GENERAL CONDITION GIS / HIS NO. DESCRIPTION UNIT REQUIRED GIS 150 KV HIS 70 KV PROPOSED GIS 150 KV ABB AG, Hanau - Germany Indoor m
o
HIS 70 KV NA
1 2 3 4 5 6 7 8 9
Manufacturer Design Altitude above sea level Ambient temperature Free of partial discharge Rated voltage Rated max. voltage Rated Frequency Rated Normal Current : Transformer bay outdoor < 1000 -10 s/d +40 =< 5 70 72,5 50
pC kV kV Hz
A %
10 Annual gas loss (per year) 11 Rated power frequency withstand voltage (50 Hz, min.) to ground at Power Frequency 1 min. at Lightning impulse (1.2/50 us wave) 12 Rated SF6 pressure at 20 deg. C Switchgear Circuit Breaker 13 SF6 gas refill signal (alarm pressure) Switchgear Circuit Breaker 14 Minimum operating pressure (guarantee value) Switchgear Circuit Breaker
kV kVp
325 750
325 750
bar bar
6,3 6,3
6 bar a 7 bar a
bar bar
5,8 5,8
bar bar
5,5 5,5
6 bar a 7 bar a
Page1
15 Rated Power Frequency test Voltage (1 min.) of secondary circuit 16 17 18 19 Surface protection of steel frames Surface finish of switchgear Operating Mecanism Enclosure (GIS) : - phase segregated or three phases - Material - Overall diameter - Thickness
kV
2 Hot dip galvanized Bare aluminium housing Hydraulic spring drive Three phase Al / Alloy <12 NA
mm mm
Three phases
20 Enclosure (HIS) : - Cross section area of conductor - Material - Overall diameter - Thickness 21 22 23 24 25 26 27 28 29 Voltage control Equipment (Existing) Insulator Material Standar Manufacture Experience Operasional experience in tropical country Catalogue, drawings or other references Test Certificate Reference Compatible with existing equipment Supporting Letter from GIS existing manufacturer or Agent
mm mm VDC IEC 10 (min.) 3 (min.) required required yes yes 110 IEC > 10 > 10 attached to the offer 1HDG116001 Rev 4 Yes No
years years
>3
Page2
40 41 Length of stroke 42 Weight of circuit unit complete, without operating mechanism and structure 43 Weight of circuit breaker complete, with all fitting as in service mm Kg approx 1000
Kg
approx 1200
Page3
44 Maximum shockload imposed on floor our foundation when opening under fault conditions (state compression or tension) 45 Maximum pressure rise in circuit breakers due to making of rated current in outer chamber 46 Routine pressure test on circuit breakers tanks or chamber 47 Design pressure type test on circuit breakers tanks or chamber 48 Quantity of gas : - Complete 3-phase circuit breaker - Complete 1-phase circuit breaker
O 49 Interrupting gas pressure Normal (20 C)
kN/m2
kN/m2
Acc. to CENELEC EN
kN/m2
Acc. to CENELEC EN
Kg Kg bar
approx 50 7 bar a
50 Opening time : Without current at 100% of rated breaking current 51 Maximum arc which maximum arc duration occurs (critical current) 52 Current at which maximum arc duration occurs (critical current) 53 Make time 54 Minimum time for arc extension to contact remake when adapted for auto reclosing 55 Time from closing of control switch to completion of closing stroke during fault making
ms ms
20 - 35 20 - 35
ms at ..%
acc. To IEC
ms ms
43 - 59 300
ms
Page4
56 Is an external series break incorporated in the breaker ? 57 Is any device used to limit transient recovery voltage ? 58 Number of close / trip operations possible on one spring charge 59 Rated voltage of spring winding motor for closing 60 Spring winding motor current 61 Closing release coil current 62 Closing release coil voltage 63 Overall dimension of bay Height Width Depth 64 Material of tank or chamber 65 Material of moving contact tension rod 66 Min. burn throunght time of the circuit breaker enclosure 67 Withstand voltage guarantee with SF6 gas pressure of : a. Maximum - power frequency - impulse b. Nominal - power frequency - impulse c. Minimum - power frequency - impulse
Vdc A A Vdc
Page5
68 Interrupting gas pressure (relative value) a. Maximum b. Normal c. Minimum 69 Operating mechanism pressure a. Maximum b. Normal c. Minimum 70 Type tests made on identical designs of equipment to those offered a. Terminal faults (test duties : 1,2,3,4 & 5 to IEC 60056) b. Making current c. Short time current d. Dielectric e. Temperature rise f. Machanical endurance g. Short line switching : - (Lines) - (cables) 71 Catalogue, drawings reference II. 150 kV DISCONNECTORS 1 Manufacturer 2 3 4 5 6 Type of designation Frequency Nominal Voltage Rated Voltage Rated continuous current at 40 ambient - Bus Coupler - Transformer circuits - Feeder circuits
requested
Hz kV kV 50 150 170
A A A
2000 -
Page6
Impulse withstand voltage a. Open gap b. Closed contact to earth Rated short time current ( 1 second ) Type of operating mechanism
860 750 40
8 9
10 Motor operating voltage 11 Current at full load / locker rotor 12 Number of pole per complete unit 13 State whether automatic lockout under low pressure conditions is provided and at what pressure 14 Method of indicating contact position 15 Insulating medium normal operating pressure 16 Time from trip impulse to contact separation 17 Time from closing impulse to contact make 18 Minimum gas pressure at which rated BIL will be maintained 19 Min. clearance between live parts and earth 20 Total weight of 1-phase isolator complete 21 Switching capability of capacitive current at atmospheric pressure and 200C equivalent if no automatic lockout at low pressure is provided (a) making (b) breaking
