Duct Humidity Sensors
Duct Humidity Sensors
864
1864P01
Symaro
Duct sensors
for relative humidity and temperature Use
QFM21...
Operating voltage AC 24 V / DC 13.5...35 V Signal output DC 0...10 V / 420 mA for relative humidity Signal output DC 0...10 V / 420 mA / T1 / LG-Ni 1000 for temperature Measuring accuracy 3 % r. h. within the comfort range Range of use 15+60 C / 095 % r. h. (non-condensing)
The QFM21 duct sensors are for use in air ducts of ventilation and air conditioning plant for acquiring: The relative humidity and The temperature. The sensors are used as: Control sensors in the supply or extract air Reference sensors, e.g. for shifting the dew point Limit sensors, e.g. in connection with steam humidifiers Limit sensors, e.g. for measured value indication or for connection to a building automation and control system Sensors for enthalpy and absolute humidity, together with SEZ220 (see Data Sheet N5146)
CE1N1864en 02.07.2008
Building Technologies
Type summary
Type reference QFM2100 QFM2101 QFM2120 QFM2140 QFM2160 QFM2171 Temperature measuring range None None 35...+ 5 0 C 35...+ 5 0 C 0...50 C / 35...+ 3 5 C or 40...+ 7 0 C 0...50 C / 35...+ 3 5 C or 40...+ 7 0 C Temperature signal output None None passive, LG-Ni 1000 passive, T1 (PTC) active, DC 0...10 V active, 420 mA Humidity measuring range 0...100 % 0...100 % 0...100 % 0...100 % 0...100 % 0...100 % Humidity signal output active, DC 0...10 V active, 420 mA active, DC 0...10 V active, DC 0...10 V active, DC 0...10 V active, 420 mA Operating voltage AC 24 V or DC 13.535 V DC 13.535 V AC 24 V or DC 13.535 V AC 24 V or DC 13.535 V AC 24 V or DC 13.535 V DC 13.535 V
Ordering and delivery When ordering, please give name and type reference, e.g.: Duct sensor QFM2120 The sensor is supplied with mounting flange and cable entry gland M16. Equipment combinations All systems and devices capable of acquiring and handling the sensors DC 0...10 V , 4...20 mA, LG-Ni 1000 or T1 output signal. When using the sensors for minimum or maximum selection, for averageing, or to calculate enthalpy, enthalpy difference, absolute humidity, and dewpoint, we recommend to use the SEZ220 signal converter (see Data Sheet N5146). Function Relative humidity The sensor acquires the relative humidity in the air duct via its capacitive humidity sensing element whose electrical capacitance changes as a function of the relative humidity. The electronic measuring circuit converts the sensors signal to a continuous DC 0...10 V or 420 mA signal, which corresponds to 0...100 % r. h. The sensor acquires the temperature in the air duct via its sensing element whose electrical resistance changes as a function of the temperature. Depending on the type of sensor this change in resistance is converted either to an active DC 010 V or 420 mA output signal corresponding to a temperature range of 0 50 C, 35+35 C, or 40...+70 C. The measuring range can be selected. The temperature is provided as a simulated passive LG-Ni 1000- or T1-output signal ( 3550 C) as an alternative to the active output signal. The measuring current of systems / devices for acquiring the electrical resistance of the passive sensor differs greatly and impacts self-heating of the temperature sensing element at the end of the measuring tip. To compensate the impact, the passive output signal is simulated with an electronic circuit.
Temperature
Characteristic:
R []
1811D01
1400
1200
1000
800
600 50 40 30 20 10
10
20 30 40 50 60 70 80
[C]
T1 (PTC)
3200 3000 2800 2600 2400 2200 2000 1800 1600 1400
R []
1864D01
40 30 20 10
10
20 30 40 50 60 70 80
[C]
Legend
Burden diagram
Burden [Ohm]
10
20
30
40
Operating voltage
[DC V]
Mechanical design The duct sensor consists of a housing, a printed circuit board, connection terminals, a mounting flange and an immersion rod having a measuring tip. The 2-sectional housing comprises a base and a removable cover (snap-on design). The measuring circuit and the setting element are located on the printed circuit board inside the cover, the connection terminals on the base. The sensing elements are located at the end of the measuring tip and protected by a filter cap. Cable entry is made via the screwed cable gland M16 supplied with the sensor. Immersion rod and housing are made of plastic and are rigidly connected. The sensor is fitted with the mounting flange supplied with the sensor. The flange is to be placed over the immersion rod and then secured in accordance with the required immersion length.
