SINAMICS G130 FP 1008 Eng
SINAMICS G130 FP 1008 Eng
SINAMICS G130 FP 1008 Eng
SINAMICS
Main menu
Local
M
7 8 9 0 Remot
e
4 5 6 .
[610]
PROFIBUS
p0700 = PROFIdrive
[700-710]
p1000 = PROFIdrive
8
[621-623]
p0700 = TM31
p1000 = TM31
(optional) [630-635]
p0700 = terminals CU
p1000 = TM31
Chapter of
[651]
Operating
Instructions (OI)
10 9
Faults/ Monitoring Technology Protective
Diagnosis alarms functions Functions controller functions
Function diagram -
[901] [904] [902-903]
number
1 2 3 4 5 6 7 8
Overall view A5E00332118A AE Function diagram
- 010 -
13.08.08 SINAMICS G130
Control via operator panel
(LOCAL mode)
AOP30
Switchover during
I LOCAL operation can be inhibited
REMOTE
via the AOP settings
O Jog
p0806
Inhibit master control
0: REMOTE
RS232
1: LOCAL
&
0: REMOTE
r0807.0 1: LOCAL
Speed setpoint
[700.1]
"LOCAL" control
1 2 3 4 5 6 7 8
Drive control A5E00332118A AE Function diagram
- 610 -
Control via operator panel (LOCAL mode) - Chapter 6 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Communication via PROFIdrive
PROFIBUS
Slave address
p0918 Selection of
standard message frame
Input of the slave address PZD 1 PZD 2 PZD 3 PZD 4 PZD 5 PZD 6 PZD 7 PZD 8 PZD 9 PZD 10
p0922
-S1 DP ADDRESS Standard speed controller message frame
2
1 STW1 NSOLL_A Setpoint message frame [622]
0 Storage p0922=1 2
ZSW1 NIST_A Actual value message frame [623]
1 2 4 8 16 32 64 SET
1)
r2054: 0=OFF
Standard message frame PCS 7
1=no connection
6
2=baudrate detected STW1 NSOLL_A unused unused unused unused
3=cyclic connection to master p0922=352 6
ZSW1 NIST_GLATT IAIST_GLATT MIST_GLATT WARN_CODE FAULT_CODE
4=cyclic data OK
1 2 3 4 5 6 7 8
Communication via PROFIdrive A5E00332118A AE Function diagram
- 621 -
General - Chapter 6 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Control via PROFIdrive (REMOTE mode)
Control word
r2090.2
p0848 No rapid stop (no OFF3)
r2090.3
Receive message frame p0852 Enable operation
r2090.4 [610.4]
PZD1 p1140 Ramp-function generator enable
r2050[0] r2090.5
STW1 p1141 Start ramp-function generator
r2090.6
p1142 Enable speed setpoint
r2090.13
p1035 Motor potentiometer up (MOP UP)
[630.1]
r2090.14
p1036 Motor potentiometer down (MOP DN)
1)
PROFIdrive setpoint [630.1]
1)
4000h = 100% = (p2000) default: n_max
1 2 3 4 5 6 7 8
Control via PROFIdrive A5E00332118A AE Function diagram
- 622a -
Receive p0700 = 70001 / 70004 - Chapter 6 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Control via PROFIdrive and terminal block (REMOTE mode)
Control word
TM31
X530
1 DI 4 r4022.4 0=coast down (OFF2) [610.4]
p0845
1=no coast down
2 DI 5 r4022.5 0=fast stop (OFF3)
p0849
1=no fast stop
3 DI 6 r4022.6 0=external fault 1
p2106
1=no external fault
4 DI 7 r4022.7
5 M1
1) 6 M
1)
1 2 3 4 5 6 7 8
Control via PROFIdrive and terminal block TM31 (optional) A5E00332118A AE Function diagram
- 622b -
p0700 = 70004 - Chapter 6 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Status word 1 (ZSW 1) Signal list Selection of the transmit Transmit telegram
