TECHNICAL PARTICULAR AND GUARANTEES

GENERAL CONDITION GIS / HIS NO. DESCRIPTION UNIT REQUIRED GIS 150 KV HIS 70 KV PROPOSED GIS 150 KV ABB AG, Hanau - Germany Indoor m
o

HIS 70 KV NA

1 2 3 4 5 6 7 8 9

Manufacturer Design Altitude above sea level Ambient temperature Free of partial discharge Rated voltage Rated max. voltage Rated Frequency Rated Normal Current : Transformer bay outdoor < 1000 -10 s/d +40 =< 5 70 72,5 50

Indoor < 1000 -10 to =< 2 150 170 50 +40

< 1000 -10 s/d +40 =< 5 150 170 50

pC kV kV Hz

A %

1250 =< 0.5

2000 =< 0.5

10 Annual gas loss (per year) 11 Rated power frequency withstand voltage (50 Hz, min.) to ground at Power Frequency 1 min. at Lightning impulse (1.2/50 us wave) 12 Rated SF6 pressure at 20 deg. C Switchgear Circuit Breaker 13 SF6 gas refill signal (alarm pressure) Switchgear Circuit Breaker 14 Minimum operating pressure (guarantee value) Switchgear Circuit Breaker

kV kVp

325 750

325 750

bar bar

6,3 6,3

6 bar a 7 bar a

bar bar

5,8 5,8

5,2 bar a 6,2 bar a

bar bar

5,5 5,5

6 bar a 7 bar a

Page1

TECHNICAL PARTICULAR AND GUARANTEES


GENERAL CONDITION GIS / HIS NO. DESCRIPTION UNIT REQUIRED GIS 150 KV HIS 70 KV PROPOSED GIS 150 KV HIS 70 KV

15 Rated Power Frequency test Voltage (1 min.) of secondary circuit 16 17 18 19 Surface protection of steel frames Surface finish of switchgear Operating Mecanism Enclosure (GIS) : - phase segregated or three phases - Material - Overall diameter - Thickness

kV

2 Hot dip galvanized Bare aluminium housing Spring

2 Hot dip galvanized Bare aluminium housing Hydraulic spring drive Three phase Al / Alloy <12 NA

mm mm

Three phases

20 Enclosure (HIS) : - Cross section area of conductor - Material - Overall diameter - Thickness 21 22 23 24 25 26 27 28 29 Voltage control Equipment (Existing) Insulator Material Standar Manufacture Experience Operasional experience in tropical country Catalogue, drawings or other references Test Certificate Reference Compatible with existing equipment Supporting Letter from GIS existing manufacturer or Agent

mm mm VDC IEC 10 (min.) 3 (min.) required required yes yes 110 IEC > 10 > 10 attached to the offer 1HDG116001 Rev 4 Yes No

years years

>3

Page2

TECHNICAL PARTICULAR AND GUARANTEES


GENERAL CONDITION GIS / HIS NO. 26 27 28 29 30 31 32 33 34 35 36 37 38 39 No Yes Yes 1,5 DESCRIPTION UNIT REQUIRED GIS 150 KV HIS 70 KV PROPOSED GIS 150 KV HIS 70 KV

40 41 Length of stroke 42 Weight of circuit unit complete, without operating mechanism and structure 43 Weight of circuit breaker complete, with all fitting as in service mm Kg approx 1000

Kg

approx 1200

Page3

TECHNICAL PARTICULAR AND GUARANTEES


GENERAL CONDITION GIS / HIS NO. DESCRIPTION UNIT REQUIRED GIS 150 KV HIS 70 KV PROPOSED GIS 150 KV Will be given in case of order HIS 70 KV

