Saudi Arabia Distribution Code
Saudi Arabia Distribution Code
Saudi Arabia Distribution Code
No part of this publication may be reproduced, stored in a retrieval system or transmitted in any form or by any means electronic, mechanical, photocopying, recording or otherwise, without written permission of the Electricity & Cogeneration Regulatory Authority.
Sr. No.
Revision No.
Date
The Distribution Code is designed to indicate the procedures for both planning and operational purposes and covers both normal and exceptional circumstances. It is however a live working document. It will be, from time to time, subject to change and/or revision to reflect stages of development of the regulatory framework of the industry and changes to comply with legislation and good industry practice. The proposals for change will be received by the Distribution Code Review Panel (DCRP). The rules and responsibilities of the DCRP are described in chapter DGC6. Upon receipt of such proposals for change, the DCRP will carry out the necessary process as appropriate to study these proposals and officially prepare a report of recommendations to ECRA for its approval. The DCRP is a stakeholders representation panel and its members are outlined in chapter DGC6.3 of the Distribution Code.
As a User of this Distribution Code, it is your responsibility to ensure that you possess the most up to date issue. Issues of the Distribution Code can be downloaded from ECRAs web site www.ecra.gov.sa.
This Preface is provided to Users and to prospective Users for their information only and does not constitute a part of the Distribution Code.
Preface
The Saudi Arabia Distribution Code has been developed to define the rules and regulations for various participants for accessing and using the Distribution System. The objective is to establish the obligations of the distribution service providers (DSP's) and other system Users- TSP, Embedded Generators, other distribution service providers and Customers for accessing and using the Distribution System, more specifically to: (i) define obligations, responsibilities, and accountabilities of all the parties for ensuring open, transparent, non-discriminatory, and economic access and use of the system while maintaining its safe, reliable and efficient operation; (ii) (iii) define minimum technical requirements for the participants; and Set out the information exchange obligations of the participants.
CONTENTS
1.
INTRODUCTION
2.
GENERAL CONDITIONS
13
3.
PLANNING
21
4.
CONNECTION CONDITIONS
35
5.
OPERATION
61
6. 7.
DEFINITIONS SECURITY AND PLANNING STANDARDS FOR THE DISTRIBUTION SYSTEM (Demand Customers Only)
83 93
PART 1: INTRODUCTION
Contents
Purpose of the Distribution Code Structure of the Distribution Code Structure of the Electricity Supply Industry Users of the Distribution System Purpose of the Distribution Code
The Distribution Code specifies the technical aspects of the working relationship between the DSP(s) and all Users of the Distribution system which are necessary to ensure a stable, reliable and economical electrical Distribution system and to enable the DSP(s) to fulfil their obligations specified in the Saudi Arabian Grid Code (SAGC). The relationship between all Users, the Grid Code and the Distribution Code is shown diagrammatically in Figure 1.1.
Transmission Connected Customers Generators TSP National Control Centre Generators (Captive) Suppliers DSP(s)
Subject to central dispatch and scheduling Not subject to central dispatch and scheduling
Transmission System
Isolated Generation
Distribution System
Information DSP Distribution Control Centre (s)
1.2
Structure of Distribution Code The Distribution Code is in seven parts, as follows: Part 1: Introduction This outlines the purpose of the Code, its relationship with the Saudi Arabian Grid Code (SAGC), the structure of the electricity supply industry, and how the various parts of the Code are relevant to the different Users of the Distribution system. Part 2: General Conditions This presents provisions which are of general application to all parts of the Code. Part 3: Planning This specifies the technical and design criteria and the procedures to be employed in the planning and development of the Distribution system. Part 4: Connection Conditions These define the minimum standards for methods of connection to the Distribution System. Part 5: Operation This part addresses various operational issues including load forecasting, planning outages, reporting of operational changes and events, safety matters and procedures for dealing with emergencies. Part 6: Definitions Part 7: References This lists other documentation which is referred to in the Code.
1.3
The Electricity Supply Industry comprises the following entities: (a) The Transmission Service Provider (TSP) owns and operates the Transmission System. The Transmission System transports the electricity, generated by Generating Units, to the Distribution System, through which most Customers will be supplied. Some Generating Plant is connected directly to the Distribution System and is referred to as Embedded Generation. The Distribution Service Provider (DSP(s)) is responsible for operating and maintaining secure, reliable and efficient electricity Distribution System. The Distribution System transports electricity from the Transmission System or from Embedded Generating Units to the final Customer. Retailers supply electricity to Customers. For this purpose, Retailers will be entitled to use both the Transmission System and the Distribution System for the transport of electricity from Generating Units to Customers. Traders supply electricity to other licensees and/ or eligible Customers. For this purpose, Traders will be entitled to use both the Transmission System and the Distribution System for the transport of electricity from Generating Units to those licensees or eligible Customers Generators generate electricity which is fed onto the Transmission or Distribution Systems. Generating Units are classified according to their voltage, output power and whether or not they are subject to Central Dispatch by the TSP. Customers may purchase electricity from the DSP(s), Traders or Retailers. Some Customers have their own generating Plant for supplying all or part of their own needs. These are referred to as Customers with CHP or Customers with Auto-Production. ECRA was established to regulate the new Electricity Industry.
(b)
(c)
(d)
(e)
(f)
(g)
1.4
Use of the Distribution System may involve any of the following transactions: (a) Any connection at entry to or exit from the Distribution System, which is called an interface point. An entry point is the connection between the Distribution System and the Transmission System or an Isolated/ Embedded Generating Plant. An exit point is the connection between the Distribution System and the Customers premises. Use of the Distribution System to transport electricity between entry and exit points. Construction of a Connection Point. Work and/or operation associated with equipment at the interface with the Distribution System.
(b)
(c) (d)
Users connected to the Distribution System shall comply with the relevant sections of the Distribution Code. The categories of Users of the Distribution System are described in Table 1 and the sections of the Code that apply to each User are shown in Table 2. Users shall also comply with the requirements of relevant legislation, which from time to time comes into force.
There are a number of technical documents annexed to the Distribution Code. Users are bound to comply with the requirements of these documents as appropriate to their circumstances.User Users shall also be required to enter into technical and other agreements. Customers and Generator Embedded Generators shall be required to have Connection Agreements with the DSP(s) and Retailers/ Traders shall be required to enter into Use of System Agreements with the DSP(s) or the TSP as the case may be.
CATEGORIES OF USERS OF THE DISTRIBUTION SYSTEM A1 A2 A3 A4 A5 B1 B2 B3 B4 C D Embedded Generator> 10 MW Embedded Generator> 2 MW <10 MW Embedded Generator< 2 MW Customers with CHP or Customers with Auto-production Customers with stand-by Generators Major Customers connected at High Voltage Customers connected at Medium Voltage Industrial and commercial Customers connected at Low Voltage Domestic Customers Retailers/ Traders The Distribution Service Provider (DSP(s)) Table 1
SECTIONS OF THE DISTRIBUTION CODE APPLYING TO PARTICULAR CATEGORIES OF USERS OF THE DISTRIBUTION SYSTEM CATEGORY OF USERS D Code Ref DGC DPC1 DPC2 DPC3 DCC1 DCC2 DCC3 DCC4 DCC5 DCC6 DOC1 DOC2 DOC5 DOC7 DOC8 A1 D R D R R R R D D D A2 D R D R R R R D D D D D R D D A3 D R D R R R R D D D D D D D A4 D R D R R R R D D D D R R R A5 D R R R R R R B1 D R R R R R R D D D D D R D D B2 D R R R R R R D D D D R B3 D R R R R R R D R D B4 D R R R R R R D R D C D R R R R R R R R R D D R D R R R R D D D D D D D D
R D D
Table 2
Not Applicable D Applicable with specific obligations R Relevant for information but no specific obligations Note (1): Customers represented in Categories A4 and A5 must comply with the Code sections relevant to that category and additionally to the relevant sections of the category of Customer to which they belong.
DGC1: Introduction While each part of the Distribution Code presents the rules and provisions relating specifically to that part, the Distribution General Conditions (DGC) presents provisions which are of general application to all parts of the Distribution Code. DGC2: Scope The General Conditions apply to all Users of the Distribution System. DGC3: Implementation DGC3.1 The Distribution Service Provider Licence imposes a duty upon DSP(s) to implement and enforce the Distribution Code. In order to do this DSP(s) may need access across boundaries, services, and facilities from Users or to issue instructions to Users, for example to isolate or disconnect Plant or apparatus. It is considered that these cases will be exceptional and it is not, therefore, possible to envisage precisely or comprehensively what DSP(s) might reasonably require in order to carry out its duty. DGC3.2 All Users are required to abide by the Distribution Code and also to provide the DSP(s) rights of access, services and facilities and to comply with such instructions as may be reasonably required to implement and enforce the Distribution Code.
DGC4: Unforeseen Circumstances DGC4.1 If circumstances arise which the provisions of the Distribution Code have not foreseen, DSP(s) shall, to the extent reasonably practicable in the circumstances, consult promptly and in good faith with affected Users in an effort to reach agreement as to what should be done. If agreement cannot be reached in the time available DSP(s) shall determine what is to be done. DGC4.2 Whenever DSP(s) makes a determination, it shall have regard, wherever possible to the views expressed by Users, and in any event, to what is reasonable in all the circumstances. DGC4.3 Each User shall comply with all instructions given to it by DSP(s) following such a determination, provided that the instructions are consistent with the then current technical parameters of the particular Users System registered under the Distribution Code. The DSP(s) shall promptly refer all such unforeseen circumstances and any such determination to the Distribution Code Review Panel (DCRP) in accordance with DGC6.2. DGC5: Hierarchy DGC5.1 In the event of any conflict between the provisions of any direction of ECRA on the one hand and the provisions of the Distribution Code on the other, the provisions of ECRAs direction shall prevail. DGC5.2 In the event of any conflict between the provisions of the Distribution Code and any contract, agreement or arrangement between DSP(s) and a User, the provisions of the Distribution Code shall prevail unless the Distribution Code expressly provides otherwise. DGC5.3 In the event of any conflict between the provisions of the Distribution Code and the Transmission Code relating to system operation, the provisions of the Transmission Code shall prevail [unless the Distribution Code expressly provides otherwise.]
