Manual ASDA B2
Manual ASDA B2
Manual ASDA B2
Preface
Thank you very much for purchasing DELTAs AC servo products. This manual will be helpful in the installation, wiring, inspection, and operation of Delta AC servo drive and motor. Before using the product, please read this user manual to ensure correct use. You should thoroughly understand all safety precautions (DANGERS, WARNINGS and STOPS) before proceeding with the installation, wiring and operation. If you do not understand please contact your local Delta sales representative. Place this user manual in a safe location for future reference.
Important precautions
Before using the product, please read this user manual thoroughly to ensure correct use. Store this manual in a safe and handy place for quick reference whenever necessary. Always observe the following precautions: Do not use the product in a potentially explosive environment. Install the product in a clean and dry location free from corrosive and inflammable gases or liquids.
Revision January 2012
Preface
ASDA-B2
Do not connect commercial power to the U, V, W terminals. Failure to observe this precaution will cause severe damage to the Servo drive. Ensure that the motor and drive are correctly connected to a ground. The grounding method must comply with the electrical standard of the country (Please refer to NFPA 70: National Electrical Code, 2005 Ed.).
Do not disconnect the AC servo drive and motor while the power is ON. Do not attach, modify or remove wiring while power is applied to the AC servo drive. Before starting the operation with a mechanical system connected, make sure the emergency stop equipment can be energized and work at any time. Do not touch the drive heat sink or the servo motor during operation, this may cause serious personnel injury.
PLEASE READ PRIOR TO INSTALLATION FOR SAFETY. Carefully note and observe the following safety precautions when receiving, inspecting, installing, operating, maintaining and troubleshooting. The following words, DANGER, WARNING and STOP are used to mark safety precautions when using the Deltas servo product. Failure to observe these precautions may void the warranty! ASDA-B2 series drives are open type servo drives and must be installed in an NEMA enclosure such as a protection control panel during operation to comply with the requirements of the international safety standards. They are provided with precise feedback control and highspeed calculation function incorporating DSP (Digital Signal Processor) technology, and intended to drive three-phase permanent magnet synchronous motors (PMSM) to achieve precise positioning by means of accurate current output generated by IGBT (Insulated Gate Bipolar Transistor). ASDA-B2 series drives can be used in industrial applications and for installation in an end-use enclosure that do not exceed the specifications defined in the ASDA-B2 series user manual (Drives, cables and motors are for use in a suitable enclosure with a minimum of a UL50 type 1 or NEMA 250 Type 1 rating). The words, DANGER, WARNING and STOP, have the following meaning: Indicates a potentially hazardous situation and if not avoided, may result in serious injury or death. Indicates a potentially hazardous situation and if not avoided, may result in minor to moderate injury or serious damage to the product. Indicates an improper action that it is not recommended. Doing so may cause damage or malfunction.
ii
ASDA-B2
Preface
Unpacking Check
Please ensure that both the servo drive and motor are correctly matched for size (power rating). Failure to observe this precaution may cause fire, seriously damage to the drive / motor or cause personal injury.
Installation
Do not install the product in a location that is outside the stated specification for the drive and motor. Failure to observe this caution may result in electric shock, fire, or personal injury.
Wiring
Connect the ground terminals to a class-3 ground (Ground resistance should not exceed 100 ). Improper grounding may result in electric shock or fire. Do not connect any power supplies to the U, V, W terminals. Failure to observe this precaution may result in serious injury, damage to the drive or fire. Ensure that all screws, connectors and wire terminations are secure on the power supply, servo drive and motor. Failure to observe this caution may result in damage, fire or personal injury.
Operation
Before starting the operation with a mechanical system connected, change the drive parameters to match the user-defined parameters of the mechanical system. Starting the operation without matching the correct parameters may result in servo drive or motor damage, or damage to the mechanical system. Ensure that the emergency stop equipment or device is connected and working correctly before operating the motor that is connected to a mechanical system. Do not approach or touch any rotating parts (e.g. shaft) while the motor is running. Failure to observe this precaution may cause serious personal injury. In order to prevent accidents, the initial trial run for servo motor should be conducted under no load conditions (separate the motor from its couplings and belts). For the initial trial run, do not operate the servo motor while it is connected to its mechanical system. Connecting the motor to its mechanical system may cause damage or result in personal injury during the trail run. Connect the servo motor once it has successfully completed a trail run. Caution: Please perform trial run without load first and then perform trial run with load connected. After the servo motor is running normally and regularly without load, then run servo motor with load connected. Ensure to perform trial run in this order to prevent unnecessary danger. Do not touch either the drive heat sink or the motor during operation as they may become hot and personal injury may result.
iii
Preface
ASDA-B2
NOTE
1) In this manual, actual measured values are in metric units. Dimensions in (imperial units) are for reference only. Please use metric units for precise measurements. 2) The content of this manual may be revised without prior notice. Please consult our distributors or download the most updated version at http://www.delta.com.tw/industrialautomation.
iv
Table of Contents
1.3 Servo Drive and Servo Motor Combinations ....................................................... 1-5 1.4 Servo Drive Features ......................................................................................... 1-6 1.5 Control Modes of Servo Drive ............................................................................ 1-7
Table of Contents
Motor Power Cable Connector Specifications ............................................ 3-7 Encoder Connector Specifications ............................................................. 3-9 Cable Specifications for Servo Drive.......................................................... 3-13
3.2 Basic Wiring ...................................................................................................... 3-15 3.3 Input / Output Interface Connector - CN1 .......................................................... 3-19 3.3.1 3.3.2 3.3.3 3.3.4 CN1 Terminal Identification ..................................................................... 3-19 Signals Explanation of Connector - CN1.................................................... 3-21 User-defined DI and DO signals ................................................................ 3-30 Wiring Diagrams of I/O Signals - CN1 ....................................................... 3-35
3.4 Encoder Connector - CN2 .................................................................................. 3-36 3.5 Serial Communication Connector - CN3 ............................................................. 3-39 3.6 Analog Monitor Output Connector - CN5 ........................................................... 3-40 3.7 Standard Connection Example ........................................................................... 3-41 3.7.1 3.7.2 3.7.3 Position (PT) Control Mode ....................................................................... 3-41 Speed Control Mode................................................................................. 3-42 Torque Control Mode ............................................................................... 3-43
vi
Table of Contents
4.3.4 4.3.5
Polarity Setting Display ............................................................................ 4-3 Monitor Setting Display ............................................................................ 4-4
4.4 General Function Operation .............................................................................. 4-7 4.4.1 4.4.2 4.4.3 4.4.4 4.4.5 Fault Code Display Operation ................................................................... 4-7 JOG Operation.......................................................................................... 4-8 Force Output Control Operation ............................................................... 4-9 DI Diagnosis Operation ............................................................................ 4-10 DO Diagnosis Operation........................................................................... 4-11
vii
Table of Contents
6.3 Speed Control Mode ......................................................................................... 6-11 6.3.1 6.3.2 6.3.3 6.3.4 6.3.5 6.3.6 6.3.7 Command Source of Speed Control Mode ................................................. 6-11 Structure of Speed Control Mode .............................................................. 6-12 Smoothing Strategy of Speed Control Mode .............................................. 6-13 Analog Speed Input Scaling ...................................................................... 6-18 Timing Chart of Speed Control Mode ........................................................ 6-19 Speed Loop Gain Adjustment ................................................................... 6-19 Resonance Suppression............................................................................ 6-26
6.4 Torque Control Mode ........................................................................................ 6-34 6.4.1 6.4.2 6.4.3 6.4.4 6.4.5 Command Source of Torque Control Mode ............................................... 6-34 Structure of Torque Control Mode ............................................................ 6-35 Smoothing Strategy of Torque Control Mode ............................................ 6-36 Analog Torque Input Scaling .................................................................... 6-36 Timing Chart of Torque Control Mode ...................................................... 6-37
viii
Table of Contents
Speed / Position Control Mode Selection .................................................. 6-38 Speed / Torque Control Mode Selection.................................................... 6-39 Torque / Position Control Mode Selection................................................. 6-39
6.6 Others .............................................................................................................. 6-40 6.6.1 6.6.2 6.6.3 6.6.4 Speed Limit.............................................................................................. 6-40 Torque Limit ............................................................................................ 6-40 Analog Monitor ........................................................................................ 6-41 Electromagnetic Brake .............................................................................. 6-45
ix
Table of Contents
10.2 Specifications of Servo Motors (ECMA Series) ................................................... 10-4 10.3 Servo Motor Speed-Torque Curves ................................................................... 10-8 10.4 Overload Characteristics ................................................................................. 10-9 10.5 Dimensions of Servo Drives ............................................................................. 10-11 10.6 Dimensions of Servo Motors ............................................................................ 10-15
Appendix A Appendix B
Table of Contents
About this Manual User Information Be sure to store this manual in a safe place. Due to constantly growing product range, technical improvement, alteration or changed texts, figures and diagrams, we reserve the right to make information changes within this manual without prior notice. Coping or reproducing any part of this manual, without written consent of Delta Electronics Inc. is prohibited.
Technical Support and Service You are welcome to contact our Technical Support Team at the below numbers or visit our web site (http://www.delta.com.tw/industrialautomation/) if you need technical support, service, information, or if you have any questions in the use of this product. We look forward to serving your needs and are willing to offer our best support and service to you.
ASIA DELTA ELECTRONICS, INC. Taoyuan Plant 3 No.18, Xinglong Rd., Taoyuan City, Taoyuan County 33068, TAIWAN, R.O.C. TEL: 886-3-362-6301 FAX: 886-3-362-7267 JAPAN DELTA ELECTRONICS (JAPAN), INC. Tokyo Office DELTA SHIBADAIMON BUILDING 2-1-14 SHIBADAIMON, MINATO-KU, TOKYO, 105-0012, JAPAN TEL: 81-3-5733-1111 FAX: 81-3-5733-1211
NORTH/SOUTH AMERICA DELTA PRODUCTS CORPORATION (USA) Raleigh Office P.O. BOX 12173 5101 DAVIS DRIVE, RESEARCH TRIANGLE PARK, NC 27709, U.S.A. TEL: 1-919-767-3813 FAX: 1-919-767-3969 EUROPE DELTRONICS (THE NETHERLANDS) B.V. Eindhoven Office DE WITBOGT 15, 5652 AG EINDHOVEN, THE NETHERLANDS TEL: 31-40-259-2850 FAX: 31-40-259-2851
xi
Table of Contents
xii
One operating lever (for wire to terminal block insertion) One jumper bar (installed at pins P Instruction Sheets and D of the 3 PIN Terminal Block for P , D, C)
Part II : Optional parts (Refer to Appendix A) (1) One power cable, which is used to connect servo motor to U, V, W terminals of servo drive. This power cable includes a green grounding cable. Please connect the green grounding cable to the ground terminal of the servo drive.
1-1
ASDA-B2
(2)
One encoder cable, which is used to connect the encoder of servo motor to the CN2 terminal of servo drive.
CN1 Connector: 4 PIN Connector (3M type analog product) CN2 Connector: 9 PIN Connector (3M type analog product) CN3 Connector: 6 PIN Connector (IEEE1394 analog product)
Nameplate Explanation
Nameplate Explanation
1-2
ASDA-B2
1-3
ASDA-B2
1-4
ASDA-B2
400W
ASD-B2-0421-B
750W
ASD-B2-0721-B
1000W
ASD-B2-1021-B
1500W 2000W
ASD-B2-1521-B ASD-B2-2023-B
3000W
ASD-B2-3023-B
The servo drives shown in the above table are designed for use in combination with the specific servo motors. Check the specifications of the drives and motors you want to use. Also, please ensure that both the servo drive and motor are correctly matched for size (power rating). If the power of motor and drive is not within the specifications, the drive and motor may overheat and servo alarm would be activated. For the detail specifications of servo drives and motors, please refer to Chapter 11 Specifications. The drives shown in the above table are designed according to the three multiple of rated current of motors shown in the above table. If the drives which are designed according to the six multiple of rated current of motors are needed, please contact our distributors or your local Delta sales representative.
1-5
ASDA-B2
1-6
ASDA-B2
Speed Control
Sz
Torque Control
Tz
The above control modes can be accessed and changed via parameter P1-01. Enter the new control mode via P1-01 then switch the main power to the servo drive OFF then ON. The new control mode will only be valid after the drives main power is switched OFF then ON. Please see safety precautions on page iii (switching drive off/on multiple times).
1-7
ASDA-B2
1-8
Do not bend or strain the connection cables between servo drive and motor. When mounting the servo drive, make sure to tighten all screws to secure the drive in
place.
If the servo motor shaft is coupled directly to a rotating device ensure that the alignment
specifications of the servo motor, coupling, and device are followed. Failure to do so may cause unnecessary loads or premature failure to the servo motor.
If the length of cable connected between servo drive and motor is more than 20m, please
increase the wire gauge of the encoder cable and motor connection cable (connected to U, V, W terminals).
Store in a clean and dry location free from direct sunlight. Store within an ambient temperature range of -20C to +65C (-4F to 149F). Store within a relative humidity range of 0% to 90% and non-condensing. Do not store in a place subjected to corrosive gases and liquids. Store in original packaging and placed on a solid surface.
2-1
ASDA-B2
The ambient temperature of servo drive should be under 45C (113F) for long-term reliability. If the ambient temperature of servo drive is greater than 45C (113F), please install the drive in a well-ventilated location and do not obstruct the airflow for the cooling fan. Caution The servo drive and motor will generate heat. If they are installed in a control panel, please ensure sufficient space around the units for heat dissipation. Pay particular attention to vibration of the units and check if the vibration has impacted the electric devices in the control panel. Please observe the following precautions when selecting a mounting location. Failure to observe the following precautions may void the warranty!
Do not mount the servo drive or motor adjacent to heat-radiating elements or in direct
sunlight.
Do not mount the servo drive or motor in a location subjected to corrosive gases, liquids,
airborne dust or metallic particles.
Do not mount the servo drive or motor in a location where temperatures and humidity will
exceed specification.
Do not mount the servo drive or motor in a location where vibration and shock will exceed
specification.
Do not mount the servo drive or motor in a location where it will be subjected to high
levels of electromagnetic radiation.
2-2
ASDA-B2
Drive Mounting The ASDA-B2 servo drives must be back mounted vertically on a dry and solid surface such as a NEMA enclosure. A minimum spacing of two inches must be maintained above and below the drive for ventilation and heat dissipation. Additional space may be necessary for wiring and cable connections. Also, as the drive conducts heat away via the mounting, the mounting plane or surface should not conduct heat into the drive from external sources Motor Mounting The ECMA servo motors should be mounted firmly to a dry and solid mounting surface to ensure maximum heat transfer for maximum power output and to provide a good ground. For the dimensions and weights specifications of servo drive or motor, please refer to Chapter 11 Specifications". Minimum Clearances Install a fan to increase ventilation to avoid ambient temperatures that exceed the specification. When installing two or more drives adjacent to each other please follow the clearances as shown in the following diagram.
2-3
ASDA-B2
Minimum Clearances
2-4
ASDA-B2
Servo Drive Model Operation Mode ASD-B2-0121-B ASD-B2-0221-B ASD-B2-0421-B ASD-B2-0721-B ASD-B2-1021-B ASD-B2-1521-B ASD-B2-2023-B ASD-B2-3023-B
Recommended Fuse (Class T) General 5A 6A 10A 20A 25A 40A 50A 70A
NOTE
1) When using a GFCI (Ground Fault Circuit Interrupter), select a current sensor with sensitivity of equal to or more than 200mA, and not less than 0.1-second detection time to avoid nuisance tripping.
2-5
ASDA-B2
EN61000-6-4 (2001) EN61800-3 (2004) PDS of category C2 EN55011+A2 (2007) Class A Group 1
General Precaution To ensure the best interference elimination performance when using Deltas EMI filter, please follow the guidelines in this user manual to perform wiring and/or installation. In addition, please also observe the following precautions:
EMI filter and AC servo drive should be installed on the same metal plate. Please install AC servo drive on same footprint with EMI filter or install EMI filter as close
as possible to the AC servo drive.
All wiring should be as short as possible. Metal plate should be grounded. The cover of EMI filter and AC servo drive or grounding should be fixed on the metal plate
and the contact area should be as large as possible.
2-6
ASDA-B2
Choose Suitable Motor Cable and Precautions Improper installation and choice of motor cable will affect the performance of EMI filter. Be sure to observe the following precautions when selecting motor cable.
Use the cable with shielding (double shielding is the best). The shielding on both ends of the motor cable should be grounded with the minimum
length and maximum contact area.
Remove any paint on metal saddle for good ground contact with the plate and shielding
(Please refer to Figure 1 below).
The connection between the metal saddle and the shielding on both ends of the motor
cable should be correct and well installed. Please refer to Figure 2 on next page for correct wiring method.
Figure 1
Figure 2
2-7
ASDA-B2
2-8
ASDA-B2
*1 Regenerative Power Calculation: The amount of regenerative power (average value) that can be processed is rated at 50% of the capacity of the servo drive's built-in regenerative resistor. The regenerative power calculation method of external regenerative resistor is the same. When the regenerative power exceeds the processing capacity of the servo drive, install an external regenerative resistor. Please pay close attention on the following notes when using a regenerative resistor. 1. Make sure that the settings of resistance (parameter P1-52) and capacity (parameter P153) is set correctly. 2. When the users want to install an external regenerative resistor, ensure that its resistance value is the same as the resistance of built-in regenerative resistor. If combining multiple small-capacity regenerative resistors in parallel to increase the regenerative resistor capacity, make sure that the resistance value of the regenerative resistor should comply with the specifications listed in the above table. 3. In general, when the amount of regenerative power (average value) that can be processed is used at or below the rated load ratio, the resistance temperature will
Revision January 2012
2-9
ASDA-B2
increase to 120C or higher (on condition that when the regeneration continuously occurred). For safety reasons, forced air cooling is good way that can be used to reduce the temperature of the regenerative resistors. We also recommend the users to use the regenerative resistors with thermal switches. As for the load characteristics of the regenerative resistors, please check with the manufacturer.
External Regenerative Resistor When using external regenerative resistor, connect it to P and C, and make sure the circuit between P and D is open. We recommend the users should use the external regenerative resistor that the resistance value following the above table (Built-in Regenerative Resistor Specifications). We ignore the dissipative power of IGBT (Insulated Gate Bipolar Transistor) in order to let the users easily calculate the capacity of regenerative resistor. In the following sections, we will describe Regenerative Power Calculation Method and Simple Calculation Method for calculating the regenerative power capacity of external regenerative resistors. Regenerative Power Calculation Method (1) Without Load When there is no external load torque, if the servo motor repeats operation, the returned regenerative power generated when braking will transmitted into the capacitance of DC bus. After the capacitance voltage exceeds some high value, regenerative resistor can dissipate the remained regenerative power. Use the table and procedure described below to calculate the regenerative power. Servo Drive (kW) Rotor Inertia J ( 10-4kg.m2) 0.037 0.177 0.277 0.68 1.13 2.65 4.45 8.17 8.41 11.18 14.59 34.68 54.95 Regenerative power from empty load 3000r/min to stop Eo (joule) 0.18 0.87 1.37 3.36 5.59 13.1 22.0 40.40 41.59 55.28 72.15 171.50 271.73 Max. regenerative power of capacitance Ec(joule) 3 4 8 14 18 21 8 18 18 21 28
Servo Motor
0.75 ECMA-C20807 1.0 ECMA-C21010 2.0 ECMA-C21020 0.4 ECMA-E21305 1.0 ECMA-E21310
2-10
ASDA-B2
Servo Motor
Regenerative power from empty load 3000r/min to stop Eo (joule) 40.40 41.59 55.29
0.4 ECMA-G21303 High 0.75 ECMA-G21306 Inertia 1.0 ECMA-G21309 Eo = J x wr2/182 (joule)
, Wr : r/min
If the load inertia is N motor inertia, the regenerative power will be (N+1) x E0 when servo motor brakes from 3000r/min to 0. Then, the regenerative resistor can dissipate: (N+1) x E0 - Ec (joule). If the time of repeat operation cycle is T sec, then the regenerative power = 2 x ((N+1) x E0 - Ec) / T. The calculating procedure is as follows: Step 1 2 3 4 5 6 7 Procedure Set the capacity of regenerative resistor to the maximum Set the operation cycle T Set motor speed wr Set load/motor inertia ratio N Calculate the max. regenerative power Eo Set the regenerative power Ec that can be absorbed Calculate the required regenerative power capacity Equation and Setting Method Change the value of P1-53 to maximum Input by the users Input by the users or read via P0-02 Drive State Display Input by the users or read via P0-02 Drive State Display Eo = J x wr2/182 Refer to the table above 2 x (N+1) x EoEc/ T
For example: If we use 400W servo drive, the time of repeat operation cycle is T = 0.4 sec, max. motor speed is 3000r/min, the load inertia = 7 motor inertia, then the necessary the power of regenerative resistor = 2 x ( (7+1) 1.68 - 8) / 0.4 = 27.2W. If the calculation result is smaller than regenerative power, we recommend the users to use the built-in 60W regenerative resistor. Usually the built-in regenerative resistor provided by ASDA-B2 series can meet the requirement of general application when the external load inertia is not excessive. The users can see when the capacity of regenerative resistor is too small, the accumulated power will be larger and the temperature will also increase. The fault, ALE05 may occur if the temperature is over high. The following figure shows the actual operation of regenerative resistor.
2-11
ASDA-B2
(2) With Load When there is an external load torque, servo motor is in reverse rotation when external load greater than motor torque. Servo motor is usually in forward rotation and the motor torque output direction is the same as the rotation direction. However, there is still some special condition. If the motor output torque is in the reverse direction of rotation, the servo motor is also in the reverse direction of rotation. The external power is input into the servo drive through servo motor. The figure below is an example. The users can see the motor is in forward rotation at constant speed when a sudden external load torque change and great power is transmitted to regenerative resistor rapidly.
Motor Rotation Speed
Reverse Rotation
Forward Rotation
Reverse Rotation
Forward Rotation
For the safety, we strongly recommend the users should select the proper resistance value according to the load. For example: When external load torque is a +70% rated torque and rotation speed reaches 3000r/min, if using 400W servo drive (rated torque: 1.27Nt-m), then the users need to connect a external regenerative resistor which power is 2 x (0.7 x 1.27) x (3000 x 2 x / 60) = 560W, 40.
2-12
ASDA-B2
Simple Calculation Method The users can select the adequate regenerative resistors according to the allowable frequency required by actual operation and the allowable frequency when the servo motor runs without load. The allowable frequency when the servo motor run without load is the maximum frequency that can be operated during continuous operation when servo motor accelerate from 0r/min to rated speed and decelerate from rated speed down to 0r/min. The allowable frequencies when the servo motor run without load are summarized in the following table. Allowable Frequencies for Servo Motor Running Without Load (times/min) When Using Built-in Regenerative Resistor Motor Capacity 600W ECMA Series 06 ECMAC ECMAE ECMAG 42 750W 07 312 900W 09 31 1.0kW 10 137 42 1.5kW 15 32 2.0kW 20 2.0kW 20 3.0kW 30 11 -
( ) : motor frame size, unit is in millimeters. When the servo motor runs with load, the allowable frequency will change according to the changes of the load inertia and rotation speed. Use the following equation to calculate the allowable frequency.
Allowable fr equency = Allowable frequency when serv o motor run without load m+1 x Rated s peed Operating speed
2
times mi n.
2-13
ASDA-B2
The users can select the adequate regenerative resistors according to the allowable frequency by referring to the table below: Allowable Frequencies for Servo Motor Running Without Load (times/min) When Using External Regenerative Resistor Motor Capacity Delta External Regenerative Resistor BR400W040 (400W 40) BR1K0W020 (1kW 20) Motor Capacity 0.5kW Delta External Regenerative Resistor BR400W040 (400W 40) BR1K0W020 (1kW 20) BR3K0W010 (1kW 10) Motor Capacity 0.3kW Delta External Regenerative Resistor BR400W040 (400W 40) BR1K0W020 (1kW 20) 03 292 729 05 291 729 1kW 1.0 283 708 100W 01 200W 02 400W (F60) 04 8608 ECMAC 400W (F80) 04 3506 8765 ECMAE 1.5kW 15 213 533 0.6kW 06 283 708 2.0kW 20 163 (F130) 408 2.0kW 20 68 (F180) 171 0.9kW 09 213 533 3.0kW 30 331 750W 07 2110 5274 1.0kW 10 925 2312 2.0kW 20 562 1406
ECMAG
( ) : motor frame size, unit is in millimeters. When the regenerative resistor capacity is not enough, the users can connect to multiple the same capacity regenerative resistors in parallel to increase it.
2-14
ASDA-B2
Dimensions Delta Part Number : BR400W040 (400W 40) L1 265 L2 250 H 30 D 5.3 W 60 MAX. WEIGHT(g) 930
Delta Part Number : BR1K0W020 (1kW 20) L1 400 L2 385 H 50 D 5.3 W 100 MAX. WEIGHT(g) 2800
2-15
ASDA-B2
NOTE
1) Regarding the selection of regenerative resistor, please refer to the table of regenerative resistor specifications described in Appendix A.
2-16
This chapter provides information on wiring ASDA-B2 series products, the descriptions of I/O signals and gives typical examples of wiring diagrams.
3-1
ASDA-B2
R, S, T
FG(
Green
Internal resistor External resistor P , D, C, Regenerative resistor terminal or braking unit External braking unit
Ensure the circuit is closed between P and D, and the circuit is open between P and C. Connect regenerative resistor to P and C, and ensure an open circuit between P and D. Connect braking unit to P and , and ensure an open circuit between P and D, and P and C. (N terminal is built in L1c, L2c, , and R, S, T.) P : Connecting to (+) terminal of V_BUS voltage. : Connecting to (-) terminal of V_BUS voltage.
3-2
ASDA-B2
Notes Used to connect external controllers. Please refer to section 3.3 for details. Used to connect encoder of servo motor. Please refer to section 3.4 for details. Terminal Symbol T+ TReserved Reserved Reserved Reserved +5V GND Wire Color Blue Blue/Black Red / Red & White Black / Black & White PIN No. 4 5 3 2 1 9 8 6, 7
CN2
Encoder connector
CN3 CN4
Used to connect PC or keypad. Please refer to section 3.5 for details. Reserved Used to monitor the operation status. The drive provides two channels, MON1 and MON2 to output the analog voltage data. Output voltage is reference to the power ground (GND).
CN5
NOTE
1) U, V ,W , CN1, CN2, CN3 terminals provide short circuit protection.
3-3
ASDA-B2
Wiring Notes Please observe the following wiring notes while performing wiring and touching any electrical connections on the servo drive or servo motor. 1. Ensure to check if the power supply and wiring of the "power" terminals (R, S, T, L1c, L2c, U, V, & W) is correct. 2. Please use shielded twisted-pair cables for wiring to prevent voltage coupling and eliminate electrical noise and interference. 3. As a residual hazardous voltage may remain inside the drive, please do not immediately touch any of the "power" terminals (R, S, T, L1c, L2c, U, V, & W) and/or the cables connected to them after the power has been turned off and the charge LED is lit. (Please refer to the Safety Precautions on page ii). 4. The cables connected to R, S, T and U, V, W terminals should be placed in separate conduits from the encoder or other signal cables. Separate them by at least 30cm (11.8 inches). 5. If the encoder cable is too short, please use a twisted-shield signal wire with grounding conductor. The wire length should be 20m (65.62ft.) or less. For lengths greater than 20m (65.62ft.), the wire gauge should be doubled in order to lessen any signal attenuation. Regarding the specifications of 20m (65.62ft.) encoder cable, please choose wire gauge AWG26, UL2464 metal braided shield twisted-pair cable. 6. As for motor cable selection, please use the 600V PTFE wire and the wire length should be less than 98.4ft. (30m). If the wiring distance is longer than 30m (98.4ft.), please choose the adequate wire size according to the voltage. 7. The shield of shielded twisted-pair cables should be connected to the SHIELD end (terminal marked 8. ) of the servo drive.
For the connectors and cables specifications, please refer to section 3.1.6 for details.
3-4
ASDA-B2
3-5
ASDA-B2
3-6
ASDA-B2
3106A-20-18S
3106A-24-11S
3-7
ASDA-B2
Terminal Identification A B C D
U (Red) 1 1 F D
V (White) 2 2 I E
W (Black) 3 4 B F
BRAKE1 (Blue) 3 G A
BRAKE2 (Brown) 6 H B
NOTE
1) The coil of brake has no polarity. The names of terminal identification are BRAKE1 (Blue) and BRAKE2 (Brown). 2) The power supply for brake is DC24V. Never use it for VDD, the +24V source voltage.
3-8
ASDA-B2
*2
Quick Connector Connector of Encoder Cable (Drive Side) Connector of Encoder Cable (Motor Side)
*1
CN2 Connector
Servo Motor
NOTE The scale of the objects does not match the dimensions as shown in the
drawing above. For different models of AC servo drives and motors, the connection cables may differ. 1) Please refer to the descriptions of Terminal Identification of Encoder Connector on page 3-10. 2) Please refer to section 3.4 for the descriptions of Encoder Connector CN2.
The boxes () in the model names are for optional configurations (keyway, brake and oil seal). (Please refer to section 1.2 for model explanation.) Motor Model Name ECMA-C20401S (100W) ECMA-C20602S (200W) ECMA-C20604S (400W) ECMA-CM0604PS (400W) ECMA-C208047 (400W) ECMA-C20807S (750W) ECMA-C20907S (750W) Encoder Connector
9 6 3 8 5 2 7 4 1
3 6 9 2 5 8 1 4 7
3-9
ASDA-B2
Servo Drive (CN2) View from this side View from this side
Motor Encoder
1 Blue T+ 4
Blue/Black
2 Green 5
2 Black
T7
9
Shield
9
Shield
DC+5V
GND
8 Blue GND
The core color of the drive encoder connector is for reference only. For the actual core color, please refer to the actual purchased product.
1 2 Motor Encoder 3 4 2 3 4
If the users do not use the connector (without housing) and connect the cores from the cable for wiring, please follow the terminal identification and core number of encoder connector shown in the above table to complete the wiring. The users need to connect core #1 to core #1, core #2 to core #2 and so on. To ease connection and to avoid wiring error, it is recommended to number the cores first in accordance with the terminal identification and then conducting the wiring.
3-10
ASDA-B2
1 CN2 Connector
Military Connector
Servo Motor
NOTE The scale of the objects does not match the dimensions as shown in the
drawing above. For different models of AC servo drives and motors, the connection cables may differ. 1) Please refer to section 3.4 for the descriptions of Encoder Connector CN2.
3-11
ASDA-B2
The boxes () in the model names are for optional configurations (keyway, brake and oil seal). (Please refer to section 1.2 for model explanation.) Motor Model Name ECMA-G21303S (300W) ECMA-E21305S (500W) ECMA-G21306S (600W) ECMA-GM1306PS (600W) ECMA-G21309S (900W) ECMA-GM1309PS (900W) ECMA-C20910S (1000W) ECMA-C21010S (1000W) ECMA-E21310S (1000W) ECMA-E21315S (1500W) ECMA-C21020S (2000W) ECMA-E21320S (2000W) ECMA-E21820S (2000W) ECMA-E21830S (3000W) ECMA-F21830S (3000W) Encoder Connector
Pin No. A B
Terminal Identification
B A M L N P T D K R S E J F G H C
S R L
Please note: 1. The shield of shielded twisted-pair cables should be connected to the SHIELD end (terminal marked ) of the servo drive.
2. For the connectors and cables specifications, please refer to section 3.1.6 for details.
3-12
ASDA-B2
3-13
ASDA-B2
Encoder Cable Encoder Cable - Wire Gauge AWG (mm2) Servo Drive ASD-B2-0121- ASD-B2-0221- ASD-B2-0421- ASD-B2-0721- ASD-B2-1021- ASD-B2-1521- ASD-B2-2023- ASD-B2-3023- Wire Size 0.13 (AWG26) 0.13 (AWG26) 0.13 (AWG26) 0.13 (AWG26) 0.13 (AWG26) 0.13 (AWG26) 0.13 (AWG26) 0.13 (AWG26) Core Number 10 core (4 pair) 10 core (4 pair) 10 core (4 pair) 10 core (4 pair) 10 core (4 pair) 10 core (4 pair) 10 core (4 pair) 10 core (4 pair) UL Rating UL2464 UL2464 UL2464 UL2464 UL2464 UL2464 UL2464 UL2464 Standard Wire Length 3m (9.84ft.) 3m (9.84ft.) 3m (9.84ft.) 3m (9.84ft.) 3m (9.84ft.) 3m (9.84ft.) 3m (9.84ft.) 3m (9.84ft.)
NOTE
1) 2) 3) 4) Please use shielded twisted-pair cables for wiring to prevent voltage coupling and eliminate electrical noise and interference. The shield of shielded twisted-pair cables should be connected to the SHIELD end (terminal marked ) of the servo drive. In order to prevent fire hazard and accidents, please form the wiring by following the cable specifications outlined above. The boxes () at the ends of the servo drive model names represent the model type of ASDA-B2 series. For the actual model name, please refer to the ordering information of the actual purchased product. 5) The boxes () in the servo motor model names are for optional configurations (keyway, brake and oil sea).
3-14
ASDA-B2
D C
PRB 60W
Servo Drive
IPM Module
R
s s o nL oe i t s ca e t h eP D A/D N C 1 CN4
S T
U V
n o i t a r e n e g t e i u c R r i C t i u c r i C r e i f i t c e R 15V +5V +3.3V +24V Protection Circuit Position Control Speed Control GATE DRIVE
r e w o P l o r t n o C
Servo Motor M
L1C L2C
Encoder
External Speed External Torque Position Pulse Digital Input Encoder Signal A, B, Z Output Digital Output
Current Control
PWM
A/D
Encoder Signal Processing
CN2
CPLD
CHARGE
Display
SHIFT SET
MODE
D/A
CN5
3-15
ASDA-B2
Figure 3.5 Basic Wiring Schematic of 750W model (with built-in regenerative resistor, but without cooling fan)
3-16
ASDA-B2
Figure 3.6 Basic Wiring Schematic of 1kW~1.5kW models (with built-in regenerative resistor and cooling fan)
3-17
ASDA-B2
Figure 3.7 Basic Wiring Schematic of 2kW~3kW models (with built-in regenerative resistor and cooling fan)
3-18
ASDA-B2
iii 5 programmable Digital Outputs (DO), can be set via parameters P2-18 ~ P2-22 A detailed explanation of each group is available in Section 3.3.2, Tables 3.A, 3.B & 3.C.
Side View
Rear View
3-19
ASDA-B2
16 1 DO4+ Digital output 17 2 DO3Digital output 18 3 4 5 DO3+ DO2DO2+ Digital output 19 Digital output 20 Digital output 21 6 DO1Digital output 22 7 DO1+ Digital output 23 8 DI4Digital input 24 9 10 11 DI1DI2COM+ Digital input 25 Digital input Power input (12~24V) Digital input 28 13 OZ Encoder Z pulse Line-driver output VDD(24V) power ground Digital output 26 27
DO6+
Digital output +24V power output (for external I/O) Analog torque Input Analog input signal ground Analog speed input (+) Encoder A pulse output Encoder /A pulse output Encoder /B pulse output 38 Encoder /Z pulse output 39 Encoder B pulse output 40 /HSIGN /PULSE Digital output 41 Digital output 42 HSIGN 31 DI7Digital input
VDD
32
DI6-
Digital input
33 34 35
DI5DI3PULL HI
36
/OA
37 /OB
/OZ
High-speed HPULSE position pulse (+) SIGN Position sign (+) High-speed position sign (-) Pulse input (-) High-speed position sign (+)
OB DO4DO5-
12
DI9-
DO5+
29
GND
14
COM-
44 30 DI8Digital input
OCZ
15
DO6-
3-20
ASDA-B2
V_REF
20
C1
T_REF
18
C1
43 41 39 37 35
C3/C4
High- HPULSE speed /HPULSE Position Pulse HSIGN Input /HSIGN OA /OA Position Pulse Output OB /OB OZ /OZ OCZ VDD
38 36 42 40 21 22 25 23 13 24 44 17
C4-2
Encoder signal output A, B, Z (Line-driver output). The motor encoder signals are available through these terminals.
C13/C14
Encoder signal output Z (Open-collector output). VDD is the +24V source voltage provided by the drive. Maximum permissible current 500mA. COM+ is the common voltage rail of the Digital Input and Digital Output signals. Connect VDD to COM+ for source mode. For external applied power sink mode (+12V to +24V), the positive terminal should be connected to COM+ and the negative to COM-.
