Protection Relay Testing For Commissioning SWP: 1. Purpose and Scope
Protection Relay Testing For Commissioning SWP: 1. Purpose and Scope
Protection Relay Testing For Commissioning SWP: 1. Purpose and Scope
3. DOCUMENTATION
CS000501F115. Daily / Task Risk Management Plan (Form) ES000901R102. Health and Safety Risk Control Guide (Reference) MN000301R165. 8 Level Field Test Competency (Reference) MN000301R167. Greenlining and Bluelining of Ergon Energy Substation Drawings (Reference) MN000301W107. Commission New and Augmented High Voltage Plant (Work Instruction) P53. Operate the Network Enterprise Process SWMS007. Live Work (Low Voltage) SWMS007 (Safe Work Method Statement) SP0506. Substation Primary Plant and Secondary Systems Field Testing SWP (Standard Work Practice) Ergon Energy - Standard for Substation Protection AM-P-STD-002A Auto-Reclose Standards Relay Configuration Standards Relay Application Guides
2. STAFFING RESOURCES
Electrical Fitter and / or Mechanic Competent Assistant Required Training and Certificates Regulatory Training Course Code 2120 2130 Course Description Perform Cardio Pulmonary Resuscitation Low Voltage Switchboard Rescue
Page 1 of 15
Ergon Energy Corporation Limited ABN 50 087 646 062 Ergon Energy Queensland Pty Ltd ABN 11 121 177 802
Page 2 of 15
Ergon Energy Corporation Limited ABN 50 087 646 062 Ergon Energy Queensland Pty Ltd ABN 11 121 177 802
PIR: Permissive Intertrip Receive PIS: Permissive Intertrip Send PSL: Protection Setting Logic PSR: Protection Setting Request RAG: Relay Application Guide REF: Restricted Earth Fault RCS: Relay Configuration Standard SEF: Sensitive Earth Fault SEL: Schweitzer Engineering Laboratories tnom: Relay Nominal Operating Time
6. TEST PLANS
Test Plans will be developed in accordance with this SWP and: Ergon Energy Relay Configuration Standards Ergon Energy Relay Application Guides Ergon Energy Test Plan Templates Manufacturer Equipment Manuals 6.1 Test Plan Naming Convention Standard Test Plans will have the following format: <RELAY CONFIGURATION STD>_<RELAY MODEL>_<(VER)> e.g. 0031B_P142_(0A) refers to revision 0A of a test plan for a MiCOM P142 relay utilising Ergon Energy Relay Configuration Standard AM-P-STD-0031B.
6.3 Test Plans Modifications and Version Control Version control of test plans will be facilitated by a document controlled by a Senior Commissioning Engineer. The version control document will contain the following details: Description of the test plan modification Reason for test plan modification Date of modification Author Approver The version control document will be maintained by the test plan approver. The version control document for test plans will be in the following format:
Check this is the latest Process Zone version before use. Page 4 of 15
Ergon Energy Corporation Limited ABN 50 087 646 062 Ergon Energy Queensland Pty Ltd ABN 11 121 177 802
Design drawings to relay: o o o Nominal current rating Aux supply voltage Aux input voltage
Select the appropriate test plan template as detailed in the Standard field on the PSR. 7.4 PSR Sanity Checks Carry out sanity checks of the protection scheme and settings to look for any possible abnormalities. This could include: Ensure setting reports, PSRs, Relay Application Guides and Relay Configuration Standards are followed and align, Ensure the scheme used matches the application,
Check for irregular CT ratios (e.g. Feeders should be greater than the maximum expected load and transformers should be greater than 1.5 times the name plate MVA rating. All CTs in high impedance diff schemes are set to the same ratio. This information can be found in the Protection Setting Report.). 7.5 Populate the Test Plan Apply relay specific settings to the appropriate standard test plan template as per the PSR. 7.6 Secondary Isolation Carry out secondary isolation in accordance with Secondary Systems Isolation guidelines. 7.7 Apply PSR Apply the approved settings to the relay under test.
Ergon Energy Corporation Limited ABN 50 087 646 062 Ergon Energy Queensland Pty Ltd ABN 11 121 177 802
Check displayed values against expected values. 7.11 System Testing System testing is to be completed based on primary values of the system in order to test the overall protection scheme and testing setup. Testing is to be performed as per specific direction in Section 8 of this document following parameters given in the Protection Setting Report. 7.12 Element Testing Element testing is to be completed using secondary values of the system to test the specific, changeable protection elements of the relay. All enabled element testing is to be performed as per specific direction in Section 9 of this document following parameters given in the Protection Setting Report. Element accuracies are to be as per Section 11 of this document. 7.13 Logic Testing Logic testing shall be performed on I/O according to the RAG logic diagram, Section 10 of this document and the elements that are enabled as per PSR.