DGC6: Distribution Code Review Panel DGC6.1 The DSP(s) shall establish and maintain the DCRP, which shall be a standing body, to carry out the functions referred to in DGC6.2. DGC6.2 The Panel shall
(c)
(d)
(e)
(f)
(g)
(h)
DGC6.3 The Panel shall consist of (a) chairperson and two persons appointed by, and representing DSP(s), (b) (c) one person appointed by and representing ECRA, one person representing the TSP,
(d) one person representing Generators with Embedded generation, (e) (f) (g) one person representing Major Customers, one person representing suppliers, and one representative of the SASO
If any of the above parties fails to appoint its representative (ECRA) shall appoint one on its behalf. Each of the above shall be appointed pursuant to the rules issued pursuant to DGC6.4. DGC6.4 The Panel shall establish and comply at all times with its own rules and procedures relating to the conduct of its business, such rules and procedures to be known as the Constitution and Rules of the Panel, which shall be approved by ECRA. The DSP shall consult all Users liable to be affected in relation to all proposed amendments to the Distribution Code and shall submit all proposed amendments to the Distribution Code to the DCRP for discussion prior to such consultation. Unless an amendment is urgently required, ECRA will not amend the Distribution Code until all affected Users have been given a reasonable opportunity to make representations to ECRA concerning the amendment, and those representations have been taken into account. ECRA will notify all DSP's and all affected Users of any amendment that ECRA makes to the Distribution Code. DGC6.6 DCRP shall, from time to time or at the behest of ECRA having regard to the recommendations of the Panel, submit a revised Distribution Code to ECRA for approval.
DGC7: Communications between DSP(s) and Users DGC7.1 Unless otherwise specified in the Distribution Code the methods of operational communication and data transfer shall be agreed between DSP(s) and Users from time to time. DGC8: Emergency Situations DGC8.1 Users should note that the provisions of the Distribution Code may be suspended, in whole or in part, pursuant to any directions given and/or orders made by ECRA in emergency situations, pursuant to provisions of the Electricity Law issued by Royal Decree No. M/56.
DGC9: Derogations DGC9.1 If a User finds that they are, or will be, unable to comply with any provision of the Distribution Code, then they shall without delay report such non-compliance to DCRP and shall, subject to the provisions of DGC9.2 make such reasonable efforts as are required to remedy such non-compliance as soon as reasonably practicable. DGC9.2 Where the non-compliance is (a) with reference to Plant and/or apparatus connected to the Distribution System and is caused solely or mainly as a result of a revision to the Distribution Code, or (b) with reference to Plant and/or apparatus which is connected, approved to connect, or for which approval to connect to the Distribution System is being sought,
and the User believes either that it would be unreasonable (including cost and technical considerations) to require it to remedy such non-compliance or that it should be granted an extended period to remedy such non-compliance it shall promptly submit to DCRP a request for a derogation from such provision in accordance with the requirements of DGC9.3 and shall provide DSP(s) with a copy of such application. DGC9.3 A request for derogation from any provision of the Distribution Code shall contain the following: (a) the issue number and the date of the Distribution Code provision against which the non-compliance or predicted noncompliance was identified; identification of the Plant and/or apparatus in respect of which a derogation is sought, and if relevant, the nature and extent to which the non-compliance exists; identification of the provision with which the User is, or will be, unable to comply;
(b)
(c)
(d) (e)
the reason for the non-compliance; and the date by which compliance will be achieved (if remedy of the non-compliance is possible) subject to DGC9.2 (b)
A standard Distribution Code Derogation Application form is included in Annex 2. DGC9.4 If DSP(s) finds that they are, or will be, unable to comply with any provision of the Distribution Code, then they shall, subject to the remaining provisions of DGC9 make such reasonable efforts as are required to remedy such non-compliance as soon as reasonably practicable. DGC9.5 In the case where DSP(s) requests derogation, DSP(s) shall submit the information set out in DGC9.3 to DCRP. DGC9.6 On receipt of any request for derogation, DCRP shall promptly consider such request and discuss the potential outcomes of such request with ECRA. Following such discussion, DCRP shall recommend to ECRA such derogation, provided that DCRP considers that the grounds for the derogation are reasonable. DCRP will not recommend to ECRA such derogation if (a) It would, or it is likely that it would, have a material adverse impact on the security and stability of the Distribution System, or (b) It would result in ECRA imposing unreasonable costs on the operation of the Distribution System or Transmission System or on other Users. In its consideration of a derogation request by a User, DCRP may contact the relevant User and/or DSP(s) to obtain clarification of the request or to discuss changes to the request. Derogation from any provision of the Distribution Code shall contain the following: (a) the issue number and the date of the Distribution Code provision against which the derogation applies; identification of the provision with which the derogation applies;
(b)
(d) (e)
DGC9.7 To the extent of any derogation granted in accordance with this DGC9, DSP(s) and/or the User (as the case my be) shall be relieved from its obligation to comply with the applicable provision of the Distribution Code and shall not be liable for failure to so comply but shall comply with any alternate provision as set forth in the derogation. Should a derogation not be granted, then the User will be required to comply with the applicable provision of the Distribution Code and will be liable for failure to so comply. DGC9.8 DCRP shall (a) keep a register of all derogations which have been granted, identifying the name of the person in respect of whom the derogation has been granted, the relevant provision of the Distribution Code and the period of the derogation, and on request from any User, provide a copy of such register of derogations to such User.
(b)
DGC9.9 Where a material change in circumstance has occurred, a review of any existing derogations, and any derogations under consideration, may be initiated by DCRP at the request of ECRA, DSP(s), or Users. DGC10: Confidentiality DGC10.1 The Distribution Code contains procedures under which the DSP(s) will receive information from Users relating to the intentions of such Users. The DSP shall not, except in pursuance of specific requirements of the Distribution Code, disclose such information to any User or other person without the prior written consent of the provider of the information, subject to the requirements of the Distribution Licence.
PART 3: PLANNING
Contents DPC 1 DPC2 DPC3 Introduction Design Standards Transfer of Planning Data
DPC1: Introduction DPC1.1 Part 3: Planning specifies the technical and design criteria and the procedures to be complied with by DSP(s) in the planning and development of the Distribution System. It also applies to Users in the planning and development of their installations in so far as they affect the Distribution System. DPC1.2 The Users requirements may necessitate the reinforcement of, or an extension to, the Distribution System and for reinforcement of, or extension to, the relevant Transmission/Distribution interface capacity, such work being identified by DSP(s) or TSP as appropriate. DPC1.3 The time required for the planning and development of the Distribution System and any consequential requirement of the interface with the Transmission System, will depend on the type and extent of the necessary reinforcement and/or extension work, the time required for obtaining planning permission and right of way, including any associated hearings, and the degree of complexity in undertaking the new work while maintaining satisfactory security and quality of supply. DPC1.4 Reference is made in Part 3 to DSP(s) supplying information or advice to Users. For avoidance of doubt, unless the context otherwise requires, such information or advice shall be provided by DSP(s) as soon as practical following a request by the User (whether during the application for connection process or otherwise).
DPC2: Design Standards DPC2.1 Frequency The Frequency of supply is outside the control of DSP(s); however the standard Frequency range is as follows: The Transmission System Frequency is nominally 60Hz and shall normally be controlled within the limits of 59.9Hz to 60.1Hz. The system Frequency could rise to 62.5 Hz or fall to 57.0 Hz in exceptional circumstances. Design of Generators Plant and apparatus must enable operation of that Plant and apparatus within that range in accordance with the following: Below nominal Frequency(Hz) 58.8 -60.0 57.5 -58.7 57.0- 57.4 Above nominal Frequency(Hz) 60.0 -60.5 60.6-61.5 61.6-62.5 Operation requirement continuous For period of 30 minutes For period of 30 seconds
Users should ensure their equipment is designed or protected for these exceptional circumstances. DPC2.2 Voltages The voltages listed in Table DPC2.1 shall be used as standard service voltages at the interfaces with power Customers. The service voltage shall be maintained within the range defined by the indicated lowest and highest values, under steady state and normal system conditions and over the full loading range of the system. Where two voltages are listed e.g. 220/127V the lower value refers to the phase to neutral voltages. All other values are phase-tophase voltages. Existing, but non-standard, voltages are listed in Table DPC2.2.
Nominal Voltage
11kV 34.5kV
Lowest Voltage
10.45kV 32.78kV
Highest Voltage
11.55kV 36.23kV
Table DPC2.3: Maximum Continuous Harmonic Levels Note: N is the harmonic order, or multiple of the fundamental Frequency. Voltage distortion is expressed as a percentage of the fundamental voltage. The indicated values refer to maximum continuous levels. DPC2.4 Power Factor Each Customer shall maintain a Power Factor of not less than 0.85 lagging at the interface with DSP(s). No Customer shall present a leading Power Factor to the DSP(s) system. DPC2.5 Phase Unbalance Under normal system conditions the three phase voltages shall be balanced at MV, and higher voltages in the system, such that the negative phase sequence voltage does not exceed 2% of the positive phase sequence voltage. Customers with a dedicated transformer or those supplied at 13.8kV or a higher voltage shall balance their loads, such that the load phase unbalance at the Customer interface meets the above criterion. All other Customers shall balance their loads over the three phases to the greatest degree possible. The DSP(s) shall then balance these loads, within the power system, to meet the above criterion.