C15
3-21
ASDA-B2
Pin No 19
Signals Explanation of Connector CN5 Signal Pin No Details Monitor operation status: Motor characteristics such as speed and current can be represented by analog voltages. The drive provides two channels (MON1 and MON2) which can be configured with the parameter P0-03 to output the desired characteristics. Please refer to the parameter P0-03 for monitoring commands and P1-04 / P1-05 for scaling factors. Output voltage is reference to the power ground (GND). Wiring Diagram (Refer to 3.3.3)
1 2 3
C2
The Digital Input (DI) and Digital Output (DO) have factory default settings which correspond to the various servo drive control modes. (See section 1.5). However, both the DI's and DO's can be programmed independently to meet the requirements of the users. Detailed in Tables 3.B and 3.C are the DO and DI functions with their corresponding signal name and wiring schematic. The factory default settings of the DI and DO signals are detailed in Table 3.F and 3.G. All of the DI's and DO's and their corresponding pin numbers are factory set and nonchangeable, however, all of the assigned signals and control modes are user changeable. For Example, the factory default setting of DO5 (pins 28/27) can be assigned to DO1 (pins 7/6) and vise versa. The following Tables 3.B and 3.C detail the functions, applicable operational modes, signal name and relevant wiring schematic of the default DI and DO signals.
3-22
ASDA-B2
Table 3.B DO Signals Pin No. DO Assigned (Default) Signal Control Mode + SRDY ALL 7 Wiring Diagram (Refer to 3.3.3)
Details
SRDY is activated when the servo drive is ready to run. All fault and alarm 6 conditions, if present, have been cleared. Servo ready (SRDY) is "ON" where the servo is ready to run, NO fault / alarm exists.
SON
Not assigned
ZSPD
ALL
ZSPD is activated when the drive senses the motor is equal to or below 4 the Zero Speed Range setting as defined in parameter P1-38. TSPD is activated once the drive has detected the motor has reached the Target Rotation Speed setting as defined in parameter P1-39. 1. When the drive is in PT mode, TPOS will be activated when the position 26 error is equal and below the setting value of P1-54. TQL is activated when the drive has - detected that the motor has reached the torques limits. ALRM is activated when the drive has detected a fault condition. (However, when Reverse limit error, Forward limit 27 error, Emergency stop, Serial communication error, and Undervoltage these fault occur, WARN is activated first.) BRKR is the control terminal of motor brake. OLW is activated when the servo drive has detected that the motor has reached the output overload level . Servo warning output. WARN is activated when the drive has detected Reverse limit error, Forward limit error, Emergency stop, Serial communication error, and Undervoltage these fault conditions. SP_CMP will be activated when the speed error is equal and below the setting value of P1-47. Output the status of bit00 of P4-06. Output the status of bit01 of P4-06. Output the status of bit02 of P4-06.
3-23
TSPD
TPOS
TQL
Not assigned
C5/C6/C7/C8
ALRM
ALL
28
BRKR OLW
ALL ALL
WARN
ALL
ASDA-B2
Pin No. DO Assigned (Default) Signal Control Mode + SDO_3 SDO_4 SDO_5 SDO_6 SDO_7 SDO_8 SDO_9 SDO_A SDO_B SDO_C SDO_D SDO_E SDO_F ALL ALL ALL ALL ALL ALL ALL ALL ALL ALL ALL ALL ALL -
Details Output the status of bit03 of P4-06. Output the status of bit04 of P4-06. Output the status of bit05 of P4-06. Output the status of bit06 of P4-06. Output the status of bit07 of P4-06. Output the status of bit08 of P4-06. Output the status of bit09 of P4-06. Output the status of bit10 of P4-06. Output the status of bit11 of P4-06. Output the status of bit12 of P4-06. Output the status of bit13 of P4-06. Output the status of bit14 of P4-06. Output the status of bit15 of P4-06.
C5/C6/C7/C8
NOTE
1) PINS 3 & 2 can TSPD when control mode S is selected. 2) The DO signals that do not have pin numbers in Tables 3.B are not default DO signals. If the users want to use these non-default DO signals, the users need to change the settings of parameters P2-18 ~ P2-22. The state of the output function may be turned ON or OFF as it will be dependant on the settings of parameters P2-18 ~ P2-22. Please refer to section 3.3.3 for details.
Table 3.C DI Signals DI Signal SON ARST GAINUP CCLR Assigned Pin No. Control Mode (Default) ALL ALL ALL PT 9 33 10 Details Servo On. Switch servo to "Servo Ready". A number of Faults (Alarms) can be cleared by activating ARST. Gain switching When CCLR is activated the setting is parameter P2-50 Pulse Clear Mode is executed. When this signal is On and the motor speed value is lower than the setting value of P1-38, it is used to lock the motor in the instant position while ZCLAMP is On. C9/C10 C11/C12 Wiring Diagram (Refer to 3.3.3)
ZCLAMP
ALL
3-24
ASDA-B2
DI Signal CMDINV TRQLM SPDLM STOP SPD0 SPD1 TCM0 TCM1 S-P S-T T-P EMGS NL(CWL)
Assigned Pin No. Control Mode (Default) T, S S, Sz T, Tz S, Sz, PT-S, S-T PT, T, Tz, PT-T S-T PT-S S-T PT-T ALL PT, S, T Sz, Tz PT, S, T Sz, Tz Not assigned Not assigned ALL 10 10 34 8 34 8 31 31 31 30 32
Details When this signal is On, the motor is in reverse rotation. ON indicates the torque limit command is valid. ON indicates the speed limit command is valid. Motor stop. Select the source of speed command: See table 3.D. Select the source of torque command: See table 3.E. Speed / Position mode switching OFF: Speed, ON: Position Speed / Torque mode switching OFF: Speed, ON: Torque Torque / Position mode switching OFF: Torque, ON: Position It should be contact b and normally ON or a fault (ALRM) will display. Reverse inhibit limit. It should be contact b and normally ON or a fault (ALRM) will display. Forward inhibit limit. It should be contact b and normally ON or a fault (ALRM) will display. Reverse operation torque limit (Torque limit function is valid only when P1-02 is enabled) Forward operation torque limit (Torque limit function is valid only when P1-02 is enabled) Forward JOG input. When JOGU is activated, the motor will JOG in forward direction. Reverse JOG input. When JOGD is activated, the motor will JOG in reverse direction. Electronic gear ratio (Numerator) selection 0 [See P2-60~P2-62] Electronic gear ratio (Numerator) selection 1 [See P2-60~P2-62]
C9/C10 C11/C12
PL(CCWL)
31
TLLM
TRLM
JOGU
3-25
ASDA-B2
DI Signal
Details Pulses inhibit input. When the drive is in position mode, if INHP is activated, the external pulse input command is not valid.
INHP
NOTE
1) The DI signals that do not have pin numbers in Tables 3.C are not default DI signals. If the users want to use these non-default DI signals, the users need to change the settings of parameters P2-10 ~ P2-17. The state of the output function may be turned ON or OFF as it will be dependant on the settings of parameters P2-10 ~ P2-17. Please refer to section 3.3.3 for details.
Table 3.D Source of Speed Command SPD1 OFF OFF ON ON SPD0 OFF ON OFF ON Parameter S mode: analog input Sz mode: 0 P1-09 P1-10 P1-11
Table 3.E Source of Torque Command TCM1 OFF OFF ON ON TCM0 OFF ON OFF ON Parameter T mode: analog input Tz mode: 0 P1-12 P1-13 P1-14
The default DI and DO signals in different control mode are listed in the following table 3.F and table 3.G. Although the content of the table 3.F and table 3.G do not provide more information than the table 3.B and table 3.C above, as each control mode is separated and listed in different row, it is easy for user to view and can avoid confusion. However, the Pin number of each signal can not be displayed in the table 3.F and table 3.G.
3-26
ASDA-B2
Table 3.F Default DI signals and Control modes Signal SON ARST GAINUP CCLR ZCLAMP CMDINV Reserved Reserved TRQLM SPDLM STOP SPD0 SPD1 TCM0 TCM1 S-P DI Code 01 02 03 04 05 06 07 08 09 10 46 14 15 16 17 18 Function Servo On Reset Gain switching in speed and position mode Pulse clear Low speed CLAMP Command input reverse control Reserved Reserved Torque limit enabled Speed limit enabled Motor stop Speed command selection 0 Speed command selection 1 Torque command selection 0 Torque command selection 1 Position / Speed mode switching (OFF: Speed, ON: Position) Speed / Torque mode switching (OFF: Speed, ON: Torque) Torque / Position mode switching (OFF: Torque, ON: Position) Reserved Reserved Emergency stop Reverse inhibit limit Forward inhibit limit Reserved Reverse operation torque limit DI8 DI6 DI7 DI8 DI6 DI7 DI8 DI6 DI7 DI8 DI6 DI7 DI8 DI6 DI7 DI8 DI8 DI8 DI7 DI3 DI4 DI3 DI4 DI3 DI4 DI3 DI4 DI3 DI4 DI7 DI3 DI4 DI3 DI4 DI3 DI4 DI5 DI6 DI2 DI2 DI2 DI2 DI2 DI2 DI2 PT DI1 DI5 S DI1 DI5 T DI1 DI5 Sz DI1 DI5 Tz DI1 DI5 PT-S PT-T DI1 DI1 S-T DI1
S-T
19
DI7
20 2C 2D 21 22 23 24 25
3-27
ASDA-B2
DI Code 26 27 36 37 38 43
Function Forward operation torque limit Reserved Reserved Forward JOG input Reverse JOG input Electronic gear ratio (Numerator) selection 0 Electronic gear ratio (Numerator) selection 1 Pulse inhibit input
PT
Sz
Tz
PT-S PT-T
S-T
GNUM1 INHP
44 45
NOTE
1) For Pin numbers of DI1~DI8 signals, please refer to section 3.3.1.
Table 3.G Default DO signals and Control modes Signal SRDY SON ZSPD TSPD TPOS TQL ALRM BRKR OLW WARN SNL(SCWL) SPL(SCCWL) DO Code Function PT S T Sz Tz PT-S PT-T S-T
01 Servo ready 02 Servo On 03 Zero speed 04 Speed reached 05 06 07 08 10 11 13 14 Positioning completed Reached torques limits Servo alarm output (Servo fault) Electromagnetic brake Output overload warning Servo warning output Reverse software limit Forward software limit
DO2 DO2 DO2 DO2 DO2 DO2 DO2 DO2 DO3 DO3 DO3 DO3 DO3 DO3 DO3 DO4 DO4 DO4
DO5 DO5 DO5 DO5 DO5 DO5 DO5 DO5 DO4 DO4 DO4 DO4
3-28
ASDA-B2
Signal SP_OK SDO_0 SDO_1 SDO_2 SDO_3 SDO_4 SDO_5 SDO_6 SDO_7 SDO_8 SDO_9 SDO_A SDO_B SDO_C SDO_D SDO_E SDO_F
DO Code 19 30 31 32 33 34 35 36 37 38 39 3A 3B 3C 3D 3E 3F
Function Speed reached output Output the status of bit00 of P4-06. Output the status of bit01 of P4-06. Output the status of bit02 of P4-06. Output the status of bit03 of P4-06. Output the status of bit04 of P4-06. Output the status of bit05 of P4-06. Output the status of bit06 of P4-06. Output the status of bit07 of P4-06. Output the status of bit08 of P4-06. Output the status of bit09 of P4-06. Output the status of bit10 of P4-06. Output the status of bit11 of P4-06. Output the status of bit12 of P4-06. Output the status of bit13 of P4-06. Output the status of bit14 of P4-06. Output the status of bit15 of P4-06.
PT
Sz
Tz
PT-S PT-T
S-T
NOTE
1) For Pin numbers of DO1~DO6 signals, please refer to section 3.3.1.
3-29
ASDA-B2
There are two kinds of pulse inputs, Line driver input and Open-collector input. Max. input pulse frequency of Line driver input is 500kpps and max. input pulse frequency of Open-collector input is 200kpps. C3-1: Pulse input, for the use of internal power supply (Open-collector input)
3-30
ASDA-B2
C3-2: Pulse input, for the use of external power supply (Open-collector input)
Caution: Do not use dual power supply. Failure to observe this caution may result in damage to the servo drive and servo motor.
C4-1: Pulse input (Line driver) It requires 5V power supply only. Never apply a 24V power supply.
3-31
ASDA-B2
C4-2: High-speed pulse input (Line driver). It requires 5V power supply only. Never apply a 24V power supply.
Caution: The high-speed pulse input interface is not an isolated input interface. To prevent noise and interference, ensure that the ground terminal of the controller and the servo drive should be connected to each other.
Be sure to connect a diode when the drive is applied to inductive load. (Permissible current: 40mA, Instantaneous peak current: max. 100mA) C5: Wiring of DO signal, for the use of C6: Wiring of DO signal, for the use of internal power supply, general load internal power supply, inductive load
3-32
ASDA-B2
C7: Wiring of DO signal, for the use of external power supply, general load
C8: Wiring of DO signal, for the use of external power supply, inductive load
Use a relay or open-collector transistor to input signal. NPN transistor with multiple emitter fingers (SINK Mode) C9: Wiring of DI signal, for the use of C10: Wiring of DI signal, for the use of internal power supply external power supply
PNP transistor with multiple emitter fingers (SOURCE Mode) C11: Wiring of DI signal, for the use of C12: Wiring of DI signal, for the use of internal power supply external power supply
Caution: Do not use dual power supply. Failure to observe this caution may result in damage to the servo drive and servo motor.
3-33
ASDA-B2
Controller
Controller
200
OA 21
OA 21
/OA 22 125 OB 25
/OA 22 OB 25 200
High speed photocoupler
/OB 23 125 OZ 13
/OB 23 OZ 13 200
High speed photocoupler
/OZ 24 125 SG
/OZ 24
High speed photocoupler
SG
Servo Drive
Max. Spec: 30V 100mA
OCZ 44 GND 29
3-34
ASDA-B2
3-35
ASDA-B2
Side View
Rear View
rom w f ide e i V is s th
9 6 3 8 5 2 7 4 1
B A M L C N P T D K R S E J F G H
Quick Connector
3106A-20-29S
Military Connector
3-36
ASDA-B2
CN2 Terminal Signal Identification Drive Connector PIN No. 4 5 8 7, 6 Shell Terminal Identification T+ T+5V GND Shielding Description Serial communication signal input / output (+) Serial communication signal input / output (-) Reserved Reserved +5V power supply Ground Shielding Motor Connector Military Connector A B S R L Quick Connector 1 4 7 8 9 Color Blue Blue & Black Red / Red & White Black / Black & White -
3-37
ASDA-B2
Using the encoder cable with shielding (double shielding is the best) is able to prevent voltage coupling and eliminate the noise and interference from other electrical sources. Be sure to observe the following steps to complete the shielding surrounding the encoder cable.
(1) Solder the centre cores on the metal part of the connector adequately for good ground contact with the plate and shielding.
(2) Trim the ends of the cores and install the cores with shielding into the plastic case of the connector as shown in the figure.
3-38
ASDA-B2
3.5 Serial Communication Connector CN3 CN3 Terminal Layout and Identification
The servo drive can be connected to a PC or controller via a serial communication connector. Users can operate the servo drive through PC software supplied by Delta (contact to the dealer). The communication connector/port of Delta servo drive can provide three common serial communication interfaces: RS-232 and RS-485 connection. RS-232 is mostly be used but is somewhat limited. The maximum cable length for an RS232 connection is 15 meters (50 feet). Using RS-485 interface can allow longer distance for transmission and support multiple drives to be connected simultaneously.
*1
*1
Reserved
*2
Please read carefully the following note. Improper wiring may cause damage or injury! CN3 Terminal Signal Identification
PIN No. 1 2 3 4 5 6
Signal Name Grounding RS-232 data transmission RS-232 data receiving RS-485 data transmission RS-485 data transmission
Description
For data transmission of the servo drive. Connected to the RS-232 interface of PC. Reserved For data receiving of the servo drive. Connected to the RS-232 interface of PC. For data transmission of the servo drive (differential line driver + end) For data transmission of the servo drive (differential line driver - end)
NOTE
1) 2) For the connection of RS-485, please refer to section 8.1 in Chapter 8. There are two kinds of IEEE1394 communication cables available on the market. If the user uses one kind of cable, which its GND terminal (Pin 1) and its shielding is short-circuited, the communication may be damaged. Never connect the case of the terminal to the ground of this kind of communication cable. 3-39
ASDA-B2
CN5
1 2 3
205
PIN No. 1 2 3 Signal Name MON1 GND MON2 Description Monitor analog data 1 Ground Monitor analog data 2 Color Red White Black C2 Wiring Diagram (Refer to 3.3.3)
3-40
ASDA-B2
Please note: *1 Please refer to C3 ~ C4 wiring diagrams in section 3.3.3 (on page 3-30 ~ 3-32). *2 Please refer to C3 ~ C4 wiring diagrams in section 3.3.3 (on page 3-30 ~ 3-32). *3 Please refer to C9 ~ C12 wiring diagrams (SINK / SOURCE mode) in section 3.3.3 (on page 3-33). *4 The servo drive provides built-in regenerative resistor. *5 The brake coil has no polarity.
3-41
ASDA-B2
Please note: *1 Please refer to C9 ~ C12 wiring diagrams (SINK / SOURCE mode) in section 3.3.3 (on page 3-33). *2 The servo drive provides built-in regenerative resistor. *3 The brake coil has no polarity.
3-42
ASDA-B2
Please note: *1 Please refer to C9 ~ C12 wiring diagrams (SINK / SOURCE mode) in section 3.3.3 (on page 3-33). *2 The servo drive provides built-in regenerative resistor. *3 The brake coil has no polarity.
3-43
ASDA-B2
3-44
This chapter describes the basic operation of the digital keypad and the features it offers.
Figure 4.1
Function The LCD Display (5-digit, 7-step display panel) shows the monitor codes, parameter settings and operation values of the AC servo drive. The Charge LED lights to indicate the power is applied to the circuit. MODE Key. Pressing MODE key can enter or exit different parameter groups, and switch between Monitor mode and Parameter mode. SHIFT Key. Pressing SHIFT key can scrolls through parameter groups. After a parameter is selected and its value displayed, pressing SHIFT key can move the cursor to the left and then change parameter settings (blinking digits) by using arrow keys. UP and DOWN arrow Key. Pressing the UP and DOWN arrow key can scroll through and change monitor codes, parameter groups and various parameter settings. SET Key. Pressing the SET key can display and save the parameter groups, the various parameter settings. In monitor mode, pressing SET key can switch decimal or hexadecimal display. In parameter mode, pressing SET key can enter into parameter setting mode. During diagnosis operation, pressing SET key can execute the function in the last step. (The parameter settings changes are not effective until the SET key is pressed.)
SHIFT Key
SET Key
4-1
ASDA-B2
1.
When the power is applied to the AC servo drive, the LCD display will show the monitor function codes for approximately one second, then enter into the monitor mode.
2.
In monitor mode, pressing MODE key can enter into parameter mode. In parameter mode, pressing MODE key can return to monitor mode.
3.
No matter working in which mode, when an alarm occurs, the system will enter into fault mode immediately. In fault mode, pressing MODE key can switch to other modes. In other modes, if no key is pressed for over 20 seconds, the system will return to fault mode automatically.
4.
In monitor mode, pressing UP or DOWN arrow key can switch monitor parameter code. At this time, monitor display symbol will display for approximately one second.
5.
In monitor mode, pressing MODE key can enter into parameter mode, pressing the SHIFT key can switch parameter group and pressing UP or DOWN arrow key can change parameter group code.
6.
In parameter mode, the system will enter into the setting mode immediately after the Set key is pressed. The LCD display will display the corresponding setting value of this parameter simultaneously. Then, users can use UP or DOWN arrow key to change parameter value or press MODE key to exit and return back to the parameter mode.
7.
In parameter setting mode, the users can move the cursor to left by pressing the SHIFT key and change the parameter settings (blinking digits) by pressing the UP or DOWN arrow key.
8.
After the setting value change is completed, press SET key to save parameter settings or execute command.
9.
When the parameter setting is completed, LCD display will show the end code SAVED and automatically return back to parameter mode.
4-2
ASDA-B2
4-3
ASDA-B2
Display Message
Description Negative value display. Continuously press SHIFT key for two seconds and then the positive(+) or negative(-) sign can be switched. When the setting value exceeds its setting range, the positive(+) and negative(-) sign can not be switched. (The negative value display is for a decimal negative value only. There is no negative value display for a hexadecimal negative value.)
2 3 4
5 6 7 8 9
4-4
ASDA-B2
P0-02 Setting 10 11 12 13 14
Display Message
Description Torque input command Torque input command Average load Peak load Main circuit voltage Ratio of load inertia to Motor inertia (Please note that if the display is 130, it indicates that the actual inertia is 13.0) IGBT temperature Resonance frequency (The low byte is the first resonance point and the high byte is the second resonance point.) Absolute pulse number relative to encoder (use Z phase as home). The value of Z phase home point is 0, and it can be the value from -5000 to +5000 pulses.
15
[0.1times]
16
[oC]
17
[Hz]
18
The following table lists the display examples of monitor value: Display Message (Dec.) (Hex.) (Dec. High Byte) (Dec. Low Byte) (Hex. High Byte) (Hex. Low Byte) 32-bit Data 16-bit Data Description Decimal display. When the actual value is 1234, the display is 01234. Hexadecimal display. When the actual value is 0x1234, the display is 1234. Decimal display. When the actual value is 1234567890, the display of high byte is 1234.5 and the display of low byte is 67890. Hexadecimal display. When the actual value is 0x12345678, the display of high byte is h1234 and the display of low byte is L5678.
Negative value display. When the actual value is 12345, the display is 1.2.345. (The negative value display is displayed to indicate a decimal negative value. There is no negative value display for a hexadecimal negative value.)
4-5
ASDA-B2
NOTE
1) Dec. represents Decimal display and Hex. represents Hexadecimal display. 2) The above display methods are both available in monitor mode and parameter setting mode. 3) All monitor variables are 32-bit data. The users can switch to high byte or low byte and display format (Dec. or Hex.) freely. Regarding the parameters listed in Chapter 8, for each parameter, only one kind of display format is available and cannot be changed.
4-6
ASDA-B2
4-7
ASDA-B2
NOTE
1) JOG operation is effective only when Servo On (when the servo drive is enabled).
Figure 4.4
4-8
ASDA-B2
NOTE
1) As the display of P4-06 is hexadecimal, 0(zero) of the fifth digit will not show on the LED display.
4-9
ASDA-B2
(Hexadecimal Display)
4-10
ASDA-B2
(Hexadecimal Display)
4-11
ASDA-B2
4-12
This chapter, which is divided into two parts, describes trial run for servo drive and motor. One part is to introduce the trial run without load, and the other part is to introduce trial run with load. Ensure to complete the trial run without load first before performing the trial run with load.
After power in connected to AC servo drive, the charge LED will light and it indicates that AC servo drive is ready. Please check the followings before trial run: Inspection before operation (Control power is not applied)
Inspect the servo drive and servo motor to insure they were not damaged. To avoid an electric shock, be sure to connect the ground terminal of servo drive to the ground terminal of control panel.
Before making any connection, wait 10 minutes for capacitors to discharge after the power is disconnected, alternatively, use an appropriate discharge device to discharge.
Ensure that all wiring terminals are correctly insulated. Ensure that all wiring is correct or damage and or malfunction may result. Visually check to ensure that there are not any unused screws, metal strips, or any conductive or inflammable materials inside the drive.
5-1
ASDA-B2
Never put inflammable objects on servo drive or close to the external regenerative resistor.
Make sure control switch is OFF. If the electromagnetic brake is being used, ensure that it is correctly wired. If required, use an appropriate electrical filter to eliminate noise to the servo drive. Ensure that the external applied voltage to the drive is correct and matched to the controller.
Ensure that the cables are not damaged, stressed excessively or loaded heavily. When the motor is running, pay close attention on the connection of the cables and notice that if they are damaged, frayed or over extended.
Check for abnormal vibrations and sounds during operation. If the servo motor is vibrating or there are unusual noises while the motor is running, please contact the dealer or manufacturer for assistance.
Ensure that all user-defined parameters are set correctly. Since the characteristics of various machinery equipment are different, in order to avoid accident or cause damage, do not adjust the parameter abnormally and ensure the parameter setting is not an excessive value.
Ensure to reset some parameters when the servo drive is off (Please refer to Chapter 7). Otherwise, it may result in malfunction.
If there is no contact sound or there be any unusual noises when the relay of the servo drive is operating, please contact your distributor for assistance or contact with Delta.
Check for abnormal conditions of the power indicators and LED display. If there is any abnormal condition of the power indicators and LED display, please contact your distributor for assistance or contact with Delta.
5-2
ASDA-B2
2. Main circuit wiring Connect power to the AC servo. For three-phase input power connection and single-phase input power connection, please refer to Section 3.1.3. 3. Turn the Power On The Power includes control circuit power (L1c, L2c) and main circuit power (R, S, T). When the power is on, the normal display should be shown as the following figure:
As the default settings of digital input signal, DI6, DI7 and DI8 are Reverse Inhibit Limit (NL), Forward Inhibit Limit (PL) and Emergency Stop (EMGS) respectively, if the users do not want to use the default settings of DI6~DI8, the users can change their settings by using parameters P2-15 to P2-17 freely. When the setting value of parameters P2-15 to P2-17 is 0, it indicates the function of this DI signal is disabled. For more information of parameters P2-15 to P2-17, please refer to Chapter 7 Parameters. If the parameter P0-02 is set as motor speed (06), the normal display should be shown as the following figure:
If there is no text or character displayed on the LED display, please check if the voltage of the control circuit terminal (L1c and L2c) is over low.
5-3
ASDA-B2
Over voltage: The main circuit voltage has exceeded its maximum allowable value or input power is error (Incorrect power input). Corrective Actions: Use voltmeter to check whether the input voltage falls within the rated input voltage. Use voltmeter to check whether the input voltage is within the specified limit.
Encoder error: Check if the wiring is correct. Check if the encoder wiring (CN2) of servo motor is loose or incorrect. Corrective Actions: Check if the users perform wiring recommended in the user manual. Examine the encoder connector and cable. Inspect whether wire is loose or not. Check if the encoder is damaged.
Emergency stop activated: Please check if any of digital inputs DI1~DI9 signal is set to Emergency Stop (EMGS). Corrective Actions: If it does not need to use Emergency Stop (EMGS) as input signal, the users only need to confirm that if all of the digital inputs DI1~DI8 are not set to Emergency
5-4
ASDA-B2
Stop (EMGS). (The setting value of parameter P2-10 to P2-17 and P2-36 is not set to 21.) If it is necessary to use Emergency Stop (EMGS) as input signal, the users only need to confirm that which of digital inputs DI1~DI9 is set to Emergency Stop (EMGS) and check if the digital input signal is ON (It should be activated). 4) When display shows:
Reverse limit switch error: Please check if any of digital inputs DI1~DI9 signal is set to Reverse inhibit limit (NL) and check if the signal is ON or not. Corrective Actions: If it does not need to use Reverse inhibit limit (NL) as input signal, the users only need to confirm that if all of the digital inputs DI1~DI9 are not set to Reverse inhibit limit (NL). (The setting value of parameter P2-10 to P2-17 and P2-36 is not set to 22.) If it is necessary to use Reverse inhibit limit (NL) as input signal, the users only need to confirm that which of digital inputs DI1~DI9 is set to Reverse inhibit limit (NL) and check if the digital input signal is ON (It should be activated). 5) When display shows:
Forward limit switch error: Please check if any of digital inputs DI1~DI9 signal is set to Forward inhibit limit (PL) and check if the signal is ON or not. Corrective Actions: If it is no need to use Forward inhibit limit (PL) as input signal, the users only need to confirm that if all of the digital inputs DI1~DI9 are not set to Forward inhibit limit (PL). (The setting value of parameter P2-10 to P2-17 and P2-36 is not set to 23.)
5-5
ASDA-B2
If it is necessary to use Forward inhibit limit (PL) as input signal, the users only need to confirm that which of digital inputs DI1~DI9 is set to Forward inhibit limit (PL) and check if the digital input signal is ON (It should be activated).
When Digital Input 1 (DI1) is set to Servo On (SON), if DI1 is set to ON (it indicates that Servo On (SON) function is enabled) and the following fault message shows on the display: 6) When display shows:
Overcurrent: Corrective Actions: Check the wiring connections between the servo drive and motor. Check if the circuit of the wiring is closed. Remove the short-circuited condition and avoid metal conductor being exposed.
Undervoltage: Corrective Actions: Check whether the wiring of main circuit input voltage is normal. Use voltmeter to check whether input voltage of main circuit is normal. Use voltmeter to check whether the input voltage is within the specified specification.
NOTE
1) If there are any unknown fault codes and abnormal display when applying power to the drive or servo on is activated (without giving any command), please inform the distributor or contact with Delta for assistance.
5-6
ASDA-B2
5-7
ASDA-B2
In the example below, the JOG speed is adjusted from 20r/min (Default setting) to 100r/min.
5-8
ASDA-B2
By default, DI6 is the function of reverse inhibit limit, DI7 is the function of forward inhibit limit and DI6 is the function of emergency stop (DI8), if the users do not set the setting value of parameters P2-15 to P2-17 and P2-36 to 0 (Disabled), the faults (ALE13, 14 and 15) will occur (For the information of fault messages, please refer to Chapter 10). Therefore, if the users do not need to use these three digit inputs, please set the setting value of parameters P2-15 to P2-17 and P2-36 to 0 (Disabled) in advance. All the digital inputs of Delta ASDA-B2 series are user-defined, and the users can set the DI signals freely. Ensure to refer to the definitions of DI signals before defining them (For the description of DI signals, please refer to Table 7.A in Chapter 7). If any alarm code displays after the setting is completed, the users can restart the drive or set DI5 to be activated to clear the fault. Please refer to section 5.2.
5-9
ASDA-B2
The speed command is selected by SPD0, SPD1. Please refer to the following table: DI signal of CN1 Speed Command No. SPD1 SPD0 S1 S2 S3 S4 0 0 1 1 0 1 0 1 Internal parameter Command Source External analog command Content Voltage between V-REF and GND P1-09 P1-10 P1-11 Range -10V ~ +10V -50000 ~ 50000 -50000 ~ 50000 -50000 ~ 50000
0: indicates OFF (Normally Open); 1: indicates ON (Normally Closed) The range of internal parameter is from -50000 to 50000. Setting value of speed command = Setting range x unit (0.1 r/min). For example: If P1-09 is set to +30000, the setting value of speed command = +30000 x 0.1 r/min = +3000 r/min. The settings of speed command: P1-09 is set to 30000 P1-10 is set to 1000 P1-11 is set to -30000 STEP 3: 1. 2. The users can use DI1 to enable the servo drive (Servo ON). If DI3 (SPD0) and DI4 (SPD1) are OFF both, it indicates S1 command is selected. At this time, the motor is operating according to external analog command. 3. If only DI3 is ON (SPD0), it indicates S2 command (P1-09 is set to 3000) is selected, and the motor speed is 3000r/min at this time. 4. If only DI4 is ON (SPD1), it indicates S3 command (P1-10 is set to 100) is selected, and the motor speed is 100r/min at this time. 5. If DI3 (SPD0) and DI4 (SPD1) are ON both, it indicates S4 command (P1-11 is set to 3000) is selected, and the motor speed is -3000r/min at this time. 6. 7. Repeat the action of (3), (4), (5) freely. When the users want to stop the speed trial run, use DI1 to disable the servo drive (Servo OFF). Input value command + Rotation direction CW CCW
5-10
ASDA-B2
7. 8. 9.
10. At this time, the servo drive is ON and the right side display will appear next. 11. Press DOWN key three times to select the ratio of Load Inertia to Servo Motor Inertia (J_load /J_motor). 12. Display the current ratio of Load Inertia to Servo Motor Inertia (J_load /J_motor). (5.0 is default setting.) 13. Press MODE key to select parameter mode. 14. Press SHIFT key twice to select parameter group. 15. Press UP key to select user parameter P4-05. 16. Press SET key and JOG speed 20r/min will be displayed. Press UP and DOWN key to increase and decrease JOG speed. To press SHIFT key one time can add one digit number.
17. Select desired JOG speed, press SET key and it will show the right side display. 18. Pressing UP key is forward rotation and pressing DOWN key is reverse rotation. 19. Execute JOG operation in low speed first. After the machine is running smoothly, then execute JOG operation in high speed.
5-11
ASDA-B2
Tuning Procedure
Display
20. The ratio of Load Inertia to Servo Motor Inertia (J_load /J_motor) cannot be shown in the display of JOG parameter P4-05 operation. Please press MODE key twice continuously and the users can see the ratio of Load Inertia to Servo Motor Inertia (J_load /J_motor). Then, execute JOG operation again, press MODE key once and press SET key twice to view the display on the keypad. Check if the value of J_load /J_motor is adjusted to a fixed value and displayed on the keypad after acceleration and deceleration repeatedly.
5-12
ASDA-B2
5-13
ASDA-B2
5-14
ASDA-B2
5-15
ASDA-B2
NOTE
1) When bit0 of P2-33 is set to 1, it indicates that the system inertia estimation of semi-auto mode has been completed and the measured load inertia value is saved and memorized in P137 automatically. 2) If reset bit0 of P2-33 to 0, it will start estimating the system inertia again.
5-16
ASDA-B2
5-17
ASDA-B2
NOTE
1) Parameters P2-44 and P2-46 are used to set notch filter attenuation rate. If the resonance can not be suppressed when the setting values of P2-44 and P2-46 are set to 32bB (the maximum value), please decrease the speed loop frequency response. After setting P2-47, the users can check the setting values of P2-44 and P2-46. If the setting value of P2-44 is not 0, it indicates that one resonance frequency exists in the system and then the users can read P2-43, i.e. the frequency (unit is Hz) of the resonance point. When there is any resonance point in the system, its information will be shown in P2-45 and P2-46 as P2-43 and P2-44. 2) If the resonance conditions are not improved when P2-47 is set to 1 for over three times, please adjust notch filters (resonance suppression parameters) manually to or eliminate the resonance.
5-18
ASDA-B2
5-19
ASDA-B2
Manual Mode
0(Default setting)
None
Fixed
P1-37 P2-00 P2-02 P2-04 P2-06 P2-25 P2-26 P2-49 P1-37 P2-00 P2-02 P2-04 P2-06 P2-25 P2-26 P2-49
When switching mode #1 to #0, the setting value of P2-00, P2-02, P2-04, P2-06, P2-25, P2-26 and P2-49 will change to the value that measured in #1 auto-tuning mode. When switching mode #2 to #0, the setting value of P2-00, P2-02, P2-04, P2-06, P2-25, P2-26 and P2-49 will change to the value that measured in #2 semi-auto tuning mode.
5-20
ASDA-B2
KVP, Parameter P2-04 Proportional Speed Loop Gain This parameter is used to determine the frequency response of speed loop (speed loop gain). It could be used to expedite speed loop response. When the setting value of KVP is higher, the response to the speed command is quicker. However, if the setting value is over high, it may result in the resonance of machinery system. The frequency response of speed loop must be higher than the 4~6 times of the frequency response of position loop. If frequency response of position loop is higher than the frequency response of speed loop, the machinery system may generate vibration or noise, or even overshoot during positioning. The speed loop frequency response is calculated as follows:
JM: Motor Inertia JL: Load Inertia P1-37: 0.1 times
When the value of P1-37 (no matter it is the measured load inertia value or the set load inertia value) is equal to the actual load inertia value, the actual speed loop frequency response will be:
= K VP Hz 2 .
5-21
ASDA-B2
KVI, Parameter P2-06 Speed Integral Compensation If the setting value of KVI is higher, the capability of decreasing the speed control deviation is better. However, if the setting value is over high, it may easily result in the vibration of machinery system. The recommended setting value is as follows:
NLP, Parameter P2-25 Low-pass Filter Time Constant of Resonance Suppression When the value of (J_load / J_motor) is high, the responsiveness of speed loop may decrease. At this time, the users can increase the setting value of KVP (P2-04) to keep the responsiveness of speed loop. However, when increasing the setting value of KVP (P2-04), it may easily result in the vibration of machinery system. Please use this parameter to suppress or eliminate the noise of resonance. If the setting value of NLP is higher, the capability of improving the noise of resonance is better. However, if the setting value is over high, it may easily lead to the instability of speed loop and overshoot of machinery system. The recommended setting value is as follows:
DST, Parameter P2-26 External Anti-Interference Gain This parameter is used to enhance the anti-interference capability and reduce the occurrence of overshoot. The default setting is 0 (Disabled). It is not recommended to use it in manual mode only when performing a few tuning on the value gotten through P2-32 AutoMode (PDFF) (setting value is 5, mode 5) automatically (The setting value of P2-26 will change to the value that measured in mode 5 (AutoMode (PDFF)) when switching mode 5 ((AutoMode (PDFF)) to mode 0 (Manual mode)).
