means of meeting
(9.14 m3/sec). Fan selected is Woods JM the demands of a pressurisation system
Aerofoil - 80JM 25/4/9/32. At 9.14 m3/ and should be used with care.
sec this fan will develop a pressure of
CHART 3 illustrates a second solution to the
about 300 Pa,, leaving 250 Pa available
problem described under paragraph 4.7.2.
to overcome the system resistance.
Here the size of the Pressure Relief Damper
b) Without a PRESSURE RELIEF DAMPER
is reduced by operating two Woods JM
the fan would stall when all the doors
Aerofoils 50 JM/20/2/6/30, (smaller fans), in
were closed resulting in an indetermi-
parallel. Both fans would run to provide the
nable pressure in the staircase but a
requirements of Mode 3 - (9.14 m3/sec).
pressure likely to be above 60 Pa
One fan only would be run during the
maximum.
Dectection Phase (Mode 1)
c) To maintain 50 Pa Maximum, 8.34 m3/
The amount of air to be wasted would now re-
sec (Dimension X) needs to be wasted
duce to 4.8 m3/sec (Dimension X + Y) demand-
through a damper 1.43 m2 in area. This
ing a pressure relief damper 0.82 m2 in area.
will increase to 1.75 m2 when allowance
is made for the change in the fans work- The fan speed is maintained eliminating the
ing point (Dimension X + Y). dangers inherent with speed reduction.
26
600 Woods JM Aerofoil
Pa - 2
50JM/20/2/6/30
Two fans in parallel
Pa - 1
500
200
100 MODE 2
MODE 1 (CLASS A)
50 50
X+Y
0 1 2 3 4 5 6 7 8 9 10 11 12
Volume Flow (m3/sec)
CHART 4 illustrates a third possible solution the example shown the air to be wasted
to the problem described in Paragraph 4.7.2 would be 2.0 m3/sec (Dimensions X + Y)
and would demand a damper 0.34 m2 in
The 9.14 m3/sec required for MODE 3 is met by area.
using a Woods Varofoil - variable pitch in motion
fan - 80KG40A-4-6. The air duty requirements of Again the fan speed is maintained elimi-
MODES 1 and 2 are then achieved by reducing nating the dangers inherent with fan
the pitch angle of the fan. speed reduction. As an added advan-
tage, using Varofoil, the fan will tend to
The size of the Pressure Relief Damper is correct for any unidentified leakage etc
now greatly reduced, but not eliminated. In in the staircase and system.
700
Pa 1
Pa 2
600
500 Pa 3
p sf - Fan Static Pressure
Chart 4
400
300 Mode 3
CLASS B
Mode 2
CLASS E
200
27
CHAPTER 6
The requirements of both SUPPLY and EX- Within the limits imposed by the general re-
HAUST fans in Pressurisation Systems can quirements of a supply air fan, providing for
be listed as follows:- variable air duty can best be achieved by
a) Supply Air Fans must be capable of vol- one of the following methods.
ume variation to meet the demands of a) A Constant Speed - Single fan with
all three operating modes of the system.
pressure relief damper.
This is discussed in more details under
paragraph 6.2 b) Constant Speed - Twin fan with pres-
b) Supply Air Fans must be capable of duty sure relief damper - varying the number
changes on site, to compensate for any of fans operating.
under or over sizing inherent in the de-
c) Variable Speed Fans.
sign procedure.
c) Supply Air Fans should have a steep d) Constant Speed - Variable pitch in mo-
volume/pressure curve to limit the air tion fans (Varofoil).
wastage through the pressure relief
Constant speed fans ensure that the maxi-
damper - and hence its size.
mum pressure capability of the fan is avail-
d) Supply Air Fans should maintain a high able at all three operating modes of the
pressure capability ensuring that suffi- system.
cient pressure is always available to the
system. The use of variable speed fans
to obtain the air volume changes needs With variable speed fans this will not be
expert advice.
thecase. The pressure developed by the
e) Exhaust Air Fans must be capable of fan varies with the speed squared. If the
handling the hot fire smoke at 600 °C in speed of the fan is halved to achieve the
unsprinkerled, and 300°C in sprinkerled
lower air duty requirements of MODES 1
buildings. They should comply with
and 2, then the pressure development is re-
BS7346 Part 2 or similar testing
standard. duced by four times.
28
6.3 STAND-BY FANS Since 1984 Quality Control throughout the
British fan manufacturing industry has im-
The need for STAND-BY FANS in a Pres- proved with the introduction of a BS EN ISO
surisation System is a function of two con- 9001 (formally BS5750) registered firm
siderations. scheme. One of the important require-
ments of all fan equipment used in FIRE
a) The degree of fire risk. SAFETY systems is that it should be manu-
b) The reliability of the fan equipment. factured by companies who are registered
and certified to BS EN ISO 9001. Building
The degree of fire risk must of course be Control Authorities should insist on these
determined by the relevant fire and building STANDARDS.
control authorities.
The reliability of the fans is under the control BS5588: Part 4: 1998 Specifies that
of fan manufacturers and building owners, STANDBY FANS and equipment be pro-
the latter having responsibility for ensuring vided on all pressurisation systems de-
correct and adequate maintenance. signed for smoke control - both Supply
Fans and Exhaust Fans.
Hobson and Stewart investigated the reli-
ability of fan equipment as part of their re- Axial flow fans can be mounted in SERIES
search (Ref 6). In 1972 they found that or PARALLEL to provide this STAND-BY
AXIAL FLOW FANS - direct driven - had a requirement.
failure rate of 0.052 per year and a reliabil-
ity of 94.9%. A system using STAND-BY 6.4 CONCLUSIONS
FANS to provide 100% backup would in-
crease this reliability to 99.8%. For com- Smoke control using pressure differential
parison the same figures for belt driven has been described as -
CENTRIFUGAL FANS were 0.5 failures per
year! 50% and 91% reliability respectively. Simply in Concept but Difficult in Practice
(Ref 11).
They concluded that direct driven AXIAL
FLOW FANS were more reliable, and the The discussion in this paper shows that cur-
need for STAND-BY FANS was not objec- rent fan engineering technology is well able
tively necessary to achieve a high level of to provide the requirements of both SUP-
plant reliability in the event of a fire. PLY and EXHAUST AIR FANS of a PRES-
SURISATION SYSTEM for SMOKE
However, in spite of these findings, they rec-
ognised that, in FIRE SAFETY SYSTEMS,
‘“RELIABILITY is of PARAMOUNT IMPOR-
TANCE” and warranted the provision of
STAND-BY FANS.
29
APPENDIX ONE
References
1. J.A. Wild Fans for Fire Smoke Venting Woods Air Movement Ltd
Technical Paper WTP20
June 1989 (revised Nov. 1990)
This document has been produced as a general guide and its contents should not be construed as any
representation on our part as to the quality or fitness of our products for any particular purpose, nor as
providing advice on the design of fire and smoke control systems. You are recommended to consult your
professional advisers on matters relating to the design and installation of any such systems.
30
Ref: WTP 41 31