Substation Grounding Grid Design Using A
Substation Grounding Grid Design Using A
Substation grounding grid design using Alternative Transients Program-ATP and ASPIX
This example shows the method for designing a grounding grid following the standard IEEE 80 safety criteria. It
shows the procedure for designing the grounding grid of a substation with voltage levels of 115 kV and 34.5 kV.
1 Software
This example of the design was developed with the aid of the following software:
Alternative Transients Program (ATP): Licensing to use ATP is free of all charges for all who are not engaged in
EMTP commerce. For information on the licensing and user groups, visit the website: http://www.emtp.org/
Aspix: You may obtain a trial version for 30 days. This version allows you to run simulations and observe the
results; however, you cannot save or generate reports. You can request a 30-day free license without
functionality limitations. The program can be downloaded from the following website:
http://www.spartalightning.com/products/aspix
Aspix Resistivity Analyzer: It is an Excel spreadsheet that allows the processing of the resistivity
measurements to obtain a two-layer model. This spreadsheet sheet is available for free and can be
downloaded from the website: http://www.spartalightning.com/download
2 Design method
The method for designing the grounding grids includes the following steps:
1. Measuring and analyzing the soil resistivity.
2. Plotting the grounding grid layout.
3. Calculating the grounding grid resistance with the initial design.
4. Calculating the earth current distribution.
5. Calculating the touch and step voltages.
6. Verifying the touch and step voltages.
7. Redesign of the grounding grid when the calculated touch and step voltages are higher than the tolerated
values; the procedure is repeated from point 2.
3 Input information
The following information is required for designing the grounding grid:
Single line diagram of the power system
Short-circuit levels
Parameters of the power transformers
Substation plan view
Measurements of the soil resistivity
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 2
230 kV
150 MVA
Ynyn0D11
115 kV Z1 = 14% Z0= 14%
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 3
5 Resistivity measurements
The measurements are obtained using the Wenner method for a separation of the electrodes of up to 8 m and
using the Schlumberger-Palmer method for a separation of the voltage electrodes of up to 32 m. The soil
resistivity measurement data are summarized in Table 1.
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 4
The Aspix Resistivity Analyzer is used for processing the resistivity measurements and to obtain the two-layer
model. This processor is an Excel spreadsheet that generates a curve of resistivity with a probability of
non-exceedance of 70%. From this curve, Aspix Resistivity Analyzer tries to find the values of the upper-layer
resistivity, bottom-layer resistivity, and depth of the top layer that best suit to the obtained measurements. This
tool displays a graph where the user can observe the resistivity measurements and the values calculated by the
analyzer, allowing comparison of the model with the measurements. Table 2 summarizes the processing of the
resistivity measurements in Table 1.
Table 2. Earth resistivity measurement processing
Resistivity Analyzer
Resistivity Analyzer Version 1.0
Unequally Spaced - Schlumberger-Palmer http://www.spartalightning.com/
Equally Spaced - Wenner Method
Method
Profile
a (m) a (m) c(m) a (m) c(m) a (m) c(m) a (m) c(m) Resistivity_70% Resistivity 2LModel
2 4 8 16 4 32 4 250
P1 (Ohm_m) 193.1 168.5 139.6 101.7 210.7
P2 (Ohm_m) 167.7 185.3 185 211.4 66.9
200
P3 (Ohm_m) 222.3 129.5 117.9 164.4 123.4
Resistivity (ohm-m)
The resistivity analyzer provides the following parameters for the two-layer model:
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 5
6 Initial design
6.1 Grounding grid layout
The design of the grounding grid must be such that it ensures the safety of persons against failures, and requires
the minimum amount of materials and work. In the design method, initially a mesh is drawn on the substation
layout covering all the substation equipment. This first layout of the grounding grid must take into account the
following:
All the substation equipment require at least one ground pigtail for their structures.