Check this is the latest Process Zone version before use. Page 7 of 15
Initial of tester 7.17 Settings Returned to Protection Group Extract all as tested setting files from the relay Sign off on PSR
Forward signed off PSR and extracted setting files to Protection Group in a timely manner. 7.18 On Load Checks Carry out on load checks to verify primary analogue values and phase angles to relay displayed values. Verify sequence components as required. Verify diff and bias currents as required. Line diff specific: Energise feeder from each end in turn and record diff current from line capacitance.
Standard Work Practice SP0518 Ver 2
Ergon Energy Corporation Limited ABN 50 087 646 062 Ergon Energy Queensland Pty Ltd ABN 11 121 177 802
In addition to the above tests, the fault locator will be tested for correct operation by applying a single phase to ground fault at 50% of the feeder length. 8.3 Directional Over Current and Earth Fault Carry out the following tests: 3 phase fault at 50% of line at the line angle Earth fault on each phase at 50% of the line at the line angle 8.4 High Impedance Differential Protection Confirm the setting voltage is less than half the lowest knee point voltage of all CTs in the scheme Check that any resistor (shunt or stabilising) utilised in the circuit is utilising at least 2/3 of the total available resistance. 8.5 Transformer Biased Differential Protection 8.5.1 Through fault stability for phase faults Determine load side transformer current at the break point between Slope 1 and 2. From this load side current determine the source side current if the transformer was on top tap and determine the source side current if the transformer was on bottom tap.
Note:- All values are complex numbers, Nominal System Volts (11000 V, 22000 V, 33000 V etc.) Three Phase Source Impedance = (Nominal System Voltage at faulted Point) / ( 3 Three Phase Fault Current) Three Phase Fault Current at measuring point = (Nominal System Voltage at measuring point) / ( 3 (Three Phase Source Impedance to measuring point + Three Phase Impedance from measuring point to the Fault)) 8.2 Distance Relay System Testing Carry out the following tests: 3 phase fault for each zone at the line angle Earth fault for each zone at the fault loop impedance angle
Page 8 of 15
Ergon Energy Corporation Limited ABN 50 087 646 062 Ergon Energy Queensland Pty Ltd ABN 11 121 177 802
Operate time only need be recorded for 1 earth fault and 1 phase fault at each of the current multiples. 9.2 Directional Overcurrent / Earth Fault Check maximum torque angle at 2x pickup Check pickup for all phases Time at 2x, 5x, 10x pickup on all contacts that are tripped by this fault type If an instantaneous element is enabled and set at a value less than or equal to 10 times pickup, only the 2x and 5x tests are required
Operate time only need be recorded for 1 earth fault and 1 phase fault at each of the current multiples. 9.3 Definite Time Check pickup for all phases Check timing at 2x pickup on all contacts that are tripped by this fault type (check this value does not exceed the current limits and thermal rating of the relay set by the relay manufacture). Test set limitations or relay specifications may prevent timing tests at 2x pickup therefore a more suitable
Standard Work Practice SP0518 Ver 2
9.4.5 Load encroachment blinders Test that relay is blocked for load encroachment in accordance with relays designed operation. 9.5 Inter-tripping Schemes 9.5.1 Direct Check DIS initiates correctly as per logic Check DIR initiates correctly as per logic Time overall operation in each direction end to end
9.4.2 Line and Resistive Reach Relay operation for zone boundaries set in the grading plan should be tested. This shall include A-B, A-E, B-E and C-E faults at the line angle. If the relay has a quad set then the resistive and reactive reach shall be tested. If the quad has a setting to apply a tilt angle that angle shall be tested. The resistive reach on a mho characteristic shall not be tested since the reach can be overly sensitive to measurement errors when the mho crosses the x axis at a shallow angle. Test reverse element if set. Tripping times to be checked at 50% of Z1 reach for Z1 and 50% of (Z1+Z2) reach for Z2 and 50% of (Z2+Z3) for Z3 etc.
9.5.2 Permissive Under-Reaching Check PIS initiates correctly as per logic Check PIR initiates trip if Z2 is active and does not trip if Z2 is inactive Time overall operation in each direction end to end Time overall loop time with a loop applied at the remote end.
9.4.3 Voltage Supervision Simulate a single and three phase loss of VT supply and confirm VT supervision operation Test that relay distance elements are blocked for VT supervision operation in accordance with relays designed operation.
9.5.3 Permissive Over-Reaching Check PIS initiates correctly as per logic Check PIR initiates trip if Z2 is active and does not trip if Z2 is inactive For ECHO-Logic, check that the relay performs as per the relay manufacturers logic diagram
Standard Work Practice SP0518 Ver 2
Page 10 of 15
Ergon Energy Corporation Limited ABN 50 087 646 062 Ergon Energy Queensland Pty Ltd ABN 11 121 177 802
Time overall loop time with a loop applied at the remote end. 9.6 Feeder Current Differential Functions Current differential tests may require a temporary second relay at site to facilitate characteristic testing. 9.6.1 Current Differential Characteristic Test pickup for all phase to ground and AB phase faults Test the slope characteristic two points per slope Test the alpha plane characteristic (SEL relays): o o o Confirm 87LPP, 87L2P and 87GP Settings. Inject a through fault above the supervision element. Increase the current in the temporary relay to prove 87LR. Inject a through fault above supervision element setting and rotate remote currents to confirm accuracy of 87LANG. Confirm operation of 87LA, 87LB, 87LC, 87L2 and 87LG elements.