44 Maximum shockload imposed on floor our foundation when opening under fault conditions (state compression or tension) 45 Maximum pressure rise in circuit breakers due to making of rated current in outer chamber 46 Routine pressure test on circuit breakers tanks or chamber 47 Design pressure type test on circuit breakers tanks or chamber 48 Quantity of gas : - Complete 3-phase circuit breaker - Complete 1-phase circuit breaker
O 49 Interrupting gas pressure Normal (20 C)

kN/m2

kN/m2

Acc. to CENELEC EN

kN/m2

Acc. to CENELEC EN

Kg Kg bar

approx 50 7 bar a

50 Opening time : Without current at 100% of rated breaking current 51 Maximum arc which maximum arc duration occurs (critical current) 52 Current at which maximum arc duration occurs (critical current) 53 Make time 54 Minimum time for arc extension to contact remake when adapted for auto reclosing 55 Time from closing of control switch to completion of closing stroke during fault making

ms ms

20 - 35 20 - 35

ms at ..%

acc. To IEC

ms ms

43 - 59 300

ms

Page4

TECHNICAL PARTICULAR AND GUARANTEES


GENERAL CONDITION GIS / HIS NO. DESCRIPTION UNIT REQUIRED GIS 150 KV HIS 70 KV n/a n/a O- CO PROPOSED GIS 150 KV HIS 70 KV

56 Is an external series break incorporated in the breaker ? 57 Is any device used to limit transient recovery voltage ? 58 Number of close / trip operations possible on one spring charge 59 Rated voltage of spring winding motor for closing 60 Spring winding motor current 61 Closing release coil current 62 Closing release coil voltage 63 Overall dimension of bay Height Width Depth 64 Material of tank or chamber 65 Material of moving contact tension rod 66 Min. burn throunght time of the circuit breaker enclosure 67 Withstand voltage guarantee with SF6 gas pressure of : a. Maximum - power frequency - impulse b. Nominal - power frequency - impulse c. Minimum - power frequency - impulse

Vdc A A Vdc

110 660 W 660 W 110 Ref. to attached drawing

mm mm mm mm Al / Alloy enclosure insulated rod 300 ms

Bars kV kV Bars kV kV Bars kV kV

7 bar a 325 750 7 bar a 325 750 6 bar a 325 750

Page5

TECHNICAL PARTICULAR AND GUARANTEES


GENERAL CONDITION GIS / HIS NO. DESCRIPTION UNIT REQUIRED GIS 150 KV HIS 70 KV PROPOSED GIS 150 KV 7 bar a 6.2 bar a 6,0 bar a Hydraulic spring drive Bars Bars Bars acc. IEC HIS 70 KV

68 Interrupting gas pressure (relative value) a. Maximum b. Normal c. Minimum 69 Operating mechanism pressure a. Maximum b. Normal c. Minimum 70 Type tests made on identical designs of equipment to those offered a. Terminal faults (test duties : 1,2,3,4 & 5 to IEC 60056) b. Making current c. Short time current d. Dielectric e. Temperature rise f. Machanical endurance g. Short line switching : - (Lines) - (cables) 71 Catalogue, drawings reference II. 150 kV DISCONNECTORS 1 Manufacturer 2 3 4 5 6 Type of designation Frequency Nominal Voltage Rated Voltage Rated continuous current at 40 ambient - Bus Coupler - Transformer circuits - Feeder circuits

Bars Bars Bars

requested

attached to the offer

Hz kV kV 50 150 170

ABB AG, Hanau - Germany ELK-DE0 50 150 170

A A A

2000 1250 1600

2000 -

Page6

TECHNICAL PARTICULAR AND GUARANTEES


GENERAL CONDITION GIS / HIS NO. DESCRIPTION UNIT REQUIRED GIS 150 KV HIS 70 KV PROPOSED GIS 150 KV HIS 70 KV

Impulse withstand voltage a. Open gap b. Closed contact to earth Rated short time current ( 1 second ) Type of operating mechanism

kV peak kV peak kA Volt DC A kN/m2

860 750 40

860 750 40 Motor

8 9

10 Motor operating voltage 11 Current at full load / locker rotor 12 Number of pole per complete unit 13 State whether automatic lockout under low pressure conditions is provided and at what pressure 14 Method of indicating contact position 15 Insulating medium normal operating pressure 16 Time from trip impulse to contact separation 17 Time from closing impulse to contact make 18 Minimum gas pressure at which rated BIL will be maintained 19 Min. clearance between live parts and earth 20 Total weight of 1-phase isolator complete 21 Switching capability of capacitive current at atmospheric pressure and 200C equivalent if no automatic lockout at low pressure is provided (a) making (b) breaking