PFG, Parameter P2-02 Position Feed Forward Gain This parameter is used to reduce position error and shorten the positioning settling time. However, if the setting value is over high, it may easily lead to the overshoot of machinery system. If the value of electronic gear ratio (1-44/1-45) is over than 10, the machinery system may also easily generate vibration or noise.
5-22
Speed Control
Sz
Torque Control
Tz
S-P Dual Mode T-P S-T The steps of changing mode: (1) (2) (3)
Switching the servo drive to Servo Off status. Turning SON signal of Digit input to be off can complete this action. Using parameter P1-01. (Refer to chapter 7). After the setting is completed, cut the power off and restart the drive again.
The following sections describe the operation of each control mode, including control structure, command source and loop gain adjustment, etc.
6-1
ASDA-B2
Operation Keypad/Software Interface: Default: 0x2 Control PT Mode: Unit: Range: 0 ~ 1132 Data Size: 16-bit Display Hexadecimal Format: Settings:
A: Input pulse type 0: AB phase pulse (4x) (Quadrature Input) 1: Clockwise (CW) + Counterclockwise(CCW) pulse 2: Pulse + Direction 3: Other settings:
6-2
ASDA-B2
B: Input pulse filter This setting is used to suppress or reduce the chatter caused by the noise, etc. However, if the instant input pulse filter frequency is over high, the frequency that exceeds the setting value will be regarded as noise and filtered. Setting Low-speed Filter Frequency Setting High-speed Filter Frequency Value (Min. Filter Frequency (see note 1)) Value (Min. Filter Frequency (see note 1)) 0 1 2 3 4 0.83Mpps (600ns) 208Kpps (2.4us) 104Kpps (4.8us) 52Kpps (9.6us) No Filter Function 0 1 2 3 4 3.33Mpps (150ns) 0.83Mpps (600ns) 416Kpps (1.2us) 208Kpps (2.4us) No Filter Function
Please note: 1.
<150ns 150ns
<150ns 150ns
Pulse Input
Pulse Input
filtered signal When this pulse frequency is less than 150 ns, this signal will be regarded as a low-level pulse and two input pulses will be regarded as one input pulse.
filtered signal When this pulse frequency is less than 150 ns, this signal will be regarded as a high-level pulse and two input pulses will be regarded as one input pulse.
>150 ns >150 ns
When the pulse frequencies of high-level duty and low-level duty both are greater than 150 ns, the signal will not be filtered (that is, the pulse command will pass through).
If an input pulse of 2~4MHz is used, it is recommended to change the setting value B (Input pulse filter) and set this setting value to 4. Please note that this function is available for DSP version V1.036 sub05, CPLD version V10 and later models only. Note: If the signal is a 4Mpps high input pulse, setting the value B to 4 is able to ensure that the signal will not be filtered and will be certainly delivered.
6-3
ASDA-B2
Forward
TH
Reverse
TH
Pulse T1 T1 T1 T1 T1
Sign
Sign
Positive 0 Logic
CW + CCW pulse
Pulse
TH T2 T2 T2
T3 T2 T2 T2
TH
Sign
Pulse + Direction
Pulse T4 Sign T5 T6 T5 T6 T5 T4
TH
Pulse T4 Sign T5 T6 T5 T6 T5 T4
TH
AB phase pulse
Pulse TH Sign T1 T1 T1 T1 T1 T1
Pulse TH Sign T1 T1 T1 T1
Pulse T2 Sign T2 T2 T3 T2 T2 T2 TH
Pulse
Pulse + Direction
Sign
TH T4 T5 T6 T5 T6 T5 T4
Pulse Sign T4 T5 T6 T5 T6 T5 T4
TH
Pulse specification High-speed pulse Low-speed pulse Line driver Line driver Open collector
Min. time width T1 62.5ns 0.5s 1.25s T2 125ns 1s 2.5s T3 250ns 2s 5s T4 200ns 2s 5s T5 125ns 1s 2.5s T6 125ns 1s 2.5s
6-4
ASDA-B2
Pulse specification High-speed pulse Low-speed pulse Line driver Line driver Open collector
D: Source of pulse command Setting value 0 1 Input pulse interface Open collector for low-speed pulse Line driver for high-speed pulse Remark CN1 Terminal Identification: PULSE, SIGN CN1 Terminal Identification: PULSE_D, SIGN_D
Position pulse can be input from these terminals, /PULSE (41), PULSE (43), HPULSE (38), /HPULSE (36), /SIGN (37), SIGN (39) and HSIGN (42), /HSIGN (40). It can be an open-collector circuit or line driver circuit. For the detail wiring, please refer to 3.6.1.
In order to pursue the goal of perfection in position control, the pulse signal should be modified through position command processing and the structure is shown as the figure below:
6-5
ASDA-B2
Using parameter P1-01 can select P mode. Electronic gear ratio can be set in P modes to set proper position revolution. ASDA-B2 series servo drive also provides low-pass filter, which are used whenever the motor and load need to be operated more smoothly. As for the information of electronic gear ratio, and low-pass filter, please refer to the following sections 6.2.3 and 6.2.4. Pulse Inhibit Input Function (INHP) INHP is activated via digital inputs (Please refer to parameter P2-10 ~ P2-17P2-36 and DI INHP(07) in Table 7.1).When the drive is in position mode, if INHP is activated, the external pulse input command is not valid and the motor will stop.
Operation Keypad/Software Interface: Default: 16 Control PT Mode: Unit: pulse Range: 1 ~ (226-1) Data Size: 32-bit Display Decimal Format: Settings:
This parameter is used to set the numerator of the electronic gear ratio. The denominator of the electronic gear ratio is set by P1-45. P2-60 ~ P2-62 are used to set the additional numerators. Please note: 1. In PT mode, the setting value of P1-44 can be changed only when the servo drive is enabled (Servo On).
6-6
Revision January 2012
ASDA-B2
P1-45
GR2
Operation Keypad/Software Interface: Default: 10 Control PT Mode: Unit: pulse Range: 1 ~ (231-1) Data Size: 32-bit Display Decimal Format: Settings:
This parameter is used to set the denominator of the electronic gear ratio. The numerator of the electronic gear ratio is set by P1-44. P2-60 ~ P2-62 are used to set the additional numerators. As the wrong setting may cause motor to run chaotically (out of control) and it may lead to personnel injury, therefore, ensure to observe the following rule when setting P1-44, P1-45. The electronic gear ratio setting (Please also see P1-44, P2-60 ~ P2-62):
Pulse input f1 N M Position command N f2 = f1 x M
f1: Pulse input P2-60 ~ P2-62 M: Denominator, the setting value of P1-45 f2: Position command N: Numerator, the setting value of P1-44 or
The electronic gear ratio setting range must be within: 1/50<N/M<25600. Please note: 1. In PT mode, the setting value of P1-45 can not be changed when the servo drive is enabled (Servo On).
The electronic gear function provides easy travel distance ratio change. However, the over high electronic gear ratio will command the motor to move not smoothly. At this time, the users can use low-pass filter parameter to improve this kind of situation. For example, assume that the electronic gear ratio is equal to 1 and the encoder pulse per revolution is 10000ppr, if the electronic gear ratio is changed to 0.5, then the motor will rotate one pulse when the command from external controller is two pulses. For example, after the proper electronic gear ratio is set, the reference travel distance is 1 m/pulse, the machinery will become easier to be used.
6-7
ASDA-B2
Electronic Gear Ratio When the electronic gear ratio is not used When the electronic gear ratio is used
=
= 1 1
1000 0 300 0
=1 m
Operation Keypad/Software Interface: Default: 0 Control PT Mode: Unit: 10ms Range: 0 ~ 1000 Data Size: 16-bit Display Decimal Format: Settings: 0: Disabled For example: 11=110 msec
Position Tar get pos ition
Time (ms) PF LT
6-8
ASDA-B2
fp <
KPP = 2 fp. For example, the desired position loop responsiveness is equal to 20 Hz. Then, KPP = 2 20= 125 rad/s. Relevant parameters: P2-00 KPP Proportional Position Loop Gain Communication Address: 0200H 0201H Related Section: Section 6.2.5
Operation Keypad/Software Interface: Default: 35 Control PT Mode: Unit: rad/s Range: 0 ~ 2047 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set the position loop gain. It can increase stiffness, expedite position loop response and reduce position error. However, if the setting value is over high, it may generate vibration or noise.
6-9
ASDA-B2
P2-02
PFG
Operation Keypad/Software Interface: Default: 50 Control PT Mode: Unit: % Range: 0 ~ 100 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set the feed forward gain when executing position control command. When using position smooth command, increase gain can improve position track deviation. When not using position smooth command, decrease gain can improve the resonance condition of mechanical system.
When the value of Proportional Position Loop Gain, KPP is too great, the position loop responsiveness will be increased and it will result in small phase margin. If this happens, the rotor of motor will oscillate. At this time, the users have to decrease the value of KPP until the rotor of motor stop oscillating. When there is an external torque command interrupted, over low KPP value will let the motor cannot overcome the external strength and fail to meet the requirement of reasonable position track error demand. Adjust feed forward gain, PFG (P2-02) to efficiently reduce the dynamic position track error.
6-10
ASDA-B2
S1
Mode
6-11
ASDA-B2
When SPD0 and SPD1 are both = 0 (OFF), if the control mode of operation is Sz, then the speed command is 0. Therefore, if the users do not use analog voltage as speed command, the users can choose Sz mode and avoid the zero point drift problem of analog voltage signal. If the speed control mode is S mode, then the command is the analog voltage between V-REF and GND. The setting range of the input voltage is from -10V to +10V and the corresponding motor speed is adjustable (Please see parameter P1-40).
When at least one of SPD0 and SPD1 is not 0 (OFF), the speed command is internal parameter (P1-09 to P1-11). The command is valid (enabled) after either SPD0 or SPD1 is changed.
The range of internal parameters is within -50000 ~ +50000 r/min. Setting value = Range x Unit (0.1 r/min). For example, if P1-09 is set to +30000, the setting value = +30000 x 0.1 r/min = +3000 r/min.
The speed command that is described in this section not only can be taken as speed command in speed control mode (S or Sz mode) but also can be the speed limit input command in torque control mode (T or Tz mode).
In the figure above, the speed command processing is used to select the command source of speed control according to chapter 6.3.1, including proportional gain (P1-40) and S-curve filter smoothing strategy of speed control. The speed control block diagram is used to manage the gain parameters of the servo drive and calculate the current input provided to motor instantaneously. The resonance suppression block diagram is used to suppress the resonance of mechanical system.
6-12
ASDA-B2
The function and structure of speed command processing is shown as the figure below:
The command source is selected according to the state of SPD0, SPD1 and parameter P101 (S or Sz). Whenever the command signal needs to be more smoothly, we recommend the users to use S-curve and low-pass filter.
6-13
ASDA-B2
Relevant parameters: P1-34 TACC Acceleration Time Communication Address: 0144H 0145H Related Section: Section 6.3.3
Operation Keypad/Software Interface: Default: 200 Control S Mode: Unit: ms Range: 1 ~ 20000 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to determine the acceleration time to accelerate from 0 to its rated motor speed. The functions of parameters P1-34, P1-35 and P1-36 are each individual. Please note: 1. When the source of speed command is analog command, the maximum setting value of P1-36 is set to 0, the acceleration and deceleration function will be disabled.
6-14
ASDA-B2
P1-35
TDEC
Operation Keypad/Software Interface: Default: 200 Control S Mode: Unit: ms Range: 1 ~ 20000 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to determine the acceleration time to accelerate from 0 to its rated motor speed. The functions of parameters P1-34, P1-35 and P1-36 are each individual. Please note: 1. When the source of speed command is analog command, the maximum setting value of P1-36 is set to 0, the acceleration and deceleration function will be disabled. Address: 0148H 0149H Communication Related Section: Section 6.3.3
P1-36
TSL
Range: 0 ~ 10000 (0: Disabled) Data Size: 16-bit Display Decimal Format: Settings: This parameter is used to make the motor run more smoothly when startup and windup. Using this parameter can improve the motor running stability.
6-15
ASDA-B2
TSL: P1-36, Accel /Decel S-curve Total acceleration time = TACC + TSL Total deceleration time = TDEC + TSL The functions of parameters P1-34, P1-35 and P1-36 are each individual. When P1-36 is set to 0 (Disabled), the settings of P1-34, P1-35 are still effective. It indicates that the parameters P1-34 and P1-35 will not become disabled even when P1-36 is disabled. Please note: 1. When the source of speed command is analog command, the maximum setting value of P1-36 is set to 0, the acceleration and deceleration function will be disabled. Analog Speed Command S-curve Filter ASDA-B2 series servo drives also provide Analog Speed Command S-curve Filter for the smoothing in response to a sudden analog input signal.
Speed (rpm) 3000 Analog speed command Motor Torque
Time (sec)
-3000
The analog speed command S-curve filter is for the smoothing of analog input signal and its function is the same as the S-curve filter. The speed and acceleration curve of analog speed command S-curve filter are both continuous. The above figure shows the curve of analog speed command S-curve filter and the users can see the ramp of speed command is different during acceleration and deceleration. Also, the users can see the difference of input command tracking and can adjust time setting by using parameter P1-34, P1-35, P136 to improve the actual motor performance according to actual condition.
6-16
ASDA-B2
Analog Speed Command Low-pass Filter Analog Speed Command Low-pass Filter is used to eliminate high frequency response and electrical interference from an analog speed command and it is also with smoothing function. Relevant parameters: P1-06 SFLT Accel / Decel Smooth Constant of Analog Speed Command (Low-pass Filter) Communication Address: 010CH 010DH Related Section: Section 6.3.3
Range: 0 ~ 1000 (0: Disabled) Data Size: 16-bit Display Decimal Format: Settings: 0: Disabled
NOTE
1) If the setting value of parameter P1-06 is set to 0, it indicates the function of this parameter is disabled and the command is just By-Pass.
Target Speed
SFLT
6-17
ASDA-B2
-10
-3000rpm -5000rpm
Relevant parameters: P1-40 VCM Max. Analog Speed Command or Limit Communication Address: 0150H 0151H Related Section: Section 6.3.4
Operation Keypad/Software Interface: Default: rated speed Control S, T Mode: Unit: r/min Range: 0 ~ 10000 Data Size: 16-bit Display Decimal Format: Settings:
In Speed mode, this parameter is used to set the maximum analog speed command based on the maximum input voltage (10V). In Torque mode, this parameter is used to set the maximum analog speed limit based on the maximum input voltage (10V). For example, in speed mode, if P1-40 is set to 3000 and the input voltage is 10V, it indicates that the speed command is 3000 r/min. If P1-40 is set to 3000, but the input voltage is changed to 5V, then the speed command is changed to 1500 r/min. Speed Command / Limit = Input Voltage Value x Setting value of P1-40 / 10
6-18
ASDA-B2
NOTE
1) OFF indicates normally open and ON indicates normally closed. 2) When speed control mode is Sz, the speed command S1=0; when speed control mode is S, the speed command S1 is external analog voltage input (Please refer to P1-01). 3) After Servo ON, the users can select command according to the state of SPD0~1.
6-19
ASDA-B2
There are two turning modes of gain adjustment: Manual and Auto modes. The gain of ASDA-B2 series servo drives can be adjusted by using any one of three tuning modes. Manual Mode: User-defined loop gain adjustment. When using this mode, all auto and auxiliary function will be disabled. Auto Mode: Continuous adjustment of loop gains according to measured inertia, with ten levels of system bandwidth. The parameter set by user is default value. The mode of gain adjustment can be selected by parameter P2-32: P2-32 AUT2 Tuning Mode Selection Communication Address: 0240H 0241H Related Section: Section 5.6, Section 6.3.6
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: N/A Range: 0 ~ 2 Data Size: 16-bit Display Hexadecimal Format: Settings: 0: Manual mode
1: Auto Mode [Continuous adjustment] 2: Semi-Auto Mode [Non-continuous adjustment] Explanation of manual mode: 1. When P2-32 is set to mode#0, the setting value of P2-00, P2-02, P2-04, P2-06, P2-07, P2-25 and P2-26 can be user-defined. When switching mode #1 or #2 to #0, the setting value of P2-00, P2-02, P2-04, P2-06, P2-07, P2-25 and P226 will change to the value that measured in #1 auto-tuning mode or #2 semi-auto tuning mode. Explanation of auto-tuning mode: The servo drive will continuously estimate the system inertia, save the measured load inertia value automatically and memorized in P1-37 every 30 minutes by referring to the frequency response settings of P2-31. 1. When switching mode #1 or #2 to #0, the servo drive will continuously estimate the system inertia, save the measured load inertia value automatically and memorized in P1-37. Then, set the corresponding parameters according to this measured load inertia value. 2. When switching mode#0 or #1 to #2, enter the appropriate load inertia value in P1-37. 3. When switching mode#1 to #0, the setting value of P2-00, P2-04 and P2-06 will change to the value that measured in #1 auto-tuning mode.
6-20
ASDA-B2
Explanation of semi-auto tuning mode: 1. When switching mode #2 to #0, the setting value of P2-00, P2-04, P2-06, P225 and P2-26 will change to the value that measured in #1 auto-tuning mode. 2. After the system inertia becomes stable (The displau of P2-33 will show 1), it will stop estimating the system inertia, save the measured load inertia value automatically, and memorized in P1-37. However, when P2-32 is set to mode#1 or #2, the servo drive will continuously perform the adjustment for a period of time. 3. When the value of the system inertia becomes over high, the display of P2-33 will show 0 and the servo drive will start to adjust the load inertia value continuously.
Manual Mode When Tuning Mode Settings of P2-32 is set to 0, the users can define the proportional speed loop gain (P2-04), speed integral gain (P2-06) feed forward gain (P2-07) and ratio of load inertia to servo motor Inertia (1-37). Please refer to the following description: Proportional gain: Adjust this gain can increase the position loop responsiveness. Integral gain: Adjust this gain can enhance the low-frequency stiffness of speed loop and eliminate the steady error. Also, reduce the value of phase margin. Over high integral gain will result in the unstable servo system. Feed forward gain: Adjust this gain can decrease the phase delay error
P2-04
KVP
Operation Keypad/Software Interface: Default: 500 Control ALL Mode: Unit: rad/s Range: 0 ~ 8191 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set the speed loop gain. When the value of proportional speed loop gain is increased, it can expedite speed loop response. However, if the setting value is over high, it may generate vibration or noise.
6-21
ASDA-B2
P2-06
KVI
Operation Keypad/Software Interface: Default: 100 Control ALL Mode: Unit: rad/s Range: 0 ~ 1023 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set the integral time of speed loop. When the value of speed integral compensation is increased, it can improve the speed response ability and decrease the speed control deviation. However, if the setting value is over high, it may generate vibration or noise. Address: 020EH 020FH Related Section: Section 6.3.6
P2-07
KVF
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: % Range: 0 ~ 100 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set the feed forward gain when executing speed control command. When using speed smooth command, increase gain can improve speed track deviation. When not using speed smooth command, decrease gain can improve the resonance condition of mechanical system.
6-22
ASDA-B2
In theory, stepping response can be used to explain proportional gain (KVP), integral gain (KVI) and feed forward gain (KVF). Now we use frequency area and time area respectively to explain the logic. Frequency Domain
6-23
ASDA-B2
Time Domain
6-24
ASDA-B2
In general, the equipment, such as spectrum analyzer is needed and used to analyze when using frequency domain method and the users also should have this kind of analysis technology. However, when using time domain method, the users only need to prepare an oscilloscope. Therefore, the general users usually use time domain method with the analog DI/DO terminal provided by the servo drive to adjust what is called as PI (Proportional and Integral) type controller. As for the performance of torque shaft load, input command tracking and torque shaft load have the same responsiveness when using frequency domain method and time domain method. The users can reduce the responsiveness of input command tracking by using input command low-pass filter. Auto Mode (Continuous adjustment)) This Auto Mode provides continuous adjustment of loop gains according to measured inertia automatically. It is suitable when the load inertia is fixed or the load inertia change is small and is not suitable for wide range of load inertia change. The period of adjustment time is different depending on the acceleration and deceleration of servo motor. To change the stiffness and responsiveness, please use parameter P2-31.
Motor Speed
Inertia Measurement
6-25
ASDA-B2
Operation Keypad/Software Interface: Default: 1000 Control ALL Mode: Unit: Hz Range: 50 ~ 2000 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set first resonance frequency of mechanical system. It can be used to suppress the resonance of mechanical system and reduce the vibration of mechanical system. If P2-24 is set to 0, this parameter is disabled. The parameters P2-23 and P2-24 are the first group of notch filter parameters and the parameters P2-43 and P2-44 are the second group of notch filter parameters. Notch Filter Attenuation Rate 1 (Resonance Suppression) Communication Address: 0230H 0231H Related Section: Section 6.3.7
P2-24
DPH1
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: dB Range: 0 ~ 32 (0: Disabled) Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set magnitude of the resonance suppression that is set by parameter P2-23. If P2-24 is set to 0, the parameters P2-23 and P2-24 are both disabled.
6-26
Revision January 2012
ASDA-B2
The parameters P2-23 and P2-24 are the first group of notch filter parameters and the parameters P2-43 and P2-44 are the second group of notch filter parameters. Address: 0256H 0257H Related Section: Section 6.3.7
P2-43
NCF2
Operation Keypad/Software Interface: Default: 1000 Control ALL Mode: Unit: Hz Range: 50 ~ 2000 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set second resonance frequency of mechanical system. It can be used to suppress the resonance of mechanical system and reduce the vibration of mechanical system. If P2-43 is set to 0, this parameter is disabled. The parameters P2-23 and P2-24 are the first group of notch filter parameters and the parameters P2-43 and P2-44 are the second group of notch filter parameters. Notch Filter Attenuation Rate 2 (Resonance Suppression) Communication Address: 0258H 0259H Related Section: Section 6.3.7
P2-44
DPH2
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: dB Range: 0 ~ 32 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set magnitude of the resonance suppression that is set by parameter P2-43. If P2-44 is set to 0, the parameters P2-43 and P2-44 are both disabled.
6-27
ASDA-B2
P2-45
NCF3
Operation Keypad/Software Interface: Default: 1000 Control ALL Mode: Unit: Hz Range: 50 ~ 2000 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set third resonance frequency of mechanical system. It can be used to suppress the resonance of mechanical system and reduce the vibration of mechanical system. If P2-45 is set to 0, this parameter is disabled. Notch Filter Attenuation Rate 3 (Resonance Suppression) Communication Address: 025CH 025DH Related Section: Section 6.3.7
P2-46
DPH3
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: dB Range: 0 ~ 32 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set magnitude of the resonance suppression that is set by parameter P2-45. If P2-46 is set to 0, the parameters P2-45 and P2-46 are both disabled.
6-28
ASDA-B2
P2-25
NLP
Default: 0.2 (1kW and below 2 (1kW and below models) or 0.5 (other models) or 5 (other models) models) Control ALL Mode: Unit: 1ms Range: 0.0 ~ 100.0 Data Size: 16-bit Display One-digit Format: Input Value 1.5 = 1.5 ms Example: Settings: This parameter is used to set low-pass filter time constant of resonance suppression. If P2-25 is set to 0, this parameter is disabled. Decimal 15 = 1.5 ms 0.1ms 0 ~ 1000
There are two groups of notch filters provided by ASDA-A2 series. The first group of notch filter is P2-43 and P2-44, and the second group of notch filter is P2-45 and P2-46. When there is resonance, please set P2-47 to 1 or 2 (Auto mode), and then the servo drive will find resonance frequency and suppress the resonance automatically. After suppressing the resonance point, the system will memorize the notch filter frequency into P2-43 and P-45, and memorize the notch filter attenuation rate into P2-44 and P2-46. When P2-47 is set to 1, the resonance suppression will be enabled automatically. After the mechanical system becomes stable (approximate 20 minutes), the setting value of P2-47 will return to 0 (Disable auto resonance suppression function). When P2-47 is set to 2, the system will find the resonance point continuously even after the mechanical system becomes stable.
6-29
ASDA-B2
When P2-47 is set to 1 or 2, if the resonance conditions can not be eliminated, we recommend the users to check the settings of P2-44 and P2-46. If either of the setting value of P2-44 and P2-46 is set to 32, please decrease the speed frequency response and estimate the resonance point again. If the resonance conditions can not be eliminated when the setting values of P244 and P2-46 are both less than 32, please set P2-47 to 0 first, and increase the setting value of P2-44 and P2-46 manually. If the resonance exists still after increasing the setting value of P2-44 and P2-46, please decrease the value of speed frequency response again and then use the resonance suppression function again. When increasing the setting value of P2-44 and P2-46 manually, ensure to pay close attention on the setting value of P2-44 and P2-46. If the value of P2-44 and P2-46 is greater than 0, it indicates that the corresponding resonance frequency of P2-43 and P2-45 is found through auto resonance suppression function. If the value of P2-44 and P2-46 is equal to 0, it indicates that the value of P2-43 and P2-45 will be the default value 1000 and this is not the frequency found by auto resonance suppression function. At this time, if the users increase the value of notch filter attenuation rate which does not exist, the performance of the current mechanical system may deteriorate.
Settings of P2-47 Current Value 0 0 1 1 1 2 2 2 Desired Value 1 2 0 1 2 0 1 2 Function Clear the setting value of P2-43 ~ P2-46 and enable auto resonance suppression function. Clear the setting value of P2-43 ~ P2-46 and enable auto resonance suppression function. Save the setting value of P2-43 ~ P2-46 and disable auto resonance suppression function. Clear the setting value of P2-43 ~ P2-46 and enable auto resonance suppression function. Do not clear the setting value of P2-43 ~ P2-46 and enable auto resonance suppression function continuously. Save the setting value of P2-43 ~ P2-46 and disable auto resonance suppression function. Clear the setting value of P2-43 ~ P2-46 and enable auto resonance suppression function. Do not clear the setting value of P2-43 ~ P2-46 and enable auto resonance suppression function continuously.
6-30
ASDA-B2
6-31
ASDA-B2
Low-pass filter Please use parameter P2-25. The figure below shows the resonant open-loop gain.
Gain
Frequency
When the low-pass filter (parameter P2-25) is adjusted from 0 to high value, the value of Low-pass frequency (BW) will become smaller (see the figure below). The resonant condition is improved and the frequency response and phase margin will also decrease.
Gain
0dB
BW
Frequency
Notch Filter Usually, if the users know the resonance frequency, we recommend the users can eliminate the resonance conditions directly by using notch filter (parameter P2-23, P2-24). However, the range of frequency setting is from 50 to 1000Hz only and the range of resonant attenuation is 0~32 dB only. Therefore, if the resonant frequency is out of this range, we recommend the users to use low-pass filter (parameter P2-25) to improve resonant condition. Please refer to the following figures and explanation to know how to use notch filter and low-pass filter to improve resonant condition.
6-32
ASDA-B2
Gain
Notch Filter
Gain
Frequency
Resonance Frequency .
When the low-pass filter (parameter P2-25) is adjusted from 0 to high value, the value of Low-pass frequency will become smaller (see the figure on page 6-26). The resonant condition is improved but the frequency response and phase margin will also decrease and the system may become unstable. Therefore, if the users know the resonance frequency, the users can eliminate the resonance conditions directly by using notch filter (parameter P2-23, P2-24). Usually, if the resonant frequency can be recognized, we recommend the users can directly use notch filter (parameter P2-23, P2-24) to eliminate the resonance. However, if the resonant frequency will drift or drift out of the notch filter range, we recommend the users not to use notch filter and use low-pass filter to improve resonant conditions.
6-33
ASDA-B2
T1
When TCM0 and TCM1 are both 0 (OFF), if the control mode of operation is Tz, then the command is 0. Therefore, if the users do not use analog voltage as torque command, the users can choose Tz mode to operation torque control to avoid the zero point drift problem of analog voltage. If the control mode of operation is T, then the command is the analog voltage between T-REF and GND. The setting range of the input voltage is from -10V to +10V and the corresponding torque is adjustable (see parameter P1-41).
When at least one of TCM0 and TCM1 is not 0 (OFF), the torque command is internal parameter. The command is valid (enabled) after either TCM0 or TCM1 is changed.
The torque command that is described in this section not only can be taken as torque command in torque control mode (T or Tz mode) but also can be the torque limit input command in position mode (P mode) and speed control mode (S or Sz mode).
6-34
ASDA-B2
The toque command processing is used to select the command source of torque control according to chapter 6.4.1, including max. analog torque command (parameter P1-41) and smoothing strategy of torque control mode. The current control block diagram is used to manage the gain parameters of the servo drive and calculate the current input provided to motor instantaneously. As the current control block diagram is too complicated, setting the parameters of current control block diagram is not allowed. The function and structure of torque command processing is shown as the figure below:
The command source is selected according to the state of TCM0, TCM1 and parameter P1-01 (T or Tz). Whenever the command signal needs to be more smoothly, we recommend the users to use proportional gain (scalar) and low-pass filter to adjust torque.
6-35
ASDA-B2
Range: 0 ~ 1000 (0: Disabled) Data Size: 16-bit Display Decimal Format: Settings: 0: Disabled
NOTE
1) If the setting value of parameter P1-07 is set to 0, it indicates the function of this parameter is disabled and the command is just By-Pass.
Target Speed
TFLT
Torque command
-10
-100% -300%
6-36
ASDA-B2
Relevant parameters: P1-41 TCM Max. Analog Torque Command or Limit Communication Address: 0152H 0153H Related Section: Section 6.4.4
Operation Keypad/Software Interface: Default: 100 Control ALL Mode: Unit: % Range: 0 ~ 1000 Data Size: 16-bit Display Decimal Format: Settings:
In Torque mode, this parameter is used to set the maximum analog torque command based on the maximum input voltage (10V). In PT and Speed mode, this parameter is used to set the maximum analog torque limit based on the maximum input voltage (10V). For example, in torque mode, if P1-41 is set to 100 and the input voltage is 10V, it indicates that the torque command is 100% rated torque. If P1-41 is set to 100, but the input voltage is changed to 5V, then the torque command is changed to 50% rated torque. Torque Command / Limit = Input Voltage Value x Setting value of P1-41 / 10
OFF OFF ON
ON
OFF ON
ON
NOTE
1) OFF indicates normally open and ON indicates normally closed. 2) When torque control mode is Tz, the torque command T1=0; when torque control mode is T, the speed command T1 is external analog voltage input (Please refer to P1-01). 3) After Servo ON, the users can select command according to the state of TCM0~1. 6-37
ASDA-B2
Sz and Tz mode selection is not provided. In order to avoid using too much DI inputs, we recommend that the users can use external analog signal as input command in speed and torque mode to reduce the use of DI inputs (SPD0~1 or TCM0~1). Please refer to table 3.B and table 3.C in section 3.3.2 to see the default pin number of DI/DO signal.
6-38
ASDA-B2
In torque mode (when S-T is ON), torque command is selected by TCM0~1. When switching to the speed mode (when S-T is OFF), the speed command is selected by SPD0~1, and then the motor will immediately rotate following the command. After S-T is ON again, it will immediately return to torque mode.
6-39
ASDA-B2
SPD0~1 VALID
TCM0~1 VALID
6-40
ASDA-B2
Operation Keypad/Software Interface: Default: 00 Control ALL Mode: Unit: Range: 00 ~ 77 Data Size: 16-bit Display Hexadecimal Format: Settings:
MON1, MON2 Settings: 0: Motor speed (+/-8V / maximum motor speed) 1: Motor torque (+/-8V / maximum torque) 2: Pulse command frequency (+8Volts / 4.5Mpps) 3: Speed command (+/-8Volts / maximum speed command) 4: Torque command (+/-8Volts / maximum torque command) 5: V_BUS voltage (+/-8Volts / 450V) 6: Reserved 7: Reserved Please note: For the setting of analog output voltage proportion, refer to the P104 and P1-05. Example: P0-03 = 01 (MON1 is motor speed analog output, MON2 is motor torque analog output) Motor speed MON1 output voltage= 8 (Max. motor speed P1-04 100 (unit: Volts) )
6-41
ASDA-B2
Motor toque MON2 output voltage= 8 (Max. motor torque P1-05 100 (unit: Volts) )
P1-03
AOUT Pulse Output Polarity Setting Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: Range: 0 ~ 13 Data Size: 16-bit Display Hexadecimal Format: Settings: Communication
A: Analog monitor outputs polarity 0: MON1(+), MON2(+) 1: MON1(+), MON2(-) 2: MON1(-), MON2(+) 3: MON1(-), MON2(-)
P1-04
MON1 Analog Monitor Output Proportion 1 (MON1) Operation Keypad/Software Interface: Default: 100 Control ALL Mode: Unit: % (full scale) Range: 0 ~ 100 Data Size: 16-bit Display Decimal Format: Communication
6-42
ASDA-B2
Settings: Please note: For the setting of analog output voltage proportion, refer to the P1-03. Example: P0-03 = 01 (MON1 is motor speed analog output, MON2 is motor torque analog output) Motor speed MON1 output voltage= 8 (Max. motor speed P1-04 100 (unit: Volts) )
Motor toque MON2 output voltage= 8 (Max. motor torque P1-05 100 (unit: Volts) )
P1-05
MON2 Analog Monitor Output Proportion 2 (MON2) Operation Keypad/Software Interface: Default: 100 Control ALL Mode: Unit: % (full scale) Range: 0 ~ 100 Data Size: 16-bit Display Decimal Format: Settings: Please note: Communication
For the setting of analog output voltage proportion, refer to the P1-03. Example: P0-03 = 01 (MON1 is motor speed analog output, MON2 is motor torque analog output) Motor speed MON1 output voltage= 8 (Max. motor speed P1-04 100 (unit: Volts) )
Motor toque MON2 output voltage= 8 (Max. motor torque P1-05 100 (unit: Volts) )
6-43
ASDA-B2
P4-20
DOF1
Operation Keypad / Software Interface: Default: Factory setting Control ALL Mode: Unit: mV Range: -800 ~ 800 Data Size: 16-bit Display Decimal Format: Settings:
Please note that when P2-08 is set to 10, the users cannot reset this parameter. Analog Monitor Output Drift Adjustment (MON2) Communication Address: 042AH 042BH Related Section: Section 6.4.4
P4-21
DOF2
Operation Keypad / Software Interface: Default: 0 Control ALL Mode: Unit: mV Range: -800 ~ 800 Data Size: 16-bit Display Decimal Format: Settings:
Please note that when P2-08 is set to 10, the users cannot reset this parameter.
6-44
ASDA-B2
For example, when the users want to observe the analog voltage signal of channel 1, if the monitor output setting range is 8V per 325Kpps, then it is needed to change the setting value of parameter P1-04 (Analog Monitor Output Proportion 1) to 50 (=325Kpps/Max. input frequency). Other related parameters setting include parameter P003 (A=3) and P1-03 (A=0~3, output polarity setting). In general, when output voltage value of Ch1 is V1, the pulse command frequency is equal to (Max. input frequency V1/8) P1-04/100. Because there is an offset value of analog monitor output voltage, the zero voltage level of analog monitor output does not match to the zero point of setting value. We recommend the users can use Analog Monitor Output Drift Adjustment, DOF1 (parameter P4-20) and DOF2 (parameter P4-21) to improve this condition. The maximum output voltage range of analog monitor output is 8V. If the output voltage exceed its limit, it is still limited within the range of 8V. The revolution provided by ASDA-B2 series is 10bit, approximated to 13mv/LSB.
8V DOF
-8V
6-45
ASDA-B2
If the users desire to control electromagnetic brake via external controller, not by the servo drive, the users must execute the function of electromagnetic brake during the period of time when servo motor is braking. The braking strength of motor and electromagnetic brake must be in the same direction when servo motor is braking. Then, the servo drive will operate normally. However, the servo drive may generate larger current during acceleration or at constant speed and it may the cause of overload (servo fault).
MBT1(P1-42)
MBT2(P1-43) ZSPD(P1-38)
Motor Speed
BRKR output timing explanation: 1. When SERVO OFF (when DI SON is not activated), the BRKR output goes Off (electromagnetic brake is locked) after the delay time set by P1-43 is reached and the motor speed is still higher than the setting value of P1-38. 2. When SERVO OFF (when DI SON is not activated), the BRKR output goes Off (electromagnetic brake is locked) if the delay time set by P1-43 is not reached and the motor speed is still lower than the setting value of P1-38.
