ShortCircuitCalculations Reactance
ShortCircuitCalculations Reactance
By Wayne L. Carey
January 4, 2006
Short-Circuit Calculations
Introduction
Utility
The first step in analyzing a power system is to get the data for the
power available at the site, the utility data. This data can be obtained
from the power company. When calling the power company, explain
the type of information you need and ask for the engineering
department. It may be helpful to explain why you need the
information.
The power company will be able to supply this information for the point
in the power system where their responsibility for the power system
ends and the customer’s responsibility starts. A common location for
this point is the secondary of a pole or pad mounted transformer. If
the customer is responsible for the transformer, the transition point
would be the primary of the transformer. Sometimes a pole mounted
disconnect will be the transition point. The power company will specify
where in the system their responsibility ends.
The data needed is the line to line voltage (VLL), short-circuit kVA
(kVASC), and X/R. Obtaining the voltage is simple enough. Short-
circuit kVA is the power available at a bolted three phase fault. Bolted
means all three phases connected together with no added impedance.
2
X/R is the ratio of reactance to resistance in the supply. Short-circuit
kVA and X/R may need to be derived from other data.
3 ∗ I SC ∗ VLL
kVA SC = (Eq. 1)
1000
3 ∗ I SC ∗VLN 3 ∗ I SC V LL 3 ∗ I SC ∗VLL
kVA SC = = ∗ = (Eq. 2)
1000 1000 3 1000
When neither X/R nor power factor are specified for the utility, it is
usually safe to assume the impedance of the utility is all reactance and
X/R is infinite. Unless there are many miles of transmission line, the
impedance of the utility will be mainly reactance in the generator. This
is all the data needed for the utility. From this data, the short-circuit
calculation program can be used to calculate impedance (Z),
resistance (R), and reactance (X). This data can also be calculated
manually.
VLL2
Z= (Eq. 4)
kVASC ∗1000
3
Resistance and reactance are then calculated from the impedance
using X/R.
Since: Z= X 2 + R 2 (Eq. 5)
Z
R= (Eq. 5a) And X = R ∗ ( X / R) (Eq. 5b)
1 + ( X / R)
2
Resistance and reactance are calculated at the voltages for the points
in the circuit where the short-circuit currents are calculated. For
example, even though the utility voltage may be 69 kilovolts (kV), if
the short-circuit currents are being calculated further down the circuit
where the voltage is 2400 volts, the resistance and reactance will be
calculated at 2400 volts. The computer program initially calculates
resistance and reactance for the utility at the utility voltage. As the
program works down through a circuit, encountering transformers, it
converts the resistance and reactance to the new voltage by
multiplying by the ratio of the voltages squared.
V22
R2 = R1 ∗ (Eq. 6)
V12
Transformers
% Z ∗V 2 %Z V 2
Z = Or Z = * (Eq. 7)
kVA ∗100 ,000 100 VA
4
Resistance and reactance are then calculated from Z and X/R as they
were for the utility. Again, these resistances and reactances are for a
short-circuit at the secondary of the transformer. If the short-circuit is
at a point further down the circuit and after another transformer, the
voltage at the short-circuit should be used in equation 7. Alternatively,
the calculated resistances and reactances can be converted to the new
voltage by multiplying by the ratio of the voltages squared.
Z ps = Z p + Z s (Eq. 8a)
Z pt = Z p + Z t (Eq. 8b)
Z st = Z s + Z t (Eq. 8c)
5
If all impedances are to be at the primary voltage, Xst and Rst must be
transferred.
Cables
The minimum data needed for cables is size, length, voltage rating,
and type. Size, voltage rating, and type of cables is embossed into the
jacket. Size and type of aerial cable may be shown on a drawing or
listed on an invoice. Lengths may be measured, determined from mine
maps, or paced off and estimated. Some cables such as types SHD
and MPF have different constructions for different voltage ratings and
the voltage rating will need to be specified. It will be embossed in the
cable jacket. It should be noted if more than one cable is used in
parallel. The spacing of conductors of aerial cable will affect
inductance. The computer program uses a default spacing of three
feet. If the spacing is different than three feet, it should be noted. The
computer program has stored values for resistance and reactance per
thousand feet for most commonly used cable types. This data is also
available in cable standards and manufacturer’s specifications.
Resistance is specified at ambient temperature.
R2 = R1 [1 + α ( T2 − T1 ) ] (Eq. 9)
6
be the maximum available current. If the cable is initially at a
temperature between ambient and its rated operating temperature
and a short-circuit occurs, it is possible that the cable will reach a
higher final temperature at a current lower than the maximum
available current. The current depends on the cable’s resistance, but
the resistance depends on the current. Therefore, the computer
program calculates current that causes maximum temperature with an
initial temperature of ambient and with an initial temperature at one
degree increments up to the cable’s rated operating temperature. This
is one place where the power of the computer really comes in handy.
The computer program also uses the subtransient reactance
(discussed below) to calculate temperature after one cycle of short-
circuit. This temperature is used as the initial temperature along with
transient reactance in an additional calculation to calculate
temperature at the end of the short-circuit (when the circuit protective
device opens). The maximum available current calculated in the
computer program is actually the current that causes maximum
temperature.
1
X L = 0.02298 ∗ ln (Eq. 10)
GMR
ln ( spacing )
X new = X old 1 + (Eq. 12)
1
ln
GMR
7
Motors
Table 1
X PU ∗ V 2
X = (Eq. 13)
746 ∗ HP
8
reactance should be used in the calculation. A&CC does not include
motor contribution in minimum available short-circuit current. When
adding impedances working down through a circuit, the impedance of
a motor should be added in parallel with the total impedance up to the
point in the circuit where the motor contributes. This reduces the
impedance at that point. Adding impedances in parallel is most easily
done by first converting resistance and reactance to conductance and
susceptance, adding the conductances and susceptances, and
converting the conductance and susceptance back to resistance and
reactance. Conductance, susceptance, resistance, and reactance are
related by the following formulas.
