66 KV 400sqmm Cable Data
66 KV 400sqmm Cable Data
66 KV 400sqmm Cable Data
ELECTRIC CABLE 66000 V nkt cables 1X400+35 XLPE-CU 2004 0075 m >>>>
Application
Application Conductor temperature Short circiut temperature Installation temperature Min. radius of bend Max. pullings tension 66 kV A.C. Electricity distribution cable. Max. 90C Max. 250C Min. -15C 15 x D Directly on conductor 50 N/mm of total conductor cross section.
Construction
Conductor Conductor screen Insulation Insulation screen Screen Outer sheath Colour of sheath Nominel area of conductor and screen Circular stranded and compacted copper conductor Extruded semi-conducting compound XLPE Extruded semi-conducting compound Concentric layer of copper wires with a copper tape applied in the opposite direction. PE Black Diameter of conductor nominel Radial thickness of insulation Standard lenght
Technical
Standard Marking of sheath IEC 60840 ELECTRIC CABLE 66000 V nkt cables Dimension Year Metres (additional text on request) 66 kV AC between phases Available on request 25 mm, 50 mm on request
Approx weight
EAN-nr
mm 1X400+35
mm 23.4
mm 10.0
m On request
kg pr. km 5600
Mechanical properties
Area of conductor Diameter of conductor, nom. Insulation thickness, nom Diameter over isulation, nom. Area of copper screen, nom. Diameter over screen, nom. Thickness of sheath, nom. Diameter over sheath, nom. Diameter over sheath, max. weight of cable. appr. Radius of bend, min. Pulling tension on the cable. mm mm mm mm mm2 mm mm mm mm kg/m mm kN 400 23.4 10.0 45.4 35 51.7 3.0 58.0 62.0 5.6 870 12.3
18-02-2005
E/N
GB0010.701
Edition 0
Side 1 af 2
Medium voltage
66 kV single core cable XLPE-CU
Electrical properties
Area of conductor Resistance, DC, at 20C, max. Capacitance, max. Short circuit rating for 1 sec. Conductor with initial temperature 90C and final temperature 250C Short curcuit rating for 1 sec. Screen with final screen temperature 300C mm /km F/km 400 0.0470 0.23
Halogen free
kA kA
57.2 7.0
mm
400
G) Screens bonded at both ends trefoil formation, close together S = D flat formation, close together S = D flat formaton, free distance between cable S = D + 70 mm Screens bonded at a single point trefoil formation, close together S = D flat formation, close together S = D flat formaton, free distance between cable S = D + 70 mm A) Screens bonded at both ends trefoil formation, close together S = D flat formation, close together S = D flat formaton, free distance between cable S = D + 70 mm Screens bonded at a single point trefoil formation, close together S = D flat formation, close together S = D flat formaton, free distance between cable S = D + 70 mm Reactance at 50 Hz trefoil formation, close together S = D flat formation, close together S = D flat formaton, free distance between cable S = D + 70 mm
A A A A A A
18-02-2005
E/N
GB0010.701
Edition 0
Side 2 af 2