110
kN/m2 ms ms kN/m2
Kg
n/a
A A
Page7
22 Insulation strength across open gap at atmospheric - Power Frequency - Impulse withstand - Switching surge withstand 23 Power frequency (one minute) withstand at atmospheric pressure and 200C or insulant minimum normal working density (a) Open gap (b) Closed contact to earth
0 24 Insulant operating pressure at 20 C equivalent to minimum normal working density
kV kV kV
25 Time from trip impulse to contact separation 26 Time from closing impulse to contact make 27 Driving mechanism voltage 28 Driving mechanism power 29 Minimum gas pressure at which rated BIL will be maintained 30 Rated insulation levels at normal gas pressure across isolating gap : - Power frequency one minute withstand - Ligtning impulse withstand voltage - Switching impulse withstand voltage 31 Type of pressure relieve device fitted 32 Insulation strength to ground at normal gas pressure - Power frequency one minute withstand - Ligtning impulse withstand voltage - Switching impulse withstand voltage
ms ms V W kN/m2
kV rms kV kV
kV rms kV kV
Page8
33 Enclosure : (a) Material (b) Thickness (c) Burn through time at rated short circuit current 34 Testing Authoruty 35 Test Certificate report reference 36 Catalogue, drawings reference III. 150 kV HIGH SPEED EARTHING SWITCH 1 Manufacturer 2 3 4 5 6 7 8 9 Type of designation Number of breaks per pole Number of phase per enclosure Type of contacts Material of contact surface Rated current Rated short time current Maximum short circuit making current
mm ms
requested
A kA (rms) kA (peak) mm 40
40 100
10 Gap between poles of one phase 11 Type of operating mechanism 12 Motor of operating mechanism - Operating Voltage - Power consumption
Volt kW
110 DC 0,15
Page9
kV kV (peak) Kg 70
mm ms
Al alloy < 12 300 KEMA & Various Labs 1HDG116001 Rev 4 IEC attached to the offer
IV. 150 kV MAINTENANCE EARTHING SWITCH 1 Manufacturer 2 3 Type of designation Number of breaks per pole
bove -
Page10
10 Gap between poles of one phase 11 Type of operating mechanism 12 Motor of operating mechanism - Operating Voltage - Power consumption - Operating time 13 Insulation strength across open gap : (a) at normal gas pressure : - power freq. withstand voltage - impulse withstand voltage (b) atmospheric gas pressure : - power freq. withstand voltage - impulse withstand voltage 14 Total weight of single pole earthing switch 15 Enclosure : (a) Material (b) Thickness (c) Burn through time at rated short circuit current 16 Testing Authoruty
Volt kW S
kV kV (peak) Kg
mm ms
Page11
17 Test Certificate report reference 18 Standard 19 Catalogue, drawings, or other reference V. 1 2 3 4 5 6 7 150 kV INSULATED BUSBARS AND CONNECTIONS Manufacturer Insulating medium Frequency Nominal Voltage Rated Voltage Continuous current Enclosure : (a) Material (b) Overall diameter (c) Thickness Phase segregated or three phase Cross sectional area of conductor IEC requested
8 9
10 Rated insulation levels at normal gas - pressure : - Power frequency impulse 1 minute withstand voltage - Ligtning impulse withstand voltage - Switching surge withstand voltage 11 Withstand voltage guaranteed with SF6 - gas atmospheric pressure : - Power frequency impulse 1 minute withstand voltage - Ligtning impulse withstand voltage
kV kV kV
kV kV
Page12
kA kA kA
o o
C C
H/m F/m Ohms requested IEC requested IEC attache to the offer KEMA & Various Labs 1HDG116001 Rev 4
cable
Page13
3 4 5 6 7 8 9
Material Insulating medium Continuous current rating Short time ( one sedond ) current Insulator material (outdoor) Length of insulator overall Total creepage distance over insulator externally
A kA mm mm kV kV -
40 Poscelain
10 50 Hz 1 minute withstand voltage all equipment 11 Impulse withstand voltage (1.2/50 msec. wave) 12 Testing Authoruty 13 Test Certificate reference 14 Catalogue, drawings, or other reference VII. 150 kV CURRENT TRANSFORMER 1 Manufacturer 2 3 4 5 6 Type of designation Type of current transformer Nominal Voltage Rated Voltage Frequency
kV kV Hz 150 170 50
Page14
10 Number of tap each core 11 Ratio current 12 Accuracy class 13 Rated burden 14 Rated symmetrical short circuit 15 Knee point voltage 16 Internal resistance of CT 17 Accuracy limit factor at nominal burden 18 Total weight complete 19 Testing Authoruty 20 Test Certificate reference 21 Catalogue, drawings, or other reference VIII. 150 kV VOLTAGE TRANSFORMER 1 Manufacturer 2 3 4 Type of designation Type of voltage transformer Nominal Voltage
Page15
5 6 7 8 9
Rated Voltage Primary Voltage Frequency Basic Insulation Level A.C. withstand voltage
kV kV Hz kV kV (rms) V
10 Secondary voltage 11 Accuracy class : - for protection - for instrument and metering 12 Rated burden - for protection - for instrument and metering 13 Rated capacitance (min) 14 Standard 15 Testing Authoruty 16 Test Certificate reference 17 Catalogue, drawings, or other reference
3P 0,5
VA VA pF -
100 100
IEC
requested
Page16
4 5
Purity capability Spare gas cylinder - volume - pressure Electrical requirements - Voltage - Power consumption - Single or three phase Testing Authoruty Test Certificate reference Catalogue, drawings, or other reference
ppm
Volt kW -
7 8 9
requested
Page17