2-Pole Turbine Driven Generators - Brushless Excitation
2-Pole Turbine Driven Generators - Brushless Excitation
v v
v v
100% redundant diodes with indicating fuses are provided to ensure continuous service. No exciter outboard bearing is required which eliminates alignment problems associated with three bearing arrangements. No carbon dust problems. The exciter operates in the same enclosure as the generator. The shaft-driven permanent magnet pilot exciter provides a reliable source of exciter field power that eliminates bulky power transformer and dependence on station battery for field flashing.
v v
Short circuit sustaining capability provides fault current support. No heavy bus work or cable connections are required between excitation cubicles and the generator, thus simplifying installations. Large expensive field circuit breaker and field discharge resistor are not required. Compact voltage regulator hardware for installation and control panel or switchgear eliminates large excitation cubicles. EM experience...over 500 units installed.
v v v
v v
v v
BRUSHLESS EXCITERS
}
CCCT Generator Field Stator
Automatic Voltage Regulator Permanent Magnet Generator ACB PMG Field Transfer Switch
}
Stationary Receiver Field Ground Detector Rotating Transmitter Relay Unit (Mounted in Switchboard) Rotating Components Strobe Light Backup Automatic Voltage Regulator Voltage Adjust Rheostat
To Alarm
Diode
Armature Winding
Field Ground Dection Receiver (Diode Wheel Mounted Transmitter Not Shown)