110

110 660 W 3 520

kN/m2 ms ms kN/m2

Position indicator 520 < 700 < 700 520

Kg

n/a

A A

Page7

TECHNICAL PARTICULAR AND GUARANTEES


GENERAL CONDITION GIS / HIS NO. DESCRIPTION UNIT REQUIRED GIS 150 KV HIS 70 KV PROPOSED GIS 150 KV HIS 70 KV

22 Insulation strength across open gap at atmospheric - Power Frequency - Impulse withstand - Switching surge withstand 23 Power frequency (one minute) withstand at atmospheric pressure and 200C or insulant minimum normal working density (a) Open gap (b) Closed contact to earth
0 24 Insulant operating pressure at 20 C equivalent to minimum normal working density

kV kV kV

325 750 n/a 150/3 kV

kV kV kN/m2 520 Kpa

25 Time from trip impulse to contact separation 26 Time from closing impulse to contact make 27 Driving mechanism voltage 28 Driving mechanism power 29 Minimum gas pressure at which rated BIL will be maintained 30 Rated insulation levels at normal gas pressure across isolating gap : - Power frequency one minute withstand - Ligtning impulse withstand voltage - Switching impulse withstand voltage 31 Type of pressure relieve device fitted 32 Insulation strength to ground at normal gas pressure - Power frequency one minute withstand - Ligtning impulse withstand voltage - Switching impulse withstand voltage

ms ms V W kN/m2

< 700 < 700 110 VDC 660 520 Kpa

kV rms kV kV

325 750 n/a Bursting disc

kV rms kV kV

325 750 n/a

Page8

TECHNICAL PARTICULAR AND GUARANTEES


GENERAL CONDITION GIS / HIS NO. DESCRIPTION UNIT REQUIRED GIS 150 KV HIS 70 KV PROPOSED GIS 150 KV HIS 70 KV

33 Enclosure : (a) Material (b) Thickness (c) Burn through time at rated short circuit current 34 Testing Authoruty 35 Test Certificate report reference 36 Catalogue, drawings reference III. 150 kV HIGH SPEED EARTHING SWITCH 1 Manufacturer 2 3 4 5 6 7 8 9 Type of designation Number of breaks per pole Number of phase per enclosure Type of contacts Material of contact surface Rated current Rated short time current Maximum short circuit making current

mm ms

Al Alloy < 12 300 KEMA & Various Labs 1HDG116001 Rev 4

requested

attached to the offer

A kA (rms) kA (peak) mm 40

ABB AG, Hanau - Germany ELK-ES0 1 3 Tulip Silver plated

40 100

10 Gap between poles of one phase 11 Type of operating mechanism 12 Motor of operating mechanism - Operating Voltage - Power consumption

Motor operated snap spring

Volt kW

110 DC 0,15

Page9

TECHNICAL PARTICULAR AND GUARANTEES


GENERAL CONDITION GIS / HIS NO. - Operating time 13 Charging current breaking capacity 14 Magnetizing current breaking capacity 15 Insulation strength across open gap : (a) at normal gas pressure : - power freq. withstand voltage - impulse withstand voltage (b) atmospheric gas pressure : - power freq. withstand voltage - impulse withstand voltage 16 Total weight of single pole earthing switch 17 Enclosure : (a) Material (b) Thickness (c) Burn through time at rated short circuit current 18 Testing Authoruty 19 Test Certificate report reference 20 Standard 21 Catalogue, drawings, or other reference IEC requested DESCRIPTION UNIT S A A REQUIRED GIS 150 KV HIS 70 KV < 0,6 PROPOSED GIS 150 KV HIS 70 KV