DPC2.7 Earthing Requirements 1. Separation of LV Neutral and MV Grounds. LV neutral ground and any grounds associated with MV equipment / system (e.g. MV metal work, cable screen, etc.) shall always be kept separate. Primary neutral (if available) shall not be bonded to secondary neutral. 1. Separation between LV neutral ground and MV equipment / system ground shall be achieved by grounding LV neutral points which are remote from MV grounds. Minimum distance between any part of MV ground system and nearest LV neutral ground shall be 4 meters. 2. Recommended ground resistance limits for different installations should be as under: System GROUND ALL distribution substation Surge arresters LV distribution panel 5 ohms 5 ohms 5 ohms 10 ohms
3. LV metering Installations It shall be essential for the Customer to provide grounding at his interface. The Customer shall bring the ground wire to the grounding terminals provided in the meter box. The ground wire of the Customer shall be connected to the ground terminal inside the meter box. The ground terminal shall be short linked with the neutral.
For more than one KWH -meters at one location, four KWH-meters shall be connected to one ground rod. In case of additional KWHmeters at the premises, additional ground rods shall be provided. 4. Ground mounted MV equipment The equipment covered are RMU, MV switches etc, when separated from Transformer and Bulk Customer Indoor Switchgear. All metal work shall be bonded together and to the substation metalwork grounding system. Each continuous piece of metal that could form part of the path of a ground fault current shall be bonded to its neighbors so that continuity of grounding circuit does not depend on mechanical connections between components.
Licensed Distributors shall advise on the method of Earthing of the Distribution System, for example, whether it is connected solidly to Earth or through impedance. The specification of associated apparatus and Plant of the Distribution System User shall meet the voltages that will be imposed on the apparatus and Plant as a result of the method of Earthing. Notwithstanding the above, the DSP(s) shall provide a complete separate Earthing code to define the Earthing requirements for safe use of the system. This code shall constitute an integral part of the Distribution code. Distribution System Users shall take precautions to limit the occurrence and effects of circulating currents in respect of the neutral points connected with Earth where there is more than one source of electricity. DPC2.8 Security of Supply DPC2.8.1 The Security Standard for the Distribution System is as follows: Security of supply (also known as continuity) is evaluated in terms of four indices, as follows: (1) System Average Interruption Frequency Index (SAIFI) SAIFI = Total Customer Interruptions Total Connected Customers
(2)
System Average Interruption Duration Index (SAIDI) SAIDI =Total Customer Hours of Interruptions Total Connected Customers
(3)
(4)
Index of Reliability (IR)Average system availability Index (ASAI) IR (ASAI)= 8760 Hours/Year SAIDI x 100 8760 Hours/Year (Expressed as a percentage)
The DSP(s) will have to comply with the security of supply standards limits as published by ECRA from time to time. DPC2.8.2 DSP(s) shall use reasonable endeavours to maintain a supply from the system. This cannot be ensured, since faults, planned maintenance and new works outages and other circumstances outside DSP(s) control can cause interruptions. On such occasions, DSP(s) shall use reasonable endeavours to restore the supply or connection as soon as practicable but shall be under no liability for any direct or indirect damage or associated loss incurred by the User. DPC2.8.3 Restoration times for different outage types are as follows: Fault Outages: DSP(s) shall endeavour to restore access to the system as soon as practically possible taking into consideration the KPI set values approved by ECRA DSP(s) shall give five days notice to relevant Users of planned supply interruptions. In some situations to facilitate emergency
Planned Outages:
DPC2.8.4 DSP(s) may disconnect Users under certain circumstances. These circumstances shall include: (a) Where the Customers installation or use of electricity is such as to interfere with the satisfactory operation of the Distribution or Transmission system or to cause disturbance to other Customers. Where DSP(s) considers that the Customers installation is in a dangerous condition. Where alterations, repairs, renewal or maintenance of the Distribution System or DSP(s) assets or means of connection require the de-energisation of the Connection Point. Where a Customer extends supply for use by another party whom DSP(s) considers to be a separate Customer. In any other circumstances in which discretion is necessary or appropriate to enable DSP(s) to comply with the Distribution Code and/or to operate the Distribution System in accordance with Good Industry Practice or is required by any law, direction, rule or regulation having the force of law.
(b)
(c)
(d)
(e)
DPC3: Transfer of Planning Data DPC3.1 Planning information to be provided by Users. DPC3.1.1 Users of the Distribution System shall provide sufficient planning data/ information as can reasonably be expected to be made available, when requested by DSP(s) from time to time to enable DSP(s) to comply with the requirements under its Distribution Licence. DPC3.1.2 Users of the Distribution System shall provide planning data for specific future time periods updated annually as necessary and including projected Demand requirements, anticipated changes in maximum Demand, or generating capacity, as appropriate. The data and timescales over which the data is required are given in Distribution Operating Code 1 (DOC1). DPC 3.1.3 In addition to periodic updates of planning information, a User shall give adequate notice of any significant change to their system or operating regime to enable DSP(s) to prepare its development plans and implement any necessary system modifications. In the event of unplanned changes in a Users System or operating regime a User shall notify DSP(s) as soon as is practically possible to ensure any necessary measures can be implemented. DPC3.1.4 Users shall also provide details of reactive compensation Plant directly or indirectly connected to the Distribution System other than at Low Voltage, including its rating and operational control. DPC3.1.5 Users may be required to provide DSP(s) with detailed data relating to the interface between their System and that of the Distribution System covering circuit parameters, switchgear and Protection arrangements of equipment directly connected to or affecting the Distribution System to enable DSP(s) to assess any implications associated with these points of connection. DPC3.2 Information to be exchanged. DPC3.2.1 On the request of a User, DSP(s) shall provide such information as may be reasonably required on the design and other characteristics of the Distribution System.
DPC3.2.2 Where DSP(s) proposes to make certain modifications to its system or where it has received information from a User under DPC4.1 above, which may impact on other User installations then DSP(s) will notify Users of the proposal, subject to any constraint of confidentiality or timing. DPC3.2.3 DSP(s) shall provide information on request to Users regarding the local network conditions to enable them to determine their Protection requirements. DPC3.2.4 Where the Users installation is connected to the bus bars of the Distribution System, sufficient details may need to be exchanged with respect to User/ DSP(s) Ownership Boundary to enable an assessment to be made of transient over voltage effects. The request for information may be initiated by either DSP(s) or the User. DPC3.2.5 Information may be exchanged between DSP(s) and the User on fault in feed levels at the feeding bus bar or point of connection to the Distribution System as appropriate, in the form of Three phase and single phase to earth short circuit in feed. The X/R ratio under three phase fault conditions.
DPC3.2.6 Information shall be exchanged between DSP(s) and User on Demand Transfer Capability where the same Demand can be supplied from alternate User points of supply. This shall include the proportion of Demand normally fed from each point of supply and the arrangements (manual or automatic) for transfer under planned/fault outage conditions. DPC3.3 Planning Studies DPC3.3.1 In order to facilitate connections to the Distribution System DSP(s) shall prepare on request a study showing the implications of a connection at a particular point on the system. DPC3.3.2 Under the terms of the Distribution Licence a reasonable charge (as submitted by DSP(s) and approved by ECRA) may be levied by DSP(s) for the planning study.
DPC3.3.3 A User or potential Users shall provide DSP(s) with information regarding the proposed facility including load details, interface arrangements, proposed Connection Point and import/export requirements. DPC3.3.4 The studies shall normally be prepared within 28 days after the date of receipt of the information or the agreement of the person making the request to pay the cost of the study, whichever is the longer. In the case of Generators and Major Customers seeking connection, depending on the nature and complexity of the request, this period may extend up to 100 days or a further 28 days from the receipt of planning information from the TSP whichever is the greater. DPC3.3.5 Details of the procedures for application for connection to the Distribution System are contained in [CUSTOMER SERIVICE MANUAL] as prepared by DSP(s) and approved by ECRA. DPC3.3.6 Where such information is available DSP(s) shall provide on request a statement of present and future circuit capacities, forecast power flows and loadings on part or parts of the Distribution System specified in the request and shall include Fault Levels at each Distribution node covered by the request. DSP(s) may levy a charge for the provision of this statement as approved by ECRA on account of the reasonable costs incurred by DSP(s) in preparing this statement. The statement shall be prepared within 28 days after the date of receipt of the information or the agreement of the person making the request to pay the cost of the statement, whichever is the longer. In the case of Generators and Major Customers seeking connection this period may extend up to 100 days depending on the nature and complexity of the request. DPC3.3.7 The dates given in this DPC3.3 are target dates only and do not constitute a legal commitment. DSP(s) shall however use reasonable endeavours to abide by them.