6-46
ASDA-B2
NOTE
1) 2) Please refer to Chapter 3 Connections and Wiring for more wiring information. The BRKR signal is used to control the brake operation. The VDD DC24V power supply of the servo drive can be used to power the relay coil (Relay). When BRKR signal is ON, the motor brake will be activated. 3) 4) Please note that the coil of brake has no polarity. The power supply for brake is DC24V. Never use it for VDD, the +24V source voltage.
6-47
ASDA-B2
The timing charts of control circuit power and main circuit power:
L1, L2 Control Circuit Power 5V Control Circuit Power R, S, T Main Circuit Power BUS Voltage READY SERVO READY SERVO ON (DI Input) SERVO ON (DO Output) Position \ Speed \ Torque Command Input Input available 2 sec > 0msec
1 sec
800ms
6-48
Chapter 7
7.1 Definition
Servo Parameters
There are following five groups for drive parameters: Group 0: Monitor parameters Group 1: Basic parameters Group 2: Extension parameters Group 3: Communication parameters Group 4: Diagnosis parameters (example: P0-xx) (example: P1-xx) (example: P2-xx) (example: P3-xx) (example: P4-xx)
Abbreviation of control modes: PT: Position control mode (command from external signal) S T : : Speed control mode Torque control mode
Explanation of symbols (marked after parameter) () () () () Read-only register, such as P0-00, P0-01, P4-00. Parameter cannot be set when Servo On (when the servo drive is enabled), such as P1-00, P1-46 and P2-33. Parameter is effective only after the servo drive is restarted (after switching power off and on), such as P1-01 and P3-00. Parameter setting values are not retained when power is off, such as P2-31 and P3-06.
7-1
ASDA-B2
7.2
Parameters Summary
Monitor and General Use
Parameter P0-00 P0-01 P0-02 P0-03 P0-08 P0-09 P0-10 P0-11 P0-12 P0-13 P0-17 P0-18 P0-19 P0-20 P0-21 P0-46 P1-04 P1-05
Name VER ALE STS MON TSON CM1 CM2 CM3 CM4 CM5 CM1A CM2A CM3A CM4A CM5A SVSTS MON1 MON2
Function Firmware Version Drive Fault Code Drive Status (Front Panel Display) Analog Monitor Output Servo Startup Time Status Monitor 1 Status Monitor 2 Status Monitor 3 Status Monitor 4 Status Monitor 5 Status Monitor Selection 1 Status Monitor Selection 2 Status Monitor Selection 3 Status Monitor Selection 4 Status Monitor Selection 5 Servo Output Status Display Analog Monitor Output Proportion 1 (MON1) Analog Monitor Output Proportion 2 (MON2)
Default Factory Setting N/A 00 01 0 N/A N/A N/A N/A N/A 0 0 0 0 0 0 100 100
Unit N/A N/A N/A N/A Hour N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A %(full scale) %(full scale)
Control Mode PT O O O O S O O O O T O O O O
O O O O O
O O O O O
O O O O O
O O O
O O O
O O O
6.4.4 6.4.4
Explanation of symbols (marked after parameter) ( ) () () () Read-only register. Parameter cannot be set when Servo On (when the servo drive is enabled). Parameter is effective only after the servo drive is restarted (after switching power off and on). Parameter setting values are not retained when power is off.
7-2
ASDA-B2
P1-06
SFLT
ms
P1-07 P1-08 P1-34 P1-35 P1-36 P1-59 P1-62 P1-63 P1-68 P2-23 P2-24 P2-43 P2-44 P2-45 P2-46 P2-47 P2-48 P2-25 P2-49
TFLT PFLT TACC TDEC TSL MFLT FRCL FRCT PFLT2 NCF1 DPH1 NCF2 DPH2 NCF3 DPH3 ANCF ANCL NLP SJIT
O O
O O O O O O O O O O
Explanation of symbols (marked after parameter) ( ) () () () Read-only register. Parameter cannot be set when Servo On (when the servo drive is enabled). Parameter is effective only after the servo drive is restarted (after switching power off and on). Parameter setting values are not retained when power is off.
7-3
ASDA-B2
P2-31
AUT1
P2-32
AUT2
N/A
Explanation of symbols (marked after parameter) ( ) () () () Read-only register. Parameter cannot be set when Servo On (when the servo drive is enabled). Parameter is effective only after the servo drive is restarted (after switching power off and on). Parameter setting values are not retained when power is off.
7-4
ASDA-B2
Position Control
Parameter Name Function Control Mode and Output Direction Speed and Torque Limit Default Unit pulse r/min N-M N/A % pulse r/min N/A Control Mode PT O O O O O O S O O O O O T O O O O O Related Section 6.1 6.6 6.4.1 -
CTL PSTL
TQ1 ~ 3 1st ~ 3rd Torque Limit GR3 MSPD DCLR Encoder Output Pulse Number Maximum Speed Limit Pulse Deviation Clear Mode
External Pulse Control Command (PT mode) P1-00 P1-44 P1-45 P2-60 P2-61 P2-62 PTT GR1 GR2 GR4 GR5 GR6 External Pulse Input Type Electronic Gear Ratio (1st Numerator) (N1) Electronic Gear Ratio (Denominator) (M) Electronic Gear Ratio (2nd Numerator) (N2) Electronic Gear Ratio (3rd Numerator) (N3) Electronic Gear Ratio (4th Numerator) (N4) 0x2 1 1 1 1 1 N/A pulse pulse pulse pulse pulse O O O O O O 6.2.1 6.2.3 6.2.3 -
Explanation of symbols (marked after parameter) ( ) () () () Read-only register. Parameter cannot be set when Servo On (when the servo drive is enabled). Parameter is effective only after the servo drive is restarted (after switching power off and on). Parameter setting values are not retained when power is off.
7-5
ASDA-B2
Speed Control
Parameter Name Function Control Mode and Output Direction Speed and Torque Limit Encoder Output Pulse Number Maximum Speed Limit Default Unit pulse r/min N-M N/A pulse r/min 0.1 r/min % r/min % r/min O O O Control Mode PT O O O O S O O O O O O O O O T O O O O O O O O O Related Section 6.1 6.6 6.3.1 6.6.2 6.3.4 -
P1-01 P1-02 P1-46 P1-55 P1-09 ~ P1-11 P1-12 ~ P1-14 P1-40 P1-41 P1-76
SP1 ~ 3 1st ~ 3rd Speed Command TQ1 ~ 3 1st ~ 3rd Torque Limit VCM TCM AMSPD Max. Analog Speed Command or Limit Max. Analog Torque Command or Limit Max. Rotation Speed of Encoder Output
Explanation of symbols (marked after parameter) ( ) () () () Read-only register. Parameter cannot be set when Servo On (when the servo drive is enabled). Parameter is effective only after the servo drive is restarted (after switching power off and on). Parameter setting values are not retained when power is off.
7-6
ASDA-B2
Torque Control
Parameter Name Function Control Mode and Output Direction Speed and Torque Limit Encoder Output Pulse Number Maximum Speed Limit 1st ~ 3rd Speed Limit Default Unit pulse r/min N-M N/A pulse r/min r/min Control Mode PT O O O O S O O O O O T O O O O O Related Section 6.1 6.6 6.6.1
P1-01 P1-02 P1-46 P1-55 P1-09 ~ P1-11 P1-12 ~ P1-14 P1-40 P1-41
1st ~ 3rd Torque Command Max. Analog Speed Command or Limit Max. Analog Torque Command or Limit
% r/min %
O O
O O O
6.4.1 6.4.4
Explanation of symbols (marked after parameter) ( ) () () () Read-only register. Parameter cannot be set when Servo On (when the servo drive is enabled). Parameter is effective only after the servo drive is restarted (after switching power off and on). Parameter setting values are not retained when power is off.
7-7
ASDA-B2
Explanation of symbols (marked after parameter) ( ) () () () Read-only register. Parameter cannot be set when Servo On (when the servo drive is enabled). Parameter is effective only after the servo drive is restarted (after switching power off and on). Parameter setting values are not retained when power is off.
7-8
ASDA-B2
Communication
Parameter P3-00 P3-01 P3-02 P3-03 P3-04 P3-05 P3-06 Name ADR BRT PTL FLT CWD CMM SDI Function Communication Address Setting Transmission Speed Communication Protocol Transmission Fault Treatment Communication Time Out Detection Communication Selection Digital Input Communication Function Communication Response Delay Time Monitor Mode Default 0x7F 0x0203 6 0 0 0 0 Unit N/A bps N/A N/A sec N/A N/A Control Mode PT O O O O O O O S O O O O O O O T O O O O O O O Related Section 8.2 8.2 8.2 8.2 8.2 8.2 8.2
P3-07 P3-08
CDT MNS
0 0000
1ms N/A
O O
O O
O O
8.2 8.2
Explanation of symbols (marked after parameter) ( ) () () () Read-only register. Parameter cannot be set when Servo On (when the servo drive is enabled). Parameter is effective only after the servo drive is restarted (after switching power off and on). Parameter setting values are not retained when power is off.
7-9
ASDA-B2
Diagnosis
Parameter P4-00 P4-01 P4-02 P4-03 P4-04 P4-05 P4-06 P4-07 P4-08 P4-09 P4-10 P4-11 P4-12 P4-14 P4-15 P4-16 P4-17 P4-18 P4-19 P4-20 P4-21 P4-22 P4-23 Name ASH1 ASH2 ASH3 ASH4 ASH5 JOG FOT ITST PKEY MOT CEN SOF1 SOF2 TOF2 COF1 COF2 COF3 COF4 TIGB DOF1 DOF2 SAO TAO Function Fault Record (N) Fault Record (N-1) Fault Record (N-2) Fault Record (N-3) Fault Record (N-4) JOG Operation Force Output Contact Control Input Status Digital Keypad Input of Servo Drive Output Status Adjustment Function Analog Speed Input Drift Adjustment 1 Analog Speed Input Drift Adjustment 2 Analog Torque Drift Adjustment 2 Current Detector Drift Adjustment (V1 phase) Current Detector Drift Adjustment (V2 phase) Current Detector Drift Adjustment (W1 phase) Current Detector Drift Adjustment (W2 phase) IGBT NTC Calibration Analog Monitor Output Drift Adjustment (MON1) Analog Monitor Output Drift Adjustment (MON2) Analog Speed Input Offset Analog Torque Input Offset Default 0 0 0 0 0 20 0 0 N/A N/A 0 Factory Setting Factory Setting Factory Setting Factory Setting Factory Setting Factory Setting Factory Setting Factory Setting 0 0 0 0 Unit N/A N/A N/A N/A N/A r/min N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A mV mV mV mV Control Mode PT O O O O O O O O O O O O O O O O O O O O O S O O O O O O O O O O O O O O O O O O O O O O O T O O O O O O O O O O O O O O O O O O O O O Related Section 4.4.1 4.4.1 4.4.1 4.4.1 4.4.1 4.4.2 4.4.4 4.4.5 8.2 4.4.6 6.4.4 6.4.4 -
Explanation of symbols (marked after parameter) ( ) () () () Read-only register. Parameter cannot be set when Servo On (when the servo drive is enabled). Parameter is effective only after the servo drive is restarted (after switching power off and on). Parameter setting values are not retained when power is off.
7-10
ASDA-B2
Operation Keypad/Software Interface: Default: Factory setting Control ALL Mode: Unit: Range: Data Size: 16-bit Display Decimal Format: Settings:
This parameter displays the firmware version of the servo drive. P0-01 ALE Drive Fault Code Address: 0002H 0003H Related Section: Section: 11.1 Section: 11.2 Section: 11.3
Operation Keypad/Software Communication Interface: Default: Control ALL Mode: Unit: Range: 0 ~ 0 (0: clear the fault or restart the servo drive, the same function of ARST (DI signal)) Data Size: 16-bit Display BCD Format: Settings:
This parameter shows the current servo drive fault if the servo drive is currently faulted. The fault code is hexadecimal data but displayed in BCD format (Binary coded decimal). Servo Drive Fault Codes: 001: Overcurrent 002: Overvoltage 003: Undervoltage (This fault code shows when main circuit voltage is below its minimum specified value while Servo On, and it will not show while Servo Off. This fault code cant be cleared automatically after the voltage has returned within its specification. Please refer to parameter P2-66.) 004: Motor error (The drive and motor are not correctly matched for size (power rating). 005: Regeneration error 006: Overload 007: Overspeed
7-11
ASDA-B2
008: Abnormal pulse control command 009: Excessive deviation 010: Reserved 011: Encoder error (The wiring of the encoder is in error and this causes the communication error between the servo drive and the encoder.) 012: Adjustment error 013: Emergency stop activated 014: Reverse limit switch error 015: Forward limit switch error 016: IGBT temperature error 017: Memory error 018: Encoder output error 019: Serial communication error 020: Serial communication time out 021: Reserved 022: Input power phase loss 023: Pre-overload warning 024: Encoder initial magnetic field error 025: Encoder internal error 026: Encoder data error 027: Motor internal error 028: Motor internal error 029: Motor internal error 030: Motor protection error 030: Motor protection error 031: U,V,W, GND wiring error 035: Motor temperature error 048: Excessive encoder output error 067: Motor temperature warning 099: DSP firmware upgrade P0-02 STS Drive Status (Front Panel Display) Communication Address: 0004H 0005H Related Section: Section 7.2
Operation Keypad/Software Interface: Default: 00 Control ALL Mode: Unit: Range: 0 ~ 18 Data Size: 16-bit Display Decimal Format:
7-12
ASDA-B2
Settings: This parameter shows the servo drive status. 00: Motor feedback pulse number (after electronic gear ratio is set) [user unit] 01: Input pulse number of pulse command (after electronic gear ratio is set) [user unit] 02: Position error counts between control command pulse and feedback pulse [user unit] 03: Motor feedback pulse number (encoder unit, 160000 pulse/rev) [pulse] 04: Input pulse number of pulse command (before electronic gear ratio is set) [pulse] 05: Position error counts [pulse] 06: Input frequency of pulse command [Kpps] 07: Motor rotation speed [r/min] 08: Speed input command [Volt] 09: Speed input command [r/min] 10: Torque input command [Volt] 11: Torque input command [%] 12: Average load [%] 13: Peak load [%] 14: Main circuit voltage [Volt] 15: Ratio of load inertia to Motor inertia [0.1times] 16: IGBT temperature 17: Resonance frequency [Hz] 18: Absolute pulse number relative to encoder (use Z phase as home). The value of Z phase home point is 0, and it can be the value from -5000 to +5000 pulses.
0
+5000 -4999 +5000 -4999
The interval of two Z phase pulse command is 10000 pulse. P0-03 MON Analog Monitor Output Communication Address: 0006H 0007H Related Section: Section 6.6.3
Operation Keypad/Software Interface: Default: 00 Control ALL Mode: Unit: Range: 00 ~ 77 Data Size: 16-bit Display Hexadecimal Format:
7-13
ASDA-B2
Settings: This parameter determines the functions of the analog monitor outputs.
MON1, MON2 Settings: 0: Motor speed (+/-8V / maximum motor speed) 1: Motor torque (+/-8V / maximum torque) 2: Pulse command frequency (+8Volts / 4.5Mpps) 3: Speed command (+/-8Volts / maximum speed command) 4: Torque command (+/-8Volts / maximum torque command) 5: V_BUS voltage (+/-8Volts / 450V) 6: Reserved 7: Reserved Please note: For the setting of analog output voltage proportion, refer to the P1-04 and P1-05. Example: P0-03 = 01 (MON1 is motor speed analog output, MON2 is motor torque analog output) Motor speed MON1 output voltage= 8 (Max. motor speed P1-04 100 (unit: Volts) )
Motor toque MON2 output voltage= 8 (Max. motor torque P1-05 100 (unit: Volts) )
Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use)
Address: 0008H 0009H Address: 000AH 000BH Address: 000CH 000DH Address: 000EH 000FH
7-14
ASDA-B2
P0-08
TSON
Operation Keypad/Software Communication Interface: Default: 0 Control Mode: Unit: Hour Range: High Word: 0 ~ 65535 Low Word: 0 ~ 65535 Data Size: 16-bit Display Decimal Format: Settings: High Word: Servo enable time Low Word: Servo power on time P0-09 CM1 Status Monitor 1 Communication
Operation Keypad/Software Interface: Default: Control ALL Mode: Unit: Range: Data Size: 32-bit Display Decimal Format: Settings:
This parameter is used to provide the value of one of the status monitoring functions found in P0-02. The value of P0-09 is determined by P0-17 (desired drive status) through communication setting or the keypad. The drive status can be read from the communication address of this parameter via communication port. For example: Set P0-17 to 3, then all consequent reads of P0-09 will return the motor feedback pulse number in pulse. When reading the drive status through Modbus communication, the system should read two 16-bit data stored in the addresses of 0012H and 0013H to form a 32-bit data. (0013H : 0012H) = (High Word : Low Word) When reading the drive ststus through the keypad, if P0-02 is set to 23, VAR-1 will quickly show for about two seconds and then the value of P0-09 will display on the display.
7-15
ASDA-B2
P0-10
CM2
Operation Keypad/Software Interface: Default: Control ALL Mode: Unit: Range: Data Size: 32-bit Display Decimal Format: Settings:
This parameter is used to provide the value of one of the status monitoring functions found in P0-02. The value of P0-10 is determined by P0-18 (desired drive status) through communication setting or the keypad. The drive status can be read from the communication address of this parameter via communication port. When reading the drive status through the keypad, if P0-02 is set to 24, VAR-2 will quickly show for about two seconds and then the value of P0-10 will display on the display. P0-11 CM3 Status Monitor 3 Communication Address: 0016H 0017H Related Section: Section 4.3.5
Operation Keypad/Software Interface: Default: Control ALL Mode: Unit: Range: Data Size: 32-bit Display Decimal Format: Settings:
This parameter is used to provide the value of one of the status monitoring functions found in P0-02. The value of P0-11 is determined by P0-19 (desired drive status) through communication setting or the keypad. The drive status can be read from the communication address of this parameter via communication port. When reading the drive status through the keypad, if P0-02 is set to 25, VAR-3 will quickly show for about two seconds and then the value of P0-11 will display on the display.
7-16
ASDA-B2
P0-12
CM4
Operation Keypad/Software Interface: Default: Control ALL Mode: Unit: Range: Data Size: 32-bit Display Decimal Format: Settings:
This parameter is used to provide the value of one of the status monitoring functions found in P0-02. The value of P0-12 is determined by P0-20 (desired drive status) through communication setting or the keypad. The drive status can be read from the communication address of this parameter via communication port. When reading the drive status through the keypad, if P0-02 is set to 26, VAR-4 will quickly show for about two seconds and then the value of P0-12 will display on the display. P0-13 CM5 Status Monitor 5 Communication Address: 001AH 001BH Related Section: Section 4.3.5
Operation Keypad/Software Interface: Default: Control ALL Mode: Unit: Range: Data Size: 32-bit Display Decimal Format: Settings:
This parameter is used to provide the value of one of the status monitoring functions found in P0-02. The value of P0-12 is determined by P0-20 (desired drive status) through communication setting or the keypad. The drive status can be read from the communication address of this parameter via communication port. P0-14 P0-15 P0-16 Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Address: 001CH 001DH Address: 001EH 001FH Address: 0020H 0021H
7-17
ASDA-B2
P0-17
CM1A Status Monitor Selection 1 Operation Keypad/Software Interface: Default: 0 Control Mode: Unit: Range: 0 ~ 18 Data Size: 16-bit Display Decimal Format: Settings: Communication
This parameter is used to determine the drive status found in P0-02. The selected drive status will be displayed by P0-09. For example: Set P0-17 to 7, then all consequent reads of P0-09 will return the motor rotation speed in r/min. P0-18 CM2A Status Monitor Selection 2 Operation Keypad/Software Interface: Default: 0 Control Mode: Unit: Range: 0 ~ 18 Data Size: 16-bit Display Decimal Format: Settings: This parameter is used to determine the drive status found in P0-02. P0-19 CM3A Status Monitor Selection 3 Operation Keypad/Software Interface: Default: 0 Control Mode: Unit: Range: 0 ~ 18 Data Size: 16-bit Display Decimal Format: Settings: This parameter is used to determine the drive status found in P0-02. Communication Address: 0026H 0027H Related Section: N/A Communication Address: 0024H 0025H Related Section: N/A
7-18
ASDA-B2
P0-19
CM3A Status Monitor Selection 3 Operation Keypad/Software Interface: Default: 0 Control Mode: Unit: Range: 0 ~ 18 Data Size: 16-bit Display Decimal Format: Settings: Communication
This parameter is used to determine the drive status found in P0-02. P0-20 CM4A Status Monitor Selection 4 Operation Keypad/Software Interface: Default: 0 Control Mode: Unit: Range: 0 ~ 18 Data Size: 16-bit Display Decimal Format: Settings: This parameter is used to determine the drive status found in P0-02. P0-21 CM5A Status Monitor Selection 5 Operation Keypad/Software Interface: Default: 0 Control Mode: Unit: Range: 0 ~ 18 Data Size: 16-bit Display Decimal Format: Settings: This parameter is used to determine the drive status found in P0-02. Communication Address: 002AH 002BH Related Section: N/A Communication Address: 0028H 0029H Related Section: N/A
7-19
ASDA-B2
Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) PCMN Status Monitor Register (PC Software Setting) Operation Keypad/Software Communication Interface: Default: 0x0 Control ALL Mode: Unit: Range: determined by the communication address of the designated parameter Data Size: 32-bit Display Decimal Format: Settings:
Address: 002CH 002DH Address: 002EH 002FH Address: 0030H 0031H Address: 0058H 0059H Related Section: Section 4.3.5
The function of this parameter is the same as P0-09 (Please refer to P0-09). Please note that this pamameter can be set through communication setting only. P0-45 PCMNA Status Monitor Register Selection (PC Software Setting) Communication Address: 005AH 005BH Related Section: Section 4.3.5
Operation Keypad/Software Interface: Default: 0x0 Control ALL Mode: Unit: Range: 0~127 Data Size: 16-bit Display Decimal Format: Settings:
The function of this parameter is the same as P0-17 (Please refer to P0-17). Please note that this pamameter can be set through communication setting only.
7-20
ASDA-B2
P0-46
SVSTS Servo Output Status Display Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: Range: 0x00 ~ 0xFF Data Size: 16-bit Display Hexadecimal Format: Settings: Communication
This parameter is used to display the digital output signal of the servo drive. The servo output status display will show in hexadecimal format. Bit0: SRDY (Servo ready) Bit1: SON (Servo On) Bit2: ZSPD (At Zero speed) Bit3: TSPD (At Speed reached) Bit4: TPOS (At Positioning completed) Bit5: TQL (At Torque limit) Bit6: ALRM (Servo alarm activated) Bit7: BRKR (Electromagnetic brake control) Bit9: OLW (Output overload warning) Bit10: WARN (Servo warning activated. WARN is activated when the drive has detected reverse limit error; forward limit error, emergency stop, serial communication error, and undervoltage these fault conditions.) Bit11: Reserved Bit12: Reserved Bit13: Reserved Bit14: Reserved Bit15: Reserved The servo output status display can be monitored through communication also.
7-21
ASDA-B2
Basic Parameters PTT External Pulse Input Type Communication Address: 0100H 0101H Related Section: Section 6.2.1
Operation Keypad/Software Interface: Default: 0x2 Control PT Mode: Unit: Range: 0 ~ 1132 Data Size: 16-bit Display Hexadecimal Format: Settings:
A: Input pulse type 0: AB phase pulse (4x) (Quadrature Input) 1: Clockwise (CW) + Counterclockwise(CCW) pulse 2: Pulse + Direction 3: Other settings: B: Input pulse filter This setting is used to suppress or reduce the chatter caused by the noise, etc. However, if the instant input pulse filter frequency is over high, the frequency that exceeds the setting value will be regarded as noise and filtered. Setting 0 1 2 3 4 Low-speed Filter Frequency
(see note 1)
0.83Mpps (600ns) 208Kpps (2.4us) 104Kpps (4.8us) 52Kpps (9.6us) No Filter Function
3.33Mpps (150ns) 0.83Mpps (600ns) 416Kpps (1.2us) 208Kpps (2.4us) No Filter Function
7-22
ASDA-B2
Pleae note: 1.
<150ns 150ns <150ns 150ns
Pulse Input
Pulse Input
filtered signal When this pulse frequency is less than 150 ns, this signal will be regarded as a low-level pulse and two input pulses will be regarded as one input pulse.
filtered signal When this pulse frequency is less than 150 ns, this signal will be regarded as a high-level pulse and two input pulses will be regarded as one input pulse.
>150 ns >150 ns
When the pulse frequencies of high-level duty and low-level duty both are greater than 150 ns, the signal will not be filtered (that is, the pulse command will pass through).
If an input pulse of 2~4MHz is used, it is recommended to change the setting value B (Input pulse filter) and set this setting value to 4. Please note that this function is available for DSP version V1.036 sub05, CPLD version V10 and later models only. Note: If the signal is a 4Mpps high input pulse, setting the value B to 4 is able to ensure that the signal will not be filtered and will be certainly delivered.
7-23
ASDA-B2
Forward
TH
Reverse
TH
Pulse T1 T1 T1 T1 T1
Sign
Sign
Positive Logic
CW + CCW pulse
Pulse
TH T2 T2 T2
T3 T2 T2 T2
TH
Sign
TH T4 Sign T5 T6 T5 T6 T5 T4
Pulse + Direction
Pulse
Pulse T4 Sign T5 T6 T5 T6 T5 T4
TH
Pulse
Pulse
TH
AB phase pulse
Sign T1 T1 T1 T1 T1 T1
TH Sign T1 T1 T1 T1
Negative Logic
CW + CCW pulse
Pulse T2 Sign T2 T2 T3 T2 T2 T2 TH
Pulse
Pulse + Direction
Sign T4
TH T5 T6 T5 T6 T5 T4
Pulse Sign T4 T5 T6 T5 T6 T5 T4
TH
Pulse specification High-speed pulse Low-speed pulse Line driver Line driver Open collector
Min. time width T1 62.5ns 0.5s 1.25s T2 125ns 1s 2.5s T3 250ns 2s 5s T4 200ns 2s 5s T5 125ns 1s 2.5s T6 125ns 1s 2.5s
Pulse specification High-speed pulse Low-speed pulse Line driver Line driver Open collector
7-24
ASDA-B2
D: Source of pulse command Setting value 0 1 Input pulse interface Open collector for low-speed pulse Line driver for high-speed pulse Remark CN1 Terminal Identification: PULSE, SIGN CN1 Terminal Identification: PULSE_D, SIGN_D Address: 0102H 0103H Related Section: Section 6.1, Table 7.A
P1-01
CTL
Operation Keypad/Software Communication Interface: Default: 0 Control ALL Mode: Unit: pulse (P mode), r/min (S mode), N-m (T mode) Range: 00 ~ 110 Data Size: 16-bit Display Hexadecimal Format: Settings:
A: Control mode settings Mode 00 01 02 03 04 05 Multiple Mode 06 07 08 09 0A Reserved Reserved PT Reserved S Single Mode T Sz Tz
7-25
ASDA-B2
Single Mode: PT: Position control mode. The command is from external pulse or analog voltage (external analog voltage will be available soon). Execution of the command selection is via DI signal, PTAS.S: Speed control mode. The command is from external signal or internal signal. Execution of the command selection is via DI signals, SPD0 and SPD1. T: Torque control mode. The command is from external signal or internal signal. Execution of the command selection is via DI signals, TCM0 and TCM1. Sz: Zero speed / internal speed command Tz: Zero torque / internal torque commandMultiple Mode: Control of the mode selection is via DI signals. For example, either PT or S control mode can be selected via DI signals, S-P (see Table 7.A). B: Torque output direction settings Direction Forward 0 1
Reverse
P1-02
PSTL
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: Range: 00 ~ 11 Data Size: 16-bit Display Hexadecimal Format: Settings:
A: Disable or Enable speed limit function 0: Disable speed limit function 1: Enable speed limit function (It is available in torque mode)
7-26
ASDA-B2
B: Disable or Enable torque limit function 0: Disable torque limit function 1: Enable torque limit function (It is available in position and speed mode)
This parameter is used to determine that the speed and torque limit functions are enabled or disabled. If P1-02 is set to 11, it indicates that the speed and torque limit functions are enabled always. The users can also use DI signals, SPDLM and TRQLM to enable the speed and torque limit functions. Please note that DI signals, SPD0, SPD1, TCM0, and TCM1 are used to select the command source of the speed and torque limit. P1-03 AOUT Pulse Output Polarity Setting Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: Range: 0 ~ 13 Data Size: 16-bit Display Hexadecimal Format: Settings: Communication Address: 0106H 0107H Related Section: Section 3.3.3
A: Analog monitor outputs polarity 0: MON1(+), MON2(+) 1: MON1(+), MON2(-) 2: MON1(-), MON2(+) 3: MON1(-), MON2(-)
7-27
ASDA-B2
P1-04
MON1 Analog Monitor Output Proportion 1 (MON1) Operation Keypad/Software Interface: Default: 100 Control ALL Mode: Unit: % (full scale) Range: 0 ~ 100 Data Size: 16-bit Display Decimal Format: Settings: Please note: Communication
For the setting of analog output voltage proportion, refer to the P1-03. Example: P0-03 = 01 (MON1 is motor speed analog output, MON2 is motor torque analog output) Motor speed MON1 output voltage= 8 (Max. motor speed Motor toque MON2 output voltage= 8 (Max. motor torque P1-05 P1-05 ) 100 (unit: Volts) P1-04 ) 100 (unit: Volts)
MON2 Analog Monitor Output Proportion 2 (MON2) Operation Keypad/Software Interface: Default: 100 Control ALL Mode: Unit: % (full scale) Range: 0 ~ 100 Data Size: 16-bit Display Decimal Format: Settings: Please note: Communication
For the setting of analog output voltage proportion, refer to the P1-03. Example: P0-03 = 01 (MON1 is motor speed analog output, MON2 is motor torque analog output) Motor speed MON1 output voltage= 8 (Max. motor speed P1-04 ) 100 (unit: Volts)
7-28
ASDA-B2
Motor toque MON2 output voltage= 8 (Max. motor torque Accel / Decel Smooth Constant of Analog Speed Command (Low-pass Filter) P1-05 ) 100 (unit: Volts)
P1-06
SFLT
Operation Keypad/Software Communication Interface: Default: 0 Control S Mode: Unit: ms Range: 0 ~ 1000 (0: Disabled) Data Size: 16-bit Display Decimal Format: Settings: 0: Disabled P1-07 TFLT Smooth Constant of Analog Torque Command (Low-pass Filter)
Operation Keypad/Software Communication Interface: Default: 0 Control T Mode: Unit: ms Range: 0 ~ 1000 (0: Disabled) Data Size: 16-bit Display Decimal Format: Settings: 0: Disabled P1-08 PFLT Smooth Constant of Position Command (Low-pass Filter) Communication
Operation Keypad/Software Interface: Default: 0 Control PT Mode: Unit: 10ms Range: 0 ~ 1000 Data Size: 16-bit Display Decimal Format: Settings: 0: Disabled For example: 11=110 msec
7-29
ASDA-B2
P1-09
SP1
Operation Keypad/Software Interface: Default: 1000 Control S, T Mode: Unit: 0.1r/min Range: -50000 ~ +50000 Data Size: 32-bit Display Decimal Format: Settings: For example: 120=12 r/min 1st Speed Command
In Speed mode, this parameter is used to set speed 1 of internal speed command. 1st Speed Limit In Torque mode, this parameter is used to set speed limit 1 of internal speed command. P1-10 SP2 2nd Speed Command or Limit Communication Address: 0114H 0115H Related Section: Section 6.3.1
Operation Keypad/Software Interface: Default: 2000 Control S, T Mode: Unit: 0.1r/min Range: -50000 ~ +50000 Data Size: 32-bit Display Decimal Format: Settings: For example: 120=12 r/min 2nd Speed Command
In Speed mode, this parameter is used to set speed 2 of internal speed command. 2nd Speed Limit In Torque mode, this parameter is used to set speed limit 2 of internal speed command.
7-30
ASDA-B2
P1-11
SP3
Operation Keypad/Software Interface: Default: 3000 Control S, T Mode: Unit: 0.1r/min Range: -50000 ~ +50000 Data Size: 32-bit Display Decimal Format: Settings: For example: 120=12 r/min 3rd Speed Command
In Speed mode, this parameter is used to set speed 3 of internal speed command. 3rd Speed Limit In Torque mode, this parameter is used to set speed limit 3 of internal speed command. P1-12 TQ1 1st Torque Command or Limit Communication Address: 0118H 0119H Related Section: Section 6.4.1
Operation Keypad/Software Interface: Default: 100 Control T, P&S Mode: Unit: % Range: -300 ~ +300 Data Size: 16-bit Display Decimal Format: Settings: 1st Torque Command
In Torque mode, this parameter is used to set torque 1 of internal torque command. 1st Torque Limit In Position and Speed mode, this parameter is used to set torque limit 1 of internal torque command.
7-31
ASDA-B2
P1-13
TQ2
Operation Keypad/Software Interface: Default: 100 Control T, P&S Mode: Unit: % Range: -300 ~ +300 Data Size: 16-bit Display Decimal Format: Settings: 2nd Torque Command
In Torque mode, this parameter is used to set torque 2 of internal torque command. 2nd Torque Limit In Position and Speed mode, this parameter is used to set torque limit 2 of internal torque command. P1-14 TQ3 3rd Torque Command or Limit Communication Address: 011CH 011DH Related Section: Section 6.4.1
Operation Keypad/Software Interface: Default: 100 Control T, P&S Mode: Unit: % Range: -300 ~ +300 Data Size: 16-bit Display Decimal Format: Settings: 3rd Speed Command
In Torque mode, this parameter is used to set torque 3 of internal torque command. 3rd Speed Limit In Position and Speed mode, this parameter is used to set torque limit 3 of internal torque command. P1-15 P1-16 P1-17 Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Address: 011EH 011FH Address: 0120H 0121H Address: 0122H 0123H
7-32
ASDA-B2
Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) LSTP Motor Stop Mode Selection Communication
Address: 0124H 0125H Address: 0126H 0127H Address: 0128H 0129H Address: 012AH 012BH Address: 012CH 012DH Address: 012EH 012FH Address: 013EH 013FH Address: 0140H 0141H Related Section: N/A
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: Range: 0 ~ 20 Data Size: 16-bit Display Hexadecimal Format: Settings:
A: Fault Stop Mode When a fault occurs (except for CWL, CCWL, EMGS and serial communication error), it is used to set servo motor stop mode. 0: Stop instantly 1: Decelerate to stop B: Dynamic Brake Option When Servo Off or a fault (servo alarm) occurs, it is used to set servo motor stop mode. 0: Use dynamic brake 1: Allow servo motor to coast to stop
7-33
ASDA-B2
2: Use dynamic brake first, after the motor speed is below than P1-38, allow servo motor to coast to stop When the fault NL(CWL) or PL(CCWL) occurs, please refer to the settings of parameter P1-06, P1-35, P1-36 to determine the deceleration time. If the deceleration time is set to 1ms, the motor will stop instantly. P1-33 P1-34 Reserved (Do Not Use) TACC Acceleration Time Communication Address: 0142H 0143H Address: 0144H 0145H Related Section: Section 6.3.3
Operation Keypad/Software Interface: Default: 200 Control S Mode: Unit: ms Range: 1 ~ 20000 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to determine the acceleration time to accelerate from 0 to its rated motor speed. The functions of parameters P1-34, P1-35 and P1-36 are each individual. Please note: 1. When the source of speed command is analog command, the maximum setting value of P1-36 is set to 0, the acceleration and deceleration function will be disabled. P1-35 TDEC Deceleration Time Communication Address: 0146H 0147H Related Section: Section 6.3.3
Operation Keypad/Software Interface: Default: 200 Control S Mode: Unit: ms Range: 1 ~ 20000 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to determine the acceleration time to accelerate from 0 to its rated motor speed. The functions of parameters P1-34, P1-35 and P1-36 are each individual. Please note: 1. When the source of speed command is analog command, the maximum setting value of P1-36 is set to 0, the acceleration and deceleration function will be disabled.
7-34
Revision January 2012
ASDA-B2
P1-36
TSL
Operation Keypad/Software Communication Interface: Default: 0 Control S Mode: Unit: ms Range: 0 ~ 10000 (0: Disabled) Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to make the motor run more smoothly when startup and windup. Using this parameter can improve the motor running stability.