9.7.2 Differential / REF Characteristic Test the slope characteristic two points per slope Time each output contact at twice the pickup
Check second harmonic restraint by using three phase injection into HV input. 9.8 Transformer Thermal Protection 9.8.1 HV Thermal Overload Time at 1.5, 2 and 3 times pickup setting on all contacts that are tripped by thermal overload Record pickups for the 5 minute and 2 hour alarms for all phases.
9.8.2 LV Thermal Overload Time at 1.5, 2 and 3 times pickup setting on all contacts that are tripped by thermal overload Record pickups for the 5 minute and 2 hour alarms for all phases.
9.6.2 Current Differential Inter-Trip (for three ended schemes) Disconnect the communication links between the relays at the two remote sites while maintaining the communication paths between the local relay under test to the remote end relays. Inject a differential current in the relay under test and verify that the two remote relays have tripped.
Page 11 of 15
Ergon Energy Corporation Limited ABN 50 087 646 062 Ergon Energy Queensland Pty Ltd ABN 11 121 177 802
Test trip time at twice pickup. 9.11 Low Impedance Bus Protection Pickup Test pickup on every CT input Test trip time at twice pickup on every CT input.
9.9.4 Balance Protection Check alarm and trip level pickup Time alarm at below trip pickup for all contacts Time trip at twice pickup to all contacts.
9.9.5 Under Frequency Refer to under frequency tests as described in this SWP. 9.9.6 Close inhibit (capacitor discharge) Check timing for close inhibit. 9.10 High Impedance Differential Check pickup Check trip time at twice set point. High Impedance Bus Protection
9.12 Under Frequency Protection Check for pickup. Check timing of operation - inject at 10mHz above set threshold and step down to below pickup. Measure operating time.
Check under voltage block. 9.13 Circuit Breaker Fail / Local Backup Functions Test pickup of current check element Test drop off (CBF timer to reset if the check values drop off during the timing period) Test operation time at 2 times pickup Test all internal and external initiations in accordance with the RAG logic diagram (all faults types should initiate CB Fail).
Standard Work Practice SP0518 Ver 2
9.10.1
Pickup Test voltage pickup and record the current value at tested voltage.
Page 12 of 15
Ergon Energy Corporation Limited ABN 50 087 646 062 Ergon Energy Queensland Pty Ltd ABN 11 121 177 802
Ensure that the relay is named correctly on the LCD display. 9.16 Event and Disturbance Recorder Functions Ensure both the event and disturbance recorder are working correctly and that you can download events Clear event records where possible after relay testing is completed. 9.17 Network Backup / NPS Protection Check pickup. Time at 2x, 5x, 10x pickup on all contacts that are tripped by this fault type. Test minimum response time if set.
Accuracy (whichever is the greater) 5% or 0.1ohms of PPS ohm 5% or 0.1ohms of PPS ohm 5% or 0.1ohms of PPS ohm 5% or 0.1ohms of PPS ohm 10% or 0.2 ohms of PPS 5% or 0.1ohms of PPS ohm 5% or 0.1ohms of PPS ohm 5% or 0.1ohms of PPS ohm N/A 5% 5% N/A N/A N/A 5% 10% 10% 10% 5% 5% 10% 10% Iset + (5% or 0.01*Inom)
Time (whichever is the greater) < 40ms set time + ( 5% or 40ms) < 40ms set time + ( 5% or 40ms) < 40ms >35ms<65ms >35ms<65ms < 35ms < 35ms N/A < 40ms < 20ms (CHECK END TO END) <60ms < 90ms < 40ms < 40ms < 40ms set time + (10% or 40ms) <30ms <30ms < 40ms set time + (10% or 40ms) N/A
Standard Work Practice SP0518 Ver 2
11.1 Acronyms and Abbreviations PPS: Positive Phase Sequence DIS: Direct Intertrip Send PIS: Permissive Intertrip Send Inom: Relay Nominal Current Iset: Setting Current PIR: Permissive Intertrip Receive PIS: Permissive Intertrip Send PSL: Protection Setting Logic PSR: Protection Setting Request
Check this is the latest Process Zone version before use. Page 15 of 15
RAG: Relay Application Guide REF: Restricted Earth Fault RCS: Relay Configuration Standard SEF: Sensitive Earth Fault SEL: Schweitzer Engineering Laboratories Inom: Relay Nominal Operating Current Iset: Relay Current Setting SPAJ: ABB Protection Relay LLWC: Live Line Work Clearance