DCC1: Introduction DCC1.1 It is necessary to require certain minimum technical, design and operational criteria to be met by Users Plant and apparatus in order to maintain, insofar as is permitted by Good Industry Practice, stable and secure operation of the Distribution System for the benefit of all Users and for the Protection of the Distribution System and Users Plant and apparatus directly connected to the Distribution System. DCC1.2 The Connection Conditions define the minimum standards for the method of connection to the Distribution System and the technical, design and operational standards to which Users connecting to the Distribution System shall comply. DCC1.3 The Connection Conditions specify the technical arrangements required at the Ownership Boundary between the Distribution System and the installation of the User and are applicable to all voltage levels covered by the Distribution Code. DCC1.4 The Connection Conditions specify the information to be provided by Users to ensure that adequate provision can be made by DSP(s) for new connections or increases in existing load. It also applies to Generators who operate in parallel with the Distribution System, where a connection is required. Prospective Users shall provide to DSP(s) in good time all the details set out in this section. DCC1.5 In conjunction with the Connection Conditions, there are Connection Agreements, which are bilateral agreements between DSP(s) and each User, and which contain the detail specific to each Users connection to and use of the Distribution System. The Connection Agreement requires the User and DSP(s) to comply with the terms of the Distribution Code.
DCC2: Information Required for Connection DCC2.1 For connections at Low Voltage it is possible in most cases to assess whether a proposed connection is acceptable, and to determine the necessary supply arrangements, from analysis of the following data: (a) (b) Maximum kVA requirements. Type and electrical loading of equipment to be connected, such as number and size of motors, cookers, showers, air conditioning, space and water electrical heating loads and nature of Disturbing Loads e.g. welding equipment. The date when connection is required. Plan covered area and location
(c) (d)
If a preliminary examination of this data indicates that more detailed information is reasonably required then it shall be provided to DSP(s) upon request. DCC2.2 Information Requirements and timeframes for quotation and connection are provided in [Customer service manual] as prepared by DSP(s) and approved by ECRA. Copies of this manual are available on request from DSP(s).
DCC2.3 For connections at distribution level the provisions of DCC2.1 also apply. Additionally, the following information may be required: (a) (i) (ii) (iii) (iv) (v) (vi) All Types of Demand Maximum Active Power requirements. Maximum and Minimum Reactive Power requirements. Type of load and control arrangements (e.g. type of motor start, controlled rectifier or large motor drives). Maximum load on each phase. Maximum harmonic currents that may be imposed on the Distribution System. Details of cyclic load variations or fluctuating loads (as below).
(b)
Disturbing Loads Comprehensive schedule of installed new equipment including details of Disturbing Loads. These are loads which have the potential to introduce Harmonics, Flicker or unbalance to the system. This could adversely affect the supply quality to other Customers. Disturbing loads could be non-linear loads, power converters/regulators and loads with a widely fluctuating Demand. The type of load information required for motive power loads, welding equipment, harmonic producing/non linear loads and generating equipment can be obtained from DSP(s) on request. In the case of compensating equipment associated with Disturbing Loads, details and mode of operation to be provided so as to ensure compliance with emission limits specified in DCC4.8.3.
(c)
Fluctuating Loads Duty cycle, including details of cyclic or other variation of Active Power and Reactive Power, in particular: (i) the rates of change of Active Power and Reactive Power, both increasing and decreasing; the shortest repetitive time interval between fluctuations in Active Power and Reactive Power; and the magnitude of the largest step changes in Active Power and Reactive Power, both increasing and decreasing.
(ii)
(iii)
DCC2.4 In some cases, more detailed information may be required to permit a full assessment of the effect of the Users load on the Distribution System. Such information may include an indication of the pattern of build up of load and a proposed Commissioning programme. This information shall be specifically requested by DSP(s) when necessary and shall be provided by the User within a reasonable time.
DCC2.5 Users shall contact DSP(s) in advance if it is proposed to make any significant change to the connection, electric lines or electric equipment, install or operate any generating equipment or do anything else that could affect the Distribution System or require alterations to connection. DCC2.6 Users shall provide to DSP(s) any information reasonably required by DSP(s) about the nature, or use by the User, of electrical equipment on the Users premises. DCC3: Connection Arrangements DCC3.1 Connection Voltage DCC3.1.1 During the application for connection process DSP(s) shall, in consultation with the User, specify the voltage level to which a User will be connected in accordance with normal practice for the type of load to be supplied and network characteristics. DCC3.1.2 Generally, the voltage level will be the minimum nominal voltage in standard use on the System, assessed against (a) (b) (c) (d) satisfactory operation of the installation, isolation of disturbance from other Customers, lifecycle costs, and cost of connection
DCC3.1.3 DSP(s) may, on occasion, specify higher connection voltage in order to avoid potential disturbances caused by the Users apparatus to other Users of the Distribution System or for other technical reasons or may agree alternative methods for minimising the effects of Disturbing Loads. DCC3.2 Information Provided by DSP(s) Based on the information provided by the User for a connection to the Distribution System, DSP(s) shall prepare a statement containing as many of the following elements as are necessary for, or relevant to, the proposed installation:
nominal voltage at which connection will be made; method of connection, extension and/or reinforcement details; the normal impedance to source at the point of connection; method of Earthing; maximum IMPORTED CAPACITY; individual Customer limits relating to (i) (ii) (iii) Harmonic Distortion Flicker Phase Unbalance
(g)
expected lead time of providing connection (following formal acceptance of terms for supply); and Cost of connection.
(h)
DCC3.3 Ownership Boundaries DCC3.3.1 The point or points at which supply is given or taken between the Distribution System and Users installation shall be agreed between DSP(s) and the User as stipulated in the Connection Agreement between DSP(s) and the User.
DCC3.3.2 For LV supplies DSP(s) responsibility extends up to the Customers Connection Point, which is normally at DSP(s) main Circuit Breaker as further specified in the Connection Agreement between DSP(s) and the User. DCC3.3.3 For Medium Voltage supplies the ownership boundaries shall be subject to specific agreement between the parties in each case. Changes in the Boundary arrangements proposed by either party shall be agreed in advance. DCC3.3.4 All equipment at the Ownership Boundary shall meet the design principles contained in DPC2 and DCC3. Connections for entry to and exit from the Distribution System shall incorporate a means of disconnection of the Users installation by DSP(s).
DCC4.2 Protection Requirements DCC4.2.1 Users shall ensure that faults in the Users Plant and apparatus do not unreasonably cause disturbances to the Distribution System or to other Users. Without limiting this obligation, a User shall, prior to connection of the Users installation to the Distribution System, install the Protection equipment specified in DCC4.2.4. DCC4.2.2 Unless provided against, faults on the Distribution System can cause damage to Users Plant and apparatus through, for example, loss of a phase, over voltage, or under voltage. The User shall take account of the established practices of the particular network to which a connection is to be made, and ensure that Protection installed is compatible with that used by DSP(s). The adequacy of the Protection installed by the User is the Users responsibility. DCC4.2.3 The Users Protection arrangements at the Ownership Boundary, including types of Equipment and Protection settings, shall be compatible with existing system conditions and the Distribution System Protection practice as specified by DSP(s) at the time of application. In particular (a) the maximum clearance times (from fault current inception to arc extinction) shall be within the limits established by DSP(s) in accordance with Protection and equipment short circuit rating policy adopted for the Distribution System; in connecting to the Distribution System the User should be aware that fast and slow-speed automatic re-closing is a feature of Power System operation. This is characterised by sudden de/re-energisation of the power supply. Dead times are typically 0.3s, 1s and 10s at Medium Voltage and 3s and 60s on 38kV systems; and Users should also be aware that disconnection of one or two phases only of a three phase system may be effected by Distribution Protection arrangements for certain types of faults.
(b)
(c)
DCC4.2.5 Where interface Circuit Breakers are used they shall be fitted with relays of a type acceptable to DSP(s). These relays shall have three phases over current elements and one earth fault element and shall have time-current characteristics complying with standard types A, S and C of IEC 244. Maximum permissible relay settings at the ownership boundary, necessary to provide selectivity any time in the future will be provided by DSP(s). Distribution Protection aims to minimise the impact of faults including voltage dip duration and must not be adversely affected by Customers Protection limitations. (a) In order to ensure satisfactory operation of the Distribution System, Protection systems, operating times, discrimination, and sensitivity at the ownership boundary shall be agreed between DSP(s) and the User during the application for connection process, and may be reviewed from time to time by DSP(s). In order to provide against the failure of a Circuit Breaker, or equipment having a similar function, to operate correctly by interrupting fault current on the system, back-up Protection shall normally be provided by operation of other Circuit Breakers or equipment having a similar function.
(b)
DCC4.2.6 Protection relays shall be commissioned on site by the User who shall ensure that the settings are below the maximum permitted levels. In certain cases DSP(s) may wish to witness these tests and it shall be the responsibility of the User to ensure that sufficient notice is given to DSP(s) in such cases. Users shall ensure that the Protection settings remain below the maximum permitted levels. This may require regular testing of the relays. DCC4.3 Earthing DCC4.3.1 Earthing of the part of the Users installation that is connected to the Distribution System shall comply with the requirements of DPC2.7. DCC4.3.2 The arrangements for connecting the Users installation with earth shall be designed to comply with relevant international and national standards. DCC4.3.3 The method of Earthing the Distribution System whether, for example, it is connected to earth solidly or through impedance, shall be advised by DSP(s). The specification of associated equipment shall be appropriate to the voltages that will be imposed on the equipment as a result of the method of Earthing. DCC4.3.4 Where there is more than one source of energy, Users shall take precautions to limit the occurrence and effects of circulating currents in respect of neutral points connected with earth. DCC4.4 Voltage Regulation and Control DCC4.4.1 Extensions or connections to the Distribution System shall be designed so that they do not hinder the necessary control of voltage on the Distribution System. Information on the voltage regulation and control arrangements shall be made available by DSP(s) if requested by the User.