TACC: P1-34, Acceleration time TDEC: P1-35, Deceleration time TSL: P1-36, Accel /Decel S-curve Total acceleration time = TACC + TSL Total deceleration time = TDEC + TSL The functions of parameters P1-34, P1-35 and P1-36 are each individual. When P1-36 is set to 0 (Disabled), the settings of P1-34, P1-35 are still effective. It indicates that the parameters P1-34 and P1-35 will not become disabled even when P1-36 is disabled. Please note: 1. When the source of speed command is analog command, the maximum setting value of P1-36 is set to 0, the acceleration and deceleration function will be disabled. P1-37 GDR Ratio of Load Inertia to Servo Motor Inertia Communication 10 Address: 014AH 014BH Related Section: N/A
Operation Keypad/Software Interface: Default: 1.0 Control ALL Mode: Unit: 1 times Range: 0.0 ~ 200.0 Data Size: 16-bit Display One-digit Format: Input Value 1.5 = 1.5 times Example:
Revision January 2012
ASDA-B2
Settings: Ratio of load inertia to servo motor inertia (for Rotation Motor): (J_load /J_motor) J_load: Total equivalent moment of inertia of external mechanical load J_motor: Moment of inertia of servo motor P1-38 ZSPD Zero Speed Range Setting Communication 100 Address: 014CH 014DH Related Section: Table 7.B
Operation Keypad/Software Interface: Default: 10.0 Control ALL Mode: Unit: 1 r/min Range: 0.0 ~ 200.0 Data Size: 16-bit Display One-digit Format: Input Value 1.5 = 1.5 r/min Example: Settings:
This parameter is used to set output range of zero speed signal (ZSPD) and determine when zero speed signal (ZSPD) becomes activated. ZSPD is activated when the drive senses the motor is equal to or below the Zero Speed Range setting as defined in parameter P1-38. For Example, at default ZSPD will be activated when the drive detects the motor rotating at speed at or below 100 r/min. ZSPD will remain activated until the motor speed increases above 100 r/min. P1-39 SSPD Target Motor Speed Communication Address: 014EH 014FH Related Section: Table 7.B
Operation Keypad/Software Interface: Default: 3000 Control ALL Mode: Unit: r/min Range: 0 ~ 5000 Data Size: 16-bit Display Decimal Format: Settings:
When target motor speed reaches its preset value, digital output (TSPD) is enabled. When the forward and reverse speed of servo motor is equal and higher than the setting value, the motor will reach the target motor speed, and then TSPD signal will output. TSPD is activated once the drive has detected the motor has reached the Target Motor Speed setting as defined in parameter P1-39. TSPD will remain activated until the motor speed drops below the Target Motor Speed.
7-36
ASDA-B2
P1-40
VCM
Operation Keypad/Software Interface: Default: rated speed Control S, T Mode: Unit: r/min Range: 0 ~ 10000 Data Size: 16-bit Display Decimal Format: Settings:
In Speed mode, this parameter is used to set the maximum analog speed command based on the maximum input voltage (10V). In Torque mode, this parameter is used to set the maximum analog speed limit based on the maximum input voltage (10V). For example, in speed mode, if P1-40 is set to 3000 and the input voltage is 10V, it indicates that the speed command is 3000 r/min. If P1-40 is set to 3000, but the input voltage is changed to 5V, then the speed command is changed to 1500 r/min. Speed Command / Limit = Input Voltage Value x Setting value of P1-40 / 10 P1-41 TCM Max. Analog Torque Command or Limit Communication Address: 0152H 0153H Related Section: Section 6.4.4
Operation Keypad/Software Interface: Default: 100 Control ALL Mode: Unit: % Range: 0 ~ 1000 Data Size: 16-bit Display Decimal Format: Settings:
In Torque mode, this parameter is used to set the maximum analog torque command based on the maximum input voltage (10V). In PT and Speed mode, this parameter is used to set the maximum analog torque limit based on the maximum input voltage (10V). For example, in torque mode, if P1-41 is set to 100 and the input voltage is 10V, it indicates that the torque command is 100% rated torque. If P1-41 is set to 100, but the input voltage is changed to 5V, then the torque command is changed to 50% rated torque. Torque Command / Limit = Input Voltage Value x Setting value of P1-41 / 10
7-37
ASDA-B2
P1-42
MBT1
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: ms Range: 0 ~ 1000 Data Size: 16-bit Display Decimal Format: Settings:
Used to set the period of time between when the servo drive is On (Servo On) and when electromagnetic brake output signal (BRKR) is activated. P1-43 MBT2 OFF Delay Time of Electromagnetic Brake Communication Address: 0156H 0157H Related Section: Section 6.5.5
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: ms Range: -1000 ~ +1000 Data Size: 16-bit Display Decimal Format: Settings:
Used to set the period of time between when the servo drive is Off (Servo Off) and when electromagnetic brake output signal (BRKR) is inactivated.
Please note: 1. When servo is commanded off and the off delay time set by P1-43 has not elapsed, if the motor speed is lower than the setting value of P1-38, the electromagnetic brake will be engaged regardless of the off delay time set by P1-43. 2. When servo is commanded off and the off delay time set by P1-43 has elapsed, if the motor speed is higher than the setting value of P1-38, electromagnetic brake will be engaged regardless of the current motor speed. 3. When the servo drive is disabled (Servo Off) due to a fault (except AL022) or by EMGS (Emergency stop)) being activated, if the off delay time set by P1-43 is a negative value, it will not affect the operation of the motor. A negative value of the off delay time is equivalent to one with a zero value.
7-38
Revision January 2012
ASDA-B2
P1-44
GR1
Operation Keypad/Software Interface: Default: 16 Control PT Mode: Unit: pulse Range: 1 ~ (226-1) Data Size: 32-bit Display Decimal Format: Settings:
This parameter is used to set the numerator of the electronic gear ratio. The denominator of the electronic gear ratio is set by P1-45. P2-60 ~ P2-62 are used to set the additional numerators. Please note: 1. In PT mode, the setting value of P1-44 can be changed only when the servo drive is enabled (Servo On). P1-45 GR2 Electronic Gear Ratio (Denominator) (M) Communication Address: 015AH 015BH Related Section: Section 6.2.3
Operation Keypad/Software Interface: Default: 10 Control PT Mode: Unit: pulse Range: 1 ~ (231-1) Data Size: 32-bit Display Decimal Format: Settings:
This parameter is used to set the denominator of the electronic gear ratio. The numerator of the electronic gear ratio is set by P1-44. P2-60 ~ P2-62 are used to set the additional numberators. As the wrong setting may cause motor to run chaotically (out of control) and it may lead to personnel injury, therefore, ensure to observe the following rule when setting P1-44, P1-45. The electronic gear ratio setting (Please also see P1-44, P2-60 ~ P2-62):
Pulse input f1 N M Position command N f2 = f1 x M
f1: Pulse input P2-60 ~ P2-62 M: Denominator, the setting value of P1-45 f2: Position command N: Numerator, the setting value of P1-44 or
The electronic gear ratio setting range must be within: 1/50<N/M<25600. Please note: 1. In PT mode, the setting value of P1-45 can not be changed when the servo drive is enabled (Servo On).
Revision January 2012
7-39
ASDA-B2
P1-46
GR3
Operation Keypad/Software Interface: Default: 2500 Control ALL Mode: Unit: pulse Range: 4 ~ 40000 Data Size: 32-bit Display Decimal Format: Settings:
This parameter is used to set the pulse numbers of encoder outputs per motor revolution. Please note: When the following conditions occur, the output frequency for pulse output may exceed the specification and cause that the servo drive fault AL018 (Encoder Output Error) is activated. Condition 1: Encoder error. Condition 2: Motor speed is above the value set by parameter P1-76. P1-47 SPOK Speed Reached Output Range Communication Address: 015EH 015FH Related Section: N/A
Operation Keypad/Software Interface: Default: 10 Control S, Sz Mode: Unit: r/min Range: 0 ~ 300 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set the speed reached output range. The DO signal, SP_OK (0x19) will be activated when the speed error is equal and below the setting value of P1-47.
7-40
ASDA-B2
1. Speed Command: It is the speed command input by the users (no Accel/Decel), not the frond-end command of speed control loop. The source of this command includes analog voltage and registers. 2. Feedback Speed: It is the actual motor speed which is filtered. 3. Get Absolute Value 4. Judge if the speed error is equal and below the setting value of P1-47: When P1-47 is set to 0, this digital output will be always off. 5. ON or OFF: When the speed error is equal and below the setting value of P1-47, SP_OK will be ON; otherwise, SP_OK will be OFF. P1-48 P1-49 P1-50 P1-51 P1-52 Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) RES1 Regenerative Resistor Value Communication Address: 0160H 0161H Address: 0162H 0163H Address: 0164H 0165H Address: 0166H 0167H Address: 0168H 0169H Related Section: Section 6.6.3
Operation Keypad/Software Interface: Default: See the table below Control ALL Mode: Unit: Ohm Range: 10 ~ 750 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set the resistance of the applicable regenerative resistor. Model For 750W models For 1kW to 3kW models Default
100 40
7-41
ASDA-B2
P1-53
RES2
Operation Keypad/Software Interface: Default: See the table below Control ALL Mode: Unit: Watt Range: 30 ~ 3000 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set the capacity of the applicable regenerative resistor. Model For 750W models For 1kW to 3kW models P1-54 PER Default 60W 60W Address: 016CH 016DH Related Section: Table 7.B
Operation Keypad/Software Interface: Default: 1600 Control PT Mode: Unit: pulse Range: 0 ~ 1280000 Data Size: 32-bit Display Decimal Format: Settings:
In PT mode, when the error pulse numbers is less than the setting value of parameter P1-54, TPOS (At positioning completed signal) will be activated. P1-55 MSPD Maximum Speed Limit Communication Address: 016EH 016FH Related Section: N/A
Operation Keypad/Software Interface: Default: rated speed Control ALL Mode: Unit: r/min Range: 0 ~ Max. speed Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set maximum motor speed. The default setting is rated speed.
7-42
ASDA-B2
P1-56
OVW
Operation Keypad/Software Interface: Default: 120 Control ALL Mode: Unit: % Range: 0 ~ 120 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set output overload time. If the setting value of parameter P1-56 is set to 0 ~ 100, the function of parameter P1-56 is enabled. When the motor has reached the output overload time set by parameter P1-56, the motor will send a warning to the drive. After the drive has detected the warning, the DO signal OLW will be activated. If the setting value of parameter P1-56 exceeds 100, the function of parameter P1-56 is disabled. tOL = Permissible Time for Overload x the setting value of parameter P1-56 When overload accumulated time (continuously overload time) exceeds the value of tOL, the overload warning signal will output, i.e. DO signal, OLW will be ON. However, if the accumulated overload time (continuous overload time) exceeds the permissible time for overload, the overload alarm (AL006) will occur. For example: If the setting value of parameter P1-56 (Output Overload Warning Time) is 60%, when the permissible time for overload exceeds 8 seconds at 200% rated output, the overload fault (AL006) will be detected and shown on the LED display. At this time, tOL = 8 x 60% = 4.8 seconds Result: When the drive output is at 200% rated output and the drive is continuously overloaded for 4.8 seconds, the overload warning signal will be ON, i.e. DO signal OLW will be activated. If the drive is continuously overloaded for 8 seconds, the overload alarm will be detected and shown on the LED display (AL006). Then, Servo Fault signal will be ON (DO signal ALRM will be activated). P1-57 CRSHA Motor Protection Percentage Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: % Range: 0 ~ 300 Data Size: 16-bit Display Decimal Format: Communication Address: 0172H 0173H Related Section: N/A
7-43
ASDA-B2
Settings: This parameter is used to protect the motor in case the motor touchs the mechanical equipment. If P1-57 is set to 0, the function of P1-57 is disabled. The function of P1-57 is enabled when the setting value of P1-57 is set to 1 or more. The fault AL030 will be activated when the setting value of P1-57 is reached after a period of time set by P1-58. P1-58 CRSHT Motor Protection Time Operation Keypad/Software Interface: Default: 1 Control ALL Mode: Unit: ms Range: 0 ~ 1000 Data Size: 16-bit Display Decimal Format: Settings: This parameter is used to protect the motor in case the motor touchs the mechanical equipment. The fault AL030 will be activated when the setting value of P1-57 is reached after a period of time set by P1-58. Please note that this function is applicable for non-contact applications, such as electric discharge machines only (P1-37 must be set correctly). P1-59 MFLT Analog Speed Linear Filter (Moving Filter) Communication 0 Address: 0176H 0177H Related Section: N/A Communication Address: 0174H 0175H Related Section: N/A
Operation Keypad/Software Interface: Default: 0.0 Control S Mode: Unit: 1 ms Range: 0.0 ~ 4.0 (0: Disabled) Data Size: 16-bit Display One-digit Format: Input Value 1.5 = 1.5 ms Example: Settings:
This parameter is used to eliminate the noise generated during the operation when the host (external) controller sends the step analog voltage speed command. The parameter P1-06 is Low-pass Filter and parameter P1-59 is Moving Filter. The differences are that Low-pass Filter is usually used to smooth the end of the command but Moving Filter can be used to smooth the start and the end of step analog voltage speed command. Using Moving Filter can facilitate the smooth operation of the motor very effectively.
7-44
ASDA-B2
Therefore, it is recommended to use P1-06 Low-pass Filter when the speed command from the external controller is applied for position control loop. If the command is for speed control only, using Moving Filter P1-59 can achieve better (smooth) performance.
Reserved (Do Not Use) Reserved (Do Not Use) FRCL Friction Compensation Percentage Communication
Address: 0178H 0179H Address: 017AH 017BH Address: 017CH 017DH Related Section: N/A
Operation Keypad/Software Interface: Default: 0 Control PT, S Mode: Unit: % Range: 0 ~ 100 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set the torque percentage for friction compensation. If P1-62 is set to 0, the function of P1-62 is disabled. The function of P1-62 is enabled when the setting value of P1-62 is set to 1 or more. P1-63 FRCT Friction Compensation Percentage Communication Address: 017EH 017FH Related Section: N/A
Operation Keypad/Software Interface: Default: 0 Control PT, S Mode: Unit: ms Range: 0 ~ 1000 Data Size: 16-bit Display Decimal Format:
7-45
ASDA-B2
Settings: This parameter is used to set the smooth constant of friction compensation. P1-64 P1-65 P1-66 P1-67 P1-68 Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) PFLT2 Position Command Moving Filter 1 Operation Keypad/Software Communication Interface: Default: 4 Control PT Mode: Unit: ms Range: 0 ~ 100 (0: Disabled) Data Size: 16-bit Display Decimal Format: Settings: Moving Filter can be used to smooth the start and the end of step position command. Using Moving Filter can facilitate the smooth operation of the motor very effectively, but it will cause command delay. Address: 0180H 0181H Address: 0182H 0183H Address: 0184H 0185H Address: 0186H 0187H Address: 0188H 0189H Related Section: N/A
7-46
ASDA-B2
Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) AMSPD Max. Rotation Speed of Encoder Output Operation Keypad/Software Communication Interface: Default: 5500 Control ALL Mode: Unit: r/min Range: 0 ~ 6000 (0: Disabled) Data Size: 16-bit Display Decimal Format: Settings:
Address: 018AH 018BH Address: 018CH 018DH Address: 018EH 018FH Address: 0190H 0191H Address: 0192H 0193H Address: 0194H 0195H Address: 0196H 0197H Address: 0198H 0199H Related Section: P1-46
This parameter is used to optimize the encoder outputs (OA, OB). When the users set the actual reached maximum motor speed, the servo drive will equalize the encoder outputs automatically. When P1-76 is set to 0, it indicates that equalizing function is not available. P1-77 PFLT3 Position Command Moving Filter 2 Operation Keypad/Software Communication Interface: Default: 4 Control PT Mode: Unit: ms Range: 0 ~ 100 (0: Disabled) Data Size: 16-bit Display Decimal Format: Settings: Moving Filter can be used to smooth the start and the end of step position command. Using Moving Filter can facilitate the smooth operation of the motor
Revision January 2012
7-47
ASDA-B2
7-48
ASDA-B2
Group 2: P2-xx Extension Parameters P2-00 KPP Proportional Position Loop Gain Communication Address: 0200H 0201H Related Section: Section 6.2.5
Operation Keypad/Software Interface: Default: 35 Control PT Mode: Unit: rad/s Range: 0 ~ 2047 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set the position loop gain. It can increase stiffness, expedite position loop response and reduce position error. However, if the setting value is over high, it may generate vibration or noise. P2-01 PPR Position Loop Gain Switching Rate Communication Address: 0202H 0203H Related Section: Section 6.2.5
Operation Keypad/Software Interface: Default: 100 Control PT Mode: Unit: % Range: 10 ~ 500 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set the position gain switching rate when the gain switching condition is satisfied. Please refer to P2-27 for gain switching control selection settings and refer to P2-29 for gain switching condition settings. P2-02 PFG Position Feed Forward Gain Communication Address: 0204H 0205H Related Section: Section 6.2.5
Operation Keypad/Software Interface: Default: 50 Control PT Mode: Unit: % Range: 0 ~ 100 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set the feed forward gain when executing position control command. When using position smooth command, increase gain can
Revision January 2012
7-49
ASDA-B2
improve position track deviation. When not using position smooth command, decrease gain can improve the resonance condition of mechanical system. P2-03 PFF Smooth Constant of Position Feed Forward Gain Communication Address: 0206H 0207H Related Section: N/A
Operation Keypad/Software Interface: Default: 5 Control PT Mode: Unit: ms Range: 2 ~ 100 Data Size: 16-bit Display Decimal Format: Settings:
When using position smooth command, increase gain can improve position track deviation. When not using position smooth command, decrease gain can improve the resonance condition of mechanical system. P2-04 KVP Proportional Speed Loop Gain Communication Address: 0208H 0209H Related Section: Section 6.3.6
Operation Keypad/Software Interface: Default: 500 Control ALL Mode: Unit: rad/s Range: 0 ~ 8191 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set the speed loop gain. When the value of proportional speed loop gain is increased, it can expedite speed loop response. However, if the setting value is over high, it may generate vibration or noise. P2-05 SPR Speed Loop Gain Switching Rate Communication Address: 020AH 020BH Related Section: N/A
Operation Keypad/Software Interface: Default: 100 Control ALL Mode: Unit: % Range: 10 ~ 500 Data Size: 16-bit Display Decimal Format:
7-50
ASDA-B2
Settings: This parameter is used to set the speed gain switching rate when the gain switching condition is satisfied. Please refer to P2-27 for gain switching control selection settings and refer to P2-29 for gain switching condition settings. P2-06 KVI Speed Integral Compensation Communication Address: 020CH 020DH Related Section: Section 6.3.6
Operation Keypad/Software Interface: Default: 100 Control ALL Mode: Unit: rad/s Range: 0 ~ 1023 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set the integral time of speed loop. When the value of speed integral compensation is increased, it can improve the speed response ability and decrease the speed control deviation. However, if the setting value is over high, it may generate vibration or noise. P2-07 KVF Speed Feed Forward Gain Communication Address: 020EH 020FH Related Section: Section 6.3.6
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: % Range: 0 ~ 100 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set the feed forward gain when executing speed control command. When using speed smooth command, increase gain can improve speed track deviation. When not using speed smooth command, decrease gain can improve the resonance condition of mechanical system.
7-51
ASDA-B2
P2-08
PCTL
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: N/A Range: 0 ~ 65535 Data Size: 16-bit Display Decimal Format: Settings:
This parameter can be used to reset all parameters to their original factory settings and enable some parameters functions. Reset parameters settings: 10: Users can reset all parameter values to factory defaults. All parameter values will be reset after re-power the servo drive. (Before perform this settings, ensure that the status of the servo drive is Servo Off.) Enable parameters functions: 20: If P2-08 is set to 20, then the parameter P4-10 is enabled. 22: If P2-08 is set to 22, then the parameters P4-11~P4-19 are enabled. 406: If P2-08 is set to 406, then the Digital Output (DO) signal can be forced to be activated and the drive will enter into Force Output Control operation mode. 400: If P2-08 is set to 400, it can switch the Force Output Control operation mode to normal Digital Output (DO) Control operation mode. P2-09 DRT Bounce Filter Communication Address: 0212H 0213H Related Section: N/A
Operation Keypad/Software Interface: Default: 2 Control ALL Mode: Unit: 2ms Range: 0 ~ 20 Data Size: 16-bit Display Decimal Format: Input Value 4 = 8 ms Example: Settings:
For example, if P2-09 is set to 4, the bounce filter time is 4 x 2ms = 8ms. When there are too much vibration or noises around environment, increasing this setting value (bounce filter time) can improve reliability. However, if the time is too long, it may affect the response time.
7-52
ASDA-B2
P2-10
DI1
Operation Keypad/Software Interface: Default: 101 Control ALL Mode: Unit: N/A Range: 0 ~ 015Fh Data Size: 16-bit Display Hexadecimal Format: Settings:
The parameters from P2-10 to P2-17 and P2-36 are used to determine the functions and statuses of DI1 ~ DI8.
A: DI (Digital Input) Function Settings: For the setting value of P2- 10 ~ P2-17 and P2-36, please refer to Table 7.A. B: DI (Digital Input) Enabled Status Settings: 0: Normally closed (contact b) 1: Normally open (contact a) For example, when P2-10 is set to 101, it indicates that the function of DI1 is SON (Servo On, setting value is 0x01) and it requires a normally open contact to be connected to it. Please re-start the servo drive after parameters have been changed. Please note: The parameter P3-06 is used to set how the Digital Inputs (DI) accept commands and signals through the external terminals or via the communication which is determined by parameter P4-07. P2-11 DI2 Digital Input Terminal 2 (DI2) Communication Address: 0216H 0217H Related Section: Table 7.A
Operation Keypad/Software Interface: Default: 104 Control ALL Mode: Unit: N/A Range: 0 ~ 015Fh Data Size: 16-bit Display Hexadecimal Format:
7-53
ASDA-B2
P2-12
DI3
Operation Keypad/Software Interface: Default: 116 Control ALL Mode: Unit: N/A Range: 0 ~ 015Fh Data Size: 16-bit Display Hexadecimal Format:
Settings: Refer to P2-10 for explanation. P2-13 DI4 Digital Input Terminal 4 (DI4) Communication Address: 021AH 021BH Related Section: Table 7.A
Operation Keypad/Software Interface: Default: 117 Control ALL Mode: Unit: N/A Range: 0 ~ 015Fh Data Size: 16-bit Display Hexadecimal Format:
Settings: Refer to P2-10 for explanation. P2-14 DI5 Digital Input Terminal 5 (DI5) Communication Address: 021CH 021DH Related Section: Table 7.A
Operation Keypad/Software Interface: Default: 102 Control ALL Mode: Unit: N/A Range: 0 ~ 015Fh Data Size: 16-bit Display Hexadecimal Format:
7-54
ASDA-B2
P2-15
DI6
Operation Keypad/Software Interface: Default: 22 Control ALL Mode: Unit: N/A Range: 0 ~ 015Fh Data Size: 16-bit Display Hexadecimal Format:
Settings: Refer to P2-10 for explanation. P2-16 DI7 Digital Input Terminal 7 (DI7) Communication Address: 0220H 0221H Related Section: Table 7.A
Operation Keypad/Software Interface: Default: 23 Control ALL Mode: Unit: N/A Range: 0 ~ 015Fh Data Size: 16-bit Display Hexadecimal Format:
Settings: Refer to P2-10 for explanation. P2-17 DI8 Digital Input Terminal 8 (DI8) Communication Address: 0222H 0223H Related Section: Table 7.A
Operation Keypad/Software Interface: Default: 21 Control ALL Mode: Unit: N/A Range: 0 ~ 015Fh Data Size: 16-bit Display Hexadecimal Format:
7-55
ASDA-B2
P2-18
DO1
Operation Keypad/Software Interface: Default: 101 Control ALL Mode: Unit: N/A Range: 0 ~ 013Fh Data Size: 16-bit Display Hexadecimal Format: Settings:
The parameters from P2-18 to P2-22 and P2-37 are used to determine the functions and statuses of DO1 ~ DO5.
A: DO Function Settings: For the setting value of P2- 18 ~ P2-22 and P2-37, please refer to Table 7.B. B: DO Enabled Status Settings: 0: Normally closed (contact b) 1: Normally open (contact a) For example, when P2-18 is set to 101, it indicates that the function of DO1 is SRDY (Servo ready, setting value is 0x01) and it requires a normally open contact to be connected to it. Please re-start the servo drive after parameters have been changed. P2-19 DO2 Digital Output Terminal 2 (DO2) Communication Address: 0226H 0227H Related Section: Table 7.B
Operation Keypad/Software Interface: Default: 103 Control ALL Mode: Unit: N/A Range: 0 ~ 013Fh Data Size: 16-bit Display Hexadecimal Format:
7-56
ASDA-B2
P2-20
DO3
Operation Keypad/Software Interface: Default: 109 Control ALL Mode: Unit: N/A Range: 0 ~ 013Fh Data Size: 16-bit Display Hexadecimal Format:
Settings: Refer to P2-18 for explanation. P2-21 DO4 Digital Output Terminal 4 (DO4) Communication Address: 022AH 022BH Related Section: Table 7.B
Operation Keypad/Software Interface: Default: 105 Control ALL Mode: Unit: N/A Range: 0 ~ 013Fh Data Size: 16-bit Display Hexadecimal Format:
Settings: Refer to P2-18 for explanation. P2-22 DO5 Digital Output Terminal 5 (DO5) Communication Address: 022CH 022DH Related Section: Table 7.B
Operation Keypad/Software Interface: Default: 7 Control ALL Mode: Unit: N/A Range: 0 ~ 013Fh Data Size: 16-bit Display Hexadecimal Format:
7-57
ASDA-B2
P2-23
NCF1
Operation Keypad/Software Interface: Default: 1000 Control ALL Mode: Unit: Hz Range: 50 ~ 2000 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set first resonance frequency of mechanical system. It can be used to suppress the resonance of mechanical system and reduce the vibration of mechanical system. If P2-24 is set to 0, this parameter is disabled. The parameters P2-23 and P2-24 are the first group of notch filter parameters and the parameters P2-43 and P2-44 are the second group of notch filter parameters. P2-24 DPH1 Notch Filter Attenuation Rate 1 (Resonance Suppression) Communication Address: 0230H 0231H Related Section: Section 6.3.7
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: dB Range: 0 ~ 32 (0: Disabled) Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set magnitude of the resonance suppression that is set by parameter P2-23. If P2-24 is set to 0, the parameters P2-23 and P2-24 are both disabled. The parameters P2-23 and P2-24 are the first group of notch filter parameters and the parameters P2-43 and P2-44 are the second group of notch filter parameters.
7-58
ASDA-B2
P2-25
Low-pass Filter Time Constant (Resonance Suppression) Operation Keypad/Software Communication Interface: Default: 0.2 (1kW and below 2 (1kW and below models) or 0.5 (other models) or 5 (other models) models) Control ALL Mode: Unit: 1ms 0.1ms Range: 0.0 ~ 100.0 0 ~ 1000 Data Size: 16-bit Display One-digit Decimal Format: Input Value 1.5 = 1.5 ms 15 = 1.5 ms Example: NLP Settings:
This parameter is used to set low-pass filter time constant of resonance suppression. If P2-25 is set to 0, this parameter is disabled. P2-26 DST External Anti-Interference Gain Address: 0234H 0235H Related Section: N/A
Operation Keypad/Software Communication Interface: Default: 0 Control ALL Mode: Unit: 0.001 Range: 0 ~ 1023 (0: Disabled) Data Size: 16-bit Display Decimal Format: Settings: If P2-26 is set to 0, this parameter is disabled.
This parameter is used to increase the damping factor of speed loop. It is recommended to set the setting value of P2-26 to be equal to the setting value of P2-06. Please note: 1. In speed mode, increasing the parameter value of P2-26 can reduce speed overshoot. 2. In position mode, decreasing the parameter value of P2-26 can reduce position overshoot.
7-59
ASDA-B2
P2-27
GCC
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: N/A Range: 0 ~ 4 Data Size: 16-bit Display Hexadecimal Format: Settings: Gain Switching Condition Settings:
A: Gain Switching Condition Settings: 0: Disabled 1: Gain switching DI (Digital Input) signal (GAINUP) is On. (see Table 8.A) 2: In position mode, position deviation is higher than the setting value of P2-29. 3: Position command frequency is higher than the setting value of P2-29. 4: Servo motor speed is higher than the setting value of P2-29. 5: Gain switching DI (Digital Input) signal (GAINUP) is Off. (see Table 8.A) 6: In position mode, position deviation is lower than the setting value of P2-29. 7: Position command frequency is lower than the setting value of P2-29. 8: Servo motor speed is lower than the setting value of P2-29. B: Gain Switching Control Settings: 0: Gain multiple switching 1: P PI switching Setting P mode P2-00 x 100% P2-04 x 100% P2-00 x P2-01 P2-04 x P2-05 S mode P2-04 x 100% P2-04 x P2-05 Status Before switching After switching Before switching After switching
7-60
ASDA-B2
P2-28
GUT
Operation Keypad/Software Communication Interface: Default: 10 Control ALL Mode: Unit: 10ms Range: 0 ~ 1000 (0: Disabled) Data Size: 16-bit Display Decimal Format: Input Value 15 = 150 ms Example: Settings:
This parameter is used to set the time constant when switching the smooth gain. P2-29 GPE Gain Switching Condition Communication Address: 023AH 023BH Related Section: N/A
Operation Keypad/Software Interface: Default: 160000 Control ALL Mode: Unit: pulse, Kpps, r/min Range: 0 ~ 3840000 Data Size: 32-bit Display Decimal Format: Settings:
This parameter is used to set the value of gain switching condition (pulse error, Kpps, r/min) selected in P2-27. The setting value will be different depending on the different gain switching condition. P2-30 INH Auxiliary Function Communication Address: 023CH 023DH Related Section: N/A
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: N/A Range: -8 ~ +8 Data Size: 16-bit Display Decimal Format: Settings:
0: Disabled all functions described below. 1: Force the servo drive to be Servo On (upon software) 2~4: Reserved
Revision January 2012
7-61
ASDA-B2
5: After setting P2-30 to 5, the setting values of all parameters will lost (not remain in the EEPROM) at power-down. When the parameters data are no more needed, using this mode can allows users not to save parameters data into the EEPROM without damaging the EEPROM. P2-30 should be set to 5 when using communication control function. 6: After setting P2-30 to 6, the servo drive will enter into Simulation mode. At this time, DO signal SON (Servo on) will be disabled, and the value of DSP Error (0x6F) will be regarded as zero. The servo drive can accept commands in each mode and monitor the commands via Data Scope function provided by ASDA-Soft software program. But, the servo motor will not run when the servo drvie in Simulation mode. This setting is only used to check and ensure the command is correct. It indicates the external Servo On signal is disabled in this mode, and therefore the motor fault messages such as overcurrent, overload, or overspeed, etc. will not display. The paraemeter P0-01 displays external fault messages such as reverse inhibit limit, forward inhibit limit, or emergency stop, etc. only. Please note: 1. Please set P2-30 to 0 during normal operation. 2. The setting value of P2-30 will return to 0 automatically after re-power the servo drive. P2-31 AUT1 Speed Frequency Response Level in Auto and Address: 023EH Semi-Auto Mode 023FH Communication Related Section: Section 5.6, Section 6.3.6
Operation Keypad/Software Interface: Default: 80 Control ALL Mode: Unit: Hz Range: 1 ~ 1000 Data Size: 16-bit Display Hexadecimal Format: Settings:
This parameter allows the users to set the speed frequency response level of auto-tuning and semi-auto tuning mode. The speed frequency response settings are as follows: 1 ~ 50Hz : Low stiffness and low frequency response 51 ~ 250Hz : Medium stiffness and medium frequency response 251 ~ 550Hz : High stiffness and high frequency response Please note: 1. The servo drive will set the position frequency response according to the setting value of P2-31. 2. This parameter is activated by P2-32. Please refer to Section 5.6 for the tuning procedure and the related settings.
7-62
ASDA-B2
P2-32
AUT2
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: N/A Range: 0 ~ 2 Data Size: 16-bit Display Hexadecimal Format: Settings: 0: Manual mode
1: Auto Mode [Continuous adjustment] 2: Semi-Auto Mode [Non-continuous adjustment] Explanation of manual mode: 1. When P2-32 is set to mode#0, the setting value of P2-00, P2-02, P2-04, P2-06, P2-07, P2-25 and P2-26 can be user-defined. When switching mode #1 or #2 to #0, the setting value of P2-00, P2-02, P2-04, P2-06, P2-07, P2-25 and P2-26 will change to the value that measured in #1 auto-tuning mode or #2 semi-auto tuning mode. Explanation of auto-tuning mode: The servo drive will continuously estimate the system inertia, save the measured load inertia value automatically and memorized in P1-37 every 30 minutes by referring to the frequency response settings of P2-31. 1. When switching mode #1 or #2 to #0, the servo drive will continuously estimate the system inertia, save the measured load inertia value automatically and memorized in P1-37. Then, set the corresponding parameters according to this measured load inertia value. 2. When switching mode#0 or #1 to #2, enter the appropriate load inertia value in P1-37. 3. When switching mode#1 to #0, the setting value of P2-00, P2-04 and P2-06 will change to the value that measured in #1 auto-tuning mode. Explanation of semi-auto tuning mode: 1. When switching mode #2 to #0, the setting value of P2-00, P2-04, P2-06, P2-25 and P2-26 will change to the value that measured in #1 auto-tuning mode. 2. After the system inertia becomes stable (The displau of P2-33 will show 1), it will stop estimating the system inertia, save the measured load inertia value automatically, and memorized in P1-37. However, when P2-32 is set to mode#1 or #2, the servo drive will continuously perform the adjustment for a period of time. 3. When the value of the system inertia becomes over high, the display of P2-33 will show 0 and the servo drive will start to adjust the load inertia value continuously.
7-63
ASDA-B2
P2-33
AUT3
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: N/A Range: 0 ~ 1 Data Size: 16-bit Display Decimal Format: Settings:
When the setting value of A is set to 0 or display is 0, it indicates that the load inertia estimation of semi-auto tuning mode has been executed but not been completed yet. When the setting value of A is set to 1, it indicates that the load inertia estimation of semi-auto tuning mode has been completed. The measured load inertia is memorized in P1-37. If P2-33 is reset to 0, the servo drive will perform continuous adjustment for estimating the load inertia (P1-37) again. B: Reserved. P2-34 SDEV Overspeed Warning Condition Communication Address: 0244H 0245H Related Section: N/A
Operation Keypad/Software Interface: Default: 5000 Control S Mode: Unit: r/min Range: 1 ~ 6000 Data Size: 16-bit Display Decimal Format: Display Format: Decimal Settings:
This parameter is used to set the over speed threshold that is used to determine the over speed fault condition. When the difference in speed between the desired speed and actual motor speed is over than the setting value of parameter P2-34, the servo fault, Overspeed (AL007) will be activated.
7-64
ASDA-B2
P2-35
PDEV
Operation Keypad/Software Interface: Default: 480000 Control PT Mode: Unit: pulse Range: 1 ~ 16000000 Data Size: 32-bit Display Decimal Format: Settings:
This parameter is used to set the position deviation excessive error threshold that is used to determine the escessive deviation fault condition. When the difference in pulse number between the desired position and actual motor position is over than the setting value of parameter P2-35, the servo fault, Excessive Deviation (AL009) will be activated. P2-36 DI9 External Digital Input Terminal 9 (DI9) Communication Address: 0248H 0249H Related Section: Table 7.A
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: N/A Range: 0 ~ 015Fh Data Size: 16-bit Display Hexadecimal Format: Settings:
The parameters from P2-36 to P2-41 are used to determine the functions and statuses of external DI9 ~ DI14.
A: DI (Digital Input) Function Settings: For the setting value of P2- 36 ~ P2-41, please refer to Table 7.A. B: External DI (Digital Input) Enabled Status Settings: 0: Normally closed (contact b) 1: Normally open (contact a)
7-65
ASDA-B2
P2-37
DO6
Operation Keypad/Software Interface: Default: 7 Control ALL Mode: Unit: N/A Range: 0 ~ 013Fh Data Size: 16-bit Display Hexadecimal Format:
Settings: Refer to P2-18 for explanation. P2-38 P2-39 P2-40 P2-41 P2-42 P2-43 Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) NCF2 Notch Filter 2 (Resonance Suppression) Communication Address: 024CH 024DH Address: 024EH 024FH Address: 0250H 0251H Address: 0252H 0253H Address: 0254H 0255H Address: 0256H 0257H Related Section: Section 6.3.7
Operation Keypad/Software Interface: Default: 1000 Control ALL Mode: Unit: Hz Range: 50 ~ 2000 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set second resonance frequency of mechanical system. It can be used to suppress the resonance of mechanical system and reduce the vibration of mechanical system. If P2-43 is set to 0, this parameter is disabled. The parameters P2-23 and P2-24 are the first group of notch filter parameters and the parameters P2-43 and P2-44 are the second group of notch filter parameters.