Setting element
Range 1 2 3
U1
10 V
I2
12 mA 20 mA
1864Z05en
5 V 10 V 0V 5V 5V 0V
12 mA 4 mA
35 C 12 mA
The setting element is located inside the cover. It comprises 6 pins and a jumper. It is used to select the required measuring range and to activate the test function. The different jumper settings have the following meaning: For the passive temperature measuring range: Jumper in the middle position (R2) = 35...+ 50 C (factory setting) For the active temperature measuring range: Jumper in the left position (R1) = 35...+ 35 C, Jumper in the middle position (R2) = 0...50 C (factory setting) Jumper in the right position (R3) = 40...+70 C For activating the test function: Jumper in the horizontal position: The values according to the table "Test function active" will be made available at the signal output. Malfunction Should the temperature sensor become faulty a voltage of 0 V (4 mA) will be applied at signal output U2 (I2) or signal output BS-MS becomes high impedance (>1 M) after 60 seconds, and the humidity signal at signal output U1 (I1) will reach 10 V (20 mA). Should the humidity sensor become faulty a voltage of 10 V (20 mA) will be applied at signal output U1 (I1) after 60 seconds, and the temperature signal will remain active.
Accessories Name Filter cap (for replacement) Engineering notes A transformer for safety extra low-voltage (SELV) with separate windings for 100 % duty is required to power the sensor. When sizing and protecting the transformer, local safety regulations must be complied with. When sizing the transformer, the power consumption of the duct sensor must be taken into consideration. For correct wiring, refer to the Data Sheets of the devices with which the sensor is used. The permissible cable lengths must be considered. Cable routing and cable selection It must be considered for routing of cables that the longer the cables run side by side and the smaller the distance between them, the greater electrical interference. Shielded cables must be used in environments with EMC problems. Twisted pair cables are required for the secondary supply lines and the signal lines. Terminals G1(+) and I1 () of the humidity output must always be connected to power, even if only terminals G2 (+) and I2 () of the temperature output are used! Type reference AQF3101
Note to QFM2171
Mounting notes Location Mount the sensor in the center of the duct wall. If used together with steam humidifiers, the minimum distance after the humidifier must be 3 m to max 10 m. Fit the sensor in the extract air duct if the application involves dew point shifting. Fit only the flange to the duct wall. The sensor is then inserted through the flange and engaged. To ensure degree of protection IP 54, fit the sensor with the cable entry pointing downward. The sensing elements inside the measuring tip are sensitive to impact. Avoid any impact on mounting. The mounting instructions are printed on the inside of the package of the device.
Caution!