message frames
.0 Ready to start Temperature motor r0035
.1 Ready to run Power section overload I2T r0036 PZD 1
.2 Enable operation Speed setpoint before filter r0060 1) 2)
Status word 1 (ZSW1) r2089 [0] p2051[0]
.3 Fault Motor speed r0061
.4 OFF2 not active Speed setpoint after filter r0062
.5 OFF3 not active Actual speed after smoothing r0063
PZD 2
.6 Start block System deviation speed controller r0064 Actual speed value 1) 2)
.7 Warning Slip frequency r0065 (NIST_GLATT)
r0063[1] p2051[1]
.8 No setpoint-actual value deviation Frequency setpoint of Uoff r0066
.9 PZD master control requested Maximum output current r0067
.10 Reference value reached r0068 PZD 3
1) 2) IAIST_GLATT
.11 M/I/P limitation not active Actual DC link voltage value r0070 Selection per signal list r0068[1] p2051[2]
.12 - Converter output voltage r0072
.13 Warning overtemp. motor (none) Field-generating actual current r0076
.14 Clockwise Torque-generating actual current r0078
PZD 4
.15 Warning overtemp. converter (none) Total speed setpoint r0079 1) 2) MIST_GLATT
Actual torque r0080 Selection per signal list r0080[1] p2051[3]
Actual active power r0082
r1119
Speed setpoint speed controller r1438 PZD 5
1) 2) PIST_GLATT
Current fault code r2131
Current alarm code r2132
Selection per signal list r0082[1] p2051[4]
Input value for analog inputs r4055
Actual temperature (TM31) r4105
PZD 6
Status word 1 (ZSW1) r2089 [0] 1) 2) FAULT_CODE
Status of digital inputs on TM31 r4022 Selection per signal list r2131 p2051[5]
Status of digital outputs on TM31 r4047
2)
Factory setting: transmit message frame p0922 = 999 with default assignment as in diagram
1 2 3 4 5 6 7 8
Control via PROFIdrive A5E00332118A AE Function diagram
- 623 -
PROFIdrive transmission - Chapter 6 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Fixed setpoint bit 1
Fixed speed
Setpoint control Fixed setpoint bit 0 setpoints
0 00
p1001 (300 rpm) 01 r1024
p1002 (600 rpm) 10
1)
p1003 (1500 rpm) 11 Main setpoint
p1070
OFF 0
Motor potentiometer
(MOP)
r1024
Motor potentiometer up
r1050
r1050
Motor potentiometer down r1073 r1078
Setpoint input [610.4]
r2050[1]
r4055
Normalization
Additional 1)
-X521 Scaling setpoint
1
AI 0+ p2000 p1075
Analog input 0 [635] r4055[0]
OFF 0
AI 0-
2
r1024
r1050
r1077
1)
Default assignment of the setpoint selection depending on p1000 r2050[1]
1 2 3 4 5 6 7 8
Speed setpoint selection A5E00332118A AE Function diagram
- 630 -
Setpoint input (REMOTE mode) - Chapter 6 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Control via terminal block (REMOTE mode)
TM31
Default setting Control word Setpoint control
X520
1 DI 0 r4022.0
p0840 0=OFF (OFF1)
1=ON
2 DI 1 r4022.1
p1035/p1020 1=motorized potentiometer increase (MOP UP)
3 DI 2 r4022.2
p1036/p1021 1=motorized potentiometer lower (MOP DN)
[630.1]
4 DI 3 r4022.3
p2104 Acknowledge faults, reset
(0->1)
5 M1
1=fixed speed setpoint selection bit 0 (FSW_0)
1) 6 M
X530
1 DI 4 r4022.4 0=coast down (OFF2) [610.4]
p0845
1=no coast down