7-66
ASDA-B2
P2-44
DPH2
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: dB Range: 0 ~ 32 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set magnitude of the resonance suppression that is set by parameter P2-43. If P2-44 is set to 0, the parameters P2-43 and P2-44 are both disabled. P2-45 NCF3 Notch Filter 3 (Resonance Suppression) Communication Address: 025AH 025BH Related Section: Section 6.3.7
Operation Keypad/Software Interface: Default: 1000 Control ALL Mode: Unit: Hz Range: 50 ~ 2000 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set third resonance frequency of mechanical system. It can be used to suppress the resonance of mechanical system and reduce the vibration of mechanical system. If P2-45 is set to 0, this parameter is disabled. P2-46 DPH3 Notch Filter Attenuation Rate 3 (Resonance Suppression) Communication Address: 025CH 025DH Related Section: Section 6.3.7
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: dB Range: 0 ~ 32 Data Size: 16-bit Display Decimal Format:
7-67
ASDA-B2
Settings: This parameter is used to set magnitude of the resonance suppression that is set by parameter P2-45. If P2-46 is set to 0, the parameters P2-45 and P2-46 are both disabled. P2-47 ANCF Auto Resonance Suppression Mode Selection Communication Address: 025EH 025FH Related Section: N/A
Operation Keypad/Software Interface: Default: 1 Control ALL Mode: Unit: N/A Range: 0 ~ 2 Data Size: 16-bit Display Decimal Format: Settings:
0: Disable Auto Resonance Suppression Mode. The setting value of P2-23~P2-24 and P2-43~P2-46 will be fixed and will not be changed. 1: Auto Resonance Suppression Mode 1 [Non-continuous adjustment] After the resonance is suppressed, the setting value of P2-23, P2-24, P2-43, P2-44, P2-45 and P2-46 will be fixed and will not be changed. 2: Auto Resonance Suppression Mode 2 [Continuous adjustment] The servo drive will perform the resonance suppression continuously (will not stop). The setting value of P2-23, P2-24, P2-43, P2-44, P2-45 and P2-46 will not be fixed. When P2-47 is set to 1, the resonance suppression will be enabled automatically. After the mechanical system becomes stable, the setting value of P2-47 will return to 0. When the mechanical system is stable, the resonance suppression point will be memorized. When the mechanical system is not stable, if the servo drive is restarted or P2-47 is set to 1, the servo drive will estimate the resonance suppression point again. When P2-47 is set to 2, the servo drive will perform the resonance suppression continuously. When the mechanical system becomes stable, the resonance suppression point will be memorized. When the mechanical system is not stable, if the servo drive is restarted, the servo drive will estimate the resonance suppression point again. When switching the mode#1 or #2 to #0, the setting values of P2-43, P2-44, P2-45 and P2-46 will be saved automatically.
7-68
ASDA-B2
P2-48
ANCL
Operation Keypad/Software Interface: Default: 100 Control ALL Mode: Unit: N/A Range: 1 ~ 300% Data Size: 16-bit Display Decimal Format: Settings:
When the setting value is smaller, the system will become more sensitive to detect and find the resonance. When the value of The setting value of P2-48 , the sensitivity of detecting resonance . The setting value of P2-48 , the sensitivity of detecting resonance . P2-49 SJIT Speed Detection Filter and Jitter Suppression Communication Address: 0262H 0263H Related Section: Section 6.2.5
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: sec Range: 0 ~ 1F Data Size: 16-bit Display Decimal Format: Settings: Setting Value of P2-49 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D
Revision January 2012
Cutoff Frequency of Speed Loop Feedback (Hz) 2500 2250 2100 2000 1800 1600 1500 1400 1300 1200 1100 1000 950 900
7-69
ASDA-B2
Cutoff Frequency of Speed Loop Feedback (Hz) 850 800 750 700 650 600 550 500 450 400 350 300 250 200 175 150 125 100 Address: 0264H 0265H Related Section: N/A
Operation Keypad/Software Interface: Default: 00 Control PT Mode: Unit: N/A Range: 0 ~ 11 Data Size: 16-bit Display Hexadecimal Format: Settings:
For digital input function (DI function), please refer to Table 7.A. This pulse deviation clear function is enabled when a digital input is set to pulse clear function (CCLR mode, DI (Digital Input) setting value is 0x04). When this input is triggered, the position accumulated pulse number will be clear to 0. (available in PT mode only)
7-70
ASDA-B2
Triggering Method Settings: 0: CCLR is triggered by rising-edge 1: CCLR is triggered bu level Function Selection Settings: 0: Clear position accumulated pulse number When this input is triggered, the position accumulated pulse number will be clear to 0. 1: Clear feedback PUU When this input is triggered, the feedback PUU will be clear to 0. P2-51 P2-52 P2-53 Reserved (Do Not Use) Reserved (Do Not Use) KPI Position Integral Compensation Communication Address: 0266H 0267H Address: 0268H 0269H Address: 026AH 026BH Related Section: Section 6.3.6
Operation Keypad/Software Interface: Default: 0 Control ALL Mode: Unit: rad/s Range: 0 ~ 1023 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set the integral time of position loop. When the value of position integral compensation is increased, it can decrease the position control deviation. However, if the setting value is over high, it may generate position overshoot or noise. P2-54 P2-55 P2-56 P2-57 P2-58 P2-59 Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use) Address: 026CH 026DH Address: 026EH 026FH Address: 0270H 0271H Address: 0272H 0273H Address: 0274H 0275H Address: 0276H 0277H
7-71
ASDA-B2
P2-60
GR4
Operation Keypad/Software Interface: Default: 16 Control PT Mode: Unit: pulse Range: 1 ~ (226-1) Data Size: 32-bit Display Decimal Format: Settings:
The electronic gear numerator value can be set via GNUM0, GNUM1 (refer to Table 7.A). When the GNUM0, GNUM1 are not defined, the default of gear numerator value is set by P1-44. When the users wish to set the gear numerator value by using GNUM0, GNUM1, please set P2-60 ~ P2-62 after the servo motor has been stopped to prevent the mechanical system vibration.
P2-61
GR5
Operation Keypad/Software Interface: Default: 16 Control PT Mode: Unit: pulse Range: 1 ~ (226-1) Data Size: 32-bit Display Decimal Format: Settings: Refer to P2-60 for explanation.
7-72
ASDA-B2
P2-62
GR6
Operation Keypad/Software Interface: Default: 16 Control PT Mode: Unit: pulse Range: 1 ~ (226-1) Data Size: 32-bit Display Decimal Format: Settings: Refer to P2-60 for explanation. P2-63 P2-64 P2-65 Reserved (Do Not Use) Reserved (Do Not Use) GBIT Special Function 1
Address: 027EH 027FH Address: 0280H 0281H Address: 0282H 0283H Related Section: N/A
Operation Keypad/Software Interface: Default: 0 Control PT, S Mode: Unit: N/A Range: 0 ~ 0xFFFF Data Size: N/A Display N/A Format: Settings:
Communication
Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8 Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 Bit5 Bit4 Bit3 Bit2
Bit2 ~ Bit5: Reserved. Must be set to 0. Bit6 Bit6: Abnormal pulse command detection 0: enable abnormal pulse command detection 1: disable abnormal pulse command detection Bit8 Bit8: U, V, W wiring error detection 1: enable U, V, W wiring error detection
7-73
ASDA-B2
Bit9 Bit9: U, V, W wiring cut-off detection 1: enable U, V, W wiring cut-off detection Bit10 Bit10: DI ZCLAMP function selection When the following conditions are all met, ZCLAMP function will be activated. Condition1: Speed mode Condition2: DI ZCLAMP is activated. Condition3: External analog speed command or internal registers speed command is less than parameter P1-38. 0: When the command source is an analog speed command, the users can use ZCLAMP DI signal to stop the motor at the desire position and do not care the acceleration and deceleration speed curve of the analog speed command. The motor will be locked at the position when ZCLAMP conditions are satisfied.
0: When the command source is an internal speed command, the users can use ZCLAMP DI signal to stop the motor at the desire position and keep the the acceleration and deceleration speed curve of the internal speed command. The motor will be locked at the position when ZCLAMP conditions are satisfied.
1: When the command source is an analog speed command, the users can use ZCLAMP DI signal to stop the motor at the desire position and do not care the acceleration and deceleration speed curve of the internal speed command. When ZCLAMP conditions are satisfied, the speed command is decreased to 0 r/min. When ZCLAMP conditions are not satisfied, the speed command will follow the analog speed command through Accel/Decel S-curve.
7-74
ASDA-B2
1: When the command source is an internal speed command, the users can use ZCLAMP DI signal to stop the motor at the desire position and keep the acceleration and deceleration speed curve of the analog speed command. When ZCLAMP conditions are satisfied, the speed command is forced to 0 r/min directly.
B11 Bit11: NL(CWL)/PL(CCWL) pulse input inhibit function 0: Disable NL(CWL)/PL(CCWL) pulse input inhibit function. In PT mode, no matter NL or PL exists or not, external position pulse command will be input into the servo drive. 1: Enable NL(CWL)/PL(CCWL) pulse input inhibit function. In PT mode, if NL exists, the external NL pulse input into the servo drive will be inhibited and PL pulse input will be accepted. On the one hand, in PT mode, if PL exists, the external PL pulse input into the servo drive will be inhibited and PL pulse input will be accepted. Please note: If NL and PL both exist, NL and PL pulse input into the servo drive will be both inhibited.
7-75
ASDA-B2
Bit12 Bit12: Input power phase loss detection function 0: Enable Input power phase loss (AL022) detection function 1: Disable Input power phase loss (AL022) detection function Bit13 Bit13: Encoder output error detection function 0: Enable encoder output error (AL018) detection function 1: Disable encoder output error (AL018) detection function Bit15 Bit14
Bit14 ~ Bit15: Reserved. Must be set to 0. P2-66 GBIT2 Special Function 2 Operation Keypad/Software Interface: Default: 0 Control PT, S Mode: Unit: N/A Range: 0 ~ 0xFFFF Data Size: 16-bit Display Hexadecimal Format: Settings: Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 Bit0 Bit0: Speed limit accel / decel function The torque command source is determined by TCM0 and TCM1. When the digital input, TQP or TQN is used, the torque command is activated by TQP or TQN. When TQP is ON, the torque will be output directly as the same as the command souce. For example, when TQP is ON, if the torque command source is an input voltage of 5V and P1-41 is set to 100, it indicates that the torque command is 50% rated torque until the speed is limited. However, whenTQN is ON, if the torque command source is an input voltage of 5V and P1-41 is set to 100, it indicates that the torque command is -50% rated torque until the speed is limited. Speed limit function can be enabled always by P1-02. When P1-02 is set to 0x10, the speed limit function can be enabled all the time and the users do not need to use DI, SPDLM to switch the speed limit function. The speed limit command is determined by SPD0 and SPD1. The acceleration and deceleration time is determined by P1-34, P1-35 and P1-36. Communication Address: 0284H 0285H Related Section: N/A
7-76
ASDA-B2
Torque Output Zero torque output Output the torque of the command source directly (do not reverse the command, and output the torque directly) Reverse the torque of the command source (reverse the command first, and then output the torque) Zero torque output
The timing charts of speed limit profile (with accel / decel function)and torque command (TQP/TQN):
Motormax Speed Vref P1-40 10 P1-09 Current Speed 0 RPM P1-09 Vref P1-40 10 P1-13 P1-14 P1-12 0 torque
P1-12
P1-14
P1-13
Tref
0 torque
Tref
TCM1
SPDLM
SPD0
Bit1 Bit1: Reserved. Must be set to 0. Bit2 Bit2: Undervoltage (Servo Drive Fault, AL003) clear mode selection 0: The fault, Undervoltage will not be cleared automatically. 1: The fault, Undervoltage will be cleared automatically. Bit6 Bit5 Bit4 Bit3
Bit3 ~ Bit6: Reserved. Must be set to 0. Bit7 Bit7: Motor temperature warning (Servo Drive Fault, AL067) display mode selection 0: The fault, Undervoltage will be displayed. 1: The fault, Undervoltage will not be displayed.
Revision January 2012
7-77
ASDA-B2
P2-67
JSL
Operation Keypad/Software Interface: Default: 1.5 Control ALL Mode: Unit: 1 times Range: 0 ~ 200.0 Data Size: 16-bit Display One-digit Format: Input Value 1.5 = 1.5 times Example: Settings:
In semi-auto tuning mode, after the servo drive continuously perform the adjustment for a period of time which is determined by P2-67, the system will consider that the system inertia has become stable and finish the operation of system inertia estimation.
7-78
ASDA-B2
Group 3: P3-xx Communication Parameters P3-00 ADR Communication Address Setting Communication Address: 0300H 0301H Related Section: Section 8.2
Operation Keypad / Software Interface: Default: 0x7F Control ALL Mode: Unit: N/A Range: 0x01 ~ 0x7F Data Size: 16-bit Display Hexadecimal Format: Settings:
This parameter is used to set the communication slave address in hexadecimal format. Display Range 0 0 Y 0~7 X 0~F
X: Axis number which indicates the value must be within the range from 0 through F. Y: Group number which indicates the value must be within the range from 0 to through 7 When using RS-232/485 communication, this parameter is used set the communication address in hexadecimal format. If the AC servo drive is controlled by RS-232/485 communication, each drive (or device) must be uniquely identified. One servo drive only can set one address. If the address is duplicated, there will be a communication fault. This address is an absolute address which represents the servo drive on a RS-232/485 network. Please note: 1. When the address of host (external) controller is set to 0xFF, it is with auto-respond function. Then, the servo drive will receive from and respond to host (external) controller both no matter the address is matching or not. However, the parameter P3-00 cannot be set to 0xFF. P3-01 BRT Transmission Speed Communication Address: 0302H 0303H Related Section: Section 8.2
Operation Keypad / Software Interface: Default: 0x0033 Control ALL Mode: Unit: bps Range: 0x0000 ~ 0x0055 Data Size: 16-bit Display Hexadecimal Format:
7-79
ASDA-B2
Settings: This parameter is used to set the baud rate and data transmission speed of the communications. 0 COM Port Range Settings: 0: Baud rate 4800 (data transmission speed: bits / second) 1: Baud rate 9600 (data transmission speed: bits / second) 2: Baud rate 19200 (data transmission speed: bits / second) 3: Baud rate 38400 (data transmission speed: bits / second) 4: Baud rate 57600 (data transmission speed: bits / second) 5: Baud rate 115200 (data transmission speed: bits / second) P3-02 PTL Communication Protocol Communication Address: 0304H 0305H Related Section: Section 8.2 0 Z 0 Y RS-485 0~5 X RS-232 0~5
Operation Keypad / Software Interface: Default: 0x0066 Control ALL Mode: Unit: N/A Range: 0x0000 ~ 0x0088 Data Size: 16-bit Display Hexadecimal Format: Settings:
This parameter is used to set the communication protocol. The alphanumeric characters represent the following: 7 or 8 is the number of data bits; N, E or O refers to the parity bit, Non, Even or Odd; the 1 or 2 is the numbers of stop bits. 0 COM Port Range 0 Z 0 Y RS-485 0~8 X RS-232 0~8
0: Modbus ASCII mode, <7,N,2> 1: Modbus ASCII mode, <7,E,1> 2: Modbus ASCII mode, <7,O,1> 3: Modbus ASCII mode, <8,N,2> 4: Modbus ASCII mode, <8,E,1> 5: Modbus ASCII mode, <8,O,1> 6: Modbus RTU mode, <8,N,2> 7: Modbus RTU mode, <8,E,1> 8: Modbus RTU mode, <8,O,1>
7-80
ASDA-B2
P3-03
FLT
Operation Keypad / Software Interface: Default: 0 Control ALL Mode: Unit: N/A Range: 0 ~ 1 Data Size: 16-bit Display Hexadecimal Format: Settings:
0: Display fault and continue operating 1: Display fault and decelerate to stop operating This parameter is used to determine the operating sequence once a communication fault has been detected. If '1' is selected, the drive will stop operating upon detection the communication fault. The mode of stopping is set by parameter P1-32. P3-04 CWD Communication Time Out Detection Communication Address: 0308H 0309H Related Section: Section 8.2
Operation Keypad / Software Interface: Default: 0 Control ALL Mode: Unit: sec Range: 0 ~ 20 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to set the maximum permissible time before detecting a fault due to communication time out. When P3-04 is set to a value over than 0, it indicates this parameter is enabled. However, if not communicating with the servo in this period of time, the servo drive will assume the communication has failed and show the communication error fault message. When P3-04 is set to 0, this parameter is disabled.
7-81
ASDA-B2
P3-05
CMM
Operation Keypad / Software Interface: Default: 1 Control ALL Mode: Unit: N/A Range: 0x00 ~ 0x01 Data Size: 16-bit Display Hexadecimal Format: Settings:
RS-232 Communication interface selection 0: RS-232 via Modbus communication 1: RS-232 upon ASDA-Soft software P3-06 SDI Digital Input Communication Function Communication Address: 030CH 030DH Related Section: Section 8.2
Operation Keypad / Software Interface: Default: 0 Control ALL Mode: Unit: N/A Range: 0x0000 ~ 0x1FFF Data Size: 16-bit Display Hexadecimal Format: Settings:
The setting of this parameter determines how the Digital Inputs (DI) accept commands and signals. Bit0 ~ Bit 8 corresponds with DI1 ~ DI9. The least significant bit (Bit0) shows DI1 status and the most significant bit (Bit7) shows DI8 status. Bit settings: 0: Digital input is controlled by external command (via CN1) 1: Digital input is controlled by parameter P4-07 For the settings of DI1 ~ DI9, please refer to P2-10 ~ P2-17 and P2-36. This parameter P3-06 also works in conjunction with the parameter P4-07 which has several functions. Please see section 8.2 for details.
7-82
ASDA-B2
P3-07
CDT
Operation Keypad / Software Interface: Default: 0 Control ALL Mode: Unit: 1ms Range: 0 ~ 1000 Data Size: 16-bit Display Decimal Format: Settings:
This parameter is used to delay the communication time that servo drive responds to host controller (external controller). P3-08 MNS Monitor Mode Address: 0310H 0311H Related Section: Section 8.2
Operation Keypad / Software Communication Interface: Default: 0000 Control ALL Mode: Unit: N/A Range: refer to the description of Settings Data Size: 16-bit Display Hexadecimal Format: Settings:
This parameter is used to monitor the data of the servo drive via communication. The monitor data can be displayed on PC upon the data scope function provided by ASDA-Soft software. Word Function Range 0 0 0 Low High Monitor mode 0~3
H: Monitor mode, the value must be within the range from 0 through 3. 0: Disabled, i.e. disable monitor function. 1: Reserved. 2: High-speed monitor mode. The sampling time is 2000 times per second and 4 channels can be monitored. 3: High-speed monitor mode. The sampling time is 4000 times per second and 2 channels can be monitored.
7-83
ASDA-B2
Reserved (Do Not Use) Reserved (Do Not Use) Reserved (Do Not Use)
7-84
ASDA-B2
Group 4: P4-xx Diagnosis Parameters P4-00 ASH1 Fault Record (N) Communication Address: 0400H 0401H Related Section: Section 4.4.1
Operation Keypad / Software Interface: Default: 0 Control ALL Mode: Unit: N/A Range: N/A Data Size: 32-bit Display Hexadecimal Format: Settings:
This parameter is used to set the most recent fault record. Display of Low Word: LXXXX: It indicates the fault code, i.e. alarm code Display of High Word: hYYYY: Reserved. P4-01 ASH2 Fault Record (N-1) Communication Address: 0402H 0403H Related Section: Section 4.4.1
Operation Keypad / Software Interface: Default: 0 Control ALL Mode: Unit: N/A Range: N/A Data Size: 32-bit Display Hexadecimal Format: Settings:
This parameter is used to set the second most recent fault record. Display of Low Word: LXXXX: It indicates the fault code, i.e. alarm code. Display of High Word: hYYYY: It indicates the CANopen error code. P4-02 ASH3 Fault Record (N-2) Communication Address: 0404H 0405H Related Section: Section 4.4.1
Operation Keypad / Software Interface: Default: 0 Control ALL Mode: Unit: N/A Range: N/A Data Size: 32-bit Display Hexadecimal Format: Settings:
This parameter is used to set the third most recent fault record.
7-85
ASDA-B2
Display of Low Word: LXXXX: It indicates the fault code, i.e. alarm code. Display of High Word: hYYYY: It indicates the CANopen error code. P4-03 ASH4 Fault Record (N-3) Communication Address: 0406H 0407H Related Section: Section 4.4.1
Operation Keypad / Software Interface: Default: 0 Control ALL Mode: Unit: N/A Range: N/A Data Size: 32-bit Display Hexadecimal Format: Settings:
This parameter is used to set the fourth most recent fault record. Display of Low Word: LXXXX: It indicates the fault code, i.e. alarm code. Display of High Word: hYYYY: It indicates the CANopen error code. P4-04 ASH5 Fault Record (N-4) Communication Address: 0408H 0409H Related Section: Section 4.4.1
Operation Keypad / Software Interface: Default: 0 Control ALL Mode: Unit: N/A Range: N/A Data Size: 32-bit Display Hexadecimal Format: Settings:
This parameter is used to set the fifth most recent fault record. Display of Low Word: LXXXX: It indicates the fault code, i.e. alarm code. Display of High Word: hYYYY: It indicates the CANopen error code. P4-05 JOG JOG Operation Communication Address: 040AH 040BH Related Section: Section 4.4.2
Operation Keypad / Software Interface: Default: 20 Control ALL Mode: Unit: r/min Range: 0 ~ 5000 Data Size: 16-bit Display Decimal Format:
7-86
ASDA-B2
Settings: JOG operation command: 1. Operation Test (1) Press the SET key to display the JOG speed. (The default value is 20 r/min). (2) Press the UP or DOWN arrow keys to increase or decrease the desired JOG speed. (This also can be undertaken by using the SHIFT key to move the cursor to the desired unit column (the effected number will flash) then changed using the UP and DOWN arrow keys). (3) Press the SET when the desired JOG speed is displayed. The Servo Drive will display "JOG". (4) Press the UP or DOWN arrow keys to jog the motor either P(CCW) or N(CW) direction. The motor will only rotation while the arrow key is activated. (5) To change JOG speed again, press the MODE key. The servo Drive will display "P4 - 05". Press the SET key and the JOG speed will displayed again. Refer back to #(2) and #(3) to change speed. (6) In JOG operation mode, if any fault occurs, the motor will stop running. The maximum JOG speed is the rated speed of the servo motor. 2. DI Signal Control Set the value of DI signal as JOGU and JOGD (refer to Table 7.A). Users can perform JOG run forward and run reverse control. 3. Communication Control To perform a JOG Operation via communication command, use communication addresses 040AH and 040BH. (1) Enter 1 ~ 5000 for the desired JOG speed (2) Enter 4998 to JOG in the P(CCW) direction (3) Enter 4999 to JOG in the N(CW) direction (4) Enter 0 to stop the JOG operation Please note that when using communication control, please set P2-30 to 5 to avoid that there are excessive writes to the system flash memory. P4-06 FOT Force Output Contact Control Communication Address: 040CH 040DH Related Section: Section 4.4.3
Operation Keypad / Software Interface: Default: 0 Control ALL Mode: Unit: N/A Range: 0 ~ 0xFF Data Size: 16-bit Display Hexadecimal Format: Settings:
The function of Digital Outout (DO) is determined by the DO setting value. The user can set DO setting value (0x30 ~ 0x3F) via communication and then write the values into P4-06 to complete the settings.
Revision January 2012
7-87
ASDA-B2
Bit00 corresponds with DO setting value 0x30 Bit01 corresponds with DO setting value 0x31 Bit02 corresponds with DO setting value 0x32 Bit03 corresponds with DO setting value 0x33 Bit04 corresponds with DO setting value 0x34 Bit05 corresponds with DO setting value 0x35 Bit06 corresponds with DO setting value 0x36 Bit07 corresponds with DO setting value 0x37 Bit08 corresponds with DO setting value 0x38 Bit09 corresponds with DO setting value 0x39 Bit10 corresponds with DO setting value 0x3A Bit11 corresponds with DO setting value 0x3B Bit12 corresponds with DO setting value 0x3C Bit13 corresponds with DO setting value 0x3D Bit14 corresponds with DO setting value 0x3E Bit15 corresponds with DO setting value 0x3F For example: When P2-18 is set to 0x0130, it indicates that the state of DO1 is the Bit00 state of P4-06. This parameter can also be used to force the state of DO signal. Please refer to P2-18 ~ P2-22 to assign the functions of digital outouts (DO signals) and section 4.4.3 for the Force Outputs Operation. P4-07 ITST Input Status Communication Address: 040CH 040DH Related Section: Section 4.4.4 Section 8.2
Operation Keypad / Software Interface: Default: 0 Control ALL Mode: Unit: N/A Range: 0 ~ 01FF Data Size: 16-bit Display Hexadecimal Format: Settings:
The control of digital inputs can be determined by the external terminals (DI1 ~ DI9) or by the internal software digital inputs SDI1 ~ SDI9 (corresponds to Bit0 ~ Bit8 of P1-47) via communication (upon software). Please refer to P3-06 and section 8.2 for the setting method.
P3-06 External DIs Internal DIs Read or Write Final DI Status
7-88
ASDA-B2
Read P4-07: Display the final status of DI input signal. Write P4-07: Write the status of software digital inputs SDI1 ~ SDI9 (No matter the servo drive is controller through digital keypad or communication control, the function of this parameter is the same.) For example: External Control: Display the final status of DI input signal When the read value of P4-07 is 0x0011, it indicates that DI1 and DI5 are ON. Communication Control (Internal DIs): Read the status of input signal (upon software). For example: When the write value of P4-07 is 0x0011, it indicates that software digital inputs SDI1 and SDI5 are ON. Bit0 ~ Bit8 corresponds with DI1 ~ DI9. For the settings of DI1 ~ DI9, please refer to P2-10 ~ P2-17 and P2-36. P4-08 PKEY Digital Keypad Input of Servo Drive Communication Address: 0410H 0411H Related Section: N/A
Operation Keypad / Software Interface: Default: N/A Control ALL Mode: Unit: N/A Range: Read only Data Size: 16-bit Display Hexadecimal Format: Settings:
This parameter is used to check if MODE, UP, DOWN, SHIFT, and SET keys on the drive keypad being pressed or not. It is used to examine if these five keys work normally via communication during production. P4-09 MOT Output Status Communication Address: 0412H 0413H Related Section: Section 4.4.5
Operation Keypad / Software Interface: Default: N/A Control ALL Mode: Unit: N/A Range: 0 ~ 0x1F Data Size: 16-bit Display Hexadecimal Format: Settings:
There is no difference when reading DO output signal via the drive keypad or the communication. For the status of DO output signal, please refer to P2-18 ~ P2-22.
7-89
ASDA-B2
P4-10
CEN
Operation Keypad / Software Interface: Default: 0 Control ALL Mode: Unit: N/A Range: 0 ~ 6 Data Size: 16-bit Display Decimal Format: Settings: 0: Reserved
1: Execute analog speed input drift adjustment 2: Execute analog torque input drift adjustment 3: Execute current detector (V phase) drift adjustment 4: Execute current detector (W phase) drift adjustment 5: Execute drift adjustment of the above 1~4 6: Execute IGBT NTC calibration Please note: 1. This adjustment function is enabled after parameter P2-08 is set to 20. 2. When executing any adjustment, the external wiring connected to analog speed or torque must be removed and the servo system should be off (Servo off). P4-11 SOF1 Analog Speed Input Drift Adjustment 1 Communication Address: 0416H 0417H Related Section: N/A
Operation Keypad / Software Interface: Default: Factory setting Control ALL Mode: Unit: N/A Range: 0 ~ 32767 Data Size: 16-bit Display Decimal Format: Settings:
The adjustment functions from P4-11 through P4-19 are enabled after parameter P2-08 is set to 22. Although these parameters allow the users to execute manual adjustment, we still do not recommend the users to change the default setting value of these parameters (P4-11 ~ P4-19) manually. Please note that when P2-08 is set to 10, the users cannot reset this parameter.
7-90
ASDA-B2
P4-12
SOF2
Operation Keypad / Software Interface: Default: Factory setting Control ALL Mode: Unit: N/A Range: 0 ~ 32767 Data Size: 16-bit Display Decimal Format: Settings: Refer to P4-11 for explanation.
Please note that when P2-08 is set to 10, the users cannot reset this parameter. P4-13 TOF1 Analog Torque Drift Adjustment 1 Communication Address: 041AH 041BH Related Section: N/A
Operation Keypad / Software Interface: Default: Factory setting Control ALL Mode: Unit: N/A Range: 0 ~ 32767 Data Size: 16-bit Display Decimal Format: Settings: Refer to P4-11 for explanation.
Please note that when P2-08 is set to 10, the users cannot reset this parameter. P4-14 TOF2 Analog Torque Drift Adjustment 2 Communication Address: 041CH 041DH Related Section: N/A
Operation Keypad / Software Interface: Default: Factory setting Control ALL Mode: Unit: N/A Range: 0 ~ 32767 Data Size: 16-bit Display Decimal Format: Settings: Refer to P4-11 for explanation.
Please note that when P2-08 is set to 10, the users cannot reset this parameter.
7-91
ASDA-B2
P4-15
COF1
Operation Keypad / Software Interface: Default: Factory setting Control ALL Mode: Unit: N/A Range: 0 ~ 32767 Data Size: 16-bit Display Decimal Format: Settings: Refer to P4-11 for explanation.
Please note that when P2-08 is set to 10, the users cannot reset this parameter. P4-16 COF2 Current Detector Drift Adjustment (V2 phase) Communication Address: 0420H 0421H Related Section: N/A
Operation Keypad / Software Interface: Default: Factory setting Control ALL Mode: Unit: N/A Range: 0 ~ 32767 Data Size: 16-bit Display Decimal Format: Settings: Refer to P4-11 for explanation.
Please note that when P2-08 is set to 10, the users cannot reset this parameter. P4-17 COF3 Current Detector Drift Adjustment (W1 phase) Communication Address: 0422H 0423H Related Section: N/A
Operation Keypad / Software Interface: Default: Factory setting Control ALL Mode: Unit: N/A Range: 0 ~ 32767 Data Size: 16-bit Display Decimal Format: Settings: Refer to P4-11 for explanation.
Please note that when P2-08 is set to 10, the users cannot reset this parameter.
7-92
ASDA-B2
P4-18
COF4
Operation Keypad / Software Interface: Default: Factory setting Control ALL Mode: Unit: N/A Range: 0 ~ 32767 Data Size: 16-bit Display Decimal Format: Settings: Refer to P4-11 for explanation.
Please note that when P2-08 is set to 10, the users cannot reset this parameter. P4-19 TIGB IGBT NTC Calibration Communication Address: 0426H 0427H Related Section: N/A
Operation Keypad / Software Interface: Default: Factory setting Control ALL Mode: Unit: N/A Range: 1 ~ 3 Data Size: 16-bit Display Decimal Format: Settings: Refer to P4-11 for explanation.
When executing this auto adjustment, please ensure to cool the servo drive to o 25 C. P4-20 DOF1 Analog Monitor Output Drift Adjustment (MON1) Communication Address: 0428H 0429H Related Section: Section 6.4.4
Operation Keypad / Software Interface: Default: Factory setting Control ALL Mode: Unit: mV Range: -800 ~ 800 Data Size: 16-bit Display Decimal Format: Settings:
Please note that when P2-08 is set to 10, the users cannot reset this parameter.
7-93
ASDA-B2
P4-21
DOF2
Operation Keypad / Software Interface: Default: 0 Control ALL Mode: Unit: mV Range: -800 ~ 800 Data Size: 16-bit Display Decimal Format: Settings:
Please note that when P2-08 is set to 10, the users cannot reset this parameter. P4-22 SAO Analog Speed Input Offset Communication Address: 042CH 042DH Related Section: N/A
Operation Keypad / Software Interface: Default: 0 Control S Mode: Unit: mV Range: -5000 ~ 5000 Data Size: 16-bit Display Decimal Format: Settings:
In speed mode, the users can use this parameter to add an offset value to analog speed input. P4-23 TAO Analog Torque Input Offset Communication Address: 042EH 042FH Related Section: N/A
Operation Keypad / Software Interface: Default: 0 Control T Mode: Unit: mV Range: -5000 ~ 5000 Data Size: 16-bit Display Decimal Format: Settings:
In speed mode, the users can use this parameter to add an offset value to analog speed input.
7-94
ASDA-B2
P4-24
LVL
Operation Keypad / Software Interface: Default: 160 Control ALL Mode: Unit: V (rms) Range: 140 ~ 190 Data Size: 16-bit Display Decimal Format: Settings:
When DC Bus voltage is lower than the value of P4-24 x 2 , the fault, Undervoltage will occur.
7-95
ASDA-B2
Table 7.A
Setting value: 0x01 DI Name DI Function Description Servo On. When this DI is activated, it indicates the servo drive is enabled. Trigger Method Level Triggered Control Mode All
SON
Setting value: 0x02 DI Name DI Function Description A number of Faults (Alarms) can be cleared by activating ARST. Please see table 10-3 for applicable faults that can ARST be cleared with the ARST command. However, please investigate Fault or Alarm if it does not clear or the fault description warrants closer inspection of the drive system. Setting value: 0x03 DI Name DI Function Description Gain switching in speed and position mode. When GAINUP GAINUP is activated (P2-27 is set to 1), the gain is switched to the gain multiplied by gain switching rate. Setting value: 0x04 DI Name DI Function Description When CCLR is activated, the setting parameter P2-50 CCLR Pulse Clear Mode is executed. 0: After CCLR is activated (ON), the position accumulated pulse number will be cleared continuously. Trigger Method Rising-edge Triggered, Level Triggered PT Contro l Mode Trigger Method Level Triggered Control Mode Rising-edge Triggered All Trigger Method Control Mode
PT S
7-96
ASDA-B2
Setting value: 0x05 DI Name DI Function Description When this signal is On and the motor speed value is lower than the setting value of P1-38, it is used to lock the motor in the instant position while ZCLAMP is On.