Bars (abs) kV kV (peak)

6 bar a 325 750 n/a

kV kV (peak) Kg 70

mm ms

Al alloy < 12 300 KEMA & Various Labs 1HDG116001 Rev 4 IEC attached to the offer

IV. 150 kV MAINTENANCE EARTHING SWITCH 1 Manufacturer 2 3 Type of designation Number of breaks per pole

bove -

Page10

TECHNICAL PARTICULAR AND GUARANTEES


GENERAL CONDITION GIS / HIS NO. 4 5 6 7 8 9 DESCRIPTION Number of contact (surface) fingers Type of contacts surface Material of contact surface Rated current Rated short time current ( 3 sedonds ) Maximum short circuit making current UNIT A kA (rms) kA (peak) mm 40 REQUIRED Maintenance Earth Switch is Combined with the Disconnector Switch type ELK-DE0, already given under Item II ab GIS 150 KV HIS 70 KV PROPOSED GIS 150 KV HIS 70 KV

10 Gap between poles of one phase 11 Type of operating mechanism 12 Motor of operating mechanism - Operating Voltage - Power consumption - Operating time 13 Insulation strength across open gap : (a) at normal gas pressure : - power freq. withstand voltage - impulse withstand voltage (b) atmospheric gas pressure : - power freq. withstand voltage - impulse withstand voltage 14 Total weight of single pole earthing switch 15 Enclosure : (a) Material (b) Thickness (c) Burn through time at rated short circuit current 16 Testing Authoruty

Volt kW S

Bars (abs) kV kV (peak)

kV kV (peak) Kg

mm ms

Page11

TECHNICAL PARTICULAR AND GUARANTEES


GENERAL CONDITION GIS / HIS NO. DESCRIPTION UNIT REQUIRED M GIS 150 KV HIS 70 KV PROPOSED GIS 150 KV HIS 70 KV

17 Test Certificate report reference 18 Standard 19 Catalogue, drawings, or other reference V. 1 2 3 4 5 6 7 150 kV INSULATED BUSBARS AND CONNECTIONS Manufacturer Insulating medium Frequency Nominal Voltage Rated Voltage Continuous current Enclosure : (a) Material (b) Overall diameter (c) Thickness Phase segregated or three phase Cross sectional area of conductor IEC requested

Hz kV kV A ( rms ) SF6 50 150 170 2000

ABB AG, Hanau - Germany SF6 50 150 170 2000

Al alloy mm mm mm2 < 12 3 phase

8 9

10 Rated insulation levels at normal gas - pressure : - Power frequency impulse 1 minute withstand voltage - Ligtning impulse withstand voltage - Switching surge withstand voltage 11 Withstand voltage guaranteed with SF6 - gas atmospheric pressure : - Power frequency impulse 1 minute withstand voltage - Ligtning impulse withstand voltage

kV kV kV

325 750 n/a 150/3 kV

kV kV

Page12

TECHNICAL PARTICULAR AND GUARANTEES


GENERAL CONDITION GIS / HIS NO. DESCRIPTION - Switching surge withstand voltage 12 Insulating gas pressure a. Maximum b. Normal c. Minimum 13 Short time current rating : a. One second b. Three seonds c. Peak current 14 Insulator material 15 Maximum temperature rise of any section at rated current - Conductor - Enclosure 16 Inductance 17 Capacitance 18 Surge Impedance 19 Standard 20 Catalogue, drawings, or other reference 21 Testing Authoruty 22 Test Certificate reference VI. 150 kV INSULATOR AND BUSHING 1 Manufacturer 2 Type UNIT kV REQUIRED GIS 150 KV HIS 70 KV PROPOSED GIS 150 KV HIS 70 KV