2 DI 5 r4022.5 0=fast stop (OFF3)
p0849
1=no fast stop
3 DI 6 r4022.6 0=external fault 1
p2106
1=no external fault
4 DI 7 r4022.7
5 M1
1) 6 M
1)
Remove jumper between M1 and M or
M2 and M when external 24 V DC supply
is applied
1 2 3 4 5 6 7 8
Control via terminal block TM31 (optional) A5E00332118A AE Function diagram
- 631 -
p0700 = 70002 - Chapter 6 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
1) 3) 3)
TM31.AI_char. x1 TM31.AI_char. x2
TM31.AI_type -20.000...+20.000 (V/mA) -20.000...+20.000 (V/mA)
V I S5.0 AI 0 p4057[0] (0.000) p4059[0] (0.000)
V I S5.1 p4056[0] (0)
Offset
X521.1 -20.000...20.000 TM31.AI_act U/I
p4063[0] (0.000) 0,2 AI 0 TM31.AI_char. y2 y [%]
r4052[0] -1000.00...+1000.00 %
S5.0 + y2
A + 3 p4060[0] (0.00)
3) x y
AI 0 4mA 4,5
+ 3) x1 x2 x
X521.2 D TM31.AI_char. y1
- -1000.00...+1000.00 % y1
p4058[0] (0.00)
Scaling
Analog input
wirebreak
F3505
TM31.AI_response threshold
0.0...20.00 mA
p4061[0] (2.0)
1)
0: Voltage input (0 to +10 V)
2: current input (0 to +20 mA)
3: current input (4 to +20 mA) monitored
4: voltage input (-10 V ... +10 V)
5: current input (-20 mA ... +20 mA) TM31.AI_T_filtering
AI 00.0...1000.0 ms
p4053[0] (0.0)
3)
2)
Default assignment of the scaling depending on p4056
TM31.AI_act_value
p4056 p4057 p4058 p4059 p4060 AI 0
1 2 3 4 5 6 7 8
Speed setpoint input TM31 (optional) A5E00332118A AE Function diagram
- 635 -
Setpoint input via AI 0 (scaling of the analog inputs) - Chapter 6 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Status of digital inputs
r0722
CU320
Default setting Control word Setpoint control
X122 p1035/1020
r0722.0 3)
1 DI 0 0=OFF (OFF1)
p0840 1=ON
r0722.1 3)
2 DI 1
p1035/p1020 1=Motor potentiometer up (MOP UP)
r0722.2 3)
3 DI 2
p1036/p1021 1=Motor potentiometer down (MOP DN)
4 DI 3 r0722.3 Acknowledge faults, reset [630.1]
p2104 (0->1)
5 M1
1) 6 M
10 DI/DO 10
P24 p0740 1
11 DI/DO 11 r0722.11 0=external alarm 1
p2112 1= no external alarm
12 M
X132
1 DI 4 r0722.4 0=coast down (OFF2)
p0845 1=no coast down
2 DI 5 r0722.5 0=fast stop (OFF3)
p0849 1=no fast stop
r0722.6 [610.4]
3 DI 6 0=external fault 1
p2106
1=no external fault
4 DI 7 r0722.7
5 M1
1) 6 M
2)
7 DI/DO 12 r2138.7
Acknowledge fault p0742
8 DI/DO 13
P24 p0743 1
1)
9 M Remove jumper between M1 and M or M2 and
M when external 24 V DC supply is applied
10 DI/DO 14
P24 p0744 1
2)
11 DI/DO 15
P24 p0745 1 This output is always parameterized
regardless of p0700
12 M
3)
These inputs are only parameterized
when p0700 = 70003
1 2 3 4 5 6 7 8
Control via terminal block CU320 A5E00332118A AE Function diagram
- 651 -
p0700 = 70003 - Chapter 6 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Setpoint channel, closed-loop
control, motor Gating unit
Closed-loop control and limitation
Udcl(act)
Setpoint channel [706]
r0070
Ua
Current limit r0072
p0640
Torque limitation
Converter control
[610.7]
Speed limitation
Minimum speed Speed
p1080 n/f(max,pos.DR) nLimit_pos
Ramp controller
p1082 p1083
generator
Speed setpoint r1114 r1119 r1150 x Isq Asyc.