Table DCC4.1: Short Circuit Ratings DCC4.6 Insulation Levels DCC4.6.1 The basic insulation level (BIL) and power Frequency withstand voltage for medium system voltages are as tabulated below: System Nominal Voltage (kV
RMS)
325
350
Power Frequency 140 160 withstand voltage(kV RMS) BIL (KV peak) 170 200 Power 33/34.5 Frequency 70 80/75 withstand voltage(kV RMS) BIL (KV peak) 95 110 Power 11/13.8 Frequency 38 50/45 withstand voltage(kV RMS) Note: the dry/wet power Frequency withstands voltages are: Dry for one (1) minute and wet for (10) seconds.
DCC4.7 Capacitive and Inductive Effects DCC4.7.1 The User shall, when applying to make a connection, provide DSP(s) with information as detailed in DPC3. Details shall be required of any capacitor banks and reactors connected at Medium Voltage, which could affect the Distribution System and which it is proposed to connect if agreed with DSP(s). When requested by DSP(s), details shall also be provided of distributed circuit capacitance and inductance. Sufficient detail is required for the following: (a) to verify that controlling equipment of the Distribution System is suitably rated; to show that the performance of the Distribution System will not be impaired.
(b)
DCC4.8 Voltage Disturbances DCC4.8.1 Users of the Distribution System must not generate voltage disturbances at a level that would affect other Users. Users should in their own interest select equipment that is capable of functioning satisfactorily in the presence of disturbances at the levels that can be expected, as indicated by IEEE 1159. DCC4.8.2 It is a condition of connection that equipment connected directly or indirectly to the Distribution System shall conform to the requirements of the Distribution Code as amended from time to time.
Supply quality to other Customers shall not fall below standard as a result of the presence or operation of Generating Units. DCC6.2.2 Generating Units connecting to the Distribution System and operating in parallel with, or which are capable of being operated in parallel with the Distribution System, shall comply with the relevant DSP(s) document. This document sets out the conditions with which Generating Units operating in parallel with the Distribution System shall comply. DCC6.2.3 Protection conditions and requirements are to protect the Distribution System. The Generator is responsible for Protection of its personnel and equipment and the efficient operation of its Generating Unit. DCC6.2.4 Where a Generating Unit is to be installed on premises, DSP(s) shall be informed. DSP(s) shall have the right to inspect generating installations to ensure that the requirements are met. In some cases DSP(s) may require a demonstration by operation of the Generator. Such demonstrations shall be by agreement with the User. DCC6.3 Provision of Information DCC6.3.1 Information Required from Embedded Generators Embedded Generators shall provide to DSP(s) information on (a) the Generating Plant and (b) the proposed interface arrangements between the Generating Plant and the Distribution System. The information required by DSP(s) before entering into an agreement to connect any Generating Plant to the Distribution System is shown below. (a) (i) (ii) (iii) (iv) Generating Plant Data: Terminal Volts (kV) Rated kVA Rated kW Maximum Active Power sent out (kW), Reactive Power requirements (kVAR)
Details will also be required on the following parameters: (i) (ii) (iii) (iv) (v) Inertia Constant MW secs/MVA (whole machine) Stator Resistance Direct Axis Reactance Sub-transient Synchronous Time Constraints: Direct Axis Sub-transient Zero Sequence Resistance Reactance Negative Sequence Resistance Reactance Generator Transformer Resistance Reactance MVA Rating Tap arrangement Vector Group Earthing
(vi) (vii)
(b)
Other Plant and Equipment Details: A comprehensive schedule of installed new equipment including details of Disturbing Loads is required.
(e) (f)
DCC6.3.2 The details of information required will vary depending on the type and size of the Generating Unit or the point at which connection is to be made to the Distribution System. This information shall be provided by the Generator at the reasonable request of DSP(s). DCC6.3.3 DSP(s) will use the information provided to model the Generating Unit to determine a technically acceptable method of connection. If DSP(s) reasonably concludes that the nature of the proposed connection or changes to an existing connection requires more detailed analysis then further information than that specified in DCC6.3.1 may be required. DCC6.3.4 Additional information may be required from Embedded Generators larger than 2MW or connected at a voltage level above 13.8kV. (a) (i) Technical Data Generating Plant information (impedance per unit on rating) Type of prime mover Rated MVA MW Type of excitation system (ii) Automatic Voltage Regulator (AVR): A block diagram for the model of the AVR system including the data on the forward and feedback gains, time constants and voltage control limits.
(iv) Generator Excitation System. (b) (i) Capacity and Standby Requirements Registered Capacity and minimum generation of each Generating Unit and power station in MW. Generating unit and power station auxiliary Demand (Active and Reactive Power) in MW and MVAR, at registered capacity conditions.
(ii)
(iii) Generating unit and power station auxiliary Demand (Active and Reactive Power) in MW and MVAR, under minimum generation conditions. DCC6.3.5 In normal circumstances the information specified above will enable DSP(s) to assess the connection requirements. Occasionally additional information may be required. In such circumstances, the information shall be made available by the Generator, at the reasonable request of DSP(s). DCC6.4 Information Provided by DSP(s) DCC6.4.1 DSP(s) shall prepare a statement as per DCC3.2 for Generators applying for connection to the Distribution System. DCC6.4.2 Where Generator paralleling or power export is intended the following additional information shall be provided including: (a) (b) (c) Interface Protection settings Equipment, cabling, switchgear, metering requirements Substation site and building requirements (dimensions, access, planning permission, Earthing, lighting and heating).
(b)
(c)
f) g)
h) i)
Demand Forecasting Operational Planning Demand Control Operational Communications and Liaison Event Reporting System Tests Monitoring Testing and Investigation Safety Co-Ordination
DOC1: Demand Forecasting DOC1.1 Introduction DOC1.1.1 In order for DSP(s) to operate the Distribution System efficiently and to ensure maximum system security and system stability, there is a need for those Users specified in DOC1.2 to provide loading and generation output information to DSP(s). DOC1.1.2 DOC1; Demand forecasting specifies the information to be provided to DSP(s) by other Users of the Distribution System so that these requirements can be met. DOC1.1.3 DOC 1; Demand forecasting sets out the Demand forecasting and the generating Plant output information to be provided by Users to enable DSP(s) to operate the Distribution System; and specifies the information to be provided by Users to the DSP(s). DOC1.1.4 Where Demand data is required from the User, this means the MW Demand of electricity at the Connection Point. DSP(s) may in certain cases specify that the Demand data shall include the MVAR Demand. DOC1.1.5 The means of providing the information to DSP(s) and its confirmation includes any non-transitory written form, or any other suitable means of electronic transfer which enables the recipient to retain information.
(b)
DOC1.3
DOC1.3.1 DSP(s) shall co-ordinate Demand Forecast information for each Bulk Supply Point to meet the requirement of the Saudi Arabian Grid Code (SAGC). DSP(s) shall aggregate forecast information provided by Users, where appropriate, and provide forecast information to the TSP where Demand, or change in Demand, is greater than 10MW at any Connection Point. DOC1.3.2 Embedded Generator information for Generating Plant in the Distribution System, which is not subject to Central Dispatch, shall be provided where specified to DSP(s). Customers with CHP and Customers with Auto-production may also be required to supply information. DOC1.4 Demand Forecast Data DOC1.4.1 Generating Units greater than 2MW and not subject to Central Dispatch shall provide DSP(s) with information regarding output and planned shutdowns for specified future periods. This shall be provided on an annual basis when requested by DSP(s). DOC1.4.2 Major Customers shall provide to DSP(s) information regarding Demand and planned shutdowns for specified future periods. This shall be provided on an annual basis when requested by DSP(s).
(b)
DOC2.1.2 The means of providing the information to DSP(s) and its confirmation includes any non-transitory written form, or any other suitable means of electronic transfer which enables the recipient to retain information. DOC2.1.3 In order for the DSP(s) to fulfil the requirements of DOC2 it should be noted that the information set out in the Saudi Arabian Grid Code (SAGC), to be provided by the TSP will form the basis of operational planning under DOC2. DOC2.2 Scope DOC2.2.1 DOC2 applies to the following Users of the Distribution System: (a) (b) (c) Major Customers connected to the Distribution System where DSP(s) considers it appropriate; Embedded Generating Plant connected to the Distribution System; Customers with CHP and Customers with Auto-production.
DOC2.3 Provision of Information DOC2.3.1 Information on Embedded Generating Plant not subject to Central Dispatch (including Customers with CHP and Customers with Autoproduction) shall be provided, where specified, directly to DSP(s).
DOC3: Demand Control DOC3.1 Introduction DOC3.1.1 DOC3 is concerned with provisions to be made by DSP(s) or Users of the Distribution System, in certain circumstances, to permit reductions in Demand. Reductions would be permitted (a) In the event of insufficient Generating Plant and transfers from external interconnections are available to meet Demand;
(d)
(e)
The term Demand Control is used to describe any or all of these methods of achieving a Demand reduction. DOC3.1.4 Where Demand Control is exercised by DSP(s) or the TSP it shall be done in a manner that in so far as reasonably practicable does not discriminate against any Customer or supplier and shall use reasonable endeavours to ensure that the burden is shared fairly among Customers. Exemptions may apply to vital and priority Customers as defined in the Distribution load shedding criterion/ plan submitted by DSP(s) and approved by ECRA. DOC3.2 Scope DOC3.2.1 DOC3 applies to DSP(s) and all Users of the Distribution System.
DOC4.3 Procedure DOC4.3.1 DSP(s) and Users connected to the Distribution System shall nominate persons and/or contact locations and agree communication channels for the necessary exchange of information to make effective the exchange of information required by DOC4. DOC4.3.2 SCADA equipment may be required at a Users site for transmission of information and data to and from the DSP(s). The requirement to provide this information shall normally be included in the relevant Connection Agreement.