R X
G= (Eq. 14a) −B = (Eq. 14b)
R2 + X 2 R2 + X 2
G −B
R= (Eq. 14c) X = (Eq.14d)
G + B2
2
G + B2
2
Where: R = resistance
X = reactance
G = conductance
B = susceptance
Generators
Generators are treated just like motors. They are specified by kVA,
subtransient reactance, and transient reactance. The kVA will be listed
on the generator nameplate. Table 2 lists typical values of reactance
for dc and four types of ac generators2. The four types are two-pole
turbine, four-pole turbine, salient pole with dampers and salient pole
without dampers.
Table 2
9
X PU ∗ V 2
X = (Eq. 15)
1000 ∗ kVA
Capacitors
V 2 ∗1.15
X = (Eq. 16)
kVAR ∗1000
Where: V = voltage
kVAR = kilovolt-amperes reactive
Rectifiers
0.95 ∗ VLL
I MIN = (Eq. 17)
2 ∗ Z MAX
This formula is used for AC and the DC output from a three phase
rectifier. The factor of 0.95 accounts for voltage fluctuations. The
maximum impedance is calculated from the maximum resistances and
reactances for all the elements in the circuit. For AC circuits, the
current is further reduced by multiplying by an arcing fault factor, KA.
This factor is listed in Table 3 for various voltages3.
10
Voltage (V) KA
V ≤ 480 0.85
480 < V ≤ 0.90
600
600 < V ≤ 0.95
1040
1040 < V 1.0
Table 3
For DC circuits the arc voltage depends on the current. First, the
current is calculated with Equation 17. If the calculated current is
greater than or equal to 600 amperes, the arc voltage is 60 volts. If
the calculated current is less than 600 amperes, the arc voltage is
calculated with the following formula4.
( 1842 − I )
V ARC = e
303
(Eq. 18)
The voltage is then reduced by the arc voltage and the available
current is recalculated.
V LL
I MAX − AC = (Eq. 19)
3 ∗ Z MIN
V LL
I MAX −DC = (Eq. 20)
2 ∗ Z MIN
11
Example
Figure 1
12
1. Starting at the utility, calculate the impedance using equation 4.
Remember to use the voltage at the short-circuit, 1040 volts.
V LL2 1040 2
Z = = = 0.0114 Ω
kVA ∗1000 95,000 ∗1000
Z .0114
R= = = 0.0021 Ω
1 + ( X / R) 1 + 5.23 2
2
1 1
X L = 0.02298 ∗ ln = 0.02298 ∗ ln = 0.105 Ω
GMR 0.0103
ln ( spacing ) ln (3)
X new = X old 1 + = 0.105 ∗1 + = 0.1304 Ω
1 1
ln ln
GMR
0.0103
1.04 2
X = 0.1565 ∗ = 0.0001 Ω
34 .5 2
13
voltages squared gives a maximum resistance of 0.0004 Ω. To
get the minimum resistance, the resistance at 75°C must be
converted to the resistance at 20 °C using Equation 9.
R75 0.0004
R20 = = = 0.0003 Ω
1 + α ( 75 − 20 ) 1 + 0.00393 * 55
% Z ∗V 2 6.08 * 1040 2
Z = = = 0.0066 Ω
kVA ∗100 ,000 10 ,000 * 100 ,000
The X/R ratio is not specified for the substation. A value of 4.9
can be assumed. Using this value and the impedance, find X and
R.
Z .0066
R= = = 0.0013 Ω
1 + ( X / R) 1 + 4.9 2
2
4. Next is the 6000 feet of number 2/0, 15 kV, mine power feeder
cable. From manufacturer’s specifications, reactance of 1000
feet of this cable is 0.038 Ω. The reactance of 6000 feet at 1040
volts is calculated as follows:
1040 2
X = 6 * .038 * = 0.0016 Ω
12 ,470 2
1040 2
RMIN = 6 * 0.0792 * = 0.0033 Ω
12 ,470 2
5. The power center is the next component in the circuit. First find
the impedance.
14
% Z ∗V 2 5 * 1040 2
Z = = = 0.0401 Ω
kVA ∗100 ,000 1350 * 100 ,000
The X/R ratio is not specified for the substation. A value of 4.9
can be assumed. Using this value and the impedance, find X and
R.
Z 0.0401
R= = = 0.0080 Ω
1 + ( X / R) 1 + 4.9 2
2
6. Last is the 850 feet of number 2/0, 2 kV, shielded cable. From
manufacturer’s specifications, reactance of 1000 feet of this
cable is 0.031 Ω. The reactance of 850 feet is 0.85 * 0.031 =
0.0264 Ω. From manufacturer’s specifications, resistance of this
cable at 20°C is 0.0839 Ω per 1000 feet. The minimum
resistance (RMIN) of 850 feet is 0.85 * 0.0839 = 0.0713 Ω. The
maximum resistance is the resistance at the 90 °C rated
operating temperature of mine power feeder cable.
Table 4
Z MIN = 2
RMIN + X 2 = 0.0863 2
+ 0.0851 2 = 0.1212 Ω
Z MAX = 2
RMAX + X 2 = 0.1069 2
+ 0.0851 2 = 0.1366 Ω
15
0.95 ∗ K AV LL 0.95 * 0.95 * 1040
I MIN = = = 3436 Amperes
2 ∗ Z MAX 2 * 0.1366
V LL 1040
I MAX = = = 4954 Amperes
3 ∗ Z MIN 1.732 * 0.1212
Conclusion
16
References
17