[610.6] -1 mot. 3~
y
n_set –
Setpoint inversion -1 nLimit_neg
Skip speed n/f(max,neg.DR) p1086
p1082 n_act
Ramp-up time Ramp-down time
p1120 p1121 Iset
[701] [702] [703] Starting current - flux
calculation
Technology controller
[705] [710]
n/f(act)
r0063
Set
+
+
Act
f(out)
r0066
[904]
+
Slip frequency
r0065 i(act)
Motor model r0068
1 2 3 4 5 6 7 8
Setpoint channel, closed-loop control, limitation, motor A5E00332118A AE Function diagram
- 700a -
General view without encoder - Chapter 7 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Setpoint channel, closed-loop
control, motor Gating unit
Closed-loop control and limitation
Udcl(act)
Setpoint channel [706]
r0070
Ua
Current limit r0072
p0640
Torque limitation
Converter control
[610.7]
Speed limitation
Minimum speed
n/f(max,pos.DR) nLimit_pos Ramp Speed
p1080
p1082 p1083 generator controller
[705] [710]
n/f(act) [704]
Set
+ r0063
+
Act
Optional
f(out) pulse
r0066 encoder
[904]
+
Slip frequency
r0065 i(act)
r0068
Motor model
1 2 3 4 5 6 7 8
Setpoint channel, closed-loop control, limitation, motor A5E00332118A AE Function diagram
- 700b -
General view with encoder - Chapter 7 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
1) 1)
Skip value 3
Skip value 2 p1093 (0.000)
1) p1092 (0.000)
Skip value 1
p1091 (0.000)
1)
Skip value 4
p1094 (0.000)
Minimum speed
|y|
n_min
p1080 (0.00)
y
w
n_set_2 of rotation direction limitation and switchover
x y x y
[700.3] r1114 [700.3] / [702.1]
x
w -1
w Minimum limitation
2)
w |x|
2)
p1101 (0.000)
skip frequency band
1)
A skip value of "0" deactivates the skip frequency band.
2)
If the drive is shut down not by the input setpoint but by open-loop control intervention, the
following ramp-up follows the lower part of the hysteresis loop.
1 2 3 4 5 6 7 8
Setpoint channel A5E00332118A AE Function diagram
- 701 -
Skip and minimum speed - Chapter 7 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Maximum speed
n_max_pos
p1083
Maximum speed n_max
p1082
Min
r1084 y
r1087
Speed limiter
-1 x
Max
p1086
n_max_neg
maximum speed
1 2 3 4 5 6 7 8
Setpoint channel A5E00332118A AE Function diagram
- 702 -
Speed limitation - Chapter 7 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
1) 1) 1)
Ramp-up time Ramp-down time OFF3 - Ramp-down
T_up T_dn time on rapid stop
p1120 (20 sec) p1121 (30 sec) p1135 (10 sec)
r0898.4
1 = enable ramp generator
1 2 3 4 5 6 7 8
Setpoint channel A5E00332118A AE Function diagram
- 703a -
Single ramp-function generator (p1115 = 0) - Chapter 7 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
2) 2)
OFF 3 Initial OFF 3 Final
rounding rounding
p1136 (0 sec) p1137 (0 sec)
3)
3)
Initial rounding Final rounding
4) p1130 (0 sec) p1131 (0 sec)
Rounding type
p1134
1) 1)
1)
Ramp-up time Ramp-down time OFF3 - Ramp-down
T_up T_dn time on rapid stop