DOC4.3.3 Information between DSP(s) and Users shall be exchanged on the reasonable request of either party. The request may follow a specific Operation, or be in accordance with a prior agreement to exchange information on particular types of Event. This does not preclude the voluntary exchange of information which may be perceived as being relevant to the operation of the Distribution or User Installation, in accordance with Good Industry Practice. DOC4.3.4 DSP(s) shall notify the User of any Operation on the Distribution System (or of any Operation on the Transmission System of which it has received notice) which, in the opinion of DSP(s), will have or may have an Operational Effect on the installation of the User. DOC4.3.5 A User shall notify DSP(s) of any Operation on the installation of that User which will have or may have an Operational Effect on the Distribution System. DOC4.3.6 A notification under DOC4 shall include the name of the individual reporting the Operation and, although it need not state the cause, shall be in sufficient detail to describe the Operation and to enable the recipient reasonably to know and consider the implications and risks arising there from. The recipient may ask questions to clarify the notification. DOC4.3.7 A notification under DOC4 shall be given as far in advance as possible to allow the recipient to consider and assess the implications and risks arising. DOC4.4 Significant Incidents DOC4.4.1 Where an Event on the Distribution System has had or may have had a significant effect on the Users installation or where an Event in the Users installation has had or may have had a significant effect on the Distribution System, DSP(s), in consultation with the User, shall deem the Event to be a Significant Incident. Significant incidents shall be reported in writing to the affected party in accordance with the provision of DOC5.
DOC5: Event Recording DOC5.1 Introduction DOC5.1.1 DOC5 sets the requirements for reporting in writing those Events deemed to be Significant Incidents under DOC4. DOC5.1.2 DOC5 also provides for the joint investigation of Significant Incidents by the Users involved. DOC5.2 Scope DOC5.2.1 DOC5 applies to the following Users of the Distribution System: a) Major Customers connected to the Distribution System where DSP(s) considers it appropriate; b) Embedded Generating Plant with a capacity greater than 2 MW c) Customers with CHP and Customers with Auto-production where DSP(s) reasonably considers it appropriate. DOC5.3 Procedures DOC5.3.1 DSP(s) and each User specified in DOC5.2.1 shall nominate officers and establish communication channels to ensure the effectiveness of DOC5. Such officers and communication channels may be the same as those established under DOC4. DOC5.3.2 Communication shall, as far as possible, be direct between the User and DSP(s). This does not, however, preclude communication with the Users nominated representative. DOC5.3.3 In the case of an Event that has been reported to DSP(s) under DOC4 and subsequently has been determined by DSP(s) to be a Significant Incident, a written report shall be given to DSP(s) by the User in accordance with DOC5.
DOC5.5.2 Matters applicable to DSP(s) are as follows: Effect on Users where appropriate: (a) (b) Duration of incident; and Estimated date and time of return to normal service.
DOC5.5.3 Matters applicable to Embedded Generators as follows: (a) date and time of Significant Incident; (b) location; (c) equipment involved; (d) brief description of Significant Incident; (e) details of any Demand Control undertaken; (f) conclusions and recommendations if applicable DOC6: System Tests DOC6.1 Introduction DOC6.1.1 DOC6 sets out the responsibilities and procedures for arranging and carrying out System Tests which have or may have an effect on the Systems of DSP(s) or Users. System Tests are those which involve either simulated or the controlled application of irregular, unusual or extreme conditions on the Total System or any part of the Total System, but which do not include Commissioning or reCommissioning tests or any other tests of a minor nature. DOC6.2 Scope DOC6.2.1 DOC6 applies to the following Users of the Distribution System: (a) (b) (c) Major Customers connected to the Distribution System where DSP(s) considers it appropriate; Embedded Generating Plant with a capacity greater than 2MW; Customers with CHP and Customers with Auto-production where DSP(s) reasonably considers it appropriate.
DOC6.3 Procedures DOC6.3.1 If the System Test is proposed by DSP(s) or the User connected to the Distribution System then the provisions of DOC6 shall apply.
DOC6.3.2 If the system test will or may have an affect on the Transmission System, then the provision of the Saudi Arabian Grid Code shall apply. DOC6.3.3 System Tests which have a minimal effect on the Distribution System or the systems of others will not be subject to this procedure; minimal effect shall be taken to mean variations in voltage, Frequency and waveform distortion of a value not greater than those figures which are defined in the Distribution Planning Code. DOC6.3.4 When DSP(s) or a User intends to undertake a System Test which may have significant effect on the System of others normally twelve months notice, or as otherwise agreed by DSP(s), shall be given by the person proposing the System Test (Test Proposer) to DSP(s) and to those Users who may be affected by such a System Test. DOC6.3.5 The proposal shall be in writing and shall contain details of the nature and purpose of the proposed System Test and shall indicate the extent and situation of the Plant or apparatus involved. DOC6.3.6 If the information set out in the proposal notice is considered insufficient by the recipient they shall contact the Test Proposer with a written request for further information which shall be supplied as soon as reasonably practicable. DSP(s) shall not be required to do anything under DOC6 until they are satisfied with the details supplied in the proposal or pursuant to a request for further information. DOC6.3.7 If DSP(s) wishes to undertake a System Test, DSP(s) shall be deemed to have received a proposal of that System Test. DOC6.3.8 DSP(s) shall have overall co-ordination of the System Test, using the information supplied to it under DOC6 and shall identify in its reasonable estimation, which Users other than the Test Proposer, may be affected by the proposed System Test. DOC6.3.9 Following receipt of the System Test proposal DSP(s) shall evaluate the impact of the System Test and discuss the proposals with Users identified as being affected.
DOC6.3.10 Within one month of receiving the System Test proposal DSP(s) shall submit a report to the Test Proposer which shall contain: (a) (b) proposals for carrying out the System Test (including the manner in which it is to be monitored); an allocation of costs between the affected parties, (the general principle being that the Test Proposer will bear the costs); and such other matters that DSP(s) consider appropriate; an outline of the procedure to be followed and the proposed test schedule and advice of any costs.
(c)
DOC6.3.11 the proposal report shall be submitted to all those who received a notice under DOC6.3.4. DOC6.3.12 If the proposal report (or a revised proposal report as agreed between DSP(s) and the Test Proposer) is approved by all recipients, the System Test can proceed. DOC6.3.13 At least one month prior to the date of the proposed System Test, DSP(s) shall submit to all recipients of the proposal notice a programme which in DOC6 shall be called a Final Test Programme stating the switching sequence and proposed timings, a list of those staff involved in carrying out the System Test (including those responsible for site safety) and such other matters as DSP(s) deem appropriate. DOC6.3.14 The final test programme shall bind all recipients to act in accordance with the provisions contained within the programme in relation to the proposed System Test. DOC6.3.15 At the conclusion of the System Test, the Test Proposer shall be responsible for preparing a written report (the Final Report) of the System Test for submission to DSP(s). DOC6.3.16 The Final Report shall include a description of the Plant and/or apparatus tested and of the System Test carried out, together with the results, conclusions and recommendations. DOC6.3.17 Results of tests shall be reported to relevant parties, taking into account confidentiality issues.
DOC6.3.18 all system test procedures shall comply with all applicable legislation. DOC7: Monitoring Testing and Investigation DOC7.1 Introduction DOC7.1.1 In order to discharge its responsibilities in respect of safe, secure and economic operation of the Distribution System and in accordance with its licence conditions DSP(s) shall organise and carry out monitoring, testing and investigation on the effect of Users electrical apparatus or electrical installation on the Distribution System. DOC7.2 Scope DOC7.2.1 DOC7 applies to the following Users of the Distribution System: (a) all Embedded Generators (b) all Customers who are connected to the Distribution System DOC7.3 Procedures DOC7.3.1 DSP(s) shall, from time to time, determine the need to test or monitor the quality of supply at various points on the Distribution System. DOC7.3.2 The requirements for specific testing and/or monitoring may be initiated by the receipt of specific complaints as to the quality of supply on the Distribution System. DOC7.3.3 Where testing or monitoring is required at the Connection Point with a User then DSP(s) shall advise the User involved and DSP(s) shall make available the results of such tests to the User. DOC7.3.4 Where a User is found to be operating outside the technical limits specified in the Distribution Code then the User shall rectify the situation or disconnect the apparatus causing the problem from its electrical system connected to the Distribution System immediately or within such time as agreed with DSP(s).
DOC7.3.5 Continued failure to rectify the situation shall result in the User being disconnected. DOC7.3.6 DSP(s) shall, from time to time, monitor the affects of the User on the Distribution System. DOC7.3.7 The monitoring shall normally be related to the amount of Active Power and Reactive Power or Flicker or Harmonics transferred across the Connection Point. DOC7.3.8 Where the User is exporting or importing Active Power or Reactive Power in an amount causing disturbances, DSP(s) shall inform the User and the User shall restrict the power transfer to within the specified parameters. DOC7.3.9 DSP(s) may check from time to time that Users are in compliance with agreed Protection requirements and Protection settings.
DOC8: SAFETY CO-ORDINATION DOC8.1 INTRODUCTION DOC8.1.1 DOC11 specifies the safety rules and procedures to be applied by the DSP(s) to meet statutory requirements and Distribution Licence conditions and obligations. DOC8.1.2 Similar safety rules and procedures shall be provided by other Users of the Distribution System when carrying out work or tests at the operational interface with the DSP(s). DOC8.2 OBJECTIVES DOC8.2.1 the objectives of safety co-ordination procedures are to lay down the Safety Management criteria to be applied, to ensure safety of persons working on the Distribution System and/ or across operational and ownership boundaries.