Speed Command Setting value of P1-38 (Zero speed)
Trigger Method
Contro l Mode
ZCLAMP
Level Triggered
OFF
ON
Time
Setting value: 0x06 DI Name DI Function Description Command input reverse control. When the drive is in the CMDINV Position, Speed and Torque mode, and CMDINV is activated, the motor is in reverse rotation. Setting value: 0x07 DI Name Reserved Setting value: 0x09 DI Name DI Function Description Torque limit enabled. When the drive is in speed and TRQLM position mode, and TRQLM is activated, it indicates the torque limit command is valid. The torque limit command source is internal parameter or analog voltage. Level Triggered PT, S Trigger Method Control Mode DI Function Description Trigger Method Control Mode Trigger Method Level Triggered Control Mode
S, T
7-97
ASDA-B2
Setting value: 0x10 DI Name DI Function Description Speed limit enabled. When the drive is in torque mode SPDLM and SPDLM is activated, it indicates the speed limit command is valid. The speed limit command source is internal parameter or analog voltage. Setting value: 0x14 ~ 0x15 DI Name DI Function Description Trigger Method Control Mode Level Triggered T Trigger Method Control Mode
Speed command selection 0 ~ 1 (Command S1 ~ S4) DI signal of Command Command CN1 Content Range No. Source SPD1 SPD0 Voltage External between +/-10 V S analog V-REF and command SPD0 GND S1 OFF OFF Speed SPD1 Sz None command 0 is 0 S2 OFF ON P1-09 -60000 S3 ON OFF P1-10 Internal ~ parameter +60000 S4 ON ON P1-11 r/min Mode
Level Triggered
Setting value: 0x16 ~ 0x17 DI Name DI Function Description Trigger Method Control Mode
Torque command selection 0 ~ 1 (Command T1 ~ T4) DI signal of Command Command CN1 Content Range No. Source TCM1 TCM0 Voltage Analog between T +/-10 V command V-REF and TCM0 GND T1 OFF OFF TCM1 Torque Tz None command 0 is 0 T2 OFF ON P1-12 Internal -300 ~ T3 ON OFF P1-13 parameter +300 % T4 ON ON P1-14 Mode
Level Triggered
7-98
ASDA-B2
Setting value: 0x18 DI Name DI Function Description Speed / Position mode switching. OFF: Speed mode, ON: Position mode Trigger Method Level Triggered Control Mode P, S
S-P
Setting value: 0x19 DI Name DI Function Description Speed / Torque mode switching. OFF: Speed mode, ON: Torque mode Trigger Method Level Triggered Control Mode S, T
S-T
Setting value: 0x20 DI Name DI Function Description Torque / Position mode switching. OFF: Torque mode, ON: Position mode Trigger Method Level Triggered Control Mode P, T
T-P
Setting value: 0x21 DI Name DI Function Description Emergency stop. It should be contact b and normally ON or a fault (AL013) will display. Trigger Method Level Triggered Control Mode All
EMGS
Setting value: 0x22 DI Name DI Function Description Reverse inhibit limit. It should be contact b and normally ON or a fault (AL014) will display. Trigger Method Level Triggered Control Mode All
NL(CWL)
Setting value: 0x23 DI Name DI Function Description Forward inhibit limit. It should be contact b and normally ON or a fault (AL015) will display. Trigger Method Level Triggered Control Mode All
PL(CCWL)
7-99
ASDA-B2
Setting value: 0x25 DI Name DI Function Description Torque limit - Reverse operation (Torque limit function is valid only when P1-02 is enabled) Trigger Method Level Triggered Control Mode PT, S
TLLM
Setting value: 0x26 DI Name DI Function Description Torque limit - Forward operation (Torque limit function is valid only when P1-02 is enabled) Trigger Method Level Triggered Control Mode PT, S
TRLM
Setting value: 0x37 DI Name DI Function Description Forward JOG input. When JOGU is activated, the motor will JOG in forward direction. [see P4-05] Trigger Method Level Triggered Control Mode All
JOGU
Setting value: 0x38 DI Name DI Function Description Reverse JOG input. When JOGD is activated, the motor will JOG in reverse direction. [see P4-05] Trigger Method Level Triggered Control Mode All
JOGD
Setting value: 0x43, 0x44 DI Name DI Function Description Electronic gear ratio (Numerator) selection 0 ~ 1 [see P2-60 ~ P2-62] GNUM0 GNUM1 Level Triggered Trigger Method Control Mode
PT
7-100
ASDA-B2
Setting value: 0x45 DI Name DI Function Description Pulse inhibit input. When the drive is in position mode, if INHP INHP is activated, the external pulse input command is not valid. Setting value: 0x48 DI Name DI Function Description Torque command source. Please refer to the settings of
P2-66 Bit0.
Control Mode
PT
Control Mode T
TQP
Setting value: 0x49 DI Name DI Function Description Torque command source. Please refer to the settings of
P2-66 Bit0.
Control Mode T
TQN
NOTE
1) 11 ~ 17: Single control mode, 18 ~ 20: Dual control mode 2) When P2-10 to P2-17 and P2-36 is set to 0, it indicates input function is disabled.
7-101
ASDA-B2
Table 7.B Output Function Definition Setting value: 0x01 DO Name DO Function Description Servo ready. SRDY is activated when the servo drive is SRDY ready to run. All fault and alarm conditions, if present, have been cleared. Setting value: 0x02 DO Name DO Function Description SON is activated when control power is applied the servo drive. The drive may or may not be ready to run as a fault / alarm condition may exist. SON Servo ON (SON) is "ON" with control power applied to the servo drive, there may be a fault condition or not. The servo is not ready to run. Servo ready (SRDY) is "ON" where the servo is ready to run, NO fault / alarm exists. Setting value: 0x03 DO Name DO Function Description ZSPD is activated when the drive senses the motor is equal to or below the Zero Speed Range setting as defined in parameter P1-38. ZSPD For Example, at factory default ZSPD will be activated when the drive detects the motor rotating at speed at or below 10 r/min, ZSPD will remain activated until the motor speed increases above 10 r/min. Setting value: 0x04 DO Name DO Function Description TSPD is activated once the drive has detected the motor TSPD has reached the Target Rotation Speed setting as defined in parameter P1-39. TSPD will remain activated until the motor speed drops below the Target Rotation Speed. Level Triggered All Trigger Method Control Mode Level Triggered All Trigger Method Control Mode Level Triggered All Trigger Method Control Mode Trigger Method Level Triggered Control Mode
All
7-102
ASDA-B2
Setting value: 0x05 DO Name DO Function Description When the drive is in PT mode, TPOS will be activated when TPOS the position error is equal and below the setting value of P1-54. Setting value: 0x06 DO Name DO Function Description TQL is activated when the drive has detected that the TQL motor has reached the torques limits set by either the parameters P1-12 ~ P1-14 of via an external analog voltage. Setting value: 0x07 DO Name DO Function Description ALRM is activated when the drive has detected a fault condition. (However, when Reverse limit error, Forward ALRM limit error, Emergency stop, Serial communication error, and Undervoltage these fault occur, WARN is activated first.) Setting value: 0x08 DO Name DO Function Description Electromagnetic brake control. BRKR is activated (Actuation of motor brake). (Please refer to parameters P1-42 ~ P1-43) BRKR Level Triggered Trigger Method Control Mode Level Triggered All Trigger Method Control Mode Level Triggered Trigger Method Control Mode All, except T, Tz Trigger Method Level Triggered Control Mode
PT
All
7-103
ASDA-B2
Setting value: 0x10 DO Name DO Function Description Output overload warning. OLW is activated when the servo drive has detected that the motor has reached the output overload time set by parameter P1-56. tOL = Permissible Time for Overload x setting value of P1-56 When overload accumulated time (continuously overload time) exceeds the value of tOL, the overload warning signal will output, i.e. DO signal, OLW will be ON. However, if the accumulated overload time (continuous overload time) exceeds the permissible time for overload, the overload alarm (AL006) will occur. For example: If the setting value of parameter P1-56 (Output Overload OLW Warning Time) is 60%, when the permissible time for overload exceeds 8 seconds at 200% rated output, the overload fault (AL006) will be detected and shown on the LED display. At this time, tOL = 8 x 60% = 4.8 seconds Result: When the drive output is at 200% rated output and the drive is continuously overloaded for 4.8 seconds, the overload warning signal will be ON (DO code is 0x10, i.e. DO signal OLW will be activated). If the drive is continuously overloaded for 8 seconds, the overload alarm will be detected and shown on the LED display (AL006). Then, Servo Fault signal will be ON (DO signal ALRM will be activated). Setting value: 0x11 DO Name DO Function Description Servo warning activated. WARN is activated when the drive WARN has detected Reverse limit error. Forward limit error, Emergency stop, Serial communication error, and Undervoltage these fault conditions. Level Triggered All Trigger Method Control Mode Level Triggered All Trigger Method Control Mode
7-104
ASDA-B2
Setting value: 0x13 DO Name SNL (SCWL) DO Function Description Reverse software limit. SNL is activated when the servo drive has detected that reverse software limit is reached. Trigger Method Level Triggered Control Mode All
Setting value: 0x14 DO Name SPL (SCCWL) DO Function Description Forward software limit. SPL is activated when the servo drive has detected that forward software limit is reached. Trigger Method Level Triggered Control Mode All
Setting value: 0x19 DO Name DO Function Description Speed reached output. SP_OK will be activated when the Trigger Method Level Control Mode S, Sz
SP_OK
speed error is equal and below the setting value of P1-47. Triggered
Setting value: 0x30 DO Name DO Function Description Trigger Method Level Triggered Control Mode All
SDO_0
Setting value: 0x31 DO Name DO Function Description Trigger Method Level Triggered Control Mode All
SDO_1
Setting value: 0x32 DO Name DO Function Description Trigger Method Level Triggered Control Mode All
SDO_2
7-105
ASDA-B2
Setting value: 0x33 DO Name DO Function Description Trigger Method Level Triggered Control Mode All
SDO_3
Setting value: 0x34 DO Name DO Function Description Trigger Method Level Triggered Control Mode All
SDO_4
Setting value: 0x35 DO Name DO Function Description Trigger Method Level Triggered Control Mode All
SDO_5
Setting value: 0x36 DO Name DO Function Description Trigger Method Level Triggered Control Mode All
SDO_6
Setting value: 0x37 DO Name DO Function Description Trigger Method Level Triggered Control Mode All
SDO_7
Setting value: 0x38 DO Name DO Function Description Trigger Method Level Triggered Control Mode All
SDO_8
7-106
ASDA-B2
Setting value: 0x39 DO Name DO Function Description Trigger Method Level Triggered Control Mode All
SDO_9
Setting value: 0x3A DO Name DO Function Description Trigger Method Level Triggered Control Mode All
SDO_A
Setting value: 0x3B DO Name DO Function Description Trigger Method Level Triggered Control Mode All
SDO_B
Setting value: 0x3C DO Name DO Function Description Trigger Method Level Triggered Control Mode All
SDO_C
Setting value: 0x3D DO Name DO Function Description Trigger Method Level Triggered Control Mode All
SDO_D
Setting value: 0x3E DO Name DO Function Description Trigger Method Level Triggered Control Mode All
SDO_E
7-107
ASDA-B2
Setting value: 0x3F DO Name DO Function Description Trigger Method Level Triggered Control Mode All
SDO_F
NOTE
1) When P2-18 to P2-22 and P2-37 is set to 0, it indicates output function is disabled.
7-108
Connection
NOTE
1) Recommended maximum cable length is 15m (50ft.). Please note, RFI / EME noise should be kept to a minimum, communication cable should kept apart from high voltage wires. If a transmission speed of 38400 bps or greater is required, the maximum length of the communication cable is 3m (9.84ft.) which will ensure the correct and desired baud rate. 2) The number shown in the pervious figure indicates the terminal number of each connector.
8-1
ASDA-B2
RS-485
Connection
Servo 1
5 6
485(+) 485(-)
Servo 2
5 6
NOTE
1) The maximum cable length is 100m (39.37inches) when the servo drive is installed in a location where there are only a few interferences. Please note, RFI / EME noise should be kept to a minimum, communication cable should kept apart from high voltage wires. If a transmission speed of 38400bps or greater is required, the maximum length of the communication cable is 15m (50ft.) which will ensure the correct and desired baud rate. 2) The number shown in the pervious figure indicates the terminal number of each connector. 3) The power supply should provide a +12V and higher DC voltage. 4) Please use a REPEATER if more than 32 synchronous axes are required. 5) For the terminal identification of CN3, please refer to Section 3.5.
8-2
ASDA-B2
Operation Keypad / Software Interface: Default: 0x7F Control ALL Mode: Unit: N/A Range: 0x01 ~ 0x7F Data Size: 16-bit Display Hexadecimal Format:
Settings: This parameter is used to set the communication slave address in hexadecimal format. Display Range 0 0 Y 0~7 X 0~F
X: Axis number which indicates the value must be within the range from 0 through F. Y: Group number which indicates the value must be within the range from 0 to through 7 When using RS-232/485 communication, this parameter is used set the communication address in hexadecimal format. If the AC servo drive is controlled by RS-232/485 communication, each drive (or device) must be uniquely identified. One servo drive only can set one address. If the address is duplicated, there will be a communication fault. This address is an absolute address which represents the servo drive on a RS-232/485 network. Please note: 1. When the address of host (external) controller is set to 0xFF, it is with auto-respond function. Then, the servo drive will receive from and respond to host (external) controller both no matter the address is matching or not. However, the parameter P3-00 cannot be set to 0xFF.
8-3
ASDA-B2
P3-01
BRT
Operation Keypad / Software Interface: Default: 0x0033 Control ALL Mode: Unit: bps Range: 0x0000 ~ 0x0055 Data Size: 16-bit Display Hexadecimal Format:
Settings: This parameter is used to set the baud rate and data transmission speed of the communications. 0 COM Port Range Settings: 0: Baud rate 1: Baud rate 2: Baud rate 3: Baud rate 4: Baud rate 5: Baud rate 0 Z 0 Y RS-485 0~5 X RS-232 0~5
4800 (data transmission speed: bits / second) 9600 (data transmission speed: bits / second) 19200 (data transmission speed: bits / second) 38400 (data transmission speed: bits / second) 57600 (data transmission speed: bits / second) 115200 (data transmission speed: bits / second)
P3-02
PTL
Operation Keypad / Software Interface: Default: 0x0066 Control ALL Mode: Unit: N/A Range: 0x0000 ~ 0x0088 Data Size: 16-bit Display Hexadecimal Format:
8-4
ASDA-B2
Settings: This parameter is used to set the communication protocol. The alphanumeric characters represent the following: 7 or 8 is the number of data bits; N, E or O refers to the parity bit, Non, Even or Odd; the 1 or 2 is the numbers of stop bits. 0 COM Port Range 0: 1: 2: 3: 4: 5: 6: 7: 8: Modbus Modbus Modbus Modbus Modbus Modbus Modbus Modbus Modbus 0 Z 0 Y RS-485 0~8 X RS-232 0~8
ASCII mode, <7,N,2> ASCII mode, <7,E,1> ASCII mode, <7,O,1> ASCII mode, <8,N,2> ASCII mode, <8,E,1> ASCII mode, <8,O,1> RTU mode, <8,N,2> RTU mode, <8,E,1> RTU mode, <8,O,1>
P3-05
CMM
Operation Keypad / Software Interface: Default: 1 Control ALL Mode: Unit: N/A Range: 0x00 ~ 0x01 Data Size: 16-bit Display Hexadecimal Format:
Settings: RS-232 Communication interface selection 0: RS-232 via Modbus communication 1: RS-232 upon ASDA-Soft software
8-5
ASDA-B2
Code Description:
ASCII Mode: Each 8-bit data is the combination of two ASCII characters. For example, a 1-byte data: 64 Hex, shown as 64 in ASCII, consists of 6 (36Hex) and 4 (34Hex). The following table shows the available hexadecimal characters and their corresponding ASCII codes. Character ASCII code Character ASCII code RTU Mode: Each 8-bit data is the combination of two 4-bit hexadecimal characters. For example, a 1-byte data: 64 Hex. 0 30H 8 38H 1 31H 9 39H 2 32H A 41H 3 33H B 42H 4 34H C 43H 5 35H D 44H 6 36H E 45H 7 37H F 46H
Data Format:
10-bit character frame (For 7-bit character) 7N2 Start 0 1 3 2 bit
Stop bit
Stop bit
7E1
Start bit
3 7-data bits
Even parity
Stop bit
7O1
Start bit
Odd parity
Stop bit
8-6
ASDA-B2
8E1
Start bit
3 8-data bits
Even parity
Stop bit
8O1
Start bit
3 8-data bits
Odd parity
Stop bit
Communication Protocol:
ASCII Mode: Start Slave address Function DATA(n-1) . DATA(0) LRC End 1 End 0 LRC check sum: 1-byte consists of 2 ASCII codes End code 1: (0DH)(CR) End code 0: (0AH)(LF) Contents of data: n word = n x 2-byte consists of n x 4 ASCII codes, n10 Start character: (3AH) Communication address: 1-byte consists of 2 ASCII codes Function code: 1-byte consists of 2 ASCII codes
ASCII Mode: : character ADR (Communication Address) consists of 2 ASCII codes and it ends in CR (Carriage Return) and LF (Line Feed) CR (Carriage Return) is represented by ASCII number 13, and LF (Line Feed) is represented by ASCII number 10. There are communication address, function code, contents of data, LRC (Longitudinal Redundancy Check) between start and end characters.
8-7
ASDA-B2
RTU Mode: Start Slave address Function DATA(n-1) . DATA(0) CRC End 1 CRC check sum: 1-byte A silent interval of more than 10ms Contents of data: n word = n x 2-byte, n10 A silent interval of more than 10ms Communication address: 1-byte Function code: 1-byte
RTU Mode: A silent interval of more than 10ms RTU (Remote Terminal Unit) starts from a silent signal and ends at another silent signal. There are communication address, function code, contents of data, CRC (Cyclical Redundancy Check) between start and end characters. DATA (Data Characters) The format of data characters depends on the function code. The available command codes and examples for AC servo drive are described as follows: Example 1 Function code: 03H, read N words (multiple words). The maximum value of N is 10. For example, reading continuous 2 words from starting address 0200H of AC servo drive with address 01H. ASCII Mode: Command message: Start Slave address Function Starting data address : 0 1 0 3 0 2 0 0 0 0 0 2 F 8 (0DH)(CR) (0AH)(LF) Response message: Start Slave address Function Number of data (In Byte) Contents of starting data address 0200H Contents of second data address 0201H LRC Check End 1 End 0 : 0 1 0 3 0 4' 0 0 B 1 1 F 4 0 E 8 (0DH)(CR) (0AH)(LF)
Number of data
8-8
ASDA-B2
RTU Mode: Command message: Slave address Function Starting data address Number of data (In Word) CRC Check Low CRC Check High 01H 03H 02H (Upper bytes) 00H (Lower bytes) 00H 02H C5H (Lower bytes) B3H (Upper bytes) Response message: Slave address Function Number of data (In Byte) Contents of starting data address 0200H Contents of second data address 0201H CRC Check Low CRC Check High 01H 03H 04H 00H (Upper bytes) B1H (Lower bytes) 1FH (Upper bytes) 40H (Lower bytes) A3H (Lower bytes) D4H (Upper bytes)
Please note that a silent interval of more than 10ms is required before and after data transmission in RTU mode.
Example 2 Function code: 06H, write 1 word For example, writing 100 (0064H) to starting data address 0200H of ASDA-B2 series with address 01H. ASCII Mode: Command message: Start Slave address Function Starting data address : 0 1 0 6 0 2 0 0 0 0 6 4 9 3 (0DH)(CR) (0AH)(LF) Response message: Start Slave address Function Starting data address : 0 1 0 6 0 2' 0 0 0 0 6 4 9 3 (0DH)(CR) (0AH)(LF)
Content of data
Content of data
8-9
ASDA-B2
RTU Mode: Command message: Slave Address Function Starting data address Content of data CRC Check Low CRC Check High 01H 06H 02H (Upper bytes) 00H (Lower bytes) 00H (Upper bytes) 64H (Lower bytes) 89H (Lower bytes) 99H (Upper bytes) Response message: Slave Address Function Starting data address Content of data CRC Check Low CRC Check High 01H 06H 02H (Upper bytes) 00H (Lower bytes) 00H (Upper bytes) 64H (Lower bytes) 89H (Lower bytes) 99H (Upper bytes)
Please note that a silent interval of more than 10ms is required before and after data transmission in RTU mode. Example 3 Function code: 10H, write N words (multiple words). The maximum value of N is 10. For example, writing continuous 2 words, 0BB8H and 0000H from starting address 0112H and address 0113H. ASCII Mode: Command message: Start Slave Address Function : 0 1 1 0 0 Starting data address 1 1 2 0 Number of data (In Word) Number of data (In Byte) Content of 1st data 0 0 2 0 4 0 B B 8 0 0 0 0 Content of data Starting data address Response message: Start Slave Address Function : 0 1 1 0 0 1' 1 2 0 0 0 2 D A (0DH)(CR) (0AH)(LF)
8-10
ASDA-B2
1 3 (0DH)(CR) (0AH)(LF)
RTU Mode: Command message: Slave Address Function Starting data address Number of data (In Word) Number of data (In Byte) Content of 1st data Content of 2nd data CRC Check Low CRC Check High 01H 10H (Upper (Lower (Upper (Lower 04H 0BH (Upper bytes) B8H (Lower bytes) 00H (Upper bytes) 00H (Lower bytes) FCH (Lower bytes) EBH (Upper bytes) Response message: Slave Address Function Starting data address Content of data (In Word) CRC Check Low CRC Check High 01H 10H (Upper bytes) (Lower bytes) (Upper bytes) (Lower bytes) (Lower bytes) (Upper bytes)
Please note that a silent interval of more than 10ms is required before and after data transmission in RTU mode.
LRC (ASCII Mode): LRC (Longitudinal Redundancy Check) is calculated by summing up, module 256, the values of the bytes from ADR to last data character then calculating the hexadecimal representation of the 2s-complement negation of the sum. Example STX ADR CMD : 7 F 0 3 0 5 C 4 0 0 0 1 B 4
8-11
Number of data
LRC Check
ASDA-B2
End 1 End 0
(0DH)(CR) (0AH)(LF)
7FH + 03H + 05H + C4H + 00H + 01H = 14CH, the 2s complement negation of 4CH is B4H. Hence, we can know that LRC CHK is B,4.
CRC (RTU Mode): CRC (Cyclical Redundancy Check) is calculated by the following steps: Step 1: Load a 16-bit register (called CRC register) with FFFFH. Step 2: Exclusive OR the first 8-bit byte of the command message with the low order byte of the 16-bit CRC register, putting the result in the CRC register. Step 3: Extract and examine the LSB. If the LSB of CRC register is 0, shift the CRC register one bit to the right. If the LSB of CRC register is 1, shift the CRC register one bit to the right, then Exclusive OR the CRC register with the polynomial value A001H. Step 4: Repeat step 3 until eight shifts have been performed. When this is done, a complete 8bit byte will have been processed, then perform step 5. Step 5: Repeat step 2 to step 4 for the next 8-bit byte of the command message. Continue doing this until all bytes have been processed. The final contents of the CRC register are the CRC value.
NOTE
1) When transmitting the CRC value in the message, the upper and lower bytes of the CRC value must be swapped, i.e. the lower order byte will be transmitted first. 2) For example, reading 2 words from address 0101H of the AC servo drive with address 01H. The final content of the CRC register from ADR to last data character is 3794H, then the command message is shown as follows. What should be noticed is that 94H have to be transmitted before 37H. Command ADR CMD Starting data address Number of data (In Word) CRC Check Low CRC Check High Message 01H 03H 01H (Upper byte) 01H (Lower bytes) 00H (Upper bytes) 02H (Lower bytes) 94H (Lower bytes) 37H (Upper bytes)
8-12
ASDA-B2
End1, End0 (Communication End) ASCII Mode: In ASCII mode, (0DH) stands for character \r (carriage return) and (0AH) stands for character \n (new line), they indicate communication end.
RTU Mode: In RTU mode, a silent interval of more than 10ms indicates communication end.
CRC Program Example The following is an example of CRC generation using C language. The function takes two arguments: unsigned char* data; unsigned char length The function returns the CRC value as a type of unsigned integer. unsigned int crc_chk(unsigned char* data, unsigned char length) { int j; unsigned int reg_crc=0xFFFF; while( length-- ) { reg_crc^= *data++; for (j=0; j<8; j++ ) { if( reg_crc & 0x01 ) { /*LSB(bit 0 ) = 1 */ reg_crc = (reg_crc >> 1)^0xA001; } else { reg_crc = (reg_crc>>1); } } } return reg_crc; } PC communication program example: #include<stdio.h> #include<dos.h> #include<conio.h> #include<process.h> #define PORT 0x03F8 #define THR 0x0000 #define RDR 0x0000 /* the address of COM 1 */
8-13
ASDA-B2
#define BRDL 0x0000 #define IER 0x0001 #define BRDH 0x0001 #define LCR 0x0003 #define MCR 0x0004 #define LSR 0x0005 #define MSR 0x0006 unsigned char rdat[60]; /* read 2 data from address 0200H of ASD with address 1 */ unsigned char tdat[60]={:,0,1,0,3,0,2,0,0,0,0,0,2,F,8,\r,\n}; void main() { int I; outportb(PORT+MCR,0x08); outportb(PORT+IER,0x01); /* interrupt enable */ /* interrupt as data in */
outportb(PORT+LCR,( inportb(PORT+LCR) | 0x80 ) ); /* the BRDL/BRDH can be access as LCR.b7 == 1 */ outportb(PORT+BRDL,12); outportb(PORT+BRDH,0x00); outportb(PORT+LCR,0x06); /* set prorocol <7,E,1> = 1AH, <8,N,2> = 07H <8,O,1> = 0BH */ for( I = 0; I<=16; I++ ) { while( !(inportb(PORT+LSR) & 0x20) ); outportb(PORT+THR,tdat[I]); } I = 0; while( !kbhit() ) { if( inportb(PORT+LSR)&0x01 ) { /* b0==1, read data ready */ rdat[I++] = inportb(PORT+RDR); /* read data from RDR */ } } } /* wait until THR empty */ /* send data to THR */ <7,O,1> = 0AH <8,E,1> = 1BH
8-14
ASDA-B2
For a complete listing and description of all parameters, refer to Chapter 7. Communication write-in parameters for ASDA-B2 series are including: Group 0: All parameters except P0-00 ~ P0-01, P0-08 ~ P0-13 and P0-46 Group 1: P1-00 ~ P1-76 Group 2: P2-00 ~ P2-67 Group 3: P3-00 ~ P3-11 Group 4: All parameters except P4-00 ~ P4-04 and P4-08 ~ P4-09
NOTE
1) P3-01 After the new transmission speed is set, the next data will be written in new transmission speed. 2) P3-02 After the new communication protocol is set, the next data will be written in new communication protocol. 3) P4-05 4) P4-06 JOG control of servo motor. For the description, refer to Chapter 7. Force output contact control. This parameter is for the users to test if DO (Digit output) is normal. User can set 1, 2, 4, 8, 16, 32 to test DO1, DO2, DO3, DO4, DO5, DO6 respectively. After the test has been completed, please set this parameter to 0 to inform the drive that the test has been completed. 5) P4-10 Adjustment function selection. If the user desires to change the settings of this parameter, the user has to set the value of the parameter P2-08 to 20 (hexadecimal: 14H) first and then restart. After restarting, the settings of parameter P4-10 can become modified. 6) P4-11 ~ P4-21 These parameters are for offset adjustment. Do not change the factory default setting if not necessary. If the user desires to change the settings of these parameters, the user has to set the value of the parameter P2-08 to 22 (hexadecimal: 16H) first and then restart. After restarting, the settings of parameters P4-11 to P4-21 can become modified.
8-15
ASDA-B2
Communication read-out parameters for ASDA-B2 series are including: Group 0: P0-00 ~ P0-46 Group 1: P1-00 ~ P1-76 Group 2: P2-00 ~ P2-67 Group 3: P3-00 ~ P3-11 Group 4: P4-00 ~ P4-24
8-16
Chapter 9 Troubleshooting
If a fault is detected on the servo drive or motor a corresponding fault code will be shown on the drive's LED display. Fault codes can also be transmitted via communication, see P0-01 and P4-00 ~ P4-04 for display on controller or HMI.
9-1
Chapter 9 Troubleshooting
ASDA-B2
Fault Messages Display Fault Name IGBT temperature error Memory error Encoder output error Fault Description The temperature of IGBT is over high. EE-PROM write-in and read-out is in error. The encoder output exceeds the rated output frequency.
Serial communication RS232/485 communication is in error. error Serial communication RS232/485 communication time out. time out Reserve Input power phase loss Reserve One phase of the input power is loss.
To warn that the servo motor and drive is going to overload. This alarm will display before ALM06. When the servo motor reach the setting value of P1-56, the Pre-overload warning motor will send a warning to the drive. After the drive has detected the warning, the DO signal OLW will be activated and this fault message will display. Encoder initial magnetic field error Encoder internal error Encoder data error Motor internal error Motor internal error Motor internal error Motor protection error U,V,W, GND wiring error Motor temperature error Excessive encoder output error Motor temperature warning The magnetic field of the encoder U, V, W signal is in error. The internal memory of the encoder is in error. An internal counter error is detected. An encoder data error is detected for three times. The setting value of the encoder is in error. The encoder U, V, W signals are in error. The internal address of the encoder is in error. In order to protect the motor, this alarm will be activated when the setting value of P1-57 is reached after a period of time set by P1-58. The wiring connections of U, V, W (for servo motor output) and GND (for grounding) are in error. Motor is working under temperature over 105C (221F). The encoder output errors or output pulses exceed hardware tolerance. The temperature of motor is over 85C (185F). EE-PROM is not reset after the firmware version is upgraded. This fault can be cleared after setting P2-08 to 30 first, and then setting P2-08 to 28 next and restarting the ervo drive.
9-2
ASDA-B2
Chapter 9 Troubleshooting
NOTE
1) If there is any unknown fault code that is not listed on the above table, please inform the distributor or contact with Delta for assistance.
9-3
Chapter 9 Troubleshooting
ASDA-B2
9.2 Potential Cause and Corrective Actions Servo Drive Fault Messages
: Overcurrent Potential Cause Short-circuit at drive output (U, V, W) Checking Method Corrective Actions 1. Check the wiring connections between Repair the short-circuited and drive and motor. avoid metal conductor being exposed. 2. Check if the wire is short-circuited. Check if the wiring steps are all correct when connecting motor to drive. Heat sink overheated Follow the wiring steps in the user manual to reconnect wiring. Please contact your distributor for assistance or contact with Delta. Set the setting back to factory default setting and then reset and adjust the parameter setting again. 1. Ensure that input command frequency is stable (too much fluctuation). 2. Activate filter function.
IGBT error
: Overvoltage Potential Cause Checking Method Corrective Actions The main circuit voltage has Use voltmeter to check whether the input Use correct power supply or exceeded its voltage falls within the rated input stabilizing power. maximum allowable voltage. value. Input power error (Incorrect power input) Use voltmeter to check whether the input Use correct power supply or voltage is within the specified limit. stabilizing power.
: Undervoltage Potential Cause The main circuit voltage is below its minimum specified value. No input voltage at main circuit. Input power error (Incorrect power input) Checking Method Corrective Actions
Check whether the wiring of main circuit Reconfirm voltage wiring. input voltage is normal. Use voltmeter to check whether input voltage at main circuit is normal. Reconfirm power switch.
Use voltmeter to check whether the input Use correct power supply or serial stabilizing power. voltage is within the specified limit.
9-4
ASDA-B2
Chapter 9 Troubleshooting
: Motor error Potential Cause Encoder is loose. The type of the servo motor is incorrect. Checking Method Examine the Encoder connector. Corrective Actions Repair or replace the motor. Install the motor again. Encoder is damage. Check Encoder for the damage.
Check if the servo drive and servo motor Replace the motor. are not correctly matched for size (power rating).
: Regeneration error Potential Cause Regenerative resistor is not connected. Checking Method Check the wiring connection of regenerative resistor. Corrective Actions Reconnect regenerative resistor.
Please contact your distributor Regenerative switch Check if regenerative switch transistor is for assistance or contact with transistor fault short-circuited. Delta. Parameter setting is Confirm the parameter setting and in error specifications of regenerative resistor. : Overload Potential Cause The drive has exceeded its rated load during continuous operation. Checking Method Corrective Actions Increase motor capacity or reduce load. Adjust gain value of control circuit. Decrease Accel/Decel time setting. Correctly reset parameter again.
Check if there is mechanical vibration Control system parameter setting is incorrect. Accel/Decel time setting is too fast. The wiring of drive and encoder is in error.
: Overspeed Potential Cause Speed input command is not stable (too much fluctuation). Checking Method Use signal detector to detect if input signal is abnormal. Corrective Actions Ensure that input command frequency is stable (not fluctuate too much) and activate filter function (P1-06, P1-07 and P1-08). Correctly set over-speed parameter setting (P2-34).
Over-speed Check if over-speed parameter setting parameter setting is value is too low. defective.
9-5
Chapter 9 Troubleshooting
ASDA-B2
: Abnormal pulse control command Potential Cause Pulse command frequency is higher than rated input frequency. Checking Method Corrective Actions
Use pulse frequency detector to measure Correctly set the input pulse frequency. input frequency.
: Excessive deviation Potential Cause Checking Method Corrective Actions Increases the parameter setting value of P2-35. Correctly adjust gain value. Correctly adjust torque limit value. Reduce external applied load or re-estimate the motor capacity. Check the maximum deviation Maximum deviation parameter setting and observe the parameter setting is position error value when the motor is too small. running. Gain value is too small. Torque limit is too low. Check for proper gain value. Check torque limit value.
: Reserve : Encoder error (Position detector fault) Potential Cause Checking Method Corrective Actions 1. Check if all wiring is correct. The wiring of encoder 2. Check if the users conduct the Ensure all wiring is correct. is in error. wiring by the wiring information in the user manual. Encoder is loose Examine the encoder connector. Install the motor again. Conduct the wiring again. Repair or replace the motor. The wiring of encoder Check if all connections are tight. is defective. Encoder is damage Check the encoder for the damage.
: Adjustment error Potential Cause 1. The setting value of drift adjustment has 2. exceeded its maximum allowable value. Checking Method Remove CN1 wiring. Execute the drift adjustment again. (Set P2-08 to 20 first, and then set P4-10 to 5.) Corrective Actions If the error does not clear after executing the drift adjustment again, please contact your distributor for assistance or contact with Delta.
: Emergency stop activated Potential Cause Checking Method Corrective Actions Emergency stop switch Check if emergency stop switch is On Activate emergency stop switch. is activated. or Off.
9-6
ASDA-B2
Chapter 9 Troubleshooting
: Reverse (CWL) limit switch error Potential Cause Checking Method Corrective Actions Activate reverse limit switch. Modify parameter setting and re-estimate motor capacity. Reverse limit switch is Check if reverse limit switch is On or activated. Off. Servo system is not stable. Check the value of control parameter setting and load inertia.
: Forward (CCWL) limit switch error Potential Cause Checking Method Corrective Actions Activate forward limit switch. Modify parameter setting and re-estimate motor capacity. Forward limit switch is Check if forward limit switch is On or activated. Off. Servo system is not stable. Check the value of control parameter setting and load inertia.
: IGBT temperature error Potential Cause Checking Method Corrective Actions The drive has Check if there is overload or the motor Increase motor capacity or exceeded its rated current is too high. reduce load. load during continuous operation. Short-circuit at drive output. Check the drive input wiring. Ensure all wiring is correct.
: Memory error Potential Cause Checking Method Corrective Actions 1.If this fault occurs when power is applied to the Examine the parameter settings. drive, it indicates that the Please do the following steps: setting value of one 1.Press SHIFT key on the drive keypad, parameter has exceeded the and examine the parameter shown specified range. Correct the on LED display. setting value of the 2.If E320A is displayed (in parameter to clear the fault hexadecimal format), it indicates it is and restart the servo drive. parameter P2-10. Please examine the 2.If this fault occurs during parameter settings of P2-10. normal operation, it 3.If E3610 is displayed (in hexadecimal indicates that the error format), it indicates it is parameter occurs when writing data P6-16. Please examine the parameter into EE-PROM. Turn ARST (DI settings of P6-16. signal) ON to clear the fault or restart the servo drive. If this fault occurs when resetting the parameter settings, it indicates that the servo drive type is not set correctly. Correctly set the servo drive type again.
Press SHIFT key on the drive keypad The setting value of hidden parameter is in and examine if E100X is displayed on LED display. error.
9-7
Chapter 9 Troubleshooting
ASDA-B2
Potential Cause
Checking Method
Corrective Actions If this fault occurs when power is applied to the drive, it indicates that the data in EERPM is damaged or there is no data in EE-PROM. Please contact your distributor for assistance or contact with Delta.
Press SHIFT key on the drive keypad and examine if E0001 is displayed on LED display.
: Encoder output error Potential Cause Checking Method Corrective Actions Perform the corrective actions as described in AL011, AL024, AL025 and AL026. Check if the recent fault records (P400 ~ P4-05) display on the drive Encoder itself or the wiring of encoder is in keypad in accordance with the fault codes AL011, AL024, AL025 and error. AL026.
Correctly set P1-76 and P1-46. Check if the following conditions 1.Ensure that the motor speed The output frequency occur: is below the value set by P1for pulse output may Condition 1: Motor speed is above the 76. exceed the limit of its value set by P1-76. allowable setting 2. Condition 2: value. Motor Speed 6 Motor Speed
60 P1 46 4 > 19.8 10
60 P1 46 4 < 19.8 106
: Serial communication error Potential Cause Communication parameter setting is defective. Communication address is incorrect. Communication is incorrect. value Checking Method Corrective Actions
Check the communication parameter Correctly set parameter setting. setting. Check the communication address. Check the communication value. Correctly set communication address. Correctly set communication value.
: Serial communication time out Potential Cause Setting value in time out parameter is not correct. Not receiving communication command for a long time. : Reserve Checking Method Check communication time out parameter setting. Corrective Actions Correctly set P3-07.
Tighten the communication cable, make sure the Check whether communication cable is communication cable is not loose or broken. damaged and ensure all wiring is correct.
9-8
ASDA-B2
Chapter 9 Troubleshooting
: Input power phase loss Potential Cause Checking Method Check the power cable and connections of R, S, and T. Check whether the power cable is loose or the possible loss of phase on input power. Corrective Actions If the fault does not clear even when the three-phase power is connected correctly, please contact your distributor for assistance or contact with Delta.