p1120 (20 sec) p1121 (30 sec) p1135 (10 sec)
r0898.4
1 = enable ramp generator
1 2 3 4 5 6 7 8
Setpoint channel A5E00332118A AE Function diagram
- 703b -
Extended ramp-function generator (p1115 = 1) - Chapter 7 of the Instruction Manual (Oi) 13.08.08 SINAMICS G130
1) 2)
HTL/TTL uni/bipolar
p0405.1 (0) p0405.0 (1)
X521 r0063[1]
1 Track A 1 ms
2 Track A*
3 Track B Inversion of
actual speed value Direction of rotation n_act_filtering
4 Track B*
Pulse encoder p0410.0 p1821 p1441 (0.0)
5 Track N
connection to Motor speed
6 Track N*
SMC 30 r0061 Actual speed value
7 CTRL Pulse 0 0
0 n_act
8 M encoder
evaluation 1 1
1 1 r0063[0] [700.6] / [705.1]
1
X531
1 Ub
2 M
3 Temp -
4 Temp +
5
6 Actual speed value of
7 motor model
[700.5]
8
Resolution
p0408 (1024)
1 = sensorless closed-loop
speed control active
r1407.1
1)
p0405.1 = 0 -> HTL -> Ub = 24 V
p0405.1 = 1 -> TTL -> Ub = 5 V
1 2 3 4 5 6 7 8
Closed-loop control A5E00332118A AE Function diagram
- 704 -
Actual speed value acquisition - Chapter 7 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Control word [610.7]
r0898.6
1 = enable speed setpoint
0 0
Additional setpoint 1
0 p1155 1
Additional setpoint 2
+
0 p1160 n/f cont.Kp1 n/f cont.Tn
+ p1460 p1462
<1> p1470 p1472 <1>
Filt.n/f(set)
p1416
PI speed controller
Filt.n_ist
p1442
<1> p1452
1 2 3 4 5 6 7 8
Closed-loop control A5E00332118A AE Function diagram
- 705 -
Speed controller - Chapter 7 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Mmax_scal.
p1524
Mmax_motoring
M_limit 1
p1520
p1522
r1538
Min
Current limit M
p0640 Iq
M suppl. 1
r1515 Friction characteristic
FP [7010] Frict input ctrl
0 p1511 p1569
+ +
M suppl. 2
0 p1513
y
Torque setpoint from
speed controller + + M_set total
r1508 y
[700.7]
x
[700.6] / [705.8] r0079 [710a.1]
x
+ + [710b.1]
Torque limitation
-1
M
Iq
r1539
Max
Mmax_generating
M_limit 2
p1521
p1523
Mmax_scal.
p1525
1 2 3 4 5 6 7 8
Closed-loop control A5E00332118A AE Function diagram
- 706 -
Torque and current limitation - Chapter 7 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Udcl(act) Ua
r0070 r0072
M_set total
Isq r0077
x
[700.7] / [706.8] r0079
y
[700.8]
Isd r0075
Flux setpoint
50.0 ... 200.0 [%] U_out max [V]
p1570 (100.0)
r0071
Efficiency opt.
0 ... 100 [%]
p1580 (0)
Flux calculation
1)
Mset, static
0.0 ... 200.0 [%]
p1610 (50.0)
2) Msuppl,accel
30 ms
0.0 ... 200.0 [%]
p1610 (0.0)
1)
Static starting torque in controlled range
2)
Dynamic starting torque in controlled range
1 2 3 4 5 6 7 8
Closed-loop control A5E00332118A AE Function diagram
- 710a -
Flux calculation without encoder - Chapter 7 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Udcl(act) Ua
r0070 r0072
M_set total
Isq r0077
x
[700.7] / [706.8] r0079
y
[700.8]
Isd r0075
Flux setpoint
50.0 ... 200.0 [%]
p1570 (100.0) U_out max [V]
r0071
Flux calculation
Efficiency opt.