When the substation has a metallic fence, a ground conductor can be buried outside the fence in order to
control the touch voltages. Normally, it is a cable installed 1 m outside the fence, buried at 50-cm depth. This
cable must be interconnected with the internal grounding grid every 20-50 m, depending on the soil resistivity.
A cable around the transformers, outside the transformer foundation.
A cable outside the gantry foundations.
The minimum number of cables required to facilitate grounding of all the equipment and their structures are
drawn.
In the case of the above example, the fence is a brick wall; therefore, it is not necessary to install a buried cable
outside the fence. Figure 3 shows the plan view of the substation and the grounding grid drawn according to the
above mentioned criteria.
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 6
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 7
These parameters are entered in the Aspix program using the “Simulation” option in the “Simulation Settings”
menu. Figure 4 shows the parameters entered in the program.
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 8
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 9
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 10
By assumed an average span of 300 m and a tower footing resistance of 30 , the 20 sections of the line closest
to the substation (6 km) are modeled in detail, and the remaining part is modeled as a single section. Figure 8
shows the network modeled using the ATP program.
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 11
115 kV
Ground wire
34.5 kV
2720 A
875 A
Grounding in
Towers footing resistances the fault point
Substation
grounding grid
2720 A
1121 A
815 A
Ground wire
4000
[A]
3000 Fault ground current and
transformer neutral
2000 current
1000
Substation grounding
0
grid current
-3000
-4000
0.00 0.02 0.04 0.06 0.08 [s] 0.10
(f ile Ejemplo_Aspix.pl4; x-v ar t) c:MALL -NEUT c: -MALL c:CG1 -MALL c:CG2 -MALL
c:FALL -
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 12
The effect of the direct current component of the short-circuit current is negligible given that the X/R relationship
of the system in the substation analyzed is less than 10 and the fault duration is 500 ms.
The step voltages must be controlled both inside and outside the substation; however, it is not necessary to
calculate them in very large areas because the highest step voltages appear on the perimeter of the grounding
grid. Therefore, when we control the step voltages on the perimeter, we control them elsewhere. Therefore, a
good approach is to calculate the step voltages in a region that covers the total area of the grounding grid.
The touch voltages must be controlled at all the sites where people can touch the grounded structures (steel
structures, transformers, electric panels, metal poles, etc.). Usually, these grounded structures are located
within the area covered by the grounding grid. Therefore, a valid criterion is calculating the touch voltages in a
region that covers the entire area of the grounding grid.
The areas in which the touch and step voltages are calculated are added by right-clicking on “Chart Areas” and
then clicking on the “New Chart Area.” The program displays a window that is shown in Figure 11.
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 13
Area 5
Area 4
Area 3
Area 2
Area 1
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 14
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 15
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 16
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 17
2219.1 V and is above the calculated step voltage of 406.5 V. In summary, with this initial design, the tolerable
touch voltage is exceeded, i.e., the design does not meet the safety criteria and should therefore be modified.
7 Modified design
7.1 Grounding grid layout
The modifications to the initial design must be oriented to the reduction in the touch voltages, for which there are
different alternatives such as follows:
The ground potential rise (GPR) is decreased, for which the alternatives are as follows: reduce the grounding
grid resistance or decrease maximum current through the grounding grid.
The space between the parallel conductors is reduced by adding conductors on the inside of the grid of the
initial design.
The first option is to attempt to decrease the touch voltage by reducing the space between the parallel
conductors. This requires identifying the points where the tolerable touch voltage is exceeded. The regions where
the tolerable touch voltage is exceeded appear circled as shown in Figure 18, and the modification of the design
consists of adding cables in these regions. Figure 19 shows the modified design.
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 18
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 19
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 20
115 kV
Ground wire
34.5 kV
2732 A
856 A
Grounding in
Towers footing resistances the fault point
Substation
grounding grid
2732 A
1188 A
793 A
Ground wire
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 21
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 22
http://www.spartalightning.com/
GROUNDING GRID DESIGN PAGE 23
http://www.spartalightning.com/