Duct Temperature Sensors
Duct Temperature Sensors
Duct Temperature Sensors
761
1761P03
1761P01
QAM2110.040, QAM2120.040
QAM2120.200, QAM2120.600
Symaro
1761P02
QAM21...
The duct temperature sensors are for use in ventilation and air conditioning plants as: Supply or extract air temperature sensors Limit sensors, e.g. for minimum limitation of the supply air temperature Reference sensors, e.g. for shifting the room temperature as a function of the outside temperature Measuring sensors, e.g. for measured value indication or for connection to a building automation and control system Type summary Type reference QAM2110.040 QAM2112.040 QAM2112.200 QAM2120.040 QAM2120.200 QAM2120.600 QAM2130.040 QAM2140.020 Probe length 0,4 m 0,4 m 2,0 m 0,4 m 2,0 m 6,0 m 0,4 m 0,2 m Mounting clamps keine keine 4 Stck keine 4 Stck 6 Stck keine keine Sensing element Pt 100 Pt 1000 Pt 1000 LG-Ni 1000 LG-Ni 1000 LG-Ni 1000 NTC 10k T1 (PTC)
CE1N1761en 07.02.2008
Building Technologies
Name Capillary tube clamb for the QAM2120.200 and QAM2120.600 (6 pieces) Monting flange
Ordering and delivery When ordering, please give name and type reference, e.g.: Duct temperature sensor QAM2120.040 The sensor is supplied complete with mounting flange AQM63.0 and, if required, mounting clamps AQM63.3. Equipment combinations All systems or devices capable of acquiring and handling the sensors passive output signal. Function The sensor acquires the air temperature via its sensing element whose resistance changes as a function of the temperature. The signal is delivered to a suitable controller for further handling. Sensing elements LG-Ni 1000 Characteristic:
R []
[K]
1771D01
1771D02
Accuracy:
1400
2.0
1200
1.0
1000
0.0
800
1.0
600 50 40 30 20 10
10
20 30 40 50 60 70 80
[C]
2.0 50 40 30 20 10
0 10 20 30 40 50 60 70 80 [C]
Pt 100 (class B)
Characteristic:
R []
1811D05
Accuracy:
[K]
0.8 0.4 0.0 0.4 0.8
1811D06
140
120
100
80
60 50 40 30 20 10
10
20 30 40 50 60 70
80 [C]
50 40 30 20 10
10 20 30 40 50 60 70 80
[C]
2/6 Siemens Building Technologies Duct temperature sensors QAM21... CE1N1761en 07.02.2008
Pt 1000 (class B)
Characteristic:
R []
1761D01
Accuracy:
[K]
0.8
1761D02
1400
1200
1000
800
600 50 40 30 20 10
10
20 30 40 50 60 70
80 [C]
50 40 30 20 10
10 20 30 40 50 60 70 80
[C]
T1 (PTC)
Characteristic:
R [ ]
1864D01
Accuracy:
[K]
4.0 3.0 2.0 1.0 0.0 1.0 2.0 3.0 4.0
1864D02
3200 3000 2800 2600 2400 2200 2000 1800 1600 1400 40 30 20 10 0 10 20 30 40 50 60 70
5.0
80 [C]
5.0 40 30 20 10
0 10 20 30 40 50 60 70 80 [C]
NTC 10k
Characteristic:
R []
1811D09
Accuracy:
[K]
1.20 1.00 0.80 0.60 0.40 0.20 0.00 -0.20 -0.40 -0.60 -0.80 -1.00 -1.20 -40 -30 -20 -10
1811D08
1000000
100000
10000
[C]
0 10 20 30 40 50 60 70 80
[C]
Legend
Mechanical design The duct temperature sensor consists of the following components: Two-sectional plastic housing comprised of base with connection terminals and removable cover (snap-on design) Fully active, flexible probe with sensing element which acquires the average temperature The connection terminals can be accessed after removing the cover. Cable entry is made via a grommet which, if required, can be replaced by a cable entry gland M16 (IP 54). After fitting the mounting flange, the sensor can be installed in 6 different immersion positions so that the sensor housing is always located outside the insulation for layers up to 70 mm. The probe with a length of 2 or 6 m is to be fitted across the air duct with the help of the mounting clamps supplied with the sensor.
3/6 Siemens Building Technologies Duct temperature sensors QAM21... CE1N1761en 07.02.2008
Mounting notes Mounting location For supply air temperature control: Downstream from the fan, if the fan is located after the last air handling unit. Otherwise, after the last air handling unit with a minimum distance of 0.5 m For extract air temperature control: Always upstream of the extract air fan As a limit sensor for the supply air temperature: As close as possible to the air outlet into the room For dew point control: Immediately after the spray trap of the air washer Manually bend the probe so that it lies diagonally across the duct or in equally spaced windings across the entire duct cross-section. The probe must not touch the duct wall. The sensor is supplied complete with Mounting Instructions. Mounting positions permitted: not permitted: . . . . .
Mounting examples
n. mi
20
m 0m
m
0 .7 ax
A
1761Z05
1 2
A
1761Z07
Technical data
Functional data Operating range Sensing element Probe Length Min. bending radius Time constant Dead time Measuring accuracy Protective data Protection standard of housing With cable entry gland M 16 x 1.5 Safety class Electrical connections Screw terminals for Cable entry Grommet Cable entry gland Perm. cable lengths Environmental conditions Operation Climatic conditions Temperature (housing) Humidity (housing) Transport Climatic conditions Temperature Humidity Mechanical conditions 40...+ 80 C for NTC type 50...+ 80 C other types refer to "Type summary refer to "Type summary 10 mm 30 s at 2 m / s <1 s refer to Function" IP 42 to IEC 529 IP 54 to IEC 529 (not included as standard) III to EN 60 730 (only with SELV or PELV) 1 x 2.5 mm or 2 x 1.5 mm for 5.5...7.2 mm dia. cable M 16 x 1.5 can be fitted refer to Data Sheet of the relevant controller to IEC 721-3-3 class 3K5 40...+ 70 C 5...95 % r. h. to IEC 721-3-2 class 2K3 25...+ 70 C < 95 % r. h. class 2M2
2 2
4/6 Siemens Building Technologies Duct temperature sensors QAM21... CE1N1761en 07.02.2008
1761Z09
1761Z03
copper, polyolefine polycarbonate, RAL 7001 (silver-grey) polycarbonate, RAL 7035 (light-grey) PA 66 (black) PA-GF 35 (black) corrugated cardboard ca. 0,15 kg ca. 0,15 kg ca. 0,3 kg ca. 0,15 kg ca. 0,30 kg ca. 0,53 kg ca. 0,15 kg ca. 0,15 kg
Weight
Incl. packaging QAM2110.040 QAM2112.040 QAM2112.200 QAM2120.040 QAM2120.200 QAM2120.600 QAM2130.040 QAM2140.020
Internal diagram
The internal diagram is identical for all types of duct temperature sensors covered by this Data Sheet. The connecting wires are interchangeable.
Dimensions
6
1761G01
Typ 20 QAM2140.020 QAM2130.040 QAM2110.040 QAM2120.040 QAM2112.040 106 QAM2112.200 QAM2120.200 QAM2120.600
L2 min. 37 37 37 37 37 37 37 37
. . . . . .
40 31 3,7 50
80
60
80
L1
60
Drilling plan
Dimensions in mm
1761M01
L2
21
5/6 Siemens Building Technologies Duct temperature sensors QAM21... CE1N1761en 07.02.2008