0 ... 100 [%]
p1580 (0)
1 2 3 4 5 6 7 8
Closed-loop control A5E00332118A AE Function diagram
- 710b -
Flux calculation with encoder - Chapter 7 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Output terminal block TM31
User wiring
[805]
1 2 3 4 5 6 7 8
Output terminal block TM31 (optional) A5E00332118A AE Function diagram
- 800 -
Overview - p0700 = 70002 / 70004 - Chapter 8 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Output terminal block CU320
1 2 3 4 5 6 7 8
Output terminal block CU320 A5E00332118A AE Function diagram
- 801 -
Overview - Chapter 8 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Example of AO 0 of the TM31
TM31.AO_signal 1) 1)
TM31.AO_char. x1 TM31.AO_char. x2
AO0 -100.00...+100.00 %
-100.00...+100.00 %
p4071[0] (r0063) TM31.AO_T_filtering p4079[0] (100.00)
p4077[0] (0.00)
AO0
0...1000 ms
r0060 speed setpoint p4073[0] (0) TM31.AO_pre. U/I 1)
AO0 [%] TM31.AO_char. y2 y [%]
r0063 actual speed value r4072[0] -20.000...+20.000 (V/mA) y2
p4080[0] (20.000)
x y
r0066 output frequency x2 x
1) x1
TM31.AI_char. y1
r0068 output current -20.000...+20.000 (V/mA) y1
Filtering
p4078[0] (0.000)
...............
Scaling
Normalizations:
100% =
n : p2000
U : p2001
I : p2002
M: p2003
P: p2004
2)
Type of analog outputs TM31
p4076[0]
Voltage
1) output
Default assignment of the scaling depending on p4076 r4074[0] AO 0V+ X522.1
0,1,2 y D
p4076 p4077 p4078 p4079 p4080 3,4 +-10V
0...20 mA 0% 0 mA 100 % 20 mA
+ + A AO 0A+ X522.3
0...10 V 0% 0V 100 % 10 V
4...20 mA 0% 4 mA 100 % 20 mA +-20mA
-20...20 mA 0% 0 mA 100 % 20 mA p4083[0] (0.000)
AO 0 ref X522.2
-10...10 V 0% 0V 100 % 10 V -20.000...20.000
offset Current
2) output
0: Current output (0... +20 mA )
1: Voltage output (0 to +10 V)
2: Current output (4... +20 mA ) monitored
3: Current output ( -20 mA... +20 mA)
4: Voltage output ( -10 V... +10 V)
1 2 3 4 5 6 7 8
Output terminal block TM31 (optional) A5E00332118A AE Function diagram
- 805 -
Scaling of the analog outputs - Chapter 8 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Example of DI/DO 8 of the TM31
TM31.DI8
r4022.8
TM31.DI8
inv.
1 r4023.8
1)
TM31.DI8
r4021.8
TM31
DI 8 X541.1
2) P24
TM31.DO8_signal
p4038 (r0899.0)
1) 0 X541.2
TM31.DO8_inversion DI/DO 8
r0899.0 ready to start p4048.8 (0) 1)
TM31.DO8 1
1 2 3 4 5 6 7 8
Output terminal block TM31 (optional) A5E00332118A AE Function diagram
- 810 -
Digital inputs/outputs - Chapter 8 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Example of DI/DO 8 of the CU320
CU.DI8
r0722.8
CU.DI8
inv.