Bars Bars Bars

6 bar a 6 bar a 5,2 bar a

kA kA kA

40 40 100 SF6 gas

o o

C C

65 acc. IEC 65 acc. IEC

H/m F/m Ohms requested IEC requested IEC attache to the offer KEMA & Various Labs 1HDG116001 Rev 4

cable

Page13

TECHNICAL PARTICULAR AND GUARANTEES


GENERAL CONDITION GIS / HIS NO. DESCRIPTION UNIT REQUIRED GIS 150 KV Poscelain SF6 HIS 70 KV Not included in our offer, as connection shall be through 400 sq mm c PROPOSED GIS 150 KV HIS 70 KV

3 4 5 6 7 8 9

Material Insulating medium Continuous current rating Short time ( one sedond ) current Insulator material (outdoor) Length of insulator overall Total creepage distance over insulator externally

A kA mm mm kV kV -

40 Poscelain

10 50 Hz 1 minute withstand voltage all equipment 11 Impulse withstand voltage (1.2/50 msec. wave) 12 Testing Authoruty 13 Test Certificate reference 14 Catalogue, drawings, or other reference VII. 150 kV CURRENT TRANSFORMER 1 Manufacturer 2 3 4 5 6 Type of designation Type of current transformer Nominal Voltage Rated Voltage Frequency

325 750 requested requested requested

kV kV Hz 150 170 50

Pfiffner, Switzerland ring type 150 170 50

Page14

TECHNICAL PARTICULAR AND GUARANTEES


GENERAL CONDITION GIS / HIS NO. 7 8 9 Basic Insulation Level A.C. withstand voltage Number of core DESCRIPTION UNIT kV kV (rms) kA Ohm REQUIRED GIS 150 KV 750 325 multicore multicore Sesuai Spek Sesuai Spek Sesuai Spek 40 Please refer to the drawing attached in the offer HIS 70 KV 750 325 PROPOSED GIS 150 KV HIS 70 KV

10 Number of tap each core 11 Ratio current 12 Accuracy class 13 Rated burden 14 Rated symmetrical short circuit 15 Knee point voltage 16 Internal resistance of CT 17 Accuracy limit factor at nominal burden 18 Total weight complete 19 Testing Authoruty 20 Test Certificate reference 21 Catalogue, drawings, or other reference VIII. 150 kV VOLTAGE TRANSFORMER 1 Manufacturer 2 3 4 Type of designation Type of voltage transformer Nominal Voltage

Kg attached to the offer

kV Capacitor Type 150

Page15

TECHNICAL PARTICULAR AND GUARANTEES


GENERAL CONDITION GIS / HIS NO. DESCRIPTION UNIT REQUIRED GIS 150 KV 170 150/3 50 750 325 100/3 Not required in tender doc HIS 70 KV PROPOSED GIS 150 KV HIS 70 KV

5 6 7 8 9

Rated Voltage Primary Voltage Frequency Basic Insulation Level A.C. withstand voltage

kV kV Hz kV kV (rms) V

10 Secondary voltage 11 Accuracy class : - for protection - for instrument and metering 12 Rated burden - for protection - for instrument and metering 13 Rated capacitance (min) 14 Standard 15 Testing Authoruty 16 Test Certificate reference 17 Catalogue, drawings, or other reference

3P 0,5

VA VA pF -

100 100

IEC

requested

IX. 150 kV GAS HANDLING EQUIPMENT 1 Manufacturer 2 Type of designation 3 Capacity

fer CU. m/hr

Page16

TECHNICAL PARTICULAR AND GUARANTEES


GENERAL CONDITION GIS / HIS NO. DESCRIPTION UNIT REQUIRED GIS 150 KV HIS 70 KV Not included in our off PROPOSED GIS 150 KV HIS 70 KV

4 5

Purity capability Spare gas cylinder - volume - pressure Electrical requirements - Voltage - Power consumption - Single or three phase Testing Authoruty Test Certificate reference Catalogue, drawings, or other reference

ppm

Volt kW -

7 8 9

requested

Page17