DOC8.3 SCOPE DOC8.3.1 DOC8 specifies the safety rules and procedures that apply to the DSP(s) and the following Users of the Distribution System: a) Embedded Generators b) Major Customers c) Any other party reasonably specified by the DSP(s) including Users connected at Medium or Low Voltage for appropriate sections of DOC8 when necessary d) Agents of the DSP(s) or Users working on the Distribution System or at or across operational boundaries. DOC8.4 DOC8.4.1 Procedures The Safety Management principles and procedures (Safety Management System) for ensuring the health and safety of all relevant personnel shall be specified by DSP(s) and Users for work on their respective Systems or Plant apparatus connected to them. There shall be joint agreement by DSP(s) and Users on which Safety Management System is to be used for sites or locations where an operational boundary exists and proper documentation of the safety precautions to be taken shall be maintained. There shall be written authorisation of personnel who do the work of control, operation, work or testing of Plant apparatus forming part of, or connected to, the Distribution System. There shall be joint agreement between DSP(s) and Users which specifies responsibility for system or control equipment which shall ensure that only one party is responsible for any item of Plant or apparatus at any one time. DSP(s) and each User shall at all times have nominated a person or persons responsible for the co-ordination of safety on the respective system.
DOC8.4.2
DOC8.4.3
DOC8.4.4
DOC8.4.5
DOC8.4.6
DSP(s) and each User shall maintain a suitable system of documentation which records all relevant Operational Events that have taken place on the Distribution System or other system connected to it and the co-ordination of relevant safety precautions for work. System diagrams which show sufficient information for control personnel to carry out their duties shall be exchanged between DSP(s) and User as required. Safety at the DSP(s)/User Interface The following procedures set down the basic safety requirements at the operator and DSP(s) interfaces. These procedures are necessary to ensure the safety of all who may have to work at either side of the interface or on the interface (boundary). (a) Written rules for safety working and communicating procedures shall be available and used by all persons who may have to work at or use the facilities provided at the Interface. Electrical equipment connected to either side of the interface and interface equipment shall be under the control of a named person at either side. Each item of equipment shall be controlled by only one identifiable person at any one time. Adequate means of isolation shall be provided at the interface to allow work to be carried out safely at either side of the interface. Where necessary to prevent danger adequate facilities for Earthing shall be provided at either side of the interface to allow work to be carried out safely at the interface or at either side of the interface. Adequate working space, adequate means of access and egress and, where necessary, adequate lighting shall be provided at all electrical equipment, on or near which work is being done in circumstances which may cause danger.
DOC8.4.7
DOC8.5 DOC8.5.1
(b)
(c)
(d)
(e)
(f)
(h)
DOC8.6 SAFETY RULES DOC8.6.1 Operation and Maintenance of the Users equipment shall only be carried out by authorized personnel. Before first Commissioning the Plant, operating procedures shall be agreed with the DSP(s). DOC8.6.2 Instructions for operating and / or Earthing the Users electrical equipment shall be clearly displayed in the Users Medium and High Voltage switch room. DOC8.6.3 Safety Procedures for personnel working on or in close proximity to the Distribution System Plant and apparatus shall be governed by the DSP(s). DOC8.6.4 In the event of a conflict between the provisions of this Code and the provisions of the TSP safety rules, the provisions of the TSP Safety Rules shall take precedence.
PART 6: DEFINITIONS
DCD1 Active Power The product of voltage and the in-phase component of alternating current (normally measured in kilowatts (kW) or megawatts (MW). Ambient Temperature The surrounding temperature (in the absence of the equipment) of the immediate environment in which equipment is installed. This temperature normally varies. A derived constant value is taken for the purposes of designing or rating equipment. AVR Automatic Voltage Regulator Back-Up Protection That Protection system which will open a Circuit Breaker or other fault-current interrupting device in the absence of the current Protection operation of another Protection system Black Start The procedure which is necessary for recovery from a total or partial system shutdown Bulk Supply Point A point of connection between the Transmission System and the Distribution System or between the Transmission System and a directly connected Customer Central Dispatch The Dispatch of Generating Units by the Transmission Service Provider (TSP) Centrally Dispatched Generating Units Generating Units subject to Dispatch by the TSP Circuit Breaker A mechanical switching device, capable of making, carrying and breaking currents under normal circuit conditions and also of making, carrying for a specified time and breaking currents under specified abnormal circuit conditions, such as those of short circuit
DCD2
DCD3
DCD4
DCD5
DCD6
DCD7
DCD8
DCD9
DCD10
CHP - Combined Heat and Power The simultaneous production of utilisable heat and electricity from an integrated thermo-dynamic process Commissioning The final process of testing part of a system prior to that part of the system being considered suitable for normal use Connected Load The sum of the nameplate ratings of all present and future electrical equipment installed by a Customer. Connected load is measured in volt-amperes (VA). Connection Agreement An agreement between DSP(s) and each User setting out terms relating to a connection with the Distribution System Connection Point The physical point at which Users Plant or apparatus is joined to the Distribution System. Customer A User whose premises are connected to the Distribution System for the purpose of obtaining a supply of electricity at that premises Customer with Auto-Production A Customer generating electricity for their own use. Demand The electric power which is drawn for the system by a Customer, usually expressed in MW, MVA or MVAR. Demand Load The maximum load drawn from the power system by a Customer at the Customers interface (either estimated or measured). Disconnector A device which provides in the open position a means of disconnecting apparatus from the Distribution System in accordance with specified requirements
DCD11
DCD12
DCD13
DCD14
DCD15
DCD16
DCD17
DCD18
DCD19
DCD20
Dispatch The issue of instructions for Generating Units to achieve specific Active Power and Reactive Power outputs within Registered Data parameters and by stated times. Distribution Code This code, required to be prepared by DSP(s) pursuant to condition 14 (Compliance with transmission, distribution and market codes) of the Distribution Licence and approved by ECRA as revised from time to time with the approval of, or by the direction of, ECRA. Distribution Code Review Panel The panel with the functions which are set out in DGC6 Distribution Licence A distribution licence granted under Article 5 and 6 of the Electricity Law promulgated on 20/10/1427 AH (21/11/2006 AD) by Royal Decree M/56 and ECRA Charter dated 17/05/1425 AH (05/07/2004 AD) Distribution System The system which consists of electric lines, electric Plant, transformers and switchgear and which is used for conveying electricity to final Customers Distribution Service Provider (DSP) The legal entity that is licensed to own and maintain a network on the Distribution System (or has such right by virtue of its historic existence for this purpose) Distribution Use of System Agreement The agreement between DSP(s) and Retailers/ Traders for transport of electricity from the Transmission System or Embedded Generators through the Distribution System to Customers Disturbing Loads Loads which have the potential to introduce waveform distortion (Harmonics, Flicker) or phase unbalance into the system.
DCD21
DCD22
DCD23
DCD24
DCD25
DCD26
DCD27
DCD28
Earthing The provision of a connection between conductors and earth by means of an Earthing Device. Earthing Device A means of providing a connection between a conductor and earth of adequate strength and capability for its intended purpose. ECRA Electricity and Co-Generation regulatory Authority. Effectively Earthed System A power system in which the neutral is connected to earth either directly or through a neutral resistor. Embedded Having a direct electrical connection to the Distribution System. Embedded Generators A Generator whose Generating Units are directly connected to the Distribution System and includes Customers with CHP and Customers with Auto-production. Event An unscheduled or unplanned (although it may be anticipated) occurrence on or relating to a System including, without limiting that general description, faults, incidents and breakdowns. Fault Level Prospective current that would flow into a short circuit at a stated point on the System. It is expressed in kA or in MVA.
DCD29
DCD30
DCD31
DCD32
DCD33
DCD34
DCD35
DCD36
Flicker Periodic fluctuations in voltage, at frequencies below the fundamental Frequency. These are generally expressed as percentage variations, relative to the fundamental voltage. Frequency The rate of oscillation of the AC supply. This is generally expressed as a Frequency range, in terms of a nominal Frequency in Hz (cycles per second), with plus and minus percentage limits.
DCD37
DCD38
Frequency Response The automatic adjustment of Active Power output from a Generation Unit(s) in response to Frequency changes. Fundamental Frequency The operating or system Frequency of the Power System. Parameters whose Frequency is the same as the fundamental Frequency are referred to as fundamental parameters. Generating Plant A power station with one or more Generating Units. Generating Unit An apparatus which produces electricity. Generator A person who generates electricity. Good Industry Practice The standard of practice attained by exercising that degree of skill, diligence, prudence and foresight which would reasonably and ordinarily be expected from a skilled and experienced operator engaged in the same type of undertaking under the same or similar circumstances. Grid Code The Saudi Arabian Grid Code Harmonics Sinusoidal currents with a Frequency equal to an integer multiple of the fundamental Frequency. High Voltage A voltage, used for the supply of electricity, the lower limit of nominal RMS value of which is greater than 100kV. IEC International Electrotechnical Commission.