: Pre-overload warning Potential Cause Checking Method Corrective Actions 1. Please refer to the 1. Check the load condition of the correction actions of servo motor and drive. ALE06. 2. Check the setting value of P1-56. 2. Increase the setting value Check whether the setting value of of P1-56 or set P1-56 to P1-56 is too small. 100 and above.
: Encoder initial magnetic field error Potential Cause Checking Method Corrective Actions 1.Check if the servo motor is properly grounded. 2.Check if the encoder signal cables If the error does not clear after are placed in separate conduits from each checking is done, please the cables connected to R, S, T and contact your distributor for U, V, W terminals to prevent the assistance or contact with interference. Delta. 3.Check if the shielded cables are used when performing encoder wiring.
: Encoder internal error Potential Cause Checking Method Corrective Actions 1.Please connect the grounding (green color) of U, V, W terminal to the heat sink of the servo drive. 1.Check if the servo motor is properly 2.Ensure that the encoder signal cables are placed in grounded. separate conduits from the 2.Check if the encoder signal cables cables connected to R, S, T are placed in separate conduits from and U, V, W terminals to the cables connected to R, S, T and prevent the interference. U, V, W terminals to prevent the 3.Please use shielded cables interference. for Encoder wiring. 3.Check if the shielded cables are used 4.If the error does not clear when performing encoder wiring. after all the above actions are done, please contact your distributor for assistance or contact with Delta.
The internal memory of the encoder is in error. An encoder counter error occurs.
9-9
Chapter 9 Troubleshooting
ASDA-B2
: Encoder data error Potential Cause Checking Method Corrective Actions 1.Please connect the grounding (green color) of U, V, W terminal to the heat sink of the servo drive. 1.Check if the servo motor is properly 2.Ensure that the encoder signal cables are placed in grounded. separate conduits from the 2.Check if the encoder signal cables cables connected to R, S, T are placed in separate conduits from and U, V, W terminals to An encoder data error the cables connected to R, S, T and prevent the interference. occurs for three times. U, V, W terminals to prevent the 3.Please use shielded cables interference. for Encoder wiring. 3.Check if the shielded cables are used 4. If the error does not clear when performing encoder wiring. after all the above actions are done, please contact your distributor for assistance or contact with Delta. Motor internal error Potential Cause Checking Method Corrective Actions 1. Please connect the grounding (green color) of U, V, W terminal to the heat sink of the servo drive. 1. Check if the servo motor is properly 2. Ensure that the encoder grounded. signal cables are placed in separate conduits from the 2. Check if the encoder signal cables are placed in separate conduits from cables connected to R, S, T and U, V, W terminals to the cables connected to R, S, T and The setting value of prevent the interference. U, V, W terminals to prevent the the encoder is in error. interference. 3. Please use shielded cables for Encoder wiring. 3. Check if the shielded cables are used when performing encoder 4. If the error does not clear wiring. after all the above actions are done, please contact your distributor for assistance or contact with Delta.
9-10
ASDA-B2
Chapter 9 Troubleshooting
Motor internal error Potential Cause Checking Method Corrective Actions 1. Please connect the grounding (green color) of U, V, W terminal to the heat sink of the servo drive. 1. Check if the servo motor is properly 2. Ensure that the encoder grounded. signal cables are placed in separate conduits from the 2. Check if the encoder signal cables are placed in separate conduits from cables connected to R, S, T and U, V, W terminals to the cables connected to R, S, T and prevent the interference. U, V, W terminals to prevent the interference. 3. Please use shielded cables for Encoder wiring. 3. Check if the shielded cables are used when performing encoder 4. If the error does not clear wiring. after all the above actions are done, please contact your distributor for assistance or contact with Delta.
Motor internal error Potential Cause Checking Method Corrective Actions 1. Please connect the grounding (green color) of U, V, W terminal to the heat sink of the servo drive. 1. Check if the servo motor is properly 2. Ensure that the encoder grounded. signal cables are placed in separate conduits from the 2. Check if the encoder signal cables are placed in separate conduits from cables connected to R, S, T and U, V, W terminals to The internal address of the cables connected to R, S, T and prevent the interference. U, V, W terminals to prevent the the encoder is in error. interference. 3. Please use shielded cables for Encoder wiring. 3. Check if the shielded cables are used when performing encoder 4. If the error does not clear wiring. after all the above actions are done, please contact your distributor for assistance or contact with Delta. : Motor protection error Potential Cause Checking Method Corrective Actions 1.Set P1-57 to 0. 2.Correctly set P1-57 and P158. Please note that the over-low setting may results in malfunction, but overhigh setting may let the motor protection function not operate.
9-11
The setting value of 1.Check if P1-57 is enabled. parameter P1-57 is reached after a period 2.Check if the setting values of P1-57 of time set by and P1-58 are both too small. parameter P1-58.
Chapter 9 Troubleshooting
ASDA-B2
: U, V, W, GND wiring error Potential Cause Checking Method Corrective Actions The wiring connections of U, V, W (for servo Check if wiring connections of U, V, motor output) and and W are not correct. GND (for grounding) are in error. The ground Check if the ground connection is connection is loose or loose and ensure the ground is not conducting conducting properly. properly. : Motor temperature error Potential Cause Motor is working under temperature over 105C (221F). Checking Method Corrective Actions
Follow the wiring steps in the user manual to reconnect the wiring and ground the servo drive and motor properly.
Check if the environment temperature Try to reduce environment is too high. temperature.
: Excessive encoder output error Potential Cause Encoder error causes abnormal encoder output. Checking Method Corrective Actions Exam error records (P4-00~P4Please refer to AL011, AL024, 05) to check if encoder errors AL025, AL026 and take corrective occurred. (AL011, AL024, AL025, actions. AL026)
Check if conditions below occur, Correctly set P1-76 and P1-46: P1-76 < Motor rotation speed, or, P1-76 > Motor rotation speed, and, Output pulses exceed Motor rotation speed hardware tolerance. P1 46 4 > 19.8 10 Motor rotation speed 6
60
60
P1 46 4 > 19.8 10
: Motor temperature warning Potential Cause Motor is working under temperature over 85C (185F). Checking Method Corrective Actions
Check if the environment temperature Try to reduce environment is too high. temperature.
: DSP firmware upgrade Potential Cause EE-PROM is not reset after the firmware version is upgraded. Checking Method Check if EE-PROM is reset after the firmware version is upgraded. Corrective Actions Set P2-08 to 30 first, and then 28 next, and restart the servo drive.
9-12
ASDA-B2
Chapter 9 Troubleshooting
Adjustment error
This fault message can be removed Emergency stop activated automatically by turning off EMGS (DI signal). Turn ARST (DI signal) ON to clear the fault. Reverse limit switch error This fault message can be removed when the servo drive is Off (Servo Off) Turn ARST (DI signal) ON to clear the fault. Forward limit switch error This fault message can be removed when the servo drive is Off (Servo Off) IGBT temperature error Memory error Encoder output error Serial communication error Turn ARST (DI signal) ON to clear the fault or restart the servo drive. Turn ARST (DI signal) ON to clear the fault or restart the servo drive. Turn ARST (DI signal) ON to clear the fault. Turn ARST (DI signal) ON to clear the fault. This fault message can also be removed automatically after the communication is normal.
9-13
Chapter 9 Troubleshooting
ASDA-B2
Display
Clearing Method Turn ARST (DI signal) ON to clear the fault or restart the servo drive. This fault message cannot be cleared. Turn ARST (DI signal) ON to clear the fault. This fault message can be removed automatically after input power phase lost problem is solved. Turn ARST (DI signal) ON to clear the fault or restart the servo drive. This fault message can be removed by restarting the servo drive. This fault message can be removed by restarting the servo drive. This fault message can be removed by restarting the servo drive. This fault message can be removed by restarting the servo drive. This fault message can be removed by restarting the servo drive. This fault message can be removed by restarting the servo drive. Turn ARST (DI signal) ON to clear the fault. This fault message can be removed by restarting the servo drive. This fault message can be removed by restarting the servo drive.
Pre-overload warning Encoder initial magnetic field error Encoder internal error Encoder data error Motor internal error Motor internal error Motor internal error Motor protection error U,V,W, GND wiring error Motor temperature error
Excessive encoder output Turn ARST (DI signal) ON to clear the fault. error Motor temperature warning DSP firmware upgrade This fault message can be removed after temperature drops to normal degree. This fault message can be removed after setting P2-08 to 30 first, and then 28 next and restarting the servo drive.
9-14
Chapter 10 Specifications
Power Supply
Phase / Voltage Continuous Output Current Cooling System Encoder Resolution / Feedback Resolution Control of Main Circuit Tuning Modes Dynamic Brake Max. Input Pulse Frequency
Three-phase: 170 ~ 255VAC, 5060Hz 5% Single-phase: 200 ~ 255VAC, 5060Hz 5% 0.9 Arms 1.55 Arms 2.6 Arms 5.1 Arms 7.3 Arms 8.3 Arms
Natural Air Circulation 17-bit (160000 p/rev) SVPWM Control Auto / Manual -
Fan Cooling
Built-in
Line driver: Max. 500Kpps (low speed)/ Max.4Mpps(high speed) Open collector: Max. 200Kpps Pulse + Direction, A phase + B phase, CCW pulse + CW pulse External pulse train / Internal parameters Low-pass filter Electronic gear N/M multiple N: 1 ~ (226-1)/M:1 ~ (231-1) 1/50 < N/M < 25600 Set by parameters Set by parameters 0 ~ 10 VDC 10K 2.2 us 1:5000 External analog signal / Internal parameters Low-pass and S-curve filter Set by parameters or via Analog input Maximum 550Hz 0.01% or less at load fluctuation 0 to 100% 0.01% or less at power fluctuation 10% 0.01% or less at ambient temperature fluctuation 0 C to 50 C
o o
Pulse Type Command Source Smoothing Strategy Electronic Gear Torque Limit Operation Feed Forward Compensation Voltage Range Analog Input Command Input Resistance Time Constant
Speed Control Range*1 Command Source Smoothing Strategy Torque Limit Operation Responsiveness Characteristic Speed Fluctuation Rate*2 (at rated speed)
10-1
Chapter 10 Specifications
ASDA-B2
Model: ASD-B2 Series Torque Control Mode Voltage Range Analog Input Command Input Resistance Time Constant Command Source Smoothing Strategy Speed Limit Operation Analog Monitor Output
100W 01
200W 02
400W 04
750W 07
1kW 10
1.5kW 15
2kW 20
3kW 30
0 ~ 10 VDC 10K 2.2 us External analog signal / Internal parameters Low-pass filter Parameter Setting or via Analog input Monitor signal can set by parameters (Output voltage range: 8V) Servo On, Reset, Gain switching, Pulse clear, Zero speed CLAMP, Command input reverse control, Speed/Torque limit enabled, Speed command selection, Position / Speed mode switching, Speed / Torque mode switching, Torque / Position mode switching, Emergency stop, Forward / Reverse inhibit limit, Forward / Reverse operation torque limit, Forward / Reverse JOG input, Electronic gear ratio (Numerator) selection and Pulse inhibit input Encoder signal output (A, B, Z Line Driver / Z Open collector) Servo ready, Servo On, At Zero speed, At Speed reached, At Positioning completed, At Torques limit, Servo alarm (Servo fault) activated, Electromagnetic brake control, Output overload warning, Servo warning activated Overcurrent, Overvoltage, Undervoltage, Motor overheated, Overload, Overspeed, Excessive deviation, Regeneration error, Abnormal pulse control command, Encoder error, Adjustment error, Emergency stop activated, Reverse/ Forward limit switch error, IGBT temperature error, Serial communication error, Input power phase loss, Serial communication time out, terminals with short circuit protection (U, V ,W , CN1, CN2, CN3 terminals) RS-232RS-485 Indoor location (free from direct sunlight), no corrosive liquid and gas (far away from oil mist, flammable gas, dust) Altitude 1000m or lower above sea level 86kPa to 106kPa 0 C to 55 C (32F to 131F) (If operating temperature is above specified range, forced cooling will be required) -20 ~ 65 0 to 90% (non-condensing) 9.80665m/s (1G) less than 20Hz, 5.88m/ s (0.6G) 20 to 50Hz IP20 TN System *4
IEC/EN 61800-5-1, UL 508C
2 2 o o
Outputs
Protective Functions
Communication Interface Installation Site Altitude Atmospheric pressure Operating Temperature Environment Storage Temperature Humidity Vibration IP Rating Power System
Standards/Requirement
10-2
ASDA-B2
Chapter 10 Specifications
Footnote: *1 *2 Rated rotation speed: When full load, speed ratio is defined as the minimum speed (the motor will not pause). When command is rated rotation speed, the speed fluctuation rate is defined as: (Empty load rotation speed Full load rotation speed) / Rated rotation speed *3 TN system: A power distribution system having one point directly earthed, the exposed conductive parts of the installation being connected to that points by protective earth conductor. Please refer to Chart of load and operating time in section 10.4 Overload Characteristics.
*4
10-3
Chapter 10 Specifications
ASDA-B2
Power rating (kW/s) 27.7 (without brake) Rotor moment of inertia 2 0.037 ( 10-4kg.m ) (without brake) Mechanical time constant 0.75 (ms) (without brake) Torque constant-KT 0.36 (N-m/A) Voltage constant-KE 13.6 (mV/(r/min)) Armature resistance 9.30 (Ohm) Armature inductance (mH) Electrical time constant (ms) Insulation class Insulation resistance Insulation strength Weight (kg) (without brake) Weight (kg) (with brake) Max. radial shaft load (N) Max. thrust shaft load (N) Power rating (kW/s) (with brake) Rotor moment of inertia 2 ( 10-4kg.m ) (with brake) Mechanical time constant (ms) (with brake) Brake holding torque [Nt-m (min)] *2 0.5 0.8 78.4 39.2 25.6 0.04 0.81 0.3 24.0 2.58
Class A (UL), Class B (CE) >100M, DC 500V 1500V AC, 60 seconds 1.2 1.5 196 68 21.3 0.192 0.85 1.3 1.6 2.0 196 68 53.8 0.30 0.57 1.3 2.1 2.9 245 98 22.1 0.73 0.78 2.5 3.0 3.8 245 98 48.4 1.18 0.65 2.5 2.9 3.69 245 98 29.3 1.95 1.74 2.5 3.8 5.5 245 98 37.9 2.67 1.22 2.5 4.3 4.7 490 98 30.4 3.33 0.93 8.0 6.2 7.2 490 98 82.0 4.95 0.66 8.0
10-4
ASDA-B2
Chapter 10 Specifications
Model: ECMA Series Brake power consumption (at 20 C) [W] Brake release time [ms (Max)] Brake pull-in time [ms (Max)] Vibration grade (um) Operating temperature Storage temperature Operating humidity Storage humidity Vibration capacity IP rating Approvals Footnote: *1
o
C204 01 7.2 5 25 02
C206 04 6.5 10 70 04
C209 10 8.2 10 70
6.5 10 70
8.2 10 70
8.2 10 70
20% to 90% RH (non-condensing) 20% to 90% RH (non-condensing) 2.5G IP65 (when waterproof connectors are used, or when an oil seal is used to be fitted to the rotating shaft (an oil seal model is used))
Rate torque values are continuous permissible values at 0~40oC ambient temperature when attaching with the sizes of heatsinks listed below: ECMA-__04 / 06 / 08 : 250mm x 250mm x 6mm ECMA-__10 : 300mm x 300mm x 12mm ECMA-__13 : 400mm x 400mm x 20mm ECMA-__18 : 550mm x 550mm x 30mm Material type : Aluminum F40, F60, F80, F100, F130, F180
*2 *3
The holding brake is used to hold the motor shaft, not for braking the rotation. Never use it for decelerating or stopping the machine. For the specifications of the motors with rotary magnetic encoders, please refer to the specifications of the corresponding standard models.
NOTE
1) Please refer to Section 1.2 for details about the model explanation.
10-5
Chapter 10 Specifications
ASDA-B2
14.32 19.10
14.32 21.48 28.65 28.65 42.97 57.29 2000 3000 11.01 11.22 33.0 62.5 33.66 26.3 16.1 48.3 37.3 19.4 58.2 66.4 1500
11.18 14.59 34.68 54.95 54.95 1.11 0.87 31.8 0.26 4.01 0.96 0.87 31.8 1.62 0.85 31.4 1.06 0.89 32.0 1.28 0.98 35.0
14.29 11.12
12.96 12.88 15.31 15.86 23.87 26.39 16.51 13.55 13.55 16.06 Class A (UL), Class B (CE) >100M, DC 500V AC 1500V60 sec 13.5 17.5 1176 490 24.1 18.5 22.5 1470 490 35.9 18.5 22.5 1470 490 63.9 6.8 8.2 490 98 9.2 8.94 2.0 10.0 19.0 7.0 8.4 490 98 35.9 9.14 1.51 10.0 19.0 7.5 8.9 490 98 62.1 11.9 1.13 10.0 19.0
11.90 15.88 37.86 57.06 57.06 1.19 10.0 19.0 1.05 10.0 19.0 1.77 25.0 20.4 1.10 25.0 20.4 1.33 25.0 20.4
10-6
ASDA-B2
Chapter 10 Specifications
Model: ECMA Series Brake release time [ms (Max)] Brake pull-in time [ms (Max)] Vibration grade (um) Operating temperature Storage temperature Operating humidity Storage humidity Vibration capacity IP rating Approvals Footnote: *1
E213 05 10 70 10 10 70 15 10 70 20 10 70
E218 20 10 70 15 0 ~ 40 oC -10 ~ 80 oC 30 10 70
F218 30 10 70 03 10 70
G213 06 10 70 09 10 70
20% to 90% RH (non-condensing) 20% to 90% RH (non-condensing) 2.5G IP65 (when waterproof connectors are used, or when an oil seal is used to be fitted to the rotating shaft (an oil seal model is used))
Rate torque values are continuous permissible values at 0~40oC ambient temperature when attaching with the sizes of heatsinks listed below: ECMA-__04 / 06 / 08 : 250mm x 250mm x 6mm ECMA-__10 : 300mm x 300mm x 12mm ECMA-__13 : 400mm x 400mm x 20mm ECMA-__18 : 550mm x 550mm x 30mm Material type : Aluminum F40, F60, F80, F100, F130, F180
*2 *3
The holding brake is used to hold the motor shaft, not for braking the rotation. Never use it for decelerating or stopping the machine. For the specifications of the motors with rotary magnetic encoders, please refer to the specifications of the corresponding standard models.
NOTE
1) Please refer to Section 1.2 for details about the model explanation.
10-7
Chapter 10 Specifications
ASDA-B2
10-8
ASDA-B2
Chapter 10 Specifications
Occasion of Overload
1. Motor was operated for several seconds under a torque exceeding 100% torque. 2. Motor had driven high inertia machine and had accelerated and decelerated at high frequency. 3. Motor UVW cable or encoder cable was not connected correctly. 4. Servo gain was not set properly and caused motor hunting. 5. Motor holding brake was not released.
10-9
Chapter 10 Specifications
ASDA-B2
10-10
ASDA-B2
Chapter 10 Specifications
NOTE
1) Dimensions are in millimeters (inches). 2) Weights are in kilograms (kg) and (pounds (lbs)). 3) In this manual, actual measured values are in metric units. Dimensions in (imperial units) are for reference only. Please use metric for precise measurements.
10-11
Chapter 10 Specifications
ASDA-B2
NOTE
1) Dimensions are in millimeters (inches). 2) Weights are in kilograms (kg) and (pounds (lbs)). 3) In this manual, actual measured values are in metric units. Dimensions in (imperial units) are for reference only. Please use metric for precise measurements.
10-12
ASDA-B2
Chapter 10 Specifications
NOTE
1) Dimensions are in millimeters (inches). 2) Weights are in kilograms (kg) and (pounds (lbs)). 3) In this manual, actual measured values are in metric units. Dimensions in (imperial units) are for reference only. Please use metric for precise measurements.
10-13
Chapter 10 Specifications
ASDA-B2
NOTE
1) Dimensions are in millimeters (inches).
2) Weights are in kilograms (kg) and (pounds (lbs)). 3) In this manual, actual measured values are in metric units. Dimensions in (imperial units) are for reference only. Please use metric for precise measurements.
10-14
ASDA-B2
Chapter 10 Specifications
Model LC LZ LA S LB LL (without brake) LL (with brake) LS (without oil seal) LS (with oil seal) LR LE LG LW RH WK W T TP
60 5.5 70
0 14( + 0.011)
60 5.5 70
0 14( + 0.011)
80 6.6 90
0 14( + 0.011)
80 6.6 90
0 19( + 0.013)
86 6.6 100
0 16( + 0.011)
86 6.6 100
0 16( + 0.011)
0 30( + 0.021)
0 50( + 0.025)
0 50( + 0.025)
0 70( + 0.030 )
0 70( + 0.030 )
0 80( + 0.030 )
0 80( + 0.030 )
NOTE
1) Dimensions are in millimeters. 2) Dimensions and weights of the servo motor may be revised without prior notice. 3) The boxes () in the model names are for optional configurations. (Please refer to section 1.2 for model explanation.) 4) Except ECMA-CM0604PS LL: 116.2mm, for the specifications of the motors with rotary magnetic encoders, please refer to the specifications of the corresponding standard models.
Revision January 2012
10-15
Chapter 10 Specifications
ASDA-B2
0 95( + 0.035)
NOTE
1) Dimensions are in millimeters. 2) Dimensions and weights of the servo motor may be revised without prior notice. 3) The boxes () in the model names are for optional configurations. (Please refer to section 1.2 for model explanation.) 4) For the specifications of the motors with rotary magnetic encoders, please refer to the specifications of the corresponding standard models.
10-16
ASDA-B2
Chapter 10 Specifications
NOTE
1) Dimensions are in millimeters. 2) Dimensions and weights of the servo motor may be revised without prior notice. 3) The boxes () in the model names are for optional configurations. (Please refer to section 1.2 for model explanation.)
10-17
Chapter 10 Specifications
ASDA-B2
NOTE
1) Dimensions are in millimeters. 2) Dimensions and weights of the servo motor may be revised without prior notice. 3) The boxes () in the model names are for optional configurations. (Please refer to section 1.2 for model explanation.)
10-18
Appendix A Accessories
Power Connectors
A-1
Appendix A Accessories
ASDA-B2
Power Cables
Title 1 2
Title 1 2
A-2
ASDA-B2
Appendix A Accessories
3106A-20-18S
L
Straight 3106A-20-18S 3106A-20-18S L mm 3000 50 5000 50 inch 118 2 197 2
Title 1 2
3106A-20-18S
L
Straight 3106A-20-18S 3106A-20-18S L mm 3000 50 5000 50 inch 118 2 197 2
Title 1 2
Title 1 2
A-3
Appendix A Accessories
ASDA-B2
Title 1 2
Encoder Connectors
A-4
ASDA-B2
Appendix A Accessories
Encoder Cables
Title 1 2
Title 1 2
A-5
Appendix A Accessories
ASDA-B2
80.1
22.5
21.2
Unit: mm
Part No. : ASD-CNUS0A08 3000 100 mm 118 4 inch RJ-45 A-type (USB V2.0)
A-6
1.8
ASDA-B2
Appendix A Accessories
1 2 3
205
Title Housing Terminal RS-485 Connector Part No. A2004H00-3P A2004TOP-2 Manufacturer JWT JWT
A-7
Appendix A Accessories
ASDA-B2
200W Servo Drive and 200W Low Inertia Servo Motor Servo Drive Low inertia Servo Motor Without Brake 3M Cable ASDBCAPW0203 Encoder Cable ASDBCAEN0003 Connector 5M ASDBCAPW0205 Encoder Cable ASDBCAEN0005 3M ASDBCAPW0303 Encoder Cable ASDBCAEN0003 ASD-B2-0221-B ECMA-C20602S With Brake 5M ASDBCAPW0305 Encoder Cable ASDBCAEN0005
Motor Power Cable Motor Power Cable Motor Power Cable Motor Power Cable
400W Servo Drive and 400W Low Inertia Servo Motor Servo Drive Low inertia Servo Motor Without Brake 3M Cable ASDBCAPW0203 Encoder Cable ASDBCAEN0003 Connector 5M ASDBCAPW0205 Encoder Cable ASDBCAEN0005 3M ASDBCAPW0303 Encoder Cable ASDBCAEN0003 ASD-B2-0421-B ECMA-C20604S ECMA-CM0604PS ECMA-C208047 With Brake 5M ASDBCAPW0305 Encoder Cable ASDBCAEN0005
Motor Power Cable Motor Power Cable Motor Power Cable Motor Power Cable
A-8
ASDA-B2
Appendix A Accessories
400W Servo Drive and 500W Medium Inertia Servo Motor Medium inertia Servo Motor Without Brake 3M Cable ASDBCAPW1203 Encoder Cable ASDBCAEN1003 Connector 5M ASDBCAPW1205 Encoder Cable ASDBCAEN1005 3M ASDBCAPW1303 Encoder Cable ASDBCAEN1003 ECMA-E21305S Without Brake 5M ASDBCAPW1305 Encoder Cable ASDBCAEN1005
Motor Power Cable Motor Power Cable Motor Power Cable Motor Power Cable
400W Servo Drive and 300W High Inertia Servo Motor Servo Drive High inertia Servo Motor Without Brake 3M Cable ASDBCAPW1203 Encoder Cable ASDBCAEN1003 Connector 5M ASDBCAPW1205 Encoder Cable ASDBCAEN1005 3M ASDBCAPW1303 Encoder Cable ASDBCAEN1003 ASD-B2-0421-B ECMA-G21303S With Brake 5M ASDBCAPW1305 Encoder Cable ASDBCAEN1005
Motor Power Cable Motor Power Cable Motor Power Cable Motor Power Cable
750W Servo Drive and 750W Low Inertia Servo Motor Servo Drive Low inertia Servo Motor Without Brake 3M Cable ASDBCAPW0203 Encoder Cable ASDBCAEN0003 Connector 5M ASDBCAPW0205 Encoder Cable ASDBCAEN0005 3M ASDBCAPW0303 Encoder Cable ASDBCAEN0003 ASD-B2-0721-B ECMA-C20807S ECMA-C20907S With Brake 5M ASDBCAPW0305 Encoder Cable ASDBCAEN0005
Motor Power Cable Motor Power Cable Motor Power Cable Motor Power Cable
A-9
Appendix A Accessories
ASDA-B2
750W Servo Drive and 600W High Inertia Servo Motor Servo Drive High inertia Servo Motor Without Brake 3M Cable ASDBCAPW1203 Encoder Cable ASDBCAEN1003 Connector 5M ASDBCAPW1205 Encoder Cable ASDBCAEN1005 3M ASDBCAPW1303 Encoder Cable ASDBCAEN1003 ASD-B2-0721-B ECMA-G21306S ECMA-GM1306PS With Brake 5M ASDBCAPW1305 Encoder Cable ASDBCAEN1005
Motor Power Cable Motor Power Cable Motor Power Cable Motor Power Cable
1kW Servo Drive and 1kW Low Inertia Servo Motor Servo Drive Low inertia Servo Motor Without Brake 3M Cable ASDBCAPW1203 Encoder Cable ASDBCAEN1003 Connector 5M ASDBCAPW1205 Encoder Cable ASDBCAEN1005 3M ASDBCAPW1303 Encoder Cable ASDBCAEN1003 ASD-B2-1021-B ECMA-C21010S ECMA-C20910S With Brake 5M ASDBCAPW1305 Encoder Cable ASDBCAEN1005
Motor Power Cable Motor Power Cable Motor Power Cable Motor Power Cable
1kW Servo Drive and 1kW Medium Inertia Servo Motor Servo Drive Medium inertia Servo Motor Without Brake 3M Cable ASDBCAPW1203 Encoder Cable ASDBCAEN1003 Connector 5M ASDBCAPW1205 Encoder Cable ASDBCAEN1005 3M ASDBCAPW1303 Encoder Cable ASDBCAEN1003 ASD-B2-1021-B ECMA-E21310S With Brake 5M ASDBCAPW1305 Encoder Cable ASDBCAEN1005
Motor Power Cable Motor Power Cable Motor Power Cable Motor Power Cable
A-10
ASDA-B2
Appendix A Accessories
1kW Servo Drive and 900W High Inertia Servo Motor Servo Drive High inertia Servo Motor Without Brake 3M Cable ASDBCAPW1203 Encoder Cable ASDBCAEN1003 Connector 5M ASDBCAPW1205 Encoder Cable ASDBCAEN1005 3M ASDBCAPW1303 Encoder Cable ASDBCAEN1003 ASD-B2-1021-B ECMA-G21309S ECMA-GM1309PS With Brake 5M ASDBCAPW1305 Encoder Cable ASDBCAEN1005
Motor Power Cable Motor Power Cable Motor Power Cable Motor Power Cable
1.5kW Servo Drive and 1.5kW Medium Inertia Servo Motor Servo Drive Medium inertia Servo Motor Without Brake 3M Cable ASDBCAPW1203 Encoder Cable ASDBCAEN1003 Connector 5M ASDBCAPW1205 Encoder Cable ASDBCAEN1005 3M ASDBCAPW1303 Encoder Cable ASDBCAEN1003 ASD-B2-1521-B ECMA-E21315S With Brake 5M ASDBCAPW1305 Encoder Cable ASDBCAEN1005
Motor Power Cable Motor Power Cable Motor Power Cable Motor Power Cable
2kW Servo Drive and 2kW Low Inertia Servo Motor Servo Drive Low inertia Servo Motor Without Brake 3M Cable ASDBCAPW1203 Encoder Cable ASDBCAEN1003 Connector 5M ASDBCAPW1205 Encoder Cable ASDBCAEN1005 3M ASDBCAPW1303 Encoder Cable ASDBCAEN1003 ASD-B2-2023-B ECMA-C21020S With Brake 5M ASDBCAPW1305 Encoder Cable ASDBCAEN1005
Motor Power Cable Motor Power Cable Motor Power Cable Motor Power Cable
A-11
Appendix A Accessories
ASDA-B2
2kW Servo Drive and 2kW Medium Inertia Servo Motor Servo Drive Medium inertia Servo Motor Without Brake 3M Cable ASDBCAPW1203 Encoder Cable ASDBCAEN1003 Connector 5M ASDBCAPW1205 Encoder Cable ASDBCAEN1005 3M ASDBCAPW1303 Encoder Cable ASDBCAEN1003 ASD-B2-2023-B ECMA-E21320S With Brake 5M ASDBCAPW1305 Encoder Cable ASDBCAEN1005
Motor Power Cable Motor Power Cable Motor Power Cable Motor Power Cable
2kW Servo Drive and 2kW Medium Inertia Servo Motor Servo Drive Medium inertia Servo Motor Without Brake 3M Cable ASD-CAPW2203 Encoder Cable ASDBCAEN1003 Connector 5M ASD-CAPW2205 Encoder Cable ASDBCAEN1005 3M ASD-CAPW2303 Encoder Cable ASDBCAEN1003 ASD-B2-2023-B ECMA-E21820S With Brake 5M ASD-CAPW2305 Encoder Cable ASDBCAEN1005
Motor Power Cable Motor Power Cable Motor Power Cable Motor Power Cable
3kW Servo Drive and 3kW Medium Inertia Servo Motor Servo Drive Medium inertia Servo Motor Without Brake 3M Cable ASD-CAPW2203 Encoder Cable ASDBCAEN1003 Connector 5M ASD-CAPW2205 Encoder Cable ASDBCAEN1005 3M ASD-CAPW2303 Encoder Cable ASDBCAEN1003 ASD-B2-3023-B ECMA-E21830S With Brake 5M ASD-CAPW2305 Encoder Cable ASDBCAEN1005
Motor Power Cable Motor Power Cable Motor Power Cable Motor Power Cable
A-12
ASDA-B2
Appendix A Accessories
3kW Servo Drive and 3kW Medium Inertia Servo Motor Servo Drive Medium inertia Servo Motor Without Brake 3M Cable ASD-CAPW2203 Encoder Cable ASDBCAEN1003 Connector 5M ASD-CAPW2205 Encoder Cable ASDBCAEN1005 3M ASD-CAPW2303 Encoder Cable ASDBCAEN1003 ASD-B2-3023-B ECMA-F21830S With Brake 5M ASD-CAPW2305 Encoder Cable ASDBCAEN1005
Motor Power Cable Motor Power Cable Motor Power Cable Motor Power Cable
Power Connector ASD-CAPW2000 Encoder Connector ASDBCAEN1000 Other Accessories (for ASDA-B2 series all models)
Description Communication Cable between Drive and Computer (for PC) Regenerative Resistor 400W 100 Regenerative Resistor 3kW 10
NOTE
1) The boxes () at the ends of the servo drive model names are for optional configurations (Full closed-loop, CANopen and extension DI port). For the actual model name, please refer to the ordering information of the actual purchased product. 2) The boxes () in the servo motor model names are for optional configurations (keyway, brake and oil seal).
A-13
Appendix A Accessories
ASDA-B2
A-14
Delta AC servo drives are based on solid state electronics technology. Preventive maintenance is required to operate this AC servo drives in its optimal condition, and to ensure a long life. It is recommended to perform a periodic maintenance and inspection of the AC servo drive by a qualified technician. Before any maintenance and inspection, always turn off the AC input power to the unit.
Be sure to disconnect AC power and ensure that the internal capacitors have fully discharged before performing the maintenance and inspection!
Basic Inspection
After power is in connected to the AC servo drive, the charge LED will be lit which indicates that the AC servo drive is ready. Item Content
Periodically inspect the screws of the servo drive, motor shaft, terminal block and the connection to mechanical system. Tighten screws as necessary as they may loosen due to vibration and varying temperatures. Ensure that oil, water, metallic particles or any foreign objects do not fall inside the servo drive, motor, control panel or ventilation slots and General Inspection holes. As these will cause damage. Ensure the correct installation and the control panel. It should be free from airborne dust, harmful gases or liquids. Ensure that all wiring instructions and recommendations are followed; otherwise damage to the drive and or motor may result. Inspect the servo drive and servo motor to insure they were not damaged. To avoid an electric shock, be sure to connect the ground terminal of servo drive to the ground terminal of control panel. Before making any connection, wait 10 minutes for capacitors to discharge after the power is disconnected, alternatively, use an appropriate discharge device to discharge. Inspection before Ensure that all wiring terminals are correctly insulated. operation Ensure that all wiring is correct or damage and or malfunction may (Control power is result. not applied) Visually check to ensure that there are not any unused screws, metal strips, or any conductive or inflammable materials inside the drive. Never put inflammable objects on servo drive or close to the external regenerative resistor. Make sure control switch is OFF. If the electromagnetic brake is being used, ensure that it is correctly wired.
B-1
ASDA-B2
Item
Content
Inspection before If required, use an appropriate electrical filter to eliminate noise to the servo drive. operation (Control power is Ensure that the external applied voltage to the drive is correct and matched to the controller. not applied) Ensure that the cables are not damaged, stressed excessively or loaded heavily. When the motor is running, pay close attention on the connection of the cables and notice that if they are damaged, frayed or over extended. Check for abnormal vibrations and sounds during operation. If the servo motor is vibrating or there are unusual noises while the motor is running, please contact the dealer or manufacturer for assistance. Ensure that all user-defined parameters are set correctly. Since the Inspection during characteristics of various machinery are different, in order to avoid operation accident or cause damage, do not adjust the parameter abnormally and ensure the parameter setting is not an excessive value. (Control power is applied) Ensure to reset some parameters when the servo drive is off (Please refer to Chapter 7). Otherwise, it may result in malfunction. If there is no contact sound or there be any unusual noises when the relay of the servo drive is operating, please contact your distributor for assistance or contact with Delta. Check for abnormal conditions of the power indicators and LED display. If there is any abnormal condition of the power indicators and LED display, please contact your distributor for assistance or contact with Delta.
Maintenance Use and store the product in a proper and normal environment. Periodically clean the surface and panel of servo drive and motor. Make sure the conductors or insulators are corroded and/or damaged. Do not disassemble or damage any mechanical part when performing maintenance. Clean off any dust and dirt with a vacuum cleaner. Place special emphasis on cleaning the
ventilation ports and PCBs. Always keep these areas clean, as accumulation of dust and dirt can cause unforeseen failures.
B-2
ASDA-B2
Relay
The contacts will wear and result in malfunction due to switching current. The life of relay varies according to power supply capacity. Therefore, the common guaranteed life of relay is cumulative 100,000 times of power on and power off.
Cooling fan
The cooling fan life is limited and should be changed periodically. The cooling fan will reach the end of its life in 2~3 years when it is in continuous operation. However, it also must be replaced if the cooling fan is vibrating or there are unusual noises.
B-3
ASDA-B2
B-4