1 r0723.8
1)
CU.DI8
r0721.8
CU320
DI 8 X124.+
2) P24
CU.DO8_signal
p0738 (r0899.0)
1) 0 X122.7
CU.DO8_inversion DI/DO 8
r0899.0 ready to start p0748.8 (0) 1)
CU.DO8 1
1 2 3 4 5 6 7 8
Output terminal block on CU320 A5E00332118A AE Function diagram
- 811 -
Digital inputs/outputs - Chapter 8 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Tolerance threshold
p2163 (90.00 rpm) ON delay
0.000...500.000 ms
p2166 (200.000)
Speed setpoint-actual value
Input ramp generator deviation in tolerance band
1
T 0
r1170 r2197.7
+ – 0
Tolerance threshold
(900.00 rpm)
p2155
0
p2140
(90.00 rpm)
p2150 (2.00 rpm)
n_act
r2169
p2150
p2142 (2.000 rpm)
1 2 3 4 5 6 7 8
Monitoring functions A5E00332118A AE Function diagram
- 901 -
Speed monitoring functions - Chapter 9 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Warning threshold
overtemperature motor
p0604 (120 °C)
<3>
A7910
1 warning
overtemperature
0 motor
Source T_mot
Fault threshold <1>
p0600 (0)
overtemperature motor Skip fault p0610 = 0
p0604 (155 °C)
Thermal motor model
0
248 °C (only for asynchonous F7011
R 1 T_mot
KTY machines) r0035 KTY
1 & fault
overtemperature
- A60 Sensor type 2 <4> motor
Sensor T p4100 (0) 0
resistance 3
X522 -140 °C Correction
PTC
r4101 (for KTY only) Warning threshold
7 A 2 11 overtemperature
motor 250 °C
8 PTC resistance 1 10
D threshold 1650 ohm 0
0
A7910
KTY/PTC 1 warning
1 0: evaluation deactivated 1: PTC overtemperature
2: KTY 0 T_motover time motor
PTC
0 p0606
0
-50 °C F7011
T 0 fault
250 °C overtemperature
1
motor
-140 °C 250 °C
A07015 warning
"Temperature sensor fault"
p0607
(0.1 s) <2>
T 0 F07016
fault
<1> p0610 = 0: only warning, without Imax reduction "Temperature sensor fault"
p0610 = 1: fault and warning, with Imax reduction
A07820
p0610 = 2: fault and warning, without Imax reduction
warning
<2> p0607 = 0 masks fault F07016 (on asynchronous machines).
"Temperatur sensor not
<3> If no sensor is connected, the temperature is taken from the model.
connected"
<4> In the case of KTY, the calculated temperature is output; in the case of PTC, the temperatur calculated from the thermal motor model
1 2 3 4 5 6 7 8
Protection function A5E00332118A AE Function diagram
- 902 -
Motor temperature monitoring (1) - Chapter 9 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
0.00...210 000.00 rpm
p2175 (120.00)
n_act
n_act < p2175
r2169
1)
Control type
p1300
2)
Error EMF
r1408.11
T 0 Motor stalled
1 r2198.7
Motor stalled
1) r1408.12 F7902
p1300 ³ 20 -> vector controls
p1300 < 20 -> V/Hz characteristics p2178 (0.010)
0.000...1.000 s
2) Only for vector control with sensor ON delay
1 2 3 4 5 6 7 8
Protection function A5E00332118A AE Function diagram
- 903 -
Block protection and stall protection - Chapter 9 of the Instruction Manual (OI) 13.08.08 SINAMICS G130
Setpoint technology controller
PZD3 ... PZD16 r2050.2 ... 15 Tec_cont t_ramp-up Tec_cont set T Tec_cont Kp Tec_cont Tn
Active fixed setpoint r2224 p2257 (1.00) p2261 (0.00) p2280 (1.000) p2285 (0.000)
Fixed setpoint1 ... 15 r2201 ... 15
Setpoint2 Output technology
AI0 TB30/TM31 r4055.0 technology controller + r2260 r2262 r2273 controller
AI1 TB30/TM31 r4055.1
0 p2254 r2294
Motor potentiometer T controller r2250 + + + [705.1]
Tec_cont t _ramp-down
p2258 (1.00)
Tec_cont act T
p2265 (0.00)
Tec_cont
Min_lim
p2292 (0.00)
1 2 3 4 5 6 7 8
Extended functions A5E00332118A AE Function diagram
- 904 -
Technology controller - controller (r0108.16 = 1) 13.08.08 SINAMICS G130