DCD39
DCD40
DCD41
DCD42
DCD43
DCD44
DCD45
DCD46
DCD47
DCD48
Isolated Disconnected from associated equipment by an isolator or adequate physical separation. kVA Kilo-Volt ampere. Low Voltage A voltage used for the supply of electricity, the upper limit of nominal RMS value of which does not exceed 1kV. Major Customer A Customer who is supplied at Medium Voltage whose Load is greater than 1MVA Medium Voltage A voltage used for the supply of electricity, the nominal value of which is between 11kV and 36kV. MVAR Megavar (1,000,000 Volt Amperes reactive). MW Megawatt (1,000,000 Watts). Normal Operating Frequency The Frequency at which the system normally operates i.e. 60Hz. Operation A scheduled or planned action carried out on a system. Operational Effect The effect of any Operation which causes the Transmission System or the Distribution System, or the system of other Users, to operate (or be at a materially increased risk of operating) differently from the way in which they would or may have operated in the absence of such Operation. Planned Outage An outage of Generating Plant or of part of the Transmission System or of part of the Distribution System other than a forced outage.
DCD49
DCD50
DCD51
DCD52
DCD53
DCD54
DCD55
DCD56
DCD57
DCD58
DCD59
Plant Fixed and movable items used in the generation and/or supply and/or transmission and/or distribution of electricity other than apparatus. Power Factor The ratio of Active Power to apparent power. Protection The provisions for detecting abnormal conditions in a System and initiating fault clearance or actuating signals or indications. Reactive Power The product of voltage and current and the sine of the phase angle between them which is normally measured in Kilo vars (kVAR) or Mega vars (MVAR). Retail Business The business of bulk purchase for the purpose of retail sale of electricity to Consumers or large consumers authorized by a licence. Safety Management The procedure adopted by the DSP or a User to ensure the safe operation of its system and the safety of personnel required to work on that system. Safety Procedures The procedures which are specified within a Safety Management system. Significant Incident An Event which has had or which may have an Operational Effect on the Transmission or Distribution system or on a Users installation. Step Change in Voltage A step change is defined as a single, rapid change of the RMS voltage. Distribution System voltage step changes can occur due to switching in and out of capacitors, lines, cables, transformers and other Plant.
DCD60
DCD61
DCD62
DCD63
DCD64
DCD65
DCD66
DCD67
DCD68
System Tests Those tests which involve simulating conditions or the controlled application of irregular, unusual or extreme conditions on the Total System or any part of it, but not including routine testing, Commissioning or reCommissioning tests. Total Harmonic Distortion Total harmonic distortion is the aggregate of the harmonic distortions at all harmonic frequencies. This is expressed as the root mean square value of harmonic distortions, at all harmonic frequencies. Trading Business The business of bulk purchase for the purpose of sale of electricity from/ to other Licensees or large Consumers authorized by a licence. Transmission System Reference shall be made to the Saudi Arabian Grid Code (SAGC) for detailed definition. Transmission Service Provider (TSP) The legal entity that is licensed to own and maintain a network on the Transmission System (or has such right by virtue of its historic existence for this purpose). User A term used in various sections of the Distribution Code to refer to the persons using the Distribution System, more particularly identified in each section of the Distribution Code. Voltage Reduction A method to control Demand temporarily by reduction of system voltage. Voltage Unbalance In three-phase networks, the conditions in which the RMS values of the phase voltages, or the angles between consecutive phases, are not equal.
DCD69
DCD70
DCD71
DCD72
DCD73
DCD74
DCD75
DCD76
Zero Phase Sequence A set of phases of equal magnitude and zero phase angle, relative to each other. The 3-phase values are thus in phase with each other. The term zero sequence may be applied, in the same sense, to AC voltages and currents.
CONTENTS
1.1 1.2 1.3 2.0 2.1 2.2 2.3 3.0 3.1 3.2 3.3
General Definition Aim of Planning DISTRIBUTION SYST Standard Configuration Voltage Levels Effects of Disturbing Loads ASSESSMENT OF NEW LOAD Application Form Information Required from Customers Need for room substation As per DSP(s) Customer service manual
102 102 105 107 107 108 108 109 109 109 111 111
1.0 1.1
INTRODUCTION General The DSP(s) is required to operate and ensure the maintenance of and develop, as necessary, a safe, secure, reliable, economical and efficient electricity Distribution System. To this end, this document, Security and Planning Standards for the Distribution System has been prepared in accordance with the Distribution Code. It outlines DSP(s)s approach to the development of the network, giving details of how the connection of new loads and Embedded Generators to the Distribution System are assessed. It is intended as a guide to Users of the Distribution System and is referred to in the Distribution Code (Reference 2). While this guide refers to Customers loads, the same factors will apply, in general, to Generators also. There are however, some specific requirements relating to Generators and these are included under a separate heading. (Section 5).
1.2
Definitions In general the terms used in this document have the meanings intended in the Distribution Code. As a brief guide, the terms used in this document are defined below:
Term
Connection Asset
Definition
The network erected to connect the Connection Point to the existing Distribution System. The connection asset forms part of the Distribution System and is not shared by other Users. This describes the quality of a supply as it relates to outages, whether caused by faults or planned work. A set of measures are required to describe continuity but, in general, the lower the incidence of outages and the shorter their duration, the higher the continuity. The electric lines, Plant and switch-gear used to convey electricity to final Customers (excluding Customers connected directly to the Transmission System (grid)).
Distribution System
Disturbing Load
An electrical load that of its nature may affect the quality of electricity supply of other Customers. Examples are welders, large electric motors etc. (See Appendix 1). Voltage fluctuations, caused by a disturbing load (or rapid variations in Generator output), the major effect of which is Flickering of standard (incandescent) light bulbs.
Flicker
Looped Connection
As described in DPS
Losses
Electrical losses are the difference between the energy entering the Distribution System and that delivered to Customers. Losses are the energy lost in the network due to the heating effect of the electricity passing through it. This is the maximum load that the Customer has contracted with DSP(s). The network configuration under normal conditions and when all distribution Plant is in service. The normal feeding arrangement is typically designed to provide best voltage performance, to minimise network losses and to make optimum use of the capacity of feeding substations.
Security of Connection
The short circuit level is a measure of the strength of the network i.e. the ability to limit the impact of Disturbing Loads and to maintain voltage stability. The size of the Customer switched load relative to the short circuit level determines the magnitude of its impact on the voltage. This refers to the short circuit rating of the item
Distribution Substation
1.3
Aim of Planning The aim of planning is to ensure that the Distribution System is developed in an orderly and cost effective manner. It is necessary to ensure that there is capacity available to meet new loads as they arise, and to meet ongoing growth requirements. It is also necessary to ensure that new connections are made: 1. in an economic fashion 2. with a view to the possible future needs of the Customer and the network 3. in a way that is technically acceptable
2.0 2.1
DISTRIBUTION SYSTEM Standard Configuration The standard configuration of the Distribution System is illustrated schematically in Figure 1 below. High Voltage
HV/MV Substation
MV/LV Substation Low Voltage Network Figure 1: Representation of the Distribution System
2.2
Voltage Levels There are a number of standard voltages in use on the Distribution System and Customers will be connected at one of these levels. Voltage Levels at which a connection can be provided are as follows:
Voltage Level
Low Voltage (LV) Medium Voltage (MV)
Nominal Voltage
220/127V (phase-phase/phase-neutral) 380/220V (phase-phase/phase-neutral) 13.8kV, 33kV ,69kv(standard) 11kV, 34.5kV (existing but non-standard)
Table 1: Distribution System Nominal Voltages 2.3 Effects of Disturbing Loads Certain types of equipment such as motors and welders may cause fluctuations in the supply voltage which cause disturbances to the connection of other Customers. Where Customers intend to install any equipment likely to cause supply disturbances, this equipment must be evaluated to assess the likely impact. The limits imposed on Disturbing Loads are specified in the Distribution Code. It may be necessary, depending on the characteristics of the equipment, for a Customer connection to be made using a different network configuration via a higher voltage, a dedicated substation or other method.
3.0
The assessment of the connection for a new load requires details of the load. The details should be provided by completing an application form as in (See attachment). 3.2 Information Required from Customers
Details of the information required from Demand Customers and Generators seeking connections or extensions to the Distribution System are provided in the Distribution Code. Application forms for connection are available from DSP(s) offices, and are on the DSP(s)s website. Specifically the following information may be requested, depending on the nature of the load: 3.2.1 Geographical Location Site location maps and site layout plans in order to determine the location of the proposed load in relation to the existing network and plan cover area 3.2.2 Maximum Import Capacity (MIC) Maximum Import Capacity (MIC) required, the size and nature of the load, diversity of the load and proposed phasing of the development i.e. the pace at which the load is expected to increase from a specified initial Demand to the full Demand. 3.2.3 Disturbing Loads Details of any disturbing elements of the load are required such as: Large motors - details of starting arrangements for all large motors. Disturbing Loads i.e. electric welding, and details of the nature and usage pattern of the disturbing load. Harmonics - details of any non-linear equipment likely to produce Harmonics on our system and any filtering arrangements which the Customer may have already in place. The Customer should also provide details of compensation or balancing equipment connected. Unbalanced Loads Where a Customer has a three phase supply, load should be balanced as evenly as possible over the three phases.
The above is an example of the information which may be requested. Depending of the size and complexity of the load, additional information may also be requested. Power Factor The Power Factor of the Customers load as seen by the network must be 0.85 or higher. No Customer may present a leading Power Factor load to the DSP(s) system.
3.2.4 Multiple Customer Development Versus Single Load Whether the application is for infrastructure to facilitate connections to multiple end Customers within a development or is for connection of a single Customer. 3.2.5 Specific Requirements Details of any specific Customer requirements for connection of the load. 3.2.6 Load Coincidence Customers should note when assessing the Capacity requirements that not all of the equipment will be operating at full load at the same time. The Customer should apply a coincidence factor to each component of the load, as well as to the overall load in order to assess the capacity required. Coincidence factors will vary depending on the nature of the load. 3.3 Need for room substation As per DSP(s) Customer service manual