Mounting instructions
Commissioning notes Check wiring before switching on power. The temperature measuring range must be selected on the sensor, if required. Wiring and the output signals can be checked by making use of the test function (refer to "Mechanical design"). We recommend not to use voltmeters or ohmmeters directly at the sensing element. In the case of the simulated passive output signals, measurements with commercially available meters cannot be made (measuring current too small). Technical data Power supply Operating voltage Frequency Power consumption Cable lengths for measuring signal Functional data of humidity sensor Perm. cable lengths Range of use Measuring range Measuring accuracy at 23 C and AC 24 V 0...95 % r. h. 30...70 % r. h. Temperature dependency Time constant at 0...50 C and 10...80 % r.h. Perm. air velocity Output signal, linear (terminal U1) Output signal, linear (terminal I1) Burden Functional data of temperature sensor with QFM2160, QFM2171 Measuring range AC 24 V 20 % or DC 13.5...35 V 50 / 60 Hz at AC 24 V 1 VA See data sheet of the device handling the signal 095 % r. h. (non-condensing) 0100 % r. h. 5 % r. h. 3 %, r. h. typically 0 . 1 % r. h. / C < 20 s 20 m/s DC 0...10 V max. 1 mA 0...100 % r. h.,
420 mA 0...100 % r. h. See "Function" 0...50 C (R2 = factory setting), 35...+ 35 C (R1) or 40+70 C (R3) NTC 10 k
Sensing element
Measuring accuracy at AC 24 V in the range of 15...35 C 0.8 K 35...+50 C 1 K Time constant Output signal, linear (terminal U2) < 3.5 min. in with 2 m/s moved air DC 0...10 V 0...50 C / 35...+ 35 C / 40...+ 70 C max. 1 mA
5/8 Siemens Building Technologies Duct sensors QFM21... CE1N1864en 02.07.2008
Output signal, linear (terminal I2) Burden Functional data of temperature sensor with QFM2120, QFM2140 Measuring range Sensing element simulated, corresponding to QFM2120 QFM2140
420 mA 0...50 C / 35...+ 35 C / 40...+ 70 C See "Function" 35...+ 50 C LG-Ni 1000 T1 (PTC)
Measuring accuracy at AC 24 V in the range of 15...35 C 0.8 K 35...+50 C 1 K Time constant Perm. measuring current with QFM2120 QFM2140 Protective data Degree of protection of housing Safety class Electrical connections Environmental conditions Connection terminals for Cable entry gland (enclosed) Operation Climatic conditions Temperature (housing with electronics) Humidity Mechanical conditions Transport Climatic conditions Temperature Humidity Mechanical conditions Materials and colors Base Cover Immersion rod Filter cap Mounting flange Cable entry gland Sensor (complete assembly) Packaging Standards Product safety Automatic electrical controls for household and similar use Electromagnetic compatibility Immunity Emissions conformity to conformity to Australian EMC Framework Radio Interference Emission Standard conformity 1) Weight Incl. packaging QFM21
1) Does not apply to the QFM2160 duct sensor!
< 3.5 min. in with 2 m/s moved air 1.184.21 mA 0.531.89 mA IP 54 as per IEC 60 529 in built-in state III as per EN 60 730 1 2.5 mm2 or 2 1.5 mm2 M 16 x 1.5 IEC 60721-3-3 Class 3K5 15...+ 60 C 0...95 % r. h. (non-condensing) Class 3M2 IEC 60721-3-2 Class 2K3 25...+ 70 C < 95 % r. h. Class 2M2 Polycarbonate, RAL 7001 (silver-grey) Polycarbonate, RAL 7035 (light-grey) Polycarbonate, RAL 7001 (silver-grey) Polycarbonate, RAL 7001 (silver-grey) PA66 GF35 (black) PA, RAL 7035 (light-grey) Silicone-free Corrugated cardboard
EN 60 730-1 EN 61 000-6-1 EN 61 000-6-3 EMC directive 2004/108/EC Radio Communication Act 1992 AS / NZS 3548 UL 873 Approx. 0.18 kg
QFM2120, QFM2140
1864G02
QFM2100
(r.h.)
1864G03
R3 = 40...+70 C)
G G0
G G0
G0
U1
U2
U1
BS
MS
U1
QFM2101
1864G04
QFM2171
1864G05
G1
(r.h.)
I1
G1
G2
G, G0 G1, G2 U1 U2 I1 I2 BS, MS
Operating voltage AC 24 V (SELV) or DC 13.5...35 V Operating voltage DC 13.5...35 V Signal output DC 0...10 V for 0...100 % r. h. Signal output DC 0...10 V for temperature range 0...50 C (R2 = factory setting), 35...+ 35 C (R1) or 40...+ 70 C (R3) Signal output 420 mA for 0...100 % r. h. Signal output 420 mA for temperature range 0...50 C (R2 = factory setting), 35...+ 35 C (R1) or 40...+ 70 C (R3) Signal output LG-Ni 1000- or T1 for temperature range 35...+ 50 C (passive, simulated); wires must not be interchanged
Note on connection terminals of the QFM2171: Terminals G1(+) and I1 () for the humidity output must always be connected to power, even if only the temperature output G2 (+) and I2 () is used!
Dimensions
80 60 28
39
28
M16 x 1,5
222
15
(62,8)
(41)
21(16) 60
1864M01
14,5